Bradford-White BNTV, BNTH User Manual

Page 1
Installation and Operation Instructions Document 1243
Installation and Operation Instructions for
BRUTE ELITE
Modulating Boiler Model BNTH
Sizes 080–850 MBTU/h
Water Heater Model BNTV
Sizes 150–850 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
If the information in this manual is not
WARNING
followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
AVERTISSEMENT
H2343100-
238-49220-00A REV 4/11
Page 2
Page 2
BRADFORD WHITE CORP.
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction...................................................... 4
1.2 Model Identification ......................................... 4
1.3 Appliance Overview ......................................... 4
1.4 Warranty .......................................................... 9
1.5 Unpacking ....................................................... 9
1.6 Dimensions...................................................... 9
SECTION 2. Locating the Appliance
2.1 Locating the Appliance .................................. 11
2.2 Locating Appliance for Correct Vent Distance
from Outside Wall or Roof Termination ......... 11
Section 3. Venting and Combustion Air
3.1 Combustion Air .............................................. 12
3.1.1 Combustion Air From Room .......................... 12
3.1.2 Ducted Combustion Air ................................. 12
3.2 Venting .......................................................... 13
3.2.1 Venting Requirements Unique to Canada ..... 14
3.3 Locating Vent & Combustion Air Terminals ... 14
3.3.1 Side Wall Vent Terminal ................................ 14
3.3.2 Side Wall Combustion Air Terminal ............... 15
3.3.3 Vertical Vent Terminal ................................... 15
3.3.4 Vertical Combustion Air Terminal .................. 15
3.3.5 Installations in the Commonwealth of
Massachusetts .............................................. 15
3.4 Common Vent Test ....................................... 17
Section 4. Gas Supply and Piping
4.1 Gas Supply and Piping .................................. 18
Section 5. Pump Requirements
5.1 Brute Elite Boiler Flow and
Head Requirements ...................................... 19
5.2 Brute Elite Water Heater
Flow and Head Requirements ....................... 19
Section 6A. Water Connections -
6A.1 BNTH System Piping: Hot Supply Connections20
6A.2 BNTH Cold Water Make-Up .......................... 20
6A.3 Freeze Protection .......................................... 21
6A.4 BNTH Suggested Piping Schematics ............ 21
6A.5 Recognized Chemicals.................................. 21
BNTH Boiler
Section 6B. Water Connections -
6B.1 BNTV Water Quality ...................................... 29
6B.2 Piping Requirements ..................................... 29
6B.3 Cold Water Make-Up ..................................... 30
6B.4 Freeze Protection .......................................... 30
6B.5 BNTV Suggested Piping Schematics ............ 30
6B.6 BNTV Suggested Pumps .............................. 30
BNTV Water Heater
Section 7. Electrical Connections
7.1 Main Power ................................................... 32
7.2 Pump Connections ........................................ 33
7.3 24 Vac Transformer with Integral
Circuit Breaker............................................... 33
7.4 Hydronic Call for Heat ................................... 33
7.5 Outdoor Air Temperature Sensor .................. 33
7.6 Domestic Hot Water Connection ................... 33
7.7 System Sensor
(lead lag/cascading operation only)............... 33
7.8 External Control Connections ........................ 33
7.9 Optional Field Connections ........................... 33
7.10 Lead lag/ Cascading Wiring Connections ..... 33
7.11 Wiring Diagrams ............................................ 35
Section 8. Brute Elite Control Setup and Operation
8.1 Display Navigation ......................................... 37
8.2 Ignition Control - Sequence of Events ........... 37
8.3 Modulation Control ........................................ 38
8.4 Pump Control ................................................ 38
8.5 Anti-Short Cycle (ASC) .................................. 38
8.5 High Limit ...................................................... 38
8.7 Outlet Water Temperature ............................. 38
8.8 Inlet Water Temperature ............................... 38
8.9 Heat Exchanger Temperature Rise ............... 38
8.10 Stack Temperature ........................................ 38
8.11 Domestic Hot Water Temperature ................. 38
8.12 Lead Lag/Cascading ..................................... 38
8.12.1 Lead Lag Setpoint ......................................... 39
8.12.2 Lead Lag Master/Slave Selection .................. 39
8.12.3 Lead Lag Address ......................................... 39
8.12.4 Lead Lag Hysteresis ...................................... 39
8.12.5 Lead Lag Base Load Setting ......................... 39
8.13 Boiler Pump Interrupt .................................... 39
Page 3
Brute Elite
Page 3
SECTION 9. Modes of Operation
9.1 Hydronic Heating Demand ............................ 40
9.2 Hydronic Heating with Outdoor Reset ........... 40
9.3 Hydronic Heating with Domestic Hot
Water (DHW) Priority ..................................... 40
9.4 Hydronic Heating Using External
Modulation Control ........................................ 40
9.5 Hydronic Heating Using Local Lead-Lag/
Cascading Feature ........................................ 41
9.6 Hydronic Heating Using Local Lead-Lag/ Cascading Feature with Indirect Hot Water ... 41
9.7 Warm Weather Shutdown ............................. 41
9.8 Domestic Hot Water Demand (BNTV only) ... 41
9.9 Domestic Hot Water Heating Using
External Modulation Control .......................... 42
9.10 Domestic Hot Water Heating Using Local
Lead-Lag/Cascading Feature ........................ 42
Section 10. Operating Instructions
10.1 Filling the Boiler System ................................ 43
10.2 Operating the Burner and Set Up .................. 43
10.2.1 Burner Operation ........................................... 43
10.2.2 Boiler Setup and Adjustment ......................... 44
10.3 Shutting Down Brute Elite.............................. 44
10.4 To Restart Brute Elite .................................... 44
SECTION 11. Maintenance
11.1 System Maintenance ..................................... 46
11.2 Appliance Maintenance and Component
Description .................................................... 46
11.2.1 Burner............................................................ 46
11.2.2 Modulating Gas Valve / Venturi ..................... 46
11.2.3 Appliance Control .......................................... 46
11.2.4 Ignitor Assembly ............................................ 47
11.2.5 Flame Sensor ................................................ 47
11.2.6 Transformer with Integral Circuit Breaker ...... 48
11.2.7 Blower ........................................................... 48
11.2.8 Heat Exchanger Coils.................................... 48
11.2.9 Gas Pressure Switches (optional) ................. 49
11.2.10 Gas Conversion ............................................. 49
Section 12. Trouble Shooting
12.1 Sequence of Operation ................................. 49
12.2 Short Cycling ................................................. 49
12.3 Error Codes ................................................... 49
Section 13. Replacement Parts
13.1 General Information ....................................... 52
13.2 Parts List ....................................................... 52
Page 4
Page 4
BRADFORD WHITE CORP.
SECTION 1. General Information
WARNING
Brute Elite units must be installed in accordance with the procedures detailed in this manual, or the Bradford White warranty will be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CSA B149.1 Natural Gas and Propane Gas Installation Code, and/or local codes. Where required by the authority having jurisdiction, the installation of Brute Elite boilers must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modifications to the boiler, its gas controls, or wiring may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Bradford White Brute Elite appliances. Read it carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Bradford White factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
Brute Elite is protected against over pressurization. A pressure relief valve is included with each Brute Elite. Some Brute Elites may require that the PRV be installed prior to filling the system. Refer to Figures 1-7 for PRV locations.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest Edition “National Fuel Gas Code” or 2) CSA B149.1 “Natural Gas and Propane Installation Code” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1) The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be electrically grounded in accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following information describes the model number structure.
(1-3) Model Series Designation
B N T = Brute Elite
(4) Usage
H = Hydronic V = Volume Water
(5-7) Size
0 8 0 = 80,000 BTU/hr input 1 0 5 = 105,000 BTU/hr input 1 5 0 = 150,000 BTU/hr input 1 9 9 = 199,000 BTU/hr input 2 1 0 = 210,000 BTU/hr input 2 8 5 = 285,000 BTU/hr input 3 9 9 = 399,000 BTU/hr input 5 0 0 = 500,000 BTU/hr input 6 0 0 = 600,000 BTU/hr input 7 5 0 = 750,000 BTU/hr input 8 5 0 = 850,000 BTU/hr input
(8) Fuel
N = Natural Gas P = LP Gas
(9) Options Code
X = Standard Unit C = Canadian D = Canadian CSD-1 J = CSD-1, FM, GAP, IL Code
(10) Pump Options
N = Pump included X = No pump (285-850)
(11) Revision
2 = Second version
(80-500 only)
(size 500-850 only)
Model Nomenclature
1 2 3 4 5 6 7 8 9 10 11
B N T 2
SERIES
B N T
USAGE
H - HYDRONIC
V - VOLUME
WATER
SIZE
MBTU/h
0 8 0 1 0 5 1 5 0 1 9 9 2 1 0 2 8 5 3 9 9 5 0 0 6 0 0 7 5 0 8 5 0
FUEL
N - NATURAL
P - PROPANE
OPTIONS CODE
X - STANDARD
C - CANADIAN
D - CANADIAN,
CSD-1
J - CSD-1,
FM, GAP,
(500-850 only)
IL
PUMP OPTIONS
N - PUMP INCL.
