Bradford-White DS140S, DS150S User Manual

Page 1
DIRECT VENT GAS WATER HEATER
DS140S & DS150S
INSTALLATION & OPERATING
INSTRUCTION MANUAL
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s
INTERNET VERSION FOR REFERENCE ONLY
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
For your family’s comfort, safety and convenience we recommend Bradford White water heaters to be installed and serviced by a plumbing professional.
Page 2
You have just purchased one of the finest water heaters on the market today!
This installation, operation and instruction manual will explain in detail the installation and maintenance of your new Direct Vent Gas Water Heater. We at Bradford White strongly recommend that you contact a plumbing professional for the installation of this water heater.
We require that you carefully read this manual, as well as the enclosed warranty, and refer to it when questions arise. If you have any specific questions concerning your warranty, please consult the plumbing professional from whom your water heater was purchased. For your records we recommend that you write the model, serial number and installation date of your water heater in the maintenance section in the back of this manual.
This manual should be kept with the water heater.
INTERNET VERSION FOR REFERENCE ONLY
At Bradford White we’re committed to providing you with the finest water heater made.
CONGRATULATIONS!
Page 3
TABLE OF CONTENTS
page
GENERAL INFORMATION........................................................ 4
INSTALLATION
Locating The Water Heater...................................................... 6
Minimum Clearances................................................................. 9
Optional Direct Vent-Air Intake Terminal Guard.................... 9
Venting........................................................................................ 12
Horizontal and Vertical Vent-Air Intake Lengths ................... 14
Vent-Air Intake System Installation.......................................... 17
Water Connections.................................................................... 25
Gas Connections....................................................................... 29
GENERAL OPERATION............................................................ 30
Lighting and Shutdown Instructions....................................... 31
Thermostat Adjustment............................................................. 32
Burner Flame Checks ............................................................... 33
MAINTENANCE........................................................................... 34
PARTS LIST................................................................................. 37
PARTS LIST DRAWINGS
Direct Vent Water Hea ter.......................................................... 38
Vent-Air Intake Kits.................................................................... 39
INTERNET VERSION FOR REFERENCE ONLY
INSTALLATIONS FOR POTABLE WATER AND SPACE
HEATING....................................................................................... 40
Page 4
GENERAL INFORMATION
This gas -fired water heater’s design is certified by CSA International under the
American National Standard Z21.10.1 - (as indicated on the rating plate) and CSA 4.1-M - (as indicated on the rating plate).
This water heater must be installed in accordance with local codes or, in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest Edition) and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions). The warranty for this water heater is in effect only when the water heater is installed, adjusted, and operated in accordance with these Installation and Operating Instructions. The manufacturer will not be held liable for any damage resulting from alteration and/or failure to comply with these instruc tions.
This water heater is not design certified for installation in a mobile home. Such an installation may create a hazardous condition and will nullify the warranty.
This water heater has been designed and certified for the purpose of heating potable water. The installation and use of this water heater for any purpose other than the heating of potable water may cause damage to the water heater and create a hazardous condition and nullify the warranty.
CAUTION
Incorrect operation of this appliance may create a hazard to life and property and will nullify the warranty.
Do not use this appliance if any part has been submerged in water. You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water.
DANGER
Do not store or use ga soline or other flammable, combustible, or
INTERNET VERSION FOR REFERENCE ONLY
corrosive vapors and liquids in the vicinity of this or any other appliance.
Page 5
General Information continued -
IMPORTANT
Before proceeding, please inspect the water heater and its components for possible damage. DO NOT install any damaged components. If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts.
Make sure that you check the rating plate and combination gas control on the water heater to be certain that the type of gas being supplied corresponds with the marking on the rating plate and combination gas control.
A sacrificial anode is used to extend tank life. The removal of this anode, for any reason, will nullify the warranty. In areas where water is unusually active, an odor may occur at the hot water faucet due to a reaction between the sacrificial anode and the impurities in the water. If this should happen, an alternative anode may be purchased from the supplier that installed this water heater. This will minimize the odor while protecting the tank. Additionally, the water heater should be flushed with appropriate dissolvers to eliminate any bacteria.
INTERNET VERSION FOR REFERENCE ONLY
Page 6
INSTALLATION
LOCATING THE WATER HEATER
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent -air intake system. Use proper care to avoid unnecessary contact (especially by children) with the water heater and vent -air intake components. UNDER NO CIRCUMSTANCES
MUST FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
DO NOT install the water heater in any location where gasoline or flammable vapors are likely to be present.
Water Heaters in residential garages shall be installed so that all burner(s) and burner ignition device(s) are located not less than 18 inches (46 cm) above the floor and shall be located, or protected, to avoid physical damage. For other installations refer to local codes. In the absence of local codes, the water heater shall be installed in compliance with the National Fuel Gas Code, ANSI Z223.1 - (Latest Edition) and/or in Canada, CAN/CGA B149 Installation Codes (Latest Editions).
