Bradford White RG2F40S*(N, X), RG2F50S*(N Service Manual

Page 1
High EF
Atmospheric Vent Gas Water Heater
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
RG2F40S*(N,X) RG2F50S*(N,X) (*) Denotes Warranty Years
Manual 238-51617-00A
Save this manual for future reference
Page 2
Table of Contents
Section Page
Introduction ______________________________________________ 5 How to Use this Manual _____________________________________ 6 Tools Required for Service ___________________________________ 6 Specifications _____________________________________________ 7 Sequence of Operation _____________________________________ 9 Power Up Sequence Normal Heating Sequence Abnormal Operation Troubleshooting __________________________________________ 13 Burner Maintenance _______________________________________ 15 Burner Inspection Burner Cleaning Procedure Pilot Maintenance_________________________________________ 17 Pilot Inspection, Testing and Replacement Blower Replacement ______________________________________ 19 Gas Control Testing & Replacement __________________________ 21 Determine Temperature Inside Tank _____________________ 21 Gas Control Removal _________________________________ 22 Flammable Vapor Sensor Testing ____________________________ 23 120 VAC Circuit Trace _____________________________________ 23 Diptube Inspection _______________________________________ 24 Anode Inspection _________________________________________ 25 Blower Removal __________________________________________ 25 Inner Door Removal ______________________________________ 28 Inner Door Gasket Replacement _____________________________ 30 Inner Door Installation ____________________________________ 31 Pressure Switch Testing & Replacement _______________________ 32 Arrestor Cleaning _________________________________________ 34 Common Terms __________________________________________ 35 Parts List _______________________________________________ 36 Notes __________________________________________________ 37
2
Page 2
Page 3
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
What to do if you smell gas:
x Do not try to light any appliance x Do not touch any electrical switch; do not use any phone in your building x Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions. x If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
CAUTION
Incorrect operation of this water heater may create a hazard to life and property and will nullify the warranty.
If sweat fittings are to be used, DO NOT apply heat to the nipples on top of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner.
Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
NOTICE
Before proceeding, please inspect the water heater and its components for possible damage. DO NOT install any water heater with damaged components. If damage is evident, then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts.
Page 3
3
Page 4
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or any of its components. Use proper care to avoid unnecessary contact, especially by children, with the water heater and its components. Under no circumstances must flammable materials, such as gasoline or paint thinner be used or stored in the vicinity of this water heater or in any location in which the fumes could reach the water heater.
Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend a hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas. Most people recognize this odor as a “sulfur” or “rotten egg” smell. Other conditions, such as “odorant fade” can cause the odorant to diminish in intensity, or ”fade,” and not be as readily detectable. If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately contact your gas supplier from a neighbor's telephone. Gas detectors are available. Contact your gas supplier, or plumbing professional for more information.
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4” TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES.
Page 4
4
Page 5
Introduction
The Bradford White DEFENDER Safety System®
The Bradford White DEFENDER Safety System was designed to resist the ignition of flammable vapors that can occur outside of the water heater. Use and installation are nearly identical to previous versions of atmospherically fired and vented water heaters. A number of exclusive design features are incorporated in the system that will require additional knowledge on the part of the qualified service provider. The following information will instruct service professionals on the function, proper diagnosis, and repair of water heaters employing the Bradford White DEFENDER Safety System.
Introduction
The new Bradford White High EF atmospheric vent gas water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark-to-pilot ignition system, enhanced diagnostics, simplified servicing, and the Bradford White Defender Safety System.
Spark-to-Pilot Ignition System - employing the spark-to-pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermal Well/Gas Control with LED - was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue.
Rugged Wiring Connections - receptacle type connections promote error free wiring.
The gas control maintains water temperature, ignition sequence, and regulates gas flow. If a situation outside of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency. To further promote quicker service times, the gas control can be removed and replaced without draining the water heater.
Please read the service manual completely before attempting service on this new series of High EF gas models.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater through the openings in the jacket. This air travels down and around the combustion chamber and enters through holes in the very bottom of the corrosion resistant combustion chamber bottom. The air then travels up through the flame arrestor louvers, where the velocity of the air is increased and its direction altered. The air then mixes in a normal manner with supplied gas and is efficiently combusted, producing low NOx emissions.
In the unlikely event trace amounts of flammable vapors are present in the air flowing into the combustion chamber, the vapors are harmlessly ignited by the burner. If flammable vapors are
Page 5
5
Page 6
How to Use this Manual
in sufficient quantity to prevent normal combustion, the flammable vapor sensor recognizes this and shuts down the pilot and main burner. Should the flammable vapors continue to burn, the flame arrestor prevents the flames from traveling backwards and igniting vapors outside of the combustion chamber. And, the resettable thermal switch will open and shut down the pilot and main burner.