(80-500 only)
X - NO PUMP
(285-850)
REVISION
2 - SECOND
Page 5
Brute Elite
Page 5
Figure 1. Location of Components, Sizes 80–105.
Figure 2. Location of Components, Sizes 150-210.
Page 6
Page 6
BRADFORD WHITE CORP.
Figure 3. Location of Components, Size 285.
Figure 4. Location of Components, Size 399.
Page 7
Brute Elite
Page 7
Figure 5. Location of Components, Size 500.
Figure 6. Location of Components, Size 600.
Page 8
Page 8
BRADFORD WHITE CORP.
Figure 7. Location of Components, Sizes 750 and 850.
Page 9
Brute Elite
Page 9
1.3 Appliance Overview
See Figures 1 through 7.
1.4 Warranty
Bradford White’s Brute Elite appliances are
covered by a limited warranty.
All warranty claims must be made to an authorized Bradford White representative. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items may be shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment whether visible or concealed.
1.5 Unpacking
The Brute Elite is shipped in a single crate with the following standard components packed with the appliance (see Figure 8):
A. exhaust vent terminal
(US only)
B. air intake terminal
C. temperature/pressure gauge kit
D. circulator pump/wire harness
(units with pump)
E. CPVC exhaust pipe section (80-500) (US only)
F. outdoor/system sensor kit
G. flow switch kit
(399-850)
H. alternate size vent/terminal screens
J. exhaust vent adapter CPVC/ST ST
(750-850)
K. 4x6 PVC adapter with 4x7 PVC pipe section
(750-850) (not to be used on exhaust in Canada)
1. Remove all packing and tie-down materials.
2. Check contents of the carton against items shown.
1.6 Dimensions
Dimensions are shown in Figure 9.
Figure 8. Contents of Shipping Package.
Page 10
Page 10
BRADFORD WHITE CORP.
W L H AIR INLET VENT GAS
SIZE IN CM IN CM IN CM IN CM IN CM NPT
CONNECTIONS
80 25 64 19½ 49 38¼ 97 2 5.1 2 5.1 ½
105 25 64 19½ 49 38¼ 97 2 5.1 2 5.1 ½
150 25 64 19½ 49 38¼ 97 3 7.6 3 7.6 ½
199/ 210 25 64 26¾ 68 38¼ 97 3 7.6 3 7.6 ½
285 25 64 26¾ 68 38¼ 97 11 11 ¾
399 25 64 31½ 80 38¼ 97 11 11 ¾
500 25 64 37¾ 96 38¼ 97 11 11 1
600 25 64 37¾ 96 38¼ 97 11 11 1
750 25 64 51 130 38¼ 97 11 17
850 25 64 55¼ 130 38¼ 97 11 17
Dimensions are nominal and are shown in inches, cm.
Brute Elite is shipped with adapters for the air and vent that accept
*
standard pipe of the proper size and type.
AB C D E F G J K M N
SIZE IN CM IN CM IN CM IN CM IN CM IN CM IN CM IN CM IN CM IN CM IN CM
80 BNTH 13½ 34 24 18¼ 46 19 10¾ 28 11¾ 30 13¾ 35 21 53 10¾ 27 15¼ 39 13 33
105 BNTH 13½ 34 8 21 18¼ 46 6 16 10¾ 28 11¾ 30 14¼ 36 21 53 22 15¼ 39 13 33
150 BNTH 13¼ 34 14 18¼ 46 8 10¾ 28 19 14¼ 36 19½ 49 19 15¼ 39 13 33
150 BNTV 13¼ 34 14 19 48 8 10¾ 28 19 14¼ 36 19½ 49 19 15¼ 39 13 33
210 BNTH 20½ 52 14 18¼ 46 8 17¾ 45 19 14¼ 36 19½ 49 11¾ 30 15¼ 39 13 33
199 BNTV 20½ 52 14 19 48 8 17¾ 45 19 14¼ 36 19½ 49 11¾ 30 15¼ 39 13 33
285 BNTH 20¼ 52 19 19¼ 49 16 11¼ 29 13½ 34 14 36 15 38 17 43 18¾ 48 13 33
285 BNTV 20¼ 52 19 19¾ 50 16 11¼ 29 13½ 34 14 36 15 38 17 43 18¾ 48 13 33
399 BNTH 25 64 13 19¼ 49 11 14¾ 37 18½ 47 19¼ 49 16½ 42 21¾ 55 18¾ 48 13 33
399 BNTV 25 64 13 19¾ 50 11 14¾ 37 18½ 47 19¼ 49 16½ 42 21¾ 55 18¾ 48 13 33
500 BNTH 30¼ 77 13 19½ 50 11 15¼ 38 20 51 20½ 52 19 48 26 66 18¾ 48 13 33
500 BNTV 30¼ 77 13 19¾ 50 11 15¼ 38 20 51 20½ 52 19 48 26 66 18¾ 48 13 33
600 (both) 29¾ 76 5 13 19½ 50 11 15 38 20 51 3 8 19 48 26 66 18¾ 48 21
750 (both) 35½ 90 6 15 19½ 50 13 19 48 40½ 103 8 19 48 30¾ 78 18¾ 48 21
(both) 39¾ 101 6 15 19½ 50 13 19 48 44¾ 114 9 19 48 35 89 18¾ 48 21
850
Figure 9. Dimensional Drawing, Sizes 80-500.
Page 11
Brute Elite
SECTION 2. Locating the Appliance
Page 11
2.1 Locating the Appliance
Brute Elite is for indoor installations only.
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certified by CSA­International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves. Brute
Elite Boilers must never be installed on carpeting.
The location for the appliance should be chosen with regard to the vent pipe lengths and external plumbing and on a level surface. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Brute Elite must be located as close as practical to the vertical section of the vent. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade or the maximum expected snow line.
The dimensions and requirements that are shown in Table 1 should be met when choosing the locations for the appliance.
2.2 Locating Appliance for Correct Vent
Distance from Outside Wall or
Roof Termination
The forced draft combustion air blower in the appliance has sufficient power to vent properly when the guidelines in Table 2 are followed.
NOTE: When located on the same wall, the Brute Elite combustion air intake terminal must be installed a minimum of 12" below the exhaust terminal.Models 399­850 also require a minimum horizontal distance from intake to exhaust terminal of 36".
For concentric vent terminal kit (optional), follow installation instructions included with the kit.
APPLIANCE SURFACE INCHES CM
Left Side 1 2.5
Right Side 12 31
Top 24 61
Back 6 15
Closet, Front (285-500) 6 15
Alcove, Front (285-500) 24 61
Front (600-850) 24 61
Vent
Certified by CSA for zero clearance to
STANDARD MAX EQUIV. OPTIONAL MAX EQUIV.
SIZE VENT FT. M VENT FT. M
80 2" 40 6.1 3" 100 30.5
105 2" 40 6.1 3" 100 30.5
150 3" 100 30.5 n/a
199/ 210 3" 100 30.5 n/a
285 4" 100 30 n/a
399 4" 100 30 n/a
500 4" 100 30 n/a
600 4" 100 30 n/a
750 4" 40 6.1 6" 100 30
850 4" 40 6.1 6" 100 30
Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless steel complying with UL1738. Installations in Canada require exhaust vent pipe that is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM D1527 or
galvanized material.
Installer must comply fully with manufacturer's installation instructions, including use of minimum exhaust length CPVC, to maintain ANSI Z21.13 safety certification.
Closet and alcove installations do not allow the use of PVC under any circumstances
To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each elbow used.
SUGGESTED SERVICE ACCESS CLEARANCE
combustible materials on all sides.
Table 1. Clearances.
INTAKE / EXHAUST
Table 2. Vent / Air Pipe Sizes.
Page 12
Page 12
BRADFORD WHITE CORP.
SECTION 3. Venting and Combustion Air
3.1 Combustion Air
Brute Elite boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.
A Brute Elite unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.
3.1.1 Combustion Air From Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS
2" PVC 3" PVC 4" PVC 6" PVC
SIZE
105 included optional optional optional n/a n/a
150 n/a n/a included optional n/a n/a
199/210 n/a n/a included optional n/a n/a
285 n/a n/a optional optional included n/a
399 n/a n/a n/a n/a included n/a
500 n/a n/a n/a n/a included n/a
600 n/a n/a n/a n/a included optional
750 n/a n/a n/a n/a n/a included
850 n/a n/a n/a n/a n/a included
Concentric vent terminal = 10 ft. pipe length.