The location of this water heater is of the utmost importance. Before installing this water heater, read the installation section of these instructions. After reading these installation and operating instructions, select a location for the water heater where the floor is level and is easily accessible to gas and water supply lines. DO NOT locate the water heater where water lines could
be subjected to freezing temperatures. Make sure the cold water pipes are not located directly above the gas control so that condensate during humid weather does not drip on the controls.
INTERNET VERSION FOR REFERENCE ONLY
Page 7
Installation (Locating The Water Heater) co ntinued-
Water heater corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Examples of some typical compounds that are potentially corrosive are: spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes and process chemicals. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence. NOTE: DAMAGE TO THE WATER HEATER
CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY. DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR WILL OCCUR. DO NOT STORE ANY POTENTIALLY CORROSIVE COMPOUNDS IN THE VICINITY OF THE WATER HEATER.
WARNING
Liquefied petroleum gases/propane gas are heavier than air and will remain at floor level if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of leaking gas. Before lighting, smell all around the appliance area for gas. Be sure to smell next to the floor.
IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch; do not use any
telephone in your building.
Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
DO NOT OPERATE APPLIANCE UNTIL THE LEAKAGE IS
CORRECTED!
INTERNET VERSION FOR REFERENCE ONLY
Page 8
Installation (Locating The Water Heater) continued -
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural gas have
an odorant added by the gas supplier that aids in the detection of the gas.
Most people recognize this odor as a “sulfur” or “rotten egg” smell.
Other conditions, such as “odorant fade” can cause the odorant
to diminish in intensity, or ”fade”, and not be as readily detectable.
If you have a diminished sense of smell, or are in any way unsure
of the presence of gas, immediately contact your gas supplier
from a neighbor’s telephone.
Gas detectors are available. Contact your gas supplier, or
plumbing professional, for more information.
The water heater must be located close enough to the outside wall to keep the venting distance within the maximum distance described in the installation instructions. Note: The direct vent -air intake terminal must be installed on a vertical wall. Read the venting section in this installation instruction manual before locating the water heater.
This water heater must be located in an area where leakage of the tank or water line connections and the combination temperature and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure. When such locations cannot be avoided, a suitable drain pan, adequately drained, be installed under the water heater. The pan must not restrict combustion airflow. The drain pan must be no greater than 1-½ inches (3.8 cm) deep and have a minimum length and width of at least four (4) inches (10.2 cm) measured from the jacket of the water
INTERNET VERSION FOR REFERENCE ONLY
heater. The drain pan, as described above, can be purchased from your plumbing professional. The drain pan must be piped to an adequate drain. The piping must be at least 3/4 inch (1.9 cm) in diameter and pitched for proper drainage.
It is recommended that a minimum clearance of four (4) inches (10.2 cm) be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve.
Page 9
Installation continued -
MINIMUM CLEARANCES
WARNING
Failure to adhere to these installation and operating instructions may create a hazard to life and property and will nullify the warranty.
This installation shall allow access to the front of the water heater and adequate clearance shall be provided for servicing and operating this water heater. The water heater may be installed on either a combustible or non-combustible floor. If the water heater is to be installed directly on carpeting, it shall be installed on top of a metal or wood panel extending beyond the full width and depth of the appliance by at least three (3) inches (7.6 cm) in any direction or, if the appliance is to be installed in an alcove or closet, the entire floor shall be covered by the panel. The minimum clearances to combustibles for this water heater is: zero (0) inch (0 cm) from the sides and rear, four (4) inches (10.2 cm) from the front of the jacket, zero (0) inch (0 cm) from the plenum, zero (0) inch (0 cm) from the air intake elbow and telescopic tubes and twelve (12) inches (30.5 cm) from the direct vent -air intake terminal. (See Figure 1).
OPTIONAL DIRECT VENT-AIR INTAKE TERMINAL GUARD
WARNING
The direct vent-air intake terminal is HOT while the water heater is in operation. Do not touch. Keep children, combustibles, gasoline and other liquids having flammable vapors away.
It is recommended that a vent -air intake terminal guard be installed when the vent-air intake terminal is located where it can be touched accidentally, or accessed by children. (See Figure 2).
INTERNET VERSION FOR REFERENCE ONLY
A chain link or louvered fence may be used instead of the vent -air intake terminal guard. Maintain proper clearances as specified in this instruction manual to the vent -air intake terminal. (See Figure 3).
Page 10
Installation (Minimum Clearances) continued -
Figure 1
INTERNET VERSION FOR REFERENCE ONLY
Page 11
Installation continued -
Figure 2
INTERNET VERSION FOR REFERENCE ONLY
Figure 3
Page 12
Installation continued -
VENTING
This is a Direct Vent Gas Water Heater where all air for combustion is obtained from the outside atmosphere and all flue gases are discharged to the outside atmosphere.
