Bradford White brute elite 125 BLMH Installation And Operation Instructions Manual

Page 1
Installation and Operation Instructions Document 1281D
Brute Elite
125
Installation and Operation Instructions for
Wall-Mounted Modulating Boiler Model BLMH
125 MBTU/h
Combination Boiler and Water Heater Model BLMC
125 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualié ou par le fournisseur de gaz.
AVERTISSEMENT
H2364500A
238-50569-00B REV 7/14
Page 2
Bradford White Corp.
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction ........................................................ 2
1.2 Rating Plate ........................................................ 2
1.3 Model Nomenclature........................................... 2
1.4 Start Up / Shut Down Instruction (Decal) ............3
1.5 Unpacking ...........................................................3
1.6 Warranty ............................................................. 3
1.7 Product Overview ...............................................4
1.8 Dimensions ......................................................... 5
SECTION 2.
Locating the Appliance
2.1 Locating the Appliance........................................6
2.2 Locating Appliance for Correct Vent Distance
from Outside Wall or Roof Termination ............... 6
SECTION 3.
Venting and Combustion Air
3.1 Combustion Air ................................................... 8
3.1.1 Combustion Air from Room.................................8
3.1.2 Ducted Combustion Air .......................................8
3.2 Venting (Exhaust) ............................................... 9
3.3.1 Side Wall Vent Terminal .................................... 10
3.3.2 Side Wall Combustion Air Terminal ................... 10
3.3.3 Vertical Vent Terminal ....................................... 10
3.3.4 Vertical Combustion Air Terminal ...................... 10
3.3.5 Installations in the Commonwealth
of Massachusetts ..............................................12
3.4 Common Vent Test ........................................... 12
SECTION 4.
Gas Supply and Piping
4.1 Gas Supply and Piping .......................................... 14
SECTION 5.
Pump Capacity
5.1 Brute Elite Heating System Pump Capacity .......... 15
SECTION 6. Water Connections
6.1 Central Heat System Piping.............................. 15
6.2 Cold Water Make-Up ........................................ 15
6.3 Freeze Protection .............................................16
6.4 Suggested Piping Schematics .......................... 17
6.5 Recognized Chemicals ..................................... 17
6.6 Domestic Hot Water (DHW) Piping (BLMC) ..... 17
6.7 Condensate Drain .............................................17
SECTION 7. Electrical Connections
7.1 Main Power .......................................................23
7.2 Pump Connections ...........................................23
7.3 24Vac Transformer Circuit Breaker ................... 23
7.4 Central Heat - Call for Heat ..............................23
7.5 Outdoor Air Temperature Sensor ...................... 23
7.6 Domestic Hot Water Connection ......................23
7.7 System Sensor
(lead lag/cascading operation only) .................. 23
7.8 External Control Connections ........................... 23
7.9 Lead Lag / Cascading Wiring Connections....... 23
7.10 Wiring Diagrams ............................................... 24
SECTION 8.
Control Setup and Operation
8.1 USER INTERFACE and
Digital Display Navigation ............................. 26
8.2 Ignition Control - Sequence of Events .............. 26
8.3 Modulation Control............................................ 27
8.4 Pump Control ....................................................27
8.5 High Limit ..........................................................27
8.6 Stack Temperature ............................................27
8.7 Domestic Hot Water Temperature..................... 27
8.8 Lead Lag / Cascading ........................................ 27
8.8.1 Lead Lag Setpoint............................................. 27
8.8.2 Lead Lag Master / Slave Selection ................... 27
8.8.3 Lead Lag Address ............................................. 27
8.8.4 Lead Lag Hysteresis ......................................... 27
8.8.5 Lead Lag Base Load Setting ............................27
Page 3
The Brute Elite 125
Page 1
SECTION 9.
Modes of Operation
9.1 Hydronic Heating Demand................................ 28
9.2 Hydronic Heating with Outdoor Reset ..............28
9.3 Hydronic Heating Using External
Modulation Control............................................ 28
9.4 Hydronic Heating Using Local Lead-Lag/
Cascading Feature ...........................................29
9.5 Warm Weather Shutdown ................................. 29
9.6 Domestic Hot Water Demand (BLMC only) ...... 29
SECTION 10.
Set Up Instructions
10.1 Filling the Boiler System ................................... 30
10.2 Starting the Burner after Set Up ....................... 30
10.2.1 Burner Operation ............................................ 30
10.2.2 Boiler Setup and Adjustment .......................... 31
10.2.3 Manifold Pressure Check................................31
10.3 Shutting Down Brute Elite ................................. 31
10.4 To Restart Brute Elite ........................................31
SECTION 12.
Trouble Shooting
12.1 Sequence of Operation .................................... 35
12.2 Short Cycling .................................................... 35
12.3 Error Codes ...................................................... 35
SECTION 13
Replacement Parts
13.1 General Information ..........................................38
13.2 Parts List ........................................................... 38
SECTION 11. Maintenance
11.1 System Maintenance ....................................... 33
11.2 Appliance Maintenance and Component
Description ........................................................33
11.2.1 Burner ............................................................... 33
11.2.2 Appliance Control ............................................. 33
11.2.3 Ignitor Assembly ............................................... 33
11.2.4 Flame Sensor ................................................... 34
11.2.5 Blower ............................................................... 34
11.2.6 Heat Exchanger Coils ....................................... 34
11.2.7 Gas Conversion ................................................ 34
Page 4
Page 2
SECTION 1. General Information
Bradford White Corp.
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Bradford White Corp. Brute Elite appliances. Read it carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Bradford White Corp. factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest Edition “National Fuel Gas Code” or 2) CSA B149.1 “Natural Gas and Propane Installation Code” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1) The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be
electrically grounded in accordance with these codes.
WARNING
Brute Elite units must be installed in accordance with
the procedures detailed in this manual, or the Bradford
White Corp. warranty will be voided. The installation
must conform to the requirements of the local
jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CSA B149.1 Natural Gas and Propane Gas Installation Code, and/or local codes. Where required by the authority having jurisdiction, the installation of Brute Elite boilers must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modications to the boiler, its gas controls, or wiring may void the warranty. If eld conditions require modications, consult the factory representative before initiating such modications.
1.2 Rating Plate
The Rating Plate contains Manufacture Date, Model Number, Serial Number, Output Rating, and all other information pertaining to your Brute Elite. The Rating Plate is located behind the center panel which will not
open until the lower front panel is opened rst.
To open the Brute Elite, rst loosen the two
phillips screws (see Figure 1A) and then open the front bottom panel downward. The center front panel will then also open downward, revealing the Rating Plate.
1.3 Model Nomenclature
The Model Number is shown on your Rating
Plate and consists of a series of letters and numbers
(nomenclature) that further identies the characteristics
of your Brute Elite.
The following nomenclature identies the
individual characters of your model number.
(1-3) Model Series Designation B L M = Bradford White, Brute Elite 125
(4) Usage
H = Modulating Boiler C = Combination Boiler and Water Heater
(5-7) Size 1 2 5 = 125,000 BTU/hr input
(8) Fuel N = Natural Gas P = LP Gas
(9) Altitude A = 0-10,000 Feet
(10) Revision 1 = First version
(11) Options Code X = No Options
(12) Pump Options X = No Pump
1.4 Start Up / Shut Down Instructions (Decal)
The Start Up / Shut Down Instruction (Decal) can be found on the back of the Top Panel (see Figure 1A). This Decal is also referred to as the Operating Instructions Label and/or Warning Label.
1
2 3 4 5 6 7 8 9 10 11 12
L M 1 2 5 A 1 X X
B
SERIES
B L M
USAGE
H - HYDRONIC
C - COMBI
UNIT
SIZE
MBTU/h
1 2 5
FUEL
N - NATURAL
P - PROPANE
Model Nomenclature
ALTITUDE
A - 0-10,000 FEET
REVISION
1 - FIRST
OPTIONS
X - NONE
PUMP
X - NONE
Page 5
The Brute Elite 125
START UP / SHUT DOWN
INSTRUCTION (DECAL)
IS ON THE BACK OF THE
TOP COVER
RATING PLATE
USER INTERFACE
1. LOOSEN
THESE TWO
SCREWS
Page 3
5. THE TOP
PANEL THEN
SLIDES
UPWARD
AND OFF
4. TWO
MORE
SCREWS
3. FOLD
CENTER
PANEL
DOWNWARD
2. FOLD
BOTTOM
PANEL
DOWNWARD
Figure 1A. Opening the Brute Elite to locate the Rating Plate and Start Up / Shut Down Instruction (Decal)
To open the Brute Elite, rst loosen the two
phillips screws and then open the front bottom panel downward. The center front panel will then also open downward. Then loosen the 2 phillips screws and slide
the top panel upward and off. You will nd the Start Up
/ Shut Down Instruction (Decal) on the back of the Top
adapter and 30psi PRV ow restrictor), wall
mounting bracket (bolts/mounting hardware provided by installer).
1. Remove all packing and tie-down materials.
2. Check contents of the carton against items shown.
Panel.
NOTE: For the complete Start up and Shut down
instructions for the Brute Elite, please reference
SECTION 10
of this manual.
1.6 Warranty
Bradford White Corp.’ Brute Elite appliances are covered by a limited warranty. The owner should complete the warranty registration at www. BradfordWhite.com.
All warranty claims must be made to an authorized Bradford White Corp. representative. Claims must include the serial number and model
NOTE: To operate the Brute Elite
using the USER INTERFACE, please reference
SECTION 8
of this manual.
(this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items may be shipped in separate packages. Verify receipt of all packages listed
1.5 Unpacking
The Brute Elite is shipped in a single crate with the following standard components packed with the appliance (see Figure 2):
2" PVC Terminal Kit (tee, elbow, screens, PRV
on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
Page 6
Page 4
1.7 Appliance Overview
Bradford White Corp.
Figure 1B. Location of Components.
1) PRV, 30 PSI
5) Exhaust terminal assy
2) PRV Pipe w/ washer
6) Air intake terminal assy
3) Wall attach bracket
7) Ball valve
4) Outdoor sensor
8) System sensor (not
shown)
9) Flow restrictor (not shown)
Figure 2. Contents of Shipping Package.
SHOWN WITH SEVERAL PANELS COMPLETELY REMOVED
Page 7
The Brute Elite 125
1.8 Dimensions
Page 5
Cond. Hydronic DHW 2nd Gas Hydronic DHW 2nd Outlet Return Inlet Return Supply Supply Outlet Supply
3/4" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" PVC copper NPT copper NPT NPT NPT copper
Figure 3. Dimensional Drawing.
Page 8
Page 6
SECTION 2.
Locating the Appliance
Bradford White Corp.
2.1 Locating the Appliance
Brute Elite is for indoor, wall-mounted
installations only.
