Bradford White RTG 199 HEN, RTG 199 HEX Installation And Operation Instructions Manual

Installation and Operation instructions
INDOOR MODEL
RTG 199 HE
Warning: If the information in this manual is not followed exactly, a fire
or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Installation and service must be performed by a trained and certified installer, service agency or the gas supplier.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assis­tance or additional information consult a qualified installer, service agency or the gas supplier.
In the Commonwealth of Massachusetts this product must be installed by a licensed plumber or gas fitter.
Upon completion of the installation, these instructions should be handed to the user of the appliance for future reference.
What to do if you smell gas
• Turn off the gas shut-off valve. Open windows and doors.
• Do not try to light any appliance.
• Do not touch any electrical switch, telephone, and do not use out­lets.
• Extinguish all open flames. Do not smoke! Do not use lighters!
• Warn all occupants of the building. Do not ring doorbells!
• If you can hear gas leaking, leave the building immediately. Prevent others from entering the building and notify the police and fire department from outside the building.
From outside the building, call the gas utility company and a trained
and certified installer.
RTG 199 HEN - Natural Gas RTG 199 HEX - Propane (LP Gas)
Temperature Modulated with Electronic Ignition Suitable for heating potable water and space heating
(Intended for variable flow applications)
6 720 811 617 / 238-50793-00B (2016/01)
Table of contents
RTG 199 HE – 6 720 811 617 (2016/01)
2
Table of contents
1 Key to symbols and safety instructions . . . . . . . . . . . . . . . . . . . 3
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 FCC rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Appliance details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Specifications (Technical data) . . . . . . . . . . . . . . . . . . . . 7
3.3 Unpacking the heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 General rules to follow for safe operation . . . . . . . . . . . . 8
3.5 Dimensions and minimum installation clearances . . . . . 9
4 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Specialized tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Combustion air requirements . . . . . . . . . . . . . . . . . . . . 23
4.5 Proper location for installing your heater . . . . . . . . . . 24
4.6 Heater placement and clearances . . . . . . . . . . . . . . . . 24
4.7 Hanging appliance on the wall . . . . . . . . . . . . . . . . . . . 24
4.8 Mounting installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.9 Gas piping & connections . . . . . . . . . . . . . . . . . . . . . . 26
4.10 Water connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.11 Water quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.12 Filling the condensate trap . . . . . . . . . . . . . . . . . . . . . . 30
4.13 Domestic hot water recirculation . . . . . . . . . . . . . . . . . 31
4.14 Space heating applications . . . . . . . . . . . . . . . . . . . . . . 31
4.15 Measuring gas pressure . . . . . . . . . . . . . . . . . . . . . . . . 33
5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1 Electrical power supply . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2 Position of the fuses in control unit . . . . . . . . . . . . . . . 34
6 Operation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.1 Description LCD Display . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2 For your safety read before operating
your water heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.3 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.4 Temperature selection . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.6 Reset button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.7 Program button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.8 Locked condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7 Maintenance and service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.1 Annual maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.2 Winterizing for seasonal use . . . . . . . . . . . . . . . . . . . . . 38
7.3 Mineral scale build-up . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.4 Condensing heat exchanger unit . . . . . . . . . . . . . . . . . 38
7.5 Adjusting CO2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.6 Program values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.7 Control board diagnostics . . . . . . . . . . . . . . . . . . . . . . 41
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.2 Burner does not ignite when hot water is turned ON . . 42
8.3 Water is too hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.4 Water is not hot enough . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.5 Low water flow/pressure . . . . . . . . . . . . . . . . . . . . . . . . 43
8.6 Hot water temperature fluctuates at tap . . . . . . . . . . . . 43
8.7 Noisy burner/heater during operation . . . . . . . . . . . . . . 44
9 Problem solving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.1 Error code diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10 Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11 Sensor resistance charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
12 Functional scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
13 Interior components diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 51
13.1 Interior components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
14 Protecting the environment . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
15 LIMITED TANKLESS HEATER WARRANTY . . . . . . . . . . . . . . . . 53
16 Installer Checklist to be completed by installer upon
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Key to symbols and safety instructions
RTG 199 HE – 6 720 811 617 (2016/01)
3
1 Key to symbols and safety instructions
1.1 Key to symbols
Warnings
The following keywords are defined and can be used in this document:
NOTICE indicates that damage to property may occur.
CAUTION indicates that personal injury may occur.
WARNING indicates that severe personal injury may occur.
DANGER indicates that severe personal injury or death may occur.
Important information
Additional symbols
1.2 Safety instructions
Read all instructions before installing. Perform the steps in the indicated sequence. Have the water heater inspected by a trained service technician at least once every year. Failure to comply with these instructions can result in severe, possibly fatal, personal injury as well as damage to property and equipment.
Installation and servicing
Risk of fire when soldering and brazing!