WARNING
The vent-air intake system must be properly installed. Failure to properly install the vent-air intake system properly could result in property damage, personal injury or death.
DO NOT install any damaged vent-air intake system components. Contact the manufacturer of the water heater for replacement parts.
Direct Vent-Air Intake Terminal (See Figure 4)
Shall be installed with at least a 9 in. (22.9 cm) vent termination clearance from any air opening into a building.
The bottom of the direct vent -air intake terminal shall be located at least 12 in. (30.5 cm) above grade.
Installed at least 3 ft. (91.4 m) from any gas meter, gas valve or other gas regulating equipment.
Must be installed in a location where it will not be blocked by snow.
Note: Provide protection of the building materials from degradation by flue gases from the direct vent -air intake terminal.
Exceptions for Installations in Canada The direct vent -air intake terminal shall not terminate: (a) directly above a paved sidewalk or paved driveway which is located between two single-family dwellings and serves both dwellings; (b) less than 7 ft. (2.1 m) above a paved sidewalk or a paved driveway located on public property;
INTERNET VERSION FOR REFERENCE ONLY
(c) within 6 ft. (1.8 m) of a mechanical air supply inlet to any building; (d) above a gas meter/ regulator assembly within 3 ft. (91.4 cm) horizontally
of the vertical centerline of the regulator; (e) within 6 ft. (1.8 m) of any gas service regulator vent outlet; (f) less than 12 in. (30.5 cm) above grade level; (g) within 12 in. (30.5 cm) of a window or door which can be opened in any
building, any non-mechanical air supply inlet to any building or the
combustion air inlet of any other appliance:
Page 13
Installation (Venting) continued -
(h) underneath a verandah, porch or deck, unless: (i) the verandah, porch or deck is fully open on a minimum of two
sides beneath the floor, and
(ii) the distance between the top of the vent-air intake termination and
the underside of the verandah, porch or deck is greater than 12 in. (30.5 cm).
Figure 4
INTERNET VERSION FOR REFERENCE ONLY
Page 14
Installation (Venting) continued -
The co-axial vent -air intake tubes of this water heater can be installed in any 360° configuration as long as the proper clearances for installation, plumbing, operation and servicing are maintained. (See Figure 5).
Figure 5
Note: Maintain proper clearances for installation, plumbing, operation
and service.
INTERNET VERSION FOR REFERENCE ONLY
HORIZONTAL AND VERTICAL VENT-AIR INTAKE LENGTHS
This Direct Vent Gas Water Heater comes with one (1) vent -air intake “Kit C”. Optional vent -air intake kits are available that can extend the horizontal length and/or vertical height of the vent -air intake system. Table A lists the various vertical and horizontal vent -air intake system configurations.
Page 15
Installation (Horizontal and Vertical Vent-Air Intake Lengths) continued -
13 1/4
15
22 1/4
36
58 5/16
order
order
add'l
order
order
14 3/4
*order
order
order
order
order
16 1/2
order
*order
order
order
order
23 3/4
order
order
order
*order
order
37 1/2
order
order
*order
*order
order
59 13/16
order
order
order
order
*order
The water heater is shipped with the following standard vent and air intake system: 239-41097-00. The components of this vent and air intake systems is as follows:
3” Vent Tube* Vent Terminal Hardware 5” Air Intake Tube* RTV Silicone Sealant Vent Terminal 3” Vent Elbow Inner Wall Term. Mounting Flange 5” Vent Elbow Outer Wall Term. Mounting Flange
*The vent and air intake telescopes from 13 3/4" to 23 11/16”.
Table A
Horizontal "X"
Vertical "Y"
10
15 11/16
19 3/16
33 11/16
57 3/8
105 13/16
14 3/16
kit A
kit A (2)
kit A & B
kit A
kit A & C
kit D & A
17 11/16
kit B
kit A & B
kit B (2)
kit B
kit C & B
kit D & B
32 3/16
no kit req'd
kit A
kit B
kit C
kit C (2)
kit D
55 7/8
kit C
kit A & C
kit B & C
kit C (2)
kit C (3)
kit D & C
104 5/16
kit D
kit A & D
kit B & D
kit D
kit C & D
kit D (2)
* (2) = Order two of the kits referenced.
INTERNET VERSION FOR REFERENCE ONLY
* (3) = Order three of the kits referenced. The bold text above show what kit(s) are needed in addition to the standard
vent and air intake tubes. If the standard vent and air intake tubes are not used in the venting system (those that do not have bold text) they can be discarded or saved.
Page 16
Installation (Horizontal and Vertical Vent-Air Intake Lengths) continued -
Figure 6
INTERNET VERSION FOR REFERENCE ONLY
Page 17
Installation continued -
VENT-AIR INTAKE SYSTEM INSTALLATION
WARNING
The vent-air intake system must be properly installed. Failure to properly install the vent-air intake system could result in property damage, personal injury or death.