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to
the appliance or to lower oors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certied by CSA-
International for wall-mounted installation in basements; in closets, utility rooms or alcoves. The location for the appliance should be chosen with regard to the vent pipe lengths and external plumbing and on a plumb (vertical) wall. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Brute Elite must be located as close as practical to the vertical section of the vent. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade or the maximum expected snow line.
The dimensions and requirements that are shown in Table 1 should be met when choosing the locations for the appliance.
2.2 Locating Appliance for Correct Vent
Distance from Outside Wall or
Roof Termination
The forced draft combustion air blower in the
appliance has sufcient power to vent properly when the
guidelines in Table 2 are followed.
NOTE: When located on the same wall, the Brute Elite combustion air intake terminal must be installed a minimum of 12" below the exhaust terminal.
For concentric vent terminal kit (optional), follow installation instructions included with the kit.
APPLIANCE SUGGESTED SERVICE ACCESS CLEARANCE SURFACE INCHES CM
Left Side 6 15
Right Side 6 15
Top 6 15
Closet, Front 6 15
Front 24 61
Vent 1 3
Certied by CSA for zero clearance to
combustible materials on all sides.
Table 1. Clearances.
INTAKE / EXHAUST
MAX EQUIV. CONCENTRIC MAX EQUIV. SIZE VENT F T. M VENT FT. M
125 2" 40 6.1 3/5" 40 6.1
125 *3"* 100 30.5 3/5" 40 6.1
Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless steel complying with UL1738. Installations in Canada require exhaust vent pipe that is certied to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM D1527 or galvanized material.
Installer must comply fully with manufacturer's installation instructions, to maintain ANSI Z21.13 safety certication.
Closet and alcove installations do not allow the use of PVC under any
circumstances
To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each elbow used.
* Must use 2x3 adapter within 1 ft. (30cm) of boiler exhaust outlet.
Table 2. Vent / Air Pipe Sizes.
Page 9
The Brute Elite 125
Figure 5. Mounting Detail.
Page 7
Brute Elite
Brute Elite
BLMC/H125
Note: Brute Elite
bracket and wall bracket are purposely offset.
(Minimum)
Zero clearance is allowed to combustible surfaces. However, the above minimum service clearances are strongly recommended.
Closet installations require minimum air ventilation
(see Section 3).
Figure 4. Locating the Appliance.
Figure 6. Wall Template (not to scale). Full-size template is
included with the unit.
NOTE: Brute Elite models include 16" on-center
mounting holes on upper rear of boiler jacket. These holes are not identied on the mounting template. If
mounting conditions are appropriate, the installer may opt to use this alternative method in lieu of the standard
wall bracket depicted. Installer must provide appropriate mounting/anchoring hardware.
Page 10
Page 8
Bradford White Corp.
SECTION 3.
Venting and Combustion Air
Bradford White Brute Elite includes a
standard CPVC vent/combustion air adapter. If eld connections require use of PVC/CPVC vent materials, the installer must use proper adhesive to join CPVC and/or PVC pipe and ttings.
3.1 Combustion Air
Brute Elite boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.
A Brute Elite unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.
3.1.1 Combustion Air from Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Method 1: Two permanent openings, one commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of
HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS
2" PVC 3" PVC
SIZE Standard Concentric n/a
CA006000
125 included optional contact Bradford White
Concentric vent terminal = 10 ft. pipe length.
Table 3a. PVC Vent Te
CONCENTRIC WALL ROOF SIZE ADAPTER TERMINAL TERMINAL
125 3CGV-VC 3CGV-AD- 3CVG-HZC
Table 3b. Approved Stainless Steel
Terminations and Adapters.
rminal Kits.
the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent
connectors in the conned space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
3.1.2 Ducted Combustion Air
The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the Bradford White horizontal wall terminal, shown in Table 3. See
Table 2 to select the appropriate diameter air pipe. When
taken from the roof, a eld-supplied rain cap or an
elbow arrangement must be used to prevent entry of rain water (see Figure 7).
Use ABS, PVC, CPVC or galvanized pipe for the combustion air intake (see Table 4), sized per Table 2. Route the intake to the boiler as directly as possible. Seal all joints. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is shown in Table
2. Subtract 5 allowable linear ft. (1.5m) for every elbow
used.
The connection for the intake air pipe is at the top of the unit (see Figure 2).
In addition to air needed for combustion, air
INSTALLATION STANDARDS
MATERIAL UNITED STATES CANADA
ABS ANSI/ASTM D1527 PVC, sch 40 ANSI/ASTM D1785 or D2665 Air pipe material must be chosen
CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.
Single wall galv. steel 26 gauge
Table 4. Required Combustion Air Pipe Material.
Page 11
The Brute Elite 125
Page 9
shall also be supplied for ventilation, including air required for comfort and proper working conditions for personnel.
3.2 Venting (Exhaust)
WARNING
Failure to use the appropriate vent material, installation techniques, glues/sealants could lead to vent failure causing property damage, personal injury or death.
WARNING
All venting must be installed according to this manual and any other applicable local codes, including but
not limited to, ANSI Z223.1/NFPA 54, CSA B149.1, CSAB149.2 and ULC-S636. Failure to follow this manual
and applicable codes may lead to property damage,
severe injury, or death.
The ue temperature of the Brute Elite changes
dramatically with changes in operating water temperature. Therefore, it is necessary to assess the application of the boiler to determine the required
certied vent class. If the Brute Elite is installed in
an application where the ambient temperature is elevated, and/or installed in a closet/alcove, CPVC
or stainless steel material is required. If the system
temperatures are unknown at the time of installation, stainless or CPVC material is recommended.
The Brute Elite is a Category IV appliance and may be installed with PVC and CPVC that complies with ANSI/ASTM D1785 F441, or a stainless steel venting system that complies with UL 1738 Standard (see Table 5).
IN CANADA all venting used must meet the
following requirements:
1. ULC-S636 certied and marked
2. The rst 3 feet of venting must be accessible for
visual inspection.
3. All components used in the vent system must be from a certied manufacturer.
4 . Vent system components must not be mixed
with alternate manufacturers certied
components and/or unlisted components.
5 . The venting must be installed according to the
vent manufacturers installation instructions.
The unit’s vent can terminate through the roof, or
through an outside wall.
See Table 2 to select the appropriate vent pipe
diameter. Vent pipe must pitch upward, toward the vent terminal, not less than 1/4" per foot, so that condensate will run back to the Brute Elite to drain. Route vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Please see Table 2 for proper diameter vs. length allowed.
INSTALLATIONS IN CANADA require the use
of venting material certied to ULCS636. All Gas
vents connected to the Brute Elite, plastic, stainless
steel or otherwise must be certied to this ULC
standard. Appropriate selection of vent material is very important for proper performance and safe operation of the Brute Elite.
The ue temperature of the Brute Elite changes
dramatically with changes in operating water temperature. Therefore, it is necessary to assess the application of the boiler to determine the required
certied vent class. If the Brute Elite is installed in
an application where the outlet water temperature
exceeds 145°F, and/or installed in a closet, class IIB or higher vent material is required. If the system
temperatures are unknown at the time of installation,
class IIB or higher venting material is recommended.
INSTALLATION STANDARDS
MATERIAL UNITED STATES CANADA
Stainless Steel UL 1738 Venting must be ULC-S636 certied for use as PVC, sch 40 ANSI/ASTM D178 venting material. The venting material must be chosen
CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.
Table 5. Required Exhaust Vent Material.
Figure 7. Combustion Air and Vent Through Roof.
Page 12
Page 10
Bradford White Corp.
IMPORTANT NOTE ABOUT COMMON VENTING: A
single vent that is shared by multiple Brute Elite units MUST be engineered by a competent venting specialist,
and involves the selection of draft inducing equipment,
hardware and controls to properly balance ue gas pressures. Do not common vent Brute Elite units
unless the vent system meets this requirement. Brute Elite units are never permitted to share a vent with Category I appliances.
3.3 Locating Vent & Combustion Air
Terminals
3.3.1 Side Wall Vent Terminal
The appropriate Bradford White side wall vent terminal must be used. The terminal must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 or .2 and local applicable codes. Consider the following when installing the terminal:
1. Figure 9 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or
appliances with condensing vents are not permitted
to terminate above a public walkway, or over an
area where condensate or vapor could create a
nuisance or hazard.
3. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows, gravity
inlets or other openings. Whenever possible, avoid
locations under windows or near doors.
5. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
6. Locate the terminal so the vent exhaust does not
settle on building surfaces or other nearby objects.
Vent products may damage surfaces or objects.
7. If the boiler or water heater uses ducted
combustion air from an intake terminal located on
the same wall, see Figure 9 for proper spacing and
orientation.
If the vent termination is located in an area exposed to high winds, an optional PVC tee (the same diameter as the vent pipe) may be used. The tee'd vent termination offers greater protection from wind related operating issues.
of corrosive chemical fumes (e.g., cleaning uid,
chlorine compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism. It must be at least 7 feet (2.1m) above a public walkway.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
4. For concentric vent, follow instructions
included with vent kit.
5. Multiple vent kits should be installed such that the horizontal distance between outlet group and inlet group is 36" (90cm) minimum.
6. Vent outlet must be no lower than the center of the air inlet, and must be at least 12" (30cm) away from the air inlet (see Figure 8).
3.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent
must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 7).
3.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water (see Figure 7). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
3.3.2 Side Wall Combustion Air Terminal
The Bradford White side wall combustion air terminal, or concentric terminal (see Table 3), must be used when the heater takes air from a side wall. Consider the following when installing the terminal (see
Figure 9):
1. Do not locate the air inlet terminal near a source
Figure 8. Minimum Venting Distance.
Page 13
The Brute Elite 125
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
deck, or balcony See note 6 See note 6
B= Clearance to window or door that may be Direct vent only: 12 inches (30cm); 36 inches (91 cm)
opened Other than Direct vent: 4 ft (1.2m) below or to
side of opening; 1 ft (30cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soft located
above the terminal within a horizontal See note 4 See note 5
distance of 2 feet (61cm) from the center
line of the terminal
E= Clearance to unventilated soft See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner 3 feet (91 cm) minimum See note 5
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly See note 4 above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply Direct vent only: 12" (30cm) 80-285; 36" (91cm)
inlet to building or the combustion air inlet 399-850. Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm)
to any other appliance or to side of opening; 1 ft (30cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in this
driveway located on public property for category IV appliances. location for category IV appliances.
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
4. For clearances not specied in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the
gas supplier.
5. For clearances not specied in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
6. IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have more
specic requirements, and must be consulted.
Page 11
Figure 9. Combustion Air and Vent Through Side Wall.
*When vent terminal is less than 10 feet (3m) horizontally
from a forced air inlet, the terminal must be at least 3 feet
(0.9m) above the air inlet.
Page 14
Page 12
Bradford White Corp.