How to Use this Manual
It is intended for this manual to be used by qualified service personnel for the primary purpose of troubleshooting and repair of the Bradford White High EF atmospheric gas water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater.
The Honeywell WV4462 Electronic Gas Control will display status codes in the event of abnormal operation. Status codes are listed in the troubleshooting chart beginning on page 13 of this service manual. The troubleshooting chart will also indicate the probable cause for the status code and direct the service professional to a service procedure to properly diagnose the abnormal operation.
Contact the Bradford White technical support group immediately if diagnosis cannot be made using the methods described in this service manual.
Tools Required for Service
Manometer: A liquid “U” tube type or a digital (magna-helic) type can be used. This device is
used to measure gas and/or air pressure and vacuum.
Multi-Meter: A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, amps, micro-amps and ohms.
Electronic Probes: In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm reading. It will be necessary to have special electronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets.
Thermometer: Used to measure water temperature. An accurate thermometer is recommended.
Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Various Hand Tools: Pipe wrench, channel locks, open end wrenches (3/8", 7/16", 1/2"), 12" crescent wrench, Allen wrench set, screw drivers (common & Phillips), torx bits, 1/4" nut driver, pliers (common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, flashlight, and 5 gallon pail.
6
Page 6
Page 7
Specifications
Power Supply
Gas Supply Pipe
Approved Gas Type
Gas Pressure
Approved Vent Materials
Recommended Minimum
Clearance for Servicing
Water Supply Pressure
ECO Limit
Pressure Switch Setting
(normal altitude)
Temperature Setpoint Range
Dedicated 120VAC, 60 Hz, 15A
Minimum 1/2” (Schedule 40 black iron pipe
recommended)
Natural or Propane; unit must match gas type supplied
5” w.c. minimum for Natural Gas; 11” w.c. for Propane; 14” w.c. maximum for Natural Gas / Propane
Single or Double Wall Metal Vent Pipe
18” from top; 24” from front; 4” from sides and rear
150 psi maximum allowable working pressure; check local codes for supply pressure
188°F (87°C)
-0.20” w.c. (-0.10” for Hi-Alt.)
60°F (16°C) to 160°F (71°C); approximate temperatures
Page 7
7
Page 8
Specifications
Control Timings
Ignition State Timing
Pre-purge 15 seconds
Trial for Ignition 90 seconds
Flame Stabilization Period 3 seconds
Interpurge 15 seconds
Flame Failure Response Time
Postpurge 15 seconds
Pressure Switch Fault Delay (failed open/close) Retry after 2 minutes
Soft Lockout Retry after 5 minutes
ECO Limit Lockout Indefinite (See page 21 to reset)
Verify Resistive Delay Retry after 2 minutes (repeats 5 times)
Simulated Resistive Load Lockout Indefinite (cycle power to reset)
Hardware Status Lockout
1.5 seconds (2 second maximum; 1 second mini­mum)
Indefinite (self clears if fault clears for at least 15
seconds)
Wiring Diagram
8
Page 8
Page 9
Sequence of Operation
Power Up Sequence
1. Start-up: Upon power up, the gas control runs a safe start check with a typical
delay of 5 seconds.
2. Flammable Vapor Verification: The gas control verifies that the Flammable Vapor
Sensor is in the proper operating range prior to energizing any components. If the sensor is within the proper range, the gas control resumes normal operation. If the Flammable Vapor Sensor is out of range, the gas control LED immediately flashes 7 times with a 3 second pause.
Normal Heating Sequence
1. Thermostat Calls for Heat: Prior to energizing the blower, the gas control verifies
the safety circuit to see if it is in the correct state. Normal switch positions in the safety circuit are as follows:
A) Pressure switch normally open;
B) Blower temperature switch normally closed.
If the safety circuit is closed, the gas control LED flashes 2 times with a 3 second pause. The gas control waits 2 minutes. Then, the blower is energized for 30 seconds. This cycle repeats until the safety circuit opens.
2. Blower Energizes
3. Safety Circuit Check: If the safety circuit does not close within 30 seconds, the
gas control LED flashes 3 times with a 3 second pause. The blower runs for a maximum of 30 seconds every 2 minutes trying to close the safety circuit. This cycle repeats as long as there is a call for heat.
4. Blower Pre-Purge (15 seconds)
5. Trial for Pilot Ignition (90 seconds): The gas control lights the pilot by activating
the spark igniter and gas flow to the pilot burner. If flame is not sensed within 90 seconds, the spark igniter and gas flow are deactivated. The blower will postpurge, and the gas control LED flashes 6 times then 1 time with a 3 second pause.
6. Main Burner Ignition: After pilot flame is sensed, the gas control activates the
main valve for main burner ignition. The gas control will ignore flame signals for 3 seconds to allow for the main burner to stabilize.
