Bradford-White EF-100T-199 User Manual

Page 1
Commercial Gas
Ultra High Efficiency Water Heater
he Ultra High Efficiency Water Heater Models Feature:
T
Thermal Efficiency Up To 99.1%.
0 Gallon Tank Capacity in 125,000, 150,000 and 199,999
6
BTU/hr Inputs
100 Gallon Tank Capacity in 150,000, 199,999, 250,000, 300,000
and 399,999 BTU/hr Inputs
Flexible V
Three Pass Flue System.
Low NOx Premix Power Burner.
Ultra Quiet Operation.
Submerged Combustion Chamber.
1" NPT Side Connection For Hydronic Applications.
Electronic Controls.
Zero Inch Clearance To Combustibles.
Vitraglas
Four Protective Magnesium Anode Rods (except EF-100T-399).
Powered Anode Rods (only EF-100T-399).
Hand Hole Cleanout—Allows inspection of tank interior.
Factory Installed Hydrojet
Factory Installed Dielectric Fittings.
Non-CFC Foam Insulation.
3" Optional Concentric Vent Kit.
ASME Construction Available.
NSF Construction A
Brass Drain Valve.
T&P Relief Valve Factory Installed.
Three Year Limited Warranty On Steel Tank.
One Year Limited Warranty On Parts.
Photo is of
EF-100T-199
enting—
®
Lined Tank.
Conventional, Thr
®
Sediment Reduction System.
ough-the-Wall or Direct Vent.
vailable With Optional Kit
800-B-1006-A
3 or 5-Year Limited Tank Warranties / 1-Year Limited Warranty on Component Parts.
For more information on warranty, please visit www.bradfordwhite.com
oducts installed in USA, Canada and Puer
For pr See complete copy of the warranty included with the heater.
TENTS:
ACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. P
MANUF
5,485,879; 5,277,171; (B1)5,341,770; 5,660,165; 5,596,952; 5,682,666; 4,904,428; 5,023,031; 5,000,893; 4,669,448; 4,829,983; 4,808,356; 5,115,767; 5,092,519; 5,052,346; 4,416,222; 4,628,184; 4,861,968; 4,672,919; Re. 34,534. OTHER U.S. AND FOREIGN PATENT APPLICATIONS PENDING. CURRENT CANADIAN PATENTS: 1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,112,515; 2,108,186; 2,107,012; 2,092,105.
itraglas
V
®
and Hydr
®
ojet
e registered trademarks of Bradford White
ar
A
7,063,133 B2; 5,954,492; 5,954,492; 5,761,379; 5,943,984; 5,081,696; 5,988,117; 6,142,216; 5,199,385; 5,574,822; 5,372,185;
®
Corporation.
©2006, Bradford White Corporation. All rights reserved. Printed in U.S.A.
to Rico. Some states do not allow limitations on warranties.
Page 2
Ultra High Efficiency Water Heaters
Intake/ Combustion Air
Rain Cap
Vent Exhaust
46 3/4"
Model
Number
EF-60T-125 EF-60T-150 EF-60T-199 EF-100T-150 EF-100T-199 EF-100T-250 EF-100T-300 EF-100T-399
Max. 3" PVC,
ABS & CPVC
120 ft. 100 ft.
80 ft. 120 ft. 100 ft.
80 ft.
60 ft.
50 ft.
Max. 4" PVC,
ABS & CPVC
170 ft. 150 ft. 130 ft. 170 ft. 150 ft. 130 ft. 110 ft. 100 ft.
eF Series®Standard Equipment Features:
Thermal Efficiency up to 99.1%—Fully condensing design.
Three Pass Flue System—The three pass flue system
keeps the hot combustion gases moving at a high velocity. The combination of high turbulence and velocity causes an enormous rate of heat transfer into the water.