3.3.5 Installations in the Commonwealth of Massachusetts
In Massachusetts the following items are required
if the side-wall exhaust vent termination is less than
seven (7) feet above nished grade in the area of the
venting, including but not limited to decks and porches. From Massachusetts Rules and regulations 248 CMR
5.08
1. Installation of Carbon Monoxide Detectors At the time of installation of the side wall vented
gas fueled appliance, the installing plumber or
gastter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-up is
installed on the oor level where the gas appliance
is to be installed. In addition, the installing plumber
or gastter shall observe that a battery operated or
hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualied licensed professionals
for installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall horizontally vented
gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide with alarm and battery back-up may be installed on the next
adjacent oor level.
b. In the event that the requirements of the
subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above
Optional concentric vent kit sold separately.
Figure 10. Vent Dimensions, 2-Pipe System.
requirements, provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm be installed.
2. Approved Carbon Monoxide Detectors Each carbon monoxide detector shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. Signage
A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print no less than one-half (1/2) inch in size: "GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS".
4. Inspection The state or local gas inspector of the side-wall
horizontally vented gas fueled appliance shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1-4.
3.4 Common Vent Test
NOTE: This section does not describe a method for
common venting Brute Elite units. It describes what must be done when a unit is removed from a common vent system. Brute Elite units require special vent systems and fans for common vent. Contact the factory if you have questions about common venting Brute Elite units.
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other
deciencies which could cause an unsafe condition.
3. Insofar as it is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close
Page 15
The Brute Elite 125
replace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use
the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and
any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1 NFPA 54 and/or CSA B149.1, Installation Codes.
Page 13
Page 16
Page 14
SECTION 4.
Gas Supply and Piping
4.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or oor stands, not the appliance.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is tted for the proper type
of gas by checking the rating plate. Brute Elite will function properly without the use of high altitude
modication at elevations up to 10,000 feet (3050
m).
2. The maximum inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet gas pressure is 4" W.C. (1.0kPa).
3. Refer to Tables 6A, 6B, 6C and 6D to size piping.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with
piping compound resistant to action of liqueed
petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kPa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kPa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
Bradford White Corp.
Brute Elite NATURAL GAS REQUIRED
SIZE CU FT / HR.
125 125
TO SIZE PIPING:
Measure linear distance from meter outlet to last boiler. Add total input of all boilers and divide by 1000 to obtain cu ft / hr required. Add total equivalent length of ttings used according to Table 6B. Align total length (pipe and ttings) on left side column of Table 6C with highest cubic feet of gas required.
Notes:
Consult and conrm with Applicable Fuel Gas Code before beginning work. Verify gas inlet pressure is between 4 and 13 in W.C. before starting boiler.
Table 6A.
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS
NOMINAL PIPE SIZE
FITTING 1/2" 3/4" 1"
LINEAR FEET
90° ELBOW 3.6 4.4 5.2
TEE 4.2 5.3 6.6
Table 6B.
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS
NOMINAL PIPE SIZE @ 0.30" W.C. PRESSURE DROP
LENGTH 1/2" 3/4"
FT CUBIC FEET OF GAS PER HOUR
20 92 190
40 130
60 105
80 90
100
Table 6C.
WARNING:
Open ame can cause gas to ignite and result in property damage, severe injury, or loss of life.
NOTE: The Brute Elite appliance and all other gas appliances sharing the gas supply line must be ring at
maximum capacity to properly measure the inlet supply
pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line.
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
UNDILUTED PROPANE
NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP
SIZE 1/2" 3/4"
LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR
20 200 418
40 137 287
60 110 231
80 94 197
100 84 175
NOTES: 1. Follow all local and national LP gas codes for line sizing and equipment requirements. 2. Verify that inlet gas pressure remains between 4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
Table 6D.
Page 17
The Brute Elite 125
SECTION 5.
Pump Capacity
5.1 Brute Elite Heating System
Pump Capacity
Figure 11. Available Pump Head.
Figure 12. DHW Connections with Anti-Scald Valve and
Flow Restrictor.
SECTION 6. Water Connections
Page 15
PRV Included with Brute Elite
A Pressure Relief Valve is included with each Brute
Elite. The PRV must be installed prior to lling the system.
when rigid hangers are installed. Maintain 1" (2.5cm) clearance to combustibles for hot water pipes.
Pipe the discharge of the pressure relief valve (full size) to a drain or in a manner to prevent injury in the event of pressure relief. If system contains more than 24 gallons (91 liters), then an auxiliary expansion tank
is required. Minimum ll pressure must be 12psig
(82.7kPa). Install shutoff valves where required by code.
Suggested piping diagrams are shown in Figures
12 through 19. These diagrams are meant only as a
guide. Components required by local codes must be properly installed.
Brute Elite's efciency is higher with lower
return water temperatures.
Brute Elite MUST be piped in a primary-secondary fashion (using either piping or a hydraulic separator) such that the pump that is mounted on the boiler ONLY serves the boiler.
Brute Elite boiler must be located within 15 feet (4.6m) of the supply and return header (or the hydraulic separator). The pump is sized for a maximum of 30 feet (9.1m) of piping and the headloss of the boiler only.
For custom congurations, the available pump
head is provided in Figure 11. The system designer should take into account allowable boiler temperature rise of 65°F (36°C).
6.1 Central Heat System Piping
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with
this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used
6.2 Cold Water Make-Up
1. Connect the cold water supply to the inlet
connection of an automatic ll valve.
2. Install a suitable back ow preventer between the
automatic ll valve and the cold water supply.
3. Install shut off valves where required.
HEATING DHW SIZE CONN SIZE CONN SIZE
125 3/4" 1/2"
Table 7. Water Connection Pipe Sizes.
Page 18
Page 16
Bradford White Corp.
Figure 13. Hydronic Piping — High and low temp zones with indirect water heater (BLMH using internal 3-way).
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling appliances where they may be exposed to refrigerated
air circulation, must be equipped with ow control
valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A boiler installed above radiation level, or as required by the authority having jurisdiction, must be provided with a low water cutoff device at the time of boiler installation.
which could result in leaking or ooding conditions.
Do not use automotive antifreeze or ethylene glycol. To help prevent freezing, Bradford White recommends the use of inhibited propylene glycol concentrations between 20% and 35% glycol. Typically, this concentration will serve as burst protection for temperatures down to approximately -5°F (-20°C). If temperatures are expected to be lower than -5°F (-20°C), glycol concentrations up to 50% can be used. NOTE:
Bradford White supplied pumps are not all capable of maintaining the reduced temperature rise required
6.3 Freeze Protection
Brute Elite units are certied for indoor use only,
and are not design-certied for placement outdoors.
Proper precautions for freeze protection are recommended for boiler installations in areas where the danger of freezing exists.
Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc.,
with glycol concentrations greater than 35%.
IMPORTANT NOTES: Different glycol products may provide varying degrees of protection. Glycol products
must be maintained properly in a heating system,
or they may become ineffective. Consult the glycol specications, or the glycol manufacturer, for information about specic products, maintenance of solutions, and set up according to your particular conditions.
may prevent a boiler from ring. Any time a boiler is subjected to freezing conditions, and the boiler is not
able to re, and/or the water is not able to circulate,
there is a risk of freezing in the boiler or in the pipes in the system. When water freezes, it expands which
may result in bursting of pipes, or damage to the boiler,
6.4 Suggested Piping Schematics
Figures 13 through 19 show suggested piping
congurations for Brute Elite boilers. These diagrams
are only meant as a guide. All components or piping required by local code must be installed.
Page 19
The Brute Elite 125
6.5 Recognized Chemicals
The following manufacturers offer glycols, inhibitors, and anti-foamants that are suitable for use in the Brute Elite. Please refer to the manufacturers instructions for proper selection and application.
1. Sentinel Performance Solutions Group
2. Hercules Chemical Company
3. Dow Chemical Company
6.6 Hot Water Piping
6.6.1 Domestic Hot Water Piping (BLMC)
Connect domestic hot and cold water piping to the boiler at locations noted in Figure 13. Expected DHW performance is indicated in Table 8.
Use of ow restrictor is optional to prevent colder water at excessive ow rates. Contact Bradford White for alternate congurations.
6.6.2 Indirect Water Heater Piping (BLMH)
The BLMH model can control an indirect water heater zone. Pipe to the locations shown in Figure 13. Zone valve and associated wiring are not required. Setpoint is made via aquastat located on the indirect water heater, or can be controlled at the boiler via a remote sensor.
Page 17
6.7 Condensate Drain
A condensate drain trap is built into the Brute Elite. Connect a 3/4” PVC pipe between the drain
connection and a oor drain (or a condensate pump if a oor drain is not accessible).
The condensate drain must be installed so as to prevent accumulation of condensate. When a condensate pump is not used, the tubing must continuously slope downward toward the drain with no spiraling.
Consult local codes for the disposal method.
Caution
Condensate is mildly acidic (pH=5), and may harm some oor drains and/or pipes, particularly those that are metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity, or neutralize the condensate before disposal. Damage caused by
failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer’s responsibility.
Figure 14. Hydronic Piping — Low temp system with indirect water heater (BLMH using internal 3-way).
Page 20
Page 18
INLET TEMPERATURE °F
50°F 60°F 70°F
GPM TEMP RISE °F
1.0 100 90 81
2.0 90 83 79
3.0 78 76 68
4.0 59 56 51
INLET TEMPERATURE °C
10°C 16°C 21°C
LPM TEMP RISE °C
4 56 50 45
8 50 46 44
11 43 42 38
15 33 31 28
Table 8. DHW and Pump Performance Data.
Bradford White Corp.
Caution
Scalding Risk: Bradford White recommends
the use of a thermostatic mixing
valve at domestic hot water outlet (boiler location) to reduce potential for scalding.
The following thermostatic
mixing valve model has been tested and approved for
Brute Elite application:
Honeywell AM100-US-1
Contact Bradford White for additional recommended
models.
Figure 15. Hydronic Piping — Low temp system.
Installer to provide and install
(anti-scald) thermostatic mixing valve.
Page 21
The Brute Elite 125
Page 19
Figure 16. Hydronic Piping — Multi boilers for large homes with long / multiple baseboard zones.
Installer to provide DHW
(anti-scald) thermostatic mixing valve.
Page 22
Page 20
Bradford White Corp.
Figure 17. Hydronic Piping — Multi boilers for large homes with long / multiple radiant zones.
Installer to provide DHW
(anti-scald) thermostatic mixing valve.
Page 23
The Brute Elite 125
Page 21
Figure 18. Hydronic Piping — Heating zones piped with zone pumps.
Installer to provide DHW
(anti-scald) thermostatic mixing valve.
Page 24
Page 22
Bradford White Corp.
Figure 19. Hydronic Piping — Heating zones piped with zone valves.
Installer to provide DHW
(anti-scald) thermostatic mixing valve.
Page 25
The Brute Elite 125
Page 23
SECTION 7. Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/ NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in Canada. Do not rely on the gas or water piping to ground the metal parts of the boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance personnel, who work on or around the boiler, may be standing on wet oors and could be electrocuted by an ungrounded boiler. Electrocution can result in severe injury or death.