Page 9
9
Page 10
Sequence of Operation
Normal Heating Sequence (cont’d)
7. Steady State Operation: During steady state operation, the gas control monitors:
Temperature Sensor: When the setpoint temperature is satisfied, the gas control is
shutdown, and the blower will postpurge for 15 seconds. The gas control LED flashes a short flash once every 4 seconds (Idle status code).
Pressure Switch / Blower Temperature Switch: If either switch opens, the pilot and main valves are shutdown. The blower continues to run for 30 seconds attempting to close the circuit. The gas control LED flashes 3 times with a 3 second pause.
Flame Sensor: If flame is lost, the pilot and main valves are shutdown. The blower runs for 15 seconds. The gas control attempts to re-light the pilot 4 times. If unsuccessful, the blower is shutdown, and the gas control proceeds to a 5 minute lockout. The gas control re-attempts to light the pilot starting at Normal Heating Sequence #2.
8. Thermostat Satisfies: Gas control LED flashes once every 4 seconds.
9. Burner Off
10. Blower Postpurge (15 seconds)
Abnormal Operation
1. Flammable Vapor Sensor Fault:
A) If the resistance is greater than 70,000 ohms: The gas control immediately turns off all outputs. The gas control waits and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times with a 3 second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to flammable vapor lockout.
B) If the resistance is below 240 ohms: The gas control immediately turns off all outputs and proceeds to flash 8 times then 1 time with a 3 second pause. The status self clears if the resistance returns to normal range for at least 15 seconds.
10
Page 10
Page 11
Sequence of Operation
Abnormal Operation (cont’d)
2. Temperature Sensor Fault:
A) Temperature Sensor Open Circuit: The gas control immediately turns off all outputs and proceeds to flash 8 times then 2 times with a 3 second pause. The status self clears if the fault clears for at least 15 seconds.
B) Temperature Sensors Not Reading the Same Temperature within ±5°F: The gas control immediately turns off all outputs and proceeds to flash 8 times then 2 times with 3 second pause. The status self clears if the fault clears for at least 15 seconds.
C) Water Temperature in excess of ECO (Energy Cut Out) Limit: The gas control immediately turns off the pilot and main valves. The gas control LED proceeds to flash 4 times with a 3 second pause.
To reset the gas control, rotate the setpoint knob to the minimum setting for at least 6 seconds before returning to desired temperature setting.
3. Pressure Switch / Blower Temperature Switch (Safety Circuit) Fault:
A) Pressure Switch Closed at Start of Call for Heat: The gas control proceeds to
flash 2 times with a 3 second pause. The gas control waits 2 minutes, and then turns the blower on for 60 seconds. The blower turns off after 60 seconds, and the control waits for the pressure switch to open.
B) Pressure Switch Failed to Close: The gas control runs the blower for 60
seconds waiting for the pressure switch to close. If the switch does not close in 60 seconds, the blower turns off, and the control flashes 3 times with a 3 second pause. The gas control waits two minutes before turning on the blower for another 60 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes.
C) Pressure Switch / Blower Temperature Switch Opens During Burner Operation:
The gas control turns off the pilot and main valve and runs the blower for 15 seconds (inter-purge) waiting for the pressure switch and/or blower temperature switch to close. If either switch fails to close, the control proceeds as described in 3B above. If the circuit closes again by the end of the inter-purge, the recycle counter is incremented. If the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then 2 times with a 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
Page 11
11
Page 12
Sequence of Operation
Abnormal Operation (cont’d)
4. Trial for Ignition Fault:
A) Pressure Switch / Blower Temperature Switch Opens During Trial: The gas
control stops the trial for ignition. The gas control monitors the pressure switch until it closes. If the pressure switch closes within 30 seconds, the gas control will continue with the trial for ignition starting at blower pre-purge.
B) Flame Not Sensed: The gas control energizes the spark igniter attempting to
light the pilot and prove flame. If flame is not sensed within 90 seconds, the spark igniter turns off, the pilot valve is closed, and the gas control runs the blower through postpurge. The gas control LED flashes 6 times then 1 time with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
5. Flame Sensing Fault:
A) Flame Lost During Run: The gas control turns off pilot and main valves and runs the blower for 15 seconds (inter-purge). The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control LED flashes 6 times then 3 times with a 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
B) Flame Sensed Out of Sequence: The gas control only looks for pilot flame when the blower is running. If flame is present when the pilot valve is not open, the gas control continues to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost. Once the flame signal is lost, the control flashes 6 times then 4 times with a 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
12
Page 12
Page 13
LED Status Control S tatus Probable Cause Service Procedure
pply
One short flash
(
)
One short flash
)
p
(
)
Short flash once
g
y p
p
Six flashes, one
g
None (LED not on or flashing)
every four
every two
Alte rn a tes
brigh t and dim
heartbeat
every second
Two flashes,
three second
Observe the green LED on the water heater gas control. Status codes are displayed with a 3 second pause before repeating. Once the status code is known, check and repair the water heater, as recommended in the table below.