Low NOx Premix Power Burner—Developed for the eFSeries combustion chamber. This turbulence causes a thorough mixing of the gas and air for optimum combustion and high heat transfer efficiencies. — Far exceeds California
mission requirements.
e
Submerged Combustion Chamber—Submerging the combustion chamber in the center of the water storage tank minimizes radiant heat loss and improves efficiency.
Non-CFC Foam Insulation—Surrounds the tank surface, saving energy by retarding loss of heat.
Electronic Controls—Adjustable electronic thermostat for control between 80°F and 180°F. The recycling Energy Cut Off (ECO) shuts off all gas flow in an event of an overheat condition.
Zero Inch Clearance—The eFSeries®jacket is cool to the touch and is approved for zero inch clearance to combustibles for unsurpassed installation flexibility.
Vitraglas®Lined Tank—Bradford White’s water heater tanks are protected from the corrosive effects of hot water by an exclusive ceramic porcelain-like coating. Our high silica Vitraglas Bradford White’s water heater tanks.
Protective Magnesium Anode Rods—Employed to provide an extra measure of corrosion protection for longer life. Each eF heater has 4 anodes, except the EF-100T-399 which has 2 powered anode rods and one non-powered anode rod.
Factory Installed Hydrojet®Sediment Reduction System—
stainless steel for increased durability. Helps prevent sediment build up in tank.
Factory Installed Dielectric Fittings—All heaters equipped with special water heater nipples for longer heater life. No special dielectric fittings to buy
®
, a turbulent flame shoots down the submerged
®
lining provides a tough interior surface for
Cold inlet sediment reduction device made of
Flexible Venting—The eF Series®can vent vertically or horizontally with either 3" or 4" PVC, CPVC or ABS vent
ipe, and is approved for direct vent closed combustion
p applications, or those applications that require inside air for
ombustion. Foam Core pipe is permitted on the entire
c venting system. The eF Series unbalanced venting, which means the air intake pipe doesn't have to be vented the same distance as the exhaust.
(NOTE: Air intake cannot exceed exhaust by more than 30 feet.)
Determining required vent length
1. Determine the total length of straight vent pipe (in feet)
required for both the intake and the exhaust.
2. Add 5 feet of venting for every 90˚ elbow.
3. Add 2 1⁄2 feet of venting for every 45˚ elbow.
4. Total vent length cannot exceed "Max Length" in the
above venting table.
5. Air intake cannot exceed exhaust by more than 30 feet
in any venting situation.
NOTICE: Do not include the 3" exhaust elbow or vent terminals in determining maximum vent length.
Three year limited warranty on steel tank —
gauge steel automatically formed, rolled and welded to assure a continuous seam for glass lining.
One year limited warranty on parts
®
is also approved for
Heavy
eF Series®Optional Equipment Features:
Maxitrol Gas Pressure Regulating valve—Ensures proper supply pressure to eF unit of 7" to 11" W.C.
ovided incoming pr
(pr This can be ordered as a separate part, or as part of the heater. For the separate part, please use p/n 243-45517-00 (not available for use with the EF-100T
-399).
Concentric Vent Terminal Kit—3" termination fitting
ovides for only one exit opening thr
pr (p/n 239-44069-01).
NSF Compliance Kit—p/n 265-44542-04.
essure is between 1/2 and 2 psi).
ough wall or r
oof
p/n 239-44069-01
Page 3
Ultra High Efficiency Water Heaters
NOTE: Diagrams are for both the 60 and 100 gallon models.
3
4" NPT Gas Inlet
1
1
2" NPT
Outlet
1
" NPT Space
H
eating Outlet
1" NPT Space Heating Return
1
1
2" NPT Inlet
3" PVC Exhaust
3" PVC Air Inlet
G
E
B
D
3" PVC EXHAUST
1
2" NPT CONDENSATE
CONNECTION
2
3
8"
F
A
C
H
T & P Valve
Cleanout
Drain
81⁄4
B
2
8
1
4
Gas Inlet
T & P Valve
8
1
4
E
xhaust
Air Intake
NATURAL GAS AND LIQUID PROPANE GAS
eF Series®Commercial Ultra High Efficiency Water Heater
Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed
Includes Installed T&P Valve and Electronic Ignition
Model
Number
F
Floor to
Vent
Outlet
in.