Do not install any damaged vent-air intake system components. Contact the manufacturer of the water heater for replacement parts.
IMPORTANT
When the following instructions specify, to seal a vent-air intake joint, use only Loctite Ultra Blue 587 RTV Silicone sealant. A tube of Loctite Ultra Blue 587 RTV Silicone sealant is supplied with every direct vent water heater and each optional vent-air intake kit. Make sure that all joints are completely sealed.
When drilling pilot holes for the #8 sheet metal screws through the five (5) inch (12.7 cm) diameter components, be careful not to drill into the inner three (3) inch (7.6 cm) diameter components.
Tools Required For Vent-Air Intake Installation
The following minimum tools are required to properly install the vent­air intake system. Note: Wall construction will determine tool usage.
Tape Measure Drill 3/16 inch Diameter Drill Bit(s) 1/8 inch Diameter Drill Bit(s) Masonry Drill Bit(s) (For Poured Concrete, Concrete Block and Brick Wall Construction) Reciprocating Saw w/appropriate Blade(s) (Dependent on Wall
INTERNET VERSION FOR REFERENCE ONLY
Construction)
Chisel (For Poured Concrete, Concrete Block and Brick Wall Construction) Hammer (For Poured Concrete, Concrete Block and Brick Wall
Construction)
1/4 & 5/16 inch Nut Drivers (Preferred) or Slotted Head Screwdriver Phillips Head Screwdriver
Page 18
Installation (Vent-Air Intake System Installation) continued-
Figure 7
1. Measure the vertical height “Y” required in your installation. (See Figure
6). Reference the appropriate Table A to determine number of vent -air
intake kits required in your installation.
2. Measure the horizontal length “X” required in your installation (See Figure
6). Reference Table A to determine number of vent -air intake kits required
in your installation.
3. Cut a 5-1/2 inch (14 cm) diameter minimum clearance hole in the wall at
the point where the vent -air intake tubes will pass through the outside wall
and connect with the direct vent -air intake terminal (See Figure 6).
4. From outside the building, position the outer wall mount plate and direct
vent-air intake terminal over the center of the opening. Mark the mounting
screw hole locations. With a 3/16 inch diameter drill bit (not supplied), drill
holes for the wall anchors (supplied). Install the wall anchors but DO NOT
affix the outer wall mount plate and direct vent -air intake terminal to the
wall at this time (See Figure 7). Note: Certain construction of walls may
require the use of a different type of wall anchoring means than supplied.
DO NOT modify the direct vent -air intake terminal or outer wall mount
plate.
INTERNET VERSION FOR REFERENCE ONLY
Page 19
Installation (Vent-Air Intake System Installation) continued -
IMPORTANT
The following instructions detail the installation of the standard horizontal vent-air intake kit supplied with the water heater.
5. Insert the straight end of the three (3) inch (7.6 cm) diameter elbow into
the flue reducer until firmly seated and oriented in the correct direction.
With a 1/8 inch diameter drill bit (not supplied), drill three (3) holes, 120o
apart, through the flue reducer into the three (3) inch (7.6 cm) diameter
elbow. Fasten with three (3) #8 sheet metal screws (supplied). Using the
supplied special RTV silicone sealant, apply a sufficient amount to seal
the joint (See Figure 8).
INTERNET VERSION FOR REFERENCE ONLY
6. Place the straight end of the five (5) inch (12.7 cm) diameter elbow over the
three (3) inch (7.6 cm) diameter elbow and plenum collar until seated on
top of the plenum box. Make certain that the five (5) inch (12.7 cm)
diameter elbow is oriented in the same direction as the three (3) inch (7.6
cm) diameter elbow and both are oriented in the correct direction. Drill
three (3) 1/8 inch diameter holes, 120o apart, through the five (5) inch (12.7
cm) diameter elbow into the plenum collar. Fasten with three (3) #8 sheet
metal screws (supplied) (See Figure 9).
Figure 8
Page 20
Installation (Vent-Air Intake System Installation) continued -
Figure 9
7. Extend the three (3) inch (7.6 cm) diameter telescopic tube to its
maximum length and slide the backing plate over it. Place the large end of
the three (3) inch (7.6 cm) diameter telescopic tube through the hole in the
outside wall. Insert the smaller end of the three (3) inch diameter (7.6 cm)
telescopic tube into the flared end of the three (3) inch (7.6 cm) diameter
elbow, one (1) inch (2.5 cm) (or until seated). Drill three (3) 1/8 inch
diameter holes, 120o apart, through the three (3) inch (7.6 cm) diameter
elbow into the three (3) inch (7.6 cm) diameter telescopic tube. Fasten
with three (3) #8 sheet metal screws (supplied). Adjust the overall length
of the three (3) inch (7.6 cm) diameter telescopic tube so that 2-1/2 inches
INTERNET VERSION FOR REFERENCE ONLY
(6.4 cm) extends beyond the outside wall. Drill three (3) 1/8 inch diameter
holes, 120o apart, through the three (3) inch (7.6 cm) diameter telescopic
tubes where the small and large sections overlap. Fasten with three (3) #8
sheet metal screws (supplied). Using the supplied special RTV silicone
sealant, apply a sufficient amount to seal the joints (See Figure 10).