Co ntrol pow e r sw itch in "OFF" po s ition. Su
Temperature demand is satisfied (no ca ll fo r he at)
Temperature on Setback Control is adjusted down to prevent burner o
Tank temperature below setpoint of the rmo st a t
1. Uns ta ble pilo t
2. P ilo t tu be blocke d o r restricte d
3. Oxid a tion build-up o n pilot electrode
4. W ire da mage to pilo t a s s e mbly o r bad connection at
1. Pressure switch tubing kinked or blo cked
2. Blocked pressure tap on switch or blower
3. Fault
voltage inte rrupted.
eration
as control
ressure switch
Turn Power On
Normal operation
Normal operation
Normal operation
1. See Burner Inspection on page 15 2-4. Se e P ilo t Ins pe ction, Testing and Replacement on page 17
See Pressure Switch Testing and Replacement on page 32
second s
second s
pause
Ele ctrical po we r no t
present
Stand-by mode,
Thermostat is
satis fied
Stand-by mode,
Sabbath mode (no
The rmo s tat ca lling
for heat (no fault)
W e a k pilo t s ig nal
on la s t ca ll fo r h e a t
Pressure switch not
w o rkin g - clos e d
no faults
faults
po sitio n
Troubleshooting
Three flashes,
three second
Four flashes,
three second
Five flashes,
three second
flash, three second pause (Soft Lockout)
pause
pause
ause
Pressure switch or
temperature sw itch
not working - open
po sitio n
Excessive ta nk
temperature,
syste m mu st b e
reset
Fa ls e p ilo t fla me
present
Faile d to light pilot,
system resets after
(5) min u tes
1. Vent blockage or improper vent config ura tion
2. Pressure switch tubing kinked or blo cked
3. Faulty pressure switch
4. Blower not spinning up to speed
5. Da mper (inside blow e r) no t fully ope nin g
6. Faulty blower temperature switch
1. Temperature sensor out of calibratio n
2. Faulty gas control
Pilot va lve s tuck in o p e n pos ition Replace gas control
1. Uns ta ble pilo t
2. P ilo t tub e b lo ck or re s tricted
3. Oxid a tion build-up o n pilot electrode
4. W ire da mage to pilo t a s s e mbly o r bad connection at
as va lve
1. Ve rify co rd s e ts are fully plug ged in
2. See Pressure Switch Testing and Replacement on page 32
1. Test Gas Control & Temperature Sens o r
2. Replace gas control if necessary
1. See Burner Inspection on page 15 2-4. Se e P ilo t Ins pe ction, Testing and Replacement on page 17
Page 13
13
Page 14
g
p
g
p
p
p
Troubleshooting
LED Status Control Status Probable Cause Service Procedure
1. Vent blockage or improper vent configuratio n
2. Pressure switch tubing kinked or blo cke d
3. Faulty pressure switch
4. Blower not spinning up to speed
5. Da mpe r (in s id e b lo w e r) no t fully opening
6. Faulty blower temperature switch
1. Uns table pilot
2. P ilo t tube block o r restricte d
3. O xid a t io n build-up o n pilot electrode
4. Wire damage to pilot assembly or bad connection at gas control
5. Insufficient combustion air
6. Insufficient
Pilot valve stuck in open position Replace gas control
1. Flammable vapor present
2. Flammable vapor sensor exposed to e xce s s ive moistu re
3. Flammable vapor sensor exposed to extreme ambient temperature
4. Resettable thermal switch open
as pressure
1. See Burner Inspection on page 15 2-4. See Pressure Switch Testing and Replacement on page 32
1. See Burner Inspection on page 15 2-4. See Pilot Inspection, Testing and Replacement on page 17
5. Refer to Installation & Operation Manual
See Flammable Vapor Sensor Testing on page 24
Six flashe s , two
flashes, three second pause (Soft Lockout)
Six flas hes, three
flashes, three second pause (Soft Lockout)
Six flashes, four
flashes, three
second
Seven flashes,
three second
ause
pause
Pressure switch or
blower temp switch
opened during
burne r o peratio n,
system auto resets
afte r (5) minu t e s
Pilot flame
extinguished,
system auto resets
afte r (5) minu t e s
Undesired false
pilo t flame sensed,
system auto resets
Fla mma b le va p o r
se nsor o r
resettable thermal
switch fa ult
detected, see
warning la b e l
Eight flashes,
one flash, three
second pause
Eight flashes,
tw o fla s he s,
three second
pause
Eight flashes,
three flashes,
three second
pause
Eight flashes,
four fla s hes,
three second
pause
Fla mma b le va p o r
sensor out of
spe cificatio n,
po ssible s hort
Temperature
sensor fault
detected
Gas control
electronics fa u lt
detected
Gas control fault
detected
1. Flammable vapor sensor out of specification; verify Flammable Vapor Sens o r (FVS) re s ista nce is not below 25,000 Ohms.