Standard Concentric Standard Concentric Standard Standard
CA006000 CA005900 239-44069-01
80 included optional optional optional n/a n/a
Table 3a. PVC Vent Terminal Kits.
Method 1: Two permanent openings, one commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
3.1.2 Ducted Combustion Air
The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in Table(s) 3. See Table 2 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure10).
Use ABS, PVC, CPVC or galvanized pipe for the
SIZE Boiler Flue Intake Air Boiler Intermediate Flue Intake Air Boiler Flue Intake Air
399-600 F303759
750-850
MATERIAL UNITED STATES CANADA
ABS ANSI/ASTM D1527
PVC, sch 40 ANSI/ASTM D1785 or D2665
CPVC, sch 40 ANSI/ASTM F441
Single wall galv. steel 26 gauge
PRO TECH (FasNSeal) HEAT FAB (Saf-T-Vent) Z FLEX (Z-Vent)
Adapter Termination Termination Adapter Adapter Termination Termination Adapter Termination Termination
F303759
(intake only)
FSBS4 FSAIH04
FSRC4(R.C) 303888 5400CI 2SVSRCX04
FSBS6
FSAIH04
303888 Table 3b. Approved Stainless Steel Terminations and Adapters.
Table 4. Required Combustion Air Pipe Material.
KB285600 9454BUREZ-1*
INSTALLATION STANDARDS
9492
9414TERM 2SVSLA04
Air pipe material must be chosen
based upon the intended application of the boiler.
2SVSTP04
2SVSTEX0490
Page 13
Brute Elite
Page 13
combustion air intake (see Table 4), sized per Table 2. Route the intake to the boiler as directly as possible. Seal all joints. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is shown in Table 2. Subtract 5 allowable linear ft. (1.5m) for every elbow used.
The connection for the intake air pipe is at the top of
the unit (see Figure 9a or Figure 9b).
In addition to air needed for combustion, air shall also be supplied for ventilation, including air required for comfort and proper working conditions for personnel.
3.2 Venting
WARNING
Failure to use CPVC or stainless steel venting for the first 20" (285-600) / 30" (80-210) of vent material or for any part of the venting that is installed inside a closet may lead to property damage, personal injury or death. The proper length of this material is supplied with boiler. Boilers in U.S. may use pipe included with boiler.
WARNING
Failure to use the appropriate vent material, installation techniques, glues/sealants could lead to vent failure causing property damage, personal injury or death.
The unit’s vent can terminate through the roof, or
through an outside wall.
When using PVC/CPVC for vent material, venting must be connected to the CPVC section included with Brute Elite sizes 80-600. The CPVC vent section included with the Brute Elite may be broken by CPVC fittings if necessary, but never reduced in total length. See Table 2 to select the appropriate vent pipe diameter. Vent pipe must pitch upward, toward the vent terminal, not less than 1/4" per foot, so that condensate will run back to the Brute Elite to drain. Route vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Please see Table 2 for proper diameter vs. length allowed.
IMPORTANT NOTE ABOUT COMMON VENTING: A single vent that is shared by multiple Brute Elite units MUST be engineered by a competent venting specialist, and involves the selection of draft inducing equipment, hardware and controls to properly balance flue gas pressures. Do not common vent Brute Elite
WARNING
All venting must be installed according to this manual and any other applicable local codes, including but not limited to, ANSI Z223.1/NFPA 54, CSA B149.1, CSAB149.2 and ULC-S636. Failure to follow this manual and applicable codes may lead to property damage, severe injury, or death.
The flue temperature of the Brute Elite changes dramatically with changes in operating water temperature. Therefore, it is necessary to assess the application of the boiler to determine the required certified vent class. If the Brute Elite is installed in an application where the ambient temperature is elevated, and/or installed in a closet/alcove, CPVC or stainless steel material is required. If the system temperatures are unknown at the time of installation, class IIB or higher venting material is recommended.
The Brute Elite is a Category IV appliance and may be installed with PVC and CPVC that complies with ANSI/ASTM D1785 F441, or a stainless steel venting system that complies with UL 1738 Standard (see Table 5).
Figure 10. Combustion Air and Vent Through Roof.
INSTALLATION STANDARDS
MATERIAL UNITED STATES CANADA
Stainless Steel UL 1738
PVC, sch 40 ANSI/ASTM D178 venting material. The venting material must be chosen
CPVC, sch 40 ANSI/ASTM F441
Table 5. Required Exhaust Vent Material.
Venting must be ULC-S636 certified for use as
based upon the intended application of the boiler.
Page 14
Page 14
BRADFORD WHITE CORP.
units unless the vent system meets this requirement. Brute Elite units are never permitted to share a vent with Category I appliances.
A condensate drain trap is built into Brute Elite.
Connect a 3/4" PVC pipe between the drain connection and a floor drain (or condensate pump if a floor drain is not accessible).
The condensate drain must be installed so as to prevent accumulation of condensate. When a con­densate pump is not used, the tubing must continuously slope downward toward the drain with no spiraling.
Consult local codes for disposal method.
Caution
Condensate is mildly acidic (pH some floor drains and/or pipes, particularly those that are metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity, or neutralize the condensate before disposal. Damage caused by
failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer’s responsibility.

5), and may harm

3.2.1 Venting Requirements Unique to Canada
Brute Elite boilers and water heaters are Vent Category IV appliances. Per the requirements of CAN/ CSA-B149.1, only BH vent systems can be connected to these units and such vent systems, either ULC S636 certified stainless steel or other ULC S636 certified BH vent (eg. plastics) must be installed per the vent manufacturer's certified installation instructions.
As a result, two items listed in the Unpacking section (Figure 8) are
not included with Brute Elite
units for Canada (underlined):
A. exhaust vent terminal (not included)
B. air intake terminal
C. temperature/pressure gauge kit
D. circulator pump/wire harness (units with pump)
E. CPVC exhaust pipe section (80-500) (not incl.)
F. outdoor/system sensor kit
G. flow switch kit (399-850)
H. alternate size vent/terminal screens
J. exhaust vent adapter CPVC/ST ST (750-850)
It is the responsibility of the appropriately licensed technician installing this Brute Elite unit to use ULC S636 certified vent material consistent with the requirements as described in the Venting and Combustion Air section.
IMPORTANT! It is also the responsibility of the installer to ensure that a flue gas sampling port is installed in the vent system. This flue gas sampling port must be installed near the flue connection of the Brute Elite unit: within 2 feet of the flue connection. There is no flue gas sampling port internal to the Brute Elite, so
one must be installed in the vent system external to the Brute Elite unit. A flue gas sampling port available as a component of the ULC S636 certified vent system is preferred. However, if one is not available with the certified vent system, Bradford White suggests using a tee with the branch connection sized to allow for insertion of a flue gas analyzer probe. The branch connection must be resealable with a cap or other by other means to ensure the vent system remains sealed
(Figure 11).
Consideration must be given to the placement and orientation of the flue gas sampling port to ensure that condensate is free to flow back into the Brute Elite unit and not collect anywhere in the vent system - including in the flue gas sampling port.
An exhaust vent terminal must be installed. If an exhaust vent terminal is not available with the certified vent system, Bradford White suggests the use of a coupler fitting from the certified vent system into which the vent terminal screen, included with the Brute Elite and shown in the Unpacking section of the Brute Elite Installation & Operating Instructions, be installed. Be sure to install and terminate both vent and combustion air pipes per the Venting and Combustion Air section of the Brute Elite instructions.
3.3 Locating Vent & Combustion Air
Terminals
3.3.1 Side Wall Vent Terminal
The appropriate Bradford White side wall vent terminal must be used. The terminal must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 or .2 and local applicable codes. Consider the following when installing the terminal:
Figure 11. Test Port.
Page 15
Brute Elite
Page 15
1. Figure 12 shows the requirements for mechanical vent terminal clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.
3. Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. Whenever possible, avoid locations under windows or near doors.
5. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine that a vent terminal must be higher than the minimum shown in codes, depending upon local conditions.
6. Locate the terminal so the vent exhaust does not settle on building surfaces or other nearby objects. Vent products may damage surfaces or objects.
7. If the boiler or water heater uses ducted combustion air from an intake terminal located on the same wall, see Figures 12-14 for proper spacing and orientation.
If the vent termination is located in an area
exposed to high winds, an optional PVC tee (the same diameter as the vent pipe) may be used. The tee'd vent termination offers greater protection from wind related operating issues.
3.3.2 Side Wall Combustion Air Terminal
The side wall combustion air terminal, or
concentric terminal (see Table 3), must be used when the heater takes air from a side wall. Contact Bradford White for AL29-4C termination fittings. Consider the following when installing the terminal (see Figures 12-
14):
1. Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorine compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism. It must be at least 7 feet (2.1m) above a public walkway.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
4. If the Brute Elite is side-wall vented to the same wall, locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.
5. For concentric vent, follow instructions
included with vent kit.