Take appropriate protective measures when soldering and brazing around combustible and flammable material.
▶ Ensure that only a licensed contractor installs or services the water
heater.
▶ On hot components use only material with adequate temperature
stability.
Installation and commissioning
▶ In the Commonwealth of Massachusetts, the water heater must be
installed by a licensed plumber.
▶ Do not install this device in rooms with a high moisture level
(e.g. bathrooms, saunas).
Function
▶ To ensure that the water heater functions properly, follow these
installation and maintenance instructions.
▶ Never close the blow-off line of the T&P safety valve. For safety
reasons, water may escape during heating.
If you smell gas
▶ Turn off the gas shut-off valve. ▶ Open windows and doors. ▶ Do not try to light the appliance. ▶ Do not touch any electrical switch, telephone, and do not use outlets. ▶ Extinguish all open flames. Do not smoke! Do not use lighters! ▶ Warn all occupants of the building. Do not ring doorbells! ▶ If you can hear gas leaking, leave the building immediately. ▶ Prevent others from entering the building and notify the police and
fire department from outside the building.
▶ From outside the building, call the gas utility company and a trained
and certified installer.
If you smell flue gas
▶ Switch off the appliance. ▶ Open windows and doors. ▶ Inform a trained and certified installer.
Insufficient ventilation may cause toxic flue gas to escape. Risk of poisoning.
▶ Never close off or reduce the size of the air intake and outlet
openings.
▶ The appliance must not be operated until any obstructions have been
removed.
▶ Inform the system operator in writing of the problem and the
associated dangers.
Danger from escaping flue gases
▶ Ensure all vent pipes and chimneys are not damaged or blocked. ▶ Connect only one appliance to each vent system or chimney liner. ▶ The venting system piping must not feed into another air extraction
duct.
▶ Do not route the flue system piping through or inside another air
extraction duct.
Danger of explosion of flammable gases
▶ Work on gas components may only be carried out by a trained and
certified installer.
▶ Installation, gas and flue connection, initial commissioning, electrical
connections and annual maintenance must only be carried out by a trained and certified installer.
Combustion air
▶ Keep the combustion air free of corrosive substances (halogenated
hydrocarbons that contain chlorine or fluorine compounds).
Never shut off safety valves!
▶ Water may escape from the safety valve at any time when the water
is being heated.
Inspection/maintenance
▶ Servicing and repairs may only be carried out by a trained and
certified installer. ▶ Immediately correct all faults to prevent system damage. ▶ Use only Bradford White spare parts! Damage caused by the use of
parts not supplied by Bradford White may void the warranty.
Instruct the customer
▶ Explain to the customer how the appliance works and how to operate
it. ▶ Inform the customer that he/she must not carry out any alterations or
repairs.
Danger from electric shock
▶ Ensure that only an authorized contractor performs electrical work. ▶ Before performing electrical work, disconnect the power and secure
the unit against unintentional reconnection. ▶ Ensure the system has been disconnected from the power supply.
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
This symbol indicates important information where there is no risk to people or property.
Symbol Explanation
Step in an action sequence Cross-reference to another part of the document
List entry – List entry (second level)
Table 1
Key to symbols and safety instructions
RTG 199 HE – 6 720 811 617 (2016/01)
4
Risk of scalding at the hot water draw-off point
▶ When the water heater is in operation, temperatures in excess of
122 °F (50 °C) can occur. To limit the temperature at the tap, install a thermostatic DHW mixing valve.
▶ Water heated for washing the laundry, dishes and for other cleaning
purposes can cause scalding and permanent injuries.
▶ Children, elderly, and handicapped persons are more likely to be
permanently injured by hot water. Never leave such individuals in the tub or shower unattended under any circumstances. Children must not be allowed to operate hot water faucets themselves or to fill a bathtub.
▶ If the building has occupants in the above groups who operate hot
water faucets, or state laws / local ordinances stipulate specific water temperatures, take the following precautions: – Use the lowest possible temperature setting. – To prevent scalding, install a tempering device, such as an
automatic mixing valve, at hot water tap or water heater. Select and install the automatic mixing valve in accordance with the valve manufacturer's recommendations and instructions.
▶ Water exiting from drain valves can be extremely hot. To avoid
injuries: – Check that all connections are tight. – Direct exiting water away from people.
▶ Measures must be taken to protect against excessive temperature
and pressure! Installation of a T&P safety valve is required.
To protect against corrosion and ensure compliance with the rules for electrical safety, observe the following points: ▶ Use metal fittings for potable water heating systems with plastic
piping. ▶ Use only original accessories from the manufacturer. ▶ When installation of the water heater is complete, inspect the ground
conductor (including metal fittings).
Maintenance Customers are advised to:
▶ Sign a maintenance and inspection contract with an authorized
contractor. Inspect and maintain the water heater as necessary on a
yearly basis. Service as needed. ▶ Use only genuine spare parts.