2. P o s sible s hort in flammab le vapor sensor or resettable thermal switch w irin
1. Damage to temperature sensor wire s
2. Temperature sensor resistance out of range
3. Re
lace temperature sensor
1. Ve rify co ntro l is not w et o r physically damaged
2. Reset control on/off sw itch
3. Replace gas control if 8-3 error ersists
1. Ve rify co ntro l is not w et o r
physically damaged
2. Reset control on/off sw itch
3. Replace gas control if 8-4 error ersists
See Flammable Vapor Sensor Testing on page 24
See Temperature Sensor Testing on page 21
See Gas Control Removal on page 22
1. Replace gas control if wet or ph ys ically da maged
2. C ycle pow er
3. Replace gas control
Page 14
14
Page 15
Burner Maintenance
Burner Inspection
At periodic intervals (every 6 months), a visual inspection should be made of the pilot and main burner for proper operation and to assure no debris is accumulating. The pilot flame should be stable. Some causes for an unstable pilot flame are:
a) Gas pressure is out of specification.
b) Pilot flame not fully engulfing spark/flame sensor.
The main burner should light smoothly from the pilot and burn with a blue flame with a minimum of yellow tips.
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. The main burner must be free from any debris accumulation that may effect burner operation (See Burner Cleaning Procedure below).
Burner Cleaning Procedure
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Turn off the gas supply to the water heater.
Step 4. Remove the outer door.
Outer door
Page 15
15
Page 16
Burner Maintenance
Burner Cleaning Procedure (cont’d)
Step 5. Remove the (4) 1/4” hex drive screws holding the right side inner door in place.
(4) 1/4” hex drive
screws
Step 6. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Pilot and main feed-
lines
Step 7. Disconnect the spark igniter/flame sensor wire from gas control.
Gas control
Spark igniter/flame
sensor wire
Right side
inner door
Step 8. Remove the burner assembly from the combustion chamber.
Burner assembly
Burner surface area
and burner ports
Step 9. Thoroughly inspect the burner surface area and burner port area and remove any loose debris.
Step 10. Unscrew the burner from the main burner orifice.
Main feedline
Step 11. Remove the main burner orifice from the main feedline using a 1/2” wrench. Inspect the orifice and clean or replace, if necessary.
1/2” wrench
Main burner
orifice
16
Page 16
Page 17
Pilot Maintenance
Burner Cleaning Procedure (cont’d)
Step 12. Reassemble the burner assembly and reinstall into the water heater. Restore gas supply and check for gas leaks.
Step 13. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Pilot Inspection, Testing and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Turn off the gas supply to the water heater.
Step 4. Remove the outer door.
Outer door
Step 5. Remove the (4) 1/4” hex drive screws holding the right side inner door in place.
(4) 1/4” hex drive
screws
Right side
inner door
Step 6. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Pilot and main feed-
lines
Page 17
17
Page 18
Pilot Maintenance
Pilot Inspection, Testing and Replacement (cont’d)
Step 7. Disconnect the spark igniter/flame sensor wire from gas control.
Gas control
Spark igniter/flame
sensor wire
Step 8. Remove the burner assembly from the combustion chamber.
Burner assembly
Step 9. Remove the pilot assembly from the main feedline using a 1/4" nut driver.
Pilot assembly
1/4” nut driver
Step 10. Visually inspect the spark igniter/flame sense wire for damage. Replace the pilot assembly, if damage is found.
Step 11. With a multi-meter set to the ohms setting, check continuity through the spark igniter/flame sense wire. Replace the pilot, if there is no continuity.
Multi-meter
Step 12. Visually inspect the spark igniter/flame sense electrode for deterioration. Replace the pilot assembly, if necessary. The electrode should not be in contact with pilot hood. If it is in contact with the pilot hood, carefully adjust electrode to a gap distance of 3/32" from the pilot hood.
Step 13. Visually inspect the spark igniter/flame sense electrode for oxidation build up. Carefully clean any oxidation using very fine emery cloth.
18
Page 18
Page 19
Blower Replacement
Pilot Inspection, Testing and Replacement (cont’d)
Step 14. Visually inspect the pilot tubing for kinks or cracks. If damage is found, replace the pilot assembly.
Step 15. Inspect the pilot tubing and pilot orifice for blockages:
a) Remove ferrule nut from the bottom of the pilot
assembly using a 7/16" wrench.
b) Remove the pilot tube and pilot orifice.
c) Inspect the pilot tubing and pilot orifice for
blockages. Clean or replace, as necessary.