Single pole switches, including those of safety controls and protective devices must not be wired in a grounded line.
All electrical connections are made on the terminal blocks that are located inside the control panel.
NOTE: All internal electrical components have been
prewired. No attempt should be made to connect electrical wires to any other location except the terminal blocks.
Wiring connections are shown in Figures 21-22.
Important Note: DO NOT MAKE/BREAK Brute Elite LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A “call for heat / end call for heat” MUST be connected to the eld interlock terminals. Some Brute Elite components
are designed to have constant voltage during normal
operation. If the Brute Elite's supply voltage is toggled
as a call for heat signal, premature failure of these
components may result.
If using remote 4-20mA control, Brute Elite does not recognize 4mA as a signal to shut off. If the call for heat is not connected between the eld interlock terminals, Brute Elite will remain in low re when it sees 4mA as a modulating signal.
Caution
Brute Elite supply voltage must not be disengaged, except for service or isolation, or unless otherwise instructed by procedures outlined in this manual. To signal a call for heat, use the 24V eld-interlock, as shown in the wiring diagram(s).
7.1 Main Power
Plug power cord into a non-switched 115V electrical outlet with 15A circuit protection. FLA is 2A. There is an internal 10A breaker to protect internal system components.
7.2 Pump Connections
Brute Elite energizes the integral boiler pump (and
three-way valve if central heat) upon a call for heat.
Once the call for heat is satised the pump will remain on for the dened pump overrun time.
NOTE: System pump contacts are dry contacts. Appropriate voltage must be supplied to the System pump for proper operation.
System pump connections are located in the control panel (see Figure 20). The system pump contacts are rated for 120Vac, 7.4 amps. To use the contacts, power must be supplied on one terminal with the other terminal wired to the pump or a relay controlling the pump.
7.3 24Vac Transformer with Circuit Breaker
24Vac is supplied by a transformer mounted behind the upper door. All 24Vac power is supplied
through a
2A circuit breaker located behind middle door.
7.4 Central Heat - Call for Heat
Connect the Call for Heat to terminals #1 and #2 (connections labeled "T-T or interlock").
7.5 Outdoor Air Temperature Sensor
Connect the outdoor air temperature sensor to connections labeled "Outdoor temp sensor." The outdoor air temperature sensor is used for warm weather shutdown and outdoor reset.
7.6 Domestic Hot Water Connection
For BLMH and indirect water heater, connect aquastat for remote sensor to terminals 7 & 8 (see
Figures 20 and 22).
7.7 System Sensor
(lead lag/cascading operation only)
Connect the system sensor to connections labeled "system sensor."
7.8 External Control Connections
Connect 4-20mA signals from external controls or building automation systems. When making the connections, follow the polarity designations shown on the label.
7.9 Lead Lag / Cascading Wiring
Connections
Connect each boiler in the cascade system together by daisy chaining each control from Modbus port 1
(MB1) of the rst boiler to the second and so on. This
can be done using 22awg or thicker shielded twisted pair wire with drain. Two twisted pairs or three conductors are needed. a. To daisy-chain the boilers connect a wire from
Modbus port 1 (MB1) terminal A of the rst boiler
to Modbus port 1 (MB1) terminal A of the second
boiler.
Page 26
Page 24
b. If there are more boilers in the system connect a
wire from Modbus port 1 terminal A of boiler 2 to Modbus port 1 terminal A of boiler 3.
c. Repeat these steps until all Modbus port 1 terminal
A connections are wired.
d. Repeat the above steps for Modbus port 1 terminal
B and C connections to complete the wiring.
e. Connect the drain wire from the twisted pair wire
to ground on one end of the wire only.
7.10 Wiring Diagrams (see Figures 21-22)
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after
servicing
Bradford White Corp.
Figure 20. System Pump Connections on Control Panel.
Figure 21. Ladder Diagram.
Page 27
The Brute Elite 125
115V "HOT"
10A
10A
ILLUM
POWER
SWITCH
Page 25
I
U
C
T
I
C
R
E
K
R
A
E
R
B
W BK
BK
115V "HOT"
W
BK
POWER
PLUG 115V
H2345500revA
1
1
R
WIRE GUIDE
BK
W
BLOWER
O
P
24V = 22 AWG
24V = 18 AWG
115V = 18 AWG
COLOR GUIDE
BK - BLACK
W - WHITE
R - RED
Y - YELLOW
BL - BLUE
BR - BROWN
O - ORANGE
G - GREEN
PUMP
G
W
BK
G
3
5
BL
R
LMC ONLY (LMH: USE A-STAT FOR INDIRECT)
R
FLOW SWITCH
R
ALARM
SENSOR SYSTEM
LMC ONLY (LMH: USE JUMPER
B/W 7 & 8)
EMP. SENSOR
DOMESTIC
SENSOR OUTDOOR TEMP.
SENSOR OUTDOOR TEMP.
ANALOG INPUT -
ANALOG INPUT +
T-T OR INTERLOCK
P - PURPLE
GR - GRAY
BREAKER
R
R
7
8
56
34
NO COM
2
1
NC
DPDT
RELAY
1
2
CIRCUIT
GR
P
115 V "NEUTRAL"
115 V "GROUND"
115 V "HOT"
2 AMP
24V "HOT"
12
11
10
1 TERM STRIP
1 2 345 6 7 89
W
BK
BK
W
BK
TRANSFORMER
115 VAC INPUT
24V 115V
Y
Y
Y
Y
Y
YBRBLO
TEMP.
STACK
SENSOR
EXHAUST
GR
P
TEMP.
OUTLET
INLET
TEMP.
GR
GR
Y BR
BL
R
SENSOR
SENSOR
P
31
42
BLBR
1
2
24 VAC OUTPUT
YY
31
BR
GR
PO
GR
R
GAS
Y
W
VALVE
42
G
BRBL
+24V
24V
COM
Y
Y
78123 4 56
3142 56
P
Y
123 45 4 5 66 123
J10
J9
J8B
J8A
R
Y
BR
C
J2
1 3
G
W
LOCAL DISPLAY
123
O
B
A
C
ECOM
J3
HV SPARK
2 4
B
A
MB2
J1
G
G
LWCO
SWITCH
Y
Y
SWITCH
WATER PRESSURE
SWITCH
FAN PROVING
B
A
C
MB1
CONTROL MODULE
65
23
1
4
R
NO
COM
BL
N0
COM
123
465
78
BR BL
12
R
3 4 5 6
1
R
234
J4A
56
165 2
J4B
43
G
BR
Y
R20729
(OPTIONAL)
Y
R
VENT
SWITCH
BLOCKED
COM
NC
BL
BR
Y
BR
SYSTEM PUMP
7A
13 14
DRY
CONTACT
O
Figure 22. Wiring Diagram.
FLAME SENSOR
SPARK IGNITOR
P
O
RR
3 WAY
VALVE
BK BK
WATER FLOW
BK
Page 28
Page 26
SECTION 8.
Control Setup and Operation
The Brute Elite control is an integrated electronic control that replaces many of the individual components found on older appliances. The control acts as the ignition control, pump control, high limit and cascading/ lead lag control and is setup using the digital display on the appliance.
8.1 Digital Display Navigation
Figure 23. The USER INTERFACE.
The Digital Display is centered in the middle of the User Interface and has 3 seperate modes of control. They are USER, SETUP and DIAGNOSTIC. The names of these modes clearly labels the intent of the different levels of control. A USER might be the homeowner or a service technician. SETUP displays all the controls needed when setting up or expanding the boiler. And DIAGNOSTIC is intended for a trained Brute Elite technician. The menu structure and variables in each are shown in Table 9, Table 10, and Table 11.
USER Mode is the home screen shown on the control. If the display is not in USER Mode wait for the display timeout period to be reached or press the Done button to return to the USER Mode.
SETUP Mode is accessed by holding the up and down arrow keys simultaneously for 3 seconds.
DIAGNOSTIC Mode is accessed by holding the NEXT button for 3 seconds
Once in a particular Mode, navigation consists of pressing the next button to scroll from item to item and then pressing the up and down arrows to change values. Once the value is adjusted, the NEXT or DONE button can be pressed.
Bradford White Corp.
MENU ITEM FUNCTION RANGE DEFAULT
Outlet water Displays the current outlet 55-180°F 120°F temperature water temperature & allows the setpoint to be adjusted
Inlet water Displays the current inlet — temperature water temperature
Delta T Displays the current
temperature rise across the heat exchanger
Stack Displays the current stack
temperature temperature
Outdoor Displays the current outdoor
temperature air temperature
Firing Rate Displays an indicator of the current ring rate based upon fan RPM. The actual ring rate may vary.
Table 9. USER Mode Menu.
MENU ITEM DEFINITION
F or C Selects temperature units LBTHODLOD Outdoor reset enable/disable -
enables menu items
LBT Low boiler setpoint during outdoor reset
HOD High outdoor temperature setpoint
LOD Low outdoor temperature setpoint RMT Add Used for Lead/Lag (follow menus) LL Lead/Lag enable/disable - enables menu items HS Hysteresis - temp range between on/off cycles bL Base Load % - input rate before next boiler res Sd Warm weather shut-down temperature ASC Anti short cycle - minutes of delay between
startup
bAC Future use - Press DONE to exit menu. PAS Future use - Press DONE to exit menu.
NOTE: When enabling/disabling functions, select "Done" and wait 30
seconds before scrolling.
Table 10. SETUP Mode Parameters.
MENU ITEM DESCRIPTION
mA Display the ame sense signal
Alert codes Displays the current alert code
Lockout code Displays the current lockout code
Outlet limit Displays outlet temperature limit
DHW limit Displays Domestic Hot Water limit setting
DHW actual Displays Actual DHW temperature
Stack limit Displays Stack limit setting
Min. ring rate Displays the minimum ring rate allowed
Min. forced Allows the user to force the boiler to re at ring rate the minimum ring rate
Max forced Allows the user to force the boiler to re at ring rate the maximum ring rate
Rate indicator Displays a indicator of the ring rate based off of the fan RPM. Actual ring rate may vary depending upon setup.
Table 11. DIAGNOSTIC Mode Menu.
Page 29
The Brute Elite 125
Page 27
8.2 Ignition Control- Sequence of Events
1. Call for heat
2. Safety chain check
3. Fan starts.
4. Prepurge timer is started.
5. Pre ignition time of 2 seconds to check the ame
sensor operation and status.
6. Trial for ignition period, 4 seconds. The direct spark ignition switches to constant spark for three seconds, during which time the gas valve is open. For the last second of the ignition period direct
spark is de-energized and the ame sensor checks for established ame. If ame is sensed the control enters "Run" to satisfy the demand. If ame is
not established the control enters a retry, starting
from step 2. If ame has not been established in
the appropriate number of retries the control will lockout with a 109 error code.