Flooding
▶ After a flood, do not use the appliance if any part has been
submerged. Damage to appliances that have been submerged can be
quite severe and pose numerous safety risks. ▶ Every appliance that has been submerged must be replaced.
Key to symbols and safety instructions
RTG 199 HE – 6 720 811 617 (2016/01)
5
For your safety
▶ Do not store or use gasoline or other flammable, combustible or
corrosive vapors and liquids in the vicinity of this or any other appliance.
DANGER: Fatal accidents! Carbon monoxide poisoning.
▶ Carefully plan where you install the heater. Correct
combustion air supply and flue pipe installation are very important. If a gas appliance is not installed correctly, fatal accidents can result such as carbon monoxide poisoning or fire.
DANGER:
Carbon monoxide poisoning.
▶ Exhaust gas must be vented to outside using
approved vent material. See table 5, page 11 (In Canada use only ULCS636 approved material). Vent and combustion air connector piping must be sealed gas-tight to prevent flue gas spillage, carbon monoxide emissions and risk of fire, resulting in severe personal injury or death. Approved vent terminations must be used when penetrating to the outside.
DANGER: Electric shock! ▶ Field wiring connections and electrical grounding
must comply with local codes, or in the absence of local codes, with the latest edition of the National Electric Code, ANSI/NFPA 70, or in Canada, all electrical wiring must comply with the local codes and the Canadian Electrical Code, CSA C22.1 Part 1.
DANGER: Electric shock! Shock hazard: line voltage is present.
▶ Before servicing the water heater, unplug power
supply cord from outlet. Failure to do so could result in severe personal injury or death.
WARNING: Damage to the appliance from over pressure. ▶ The heater must be disconnected from the gas
supply piping system during any pressure testing of that system at test pressures equal to or more than
0.5 psi.
NOTICE:
▶ The appliance should be located in an area where
leakage of the heater or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow.
WARNING:
▶ The maximum inlet gas pressure must not exceed the
value specified by the manufacturer and the minimum value listed is for the purpose of input adjustment.
NOTICE:
▶ If a water heater is installed in a closed water supply
system, such as one having a backflow preventer in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation.
WARNING: Fire danger! ▶ Keep appliance area clear and free from combustible
materials, gasoline and other flammable vapors and liquids.
NOTICE:
▶ Do not obstruct the flow of combustion and
ventilation air.
NOTICE: Appliance malfunction! ▶ If power is lost while appliance is operating. Turn off
both water and power for 15 seconds to reset device.
WARNING: Risk of scalding and property damage. ▶ Precautions must be taken prior to manually
operating the relief valve to avoid contact with hot water discharged from the relief valve and to prevent water damage.
NOTICE: Appliance damage! ▶ Label all wires prior to disconnection when servicing
controls. Wiring errors can result in improper and dangerous operation. Verify proper operation after servicing.
WARNING: System damage! ▶ If a relief valve discharges periodically, this may be
due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the relief valve.
WARNING: Property damage! ▶ If the water heater is used in a space heating
application, all piping and components connected to the water heater must be suitable for use with potable water.
WARNING: Personal Injury from toxic chemicals. ▶ Toxic chemicals, such as those used for boiler
treatment, shall not be introduced into the potable water used for space heating.
FCC rules
RTG 199 HE – 6 720 811 617 (2016/01)
6
2 FCC rules
FCC: This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Fig. 1
The chart below shows the relationship between water temperature and time until there is a risk of scalding. It can be used as the basis for determining the safest water temperature for your application.
3Appliance details
3.1 Features
Parts
• Key Pad interface control.
• High power pre-mix compact burner with low NOx emissions.
• Modulating Gas Valve with constant gas:air ratio control.
• Modulating water valve for improved comfort and temperature control.
High quality materials for long working life
• Copper heat exchanger.
• High efficiency Ceramat Burner.
• Compact space saver: mounts on a wall with a supplied bracket.
Features
• Easily removable one-piece cover.
• On/Off and Temperature control switches.
• Reset button.
• Program button (Selectable temperature default).
• Failure codes for easy diagnostics and repair.
• Real-time diagnostics for troubleshooting/informational purposes.
• Built in freeze prevention.
Note: The freeze prevention kit is designed to provide protection for the water heater down to approximately 5°F for short term conditions only. It will not protect the appliance in areas where the temperature is routinely expected to be below freezing.
- The freeze prevention kit will not protect plumbing outside the
appliance from freezing. Precautions should be taken.
WARNING: Personal Injury from toxic chemicals. ▶ A water heater which will be used to supply potable
water shall not be connected to any heating system or component(s) previously used with a nonpotable water heating appliance.
Temperature Time to severe scalding
1)
1) Source: Moritz, A.R. and Henriques, F.C., Jr. (1947). Studies of thermal injury. II. The relative importance of time and surface temperature in the causation of cutaneous burns, Am J of Pathol, 23, 695-720.
