Bradford White RG2PDV40S6N, RG2PDV50S6N, RG2PDV50H6N, RG2PDV75H6N User Manual

Page 1
PDV Series
Power Direct Vent Gas Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
PDV Series Models: RG2PDV40S*(N,X) RG2PDV50S*(N,X) RG2PDV50H*(N,X) RG2PDV75H*(N,X) LG2PDV50H60*(N,X) LG2PDV75H80*(N,X) (*) Denotes Warranty Years
Manual 2385154100B 08/18
Save this manual for future reference
Page 2
The Bradford White
PDV Series
Powered Direct Vent Gas Water Heaters
Table of Contents
Page PDV Service Procedure
Introduction.................................................................................................................................4 ---
How to Use This Manual ..........................................................................................................5 ---
Tools Required for Service........................................................................................................5 ---
Specifications..............................................................................................................................6 ---
Control Timings.........................................................................................................................9 ---
Sequence of Operation ..............................................................................................................10 ---
Troubleshooting .........................................................................................................................14 ---
Burner Inspection, Cleaning & Replacement ..........................................................................16 I
Pilot Testing, Cleaning & Replacement ................................................................................... 17 II
Pressure Switch Testing & Replacement .................................................................................18 III
Blower Testing & Replacement ...............................................................................................20 IV
Blower TemperatureSwitch Testing & Replacement ............................................................22 V
Gas Control Testing & Replacement........................................................................................24 VI
Flammable Vapor Sensor Testing and Replacement ..............................................................28 VII
Safety Circuit Voltage Trace.....................................................................................................29 VIII
115 VAC Circuit Trace .............................................................................................................30 IX
Diptube Inspection & Replacement..........................................................................................31 X
Anode Inspection & Replacement............................................................................................32 XI
Flue Baffle/Core Inspection & Replacement........................................................................... 33 XII
Inner Door Removal, Inspection & Replacement................................................................... 34 XIII
Glossary of Terms......................................................................................................................37 ---
Parts List .....................................................................................................................................38 ---
2
2
2
Page 3
PDV Series
WARNING: If the information in these
instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
WHAT TO DO IF YOU SMELL GAS!
x
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
x
phone in your building.
Immediately call your gas supplier from a neighbor's phone.
x
Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
x
department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
IMPORTANT
Before proceeding, please inspect the
water heater and its components for
possible damage. DO NOT install any
water heater with damaged
components. If damage is evident then please contact the supplier where the water heater was purchased or the
manufacturer listed on the rating plate
for replacement parts.
WARNING
Water heaters are heat producing appliances. To avoid damage
or injury, do not store materials against the water heater or vent-
air intake system. Use proper care to avoid unnecessary contact
(especially by children) with the water heater and vent-air intake
components. UNDER NO CIRCUMSTANCES MUST
FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY OF THIS
WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY
LOCATION FROM WHICH FUMES COULD REACH THE
WATER HEATER OR VENT-AIR INTAKE SYSTEM
CAUTION
If sweat fittings are to be used DO NOT apply heat to the nipples
on top of the water heater. Sweat the tubing to the adapter
before fitting the adapter to the water connections. It is
imperative that heat is not applied to the nipples containing a
plastic liner.
WARNING
Hydrogen gas can be produced in an operating water heater that
has not had water drawn from the tank for a long period of time
(generally two weeks or more). Hydrogen gas is extremely
flammable. To prevent the possibility of injury under these
conditions, we recommend the hot water faucet to be open for
several minutes at the kitchen sink before you use any electrical
appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not
smoke or have open flame near the faucet at the time it is open.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
x
Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas.
x
Most people recognize this odor as a “sulfur” or “rotten egg” smell.
x
Other conditions, such as “odorant fade” can cause the odorant to diminish in intensity, or “fade”, and not be as readily detectable.
x
If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately contact your gas supplier from a neighbor’s telephone.
Gas detectors are available. Contact your gas supplier, or plumbing professional, for more information.
WARNING
FAI LU RE TO INST ALL AND MAINTAIN A NEW, LISTED ¾” X ¾”
TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE
THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT
FROM EXCESSIVE TEMPERATURE AND PRESSURES.
CAUTION
Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
3
3
3
Page 4
PDV Series
Introduction
The new Bradford White PDV water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark to pilot ignition system, enhanced diagnostics, simplified servicing, significantly quiet operation, additional vent lengths, and Bradford White Defender Safety System
Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue.
Powerful Blower - will eliminate problems with difficult venting situations.
Quieter and Cooler Blower Operation - blower noise is significantly reduced for both interior and exterior environments. Cooler operation increases blower life by reducing bearing wear and noise.
Rugged Wiring Connections - receptacle type connections promote error free wiring.
Increased Vent Lengths - increased venting performance is achieved while maintaining Energy Factor & FHR (not applicable on all models) performance.
®
(not available on all models).
The PDV water heaters use a combustion system where flue gases are combined with dilution air to reduce the flue gas temperature in the blower. The diluted flue gases are evacuated to the exterior through low temperature vent materials. The gas control maintains water temperature, ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency.
