Bradford-White BRHHV, BRHHH User Manual

Installation and Operation Instructions Docyment 1246
Installation and Operation Instructions for
BRUTE MAGNUM
Modulating Boiler Model BRHHH
Modulating Water Heater Model BRHHV
U.S. Patent No. 6,644,393 Canada Patent Pending
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
AVERTISSEMENT
H2343400-
238-49223-00A REV 4/11
Page 2
BRADFORD WHITE CORP.
Brute Magnum
Page 3
Table of Contents
SECTION 1 General Information
1.1 Introduction ...................................................... 5
1.2 Model Identification .......................................... 5
1.3 Warranty .......................................................... 6
1.4 Dimensions ...................................................... 6
1.5 Locating the Appliance..................................... 6
1.6 Locating Pump-Mounted Water
Heater with Respect to Storage Tank(s) .......... 6
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header ................... 6
1.8 Locating Appliance for Correct Vent Distance
From Outside Wall or Roof Termination ........... 7
SECTION 2 Venting and Combustion Air
2.1 Combustion Air ................................................ 8
2.1.1 Combustion Air From Room ............................ 8
2.1.2 Intake Combustion Air...................................... 8
2.2 Venting ............................................................. 9
2.3 Locating Vent & Combustion Air Terminals ...... 9
2.3.1 Horizontal Vent Terminal .................................. 9
2.3.2 Side Wall Combustion Air Terminal ................ 12
2.3.3 Vertical Vent Terminal .................................... 12
2.3.4 Vertical Combustion Air Terminal ................... 12
2.4 Common Vent Test – Boilers ......................... 12
SECTION 3 Gas Supply and Piping
3.1 Gas Supply and Piping .................................. 13
SECTION 4A Water Connections – BRHHH Boiler
4A.1 Heating System Piping:
Hot Supply Connections – Boiler ................... 14
4A.2 Cold Water Make-Up – Boiler ........................ 14
4A.3 Freeze Protection – Boiler ............................. 15
SECTION 4B Water Connections – BRHHV Water Heater
4B.1 Water System Piping – Water Heater ............ 15
4B.2 Hot Water Supply Piping – Water Heater ...... 15
4B.3 Water Flow Requirements – Water Heater .... 16
4B.4 Combined Water (potable)
Heating and Space Heating ........................... 18
4B.5 Freeze Protection — Water Heater ............... 19
SECTION 5 Electrical Connections
5.1 Main Power .................................................... 24
5.2 Pump Connections ........................................ 24
5.3 Temperature Control – Boiler ......................... 24
5.4 Temperature Control – Water Heater ............. 24
5.4.1 Remote Water Heater Temperature Control .. 24
5.4.2 Internal Water Heater Temperature Control ... 25
5.5 Temperature Control Features ....................... 25
5.5.1 Temperature Setpoint .................................... 25
5.5.2 Differential Setting ......................................... 25
5.5.3 Offset ............................................................. 26
5.5.4 Throttling Range ............................................ 26
5.5.5 Minimum Output Setting ................................ 27
5.5.6 Integration Constant ...................................... 27
5.6 Mixing System and Control ............................ 28
5.7 External Control Connections ........................ 29
5.8 Wiring Diagrams ............................................ 29
SECTION 6 Operating Instructions
6.1 Filling the Boiler System ................................ 36
6.2 Operating the Burner and Set Up .................. 36
6.3 Shutting Down the Brute Magnum ................. 38
6.4 To Restart the Brute Magnum ........................ 38
SECTION 7 Maintenance
7.1 System Maintenance ..................................... 38
7.2 Appliance Maintenance and
Component Description ................................. 38
7.2.1 Burner ............................................................ 40
7.2.2 Filter ............................................................... 40
7.2.3 Modulating Gas Valve .................................... 40
7.2.4 Safety Gas Valve ........................................... 41
7.2.5 Manual Reset High Limit Control ................... 41
7.2.6 Temperature Control ...................................... 41
7.2.7 Auto Reset Temperature Limit ....................... 41
7.2.8 Mixing Control ................................................ 41
7.2.9 Mixing Valves ................................................. 41
7.2.10 Mixing Actuator .............................................. 42
7.2.11 Ignition Control............................................... 42
7.2.12 Ignitor / Flame Sensor Assembly ................... 42
7.2.13 Transformers ................................................. 42
7.2.14 Blower ............................................................ 42
7.2.15 Flow Switch .................................................... 42
