Bradford White RG1PV40S, RG1PV50S, RG1PV55H, RG2PV40T, RG2PV50H Service manual

...
PV Series
Power Vent Gas Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
ThroughTheWall Models: RG1PV40S*(N,X) RG1PV50S*(N,X) RG1PV55H*(N,X) RG2PV40T*(N,X) RG2PV50H*(N,X) RG2PV50T*(N,X) RG2PV75H*(N,X) RG2PV60T*(N,X) LG1PV55H78*(N,X) LG2PV50H65*(N,X) LG2PV75H76*(N,X) (*) Denotes Warranty Years
Manual 2385154000B 08/18
Save this manual for future reference
The Bradford White
PV Series
Through-The-Wall Gas Water Heaters
Table of Contents
Page PV Service Procedure
Introduction.................................................................................................................................4 ---
How to Use This Manual ..........................................................................................................5 ---
Tools Required for Service........................................................................................................5 ---
Specifications..............................................................................................................................6 ---
Control Timings.........................................................................................................................10 ---
Sequence of Operation ..............................................................................................................11 ---
Troubleshooting .........................................................................................................................15 ---
Burner Inspection, Cleaning & Replacement ..........................................................................17 I
Pilot Testing, Cleaning & Replacement ................................................................................... 19 II
Pressure Switch Testing & Replacement .................................................................................20 III
Blower Testing & Replacement ...............................................................................................22 IV
Blower TemperatureSwitch Testing & Replacement ............................................................24 V
Gas Control Testing & Replacement........................................................................................26 VI
Flammable Vapor Device Testing and Replacement..............................................................33 VII
Safety Circuit Voltage Trace.....................................................................................................34 VIII
115 VAC Circuit Trace .............................................................................................................35 IX
Dip Tube Inspection & Replacement.......................................................................................36 X
Anode Inspection & Replacement............................................................................................37 XI
Flue Baffle Inspection & Replacement ....................................................................................38 XII
Inner Door Removal, Inspection & Replacement...................................................................39 XIII
Glossary of Terms......................................................................................................................43 ---
Parts List .....................................................................................................................................44 ---
Power Vent Gas Water Heaters
2
PV Series
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
WHAT TO DO IF YOU SMELL GAS!
x x
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
x
x
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
3
CAUTION
Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING
Hydrogen gas can be produced in an operating water heater that
has not had water drawn from the tank for a long period of time
(generally two weeks or more). Hydrogen gas is extremely
flammable. To prevent the possibility of injury under these
conditions, we recommend the hot water faucet to be open for
several minutes at the kitchen sink before you use any electrical
appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not
smoke or have open flame near the faucet at the time it is open.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED ¾” X ¾”
TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE
THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT
FROM EXCESSIVE TEMPERATURE AND PRESSURES.
CAUTION
If sweat fittings are to be used DO NOT apply heat to the nipples
on top of the water heater. Sweat the tubing to the adapter
before fitting the adapter to the water connections. It is
imperative that heat is not applied to the nipples containing a
plastic liner.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
x
Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas.
x
Most people recognize this odor as a “sulfur” or “rotten egg” smell.
x
Other conditions, such as “odorant fade” can cause the odorant to diminish in intensity, or “fade”, and not be as readily detectable.
x
If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately contact your gas supplier from a neighbor’s telephone.
Gas detectors are available. Contact your gas supplier, or plumbing professional, for more information.
WARNING
Water heaters are heat producing appliances. To avoid damage
or injury, do not store materials against the water heater or vent-
air intake system. Use proper care to avoid unnecessary contact
(especially by children) with the water heater and vent-air intake
components. UNDER NO CIRCUMSTANCES MUST
FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY OF THIS
WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY
LOCATION FROM WHICH FUMES COULD REACH THE
WATER HEATER OR VENT-AIR INTAKE SYSTEM
IMPORTANT
Before proceeding, please inspect the
water heater and its components for
possible damage. DO NOT install any
water heater with damaged
components. If damage is evident then please contact the supplier where the water heater was purchased or the
manufacturer listed on the rating plate
for replacement parts.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
3
PV Series
Introduction
The new Bradford White RG1PV & RG2PV water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark to pilot ignition system, enhanced diagnostics, simplified servicing, quiet operation, additional vent lengths, and Bradford White Defender Safety System
®
(not available on all models).
Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue.
Powerful Blower - will eliminate problems with difficult venting situations.
Quiet and Cool Blower Operation - blower noise is significantly reduced for both interior and exterior environments. Cooler operation increases blower life by reducing bearing wear and noise.
Rugged Wiring Connections - receptacle type connections promote error free wiring.
Increased Vent Lengths - increased venting performance is achieved while maintaining Energy Factor & FHR (not available on all models) performance.
The RG1PV & RG2PV water heaters use a combustion system where flue gases are combined with dilution air to reduce the flue gas temperature in the blower. The diluted flue gases are evacuated to the exterior through low temperature vent materials. The gas control maintains water temperature, ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency.
Please read the service manual completely before attempting service on this new series of power vent models.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater through the opening in the jacket. This air travels down and around the combustion chamber and enters through holes in the very bottom of the corrosion-resistant combustion chamber. The air then travels up through the oriented flame arrestor plate louvers, where the velocity of air is increased and its direction altered. The air then mixes in a normal manner with supplied gas and is efficiently combusted, producing low NOx emissions.
In the unlikely event trace amounts of flammable vapors are present in the air flowing into the combustion chamber, the vapors are harmlessly ignited by the burner. If flammable vapors are in sufficient quantity to prevent normal combustion, the flammable vapor sensor recognizes this and shuts down the pilot and main burner. Should the flammable vapor continue to burn, the flame arrestor plate prevents the flames from traveling backwards and igniting vapors outside of the combustion chamber. This feature is only on models with inputs less than or equal to 75,000 BTU/hr.
4
4
PV Series
It is intended for this manual to be used by qualified service personnel for the primary purpose of troubleshooting and repair of the Bradford White PV Series water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater.
The Honeywell WV4462A Electronic Gas Control will display error codes in the event of abnormal operation. Error codes are listed in the troubleshooting chart beginning on page 15 of this service manual. The troubleshooting chart will also indicate the probable cause for the error code and direct the service professional to a service procedure to properly diagnose the abnormal operation.
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent system to determine the problem.
Contact the Bradford White technical support group immediately if diagnosis cannot be made using the methods described in this service manual.
Tools Required for Service
A liquid “U” tube type or a digital (magnahelic) type can be used. This device is used to measure gas and/or air pressure and vacuum.
Manometer:
A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, Amps, micro-amps and ohms.
Multi-Meter:
In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm readings. It will be necessary to have special electronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets.
Electronic Probes:
Used to measure water temperature. An accurate thermometer is recommended.
Thermometer:
Used to measure water supply pressure. Also used to determine tank pressure by adapting to the drain valve of the heater.
Water Pressure Gage:
Pipe wrench, channel locks, open end wrenches (3/8”, 7/16”, 1/2”), 12” crescent wrench, allen wrench set, screw drivers (common & Phillip’s), 1/4” nut driver, pliers (common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, flashlight and 5 gallon pail.
Various Hand Tools:
5
5
PV Series
6
Power supply Dedicated 115 VAC, 60 Hz, 15A. Gas Supply Pipe Minimum 1/2” NPT (schedule 40 black iron pipe recommended). Approved Gas Type
Natural Gas or Propane, unit must match gas type supplied.
Gas Pressure
5.0” W.C. min. for Natural Gas, 11.0” W.C. min. for Propane, 14.0” W.C. maximum
(Natural Gas & Propane). Venting System Power vent through the wall or vertical through the roof. Approved Vent Materials
PVC, CPVC or ABS.
Minimum Clearance for Servicing
18” from top, 24” from front, 4” sides and rear.
Water Supply Pressure
150 PSI maximum allowable working pressure. Check local codes for supply
pressure. Gas Control ECO Limit
Residential 188°F (87°C), Commercial 199°F (93°C).
Residential Temperature Set Point Range
60°F (16°C) to 160°F (71°C) (approximate temperatures).
Commercial Temperature Set Point Range
80°F (27°C) to 180°F (82°C) (approximate temperatures).