Please read the service manual completely before attempting service on this new series of power direct vent models.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater through the vent pipe from outside your building. This air travels into the closed combustion chamber. The air then mixes in a normal manner with supplied gas and it’s efficiently combusted, producing low NOx emissions.
In the unlikely event trace amounts of flammable vapors are present in the area surrounding the water heater, the sealed combustion system prevents the flammable vapors from reaching the ignition source. In addition the flammable vapors sensor will stop the water heater from operating if a significant amount of flammable vapors are present.
4
4
4
Page 5
PDV Series
It is intended for this manual to be used by qualified service personnel for the primary purpose of troubleshooting and repair of the Bradford White PDV Series water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater.
The Honeywell WV4462A Electronic Gas Control will display status codes in the event of abnormal operation. Status codes are listed in the troubleshooting chart beginning on page 14 of this service manual. The troubleshooting chart will also indicate the probable cause for the status code and direct the service professional to a service procedure to properly diagnose the abnormal operation.
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent system to determine the problem.
Contact the Bradford White technical support group immediately if diagnosis cannot be made using the methods described in this service manual.
Tools Required for Service
Manometer:
Multi-Meter:
Electronic Probes:
Thermometer:
Water Pressure Gage:
Various Hand Tools:
A liquid “U” tube type or a digital (magnahelic) type can be used. This device is used to measure gas and/or air pressure and vacuum.
A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, Amps, micro-amps and ohms.
In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm readings. It will be necessary to have special electronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets.
Used to measure water temperature. An accurate thermometer is recommended.
Used to measure water supply pressure. Also used to determine tank pressure by adapting to the drain valve of the heater.
Pipe wrench, channel locks, open end wrenches (3/8”, 7/16”, 1/2”), 12” crescent wrench, allen wrench set, screw drivers (common & Phillip’s), 1/4” nut driver, pliers (common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, flashlight and 5 gallon pail.
5
5
5
Page 6
PDV Series
Power supply Dedicated 115 VAC, 60 Hz, 15A. Gas Supply Pipe Minimum 1/2” NPT (schedule 40 black iron pipe recommended). Approved Gas Type
Gas Pressure
Venting System Power direct vent through the wall or vertical through the roof. Approved Vent Materials Minimum Clearance for Servicing Water Supply Pressure Gas Control ECO Limit Residential Temperature Set Point Range Commercial
Temperature Set Point Range
Natural Gas or Propane, unit must match gas type supplied.
5.0” W.C. min. for Natural Gas, 11.0” W.C. min. for Propane, 14.0” W.C. maximum (Natural Gas & Propane).
PVC, CPVC or ABS.
18” from top, 24” from front, 4” sides and rear.
150 PSI maximum allowable working pressure. Check local codes for supply pressure.
Residential 188°F (87°C), Commercial 199°F (93°C).
60°F (16°C) to 160°F (71°C) (approximate temperatures).
80°F (27°C) to 180°F (82°C) (approximate temperatures).
Blower Temperature Switch
Pressure Switch
Blower
Normally closed, opens @ 155°F (68°C), auto reset @ 135°F (57°C).
Normally open, closes on vacuum increase @ -.80” W.C.; Opens on vacuum decrease @ -.73” W.C. 115 VAC, 60 Hz, 3.1 amps, 3000 RPM.
6
6
Page 7
PDV Series
Vent Tables
Venting Specifications for:
RG2PDV(40,50)S
2" Diameter (5.1 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
3" Diameter (7.6 cm) Vent Connector Lengths
Terminating
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
1
2
3
4
0
1
2
3
# of
Elbows
1
2
3
4
5
0
1
2
3
4
30 (9.1) 2 (.6)
25 (7.6)
20 (6.1) 2 (.6)
15 (4.6) 2 (.6)
35 (10.7) 7 (2.1)
30 (9.1)
25 (7.6) 7 (2.1)
20 (6.1) 7 (2.1)
Maximum
Straight
Length ft. (m)
80 (24.4) 10 (3.1)
75 (22.9) 10 (3.1)
70 (21.3) 10 (3.1)
65 (19.8) 10 (3.1)
60 (18.3) 10 (3.1)
85 (25.9) 15 (4.6)
80 (24.4) 15 (4.6)
75 (22.9) 15 (4.6)
70 (21.3) 15 (4.6)
65 (19.8) 15 (4.6)
2 (.6)
7 (2.1)
Minimum
Straight
Length ft. (m)
7
7
7
Page 8
PDV Series
Venting Specifications for:
RG2PDV(50,75)H LG2PDV(50,75)H
3" Diameter (7.6 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
4" Diameter (7.6 cm) Vent Connector Lengths
Terminating
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
1
2
3
4
0
1
2
3
# of
Elbows
1
2
3
4
5
0
1
2
3
4
55 (16.8) 2 (.6)
50 (15.2)
45 (13.7) 2 (.6)
40 (12.2) 2 (.6)
60 (18.3) 7 (2.1)
55 (16.8)
50 (15.2) 7 (2.1)
45 (13.7) 7 (2.1)
Maximum
Straight
Length ft. (m)
95 (29.0) 10 (3.1)
90 (27.4) 10 (3.1)
85 (25.9) 10 (3.1)
80 (24.4) 10 (3.1)
75 (22.9) 10 (3.1)
100 (30.5) 15 (4.6)
95 (29.0) 15 (4.6)
90 (27.4) 15 (4.6)
85 (25.9) 15 (4.6)
80 (24.4) 15 (4.6)
2 (.6)
7 (2.1)
Minimum
Straight
Length ft. (m)
8
8
Page 9
PDV Series
Control Timings
Ignition State Timing
Pre-purge Trial for Ignition 90 Seconds
Flame Stabilization Period Inter-purge
Flame Failure Response Time
Post-purge 15 Seconds PS Fault Delay (failed open/close) Retry after 2 Minutes Soft Lockout Retry after 5 Minutes ECO Limit Lockout Indefinite (see page 25) Verify Resistive Delay Retry after 2 Minutes (repeats 5 times) Flammable Vapor Sensor/Simulated Resistive Load Lockout