120 °F (48 °C) longer than 5 minutes 125 °F (51 °C) 1.5 to 2 minutes 130 °F (54 °C) approx. 30 seconds 135 °F (57 °C) approx. 10 seconds 140 °F (60 °C) less than 5 seconds 145 °F (62 °C) less than 3 seconds 150 °F (65 °C) approx. 1.5 seconds 155 °F (68 °C) approx. 1 second
Table 2 Approximate time-temperature relationship until there is a risk
of scalding
Bradford White is constantly improving its products, therefore specifications are subject to change without prior notice.
Appliance details
RTG 199 HE – 6 720 811 617 (2016/01)
7
3.2 Specifications (Technical data)
Approved in US/Canada
Safety devices
• Flame failure device (ionization flame rod sensor)
• Overheat prevention (temperature limiter)
• Inlet temperature sensor
• Outlet temperature sensor
• Back flow temperature sensor
• Exhaust gas temperature sensor
3.3 Unpacking the heater
Before installing the unit, be certain you have the correct heate r for your type of Gas - Propane or Natural Gas. Identification labels are
found on the shipping box, and on the rating plate which is located on the right side panel of the cover.
Fig. 2 Rating plate
[A] Serial number [B] Type of gas
Technical characteristics Units RTG 199 H Capacity
Maximum flow rate at a 45 °F (25 °C) rise
GPM (l/min) 8.3 (31.4)
Maximum flow rate at a 55 °F (30.6 °C) rise
GPM (l/min) 6.8 (25.7)
Maximum flow rate at a 75 °F (41.7 °C) rise
GPM (l/min) 5.0 (18.8)
Maximum flow rate at a 90 °F (50 °C) rise
GPM (l/min) 4.2 (15.7)
Maximum output BTU/hr (kW) 184,500 (54)
Maximum input BTU/hr (kW) 199,000 (58.3)
Thermal efficiency (Efficiency in %)
% > 94%
Minimum Input BTU/hr (kW) 19,900 (5.8)
Temperature Control
Selection range °F ( °C) 100 - 140 (38 - 60)
Default temperature °F ( °C) 122 (50)
Stability °F ( °C)  2 ( 1)
Gas Requirement
Gas connection inches ¾ "
Peak load inlet gas pressure
1)
Propane water column 8” - 13”
Natural Gas water column 3.5” - 10.5”
Water
Hot water connection inches ¾ "
Cold water connection inches ¾ "
Minimum water flow
2)
GPM (l/min) 0.5 (1.9)
Minimum recommended water pressure
PSI (bar) 30 (2.07)
Minimum well pressure PSI 40
Water valve material Polymer (PPS)
(Polypropylene
Sulfide)
Connections: Bottom of heater
Combustion
CO level ppm 290 (measured) CO2 level (set from factory) % see table 43
Dimensions
Depth inches (mm) 11 ¼ (286)
Width inches (mm) 17 7/8 (452)
Height inches (mm) 30½ (775)
Weight pounds (kg) 74 (33.5)
Gas types
Natural Gas
Table 3
LP Gas
Voltage
Nominal V AC 120
Frequency Hz 60
Amperage
Idle mA 40
Operation A 2.5
Noise db (A) 45 - 65
Water protection
3)
IP X4D
1) To measure Gas Pressure, see Measuring Gas Pressure, chapter 4.15, pa ge 33.
2) Activation varies with inlet water temperatures from 0.5 - 1.6 gallon/minute (1.9
- 6.1 l/m).
3) Protection against water drops.
If appliance is installed at elevations above 2000ft, refer to chapter 4.3.8 Fan speed adjustment.
Technical characteristics Units RTG 199 H
Table 3
Appliance details
RTG 199 HE – 6 720 811 617 (2016/01)
8
3.3.1 The box includes
• Tankless water heater
• Bracket for wall hanging the heater
• Exhaust vent adaptor (with 4 screws and gasket provided)
• Combustion air inlet adaptor (with 3 screws and gasket provided)
• Installation manual
• Energy Guide label
The RTG 199 H is not approved or designed for:
Manufactured (mobile) homes, boats or any mobile installation. (Modular homes are acceptable for installation).
Use above 8000 ft A.S.L. altitude (see page 21).
Outdoor installation without installation of Outdoor kit.
Applications where inlet water temperature is hi gher than 140°F
(60°C). A 3-way valve or mixing valve must be installed before the appliance if inlet water temperature exceeds this limit.
3.3.2 Remove front cover
▶ Loosen the two Phillips head screws located on bottom rear of cover.
Fig. 3 Loosen the two screws
▶ Lift front cover panel upward and remove.
Fig. 4 Remove the front cover
3.3.3 Remove combustion cover (service only)
▶ Open the four clips and remove the combustion cover.