7.2.16 Heat Exchanger Coils .................................... 42
7.2.17 Normally Open Vent Valve ............................. 43
7.2.18 Motorized Safety Valve .................................. 43
7.2.19 Gas Pressure Switches ................................. 43
SECTION 8 Troubleshooting
8.1 Sequence of Operation .................................. 43
8.2 Resolving Lockouts........................................ 44
8.3 Delayed Ignition – Possible Causes .............. 44
8.3.1 High Lockup Pressure (LP Appliances)
- Occurs on Start-up ...................................... 44
8.3.2 Gas Valve Regulation .................................... 44
8.3.3 Defective Burner - Occurs on
Startup or at Burner Shutdown ...................... 44
8.4 Short Cycling – Boiler .................................... 44
8.5 Short Cycling – Water Heater ........................ 45
8.6 High Gas Consumption.................................. 45
SECTION 9 Replacement Parts
9.1 General Information ....................................... 45
9.2 Parts List ........................................................ 45
Page 4
List of Tables
Table 1 Clearances ........................................................6
Table 2 Vent / Air Pipe Sizes .......................................... 7
Table 3 Horizontal Vent and Air Terminals
for Indoor Installations ....................................... 8
List of Figures
BRADFORD WHITE CORP.
Table 4 Required Combustion Air Piping Material..........9
Table 5 Required Venting Material .................................9
Table 6 Gas Piping Sizes ............................................. 13
Table 7 Air & Gas Orifice Differentials at Full Fire ........ 38
Figure 1 Dimensional Drawing ........................................7
Figure 2 Combustion Air and Vent Through Roof ............ 8
Figure 3 Combustion Air and Vent Through Side-Wall ..10
Figure 4 Hydronic Piping – Multiple Boilers ...................16
Figure 5 Hydronic Piping – Multiple Boilers (Alternate) . 17
Figure 6 Hydronic Piping – One Boiler,
Multi-Temperature System ..............................18
Figure 7 Internal Piping Schematic................................19
Figure 8 Water Heater Piping – One Heater, One Tank ....20
Figure 9 Water Heater Piping – Multiple Heaters,
One Tank .........................................................21
Figure 10 Water Heater Piping – One Heater,
Multiple Tanks ..................................................22
Figure 11 Water Heater Piping – Multiple Heaters,
Multiple Tanks ..................................................23
Figure 12 Temperature Control........................................24
Figure 13 Proprotional Control ........................................25
Figure 14 Control Parameter Graph ................................ 26
Figure 15 Control Parameter Graph ................................ 27
Figure 16 Control Parameter Possible Interference ........28
Figure 17 Wiring Diagram, Size 1200,
Standard and Codes A and F ..........................30
Figure 18 Wiring Diagram, Sizes 1600, 2000 and
2400, Standard and Codes A and F ................31
Figure 19 Wiring Diagram Size 1200, Code B.................32
Figure 20 Wiring Diagram, Sizess 1600, 2000 and
2400, Code B ..................................................33
Figure 21 Wiring Schematic, Size 1200,
Standard and Codes A and F ..........................34
Figure 22 Wiring Schematic, Sizes 1600, 2000 and
2400, Standard and Codes A and F ................34
Figure 23 Wiring Schematic, Size 1200, Code B ............35
Figure 24 Wiring Schematic, Sizes 1600, 2000 and
2400, Code B ..................................................35
Figure 25 Gas/Air Test Panel ...........................................37
Figure 26 Test Panel Valves ............................................ 37
Figure 27 Gas Trains .......................................................39
Figure 28 Gas Trains .......................................................40
Figure 29 Control Panel...................................................41
Figure 30 Combustion Components ................................49
Figure 31 Gas Train/Combustion Air Components .......... 50
Figure 32 Gas Train Components ...................................51
Figure 33 Electrical Components ....................................52
Figure 34 Heat Exchanger / Water Path Components ....53
Figure 35 Heat Exchanger / Water Path Components ....54
Figure 36 Jacket Components.........................................55
Brute Magnum
Page 5
Section 1 GENERAL INFORMATION
USING THIS MANUAL – Because the Brute Magnum Boilers and Brute Magnum Water Heaters are identical appliances, with the exception of materials of manufacture, labels and ultimate use application, this manual provides information for the proper installation, operation and maintenance of both products. Where differences exist between the application of the appliances and their operation, the sections pertinent to only one appliance or the other will be so identified.