Hardware Status Lockout
15 Seconds
3 Seconds 15 Seconds
1.5 Seconds (2 seconds. maximum; 1 second minimum.)
Indefinite (cycle power to restart)
Indefinite (self clears if fault clears for at least 15 seconds)
9
9
9
Page 10
PDV Series
Power Up Sequence
1. Start Up. Upon Power up, the control runs a safe-start check with a typical start-up delay of 1-5 seconds.
2.
Flammable Vapor. To assure no outputs are energized if the “Flammable Vapor Sensor” is out of range, the control will test the “Flammable Vapor Sensor” or for proper operating range. If the “Flammable Vapor Sensor” is out of range, the control LED immediately flashes 7 times with 3 second pause.
Normal Heating Sequence
1.
Thermostat calls for heat. Prior to energizing blower, gas control checks safety circuit to insure the circuit is open. Normal switch positions in the safety circuit are as follows:
a) Exhaust pressure switch normally open. b) Blower temperature switch normally closed.
If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause. Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.
2.
Blower energizes.
3.
Blower pre-purge period (15 seconds)
4.
Differential pressure switch proves blower/vent system operation. If the pressure switch does not close within 30 seconds, the control LED flashes 3 times with 3 second pause. The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to close. This cycle repeats as long as there is a call for heat.
5.
Trial for pilot ignition (90 seconds).
a.
The gas control lights the pilot by activating spark igniter and gas flow to pilot burner.
b.
If flame is not sensed within 90 seconds, igniter and gas flow are deactivated, blower will post purge and control LED flashes 6 times with 3 second pause.
6.
Main burner ignition. After pilot flame is sensed, gas control activates main valve for main burner ignition. The gas control will ignore flame and pressure switch signals for 3 seconds allowing for main burner to stabilize.
10
10
10
Page 11
PDV Series
Normal Heating Sequence (cont.)
7. Steady state operation.
During steady state operation, the control monitors:
Thermostat temperature sensor-when set point temperature is satisfied, gas valve is shut down and blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status code.
Pressure switch / blower temperature switch-if either switch opens, pilot valve and main valve is shut down. The blower continues to run for 30 seconds attempting to close the circuit. The control LED flashes 3 times with 3 second pause.
Flame sensor-if flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts to re-light pilot 4 times. If unsuccessful, blower is shut down and control proceeds to 5 minute lockout. Control re-attempts to light pilot starting at normal heating sequence #2.
Thermostat satisfies. (Control LED flashing once every 4 seconds).
8.
Burner off.
9.
10. Blower post purges (15 seconds).
Abnormal Operation
1. Flammable Vapor Sensor:
a.
If the resistance is greater than 70,000 Ohms-the gas control immediately turns off all outputs. Control waits and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then once with a three second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to flammable vapor lockout.
b.
If the resistance is below 3000 Ohms-The gas control immediately turns off all outputs and proceeds to flash 8 times then once with three second pause. The status self clears if the resistance returns to normal range for at least 15 seconds.
2. Temperature Sensor Fault:
a.
Temperature sensor detected open circuit–The gas control immediately turns off all outputs and proceeds to flash 8 times then, 3 times with 3 second pause. The status self clears if the fault clears for at least 15 seconds.
b.
Thermal well sensor not reading the same temperature within ±5.5°F – The gas control immediately turns off all outputs and proceeds to flash 8
11
11
11
Page 12
PDV Series
Abnormal Operation (cont.)
times, then 3 times twice with 3 second pause. The status self clears if the fault clears for at least 15 seconds.
c. Water temperature in excess of ECO (energy cut out) limit -The gas
control immediately turns off pilot & main valves and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset. To reset control, rotate knob of temperature control to the minimum setting for at least 6 seconds before returning to desired temperature setting.
3. Pressure Switch/Blower Temperature Fault: a.
Pressure switch closed at start of call for heat-the gas control waits 4 seconds then, proceeds to flash 2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower turns off after 30 seconds and the control waits for pressure switch to open. Any time the pressure switch opens, the blower turns on (or stays on) and the control proceeds to wait for pressure switch to close.
b.