6. Multiple vent kits should be installed such that the horizontal distance between outlet group and inlet group is 36" (90cm) (see Figure 13).
7. Vent outlet for models 80-285 must be no lower than the center of the air inlet, and must be at least
12" (30cm) away from the air inlet. Vent outlets for models 399-850 must be at least 12" above the top of the air inlet, and must be at least 36" (90cm) horizontally from the air inlet (see Figure 14).
3.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. The vent terminal included with the Brute Elite can be used in both vertical and horizontal applications. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 11).
3.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 11). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
3.3.5 Installations in the Commonwealth of Massachusetts
In Massachusetts the following items are required if the side-wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches. From Massachusetts Rules and regulations 248 CMR 5.08
1. Installation of Carbon Monoxide Detectors
At the time of installation of the side wall vented gas fueled appliance, the installing plumber or gas­fitter shall observe that a hard-wired carbon monox­ide detector with an alarm battery back-up is instal­led on the floor level where the gas appliance is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall hori­zontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for in­stallation of hard-wired carbon monoxide detectors. a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of the subdivi­sion cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements,
Page 16
Page 16
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
deck, or balcony See note 6 See note 6
B= Clearance to window or door that may be Direct vent only: 12 inches (30cm); 36 inches (91 cm)
opened Other than Direct vent: 4 ft (1.2m) below or to
side of opening; 1 ft (30cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal See note 4 See note 5 distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner 3 feet minimum 3 feet (91cm) minimum
H= Clearance to each side of center line 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly See note 4 above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to nonmechanical air supply Direct vent only: 12" (30cm) 80-285; 36" (91cm)
inlet to building or the combustion air inlet 399-850. Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm) to any other appliance or to side of opening; 1 ft (30cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in this
driveway located on public property for category IV appliances. location for category IV appliances.
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas supplier.
6. IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have more specific requirements, and must be consulted.
BRADFORD WHITE CORP.
Figure 12. Combustion Air and Vent Through Side Wall.
*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet.
Page 17
Brute Elite
Figure 13. Multiple Side-Wall Terminals, Air and Vent.
provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm be installed.
2. Approved Carbon Monoxide Detectors Each carbon monoxide detector shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print no less than
Page 17
one-half (1/2) inch in size: "GAS VENT DI­RECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS".
4. Inspection The state or local gas inspector of the side-wall horizontally vented gas fueled appliance shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1-4.
3.4 Common Vent Test
NOTE: This section does not describe a method for
common venting Brute Elite units. It describes what must be done when a unit is removed from a common vent system. Brute Elite units require special vent systems and fans for common vent. Contact the factory if you have questions about common venting Brute Elite units.
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Figure 14. Minimum Venting Distance.
Page 18
Page 18
BRADFORD WHITE CORP.
3. Insofar as it is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as deter­mined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1 NFPA 54 and/or CSA B149.1, Installation Codes.
SECTION 4. Gas Supply and Piping
4.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not the appliance.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Brute Elite will function properly without the use of high altitude modification at elevations up to 10,000 feet (3050 m).
2. The maximum inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet gas pressure is 4" W.C. (1.0kPa).
3. Refer to Tables 6A, 6B, 6C and 6D to size piping.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kPa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kPa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING:
Open flame can cause gas to ignite and result in property damage, severe injury, or loss of life.
NOTE: The Brute Elite appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line. Some Brute Elite units are equipped with low and high gas pressure switches that are integrally vent limited. These types of devices do not require venting to atmosphere.
Page 19
Brute Elite
Page 19
BRUTE ELITE
NATURAL GAS
REQUIRED
CU FT
SIZE / HR.
80 80 105 105 150 150
199/210 199/210
285 285 399 399 500 500 600 600 750 750
850 850
TO SIZE PIPING:
Measure linear distance from meter outlet to last boiler. Add total input of all boilers and divide by 1000 to obtain cu ft / hr required. Add total equivalent length of fittings used according to Table 6B. Align total length (pipe and fittings) on left side column of Table 6C with highest cubic feet of gas required.
Notes:
Consult and confirm with Applicable Fuel Gas Code before beginning work. Verify gas inlet pressure is between 4 and 13 in W.C. before starting boiler.
Table 6A.
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS
FITTING 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
90° ELBOW 3.6 4.4 5.2 6.6 7.4 8.5
TEE 4.2 5.3 6.6 8.7 9.9 12
NOMINAL PIPE SIZE
LINEAR FEET
Table 6B.
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS
NOMINAL PIPE SIZE @ 0.30" W.C. PRESSURE DROP
LENGTH 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
FT CUBIC FEET OF GAS PER HOUR
20 92 190 350 730 1100 2100
40 130 245 500 760 1450
60 105 195 400 610 1150
80 90 170 350 530 990
100 150 305 460 870
Table 6C.
SECTION 5. Pump Requirements
5.1 Brute Elite Boiler Flow and Head Requirements
20°F 25°F 30°F 35°F 40°F
FLOW H/L FLOW H/L FLOW H/L FLOW H/L FLOW H/L
SIZE GPM FT GPM FT GPM FT GPM FT GPM FT
80 7.6 14.9 6.1 10.1 5.1 7.1 4.3 5.8 3.8 4.6 105 10 23.1 8 17 6.7 12.4 5.7 9.6 5 7.6 150 14.3 28.5 11.4 19 9.5 13.6 8.1 11.2 7.1 8.8 210 20 24.1 16 16.7 13.4 11.6 11.3 9 9.9 6.9 285 27 25.5 22 17.5 18 14 15 10.5 13 8 399 39 28 31 20 25 14.5 22 11 19 9 500 48 24 38 16 32 12 27 9 24 8 600 58 44 46 31 38 22 33 18 29 15 750 72 37 58 23 48 17 41 13 36 10
850 81 33 65 22 54 15 46 10 41 8
11°C 14°C 17°C 19°C 22°C
FLOW H/L FLOW H/L FLOW H/L FLOW H/L FLOW H/L
SIZE lpm m lpm m lpm m lpm m lpm m
80 29 4.5 23 3.1 19 2.2 16 1.8 14 1.4 105 38 7.0 30 5.2 25 3.8 22 2.9 19 2.3 150 54 8.7 43 5.8 36 4.1 31 3.4 27 2.7 210 76 7.3 61 5.1 51 3.5 43 2.7 37 2.1 285 102 7.8 83 5.3 68 4.3 57 3.2 49 2.4 399 148 8.5 117 6.1 95 4.4 83 3.4 72 2.7 500 182 7.3 144 4.9 121 3.7 102 2.7 91 2.4 600 220 13.4 174 9.4 144 6.7 125 5.5 110 4.6 750 273 11.3 220 7.0 182 5.2 155 4.0 136 3.0
850 307 10.1 246 6.7 204 4.6 174 3.0 155 2.4
(see Table 7)
TEMPERATURE RISE IN °F
TEMPERATURE RISE IN °C
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP
SIZE 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR
UNDILUTED PROPANE
20 200 418 787 1616 2422 4664
40 137 287 541 1111 1664 3205
60 110 231 434 892 1337 2574
80 94 197 372 763 1144 2203
100 84 175 330 677 1014 1952
NOTES: 1. Follow all local and national LP gas codes for line sizing and equipment requirements. 2. Verify that inlet gas pressure remains between 4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
Table 6D.
Table 7. Water Flow Requirements.
5.2 Brute Elite Water Heater Flow and Head Requirements
Flow H/L Temp Flow H/L Temp
Size gpm feet Rise °F lpm m Rise °C
150 19 57 15 72 17.4 8 199 25 28 15 95 8.5 8 285 36 33 15 98 10.1 8 399 50 35 15 189 10.7 8 500 63 28 15 239 8.5 8 600** 60 24 19 227 7.3 11 750** 68 35 21 257 10.7 12
850** 68 26 24 257 7.9 13
*Maximum water hardness of 10 grains per gallon allowed. **See section 6B.6 on page 30 for pump information.
Table 8. Brute Elite Water Heater Flow Data.
(see Table 8)
NORMAL WATER*
Page 20
Page 20
BRADFORD WHITE CORP.
SECTION 6A. Water Connections -
Section 6 is divided into two parts. The first is for BNTH models and is Section 6A. The second is for BNTV models and is Section 6B. Refer to the proper section for instructions in installing and piping your product. Refer to
Table 9 for pipe sizes required.
6A.1 BNTH System Piping:
Hot Supply Connections
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa) static pressure at the boiler.