WARNING
The Brute Magnum hydronic, boiler or water heater must be installed in accordance with the procedures detailed in this manual, or the Bradford White warranty will be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CSA B149.1 Natural Gas and Propane Gas Installation Code, and/ or local codes. Where required by the authority having jurisdiction, the installation of Brute Magnum boilers must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modifications to the boiler, its gas controls, or wiring may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Bradford White Brute Magnum (copper tube or cupronickel tubes) appliances. Read it carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Bradford White factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by
improper installation.
The Brute Magnum appliance is protected against over pressurization. A pressure relief valve is fitted to all appliances. It is installed inside the jacket, at the water outlet of the unit. (See Sections 4A and 4B for instructions on how to install a relief valve outlet.)
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance with 1) American National Standard Z223.1/NFPA54­Latest Edition “National Fuel Gas Code” or 2) CSA B149.1 “Natural Gas and Propane Installation Code” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1) The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be electrically grounded in accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following information describes the model number structure.
(1-3) Model Series Designation B R H = Brute Magnum mid-sized commercial
(3) Model Efficiency H = High Efficiency (condensing)
(4) Usage H = Hydronic V = Volume Water (5-8) Size 1 2 0 0 = 1,200,000 BTU/hr input 1 6 0 0 = 1,600,000 BTU/hr input 2 0 0 0 = 2,000,000 BTU/hr input 2 4 0 0 = 2,400,000 BTU/hr input
(9) Fuel N = Natural Gas P = Liquid Propane
(10) Altitude A = Universal Altitude (0' – 10,000') (0m – 3050m)
(11) Location I = Indoor
(12) Firing Mode F = Modulating
Model Designation
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
B R H H 0 0 A I F
SERIES
R H H
USAGE
H
V
SIZE
1 2 0 0
1 6 0 0
2 0 0 0
2 4 0 0
FUEL
N
P
ALTITUDE
A
LOCATION
I
FIRING
MODE
F
REVISION
1
2
HEAT
EXCHANGER
E
F
OPTIONS
X A B F
PUMP
N H
Page 6
BRADFORD WHITE CORP.
(13) Revision 2 = Second version
(14) Heat Exchanger E = Glass-lined steel with copper tubes F = Glass-lined steel with cupronickel tubes
(15) Control Option Code X = Standard, meets CSD-1 boiler standard A = Control Pack A: CSD-1, CA, FM, IL, IRI, Alarm Bell B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN F = Non CSD-1
(16) Pump Options N = Pump mounted, normal pump (standard) H = Pump mounted, hard water pump (BRHHV)
1.3 Warranty
Bradford White’s Brute Magnum appliances are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Bradford White.
All warranty claims must be made to an authorized Bradford White representative or directly to the factory. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
1.4 Dimensions
The overall dimensions are 34.5" (88cm) wide, 65.75" (167cm) tall, 55" (140cm) deep. Other dimensions can be found in Figure 1.