Blower Temperature Switch
Normally closed, opens @ 155°F (68°C), auto reset @ approximately 135°F (57°C).
Pressure Switch
RG1PV(40,50)S, (R,L)G2PV50H Models: Normally open, closes on vacuum increase
@ -.75” W.C.; Opens on vacuum decrease @ -.72” W.C.
RG2PV(40,50)T: Normally open, closes on vacuum increase @ -.80” W.C.;
Opens on vacuum decrease @ -.77” W.C.
(R,L)1PV55H Models: Normally open, closes on vacuum increase @ -1.40” W.C.;
Opens on vacuum decrease @ -1.37” W.C.
(R,L)G2PV75H Models: Normally open, closes on vacuum increase @ -1.25” W.C.;
Opens on vacuum decrease @ -1.22” W.C.
Blower
115 VAC, 60 Hz, 3.1 amps, 3000 RPM.
6
PV Series
Vent Tables
Venting Specifications for:
RG1PV40S, RG2PV40T RG1PV50S, RG2PV50T
7
3" Diameter (10.2 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
115 (35) 10 (3.1)
Through the Wall
2
110 (33.5) 10 (3.1)
Through the Wall
3
105 (32.0) 10 (3.1)
Through the Wall
4
100 (30.5) 10 (3.1)
Through the Wall
5
95 (29.0) 10 (3.1)
Through the Roof
0
120 (36.6) 15 (4.6)
Through the Roof
1
115 (35) 15 (4.6)
Through the Roof
2
110 (33.5) 15 (4.6)
Through the Roof
3
105 (32.0) 15 (4.6)
Through the Roof
4
100 (30.5) 15 (4.6)
2" Diameter (5.1 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
45 (16.8) 2 (.6)
Through the Wall
2
40 (15.2)
2 (.6)
Through the Wall
3
35 (13.7) 2 (.6)
Through the Wall
4
30 (12.2) 2 (.6)
Through the Roof
0
50 (18.3) 7 (2.1)
Through the Roof
1
45 (16.8)
7 (2.1)
Through the Roof
2
40 (15.2) 7 (2.1)
Through the Roof
3
35 (10.7) 7 (2.1)
Through the Roof
4
30 (9.2) 7 (2.1)
7
PV Series
Vent Tables
Venting Specifications for:
RG2PV50H LG2PV50H
8
4" Diameter (10.2 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
175 (53.3) 10 (3.1)
Through the Wall
2
170 (51.8) 10 (3.1)
Through the Wall
3
165 (50.3) 10 (3.1)
Through the Wall
4
160 (48.8) 10 (3.1)
Through the Wall
5
155 (47.2) 10 (3.1)
Through the Roof
0
180 (54.9) 15 (4.6)
Through the Roof
1
175 (53.3) 15 (4.6)
Through the Roof
2
170 (51.8) 15 (4.6)
Through the Roof
3
165 (50.3) 15 (4.6)
Through the Roof
4
160 (48.8) 15 (4.6)
3" Diameter (7.6 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
55 (16.8) 2 (.6)
Through the Wall
2
50 (15.2)
2 (.6)
Through the Wall
3
45 (13.7) 2 (.6)
Through the Wall
4
40 (12.2) 2 (.6)
Through the Roof
0
60 (18.3) 7 (2.1)
Through the Roof
1
55 (16.8)
7 (2.1)
Through the Roof
2
50 (15.2) 7 (2.1)
Through the Roof
3
45 (13.7) 7 (2.1)
8
PV Series
Vent Tables
Venting Specifications for:
RG1PV55H RG2PV75H LG1PV55H LG2PV75H
9
4" Diameter (7.6 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum
Straight
Length ft. (m)
Minimum
Straight
Length ft. (m)
Through the Wall
1
175 (53.3) 10 (3.1)
Through the Wall
2
170 (51.8) 10 (3.1)
Through the Wall
3
165 (50.3) 10 (3.1)
Through the Wall
4
160 (48.8) 10 (3.1)
Through the Wall
5
155 (47.2) 10 (3.1)
Through the Roof
0
180 (54.9) 15 (4.6)
Through the Roof
1
175 (53.3) 15 (4.6)
Through the Roof
2
170 (51.8) 15 (4.6)
Through the Roof
3
165 (50.3) 15 (4.6)
Through the Roof
4
160 (48.8) 15 (4.6)
3" Diameter (7.6 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
45 (13.7) 2 (.6)
Through the Wall
2
40 (12.2)
2 (.6)
Through the Wall
3
35 (10.7) 2 (.6)
Through the Wall
4
30 (9.1) 2 (.6)
Through the Roof
0
50 (15.2) 7 (2.1)
Through the Roof
1
45 (13.7)
7 (2.1)
Through the Roof
2
40 (12.2) 7 (2.1)
Through the Roof
3
35 (10.7) 7 (2.1)
9
PV Series
Control Timings
10
Ignition State Timing