7. Call for heat complete
8. Gas valve off
9. Fan and pump over run times active to purge the system
The sequence is the same for DHW or Central
Heat modes. Upon a call for Central Heat, the 3-way valve will shift position, allowing boiler water to enter the building's heating loop.
8.3 Modulation Control
The control uses a PID algorithm to adjust
the ring rate of the boiler as the control point is
approached. The goal of the control is to operate
at a minimum ring rate to match the load on the
appliance. The burner modulates to achieve the setpoint temperature, away from the actual off point.
8.4 Pump Control
The boiler pump is active anytime there is a call
for heat applied to the control. When there is a central heat call supplied the system pump relay is active. If there is a DHW call supplied while the central heat call is active the system pump turns off. This happens because of domestic hot water priority, which forces the control to satisfy the domestic water demand prior to the
hydronic demand. When the last heat demand is satised
the boiler pump enters an overrun time.
8.5 High Limit
The control uses a dual thermistor sensor to
monitor the Brute Elite's maximum temperature. The high limit sensor is installed in the outlet water. A dual thermistor sensor is used, so that the two temperatures
can be monitored and compared to conrm accuracy. The control will automatically reduce the ring of the
Brute Elite to prevent the high limit from tripping. The high limit setpoint is not adjustable.
8.6 Stack Temperature
The stack temperature is a dual thermistor sensor and is limit rated. The control compares each of the temperature readings to determine accuracy. The stack sensor is used as a limiting feature to avoid excessive temperatures in the venting.
8.7 Domestic Hot Water Temperature
The domestic hot water temperature sensor is used to control DHW temperature. The DHW setpoint can be adjusted through the USER menu structure.
DHW setpoint is displayed during DHW mode. For BLMH model, an aquastat will be used in lieu of a sensor to control temperature of an indirect tank.
8.8 Lead Lag / Cascading
Lead Lag/Cascading allows multiple boilers to be connected together and controlled from one common sensor input. Up to 8 boilers can be connected together in a single system. To setup Lead/Lag or cascading operation there are several settings in the "setup"
menu structure that must be adjusted for the specic
installation, each is covered in the following sections.
8.8.1 Lead Lag Setpoint
The lead lag setpoint is set from the "user" menu using the "LL" variable. This is the temperature the boiler is attempting to maintain at the system sensor. This setting doesn't control the boiler outlet temperature, so the water temperature at the boiler outlet may be much hotter than the system temperature setpoint. Adjust the LL setpoint to the desired operating temperature of the system.
8.8.2 Lead Lag Master/Slave Selection
In the SETUP menu structure, the "LL" menu allows the lead lag system to be turned on and the boiler
to be congured as a master or slave control. In each
lead lag system there can only be one master control, so proper selection is important to avoid operating issues. To set the boiler to lead lag "master" operation the LL menu should be set to "LDR". To set the boiler to slave, "SLA" should be selected.
8.8.3 Lead Lag Address
The Lead Lag address must be set for each boiler connected to the lead lag system. Each boiler must have a unique address selected for the system to work properly. Typically, the lead or master boiler should be set to address one and the remaining boilers should be set to values 2–8 depending upon how many boilers are installed in the system.
8.8.4 Lead Lag Hysteresis
The lead lag system uses a hysteresis value set in the setup menu, called, "HS". The hysteresis and setpoint values control the on and off points of the boiler. If the lead lag setpoint is adjusted to 120°F with a hysteresis value of 5°F the boiler will turn off when the water temperature reaches 125°F and will turn back
Page 30
Page 28
Bradford White Corp.
on when the water temperature reaches 115°F. Set the hysteresis values to match the boiler to the system operating characteristics. Setting this value correctly will help reduce the chance of short cycling.
8.8.5 Lead Lag Base Load Setting
The lead lag system uses a base load setting that is
set through the "setup" menu called "bL". The base load
setting identies the ring rate that the operating boiler
must achieve before the next boiler in the system is allowed to operate. The default setting is 50% to avoid short cycling and operating the boilers at higher, less
efcient, ring rates.
NAME FUNCTION DEFAULT VALUE
CH on Burner demand begins when the 5°F differential outlet water temperature reaches "Outlet water temperature setpoint" minus "CH on differential"
CH off Burner demand ends when the 5°F differential outlet water temperature reaches "Outlet water temperature setpoint" plus "CH off differential"
DHW on Burner demand begins when the 2°F differential outlet water temperature reaches "Outlet water temperature setpoint" minus "DHW on differential"
DHW off Burner demand ends when the 7°F differential outlet water temperature reaches "Outlet water temperature setpoint" plus "DHW off differential"
Pump Operates the pump for the overrun 1
overrun time after the burner demand minute has ended
High Locks the boiler out when the high 200°F
limit limit temperature is reached
(requires manual reset)
Flame Flame signals lower than the ame 0.8Vdc
threshold threshold interrupt burner operation
Table 12. Default Control Settings.
SECTION 9.
Modes of Operation
The Brute Elite control allows the boiler to operate in many different modes of operation. The mode must be selected based upon the requirements of the installation. The following sections describe the basic operation of the Brute Elite in each of the different modes. Familiarize yourself with each mode and how the operation of the boiler varies, depending upon the installation and inputs the control is monitoring.
9.1 Hydronic Heating Demand
When using the Brute Elite for hydronic heating a call for heat must be supplied to the "T-T or Interlock" terminal. Once the call is supplied the control starts the boiler and system pumps, shifts the 3-way valve position and begins the ignition process. The ignition process consists of a prepurge, trial for ignition, and run period. The prepurge period starts on a call for heat once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which the direct spark ignition system and gas valve are energized.
At the end of the trial for ignition period the ame signal is compared with the preset ame threshold value. If the ame signal is higher than the ame threshold the Brute Elite enters "run". If the ame signal is below
the threshold the Brute Elite returns to prepurge and starts the ignition process over. In "run" the Brute Elite
monitors the ame signal, call for heat, safeties, and
water temperatures and modulates as needed between 100% and 20% of rate to satisfy the call for heat.
9.2 Hydronic Heating with Outdoor Reset
Outdoor reset varies the control point setpoint based on the actual outdoor temperature. The reset function works as shown in Figure 24. When the outdoor air temperature reaches the "high outdoor temperature setpoint (HOD), the control point setting is adjusted to the low boiler temperature setpoint (LBT). When the outdoor air temperature reaches the low outdoor temperature setpoint (LOD), the control setpoint is adjusted to the CH/Outlet water setpoint temperature. HOD, LOD and LBT can be adjusted by accessing SETUP mode. CH setpoint is adjustable from the USER menu structure.
9.3 Hydronic Heating Using External
Modulation Control
When using the Brute Elite for hydronic heating with external modulation control a call for heat must be supplied to the "T-T" terminal. Once the call is supplied the control starts the boiler and system pumps and begins the ignition process. In "run" the Brute Elite
monitors the ame signal, call for heat, safeties, and
Page 31
The Brute Elite 125
Page 29
water temperatures. The boiler setpoint is used to limit the maximum water temperature leaving the boiler only. The modulation rate is controlled by a 4-20mA (0­10Vdc using converter) signal supplied by an external control. When setting up a system using an external control care must be taken to set the external control algorithms to prevent the boiler from short cycling or "hunting " to prevent premature component failure.
NOTE: A call for DHW will override external control.
9.4 Hydronic Heating Using Local Lead-
Lag/Cascading Feature
When using single or multiple Brute Elite's in lead-
lag conguration, the system sensor is used to monitor
the demand and modulation rates of the operating system (see Section 7 for wiring instructions).
Let’s consider the following example:
Three Brute Elite boilers (let’s call them “Lead”, “Slave1” and “Slave2”) tied together via Modbus 1 connection, with appropriate RMT Address (1, 2,
3). System sensor input is used to indicate common secondary loop temperature.
System setpoint = 150°F
HS (hysteresis) = 10°F (default)
BL (base load) = 50% (default)
Anti-short-cycle = 5 minutes
Run sequence is initiated when system temperature falls to 140°F (setpoint less hysteresis value). Lead
boiler will start. All ring rates will depend on several application characteristics, including ow rate, system
load, water volume, etc. Boilers will start at a rate of 35%. If the load is such that Lead’s rate increases to 50%, “Slave1” will go through its startup sequence and
begin ring at 35%. At this point, both boilers (Lead and
Slave1) will continue to respond simultaneously to the load/system characteristics, by modulating up or down together, in relation to the relative system setpoint and load characteristics. Scenario 1: If the system loop temperature rises quickly,
and moves above setpoint, then the boilers will
simultaneously drop their ring rate. If when
reaching the point where both boilers drop toward
their minimum ring rate (20%), then the rst
slave will drop out. Slave1 will remain unavailable until its ASC timer has expired (5 minutes). If the load were to increase such to drive all active
boilers to 50% ring rate or more, during the ASC
time, Slave2 will begin its startup sequence and
begin to re at 35%, etc.
Scenario 2: If the system loop temperature continues
to drop (load increases), then the two boilers will
increase ring rate together. At 50%, Slave2 will begin its ring sequence and be added to the group.
All three boilers will continue to re simultaneously at
equal input rates or…
1. Modulation rate approaches minimum ring rate (20%), in which case Slave2 will rst drop out, and
then Slave1, accordingly.
2. System temperature reaches 10°F (HS- hysteresis value) above setpoint (e.g. 160°F), in which case remaining boiler will shut off.
3. Any of the boilers approach its high limit temperature the individual boiler will modulate back.
9.5 Warm Weather Shutdown
Warm weather shutdown overrides a central
heat call for heat when the outdoor air temperature is greater than the warm weather shutdown setpoint. Warm weather shutdown is always active whenever there is an outdoor sensor attached to the control. To avoid warm weather shutdown the warm weather shutdown temperature should be increased as necessary. The warm weather shutdown setpoint can be adjusted in SETUP mode, using the SD menu.
9.6 Domestic Hot Water Demand
For Combi (BLMC), DHW demand is triggered
by a ow switch located near the DHW cold water inlet. When water begins to ow (open faucet, shower, etc.), the boiler will re, based on the water temperature
requirements. It may cycle on and off under very low
ow rates. Minimum ow is 0.5 gpm.
For BLMH, an optional indirect water heater can
be piped-in using Brute Elite's integral 3-way valve as a zone valve. An aquastat in the indirect water heater
connected in place of the ow switch will signal demand
for DHW. The service person should note the minor wiring differences on Figure 22.
Figure 24. Outdoor Reset Setpoint Temperatures.
Page 32
Page 30
Bradford White Corp.
SECTION 10.
Set Up Instructions
10.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all bleeding devices and open make-up water valve.
Allow system to ll slowly.
2. Move manual lever on 3-way valve actuator to "open" position, allowing air to purge from boiler loop. Valve is normally in DHW position until there is a call for Central Heat via "T-T" contacts. If make-up water pump is employed, adjust pressure switch on pumping system to provide a minimum of 12 psi (81.8 kPa) at the highest point in the heating loop.