1.5 Locating the Appliance
The Brute Magnum is for indoor installations only.
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certified by CSA­International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves.
Brute Magnum Boilers or Water Heaters must never be installed on carpeting. The location for the
appliance should be chosen with regard to the vent pipe lengths and external plumbing. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Brute Magnum must be located as close as practical to a chimney or gas vent. If the vent terminal and/ or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade.
The dimensions and requirements that are shown in Table 1 should be met when choosing the locations for the appliance:
Appliance Clearance From Suggested Service Surface Combustible Material Clearance
inches inches
Piping Side 1 18 Opposite Side 1 1 Top 1 24 Back 1 36 Front 1 36 Vent per UL1738 venting system supplier’s instructions
Table 1. Clearances.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results the Brute Magnum water heater should be located within 15 feet (4.6m) of the storage tank(s). The pump is sized for 30 feet (9.1m) of piping.
Water heater pumps are sized for water hardness;
7.6 to 17 grains per gallon for normal water, greater than 17 grains per gallon for hard water, and 1 to
7.5 grains per gallon for soft water. If the appliance must be installed with longer piping runs, then larger diameter pipe or tubing may be able to be used, in some instances. Consult the factory for assistance.
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
Brute Magnum units must be piped in primary­secondary fashion because of the internal pump and mixing system.
For the best results the Brute Magnum Boiler should be located within 15 feet (4.6m) of the supply and return headers. The pump is sized for 30 feet (9.1m) of piping, in most cases, enough for primary­secondary piping systems.
If the appliance must be installed with longer piping runs, then larger diameter tubing may be able to be used, in some instances. Consult the factory for assistance.
Brute Magnum
Page 7
“V”
Vent Outlet
Size
1200 6 6 2-1/2” 1’ 1-1/2’ 1-1/2” 34-1/4”
1600 6 8 2-1/2” 1-1/2’ 2” 2’ 34-1/4”
2000 7 8 3” 1-1/2’ 2” 2” 34-1/4”
2400 10 8 3” 1-1/2” 2” 2” 32”
Figure 1. Dimensional Drawing.
Size Intake Exhaust Intake Exhaust Size Size Maximum Run Maximum Run 1200 6" (15 cm) dia. 6" (15 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows 1600 8" (20 cm) dia. 6" (15 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows 2000 8" (20 cm) dia. 7" (18 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows 2400 8" (20 cm) dia. 10" (25 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows
Connection
inches inches NPT NPT NPT NPT inches
“A”
Air Inlet
Connection
“W”
Water Inlet/ Outlet Connection
Table 2. Vent / Air Pipe Sizes.
“G” Gas Connects.
Control Packages
Std & A Nat/ LP
B & E
Nat
B & E
LP
“B”
1.8 Locating Appliance for Correct Vent Distance From Outside Wall or Roof Termination
The forced draft combustion air blower in the
appliance has sufficient power to vent properly when the guidelines in Table 2 are followed.
NOTE: When located on the same wall, the Brute Magnum combustion air intake terminal must be installed a minimum of 12" (30cm) below the exhaust vent terminal and separated by a minimum of 36 inches (91cm) horizontally.
Page 8
BRADFORD WHITE CORP.
Section 2 VENTING AND COMBUSTION AIR
2.1 Combustion Air
Brute Magnum boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.
A Brute Magnum unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.
2.1.1 Combustion Air From Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Method 1: Two permanent openings, one commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
2.1.2 Intake Combustion Air
The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in Table 3. See Table 2 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2).
Figure 2. Combustion Air and Vent Through Roof.
Use single-wall galvanized pipe for the combustion air intake (see Table 4), sized per Section
1.8. Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Up to five elbows can be used with the 50 feet of pipe. Subtract 10 allowable linear feet for every additional elbow used.
The connection for the intake air pipe is in the back of the unit. Take the plate off the back to reveal the collar on the filter box. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.