Pre-purge
2 Seconds
Trial for Ignition 90 Seconds Flame Stabilization Period
3 Seconds
Inter-purge
15 Seconds
Flame Failure Response Time
1.5 Seconds (2 second maximum; 1 second
minimum.) Post-purge 15 Seconds PS Fault Delay (failed open/close) Retry after 2 minutes Soft Lockout Retry after 5 minutes ECO Limit Lockout Indefinite (see page 27) Verify Resistive Delay Retry after 2 minutes (repeats 5 times) Flammable Vapor Sensor/Simulated Resistive Load Lockout
Indefinite (cycle power to restart)
Hardware Error Lockout
Indefinite (self clears if fault clears for at least 15
seconds)
10
PV Series
Power Up Sequence
1. Start Up. Upon power up, the control runs a safe-start check with a typical start-up delay of 5 seconds.
Flammable Vapor. To assure no outputs are energized if the “Flammable Vapor Sensor” (for RG1PV40S, RG1PV50S, RG2PV40T, RG2PV50T, RG2PV50H) or “Simulated Resistive Device” (for RG1PV55H and RG2PV75H) is out of range, the control will test the “Flammable Vapor Sensor” or “Simulated Resistive Device” for proper operating range. If the “Flammable Vapor Sensor” or “Simulative Resistive Device” is out of range, the control LED immediately flashes 7 times with 3 second pause.
2.
Normal Heating Sequence
Thermostat calls for heat. Prior to energizing blower, gas control checks safety circuit to ensure the circuit is open. Normal switch positions in the safety circuit are as follows:
a) Pressure switch normally open. b) Blower temperature switch normally closed.
If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause. Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.
Blower energizes. Pressure switch proves blower/vent system operation. If the pressure switch does not close within 30 seconds, the control LED flashes 3 times with 3 second pause. The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to close. This cycle repeats as long as there is a call for heat.
Blower pre-purge period (2 seconds). Trial for pilot ignition (90 seconds).
a.
The gas control lights the pilot by activating spark igniter and gas flow to pilot burner.
b.
If flame is not sensed within 90 seconds, igniter and gas flow are deactivated, blower will post purge and control LED flashes 6 times with 3
second pause. Main burner ignition. After pilot flame is sensed, gas control activates main valve for main burner ignition. The gas control will ignore flame and pressure switch signals for 3 seconds allowing for main burner to stabilize.
1.
2.
3.
4.
5.
6.
11
11
PV Series
Normal Heating Sequence (cont.)
7. Steady state operation.
During steady state operation, the control monitors:
Thermostat temperature sensor-when set point temperature is satisfied, gas valve is shut down and blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status code.
Pressure switch / blower temperature switch-if either switch opens, the pilot valve and the main valve are both shut down. The blower continues to run for 30 seconds attempting to close the circuit. The control LED flashes 3 times with 3 second pause.
Flame sensor-if flame is lost, pilot & main valves are shut down, blower runs for 15 seconds. Control attempts to re-light pilot 4 times. If unsuccessful, blower is shut down and control proceeds to 5 minute lockout. Control re-attempts to light pilot starting at normal heating sequence #2.
Thermostat satisfies. (Control LED flashing once every 4 seconds). Burner off.
8.
9.