3. If a water pressure regulator is provided on the make-up water line, adjust the pressure regulator to provide at least 12 psi (81.8 kPa) at the highest point in the heating loop.
4. Open bleeding devices on all radiation units at the high points in the piping throughout the system, unless automatic air bleeders are provided at such points.
Note that there is an air bleed located on the left
side of Brute Elite, on top of the jacket.
5. Cycle the boiler pump on and off 10 times, 10 seconds on and 10 seconds off to remove all air from the heat exchanger. Then run system and appliance pump for a minimum of 30 minutes with the gas shut off.
6. Using manual lever located on left side of 3-way valve actuator, move from "open" position back to closed position repeatedly. This process forces air out of the internal DHW loop.
WARNING
Failure to remove all air from the heat exchanger could lead to property damage, severe injury or death.
7. Recheck all air bleeders as described in Step 4.
8. Start up boiler according to the procedure in this manual. Operate the entire system, including the pump, boiler, and radiation units for one (1) hour.
9. Shut down the entire system and vent all radiation units and high points in the system piping, as described in Step 4.
10. Close make-up water valve and check strainer in pressure reducing valve for sediment or debris from the make-up water line. Reopen make-up water valve.
11. Check gauge for correct water pressure and also check water level in the system. If the height indicated above the boiler insures that water is at the highest point in the circulating loop, then the
system is ready for operation.
12. Refer to local codes and the make-up water valve manufacturer’s instructions as to whether the make-up water valve should be left open or closed.
13. After placing the unit in operation, the ignition system safety shutoff device must be tested.
First, shut off the manual gas valve, and call the
unit for heat. Main gas terminals will be energized, attempting to light, for four (4) seconds, and then will de-energize. The unit will go into lockout after the required number of trial for ignition periods.
Second, turn the power off, press the manual reset
button on the boiler control, or the user display, open the manual gas valve and allow the unit to light. While the unit is operating, close the manual gas valve and ensure that power to the main gas valve has been cut.
14. Within three (3) days of start-up, recheck all air bleeders and the expansion tank as described in Steps 4 and 8 above.
Important Note: The installer is responsible for
identifying to the owner/operator the location of all emergency shutoff devices.
WARNING
Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the control system and any gas control that may have been
under water.
10.2 Starting the Burner after Set Up
Initial setup must be checked before the unit
is put in operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to improper setup. Damage to the boiler resulting from improper setup is not covered by the limited warranty.
10.2.1 Burner Operation
REQUIRED TOOLS: differential pressure
gauge capable of reading negative 0.01 inches W.C. (0.002kPa), screw drivers, and combustion analyzer.
1. Using this manual, make sure the installation is complete and in full compliance with the instructions and all local codes.
2. Determine that the appliance and system are lled
with water and all air has been bled from both. Open all valves.
3. Observe all warnings on the Operating
Instructions (Start Up / Shut Down Instruction ) Decal, located on the back
of the Top Front Cover, and turn on gas and electrical power to appliance.
Page 33
The Brute Elite 125
Page 31
4. Brute Elite will enter the start sequence. Blower and pump will energize for pre-purge, then the ignition sequence starts. After all safety devices
are veried, the gas valve opens. If ignition doesn’t
occur, turn off the Brute Elite, check that there is proper gas supply. Wait 5 minutes and start the unit again.
5. Turn Brute Elite on.
6. After placing the appliance in operation, the Burner Safety Shutoff Device must be tested:
(a) Close gas shutoff valve with burner
operating.
(b) Flame will go out and blower will continue
to run for the post purge cycle. One or three additional attempts to light will follow
including pre-purge, ignitor on, valve/ame
on and post purge. Ignition will not occur as the gas is off. The ignition control will lockout.
(c) Open gas shutoff valve. Reset the boiler
control by pressing the RESET button on the control or on the display. Restart the appliance. The ignition sequence will start again and the burner will start. The appliance will return to its previous mode of operation.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a normal
manner, CLOSE MAIN SHUTOFF VALVE. Do not shut off switch. Contact your heating contractor, gas company, or factory representative.
10.2.2 Boiler Setup and Adjustment
1. Measure the CO2 in the ue products at high re.
The Brute Elite can be forced to high re to allow
for easier setup. Refer to Section 8.1, Table 11 for instructions on how to access the forced rate menu. The CO2 readings should be between the range shown in Table 13. If the CO2 is not within the range shown, adjustments may be made.
To adjust the high re CO2, locate the high re adjuster screw according to the appropriate gure.
Slowly make adjustments in 1/16 of a revolution increments until the CO2 is within the range
identied.
2. Measure the CO2 in the ue products at low re.
Brute Elite can be forced to low re to allow for
easier setup. Refer to Section 8.1, Table 11 for instructions on how to access the forced rate menu. CO2 readings should be between the range shown in Table 13. If the CO2 is not within the range shown, adjustments may be made. To adjust the
low re CO2, locate the low re adjuster screw according to the appropriate gure. Slowly make
adjustments in 1/16 of a revolution increments until the CO2 is within the range identied
(see Figure 25).
3. Repeat steps 1 and 2 to conrm that the CO2
ranges are within the required ranges. High and Low Fire CO2 settings should be approximately equal. Adjust if necessary.
If any your CO2 readings cannot be adjusted
to the specied ranges (see Table 13), please
consult the factory for further information.
10.2.3 Manifold Pressure Check
1. Remove the cap that covers the manifold pressure screw (See Figure 25). Loosen the manifold pressure screw one revolution, and attach manometer.
2. Check Manifold pressure at high re using
manometer (see Table 13 for pressure range).
3. When nished, remove manometer, tighten screw,
and replace the cap.
If your pressure reading is not within the
specied range (see Table 13), please consult the
factory for further information.
WARNING
Improper adjustment may lead to poor combustion
quality, increasing the amount of carbon monoxide
produced. Excessive carbon monoxide levels may lead to personal injury or death.
10.3 Shutting Down Brute Elite
1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain Brute Elite and be sure to also protect building piping from freezing. All water must be removed from heat exchanger and condensate trap or else damage from freezing may occur.
This step to be performed by a qualied service person.
10.4 To Restart Brute Elite
If drained, follow Section 10.1 in this manual
for proper lling and purging.
1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual reset high limit, etc.).
7. Set the temperature controller to the desired temperature setting and switch on electrical power.
8. Burner will go through a prepurge period and ignitor warm-up period, followed by ignition.
Page 34
Page 32
Bradford White Corp.
Gas Supply Line
Manifold
Pressure Screw (under cap)
Note: High and
Low Fire
CO2 settings should be approximately
equal.
O-Ring
Propane Gas Orice
High-re
setting
Low-re
setting
Figure 25. Adjustment Screws and Settings for CO
GAS TYPE
Natural 8.8
CO2 (%) RANGE
__
9.8 3.5 __ 4.5
Propane 9.8 __ 10.8 3.5 __ 4.5
Table 13. CO2 Range and Pressure Settings.
2
MANIFOLD
PRESSURE (inH20)
Page 35
The Brute Elite 125
Page 33
SECTION 11. Maintenance
WARNING
Disconnect all power to the appliance before attempting any service to the appliance. Contact with electricity can result in severe injury or death.
11.1 System Maintenance
(yearly, unless otherwise noted)
1. If a strainer is employed in a pressure reducing valve or the piping, clean it every six months.
2. Inspect the venting system for obstruction or leakage at least once a year. Periodically clean the screens in the vent terminal and combustion air terminal (when used).
3. Keep the appliance area clear and free from combustible materials, gasoline, and other
ammable vapors and liquids.
4. If the appliance is not going to be used for extended periods in locations where freezing normally occurs, it should be isolated from the system and completely drained of all water.
5. Low water cutoffs, if installed, should be checked every year. Float type low water cutoffs should be
ushed periodically.
6. Inspect and clean the condensate collection system yearly.
7. When a means is provided to neutralize condensate, ensure that the condensate is being neutralized properly.
8. Removal of burner door and inspection of
combustion coil and ue passages is required
at least once a year. Clean with a soft bristle brush / vacuum or wash with water if necessary. Sooting and buildup on the coils is an indication of improper set up and poor combustion. Determine the cause and make corrections.
9. Inspect the vent system and air intake system, and ensure that all joints are sealed properly. If joints need to be resealed, completely remove existing sealing material, and clean with alcohol. Apply new sealing material, and reassemble.
11.2 Appliance Maintenance and Component Description
Use only genuine Bradford White replacement parts.
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
Brute Elite gas and electric controls are engineered
for long life and dependable operation, but the safety of equipment depends on their proper functioning. Only
a qualied service technician should inspect the basic
items listed below every year:
a. Appliance control f. Flow switch b. Automatic gas valve g. Low water cutoff c. Pressure switches h. Burner d. Blower i. Heat exchanger e. Pump
11.2.1 Burner
Check the burner for debris. Remove the blower arm assembly to access the burner. Remove the 4 bolts connecting the blower to the arm (see Figure 32). Remove the 5 bolts, which hold the burner arm in place. Pull burner up and out. Clean burner, if necessary, by blowing compressed air from the outside of the burner into the center of the burner, and wipe the inside of the burner clean with glass cleaner. A dirty burner may be an indication of improper combustion or dirty combustion air. Determine the cause, and correct. If damaged, replace the burner gasket when replacing the burner.
NOTE: When installing the burner, make sure the ange is aligned with the mating surface, as each is keyed to control t.
11.2.2 Appliance Control
Brute Elite has an integrated control that incorporates manual reset high limit control, operating temperature control, modulating control, ignition control, outdoor reset control, pump control and many other features. If any of these features are thought to be defective, please consult the factory for proper trouble shooting practices prior to replacing the control. If control replacement is required, turn off all power to the appliance and shut off all manual gas valves to the appliance. Remove the front door to the appliance and the control panel plastic bezel. Remove all wire connections from the control board. The control board connections are keyed to only allow connection in the proper location, but proper handling techniques should be used to avoid damage to the wiring or connectors. To remove the control push in on the two tabs on the left side of the board to unlatch the clips from the control panel. Rotate the control around the fastening points on the right side of the control to remove the hooks from the control panel. To replace the control repeat the steps above in the reverse order making sure to connect all wires in the proper location. Place the appliance in operation following the steps outlined in Section 10.
11.2.3 Ignitor Assembly
The ignitor assembly is a two rod system that consists of a ground rod and a sense rod. To remove the ignitor assembly, shut off the 120 Volt power supply to the appliance. Turn off all manual gas valves connecting the appliance to the main gas supply line. Remove the front door of the boiler to gain access to the ignitor assembly. Remove the two wires connected to the assembly. Then remove the two bolts connecting the ignitor assembly to the burner door. Remove and replace the old ignitor assembly gasket. Reinstall a new ignitor assembly in the reverse order if the old assembly is determined defective. Replace gasket if necessary.