Page 21
Installation (Vent-Air Intake System Installation) continued -
Figure 10
8. Extend the five (5) inch (12.7 cm) diameter telescopic tube to its maximum
length. Place the large end of the five (5) inch (12.7 cm) diameter
telescopic tube over the collar on the outer wall mount plate. Drill three (3)
1/8 inch diameter holes, 120o apart, through the five (5) inch (12.7 cm)
diameter telescopic tube into the collar on the outer wall mount plate.
Fasten with three (3) #8 sheet metal screws (supplied). Using the
supplied special RTV silicone sealant, apply a sufficient amount to seal
the joint (See Figure 11).
INTERNET VERSION FOR REFERENCE ONLY
Figure 11
Page 22
Installation (Vent-Air Intake System Installation) continued -
9. From outside the building, slide the five (5) inch (12.7 cm) diameter
telescopic tube through the opening in the wall until the outer wall mount
plate is flush with the wall (See Figure 12).
Figure 12
10. Using the supplied special RTV silicone sealant, apply a bead one (1)
inch (2.5 cm) from the end of the three (3) inch (7.6 cm) diameter tube that is part of the vent -air intake terminal. Slide the direct vent-air intake terminal into the three (3) inch (7.6 cm) diameter telescopic tube that
INTERNET VERSION FOR REFERENCE ONLY
extends through the wall and position it so it is flush with the outer wall mount plate. Make sure that the rain guard and the word “HOT” on the end of the direct vent -air intake terminal are oriented properly. Secure the direct vent -air intake terminal to the outer wall mount plate and wall with four (4) #10 x 1 inch screws (supplied) (See Figure 13). Note: Certain construction of walls may require the use of different type of anchoring means than supplied. DO NOT modify the direct vent -air intake terminal or outer wall mount plate.
Page 23
Installation (Vent-Air Intake System Installation) continued -
Figure 13
11. From inside the building, slide the backing plate over the five (5) inch
(12.7 cm) diameter telescopic tube until it is flush with the wall. Adjust the length of the five (5) inch (12.7 cm) diameter telescopic tube and insert the end into the flared end of the five (5) inch (12.7 cm) diameter elbow one (1) inch (2.5 cm) (or until seated). Drill three (3) 1/8 inch diameter holes, 120o apart, through the five (5) inch (12.7 cm) diameter elbow into the five (5) inch (12.7 cm) diameter telescopic tube and through the tubes where the small and large sections overlap. Fasten with three (3) #8 sheet metal screws (supplied). Using the supplied special RTV silicone sealant, apply a sufficient amount to seal all joints (See Figure 14).
INTERNET VERSION FOR REFERENCE ONLY
Figure 14
Page 24
Installation (Vent-Air Intake System Installation) continued -
12. Mark the mounting screw hole locations for the backing plate. Rotate the
backing plate in order to gain access to the markings. With a 3/16 inch diameter drill bit (not supplied), drill holes for the supplied wall anchors. Install the wall anchors and secure the backing plate to the wall with four (4) #10 x 1 inch screws (supplied) (See Figure 15). Note: Certain construction of walls may require the use of a different type of anchoring means than supplied.
Figure 15
IMPORTANT
INTERNET VERSION FOR REFERENCE ONLY
When the installation is complete, visually inspect the air intake system to insure that all joints are completely sealed.
Page 25
Installation continued -
WATER CONNECTIONS
Note: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY VALVE.
After shutting off the main water supply, open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater. After the pressure has been relieved, close the faucet. Th e COLD water inlet and HOT water outlet are identified on the top of the water heater. The fittings at the cold water inlet and hot water outlet are dielectric waterway fittings with 3/4” NPT male thread. Make the proper plumbing connections between the water heater and the plumbing system to the house. Install a shut -off valve in the cold water supply line.
CAUTION
If sweat fittings are to be used, DO NOT apply heat to the nipples on top of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner.
INTERNET VERSION FOR REFERENCE ONLY
Page 26
WARNING
For protection against excessive temperatures and pressure, install temperature and pressure protective equipment required by local codes, but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspec tion of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 and the Standard CAN1-4.4 Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves . The combination temperature and pressure relief valve shall be marked with a maximum set pressure not to exceed the maximum working pressure of the water heater. The hourly BTU discharge capacity or the rat ed steam relief capacity of the combination temperature and pressure relief valve shall not be less than the input rating of the water heater.
Install the combination temperature and pressure relief valve into the opening provided and marked for this purpose on the water heater.