Pressure switch or blower temperature switch failed to close-the gas control runs the blower for 30 seconds waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30 seconds, the blower turns off and the control flashes 3 times with 3 second pause. The gas control waits 2 minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes.
c.
Pressure switch or blower temperature switch opens during burner operation-the gas control turns off the pilot and main valve, runs blower for
15 seconds (inter-purge) waiting for pressure switch and/or blower temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above, if the circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count as not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then, 2 times with 3 second pause. The gas control waits 5 minutes before repeating ignition sequence.
4. Trail for Ignition Fault: a.
Pressure switch opens during trial-the gas control turns off igniter and pilot valve. The gas control proceeds as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for ignition starting at blower pre-purge.
b.
Flame not sensed-the gas control energizes the spark igniter attempting to light the pilot and prove flame. If flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the blower through post purge and flashes 6 times then, once with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
12
12
12
Page 13
PDV Series
Abnormal Operation (cont.)
5. Flame sensing fault: a.
Flame lost during run-the gas control turns off pilot and main valves, runs blower for 15 seconds (inter-purge). The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then, 3 times with 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
b.
Flame sensed out of sequence-the gas control only looks for pilot flame when the blower is running. If flame is present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost. Once the flame signal is lost, the control flashes 6 times then, 4 times with 3 second pause. control waits 5 minutes before repeating the ignition sequence.
The
13
13
13
Page 14
PDV Series
Observe green LED indicator on Electronic gas control. Status flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below
LED Status Control Status Probable Cause
None, control LED not on or flashing
Short flash, once every four seconds
“Heartbeat”, alternates bright/dim
Short flash once per second
Two flash, three second pause
Three flash, three second pause
Four flash, three second pause
Five flash, three second pause
No electrical power
Stand-by mode, Waiting for call for heat (no fault). Thermostat
calling for heat (no fault).
Weak pilot signal on last call for heat.
Pressure switch not working­closed position.
Pressure switch or blower temp. switch not working -open position.
Excessive tank temperature. System must be
reset. Undesired-false pilot flame present.
Control power switch in “OFF” position. Supply voltage interrupted.
Temperature demand is satisfied.
Tank temperature below set point of thermostat.
1. Unstable pilot.
2. Pilot tube block or restricted.
3. Oxidation builds up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
1. Vent blockage or improper vent
configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high.
6. Faulty blower temperature switch.
1. Temperature sensor out of calibration.
2. Faulty gas control.
3. Plumbing leak.
1. Pilot valve stuck in open position.
Service
Procedure
Turn power on
Normal operation. Adjust thermostat to temp level Normal operation. Adjust thermostat to temp level
Page 17
Page 18
1. Check vent or vent tables.
2 & 3 Page 18
4. Page 20
5 & 6 Page 22
1 & 2. Replace gas control, page 26
Replace gas control, page 26
14
14
14
Page 15
PDV Series
LED Status Control Status Probable Cause
g
Six-one flash, three second pause
Six-two flash, three second pause
Six-three flash, three second pause
Six-four flash, three second pause
Seven flash, three second pause Eight-one flash, three second pause Eight-two flash, three second pause Eight-three flash, three second pause Eight-four flash, three second pause
Failed to light pilot. System auto
resets.
Pressure switch or blower temp switch opened during burner operation. System auto
resets.
Pilot flame extinguished. System auto
resets.
Undesired-false pilot flame sensed. System auto
resets. Flammable vapor sensor fault detected.
Flammable vapor sensor out of specification.
Temperature Sensor fault.
Gas valve electronics fault detected.
Gas valve fault detected.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
1. Vent blockage or improper vent configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Vent termination being affected by wind.
5. Blower not spinning up to speed.
6. Blower temp or exhaust temp too high.
7. Faulty blower temperature switch.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
5. Insufficient combustion air.
6. Gas pressure is out of specification..
Pilot valve stuck in open position.
Flammable vapor sensor or simulative resistance device out of specification.
Flammable vapor sensor or Simulated resistive device out of specification.
1. Damage to temperature sensor wire.
2. Temperature sensor resistance out of range.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Control needs to be reset.
2. Control is wet or physically damaged.
Service
Procedure
Page 17
1. Check vent or vent tables.
2&3Page18
4.
Refer to venting section of installationmanual
5.
Page 20
6&7Pa
1-4. Page 17
5. manual
6.
Replace gas control, page 26
Page 28
Page 28
Replace gas control, page 26.
1.
2.
1.
2.
e 22
Refer to installation
Page 24
Interrupt power supply Replace gas control, page 26
Interrupt power supply Replace gas control, page 26
15
15
15
Page 16
PDV Series
Burner Inspection
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper operation and to assure no debris is accumulating.
Pilot flame should be stable, some causes for an unstable pilot flame are:
a)
Water heater vent is less than the allowable vent length.
b)
Gas pressure is out of specification.
c)
Pilot flame not fully engulfing spark/flame sensor.
Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.
Main burner must be free from any debris accumulation that may affect burner operation (see burner cleaning procedure on page 16).
Burner Cleaning
Step 1.
Step 2. Step 3.
Step 4.
Step 5.
Step 6.
Step 7.
Step 8. Step 9.
Step 10.
Step 11.
Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Turn off gas supply to water heater. Remove outer jacket door and inner door per service procedure XIII on page 34. Disconnect pilot tube (7/16” wrench) and feedline (3/4” wrench) from gas control. Disconnect igniter/flame sensor wire from gas control. Remove burner assembly from combustion chamber. Thoroughly inspect burner surface area and burner port area and remove any loose debris. Unscrew burner from main burner orifice. Remove main burner orifice from feedline (1/2” wrench on steel burners) inspect orifice, clean or replace if necessary. Reassemble burner and reinstall into water heater. Restore gas supply and check for gas leaks. To resume operation, follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual.
16
16
16
Page 17
PDV Series
Pilot Testing and Replacement
Step 1.
Step 2.
Step 3.
Step 4.
Step 5. Step 6. Step 7. Step 8.
Step 9.
Step 10.
Step 11.
Step 12.
Step 13.
Step 14.
Step 15.
Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Turn off gas supply to water heater. Remove outer jacket door and inner door per service procedure XIII on page 34. Disconnect pilot tubing nut (7/16” wrench) and feedline nut (3/4” wrench) from gas control. Disconnect igniter/flame sense wire from gas control. Remove burner assembly from combustion chamber. Remove pilot assembly from feedline (1/4” nut driver). Visually inspect igniter/flame sense wire for damage. found. With a multi-meter set to ohms setting, check continuity through igniter/flame sense wire. Replace pilot if no continuity. Visually inspect igniter/flame sense electrode for deterioration. Replace pilot as necessary. Electrode should not be in contact with pilot hood, if so, carefully adjust electrode to a gap of distance of 3/32” (.09) from pilot hood. Visually inspect igniter/flame sense electrode for oxidation build up. Carefully clean any oxidation using very fine emery cloth. Visually inspect pilot tubing for kinks or cracks. If damage is found, replace pilot. Inspect pilot tubing and pilot orifice for blockage:
a.
Remove ferrule nut from bottom of pilot assembly (7/16” wrench).
b.
Remove pilot tube and pilot orifice.
c.
Inspect pilot tubing and pilot orifice for blockage. Clean or replace as necessary. Reassemble pilot and install on feedline. Reinstall burner assembly to water heater. Restore gas supply and check for gas leaks. To resume operation, follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual.
Replace pilot if damage is
17
17
17
Page 18
PDV Series
Pressure Switch Testing
Step 1.
Step 2.
Step 3.
Position power switch on gas control to the “OFF” position. Remove the three screws (Phillips screw driver) from control access cover on blower assembly and remove cover (see photo 1). Carefully remove pressure switch from blower housing (see photo 2).
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
18
18
18
Page 19
PDV Series
Pressure Switch Replacement
Step 1.
Step 2.
Step 3. Step 4. Step 5. Step 6. Step 7. Step 8. Step 9.
Step 10.
Position gas control power switch to “OFF” position. Remove the three screws (Phillip’s screw driver) from control access cover on blower assembly and remove cover (see photo 3). Carefully remove pressure switch from blower housing (see photo 4). Disconnect tubing from pressure switch. (see photo 5). Disconnect yellow wires from pressure switch (see photo 6). Reconnect wires from step 6 to new pressure switch. Reconnect tubing to new pressure switch. Carefully position pressure switch into blower housing. Position gas control power switch to “ON” position and verify proper heater operation. Replace control access cover from step 2.
115 volt potential exposure. Use
caution to avoid personal injury.
WARNING
19
19
19
Page 20
PDV Series
Blower Testing
Step 1.
Step 2.
Position gas control power switch to “ON” position and adjust control to call for heat. Remove the three screws (Phillip’s screw driver) from control access cover on blower assembly and remove cover (see photo 7).
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
20
20
20
Page 21
PDV Series
Blower Removal
Step 1.
Step 2.
Step 3.
Step 4.
Step 5. Step 6. Step 7.
Step 8.
Step 9.
Position gas control power switch to “OFF” position and adjust control to call for heat. Unplug blower power cord from wall outlet. Disconnect vent system from exhaust adapter on top of blower. Remove exhaust adapter from blower (blade screw driver) and retain for use on new blower. Unplug cord sets from blower. Remove vertical air intake bracket. Disconnect vertical air intake from blower. Remove the three blower mounting screws (1/4” nut driver). Remove blower with gasket from water heater.
Blower Installation
Step 10.
Step 11.
Step 12.
Step 13.
Step 14.
Step 15. Step 16.
Step 17.
Step 18.
Clean any debris from jacket head of water heater. Set new blower with gasket in place using locating pins on blower flange to line up with location holes in jacket head. Be sure not to damage gasket. Secure blower in place using mounting screws from step 8. Re-install exhaust adapter from step 4. Reconnect vent system to exhaust adapter. Reconnect cord sets from step 5. Plug blower power cord into wall outlet. Position gas control power switch to the “ON” position. Verify proper blower operation.