Page 36
Page 34
Bradford White Corp.
11.2.4 Flame Sensor
The ame sensor is a single rod system. To replace
the ame sensor electrode, shut off the 120 Volt power
supply to the boiler. Turn off all manual gas valves connecting the boiler to the main gas supply line. Remove the front door of the boiler to gain access to the
ame sensor electrode. Remove the ame sensor wire
from the electrode. Remove the two bolts fastening the electrode to the burner doors. Remove and replace the
old ame sensor gasket. Reinstall a new ame sensor
electrode in the reverse order if the old electrode is determined defective.
Caution
Igniters and sensors get hot and
can cause burns or injury.
11.2.5 Blower
The combustion air blower is a high-pressure centrifugal blower with a variable speed motor. Speed of the motor is determined by the control logic. 120 Volts remain on to the blower at all times. If a blower change is required, turn off the 120 Volt power and gas supply to the unit. Take the front panel off. Disconnect the 120 Volt and control signal connections from the blower. Disconnect the bolts connecting the venturi to the blower housing. Disconnect the fan outlet bolts from the burner door blower arm. If the fan is determined to be defective replace the existing fan with a new one reversing the steps above. Make sure to install all of the required O-rings and gaskets between the blower arm
and the blower and blower face and venturi ange.
11.2.6 Heat Exchanger Coils
Black carbon soot buildup on the external surfaces of the heat exchanger is caused by one or more of the following; incomplete combustion, combustion air problems, venting problems and heater short cycling. Soot buildup or other debris on the heat exchanger may
restrict the ue passages.
If black carbon soot buildup on the heat exchanger is suspected, disconnect electrical supply to the unit, and turn off the gas supply by closing the manual gas valve on the unit. Access the heat exchanger through the burner door at the front of the boiler, and inspect the
tubing using a ashlight. If there is a buildup of black
carbon soot or other debris on the heat exchanger, clean per the following:
Caution
Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or ame. To prevent this from happening, dampen the soot deposits with a wet brush or ne water spray before servicing the heat exchanger.
1. Shut off the 120 Volt power supply to the boiler
2. Turn off all manual gas valves connecting the
boiler to the main gas supply line.
3. Remove the four bolts connecting the blower
ange to the burner door arm.
4. Remove the nuts located on the outside diameter of the burner door to the heat exchanger.
5. Remove the burner door/burner assembly from the heat exchanger.
6. Disconnect the condensate drain line.
7. Attach a longer hose to drain and run to a bucket.
8. Clean the heat exchanger by brushing light accumulations of soot and debris. Use a brush with soft bristle (non metal) to avoid damaging the surface of the heat exchanger tubes.
9. Once the tubes have been brushed clean rinse the tubes and combustion chamber with a small amount of water to rinse all of the debris out of
the bottom of the ue collector and into the longer
condensate trap line, which is being diverted into a separate container.
NOTE: The Warranty does not cover damage caused by lack of required maintenance, lack of water ow, or improper operating practices.
WARNING
Failure to rinse the debris from the heat exchanger
and temporary drain line may lead to clogged
condensate lines, traps and neutralizers. Condensate pumps (if used) may also be damaged from the debris left behind, possibly causing property damage.
11. Install all components removed in the reverse order to place the appliance back in operation. Make sure all gaskets are in place as components are installed. Replace any damaged gaskets. Do NOT reuse damaged gaskets.
12. Place the appliance in operation according to
Section 10 checking all gas connections for leaks.
Conrm all fasteners are tight.
11.2.7 Gas Conversion
Brute Elite units can be converted from natural
to propane gas or from propane to natural gas easily
in the eld. If a gas conversion is performed, the unit must be identied with the appropriate gas labels and
a conversion sticker to allow technicians performing maintenance in the future to properly identify the gas type of the appliance. These stickers are included with the boiler during shipment.
WARNING
This conversion shall be installed by a qualied service agency in accordance with the manufacturer's
instructions and all applicable codes and
requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a re, an explosion or production of carbon
monoxide may result causing property damage,
personal injury or loss of life. The qualied
service agency is responsible for the proper and
complete installation of this kit. The installation is
Page 37
The Brute Elite 125
Page 35
not proper and complete until the operation of the
converted appliance is checked as specied in the manufacturer's instruction supplied with the kit.
AVERTISSEMENT
Ce conversion doit être installé par un organisme de service conformément aux instructions du fabricant et tous les codes et les exigences de l'autorité compétente. Si les informations contenues dans ces instructions n'est pas suivi à la lettre, un incendie, une explosion ou de la production de monoxyde de carbone mais résultat causant des dommages matériels, des blessures ou des pertes de vie. Le service est responsable pour la bonne et complète l'installation de ce kit. L'installation n'est pas correcte et complète jusqu'à ce que le fonctionnement de
l'appareil converti est vériée comme spécié dans le
manuel d'instruction fourni avec le kit.
Conversion to/from LP Gas Instructions:
Kit # R2075500
1. Remove the front covers.
2. Follow the shutdown procedure as indicated in the Lighting/Shutdown Instructions shown on inside front cover or side of appliance.
3. Turn off the gas supply to the boiler. Arrêtez l’approvisionnement en gaz à chaudière.
4. Turn off the main electrical supply to the boiler. Arrêtez l’alimentation électrique principale à chaudière.
5. Conrm that the actual gas supply is propane (conrm natural gas if converting to natural gas).
6. Install correct “Propane Gas” sticker over the “Natural Gas” sticker (or vice versa).
7. Fill out Gas Conversion Sticker completely and install adjacent to the rating plate sticker (behind the door panel).
8. Remove Gas Pipe from the outlet of the Gas Valve. (Note: You do not have to remove the gas valve from the unit).
9. Insert (or remove) Propane Gas Orice (Part# 12H6010) from valve outlet.
10. Ensure the gas O-Ring is in the Gas Pipe Flange Groove.
11. Re-Install Gas pipe.
12. Purge Old gas from the line.
13. Conrm Gas supply is on.
14. Connect power supply.
15. Start boiler per lighting procedure shown on inside front cover or side of appliance.
16. Check for Gas Leaks at gas valve/pipe.
17. With a combustion analyzer, check CO2 and CO levels at both maximum and minimum input.
18. Adjust as needed to achieve proper levels. Refer
to sections 10.2.2 and 10.2.3 of this manual for
the proper adjusting procedures.
19. Re-Install front covers.
SECTION 12.
Trouble Shooting
12.1 Sequence of Operation
Brute Elite is a cold start appliance that should start only on a call for heat from a tank aquastat, room thermostat, zone valve end switch or other space
temperature control device (ow switch for DHW).
1. Upon a call for heat: (a) the internal pump and
system pump will start; (b) the blower will begin a
short pre-purge.
2. Following the prepurge cycle the direct spark
ignition will spark and will begin a 4 second
trial for ignition. The unit is allowed one or three
ignition retries.
3. The gas valve will then be energized and a reduced
rate ignition will occur. The unit will remain in a
reduced rate start-up period for several seconds.
4. After the reduced rate start time is over, the
unit will be in normal operation. Firing rate
will modulate based on the heating load via the
temperature controller settings and readings.
5. When the call for heat is complete, or the unit
reaches its setpoint temperature, the gas valve will
close, and the fan will continue to run for its post-
purge. If a pump delay time is used, the pump will
continue to run for the specied amount of time
(adjustable from 0.1 to 10 minutes).
12.2 Short Cycling
Because the Brute Elite is a modulating boiler, and its input will decrease when there is a reduction in heating load, short cycling is greatly reduced. If the heating load drops below the minimum input of the boiler for an extended period, the boiler will have a tendency to short cycle. This can be a symptom of improper control or piping layout. When in DHW mode under low load conditions, the boiler will normally cycle more often, but should not cycle frequently during call for central heating.
12.3 Error Codes - See Table 14.
Page 38
Page 36
CODE# PROBLEM PROBABLE CAUSE SOLUTION
COMMON LOCKOUT CODES
Bradford White Corp.
27 Internal error Flame rod to ground Check wiring / probe grounded, dirty probe
47 Flame rod to ground leakage Faulty ame detector Clean or replace ame detector
49 24VAC voltage low/high Faulty transformer Check/correct supply line voltage; replace faulty
transformer
52 Motor tachometer fault Faulty fan / fan wiring Check fan harness wiring for continuity; replace faulty
fan circuit
53 AC inputs phase reversed Reverse 24V hot/neutral - use common ground
61 Anti short cycle Call for heat will be held Change ASC timer setting
until timer resets
62 Fan speed not proved Dirty / defective fan Clean or replace fan; check wiring
63 LCI off Safety chain interrupt Check ow switch, aux high limit, LWCO, gas pressure switches, condensate level and correct
problem
69 Outlet high limit High limit tripped Determine cause: low/no ow, valves closed, settings
and correct
79 Outlet high limit
80 DHW high limit High limit reached Check pump, time delay, valves closed, etc. and
81 Delta T inlet/outlet limit correct overtemp
82 Stack limit High limit reached Could be caused by high ambient temperature, or high return water temperature
88 Outlet T-rise limit
90 Heat exchanger high limit High limit reached Diagnose / repair cause of high temperature
91 Inlet sensor fault
92 Outlet sensor fault
93 DHW sensor fault Faulty sensor or wiring Check wiring / replace sensor; condition can be
95 Stack sensor fault caused by short
96 OAT temperature sensor fault Faulty outdoor air Check wiring and sensor for short; replace sensor
temperature sensor is open or shorted
105 Flame detected Flame exists at burner Clean burner of soot or other debris that could out of sequence when it should not be maintain ame
106 Flame lost in MFEP Unstable ame during
107 Flame lost early in Run lighting / ame proving Check venting, gas supply pressure, burner, fan, etc.
108 Flame lost in Run sequence
109 Ignition failed Problem with ignitor, or Check / replace ignitor, wiring; check for shorting
other ignition-related device in ignitor cable
113 Flame circuit timeout Flame not established Check all combustion components; purge gas; within expected time limit check ignition source
122 Lightoff rate proving failed
123 Purge rate proving failed
128 Fan speed failed / prepurge Fan did not reach Check fan wiring; replace fan
129 Fan speed failed / preignition expected RPM
130 Fan speed failed / ignition
131 Fan movement detected Fan should not be moving Check for common venting problems or otherwise during standby when not powered forced air
132 Fan speed failed during run Fan lost or gained speed Fan overheating or otherwise failing; check cable; during run sequence away replace fan
from control spec
137 ILK failed to close No power at interlock ILK Check J5 pin 1 for power - if no power, conrm
safeties are closed
49 Maximum cycle count Control operates correctly,
continued next page >
Page 39
The Brute Elite 125
CODE# PROBLEM PROBABLE CAUSE SOLUTION
ALERT CODES
Page 37
was reached however the cycle count will
not increment any higher
than 999,999 cycles Replace controller or adjust the count using blue display
50 Maximum hours count Control operates correctly,
was reached however the hours count will
not increment any higher than 999,999 hours
248 CH outdoor temperature
was invalid
251 CH ODR max outdoor temp- Conrm outdoor reset erature setpoint was invalid settings. An invalid
252 CH ODR min outdoor temp- adjustment has been erature setpoint was invalid made
253 CH ODR min water temp- erature setpoint was invalid
254 CH ODR temperature range Increase Outdoor air temp- Adjust setting to within appropriate range was too small erature min and max values (min. 12°C / 22°F) to a difference greater than 22°F (12°C)
255 CH setpoint minus ODR Increase Outdoor water min water temperature was temperature min and max too small (min. 12°C / 22°F) values to a difference greater Increase setpoint or than 22°F (12°C) decrease min water temp.