Approx.
Shipping
Weight
lbs.
E
Floor to
Gas
Conn.
in.
A
Floor to
Top of
Heater
in.
Input
BTU
1
ST
Hour Delivery at 100°F
Rise
Gal.
Stg.
Capacity
U.S. Gal.
Therm.
Eff.
%
D
Cold
In
in.
C HW Out
in.
B
Jacket
Dia.
in.
140°F100°F40°F
Recovery GPH
at Degree Rise
EF-60T-125E-3N(A) EF-60T-150E-3N(A) EF-60T-199E-3N(A) EF-100T-150E-3N(A) EF-100T-199E-3N(A) EF-100T-250E-3N(A) EF-100T-300E-3N(A) EF-100T-399E-3N(A)
125,000 150,000 199,999 150,000 199,999 250,000 300,000 399,999
★ ★ ★ ★ ★ ★ ★ ★
187 211 265 250 309 364 405 521
V V V V V V V V
364 423 558 450 597 735 836
1127
145 169 223 180 239 294 335 451
104 121 159 129 171 210 239 322
60 60
60 100 100 100 100 100
96.0
93.0
92.0
99.1
98.5
97.0
92.0
93.0
57 57
57 775/8 775/8 775/8 775/8 775/8
42 42 42 63 63 63 63 63
570 570 570 900 900 900 900 950
281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4
5 5 5 5 5 5 5 5
11/2 11/2 11/2 11/2 11/2 11/2 11/2 11/2
3
/4
3
/4
3
/4
3
/4
3
/4
3
/4
3
/4
1
3
/4
3
/4
3
/4
3
/4
3
/4 1 1 1
13 13 13 13 13 13 13 13
531/2 531/2 531/2 743/4 743/4 743/4 743/4 731/4
521/2 521/2 521/2 731/8 731/8 731/8 731/8 731/8
40 40 40 60 60 60 60 60
G
Floor to
Air
Intake
in.
H
Floor to
T&P
Conn.
in.
Gas
Conn.
Dia.
in.
Water Conn.
Dia.
in.
Relief Valve
Open
in.
Model
Number
F
Floor to
Vent
Outlet
mm.
Approx.
Shipping
Weight
kgs.
E
Floor to
Gas
Conn.
mm.
A
Floor to
Top of
Heater
mm.
InputkW1
ST
Hour
Delivery
at 56°C
Rise
Liters
Stg.
Capacity
Liters
Therm.
Eff.
%
D
Cold
In
mm.
C HW Out
mm.
B
Jacket
Dia.
mm.
78°C56°C22°C
Recovery LPH
at Degree Rise
EF-60T-125E-3N(A) EF-60T-150E-3N(A) EF-60T-199E-3N(A) EF-100T-150E-3N(A) EF-100T-199E-3N(A) EF-100T-250E-3N(A) EF-100T-300E-3N(A) EF-100T-399E-3N(A)
36.6
43.9
58.6
43.9
58.6
73.2
87.9
117.2
★ ★ ★ ★ ★ ★ ★ ★
708 799
1003
946 1170 1378 1533 1972
V V V V V V V V
1378 1601 3112 1703 2260 2782 3165 4266
545 640 844 681
905 1113 1268 1707
394 458 602 488 647 795 905
1219
227 227 227 379 379 379 379 379
96.0
93.0
92.0
99.1
98.5
97.0
92.0
93.0
1448 1448 1448 1972 1972 1972 1972 1972
1067 1067 1067 1600 1600 1600 1600 1600
259 259 259 408 408 408 408 431
718 718 718 718 718 718 718 718
128 128 128 128 128 128 128 128
38 38 38 38 38 38 38 38
19 19 19 19 19 19 19 25
19 19 19 19 19 25 25 25
330 330 330 330 330 330 330 330
1359 1359 1359 1899 1899 1899 1899 1861
1324 1324 1324 1857 1857 1857 1857 1857
994 994
994 1527 1527 1527 1527 1524
G
Floor to
Air
Intake
mm.