Fig. 5 Remove the combustion cover
3.4 General rules to follow for safe operation
1. You must follow these instructions when you install your heater. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada: The Installation must conform with CSA B149.(1,2) INSTALLATION CODES and /or local installation codes.
6720608917-03.1AL
Appliance details
RTG 199 HE – 6 720 811 617 (2016/01)
9
2. Carefully plan where you install the heater. Correct combustion air supply and vent pipe installation are very important. If not installed correctly, fatal accidents can occur, such as carbon monoxide poisoning or fire.
3. When the unit is installed indoors and ROOM SEALED (twin pipe) it is permitted to be located in bathrooms, bedrooms and occupied rooms that are normally kept closed. See chapter 4.3 (page 10). If the unit will be installed indoors and use indoor combustion air, the place where you install the heater must have enough ventilation. The
National Fuel Gas Codes do not allow UNSEALED gas fired water heater installations in bathrooms, bedrooms or any occupied rooms normally kept closed. See chapter 4.4 (page 23).
4. You must correctly vent your heater. See chapter 4.3 (page 10) on VENTING.
5. The appliance and its gas connection must be leak tested before placing the appliance in operation. The appliance must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve (not supplied with heater) during any pressure testing at pressures in excess of ½ Psig (3.5 kPa).
6. Keep water heater area clear and free from combustibles and flammable liquids. Do not locate the heater over any material which might burn.
7. Correct gas pressure is critical for the proper operation of this heater. Gas piping must be sized to provide the required pressure at the maximum output of the heater, while all the other gas appliances are in operation. Check with your local gas supplier, and see the section on connecting the gas supply. See chapter 4.9 (page 26).
8. Should overheating occur or the gas supply fail to shut off, turn off the gas supply at the manual gas shut off valve, on the gas line. Note: manual gas shutoff valve is not supplied with the heater but must be field installed.
9. Do not use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
10. Failure to install heater correctly may lead to unsafe operation and void the warranty.
3.5 Dimensions and minimum installation clearances
Fig. 6 Dimensions
[1] On/Off button [2] Reset button [3] Program key
[4] Power ON or stand-by LED [5] LCD display [6] Up button [7] Down button
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
10
Fig. 7 Side view
4 Installation instructions
4.1 Specialized tools
The following specialized tools may be required for installation:
• Manometer
• Multi-meter
• Combustion Gas Analyzer
4.2 Introduction
Please follow these instructions. Failure to follow instructions may result in:
▶ Damage or injury. ▶ Improper operation. ▶Loss of warranty.
4.3 Venting
For servicing access, a 2ft clearance is recommended to the front cover.
RTG 199 H
TOP (A) 12”
FRONT (B) 1”
BACK 0”
SIDES 1”
FLOOR (C) 12”
Table 4 Recommended minimum clearances
DANGER:
▶ The water heater must be installed by a qualified
installer in accordance with these instructions. If improperly installed, a hazardous condition such as explosion or carbon monoxide poisoning could result. Manufacturer is not responsible for improperly installed appliances.
Common installation practice is to first determine the venting/combustion air point of termination, then design the piping layout back to the heater.
NOTICE:
▶ Do not reduce the exhaust or combustion air vent
pipe sizes.
▶ Do not common vent with any other vented appliance
or stove.
▶ Do not use Type-B vent as the actual exhaust vent
system for the appliance.
DANGER: Flue gas poisoning! ▶ Failure to vent the exhaust gases to the outside (see
table 5 for proper material) may result in dangerous flue gases filling the structure in which it is installed.
NOTICE:
▶ In areas where outside temperatures routinely come
close to freezing, sealed combustion operation is required. Concentric termination or separate terminations for combustion and vent, must be installed on the same wall or roof surface; however, never facing the direction of prevaili ng winds. Failure to do so may result in heat exchanger freezing and bursting. This failure is not covered under the manufacturer's warranty.
WARNING: Appliance malfunction! ▶ Protect the exhaust and inlet from leaves and debris
by installing a screen on the end of the termination. ¼ " mesh minimum opening recommended on screen.
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
11
4.3.1 Vent options
The water heater is approved with the following venting options:
All combustion air and vent pipe materials and fittings must comply with the following:
For specific questions concerning vent material, specifications, usage or installation, please contact the vent manufacturer directly.
Fig. 8 PP Concentric up and out system
The concentric up and out vent system simplifies installations where the water heater is mounted on an outside wall that can be direct vented through that wall. This vent system only consists of the concentric appliance adapter, one 90° elbow, and the termination, and can not be extended further.
Concentric up and out kit
The concentric up and out system must be installed according to the respective Installation Manual.