Horizontal Combustion Horizontal Vent
Size
Air Terminal Terminal 1200 20260701 D2004500 1600 20260703 D2004500 2000 20260703 D2004600 2400 20260703 D2006200
Table 3. Horizontal Vent and Air Terminals
for Indoor Installations.
Brute Magnum
Page 9
Term Description
Pipe Single-wall galvanized steel pipe, 24 gauge
minimum (sized per section 1.9)
Joint Permanent duct tape or aluminum tape Sealing
Insulation Not required, but recommended R5 insulation
for cold installations (consult American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) handbook
Table 4. Required Combustion Air Piping Material.
In addition to air needed for combustion, air shall also be supplied for ventilation, including all air required for comfort and proper working conditions for personnel. The Brute Magnum loses less than 1 percent of its input rating to the room, but other heat sources may be present.
2.2 Venting
The Brute Magnum is a Category IV appliance and must be installed with a stainless steel venting system that complies with the UL 1738 Standard (see Table 5). It must be installed per this installation manual and the venting system manufacturer’s Installation Instructions. The unit’s vent can terminate through the roof, or through an outside wall. It can be installed through walls that are from 3" (7.6cm) to 12" (30cm) in thickness.
See Table 2 to select the appropriate vent pipe diameter. The vent pipe must be pitch upward, toward the vent terminal, so that condensate will run back to the Brute Magnum, to drain. Route the vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Horizontal runs must slope upwards not less than ¼ inch per foot (21mm/m) from the unit to the vent terminal. Up to five elbows can be used with the 50 feet (15.2m) of pipe. Subtract 10 allowable linear feet for every additional elbow used.
IMPORTANT NOTE ABOUT COMMON VENTING:
A single vent that is shared by multiple Brute Magnum units MUST be engineered by a competent venting specialist, and involves the selection of draft inducing equipment, hardware and controls to properly balance flue gas pressures. Do not common vent
Brute Magnum units unless the vent system meets this requirement. Brute Magnum units are never permitted to share a vent with Category I appliances.
A condensate drain is built into the Brute Magnum. A pressure switch monitors the condensate drain pan, and will trip if the condensate level gets too high. This will prevent the Brute Magnum from firing if there is a blockage or overflow.
Connect a clear plastic tube, minimum 3/8" diameter, between the drain connection and a floor drain (or condensate pump if a floor drain is not accessible).
Caution
Condensate is mildly acidic, and may harm some floor drains and/or pipes, particularly those that are metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity, or neutralize the condensate before disposal. Damage caused
by failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer’s responsibility.
A neutralizer kit is available from Bradford White. The kit includes a condensate pump.
The condensate tray must be primed before starting the unit. Fill the tray with water through the exhaust vent connection on the back of the unit. Continue filling until water flows out of the condensate drain port. This prevents the flue gases from escaping through the condensate drain. The condensate drain must be installed so as to prevent accumulation of condensate. When a condensate pump is not used, the tubing must continuously slope downward (except for the trap loop) toward the drain with no spiraling.
Consult local codes for disposal method.
Term Description
Venting Sealed stainless steel system certified to UL1738.
Insulation Not required, but recommended R5 insulation with protective cover for cold installations (consult American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) handbook)
Table 5. Required Venting Material.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Horizontal Vent Terminal
The appropriate side wall vent hood must be used, and is listed in the installation and operation manual. The terminal provides a means of installing the vent piping through the building wall, and must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 or .2 and local applicable codes. Consider the following when installing the terminal:
Page 10
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm) deck, or balcony
B= Clearance to window or door that may be 4 feet (1.2 m) below or to side of opening; 36 inches (91 cm) opened 1 foot (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal See note 4 See note 5 distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet above
extended above meter/regulator assembly See note 4 the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply inlet to building or the combustion air inlet to 4 feet (1.2 m) below or to side of opening; 36 inches (91 cm) any other appliance 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances. A vent shall not L= Clearance above paved sidewalk or paved for category IV appliances. For Category III terminate directly above a sidewalk or paved
driveway located on public property appliances, vent must terminate at least 7 driveway that is located between two single feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings. For Category III appliances that do not violate the previous condition, vent must terminate at least 7 feet (2.13m) above the sidewalk or driveway.