21
21
21
Page 22
PDV Series
Blower Temperature Switch Testing
Position the power switch on the gas control to the “OFF” position.
Step 1.
Step 2.
Remove the three screws (Phillip’s screw driver) from control access cover on blower and remove cover (see photo 14). Locate blower temperature switch (see photo 15).
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
22
22
Page 23
PDV Series
Blower Temperature Switch Replacement
Step 1.
Step 2.
Step 3.
Step 4.
Step 5.
Step 6. Step 7.
Step 8.
Step 9.
Step 10. Replace control access cover from
Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Remove the three screws (Phillip’s screw driver) from the control access cover on blower and remove cover (see photo 16). Locate blower temperature switch (see photo 17). Disconnect red and yellow wire leads from switch. With an appropriate tool such as side cutters, snip the retaining lug from the blower housing to allow removal of temperature switch (see photo 18). Remove switch from blower housing. Install new switch. Be sure switch is properly seated in mounting area. Reconnect red and yellow wires to new switch. Wires are interchangeable with either terminal. Position gas control power switch to the “ON” position and verify proper heater operation.
step 2.
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
23
23
23
Page 24
PDV Series
24
Honeywell Gas Control Testing & Replacement
Line Pressure
The Gas Control is designed for a maximum line pressure of 14.0” W.C. and a minimum line pressure of 1.0” W.C. over the water heater’s rated manifold pressure (check rating plate). Line pressure must be check with the main burner on and off to assure proper readings.
Manifold Pressure Testing
(This procedure presumes a maximum line pressure of
14.0” W.C.)
Step 1. Step 2.
Step 3. Step 4.
Step 5.
Step 6.
Step 7.
Set the Gas Control to the “OFF” position. Remove pressure tap plug and install 1/8” NPT pipe, coupling & pressure tap. Connect manometer to pressure tap. Follow instructions located on the lighting instructions label and proceed to light the main burner and observe manometer reading. Proper operating range for Natural Gas is
4.0” ±0.5” W.C. Proper operating range for Propane gas is: 10.0” ±0.5” W.C. If pressure is within the range specified in the previous step, set Gas Control knob to the “OFF” position, remove manometer and pressure tap, and replace pressure tap plug. Check for gas leaks prior to placing water heater back into operation by following the instructions located on the lighting label or the lighting instructions located in the installation and operation manual. If gas pressure is outside the specification noted above, refer to “Honeywell Gas Control Testing, Disassembly and Replacement” to replace gas control or valve body.
24
24
Page 25
PDV Series
25
ECO (Energy Cut Out) Reset
The Honeywell Gas Control is designed with an ECO device that will reset.
To reset the Gas Control after a status code (4), turn the Gas Control knob to the “OFF” position and wait a minimum of (5) minutes before relighting following the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
Determine Water Temperature Inside Tank
WARNING
Stored water may be HOT WHEN PERFORMING THE FOLLOWING STEPS IN
THIS PROCEDURE. Take necessary precaution to prevent personal injury.
Step 1. Step 2.
Step 3.
Position gas control power switch to “OFF” position. Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an additional gallon and immediately measure water temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow heater to drain. Compare the measured water temperature with the setting on the gas control. 10°F.
In most instances, they should not differ by more than approx.
25
25
Page 26
PDV Series
Gas Control Removal From Water Heater
Step 1.
Step 2. Step 3.
Step 4. Step 5. Step 6.
Step 7. Removal of Gas Control
Position gas valve power switch to the “OFF” position and unplug heater from power supply. Drain heater to a point below the gas control level. Turn off gas supply to water heater and disconnect gas piping from gas control. Disconnect wire harnesses from gas control. Remove outer jacket burner access door. Right side inner door removal.
a.
Remove (2) hex drive screws from RIGHT side inner door.
b.
Remove (2) hex drive screws from FLANGE SECTION of inner door.
c.
Remove right side inner door and set aside. Be careful not to damage gasket material in inner door.
a. b.
Disconnect main burner feedline and pilot tube. Remove Gas Control from water heater by rotating counter clockwise. DO NOT use a wrench on the Gas Control body, damage to the Gas Control may occur. If necessary, use a length of ½” NPT pipe threaded into gas inlet of Gas Control.
Step 8. Install new Gas Control into water heater.
26
26
a.
b. c.
26
Install new Gas Control into water heater by rotating clockwise. DO NOT use a wrench on the Gas Control body, damage to the Gas Control may occur. If necessary, use a length of ½” NPT pipe threaded into gas inlet of Gas Control. Reattach main burner feedline, pilot tube and thermopile wire. Reconnect gas supply piping to inlet of Gas Control.
Page 27
PDV Series
Reinstallation of Inner Door Assembly.
d. Prior to reinstallation of inner door, fully inspect for the following:
-Tears
-Missing Material
-Cracks
-Dirt or debris
If the gasket is not affected by any of the above, gasket replacement will not be required. If replacement is required, replace using new gasket kit following the instructions provided with kit.
e.