H
Floor to
T&P
Conn.
mm.
Gas
Conn.
Dia.
mm.
Water Conn.
Dia.
mm.
Relief Valve
Open
mm.
For pr Example: EF-100T-150-3X
V - 115V A.C. Required
- Listed with California Energy Commission
(A) ASME - All models are available with ASME construction. To order ASME construction add the (A) to the end of the model number. Example: EF-60T-125E-3NA
opane gas models change suf
onic Ignition
- Electr
fix “N” to “X” and r
emove “E” fr
om the model number.
The weight is the same for both ASME and Non-ASME models.
Note:
NSF Construction Available with optional kit
Complies with SCAQMD low NOx requirements — 10.39 ng/joule Design certified by CSA International (formerly AGA/CGA) Amp Draw range = 1.0 to 1.8 amps and 7.0 amps for EF-100T-399 150 PSI Working Pressure (1034 kPa), 300 PSI Test Pressure (2068 kPa)
Page 4
Ultra High Efficiency Water Heaters
All models are design certified by CSA International (formerly AGA/CGA) for up to 180°F (82°C) application as an Automatic Storage Heater, and an Automatic Circulating Tank Heater.
As an Automatic Storage Heater, all models are complete self-contained water heating systems. It needs no separate storage tank, pump, wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180°F (82°C) sanitizing and 140°F (60°C) general purpose hot water simultaneously. These models can be used either as a single unit or as multiples connected in parallel.
Sample Specification
The water heater shall be a Bradford White model EF-_____ with a rated storage capacity of not less than _____ gallons/ liters, a minimum gas input of __________ BTU/hr, a minimum recovery of _____ GPH/LPH at 100°F (56°C) temperature rise, and a Thermal Efficiency Rating of ____%. It shall be design certified by CSA International (formerly AGA and CGA) for 180°F (82°C) application, either with or without a separate storage tank. The tank shall be lined with Vitraglas enamel and shall have a bolted hand hole cleanout. The tank shall have four extruded magnesium anode rods installed in separate head couplings (up to 300,000 BTU/hr input) or two powered anode rods and one extruded magnesium anode rod (for 399,999 BTU/hr input). This water heater shall be equipped with stainless steel cold water inlet, Hydrojet Reduction System. The heater shall be insulated with Non-CFC foam. This water heater shall be equipped with an electronic ignition system, an ASME rated T&P relief valve and a premix closed combustion system for direct venting using either 3" (76mm) or 4" (102mm) PVC, CPVC or ABS vent pipe. (115V AC required). The water heater shall be factory assembled and tested. The water heater shall be approved for zero inch clearance to combustibles. The control shall be an adjustable electronic thermostat to any temperature up to 180°F (82°C). A recycling Energy Cut Off (E.C.O.) shuts off all gas in the event of an overheat condition. The entire installation shall be made in compliance with state and local codes and ordinances.
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
®
vitreous
®
Sediment
Sales 800-523-2931 ●Fax 215-641-1670 / Technical Support 800-334-3393 ●Fax 269-795-1089 ●Warranty 800-531-2111 ●Fax 269-795-1089
800-B-1006-A
For U.S. and Canada field service, contact your professional installer or local Bradford White sales representative.
national:
Inter
elephone
T
215-641-9400 ●T
echnical Support
Sales / T
©2006, Bradford White Corporation. All rights reserved.
elefax
Ambler, PA
215-641-9750 / Fax on Demand 888-538-7833 / www
866-690-0961 / 905-238-0100 ●Fax 905-238-0105 / www
.bradfordwhite.com
.bradfordwhitecanada.com
Printed in U.S.A.
Loading...