Step 16. Reassemble the pilot assembly and install it on the main feedline. Reinstall the burner assembly into the combustion chamber. Restore the gas supply and check for gas leaks.
Step 17. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Blower Removal & Installation
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Page 19
19
Page 20
Blower Replacement
Blower Removal & Installation (cont’d)
Step 3. Disconnect the vent system from the draft hood that is mounted on top of the blower.
Vent system
Step 4. Remove the draft hood from the blower and retain it for use on the new blower.
Draft hood
Blower
Step 5. Unplug the cord sets from the blower.
Cord sets
Step 6. Remove the three blower mounting screws using a 1/4” nut driver and retain for later use.
1/4” nut driver
Blower
Step 7. Remove the blower from the top of the water heater.
Top of water
heater
Water heater tank flue
Step 8. Clean any debris from the jacket head of the water heater.
Step 9. Set the new blower in place using the water heater tank flue and the screw holes in the jacket head.
Step 10 Secure the blower in place using the screws from Step 6.
Step 11. Re-install the draft hood from Step 4.
Step 12. Reconnect the vent system to the draft hood.
Page 20
20
Page 21
Gas Control Testing & Replacement
Blower Removal & Installation (cont’d)
Step 13. Reconnect the cord sets from Step 5.
Step 14. Plug the water heater into the wall outlet.
Step 15. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Determine Water Temperature Inside Tank
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Draw approximately 4 gallons of water from the drain valve into a container and discard. Draw an additional gallon and immediately measure the water temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow heater to drain.
Step 3. Compare the measured water temperature with the setting on the gas control. In most instances, they should not differ by more than approx. 10°F.
WARNING
Stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.
Page 21
21
Page 22
Gas Control Testing & Replacement
Gas Control Removal
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Drain the water heater to a point below the gas control level.
Step 4. Turn off the gas supply to the water heater and disconnect the gas piping from the gas control.
Step 4. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Pilot and main feed-
lines
Step 5. Disconnect the wire harnesses and spark igniter/ flame sense wire from the gas control.
Gas control
Spark igniter/flame
sensor wire
Wire harnesses
Step 6. Spin the gas control out of the water heater tank.
Page 22
22
Page 23
120 VAC Circuit Trace
Flammable Vapor Sensor Testing
CAUTION
Do not use standard multi-meter probes for this testing. Doing so will damage the con­nector. Use special pin type electronic probes or small diameter wire pins inserted into connector.
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Disconnect the flammable vapor sensor / resettable thermal switch (FVS/ RTS) harness from the gas control.
Gas control power
switch
FVS/RTS harness
Step 3. Using a multi-meter set to the ohms setting, measure the resistance of the flammable vapor sensor.
Step 4. Using a multi-meter set to the ohms setting, measure the resistance of the resettable thermal switch (between the left two pins of the wire harness). The resistance must be between 3,000 and 48,000 ohms for both the switch and sensor. If the resistance is out of this range, verify that the resettable thermal switch has not been tripped. If it hasn’t, replace the thermal switch.
120 VAC Circuit Trace
Step 1. Verify 120VAC and proper polarity are at the wall outlet.
Step 2. With the water heater plugged in and the gas control power switch in the “ON” position verify LED status.
Page 23
23
Page 24
Diptube Inspection
Diptube Inspection and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the cold water supply to the water heater. Connect a hose to the drain valve of the water heater and route to an open drain. Open a nearby hot water faucet to vent the water heater for draining. Open the drain valve of water heater and allow the water heater to drain to a point below the inlet connection nipple.
Step 4. Disconnect the inlet nipple from the plumbing system.
Step 5. With an appropriate tool, such as a pipe wrench, remove the inlet nipple/ diptube from the water heater. Use caution not to damage pipe threads.
Step 6. Visually inspect the inlet nipple/diptube. The inlet nipple/diptube should be free of cracks and any blockage. Hydro-jet slots should be open and free of any blockage. Any damage, such as cracks, restriction due to deformation, or unintentional holes are not field repairable and the inlet nipple/diptube must be replaced.
Step 7. Upon completion of the inspection or subsequent replacement, reinstall the inlet nipple/diptube into the water heater. Ensure pipe dope is used on the nipple’s threads. Connect the nipple to the plumbing system, resume water supply to the water heater, refill the water heater and check for leaks.
Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
24
Page 24
Page 25
Anode Inspection
Anode Inspection and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the cold water supply to the water heater. Connect a hose to the drain valve of the water heater and route to an open drain. Open a nearby hot water faucet to vent the water heater for draining. Open the drain valve of water heater and allow the water heater to drain to a point below the outlet connection nipple.
Step 4. Disconnect the outlet nipple from the plumbing system.
Step 5. With an appropriate tool, such as a pipe wrench, remove the outlet nipple/anode from the water heater. Use caution not to damage the pipe threads.