Note: Some models may already be equipped or supplied with a combination temperature and pressure relief valve. Verify that the combination temperature and pressure relief valve complies with local codes. If the combination temperature and pressure relief valve does not comply with local codes, replace it with one that does. Follow the installation instructions above on this page.
Install a discharge line which terminates six (6) inches (15 cm) above the floor, or any distance below the structural floor, to the outlet of the combination temperature and pressure relief valve. DO NOT allow water from the discharge line to contact any live electrical part. The discharge line is to be installed to allow for complete drainage of bot h the combination temperature and pressure relief valve and the discharge line. The water from the discharge line must be directed to a suitable drain or area that will not be damaged by water (Refer to page 6 “LOCATING THE WATER HEATER.” The discharge opening must not be subjected to blockage or freezing. DO NOT thread, plug or cap the discharge line.
It is recommended that a minimum clearance of four (4) inches (10.2 cm)
INTERNET VERSION FOR REFERENCE ONLY
be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve.
Do not place a shutoff valve between the combination temperature and pressure relief valve and the water heater, or on discharge pipes between such valves or the atmosphere.
Page 27
Installation (Water Connections) continued -
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4” TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM WHICH MIGHT RESULT FROM EXCESSIVE TEMPERATURES AND PRESSURES.
If this water heater is installed in a closed water supply system, such as the one having a back-flow preventer in the cold water supply, provisions shall be made to control thermal expansion. DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion. Your water supplier or local plumbing inspector should be contacted on how to control this situation
After installation of the water lines, open the main water supply valve and fill the water heater. While the water heater is filling, open several hot water faucets to allow air to escape from the water system. When a steady stream of water flows through the faucets, close them and check all water connections for possible leaks. NEVER OPERATE THE WATER HEATER WITHOUT
FIRST BEING CERTAIN IT IS FILLED WITH WATER.
WARNING
Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.
INTERNET VERSION FOR REFERENCE ONLY
This water heater can deliver scalding temperature water at any faucet in the system. Be careful whenever using hot water to avoid scalding injury. Certain appliances such as dishwashers and automatic clothing washers may require increased temperature water. By setting the thermostat on this water heater to obtain the increased temperature water required by these appliances, you may create the potential for scald injury. To protect against injury, you should install an ASSE approved mixing valve in the water system. This valve will reduce point of discharge temperature by mixing cold
Page 28
Installation (Water Connections) continued -
and hot water in branch supply lines. Such valves are available from the manufacturer of this water heater or a local plumbing supplier. Please consult with a plumbing professional.
INTERNET VERSION FOR REFERENCE ONLY
Page 29
GAS CONNECTIONS
The gas supply lines must meet all requirements of the National Fuel Gas Code, ANSI Z223.1 - (Latest Edition) and/or in Canada, CAN/CGA B149 Installation Codes - (Latest Editions).
The minimum permissible gas supply pressure for the purpose of input adjustment is one (1.0) inch (.25kPa) water column above the operating manifold pressure. See the rating plate and combination gas control for the manifold pressure and gas type. The maximum permissible gas supply pressure is fourteen (14.0) inches (3.5kPa) water column for natural gas and liquefied petroleum gases/propane gas.
1. Connect this water heater only to the type of gas (natural or propane gas) as shown on the rating plate. Use clean 1/2 inch black iron pipe. (Dirt and scale from the pipe can enter the combination control and
cause it to malfunction). The inlet gas line must have a drip leg (sediment
trap) installed as close as possible to the water heater’s combination gas
control having a minimum length of three (3) inches (7.6 cm). A ground
joint union must be installed in the gas supply line feeding the water heater
to permit servicing of the water heater. Compounds used on the threaded
joints of the gas piping must be resistant to the action of liquefied
petroleum gases/propane gas.
2. This water heater and its gas connection must be leak tested before placing the water heater in operation. Check for gas leaks with a soap and water solution and a brush or a commercial leak detector fluid. NEVER USE A MATCH OR OPEN FLAME FOR TESTING!
CAUTION
The water heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa). The water heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5 kPa). The supply line must be
INTERNET VERSION FOR REFERENCE ONLY
capped when not connected to the water heater.
Page 30
GENERAL OPERATION
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent -air intake system. Use proper care to avoid unnecessary contact (especially by children) with the water heater and vent -air intake system. UNDER NO
CIRCUMSTANCES MUST FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
TO FILL THE WATER HEATER
1. Close the water heater drain valve by turning the knob clockwise.
2. Open the cold water supply shut -off valve.
3. Open several hot water faucets to allow air to escape from the system.
4. When a steady stream of water flows from the faucets, the water heater is
filled. Close the faucets and check for water leaks at the water heater
drain valve, combination temperature and pressure relief valve and the hot
and cold water connections. TO DRAIN THE WATER HEATER
Should it become necessary to completely drain the water heater, make sure you follow the steps below:
1. Rotate the thermostat dial clockwise to the “PILOT LIGHTING” position.
2. Rotate and partially depress gas control knob clockwise to the “OFF”
position.