Hot water piping should be supported by suitable hangers or floor stands. Do not support piping with this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" (2.5cm) clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a drain or in a manner to prevent injury in the event of pressure relief. Install an air purger, an air vent, a diaphragm-type expansion tank, and a hydronic flow check in the system supply loop. Minimum fill pressure must be 12psig (82.7kPa). Install shutoff valves where required by code.
Suggested piping diagrams are shown in Figures
15 through 21. These diagrams are meant only as a
guide. Components required by local codes must be properly installed.
BNTH Boiler
Brute Elite's efficiency is higher with lower
return water temperatures. Therefore, to get the most
of low return temperature with multiple boilers, pipe as shown in Figures 17-19.
Brute Elite BNTH models can be ordered with or
without a pump included.
Brute Elite with a pump MUST be piped in a primary-secondary fashion (using either piping or a hydraulic separator) such that the pump that is mounted on the boiler ONLY serves the boiler.
When the pump is supplied by Bradford White, the Brute Elite boiler must be located within 15 feet (4.6m) of the supply and return header (or the hydraulic separator). Pumps supplied by Bradford White are sized for a maximum of 30 feet (9.1m) of piping and the headloss of the boiler only (see Table 7).
If longer pipe lengths are required, the pump should be sized for the boiler per Table 7 and for the piping it will serve, and should be supplied to job separately. Even with pumps supplied by others, Bradford White strongly recommends primary­secondary piping.
6A.2 BNTH Cold Water Make-Up
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling appliances where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A boiler installed above radiation level, or as required by the authority having jurisdiction, must be provided with a low water cutoff device either as a part of the boiler or at the time of boiler installation.
BNTH PIPE SIZE, BNTV PIPE SIZE,
SIZE INCHES SIZE INCHES
80 1 n/a
105 1 n/a
150 1 150
210 199
285 285 2
399 399 2
500 500 2
600 600 2
750 2 750 2
850 2 850 2
Table 9. Water Connection Pipe Sizes.
Page 21
Brute Elite
Page 21
6A.3 Freeze Protection
WARNING
Glycol must not be used in domestic hot water applications. Refer to Section 6B.4 for instructions on BNTV, domestic hot water freeze protection.
Brute Elite units are certified for indoor use only,
and are not design-certified for placement outdoors.
Proper precautions for freeze protection are recommended for boiler installations in areas where the danger of freezing exists.
Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc., may prevent a boiler from firing. Any time a boiler is
subjected to freezing conditions, and the boiler is not able to fire, and/or the water is not able to circulate, there is a risk of freezing in the boiler or in the pipes in the system. When water freezes, it expands which
may result in bursting of pipes, or damage to the boiler, which could result in leaking or flooding conditions.
Do not use automotive antifreeze. To help prevent freezing, Bradford White recommends the use of inhibited glycol concentrations between 20% and 35% glycol. Typically, this concentration will serve as burst protection for temperatures down to approximately -5°F (-20°C). If temperatures are expected to be lower than ­5°F (-20°C), glycol concentrations up to 50% can be used. When concentrations greater than 35% are used,
water flow rates must be increased to maintain a 20°F to 25°F temperature rise through the boiler. NOTE:
Bradford White supplied pumps are not all capable of maintaining the reduced temperature rise required with glycol concentrations greater than 35%. If glycol concentrations required are greater than 35% a field supplied pump should be used.
IMPORTANT NOTES: Different glycol products may provide varying degrees of protection. Glycol products must be maintained properly in a heating system, or they may become ineffective. Consult the glycol specifications, or the glycol manufacturer, for information about specific products, maintenance of solutions, and set up according to your particular conditions.
6A.4 BNTH Suggested Piping Schematics
Figures 15 through 21 show suggested piping
configurations for BNTH boilers. These diagrams are only meant as a guide. All components or piping required by local code must be installed.
6A.5 Recognized Chemicals
The following manufacturers offer glycols, inhibitors, and anti foamants that are suitable for use in the Brute Elite. Please refer to the manufacturers instructions for proper selection and application.
1. Sentinel Performance Solutions Group
2. Hercules Chemical Company
3. Dow Chemical Company
Page 22
Page 22
BRADFORD WHITE CORP.
Figure 15. Hydronic Piping — Single Boiler (zoning with circulators).
Page 23
Brute Elite
Page 23
Figure 16. Hydronic Piping — Single Boiler, Low Temp Radiant Space Heating using Low Loss Header and Zone Valves.
Page 24
Page 24
BRADFORD WHITE CORP.
Figure 17. Hydronic Piping — Multiple Boilers (zoning with circulators).
Page 25
Brute Elite
Page 25
Figure 18. Hydronic Piping — Multiple Boilers with Indirect DWH Tank Piped from System Loop.
Page 26
Page 26
BRADFORD WHITE CORP.
Figure 19. Hydronic Piping — Multiple Boilers, Reverse Return, Multi-Temp Zones (zoning with circulators).
Page 27
Brute Elite
Page 27
Figure 20. Hydronic Piping — Heating zones with indirect DWH tank piped with zone pumps (indirect directly off boiler). Boiler pump must shut down during DHW.
Page 28
Page 28
BRADFORD WHITE CORP.
Figure 21. Hydronic Piping, multiple boilers with indirect DWH off one boiler. Boiler pump must shut-down during DHW.
Page 29
Brute Elite
Page 29
SECTION 6B. Water Connections -
Section 6 is divided into two parts. The first is for BNTH models and is Section 6A. The second is for BNTV models and is Section 6B. Refer to the proper section for instructions in installing and piping your product. Refer to
Table 9 for pipe sizes required.
6B.1 BNTV Water Quality
BNTV water heaters must be installed in water
conditions of 10gpg hardness or less with a pH range of
8.2 to 9.5. Operating the BNTV in water with higher hardness levels will cause heat exchanger fouling, erosion, or corrosion leading to premature component failure, reduced efficiency, heat exchanger failure or system failure. Failure of this type will not be warranted. If the water in use exceeds the conditions recommended water softeners or other devices should be installed to improve water quality.
BNTV Water Heater
6B.2 Piping Requirements
Water piping should be supported by suitable hangers and floor stands. Do not support piping with the appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers and supports used. Rigid hangers may transmit noise through the system resulting from piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" (2.5cm) clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to the drain or in a manner to prevent injury in the event of pressure relief. Install a diaphragm-type expansion tank, flow check, and shutoff valves where needed or as required by code.
Brute Elite 80-500 can be ordered with pumps. Whether the factory pumps or other pumps are installed the piping should be installed such that the pump supplies flow to the heater it is attached to only. The factory pumps are sized for 30 feet and 6 elbows of total pipe length, so the heater should be placed within 15 feet of the tank. If longer runs are required, properly­sized field-supplied pumps should be used.
NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank.
3. Back flow preventer may be required - check local codes.
4. Thermal expansion tank may be required - check local codes.
5. Factory mounted pumps are sized for a max pipe length of 30' total, 6-90° elbows, full pipe size.
6. Caution: Pump sizing must be based opon water hardness at job site.
WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING. CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
Figure 23. DHW Piping, One Heater, One Vertical Tank.
Page 30
Page 30
BRADFORD WHITE CORP.
6B.3 Cold Water Make-Up
The cold water make-up may be connected to the
tank or to the inlet of the boiler as shown in Figures 23-
26. Install back flow preventers and shut offs where
needed or required by code.
6B.4 Freeze Protection
Brute Elite heaters are not certified for outdoor installation, so the chance of freezing is minimized. In an event such as power outage, component failure or other issue when freezing is likely, the heater and system must be drained to avoid the risk of damage due to freezing. Glycol must heating applications.
NOT be used in volume water
6B.5 BNTV Suggested Piping Schematics
Figures 23-26 show suggested piping
configurations for BNTV boilers. These diagrams are only meant as a guide. All components or piping required by local code must be installed.
6B.6 BNTV Suggested Pumps
Possible pumps for BNTV sizes 600-850 are Grundfos model TP 40-160/2B, or for size 600 (only) is Armstrong model E22B. See Table 8 for water flow and head requirements.
NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank.
3. Back flow preventer may be required - check local codes.
4. Thermal expansion tank may be required - check local codes.
5. Factory mounted pumps are sized for a max pipe length of 30' total, 6-90° elbows, full pipe size.
6. Caution: Pump sizing must be based opon water
hardness at job site.
Figure 24. DHW Piping, One Heater, Two Vertical Tanks.
WARNING: THIS DRAWING SHOWS
SUGGESTED PIPING CONFIGURATION AND VALVING. CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
Page 31
Brute Elite
WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING. CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
Page 31
NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank.
3. Back flow preventer may be required - check local codes.
4. Thermal expansion tank may be required ­check local codes.
5. Factory mounted pumps are sized for a max pipe length of 30' total, 6-90° elbows, full pipe size.
6. Caution: Pump sizing must be based opon
water hardness at job site.