Step 6. Visually inspect the outlet nipple/anode. The outlet nipple/anode should show signs of depletion, which is normal. If depletion is one-half the original anode diameter (approximately 3/4” diameter), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 7. Upon completion of the inspection or subsequent replacement, reinstall
WARNING
Water heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.
the outlet nipple/anode into the water heater. Ensure pipe dope is used on the nipple’s threads. Connect the nipple to the plumbing system, resume water supply to the water heater, refill the water heater, and check for leaks.
Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Remove the Blower to Gain Access to the Flue Baffle
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Page 25
25
Page 26
Anode Inspection
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Disconnect the vent system from the draft hood that is mounted on top of the blower.
Vent system
Draft hood
Blower
Step 4. Unplug the cord sets from the blower.
Cord sets
Step 5. Remove the (3) blower mounting screws using a 1/4” nut driver and retain for later use.
1/4” nut driver
26
Page 26
Page 27
Blower Removal
Remove the Blower to Gain Access to the Flue Baffle (cont’d)
Blower
Top of water
heater
Water heater tank flue
Step 6. Remove the blower from the top of the water heater.
Flue baffle
Step 7. Remove the flue baffle from the water heater.
Step 8. Inspect the baffle for deterioration and missing restrictors. Clean any scale or debris build-up. Replace with a new baffle, as necessary.
Step 9. Reinstall the baffle into the flue. Be sure the baffle hanger tab is inserted into the notch locations at the top of the flue.
Step 10. Check the burner to ensure no scale has accumulated during operation. See the Burner Cleaning Procedure on page 15, if accumulation has occurred.
Step 11. Secure the blower in place using the screws from Step 5.
Step 12. Reconnect the vent system to the draft hood.
Step 13. Reconnect the cord sets from Step 4.
Step 14. Plug the water heater into the wall outlet.
Step 15. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Page 27
27
Page 28
Inner Door Removal
Inner Door Removal Procedure
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Remove the outer door.
Outer door
Step 4. Remove (4) 1/4” hex drive screws from the right side inner door.
Page 28
(4) 1/4” hex drive
screws
Right side inner door
28
Page 29
Inner Door Removal
Inner Door Removal Procedure (cont.)
Step 5. Remove (2) 1/4” drive screws from the left side inner door.
Left side inner door
1/4” hex drive
screws
Step 6. Remove the connectors attached to the resettable thermal switch on the right side inner door.
Connectors attached to reset-
table thermal switch
Step 7. Inspect both inner doors for any of the following imperfections: tears, missing material, cracks, dirt or debris, lack of adhesion to the inner door, material left on combustion chamber, or any other imperfections that will inhibit a proper seal.
If any of the imperfections above are present, replace the inner door gasket following the Inner Door Gasket Replacement Procedure. If not, replacement of the inner door gaskets is not necessary.
Page 29
29
Page 30
Inner Door Gasket Replacement
Inner Door Gasket Replacement Procedure
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may re­sult causing property damage, personal injury, or death.
Step 1. Completely remove all gasket and adhesive residue from the right and left side inner doors, as needed.
Gasket Overlap must be as
shown + 1/32
Step 2. Using RTV sealant, apply a 1/8” bead to secure the inner door gasket to the inner door sections. Refer to the illustration for proper application. Note the overlap configuration in the flange area of the inner door. Set the flange section first, and this will help to achieve the proper overlap position.
Recommended pattern for RTV sealant
Gasket Overlap must be as
shown + 1/32
Enlarged
view of
flange area
Expanded view
30
Page 30
Page 31
Inner Door Installation
Inner Door Installation with Gasket
WARNING
Stripped fastener connections may allow for an inner door seal breach. A seal breach may result in a fire or explosion, causing property damage, personal injury, or death. Do not over tighten screws. If a fastener connection is stripped, contact the manufacturer listed on the water heater rating plate.
Step 1. Clean any residual gasket residue or other debris from the combustion chamber surface before installing the inner door/gasket assembly.
Step 2. Place the left side inner door into position first, being sure to firmly position the concave channel of the inner door around the feedline.
Step 3. Using the 1/4” hex drive screws removed in Step 5 of the Inner Door Removal Procedure on page 29, secure the left side inner door in place. Do not over­tighten the screws.
Step 3. Position the pilot tube and spark igniter wire against the left side inner door flange gasket. Do not route these through the concave channel with the feedline.
Step 4. Firmly place the right side inner door flange against the left side inner door flange.
Step 5. Using the 1/4” hex drive screws removed in Step 4 of the Inner Door Removal Procedure on page 29, secure the two flanges together. Do not over-tighten the screws.
Step 6. Align the right side inner door to the combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted openings. Verify seal integrity around the combustion chamber opening.