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3) or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas supplier.
BRADFORD WHITE CORP.
Figure 3. Combustion Air and Vent Through Side Wall.
*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet.
Brute Magnum
Page 11
1. The figure in this addendum shows the requirements for mechanical vent terminal clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.
3. Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. Whenever possible, locations under windows or near doors should be avoided.
5. Locate the vent terminal so that it cannot be blocked by snow. The installer may determine that a vent terminal must be higher than the minimum shown in codes, depending upon local conditions.
6. Locate the terminal so the vent exhaust does not settle on building surfaces or other nearby objects. Vent products may damage such surfaces or objects.
7. If the boiler or water heater uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard-wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard-wired carbon monoxide detectors.
a. In the event that the side wall horizontally
vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this
subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS
Each carbon monoxide detector as required
in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE
A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (½) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS."
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontal vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
Page 12
BRADFORD WHITE CORP.
(c) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fuel gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The identification of each “special venting
system” shall include either the listing of the website, phone number or manufacturer’s address where the venting system installation instructions can be obtained; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions provided with that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the
Product Approved side wall horizontally vented gas fueled equipment, and all the venting instructions, parts lists, and/or design instructions for the venting system shall remain with the appliance or equipment at the completion of the installation.
Contact factory with questions about venting
system installation.
2.3.2 Side Wall Combustion Air Terminal
The side wall combustion air terminal (see Table
4) must be used when the heater takes air from a
side wall. Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorine compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism. It must be at least 7 feet (2.1m) above a public walkway.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
4. If the Brute Magnum is side-wall vented to the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal (see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
2.4 Common Vent Test — Boilers
NOTE: This section does not describe a method for
common venting Brute Magnum units. It describes what must be done when a unit is removed from a common vent system. Brute Magnum units require special vent systems and fan for common vent. Contact the factory if you have questions about common venting Brute Magnum units.
When an existing boiler is removed from a
common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
Brute Magnum
Page 13
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Installation
Codes. When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size
as determined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1 NFPA 54 and/or CSA B149.1, Installation Codes.
Section 3 GAS SUPPLY AND PIPING
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not the appliance.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Appliances are normally equipped to operate at elevations up to 2000 feet (610m). However, the appliance will function properly without the use of high altitude modification at elevations up to 10,000 feet (3050 m).
2. The maximum inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet natural gas pressure is 4" W.C. (1.0kPa) and minimum inlet propane gas pressure is 6" (1.5kPa).
3. Refer to Table 6, size supply.
4. Run gas supply line in accordance with all applicable codes.
Note: If you have a boiler/water heater with
a normally open vent valve, install a vent line from the vent valve to an outside location as required by your installation code or IRI requirement. Do not remove 3/4 inch pipe
plug from the vent valve if venting from the normally open vent valve is not required by your installation code.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
Size and Gas Type
1200 natural 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm 1200 propane 1-1/2" 3.8cm 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm 1600 natural 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm 1600 propane 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm 2000 natural 3" 7.6cm 3" 7.6cm 3" 7.6cm 3-1/2" 8.9cm 2000 propane 2-1/2" 6.4cm 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm 2400 natural 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm 3-1/2" 8.9cm 2400 propane 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm
Distance from Gas Meter or Last Stage Regulator
0-50 feet 0-15m 50-100 feet 15-31m 100-200 feet 31-61m 200-300 feet 61-91m
Notes: 1. These figures are based on 1/2" 0.12kPa water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.
Table 6. Gas Piping Sizes.
Page 14
BRADFORD WHITE CORP.