All vent connections must be glued, except for the PP vent systems, and the exhaust adapter (chapter 4.3.4) which is screwed into place on the top of the appliance. Slide the vent pipe into the exhaust adapter. The exhaust pipe must be properly supported and must be pitched a minimum of a ¼ inch per foot back to the appliance. This allows the condensate to drain properly.
An optional concentric vent/air intake termination can be used for the installation of a vertical or horizontal venting system when using PVC, CPVC, or ABS (see fig. 9). The concentric vent/air intake body can be ordered from your local wholesaler. The appliance can also be installed with separate air intake and exhaust
piping (see fig. 12, fig. 19 and fig. 20, page 18) in PP, PVC, CPVC, and ABS. Generic PP twin pipe can be used if certified to ULC-S636 and only with 90° elbow or T terminals. Maximum vent lengths and equivalent lengths per tables 8 and 9 apply.
Fig. 9 Concentric vent kit example
[1] Exhaust [2] Combustion air [3] Roof boot/flashing (field supplied) [4] Exhaust pipe [5] Drain tee [6] Intake pipe [7] Concentric vent kit (239-44069-01) [LA] Maintain 12 in. (18 in. for Canada) minimum clearance above
highest anticipated snow level maximum of 24 in. above roof
Item Material United States Canada Vent
or air pipe and fitting
PP concentric single ULC-S636
certified only
PP common vent
PP twin pipe
PVC schedule 40 ANSI/ASTM D1785
PVC-DWV ANSI/ASTM D2665
CPVC schedule 40 ANSI/ASTM F441
ABS-DWV schedule ANSI/ASTM D2661
Pipe cement / primer
PVC ANSI/ASTM D2564
CPVC ANSI/ASTM F493
ABS ANSI/ASTM D2235
Table 5 Approved vent material
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in non­metallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.
Description Length
Kit part no. and
quantity
239-44069-01
3- In. Rain Cap N/A 1 4- In. Diameter SDR-26 Pipe 24 In. long 1 3- In. Y
Concentric Fitting
N/A 1
2- ½ In. Diameter SDR-26 Pipe 37-1/8 in.
long
1
3- In. Condensate drain Tee N/A 1
1.5- In. Condensate drain bushing N/A 1
Table 6 PVC concentric vent part breakdown
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
12
4.3.2 Vent specifications
Establish vent clearances that comply with the vent manufacturer's specifications and all applicable national/local codes.
Venting specifications
[*] ULC S636-95, UL1738 certified
Condensate drain requirements
When the Water Heater is installed in a residential single family dwelling without direct recirculation an external condensate drain is not required.
If the Water Heater is installed in an application other than a residential single family dwelling an external condensate drain (not supplied with the Water Heater) is required in the following circumstances:
• Vertical terminating exhaust vent installations.
• Horizontal terminating exhaust vent installations greater than 6 feet (1.8 m) linear measurement, (NOT total equivalent length).
• Vent installations where any section of the exhaust vent pipe passes through an unconditioned space.
Note: An external condensate drain is recommended in all installations as best practice in order to maximize the longevity of the Water Heater.
Minimum combustion air and exhaust pipe length
The minimum exhaust pipe length is 1 foot (0.3m) of straight vent pipe. The minimum combustion air pipe length is one 90 ° elbow, except with the Common Vent System where the provided air intake grill cap is used.
Maximum combustion air and exhaust pipe length
The following tables display the maximum allowable straight pipe lengths for combustion air and exhaust piping with consideration to the number of elbows used. Reduce the equivalent length for each elbow used from the maximum allowable length depending on the system used. Refer to table 8 if using 3" diameter venting. Refer to table 9 if using 4" diameter venting. Refer to table 10 if using 2" diameter venting.
Use of elbows
It is recommended to limit the amount of elbows used in the exhaust and combustion air piping to reduce friction in the air flow. The following lists the maximum amount of 90 ° elbows allowed in either the exhaust or combustion air piping:
Calculation example for 3" PVC, CPVC, or ABS venting: Exhaust
Diam. Approved terminals
E x h a u s t
3 or 4 inches “T” terminal
2, 3 or 4 inches 90° elbow
3 inches PVC Flue Cap*(ECAP321)Vertical terminations
3" diameter only
3 or 4 inches Concentric
I n t a k e
3 or 4 inches “T” terminal
2, 3 or 4 inches 90° elbow
3 inches PVC Flue Cap*(ECAP321)Vertical & horizontal
terminations approved 3" diameter only
3 or 4 inches Concentric
Table 7 Venting specifications for intake and exhaust
3" Venting
Maximum
allowable total vent
Length
Maximum allowable
Exhaust
Length
Maximum allowable
Intake
Length
Elbow
Equivalency
90° 45 °
Twin pipe 62 ft 31ft 31ft 5 ft 2.5 ft Concentric 46 ft 23ft 23ft 5 ft 2.5 ft
Table 8 Maximum Allowable Exhaust and Combustion Air Lengths for 3"
PP, PVC, CPVC, and ABS venting
4" Venting
Maximum allowable total vent
Length
Maximum allowable
Exhaust
Length
Maximum allowable
Intake
Length
Elbow
Equivalency
90° 45°
Twin pipe 126ft 63ft 63ft 5ft 2.5ft
Concentric 86ft 43ft 43ft 5ft 2.5ft
Table 9 Maximum Allowable Exhau st and Combustion Air Lengths for 4"
PP, PVC, CPVC, and ABS venting
2" Venting
Maximum allowable total vent
Length
Maximum allowable
Exhaust
Length
Maximum allowable
Intake
Length
Elbow
Equivalency
90°
1)
1) If using 90 ° short sweep elbow equivalent length is 5 ft. If using 90° long sweep elbow equivalent length is 2.5 ft.