3. Shut off the gas supply to the water heater.
4. Close the cold water supply shut -off valve.
5. Open the drain valve on the water heater by turning the knob counter-
clockwise. The drain valve has threads on the end that will allow the
connection of a standard hose coupling.
6. Open a hot water faucet to allow air to enter the system.
INTERNET VERSION FOR REFERENCE ONLY
To refill the water heater, refer to “To Fill the Water Heater.”
Page 31
INTERNET VERSION FOR REFERENCE ONLY
Page 32
General Operation continued -
THERMOSTAT ADJUSTMENT
The thermostat dial is set to its lowest temperature setting when shipped from the factory. Remember that lower temperature settings are more energy efficient. Adjust the temperature by turning the thermostat dial. It is suggested that the starting point setting not be greater than the “ ” mark on the thermostat dial (approximately 120°F [49°C]) as indicated below. Rotate the thermostat dial clockwise Rotate the thermostat dial counterclockwise temperature setting. Adjust the dial until the minimum acceptable temperature is achieved (See figure below for approximate temperature settings).
to increase the temperature setting.
to decrease the
Figure 16
Hotter water increases the risk of scald injury. Scalding may occur within five (5) seconds at a temperature setting of 135° F (57° C). To protect against hot water injury, install an ASSE approved mixing valve in the water system. This valve will reduce point of discharge temperature by mixing cold and hot water in branch water lines. A licensed plumbing professional or local plumbing authority should be consulted.
Note: This water heater is equipped with an energy cut out device to prevent overheating. Should overheating occur or the gas supply fail to
INTERNET VERSION FOR REFERENCE ONLY
shut off, turn off the manual gas control valve to the appliance and call a qualified service technician.
Note: Whenever the water heater is filled with cold water, condensate will form on the cool tank surface and drops of water will fall on the hot burner and combustion chamber surfaces producing a “sizzling” noise. Condensation is normal and does not indicate a leak. It will disappear when the tank becomes heated.
DANGER
Page 33
General Operation continued -
BURNER FLAME CHECKS
At the time of installation and at periodic intervals (not more than six (6) months), a visual check of the pilot and main burner flames should be conducted. The flames should be similar to those pictured below. The main burner should light smoothly from the pilot. (See Figure 17).
INTERNET VERSION FOR REFERENCE ONLY
Figure 17
Page 34
MAINTENANCE
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent -air intake system. Use proper care to avoid unnecessary contact (especially by children) with the wat er heater and vent-air intake system. UNDER NO
CIRCUMSTANCES MUST FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
IMPORTANT
The water heater should be inspected at a minimum annually by a qualified service technician for damaged components and/or joints not sealed. DO NOT operate this water heater if any part is found damaged or if any joint is found not sealed.
The following maintenance should be performed by a qualified service technician at the minimum periodic intervals suggested below. In some installations the maintenance interval may be more frequent depending on upon the amount of use and the operating conditions of the water heater. Regular inspection and maintenance of the water heater and vent -air intake system will help to insure safe and reliable operation.
1. Annually check the operation of the thermostat.
2. The flow of combustion and ventilation air MUST NOT be restricted.
Annually inspect the direct vent -air intake terminal to insure it is not
blocked or damaged. Clear the direct vent -air intake terminal openings of
any dirt, dust, or other restrictions. WARNING! Certain areas of the
direct vent -air intake terminal are HOT.
INTERNET VERSION FOR REFERENCE ONLY
3. Annually inspect the vent -air intake system to insure that all components
are securely fastened and all joints and seams are properly sealed.
4. At all times keep the water heater area clear and free from combustible
materials, gasoline and other flammable vapors and liquids.
5. Bi-annually conduct a visual check of the main and pilot burner flames to
determine that they are burning properly. See information on page 33
“BURNER FLA ME CHECKS.”
Page 35
Maintenance continued -
6. Annually remove the inner door and main burner assembly to clean orifices
and related parts of any dirt or other foreign material. Inspect the burner
ports for obstructions or debris and clean with a wire brush as needed.
Wire brush and/or vacuum clean the combustion chamber as needed to
remove scale deposits and debris. Inspect the inner door gasket for wear
and tear and replace if necessary. NOTE: It is imperative for proper
operation of the water heater that the inner door be properly sealed.
7. At least once a year, check the combination temperature and pressure
relief valve to insure that the valve has not become encrusted with lime.
Lift the lever at the lever at the top of the valve several times until the valve
seats properly without leaking and operates freely.
WARNING
When lifting lever of the combination temperature and pressure relief valve, hot water will be released under pressure. Be careful that any released water doe s not result in bodily injury or property damage.
8. Monthly, drain off a gallon of water to remove silt and sediment by using
the water heater’s drain valve.
WARNING! THIS WATER MAY BE HOT.