Figure 25. DHW Piping, Two Heaters, One Vertical Tank.
NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank.
3. Back flow preventer may be required - check local codes.
4. Thermal expansion tank may be required - check local codes.
5. Factory mounted pumps are sized for a max pipe length of 30' total, 6-90° elbows, full pipe size.
6. Caution: Pump sizing must
be based opon water hardness at job site.
WARNING: THIS DRAWING SHOWS
SUGGESTED PIPING CONFIGURATION AND VALVING. CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
Figure 26. DHW Piping, Two Heaters, Two Vertical Tanks.
Page 32
Page 32
BRADFORD WHITE CORP.
SECTION 7. Electrical Connections
WARNING
The appliance must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in Canada. Do not rely on the gas or water piping to ground the metal parts of the boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance personnel, who work on or around the boiler, may be standing on wet floors and could be electrocuted by an ungrounded boiler. Electrocution can result in severe injury or death.
Single pole switches, including those of safety controls and protective devices must not be wired in a grounded line.
All electrical connections are made on the terminal blocks that are located inside the control panel.
NOTE: All internal electrical components have been prewired. No attempt should be made to connect electrical wires to any other location except the terminal blocks.
Wiring connections are shown in Figures 29 and 30.
Important Note: DO NOT MAKE/BREAK BRUTE ELITE LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A “call for heat / end call for heat” MUST be connected to the field interlock terminals. Some Brute Elite components are designed to have constant voltage during normal operation. If the Brute Elite's supply voltage is toggled as a call for heat signal, premature failure of these components may result.
Brute Elite does not recognize 4mA as a signal to shut off. If the call for heat is not connected between the field interlock terminals, Brute Elite will remain in low fire when it sees 4mA as a modulating signal.
Caution
Brute Elite supply voltage must not be disengaged, except for service or isolation, or unless otherwise instructed by procedures outlined in this manual. To signal a call for heat, use the 24V field-interlock, as shown in the wiring diagram(s).
7.1 Main Power
Connect a 15A fused, 120-volt supply to the main power switch (hot leg is connected directly to switch). Neutral leg is connected directly to the white wire. Ground wire can be connected to the grounding lug in the control panel (see Table 11).
Figure 27. Control Panel Layout.
Page 33
Brute Elite
Page 33
BOILER PUMP CONNECTIONS
RATINGS
SIZES VOLTS PHASE AMPS
80–850 No Pump or 7.4A max
80-500 With Pump
Minimum 15A circuit required
*
SIZES VOLTS PHASE AMPS
150-500 No pump
150-199 With pump
285-500 With pump
600-850 See Pump Rating Plate FLA No pump (must be less than 7.4 FLA; 1HP or less)
*
Minimum 15A circuit required
120 Single 2*
Less
120 Single than
6*
Table 10. BNTH Electrical Data.
WATER HEATER
120 Single 2*
120 Single 7*
120 Single 8*
Table 11. BNTV Electrical Data.
(Boiler, System Pump and DHW Pump Connections)
115V – Maximum 1HP
115V – Maximum 1HP
or 7.4A max
7.2 Pump Connections
Brute Elite energizes the pump contacts upon a call for heat. Once the call for heat is satisfied the pump will remain on for the defined pump overrun time.
NOTE: System and DHW contacts are dry contacts. Appropriate voltage must be supplied to the System and DHW pumps for proper operation. Boiler pump contact (max 7.4 FLA) is fed by 120V (violet wire) internally from main power feed.
System pump connections are located on terminal block 5 (TB5) in the control panel (see Figure 27). The system pump contacts are rated for 120Vac, 7.4 amps. To use the contacts, power must be supplied on one terminal with the other terminal wired to the pump or a relay controlling the pump.
DHW pump connections are located on terminal block 5 (TB5) in the control panel and are rated for 120Vac, 7.4 amps. To use the contacts, power must be supplied on one terminal, and the other terminal wired to the pump or a relay controlling the pump.
7.3 24Vac Transformer with Integral Circuit
Breaker
24Vac is supplied by a transformer mounted to the backside or underneath the control panel, depending upon the appliance. All 24Vac power is supplied through a circuit breaker that is part of the transformer. The transformer is then connected to terminal blocks 3 and 4 (TB3 and TB4).
7.4 Hydronic Call for Heat
Connect the call for heat to terminal block 7 (TB7), connections labeled "T-T or interlock" in the control panel.
7.5 Outdoor Air Temperature Sensor
Connect the outdoor air temperature sensor to terminal block 7 (TB7), connections labeled Outdoor temp sensor. The outdoor air temperature sensor is used for warm weather shutdown and outdoor reset.
7.6 Domestic Hot Water Connection
Connect a DHW sensor or aquastat to terminal block 6 (TB6), connections labeled DHW stat. The aquastat or sensor will be automatically detected and initiate the DHW call as needed.
7.7 System Sensor (lead lag/cascading
operation only)
Connect the system sensor to terminal block 6 (TB6), connections labeled system sensor. Can be used in a well for DHW tank applications with lead/lag.
7.8 External Control Connections
Connect 4-20mA signals from external controls or building automation systems to terminal block 7 (TB7) in the control panel. The connections are labeled "Remote Anlaog Input". When making the connections follow the polarity designations shown on the label.
7.9 Optional Field Connections
Terminal block 8 (TB8) in the control panel can be used for connecting optional components, such as, low water cutoffs, flow switches, additional high limits and other field supplied devices that must be interlocked with the boiler. All safeties or end switches must be wired in series by removing the supplied jumpers.
7.10 Lead Lag/ Cascading Wiring
Connections
Connect each boiler in the cascade system together by daisy chaining each control from Modbus port 1 (MB1) of the first boiler to the second and so on. This can be done using 22awg or thicker shielded twisted pair wire with drain. Two twisted pairs or three conductors are needed. a. To daisy-chain the boilers connect a wire from Modbus
port 1 (MB1) terminal A of the first boiler to Modbus port 1 (MB1) terminal A of the second boiler.
b. If there are more boilers in the system connect a
wire from Modbus port 1 terminal A of boiler 2 to Modbus port 1 terminal A of boiler 3.
c. Repeat these steps until all Modbus port1 terminal
A connections are wired.
d. Repeat the above steps for Modbus port 1 terminal
B and C connections to complete the wiring.
e. Connect the drain wire from the twisted pair wire
to ground on one end of the wire only.
Page 34
Page 34
BRADFORD WHITE CORP.
Figure 28. Lead-Lag / Cascading Wiring Connections.
Page 35
Brute Elite
7.11 Wiring Diagrams (see Figures 29 and 30)
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing
Page 35
Figure 29. Ladder Diagram.
Page 36
Page 36
BRADFORD WHITE CORP.
Figure 30. Wiring Diagram (all sizes).
Page 37
Brute Elite
Page 37
SECTION 8. Brute Elite Control Setup and Operation
The Brute Elite control is an integrated electronic control that replaces many of the individual components found on older appliances. The control acts as the ignition control, pump control, high limit and cascading/ lead lag control and is setup using the display on the appliance.
Figure 31. Control Buttons on User Interface.
8.1 Display Navigation
The display is divided into three menu structures, USER, SETUP and DIAGNOSTIC. The menu structure and variables in each are shown in Tables 12-14. Once in a particular menu structure navigation consists of pressing the next button to scroll from item to item and then pressing the up and down arrows to change values.
MENU ITEM FUNCTION RANGE DEFAULT
Outlet water Displays the current outlet 55-190°F 120°F temperature water temperature & allows
the setpoint to be adjusted
Inlet water Displays the current inlet — temperature water temperature
Delta T Displays the current
temperature rise across the heat exchanger
DHW water Displays the current DHW 60-182°F 120°F temperature temperature & allows the
setpoint to be adjusted
Stack Displays the current stack — temperature temperature
Outdoor Displays the current outdoor — temperature air temperature
LL Displays the current system 60-190°F 120°F
temperature and allows the setpoint to be adjusted
Firing Rate Displays an indicator of the
current firing rate based upon fan RPM. The actual firing rate may vary.
Table 12. User Mode Menu Structure.
Once the value is adjusted the NEXT or DONE button can be pressed. The DONE button returns you to the Home screen. The NEXT button increments the display to the next item in the menu structure.
USER mode is the home screen shown on the control. If the display is not in USER mode wait for the display timeout period to be reached or press the Done button to return to the USER menu.
SETUP mode is accessed by holding the up and down arrow keys simultaneously for 3 seconds.
DIAGNOSTIC mode is accessed by holding the NEXT button for 3 seconds.