45°
Twin pipe with two terminations
19ft 9.5ft 9.5ft
5 ft /
2.5 ft
2.5 ft
Table 10 Maximum Allowable Exhaust and Combustion Air Lengths for
2" PVC venting
Max. number of 90° elbows 3" venting 4" venting 2" venting
Twin pipe system 5 7 1 or 2
1)
1) If using 90 ° short sweep elbow the max. number is 1. If using 90° long sweep elbow the max. number is 2.
Concentric system 4 7 _
Table 11
Two 45° elbows are equal to one 90 ° elbow. Any combination of 45° and 90 ° elbows may be used in the vent system as long as the combination does not exceed the maximum listed in table 11 above.
System used Concentric
Number of 90° elbows needed: 1
Number of 45° elbows needed: 2
Table 12
Calculation of example
Max. length 23’
90° elbow reduction - 5’
sub-total = 18’
45° elbow reduction - 5’
Total = 13’
Table 13
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
13
Combustion air
Calculation example for 4" PP, PVC, CPVC, or ABS venting: Exhaust
Combustion air
Calculation example for 2" PVC venting: Exhaust
Combustion air
For this example, the maximum allowable exhaust pipe length is 13 feet.
System used Concentric
Number of 90° elbows needed: 2
Number of 45° elbows needed: 1
Table 14
Calculation of example
Max. length 23’
90° elbow reduction - 10’
sub-total = 13’
45° elbow reduction - 2.5’
Total = 11.5’
Table 15
For this example, the maximum allowable combustion air pipe length is 11.5 feet.
System used Twin pipe
Number of 90° elbows needed: 1 Number of 45° elbows needed: 2
Table 16
Calculation of example
Max. length 63’ 90° elbow reduction - 5’ sub-total = 58’ 45° elbow reduction - 5’ Total = 53’
Table 17
For this example, the maximum allowable exhaust pipe length is 53 feet.
System used Twin pipe
Number of 90° elbows needed: 2 Number of 45° elbows needed: 2
Table 18
Calculation of example
Max. length 63’ 90° elbow reduction - 10’ sub-total = 53’ 45° elbow reduction - 5’ Total = 48’
Table 19
For this example, the maximum allowable combustion air pipe length is 48 feet.
System used Twin pipe
Number of 90° elbows needed: 1 Number of 45° elbows needed: 0
Table 20
Calculation of example
Max. length 9.5’ 90° elbow reduction - 5’ sub-total = 4.5’ 45° elbow reduction - 0’ Total = 4.5’
Table 21
For this example, the maximum allowable exhaust pipe length is 4.5 feet.
System used Twin pipe
Number of 90° elbows needed: 0 Number of 45° elbows needed: 2
Table 22
Calculation of example
Max. length 9.5’ 90° elbow reduction - 0’ sub-total = 9.5’ 45° elbow reduction - 5’ Total = 4.5’
Table 23
For this example, the maximum allowable combustion air pipe length is 4.5 feet.
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
14
Required direct vent terminal clearances (twin pipe / concentric penetration) for PVC, CPVC, ABS, and PP.
Fig. 10
[*] For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated:
a) A minimum clearance value determined by testing in accordance with section 2.20, or; b) A reference to the following footnote: “Clearance in accordance with local installation codes and the requirements of the gas supplier.”
Canadian installations
1)
1) In accordance with the current CSA B149.1 Natural Gas a nd Propane Installation Code.
U.S. installations
2)
2) In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
A Clearance above grade, veranda, porch, deck or balcony 12 in. 12 in.
B Clearance to window or door that may be opened 36 in. 12 in.
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffit located above the vent
termination within a horizontal distance of 2 feet (61cm) from
the center line of the termination
**
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H Clearance to each side of center line extended above meter/
regulator assembly
36 in. within a height 15 feet above
meter/ regulator assembly
*
I Clearance to service regulator vent outlet 36 in. *
J Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other application
36 in. 12 in.
K Clearance to mechanical air supply inlet 72 in. 36 in. above if within 10 feet
horizontally
L Clearance above paved sidewalk or paved driveway located on
public property
84 in.