Clean any gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly.
f.
Position thermopile wire and pilot tube against left side inner door flange gasket. DO NOT ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE. Be sure that thermopile and pilot tube are not in position to interfere with outer jacket burner access door when reinstalled.
g.
Firmly place right side inner door flange against the left side inner door flange and secure with (2) hex drive screws from step 6c. DO NOT OVER TIGHTEN
SCREWS.
h.
Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted openings. Verify seal integrity around combustion chamber opening. Secure right side inner door using (2) hex drive screws from step 6b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against the combustion chamber.
-Other imperfections that will inhibit proper seal
-Gasket adhesion to inner door
-Material left on combustion chamber (around opening)
CAUTION
A seal breach may result in a fire or explosion
causing property damage, personal injury or death.
Step 9. Step 10. Step 11.
Step 12.
Replace outer jacket burner access door. Reconnect gas supply to Gas Control. Resume water supply to water heater. Be sure tank is full of water before resuming operation. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
27
27
27
Page 28
PDV Series
Flammable Vapor Sensor Testing
Step 1. Position power switch on gas
control to the “OFF” position.
Step 2. Disconnect flammable vapor
sensor from gas control.
Step 3. Using a multi-meter set to the
ohms setting, check resistance of flammable vapor sensor. Resistance must be within 3,000 ohms and 48,000 ohms. If outside of this range replace Flammable Vapor Sensor.
CAUTION
DO NOT use a standard multi-meter probe for this
test. Doing so will damage connector. Use
special pin type electronic probes or small
diameter wire pins inserted into connector.
28
28
28
Page 29
PDV Series
Safety Circuit Voltage Trace
NOTE: This procedure assumes a cool tank.
Remove Three screws (Phillips Screw driver) from control
access cover on blower and remove cover (see photo 21)
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
.
29
29
29
Page 30
PDV Series
115 VAC Circuit Trace
Step 1. Verify 115 VAC and proper polarity
at wall outlet.
Step 2.
With unit plugged in and control
power switch in the “ON” position
verify LED status.
WARNING
115 volt potential exposure. Use
caution to avoid personal injury.
30
30
30
Page 31
PDV Series
Diptube Inspection & Replacement
WARNING
Water Heater components and stored water may be HOT when performing the
following steps in this procedure. Take necessary precaution to prevent
personal injury.
Step 1.
Step 2.
Step 3. Step 4.
Step 5.
Step 6.
Step 7.
Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet. Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water heater and allow heater to drain to a point below the inlet connection nipple. Disconnect inlet nipple from plumbing system. With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage pipe threads. Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage. Hydrojet slots should be open and free of any blockage. Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable and the inlet nipple/dip tube must be replaced. Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water heater. Ensure pipe dope is used on the nipple’s threads. Connect nipple to plumbing system, resume water supply and refill with water. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
31
31
31
Page 32
PDV Series
32
Anode Inspection & Replacement
WARNING
Water Heater components and stored water may be HOT when performing the
following steps in this procedure. Take necessary precaution to prevent
personal injury.
Step 1.
Step 2.
Step 3. Step 4.
Step 5.
Step 6.
Step 7.
Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall outlet. Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of water heater and allow water heater to drain to a point below the outlet connection nipple. Disconnect outlet nipple from plumbing system. With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use caution not to damage pipe threads. Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended. Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water heater. Ensure pipe dope is used on the nipple’s threads. Connect nipple to plumbing system, resume water supply and refill with water. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
32
32
Page 33
PDV Series
Flue Baffle/Core Inspection and Replacement
Step 1.
Step 2.
Step 3.
Step 4. Step 5.
Step 6. Step 7.
Step 8.
Step 9.
Step 10.
Step 11. Step 12.
Step 13.
Step 14.
Position gas control power switch to the “OFF” position and unplug blower from wall outlet. Disconnect vent system from exhaust adapter on top of blower. Disconnect intake air piping.
Unplug cord sets from blower (see photo 28). Remove the three blower mounting screws (1/4” nut driver) (see photo 28). Remove blower with gasket from water heater. Remove flue baffle or flue core from heater (see photos 29a and 29b). Inspect baffle or core for deterioration, missing restrictors. Clean any scale or debris build up. Replace with new baffle or core as necessary. Reinstall baffle or core into flue tube. Be sure hanger tabs are inserted into notch location at the top of the flue tube (see photos 30 & 31). Check burner to insure no scale has accumulated during this operation. cleaning procedure on page 16. Reinstall blower on water heater. Reinstall vent system with the support bracket Connect cord sets to blower. Plug water heater into wall outlet. To resume operation follow the lighting instruction location on the lighting instruction label or the lighting instructions located in the installation operation manual.
See burner
33
33
33
Page 34
PDV Series
Inner Door Removal Procedure
Step 1.
Step 2. Step 3. Step 4. Step 5. Step 6. Step 7.
Step 8.