8.2 Ignition Control- Sequence of Events
1. Call for heat
2. Safety chain check
3. Fan starts and waits to achieve prepurge RPM
MENU ITEM DEFINITION
F or C Selects temperature units LBTHODLOD Outdoor reset enable/disable -
enables menu items
LBT Low boiler setpoint during outdoor reset
see Figure 29
HOD High outdoor temperature setpoint
see Figure 29
LOD Low outdoor temperature setpoint
see Figure 29
RMT Add Used for Lead/Lag (follow menus) LL Lead/Lag enable/disable - enables menu items HS Hysteresis - temp range between on/off cycles bL Base Load % - input rate before next boiler fires Sd Warm weather shut-down temperature ASC Anti short cycle - minutes of delay between
startup bAC Future use - Press DONE to exit menu. PAS Future use - Press DONE to exit menu.
NOTE: When enabling/disabling functions, select "Done" and wait 30
seconds before scrolling.
Table 13. Setup Mode Parameters.
MENU ITEM DESCRIPTION
mA Display the flame sense signal
Alert codes Displays the current alert code
Lockout code Displays the current lockout code
Outlet Limit Displays outlet temperature limit
DHW limit Displays Domestic Hot Water limit setting
Stack Limit Displays Stack limit setting
Min. firing rate Displays the minimum firing rate allowed
Min. forced Allows the user to force the boiler to fire at firing rate the minimum firing rate
Max forced Allows the user to force the boiler to fire at firing rate the maximum firing rate
Rate indicator Displays a indicator of the firing rate based
off of the fan RPM. Actual firing rate may vary depending upon setup.
Table 14. Diagnostic Mode Menu Structure.
Page 38
Page 38
BRADFORD WHITE CORP.
4. Prepurge timer is started once the prepurge RPM is achieved.
5. Pre ignition time of 2 seconds to check the flame sensor operation and status. During this period an intermittent spark can be seen.
6. Trial for ignition period, 4 seconds. The direct spark ignition switches to constant spark for three seconds, during which time the gas valve is open. For the last second of the ignition period direct spark is de-energized and the flame sensor checks for established flame. If flame is sensed the control enters "Run" to satisfy the demand. If flame is not established the control enters a retrystarting from step 2. If flame has not been established in the appropriate number of retries the control will lockout with a 109 error code.
7. Call for heat complete
8. Gas valve off
9. Fan and pump over run times active to purge the system
This sequence is the basic operating sequence of
the appliance whether there is a DHW, or hydronic call for heat.
8.3 Modulation Control
The control uses a PID algorithm to adjust the
firing rate of the boiler as the control point is approached. The goal of the control is to operate at a minimum firing rate to match the load on the appliance. This is done by using a setpoint, and on / off differentials. The control modulates to achieve the setpoint temperature, which could be several degrees away from the actual off point. The off point is calculated by adding the setpoint + off differential. The setpoint and differentials used in operation is dependent upon the call for heat being applied. If there is a DHW call the DHW setpoint and off differentials are used. If there is a hydronic call the CH setpoint and off differential is used. When the setpoint + off differential is achieved the control interrupts appliance firing until the water temperatures reaches the setpoint - on differential. Both the hydronic and DHW setpoints are adjustable through the USER mode menu structure.
8.5 Anti-Short Cycle (ASC)
The anti short cycle period is started whenever the gas valve turns off. This period is to help prevent short cycling. Depending upon the time selected the control will wait up to 10 minutes before attempting to start the trial for ignition sequence. The ASC time can be adjusted by entering setup mode.
8.5 High Limit
The control uses a dual thermistor sensor to monitor the Brute Elite's maximum temperature. The high limit sensor is installed in the outlet water. A dual thermistor sensor is used, so that the two temperatures can be monitored and compared to confirm accuracy. The control will automatically reduce the firing of the Brute Elite to prevent the high limit from tripping. The high limit setpoint is not adjustable.
8.7 Outlet Water Temperature
The outlet water temperature is a dual thermistor sensor and is limit rated. The control compares each of the temperature readings to determine accuracy. The outlet sensor is used as the primary control point for high limit, temperature operation, and modulation. The operating setpoint can be adjusted through the USER menu structure.
8.8 Inlet Water Temperature
The inlet water temperature uses a single thermistor sensor and is used to calculate the delta T of the system.
8.9 Heat Exchanger Temperature Rise
The heat exchanger temperature rise is calculated from the outlet and inlet sensor temperatures. The result is displayed in the USER menu structure.
8.10 Stack Temperature
The stack temperature is a dual thermistor sensor and is limit rated. The control compares each of the temperature readings to determine accuracy. The stack sensor is used as a limiting feature to avoid excessive temperatures in the venting.
8.4 Pump Control
The control can operate three pumps. The boiler pump is active anytime there is a call for heat applied to the control. The DHW and system pumps are active based upon the call and priority of the heat demand being supplied. When there is a hydronic call supplied the system pump is active. If there is a DHW call supplied while the hydronic call is active the system pump turns off and the DHW turns on. This happens because of domestic hot water priority, which forces the control to attempt to satisfy the domestic water demand prior to the hydronic demand. When the last heat demand is satisfied the boiler pump enters an overrun time.
8.11 Domestic Hot Water Temperature
The domestic hot water temperature sensor is used to monitor the DHW demand. The control uses the DHW sensor to control the operation and modulation rate of the appliance when there is a DHW demand. The DHW setpoint can be adjusted through the USER menu structure.
8.12 Lead Lag / Cascading
Lead Lag/Cascading allows multiple boilers to be connected together and controlled from one common sensor input. Up to 8 boilers can be connected together in a single system. To setup Lead/Lag or cascading
Page 39
Brute Elite
Page 39
DANGER
• Water temperature over 125°F (52°C) can cause severe burns instantly or death from scalds.
• Children, disabled and elderly are at hightest risk of being scalded.
• See instruction manual before setting temperature at heating appliance.
• Feel water before bathing or showering.
• If this appliance is used to produce water that could scald if too hot, such as domestic hot water use, adjust the outlet control (limit) or use temperature limiting valves to obtain a maximum water temperature of 125°F (52°C).
operation there are several settings in the "setup" menu structure that must be adjusted for the specific installation, each is covered in the following sections.
8.12.1 Lead Lag Setpoint
The lead lag setpoint is set from the "user" menu using the "LL" variable. This is the temperature the boiler is attempting to maintain at the system sensor. This setting doesn't control the boiler outlet temperature, so the water temperature at the boiler outlet may be much hotter than the system temperature setpoint. Adjust the LL setpoint to the desired operating temperature of the system.
8.12.2 Lead Lag Master/Slave Selection
In the SETUP menu structure, the "LL" menu allows the lead lag system to be turned on and the boiler to be configured as a master or slave control. In each lead lag system there can only be one master control, so proper selection is important to avoid operating issues. To set the boiler to lead lag "master" operation the LL menu should be set to "LDR". To set the boiler to slave, "SLA" should be selected.
8.12.3 Lead Lag Address
The Lead Lag address must be set for each boiler connected to the lead lag system. Each boiler must have a unique address selected for the system to work properly. Typically, the lead or master boiler should be set to address one and the remaining boilers should be set to values 2–8 depending upon how many boilers are installed in the system.
8.12.4 Lead Lag Hysteresis
The lead lag system uses a hysteresis value set in the setup menu, called, "HS". The hysteresis and setpoint values control the on and off points of the boiler. If the lead lag setpoint is adjusted to 120°F with a hysteresis value of 5°F the boiler will turn off when the water temperature reaches 125°F and will turn back on when the water temperature reaches 115°F. Set the hysteresis values to match the boiler to the system operating characteristics. Setting this value correctly
will help reduce the chance of short cycling.
8.12.5 Lead Lag Base Load Setting
The lead lag system uses a base load setting that is set through the "setup" menu called "bL". The base load setting identifies the firing rate that the operating boiler must achieve before the next boiler in the system is allowed to operate. The default setting is 50% to avoid short cycling and operating the boilers at higher, less efficient, firing rates.
8.13 Boiler Pump Interrupt
WARNING
Failure to plumb, pump and install the appliance correctly when using this feature may lead to reduced or no water flow through the heat exchanger, causing premature failure of the heat exchanger, personal injury or death. Please consult the factory with any questions regarding the use of this feature.
The boiler pump interrupt feature is used in some applications when the boiler is being used for both hydronic and domestic hot water heating. The interrupt jumper is used to turn off the boiler pump during a domestic hot water demand. For this to work properly the system must be plumbed and pumped to allow the domestic hot water pump to supply the flow and head requirements for the boiler and indirect water heater together. It is not necessary to use the interrupt jumper in all applications. Specific modes of operation that may require the use of this feature are shown in Section 6.