565 Heat exchanger T-rise limit Heat exchanger temperature Check for correct water ow was exceeded rise exceed
MISCELLANEOUS
Boiler will not stay lit Indicates lack of ame signal, Check ame detector wiring; clean / replace ame check fault code on display detector
Boiler bangs, knocks, hisses Insufcient water ow / Check for proper ow, follow piping guidelines in pump failure; improper piping manual; replace pump; improper glycol percentage
(see Section 6)
Flame pulsates, venting Insufcient / improper Ensure venting complies with Section 3 noise or has difculty lighting venting; dirty burner; air in gas line; dirty heat exchanger
Table 14. Error Codes.
Page 40
Page 38
Bradford White Corp.
SECTION 13.
Replacement Parts
Use only genuine Bradford White replacement parts.
13.1 General Information
To order or purchase parts for the Bradford White Brute Elite, contact your nearest Bradford White dealer or distributor. If they cannot supply you with what you need, contact Customer Service (see back cover for address, telephone and fax numbers).
13.2 Parts List
ITEM DESCRIPTION SIZE 125
PANEL ASSEMBLIES – See Figures 27-30
1 Panel, front, top, assy 12H3005
1A Panel, top, upper 12H7001
1B Screw, captive, .19 x .54 fast lead, phil pan hd F2028100
1C Screw, #8-32 x 3/8", phil pan hd F2027100
1D Gasket, strip, foam, adhesive, 3/8 x 1/8 S2113900
1E Panel, front, top, subassy 12H3015
1F Washer, retaining, .50 OD, nylon F2028200
2 Panel, front, middle, assembly, BLMH 12H3003
Panel, front, middle, assembly, BLMC 12H3033
2A Panel, front, middle, plastic 12H7002
2B Gauge, press/temp, remote A2117600
2C Switch, Rocker, 120V, amber E2335000
2D Display module, electronic RE2333500
2E Hinge, front panel, middle 12H3008
2F Circuit Breaker, 10 Amp, 120V E2318900
2G Circuit Breaker, 2A, 120V E2335100
2H Support, middle panel 12H3017
2I Screw, #6 x 3/8" thd forming for plastic 1-418
2J Screw, #8-32 x 3/8", phil pan hd F2027100
2K Rivet, pop, 3/16 diameter F2015900
2L Latch, magnet, .56 dia, 3.1 lbs F2028300
2M Harness, wire, power switch/circuit breaker E2334501
2N Harness, wire, display/+24V circuit breaker E2334502
3 Panel, front, bottom, assembly 12H3004
3A Control, programmed 12H7050
3B Bracket, mounting, control 12H7004
3C Panel, front, bottom, plastic 12H7003
3D Hinge, front panel, bottom 12H3007
3E Rivet, pop, 3/16 diameter
3F Screw, #8-32 x 3/8", phil pan hd
3G Washer, retaining, .50 od, nylon
3H Screw, captive, .19 x .54 fast lead, phil pan hd
4 Panel, left side 12H3019
5 Panel, right side 12H3018
ITEM DESCRIPTION SIZE 125
BASE JACKET ASSEMBLY - see Figure 31
6 Base, jacket, assembly 12H3001
6A Base, jacket 12H3011
6B Screw, 8-32unc x 1.5l F2001900
6C Bracket, wall attach 12H3012
6D Screw, hex head, 1/4-20 unc x .75" lg. F2011600
6E Nut, ange, serrated, hex head, 1/4" 10-103
6F Bracket, hx, right side 12H3010
6G Bracket, hx, left side 12H3016
6H Screw, #8-18 x 1/2, phil pan hd F2027000
6I Switch, pressure, air/gas, inlet E2334900
6J Transformer,40Va, 115V/24V R0021300
6K Bracket, transformer 12H3009
6L Rivet, pop, 3/16 diameter F2015900
HEAT EXCHANGER CABINET - see Figure 32
7A Grommet, pipe, wire, multi size, rubber S2114000
7B Heat exchanger S2113800
7BB Gasket, vent adapter 12H5501
7C Washer, clamping, hx bracket 12H3023
7D Washer, M5, lock, internal tooth F2023700
7E Screw, M5-0.8 X 14mm, soc Hd F2025300
7G Gasket, blower fan S2105400
7H Screw, #8-18 x 1/2, phil pan hd F2027000
7I Vent, air, auto, 1/4" bspp P2074500
7J Pipe, air vent 12H4010
7K Sensor, temperature, water, 1/4" npt RE2320600
7L Rivet, pop, 3/16 diameter F2015900
7M Terminal, 1/4" push-on, male, red E0005501
7N Heat exchanger S2113800
7O Blower, combustion air RA2107500
7P Washer, sealing, .410 OD F2027700
7Q Plate, venturi 12H5002
7R Screw, m5 x 8, soc hd cap F2029300
7S O-ring, 2 1/8 id x 3/32 thick S2116000
7T Adapter, vent, cpvc 12H5500
7U Plug, hex, 1/8" npt 500-168
7V Sensor, temperature, air, 1 /4" bsp, 1.85 l RE2319700
7W Sensor, temperature, water, duplex RE2319900
Page 41
The Brute Elite 125
ITEM DESCRIPTION SIZE 125 ITEM DESCRIPTION SIZE 125
BURNER COMPONENTS - see Figure 33
1 Burner, main R2069102
2 Gasket, burner RS2108500
3 Tile, refractory, front, combustion chamber RT2109000
4 Ignitor, spark, w/gasket R2069300
5 Flame sensor, w/gasket R2069200
6 Burner door with gaskets RS2108300
7 Air/gas channel RS2108400
8 Screw, air/gas channel RS2109400
10 Heat exchanger RS2111200
11 Gasket, ignitor RW2013300
12 Burner door, w/gaskets 62108300
13 Repair kit, rear refractory tile R50D2021
14 Gaskets-only (burner door)
15 Screw, ignitor/ame sensor, M4-.7X8MM
16 Ignitor gasket RW2013300
17 Flame/sensor gasket RW2013400
PUMP ASSSEMBLY - see Figure 34
8 Pump assembly
8A Bracket, control valve 12H4012
8B Trap, condensate, small capacity A2117500
8C Screw, M4 x 10, soc hd cap F2029400
8D Valve, gas V2020600
8E Bumper, rubber, 21/32" base dia. x 1/2"
height, 5/32" thru hole S2114800
8F Washer, sealing, 0.93 OD x 0.62 ID contact
8G Pipe, 3 way valve to dhw factory
8H Bracket, 3 way valve 12H4019
8I Screw, #8-18 x 1/2, phil pan hd F2027000
8J Bracket, capture, hex 12H4022
8K Valve, three way, with actuator A2117802
8L Pump A2117700
8M Screw, 6-20 x 1/2" l self tapping F0024200
8N Sensor, temperature, dhw, 1/4" npt E2337500
8O Exchanger, heat, plate
8P Tie, cable, 14-3/4 long x 0.31" wide,
heat stabilized F2029100
8Q Flow switch, water E2337400
8R Pipe, tailpiece, 1" npt M x 3/4 tube, cu 12H4023
8S O-ring, -120, 1" ID x 1-3/16" OD S2116300
8T Pipe, pvc, 3/4" sch 40 P2067603
8U Terminal, 1/4" push-on, male, red E0005501
8V Terminal, 1/4" push-on, female, red E0005502
PLUMBING COMPONENTS - see Figure 35
P1 Tank, expansion, rect, 10 liter A2117400
P2 Bracket weldment, expansion tank 12H3020
P3 Grommet, pipe, wire, multi size, rubber S2114000
P4 Pipe, gas 12H4011
P5 O-ring, 20.04 mm ID x 27.10 mm OD S2115100
P6 Pipe, pump to hx inlet 12H4004
P7 Pipe, hx outlet to dhw 12H4001
P8 Switch, press, 3-30 psi, 1/4" bspp P2074600
P9 Gasket, expansion tank 12H3006
P10 Tee, 1/4" barb, plastic 10-596
P11 Washer, sealing, .59 OD x .32 ID x .06 poly F2027500
P12 Pipe, expansion tank 12H4006
P13 Washer, sealing, 0.93 OD x 0.62 ID F2025502
P14 Washer, sealing, .410 OD F2027700
P15 Switch, pressure, 3.80" w.c. set point E2336500
P16 Hose, drain, condensate 12H2500
P17 Tie, cable, heat stabilized, 5" F2028400
P18 Tube, silicone, .188 ID x .318 OD x 23" long Q0078800
P19 Cotter pin, horse shoe, 1/8, zinc pl F2029000
Not Shown:
Harness, wire, main E2337600
Connector assembly 12H7009
Relay, 24vac, Dpdt 8 12H7008
Harness, wire, main, heat only 2 12H7010
Harness, wire, main, BLMC E2337600
Wire, spark ignition 12H7005
Wire assy, ame sensor 12H7006
Plug, 3 prong, with cord, 14 awg 7 E2334500
Page 39
Figure 27. Outside Panels.
Page 42
Page 40
Bradford White Corp.
Figure 28. Panel Assembly, Door Top.
Page 43
The Brute Elite 125
Page 41
Figure 29. Panel Assembly, Door Middle.
Page 44
Page 42
Bradford White Corp.
Figure 30. Panel Assembly, Door Bottom.
Page 45
The Brute Elite 125
Page 43
Figure 31. Base Jacket Assembly.
Page 46
Page 44
Bradford White Corp.
Figure 32. Heat Exchanger Cabinet, Fan.
Page 47
The Brute Elite 125
Page 45
Figure 33. Heat Exchanger Burner Components.
Page 48
Page 46
Bradford White Corp.
Figure 34. Pump Assembly Components.
Page 49
The Brute Elite 125
Page 47
Figure 35. Plumbing Components.
Page 50
Page 48
Bradford White Corp.
Page 51
The Brute Elite 125
Page 49
Page 52
Dimensions and specications subject to change without notice in accordance with our policy of continuous product improvement.
Ambler, PA 19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020 www.BradfordWhite.com
Warranty Service (800) 531-2111 Litho in U.S.A. © Bradford White 1401 Document 1281D
H2364500A
Loading...