7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Open flame can cause gas to ignite and result in property damage, severe injury, or loss of life.
NOTE: The Brute Magnum appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line. A bleed line from the diaphragm-type automatic valve shall be vented per local code requirements. Brute Magnum units are equipped with low and high gas pressure switches that are integrally vent limited. These types of devices do not require venting to atmosphere.
Section 4A WATER CONNECTIONS — BRUTE MAGNUM BOILER
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" (2.5cm) clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event of pressure relief. Install an air purger, an air vent, a diaphragm-type expansion tank, and a hydronic flow check in the system supply loop. Minimum fill pressure must be 12psig (82.7kPa). Install shutoff valves where required by code.
Suggested piping diagrams are shown in Figures 4, 5, and 6. These diagrams are meant only as a guide. Components required by local codes must be properly installed. The Brute Magnum boiler’s efficiency is higher with lower return water temperatures. Therefore, to get the most of low return temperature with multiple boilers, pipe as shown in Figure 4.
The Brute Magnum boiler has an internal mixing system that ensures that the condensation does not occur on the finned copper heat exchanger, with boiler return temperature down to 50°F (10°C). This
system, that consists of automatically actuated and linked valves, is set up at the factory, and is non-adjustable. The return water goes through the
stainless steel heat exchanger, then to the mixing system (see Figure 7).
If the water at the inlet of the copper heat exchanger is less than 140°F (60°C), water from the outlet of the copper heat exchanger will be directed back to the inlet of the copper heat exchanger, and will mix to bring the inlet water up to 140°F (60°C). Once through the copper heat exchanger, the water picks up another 20-25°F (11-14°C) (when at high fire), and it leaves the boiler at 160-165°F (71-74°C). This hot water is then sent to the system.
If the water at the inlet of the copper heat exchanger is 140°F (60°C), or higher, the water will be allowed to flow through the copper heat exchanger and directly to the outlet of the Brute Magnum, and there will be a 20-25°F (11-14°C) temperature rise between the inlet and outlet of the unit, when the unit is at high fire.
The pump in the boiler is sized for the boiler’s heat exchangers, the internal mixing system, and 30 feet of full-sized piping, with a normal number of fittings taken into consideration. The piping must be primary/secondary, ensuring that the boiler’s pump is only used for the boiler, and that the system pump(s) do not interfere with the Brute Magnum pump or mixing system.
The minimum inlet water temperature for the Brute Magnum is 50°F (10°C) to avoid condensing on the copper coils.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a refrigeration system, must be installed so the chilled
Brute Magnum
Page 15
medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling appliances where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A boiler installed above radiation level, or as required by the authority having jurisdiction, must be provided with a low water cutoff device either as a part of the boiler or at the time of boiler installation.
4A.3 Freeze Protection – Boiler
Brute Magnum units are not designed to be placed outdoors, due to the potential for condensate to freeze in the unit.
Proper precautions for freeze protection are recommended for boiler installations in areas where the danger of freezing exists.
Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc., may prevent a boiler from firing. Any time a
boiler is subjected to freezing conditions, and the boiler is not able to fire, and/or the water is not able to circulate, there is a risk of freezing in the boiler or in the pipes in the system. When water freezes,
it expands. This can result in bursting of pipes in the system, or damage to the boiler, which could result in leaking or flooding conditions.
Do not use automotive anti-freeze. Maintaining a mixture of minimum 50% water and maximum 50% properly inhibited HVAC glycol, which contains an antifoamant, is the preferred method of freeze protection for Brute Magnum boilers. The percentage
of glycol used in the Brute Magnum boiler must not exceed 50%. Typically, this mixture will
serve as burst protection for temperatures down to approximately –35°F (-30°C).
IMPORTANT NOTES: Different glycol products may provide varying degrees of protection. Glycol products must be maintained properly in a heating system, or they may become ineffective. Consult the glycol specifications, or the glycol manufacturer, for information about specific products, maintenance of solutions, and set up according to your particular conditions.