Step 7. Using the 1/4” hex drive screws removed in Step 4 of the Inner Door Removal Procedure on page 29, secure the right side inner door. Do not over-tighten the screws. Verify that both the left and right side inner doors are properly positioned and sealed against the combustion chamber.
Step 8. Re-install the outer door.
Step 9. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Page 31
31
Page 32
Pressure Switch Testing
Pressure Switch Testing & Replacement
Step 1. Move the gas control power switch to the “OFF” position.
Gas control power
switch
Step 2. Unplug the water heater from the wall outlet.
Blower (water heater)
power cord
Step 3. Unplug the cord sets from the blower.
Cord sets
Slotted screwdriver
Step 4. Using a slotted screwdriver, remove the (3) screws (one on the backside of the junction box is not shown) holding the end of the blower junction box on. Retain the screws for later use.
Blower junction box
Junction box screws
Step 5. Remove the pressure switch tubing from the pressure switch.
Pressure switch tubing
Step 6. Carefully pull out and lower the blower junction box cover.
Junction box cover
32
Page 32
Page 33
Pressure Switch Testing
Pressure Switch Testing & Replacement (cont’d)
Step 7. Using a slotted screwdriver, remove the (2) screws holding the pressure to the blower junction box. Retain the screws for later use.
Pressure switch screws
Step 8. Pull the pressure switch out of the junction box.
Pressure switch
Step 9. Using a multi-meter, check the resistance across the pressure switch terminals. There should be no electrical continuity, meaning the switch is open.
Multi-meter leads
Step 10. If the switch is open, check the pressure switch tubing and pressure tap on the switch for a blockage. Clear the blockage if one is present.
Step 11. If there is not a blockage, replace the pressure switch. Verify the switch setting of the replacement switch matches the original switch’s setting.
Step 12. Remove both terminals from the pressure switch..
Step 13. Connect both terminals to the new pressure switch.
Step 14. Place the pressure switch into the blower junction box.
Step 15. Align the pressure switch and install the (2) screws removed in Step 7.
Step 16. Re-install the blower junction box cover.
Step 17. Re-install the (3) screws removed in Step 4.
Step 18. Re-install the pressure switch tubing.
Step 19. Reconnect the cord sets from Step 3.
Step 20. Plug the water heater into the wall outlet.
Page 33
33
Page 34
Arrestor Cleaning
Pressure Switch Testing & Replacement (cont’d)
Step 21. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
ScreenLok® Flame Arrestor Cleaning Procedure
Step 1. Move the gas control power switch to the “OFF” position and unplug the water heater from the wall outlet.
Step 2. Remove the outer door.
Step 3. Remove the right side inner door per the Inner Door Removal Procedure on page 32.
Step 4. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 5. Disconnect the spark igniter/flame sensor wire from gas control.
Step 6. Remove the burner assembly from the combustion chamber.
Step 7. Clean the ScreenLok® flame arrestor using a stiff brush, compressed air, and/or a shop vacuum to remove any scale or other debris accumulation. Using a soft brush, clear jacket openings from any dirt, dust, restrictions, or other obstructions.
Step 8. Remove any debris from the burner assembly following the Burner Cleaning Procedure on page 15.
Step 9. Re-install the burner assembly.
Step 10. Reconnect the main and pilot tubing and spark igniter wire to the gas control.
Step 11. Re-install the inner door per the Inner Door Installation with Gasket Procedure on page 34.
Step 12. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
34
Page 34
Page 35
Common Terms
BTU British Thermal Units ECO Energy Cut Off GPM Gallons per Minute Hz Hertz KWh Kilowatts per hour LED Light Emitting Diode NPT National Pipe Thread Ohms Ohms of resistance PSI Pounds per Square Inch RPM Revolutions per Minute VAC Volts Alternating Current W.C. Inches of Water Column
°C Degrees Centigrade °F Degrees Fahrenheit
Common Terms
Page 35
35
Page 36
Parts List
36
Page 36
PART NAME AND DESCRIPTION
1. DraŌ Hood 15. Inner Door (Right)
2. Jacket Head Pan 15A. ReseƩable Thermal Switch
3. Jacket 16. Inner Door (LeŌ)
4. Blower 17. Blower Wire Harness
5. Heat Trap—Outlet 18. Feedline
6. Magnesium Anode–Hot Water Outlet 19. Gas Control Valve
7. Heat Trap—Inlet 20. Wire Harness (FVS / RTS)
8. Flue Baŋe Assembly 21. FVS Sensor Clip
9. Dip Tube–Cold Water Inlet 22. Flammable Vapor Sensor (FVS)
10. Temperature and Pressure Relief Valve 23. Outer Door
11. Glass Lined Tank 24. Steel Burner
12. CombusƟon Chamber Assembly 25. OriĮce
13. Jacket Base Pan 26. Pilot Assembly