9. If the combination temperature and pressure relief valve on the appliance
discharges periodically, this may be due to thermal expansion in a closed
water supply system. Contact the water supplier or local plumbing
inspector on how to correct this situation. Do not plug the combination
temperature and pressure relief valve outlet.
10. A combination sacrificial anode rod/hot water outlet nipple has been
installed to extend tank life. The anode rod should be inspected
periodically (every two years) and replaced when necessary to prolong
tank life. Contact the plumbing professional who installed the water heater
INTERNET VERSION FOR REFERENCE ONLY
or the manufacturer listed on the rating plate for anode replacement
information. The use of a water softener may increase the speed of anode
consumption. More frequent inspection of the anode is needed when
using softened (or phosphate treated) water.
Maintenance (continued)-
Page 36
CAUTION
FOR YOUR SAFETY. DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL, BURNERS OR GAS PIPING. REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN.
Contact your supplier or plumbing professional for replacement parts or contact the company at the address given on the rating plate of the water heater.
Provide the part name, model and serial numbers of the water heater when ordering parts.
READ THE WARRANTY FOR A FULL EXPLANATION OF THE LENGTH OF TIME THAT PARTS AND THE WATER HEATER ARE WARRANTED.
Manufactured under one or more of the following U.S. Patents: 4,416,222; 4,628,184; 4,669,448; 4,672,919; 4,808,356; 4,829,983; 4,861,968; 4,867,106; 4,904,428; 5,000,893; 5,023,031; 5,052,346; 5,081,696; 5,092,519; 5,115,767; 5,199,385; 5,277,171; 5,341,770; 5,372,185; 5,485,879; 5,574,822; 5,596,952; 5,660,165; 5,682,666; 5,943,984. Other U.S. and Foreign patent applications pending. Current Canadian Patents: 1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,107,012; 2,108,186; 2,112,515.
Complete the following information and retain for future reference: Model No: Serial No : Installation Date: Service Phone No. Days: Nights:
INTERNET VERSION FOR REFERENCE ONLY
Address: Supplier: Supplier’s Phone No:
PART NAME & DESCRIPTION
Page 37
1. Direct Vent-Air Intake Terminal 21. Piezo Ignitor Assembly
2. Outer Wall Mount Plate 22. Drain Valve
3. Backing Plate 23. Outer Door
4. Five (5) inch (12.7 cm) Diameter Telescopic Air Intake Tube
5. Three (3) inch (7.6 cm) Diameter Telescopic Vent Tube
6. Five (5) inch (12.7 cm) Diameter Elbow
7. Three (3) inch (7.6 cm) Diameter Elbow
8. Plenum 28. Pilot Assembly w/Electrode
9. Plenum Gasket 29. Gas Feed Line (Burner)
10. Flue Reducer 30. Main Burner Orifice
11. Jacket Top 31A. 42 Port Steel Burner
12. Insulation 31B. 65 Port Cast Iron Burner
13. Glass Lined Tank 32. Radiation Shield
14. Flue Baffle Assembly 33A. Direct Vent -Air Intake Kit A
15. Dip Tube & Nipple 33B. Direct Vent -Air Intake Kit B
16. Anode Rod & Nipple 33C. Direct Vent -Air Intake Kit C
17. Temperature-Pressure Relief Valve (Certain Models)
18. Air Intake Tube 33E. Direct Vent -Air Intake Kit E
19. Combustion Chamber Assembly
20. Combination Gas Control w/E.C.O.
INTERNET VERSION FOR REFERENCE ONLY
Note: Provide the part name, model and serial numbers of the water heater when ordering parts.
24. Jacket
25. Inner Door Assembly
26. Air Intake Boot
27. Air Intak e Boot Gasket
(Certain Models)
(Optional)
(Optional)
(Supplied & Optional)
33D. Direct Vent -Air Intake Kit D
(Optional)
(Optional)
34. Loctite Ultra Blue 587 RTV Silicone Sealant
35. Direct Vent -Air Intake Terminal Guard (Optional)
THIS MANUAL SHOULD BE KEPT WITH THE WATER HEATER
Page 38
DIRECT VENT WATER HEATER
INTERNET VERSION FOR REFERENCE ONLY
Page 39
VENT-AIR INTAKE KITS
INTERNET VERSION FOR REFERENCE ONLY
Page 40
THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF:
GAS WATER HEATERS
SUITABLE FOR WATER (POTABLE) HEATING AND SPACE
HEATING
1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water. In Massachusetts, space heating piping must not exceed 50 feet.
2. Toxic chemicals, such as those used for boiler treatment, must not
be introduced into potable water used for space heating;
3. This water heater must not be connected to an existing heating system
or component(s) previously used with a non-potable water heating appliance;
4. When the system requires water for space heating at temperatures higher than required for other means, such as an ASSE approved mixing valve must be installed to temper the water for those uses in order to reduce the scald hazard potential.
Please refer to the illustration for suggested piping arrangements.
INTERNET VERSION FOR REFERENCE ONLY
Loading...