3)
3) A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
*
M Clearance under veranda, porch deck or balcony 12 in.
4)
4) Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*
Table 24
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
15
Required other than direct vent terminal clearances (single pipe penetration) for PVC, CPVC and ABS systems.
Fig. 11
[*] For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated:
a) A minimum clearance value determined by testing in accordance with section 2.20, or; b) A reference to the following footnote: “Clearance in accordance with local installation codes and the requirements of the gas supplier.”
Canadian installations
1)
U.S. installations
2)
A Clearance above grade, veranda, porch, deck or balcony 12 in. 12 in.
B Clearance to window or door that may be opened 36 in. 4 feet below or to side of opening;
1 foot above opening
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffit located above the vent
termination within a horizontal distance of 2 feet (61cm) from the
center line of the termination
**
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H Clearance to each side of center line extended above meter/
regulator assembly
36 in. within a height 15 feet above
meter/ regulator assembly
*
I Clearance to service regulator vent outlet 36 in. *
J Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other application
36 in. 4 feet below or to side of opening;
1 foot above opening
K Clearance to mechanical air supply inlet 72 in. 36 in. above if within 10 feet
horizontally
L Clearance above paved sidewalk or paved driveway located on
public property
84 in.
3)
84 in.
M Clearance under veranda, porch deck or balcony 12 in.
4)
*
Table 25
1) In accordance with the current CSA B149. 1 Natural Gas and Propane Installation Code
2) In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
3) A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
4) Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
16
4.3.3 Vent configuration examples for PP, PVC, CPVC, or ABS systems
Below are approved examples of vertical and horizontal venting installations.
Fig. 12 Vertical venting system (single pipe penetration)
[1] Drain tee (when required) [2] Intake [3] Exhaust [LA] Maintain 12 in. (18 in. for Canada) minimum clearance above
highest anticipated snow level maximum of 24 in. above roof.
Fig. 13 Horizontal venting installation (combustion air piping not
shown)
[1] Termination [2] Minimum above ground or normally expected snow accumulation
level [3] Appliance [4] Elbow (note: minimum 1ft of straight vent pipe required) [5] Horizontal run ¼ " per foot down to termination
Fig. 14 Horizontal venting system (concentric vent)
[1] Exhaust [2] Combustion air [3] Exhaust pipe [4] Drain tee (when required) [5] Intake pipe [LA] Minimum 1"
Fig. 15 Horizontal parallel venting system (twin pipe direct vent)
[A] 3 ft minimum
WARNING:
▶ Single pipe penetration should be used in non-
freezing climates only and steps must be taken to ensure that adequate combustion air is available to the water heater at all times!
NOTICE:
▶ The air intake connection on the concentric
termination can be oriented in any possible direction.
Installation instructions
RTG 199 HE – 6 720 811 617 (2016/01)
17
Fig. 16 Horizontal venting system (single pipe penetration)
[1] Exhaust pipe [2] Drain tee (when required) [3] Intake pipe [LA] Minimum 4"
4.3.4 Vent connections for PP, PVC, CPVC, and ABS systems
Attaching the exhaust and air inlet connection adaptors to the top of the heater
▶ Attach the flue gas exhaust accessory to the top of the unit fig. 17
(position 1) using the 4 screws and gasket provided, and fully insert
vent pipe into the accessory.
▶ If using 4" venting, a 3" to 4" increaser should be installed directly
after this accessory. If using 2" venting, a 3" to 2" reducer should be
installed directly after this accessory. If using the PP twin pipe
system, adapters from the appliance adapter (3" PVC compatible) to
the PP system are needed.
Fig. 17 Exhaust connection
▶ Attach the combustion air inlet accessory to the top of the unit fig. 18
(position 2) using the 3 screws and gasket provided, and install 3" air intake pipe over the accessory.
Fig. 18 Inlet connection
4.3.5 Connecting the condensate water drain
NOTICE: Risk of appliance freezing!
▶ Single pipe penetration should be used in non-
freezing climates only and steps must be taken to ensure that adequate combustion air is available to the water heater at all times!
Note: Adhesive backing needs to be removed prior to installation.
NOTE: Vent pipe must be completely vertical when inserting or blue gasket inside exhaust accessory can become displaced. Exhaust accessory can be removed with vent pipe attached to check gasket position.
NOTE: The combustion air accessory can be installed on the top right or on the top left side of the heater. The combustion air inlet that is not used must be kept sealed.
NOTICE: Risk of appliance freezing! ▶ Failure to properly install condensate drain can
damage the appliance and will void the warranty.
NOTICE: Risk of appliance freezing! ▶ Do not install condensate drain tubing in areas where
it may freeze.
The condensate must be disposed of in accordance with local codes. See chapter 4.12 “Filling the condensate trap”.
Loading...
+ 39 hidden pages