10. Blower post purges (15 seconds).
Abnormal Operation
1. Flammable Vapor Sensor or Simulated Resistive Device Fault: a.
If the resistance is greater than 70,000 Ohms-the gas control immediately turns off all outputs. Control waits and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then once with a three second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to flammable vapor lockout. If the resistance is below 3000 Ohms-The gas control immediately turns off all outputs and proceeds to flash 8 times then once with three second pause. The error self clears if the resistance returns to normal range for at least 15 seconds.
b.
2. Temperature Sensor Fault: a.
Temperature sensor detected open circuit–The gas control immediately turns off all outputs and proceeds to flash 8 times then, 3 times with 3 second pause. The error self clears if the fault clears for at least 15 seconds.
b.
Thermal well sensor not reading the same temperature within ±5.5°F – The gas control immediately turns off all outputs and proceeds to flash 8
12
12
PV Series
Abnormal Operation (cont.)
times, then 3 times twice with 3 second pauses. The error self clears if the fault clears for at least 15 seconds.
c. Water temperature in excess of ECO (energy cut out) limit -The gas
control immediately turns off pilot & main valves and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset. To reset control, rotate knob of temperature control to the minimum setting for at least 6 seconds before returning to desired temperature setting.
3. Pressure Switch/Blower Temperature Fault: a.
Pressure switch closed at start of call for heat-the gas control waits 4 seconds then, proceeds to flash 2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower turns off after 30 seconds and the control waits for pressure switch to open. Any time the pressure switch opens, the blower turns on (or stays on) and the control proceeds to wait for pressure switch to close. Pressure switch or blower temperature switch failed to close-the gas control runs the blower for 30 seconds waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30 seconds, the blower turns off and the control flashes 3 times with 3 second pause. The gas control waits 2 minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes.
Pressure switch or blower temperature switch opens during burner operation-the gas control turns off the pilot and main valve, runs blower for
15 seconds (inter-purge) waiting for pressure switch and/or blower temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above, if the circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then, 2 times with 3 second pause. The gas control waits 5 minutes before repeating ignition sequence.
b.
c.
4. Trail for Ignition Fault: a.
Pressure switch opens during trial-the gas control turns off igniter and pilot valve. The gas control proceeds as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for ignition starting at blower pre-purge.
b.
Flame not sensed-the gas control energizes the spark igniter attempting to light the pilot and prove flame. If flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the blower through post purge and flashes 6 times then, once with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
13
13
PV Series
Abnormal Operation (cont.)
5. Flame sensing fault:
a.
Flame lost during run-the gas control turns off pilot and main valves, runs blower for 15 seconds (inter-purge). The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then, 3 times with 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence. Flame sensed out of sequence-the gas control only looks for pilot flame when the blower is running. If flame is present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost. Once the flame signal is
b.
lost, the control flashes 6 times then, 4 times with 3 second pause. control waits 5 minutes before repeating the ignition sequence.
The
14
14
PV Series
Observe green LED indicator on electronic gas control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.
15
LED Status Control Status Probable Cause
Service
Procedure
None, control LED not on or flashing
No electrical power
Control power switch in “OFF” position. Supply voltage interrupted.
Turn power on
Short flash, once every four seconds
Stand-by mode, Waiting for call for heat (no fault).
Temperature demand is satisfied
Normal operation. Adjust thermostat to temp level.
“Heartbeat” alternates bright/dim
Thermostat calling for heat (no fault).
Tank temperature below set point of thermostat.
Normal operation. Adjust thermostat to temp level.
Short flash once per second
Weak pilot signal on last call for heat.
1. Unstable pilot.
2. Pilot tube block or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
Page 19
Two flash, three second pause
Pressure switch not working­closed position.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
Page 20
Three flash, three second pause
Pressure switch or blower temp. switch not working -open position.
1. Vent blockage or improper vent
configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high.
6. Faulty blower temperature switch.
1. Check vent or vent tables.
2 & 3 Page 20
4. Page 22
5 & 6 Page 24
Four flash, three second pause
Excessive tank temperature. System must be
reset.
1. Temperature sensor out of calibration.
2. Faulty gas control.
3. Plumbing leak.
1.
Page 25
2.
Replace gas control,
page 31
Five flash, three second pause
Undesired-false pilot flame present.
1. Pilot valve stuck in open position.
Replace gas control, page 31
15
Loading...
+ 33 hidden pages