For installations where temperatures are expected to fall below 15°F inside the boiler cabinet, the actuating gas valve must be equipped with a gas valve heater, part number R2010100. Note that some gas trains such as the IRI option may have double actuators, and may require 2 gas valve heaters.
Section 4B WATER CONNECTIONS — BRUTE MAGNUM WATER HEATER
4B.1 Water System Piping — Water Heater
Hot water piping should be supported by suitable hangers or floor stands. Do not support piping with this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed.
The Brute Magnum can be used with several different types of readily available storage tanks. A pump draws water from the storage tank and pumps the water through the heater and back into the tank. Pump-mounted units have a circulating pump built into the water heater.
Pipe the outlet from the heater’s relief valve such that any discharge from the relief valve will be conducted to a suitable place for disposal when relief occurs. Do not reduce line size or install any valves in this line. The line must be installed to allow complete drainage of both the valve and the line.
Suggested piping diagrams are shown in Figures 8, 9, 10, and 11. These diagrams are meant only as a guide. Components required by local codes must be properly installed.
The minimum inlet water temperature for the Brute Magnum is 50°F (10°C) to avoid condensing on the copper coils.
4B.2 Hot Water Supply Piping — Water Heater
Follow the tank manufacturer’s guidelines for completion of the hot water system connections.
NOTE: A listed temperature and pressure relief valve listed as complying with the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, 1). ANSI Z21.22 latest edition, or 2). CSA 4.4, of suitable discharge capacity must be installed in the separate storage tank system.
If the Brute Magnum water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold water supply line, the relief valve may discharge periodically, due to thermal expansion. Means (such as a properly-sized expansion tank) shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation.
Page 16
BRADFORD WHITE CORP.
Figure 4. Hydronic Piping - Multiple Boilers.
4B.3 Water Flow Requirements — Water Heater
In a water heating application (an open system), new water is constantly being introduced. With the new water comes a fresh supply of minerals that can be deposited on the unit’s heat exchanger. This is commonly known as scaling. The amount of minerals will depend upon the hardness of the water. Water can also be aggressive, and can erode metals, including copper, if the water is moved too quickly. Pump sizing for the Brute Magnum water heater is based upon the hardness of the water. The water flow is kept high enough to prevent scaling, but low enough to prevent
tube erosion. For extremely soft or hard water, cupro­nickel tubes are available. Contact a Bradford White Representative if you have questions or concerns about water quality.
The Brute Magnum water heater has an internal mixing system that ensures that the condensation does not occur on the finned copper heat exchanger, with heater return temperature down to 50°F (10°C). This
system, that consists of automatically actuated and linked valves, is set up at the factory, and is non-adjustable. The return water goes through the
stainless steel heat exchanger, then to the mixing system. (see Figure 7).
Brute Magnum
Page 17
Figure 5. Hydronic Piping — Multiple Boilers (Alternate).
If the water at the inlet of the copper heat exchanger is less than 140°F (60°C), water from the outlet of the copper heat exchanger will be directed back to the inlet of the copper heat exchanger, and will mix to bring the inlet water up to 140°F (60°C). Once through the copper heat exchanger, the water picks up another 20-25°F (11-14°C) (when at high fire), and it leaves the boiler at 160-165°F (71-74°C). This hot water is then sent to the system.
If the water at the inlet of the copper heat exchanger is 140°F (60°C), or higher, the water will be allowed to flow through the copper heat exchanger and
directly to the outlet of the Brute Magnum, and there will be a 20-25°F (11-14°C) temperature rise between the inlet and outlet of the unit, when the unit is at high fire.
The pump in the heater is sized for the heater’s heat exchangers, the internal mixing system, and 30 feet of full-sized piping, with a normal number of fittings taken into consideration.
The minimum inlet water temperature for the Brute Magnum is 50°F (10°C) to avoid condensing on the copper coils.
Loading...
+ 39 hidden pages