-Tears
-Missing material
-Cracks
-Dirt or debris
Position gas control power switch to the “OFF” position. Remove outer jacket burner access door. Remove wire tie from feedline. Remove (2) ¼” hex drive screws from right side inner door. Remove (2) ¼” drive screws from flange section of inner door. Remove (2) ¼” drive screws from left side inner door. Remove inner door and inspect per step 8.
Fully inspect inner door gaskets for the following:
-Other imperfections that will inhibit proper seal
-Gasket adhesion to inner door
-Material left on combustion chamber (around opening)
If the gasket is not affected by any of the above, gasket replacement is not required. required, proceed to Inner Door Gasket Replacement Procedure.
Inner Door Gasket Replacement Procedure
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal
injury or death.
34
34
Step 9.
Step 10.
34
After inspection of inner door as noted in step 8, completely remove gasket and adhesive residue from right and left side inner doors as needed. Use RTV sealant (recommended bead size 1/8”) to secure the inner door gasket to the inner door sections (right & left). Refer to illustration on next page for proper application. Note the overlap configuration in the flange area of the inner door. Set the flange section first, this will help to achieve the proper overlap position.
If replacement is
Page 35
PDV Series
Installation of Inner Door with Gasket
Step 11.
Step 12.
Step 13.
Clean any residual gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly. Place the left side inner door into position first. Firmly position the radiused channel of the inner door around the feedline. Using the ¼” hex drive screws from step 6, secure left side inner door in place. DO NOT OVER TIGHTEN SCREWS Position pilot tube and igniter/sensor wire against left side inner door flange gasket. DO NOT
ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE.
WARNING
Stripped fastener connections
may allow for seal breach of
inner door. A seal breach may
result in a fire or explosion
causing property damage,
personal injury or death. Do
not over tighten screws in
steps 12, 14 and 15.
35
35
35
Page 36
PDV Series
Installation of Inner Door with Gasket (cont.)
Step 14. Firmly place right side inner door flange against the left side inner door flange and secure with
(2) ¼” hex drive screws from step 5. DO NOT OVER TIGHTEN SCREWS.
Step 15.
Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with right side inner door slotted opening. Verify seal integrity around combustion opening. Secure right side inner door using ¼” hex drive screws from step
4. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of inner door are properly positioned and sealed against the combustion chamber.
36
36
Step 16. Step 17.
36
Replace outer jacket burner access door. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
Page 37
PDV Series
Frozen Exhaust Vent Terminal(s)
If an intake or exhaust vent terminal is blocked with ice or snow due to severe conditions, the pressure switch and control will not allow the burner to operate. This will result in a three flash status code. Once the blockage is removed (through melting or other means) the controls will let the burner operate. The position of the vent terminals in relation to each other and terminals from other appliances can have an effect on the potential for blockage due to ice or snow. See the installation instructions for recommended positioning of the terminals.
Testing under severe conditions has shown that the optional concentric vent terminal is resistant to ice blockage. Contact Bradford White or the supplier of the water heater for information about ordering the optional concentric vent terminal.
Bradford White has also developed an air intake relief device that can be installed in the air intake near the water heater temporarily enabling the water heater to operate with a frozen intake terminal. Contact Bradford White or the supplier of the water heater for information about the air intake relief device.
Glossary of Terms
BTU GPM Hz KWh LED NPT Ohms PSI RPM ECO VAC “ W.C. ºC ºF
British Thermal Units Gallons per minute Hertz kilowatt hour Light Emitting Diode National Pipe Thread Ohm s of resistance Pounds per square inch Revolutions per minute Energy Cut Out Volts Alternating Current Inches of Water Column Degrees Centigrade Degrees Fahrenheit
37
37
37
Page 38
PDV Series
1.
Blower Complete
2.
Temperature Switch
3.
Pressure Switch
4.
Blower Gasket
5.
Tee and Vent Pipe Ass’y
6.
Vent Adapter w/ Term.
7.
Intake Terminal
8.
Vent Terminal Elbow
9.
Exhaust adapter
10.
Condensate Hose Kit
11.
Flue Reducer (50H Only)
38
38
38
12.
Heat Trap Outlet
13.
Hot Water Outlet Anode
14.
Flue Baffle (except 75H)
15.
Heat Trap Inlet
16.
Inlet Dip Tube
17.
Wire Harness
18.
T&P Valve
19.
¾ NPT Plug
20.
Direct Vent boot escutcheon
21.
Air intake boot
22.
Air intake boot gasket
23.
Outer Door
24.
Right side inner door
25.
Left side inner door
26. Screw #10-12 x ¾
27.
Screw #8-15 x ¾
28.
Drain valve
29.
FV Sensor
30.
FV Sensor harness
31.
FV Sensor Clip
32.
Gas Control
33.
Burner Assy.
34.
Main Burner
35.
Main Burner Orifice
36.
Pilot Assy.
37.
Pilot Orifice
38.
Feedline
39.
Inner Door Gasket Kit
40.
Kit-Heat Trap insert
41.
Flue core (75H only)
42.
ASSE Approved Mixing Valve
Page 39
Page 40
Loading...