NAME FUNCTION VALUE
CH on Burner demand begins when the 5°F differential outlet water temperature reaches
CH off Burner demand ends when the 5°F differential outlet water temperature reaches
DHW on Burner demand begins when the 2°F differential outlet water temperature reaches
DHW off Burner demand ends when the 10°F differential outlet water temperature reaches
Pump Operates the pump for the overrun 1 or 5 overrun time after the burner demand minutes
High Locks the boiler out when the high 200°F limit limit temperature is reached
Flame Flame signals lower than the flame 0.8Vdc threshold threshold interrupt burner operation
DHW Time for domestic hot water priority 60 min. priority time
"Outlet water temperature setpoint" minus "CH on differential"
"Outlet water temperature setpoint" plus "CH off differential"
(80-285)
"Outlet water temperature setpoint" 5°F minus "DHW on differential"
"Outlet water temperature setpoint" 5°F plus "DHW off differential"
has ended
(requires manual reset)
Table 15. Default Control Settings.
(399-850)
(80-285)
(399-850)
Page 40
Page 40
BRADFORD WHITE CORP.
SECTION 9. Modes of Operation
The Brute Elite control allows the boiler to operate in many different modes of operation. The mode must be selected based upon the requirements of the installation. The following sections describe the basic operation of the Brute Elite in each of the different modes. Familiarize yourself with each mode and how the operation of the boiler varies, depending upon the installation and inputs the control is monitoring.
9.1 Hydronic Heating Demand
When using the Brute Elite for hydronic heating a call for heat must be supplied to the "T-T or Interlock" terminal. Once the call is supplied the control starts the boiler and system pumps and begins the ignition process. The ignition process consists of a prepurge, trial for ignition, and run period. The prepurge period starts on a call for heat once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which the direct spark ignition system and gas valve are energized. At the end of the trial for ignition period the flame signal is compared with the preset flame threshold value. If the flame signal is higher than the flame threshold the Brute Elite enters "run". If the flame signal is below the threshold the Brute Elite returns to prepurge and starts the ignition process over. In "run" the Brute Elite monitors the flame signal, call for heat, safeties, and water temperatures and modulates as needed between 100% and 20% of rate to satisfy the call for heat.
9.2 Hydronic Heating with Outdoor Reset
Outdoor reset varies the control point setpoint based on the actual outdoor temperature. The reset function works as shown in Figure 32. When the outdoor air temperature reaches the "high outdoor temperature setpoint (HOD), the control point setting is adjusted to the low boiler temperature setpoint (LBT). When the outdoor air temperature reaches the low outdoor temperature setpoint (LOD), the control setpoint is adjusted to the CH/Outlet water setpoint temperature. HOD, LOD and LBT can be adjusted by accessing SETUP mode. CH setpoint is adjustable from the USER menu structure.
once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which, the direct spark ignition system and gas valve are energized. At the end of the trial for ignition period the flame signal is compared with the preset flame threshold value. If the flame signal is higher than the flame threshold the Brute Elite enters "run". If the flame signal is below the threshold the Brute Elite returns to pre-purge and starts the ignition process over. In "run" the Brute Elite monitors the flame signal, call for heat, safeties, and water temperatures modulating as needed between 100% and 20% of rate to satisfy the call for heat. When a DHW demand is applied during a hydronic call for heat the priority feature forces the boiler to switch to the DHW demand for the priority time. The DHW priority demand forces the control to operate to the DHW setpoint, de-energizes the system pump and energizes the DHW pump.
9.4 Hydronic Heating Using External Modulation Control
When using the Brute Elite for hydronic heating
with external modulation control a call for heat must be supplied to the "T-T or Interlock" terminal. Once the call is supplied the control starts the boiler and system pumps and begins the ignition process. The ignition process consists of a prepurge, trial for ignition, and run period. The prepurge period starts on a call for heat once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which the direct spark ignition system and gas valve are energized. At the end of the trial for ignition period the flame signal is compared with the preset flame threshold value. If the flame signal is higher than the flame threshold the Brute Elite enters "run". If the flame signal is below the threshold the Brute Elite returns to prepurge and starts the ignition process over. In "run" the Brute Elite monitors the flame signal, call for heat, safeties, and water temperatures. The boiler
9.3 Hydronic Heating with Domestic Hot Water (DHW) Priority
When using the Brute Elite for hydronic heating
with domestic hot water priority a call for heat must be supplied to the "T-T or Interlock" terminal. Once the call is supplied the control starts the boiler and system pumps and begins the ignition process. The ignition process consists of a prepurge, trial for ignition, and run period. The pre-purge period starts on a call for heat
Figure 32. Outdoor Reset Setpoint Temperatures.
Page 41
Brute Elite
Page 41
setpoint is used to limit the maximum water temperature leaving the boiler only. The modulation rate is controlled by a 4-20mA (0-10Vdc using converter) signal supplied by an external control. When setting up a system using an external control care must be taken to set the external control algorithms to prevent the boiler from short cycling or "hunting " to prevent premature component failure.
9.5 Hydronic Heating Using Local Lead­Lag/Cascading Feature
When using single or multiple Brute Elites in lead
lag configuration, the system sensor and TT terminals of the Master boiler create heat demand. The TT terminals on the slave boilers are ignored as the demand for those heaters is given from the master control. The system sensor is also used to control the modulation rate of the lead lag system. (see Section 7 for wiring instructions).
Let’s consider the following example:
Three Brute Elite boilers (let’s call them “Lead”,
“Slave1” and “Slave2”) tied together via Modbus 1 connection, with appropriate RMT Address (1, 2, 3). System sensor input is used to indicate common secondary loop temperature.
System setpoint = 150°F HS (hysteresis) = 10°F (default) BL (base load) = 50% (default) Anti-short-cycle = 5 minutes
Run sequence is initiated when system temperature
falls to 140°F (setpoint less hysteresis value). Lead boiler will start. All firing rates will depend on several application characteristics, including flow rate, system load, water volume, etc. Boilers will start at a rate of 35%. If the load is such that Lead’s rate increases to 50%, “Slave1” will go through its startup sequence and begin firing at 35%. At this point, both boilers (Lead and Slave1) will continue to respond simultaneously to the load/system characteristics, by modulating up or down together, in relation to the relative system setpoint and load characteristics. Scenario 1: If the system loop temperature rises
quickly, and moves above setpoint, then the boilers will simultaneously drop their firing rate. If when reaching the point where both boilers drop toward their minimum firing rate (20%), then the first slave will drop out. Slave1 will remain unavailable until its ASC timer has expired (5 minutes). If the load were to increase such to drive all active boilers to 50% firing rate or more, during the ASC time, Slave2 will begin its startup se­quence and begin to fire at 35%, etc.
Scenario 2: If the system loop temperature continues to
drop (load increases), then the two boilers will increase firing rate together. At 50%, Slave2 will begin its firing sequence and be added to the group.
All three boilers will continue to fire simultaneously at equal input rates or…
1. Modulation rate approaches minimum firing rate (20%), in which case Slave2 will first drop out, and then Slave1, accordingly.
2. System temperature reaches 10F (HS- hysteresis value) above setpoint (e.g. 160F), in which case remaining boiler will shut off
3. Any of the boilers approach its high limit tempera­ture the individual boiler will modulate back.
9.6 Hydronic Heating Using Local Lead­Lag/Cascading Feature with Indirect Hot Water
When using the lead lag boiler system to provide
indirect domestic hot water heating, the DHW demand should be supplied to the master boiler through the existing DHW terminals. The lead lag system will change the operating mode of the Master boiler only to supply water at the DHW setpoint. The remaining boilers on the system will continue to supply hydronic heating.
When the system is supplying both hydronic heat and
domestic hot water at the same time both the system pump and DHW pump contacts are closed, so special attention must be paid to allow for proper operation. During a DHW call, the master boiler pump may need to be turned off in applications serving both hydronic and domestic heating. This will cause the DHW pump to provide flow through the boiler and indirect tank (pump must be sized properly) when there is a DHW call. To turn off the boiler pump in this application the "boiler pump interrupt" jumper should be installed. The terminal block location is terminal block 5 (TB5) contacts labeled "boiler pump interrupt" in the control panel.
9.7 Warm Weather Shutdown
Warm weather shutdown overrides a hydronic call
for heat when the outdoor air temperature is greater than the warm weather shutdown setpoint. Warm weather shutdown is always active whenever there is an outdoor sensor attached to the control. To avoid warm weather shutdown the warm weather shutdown temperature should be increased as necessary. The warm weather shutdown setpoint can be adjusted in SETUP mode, using the SD menu.
9.8 Domestic Hot Water Demand (BNTV only)
When using the Brute Elite for DHW heating a
call for heat must be supplied to the "DHW stat" terminal located on terminal block 6 (TB6). The DHW heating call can be from the supplied DHW sensor or from an aquastat. If the DHW sensor is used the heater operates to maintain the temperature at the DHW sensor. This may allow the actual heater outlet water temperature to exceed the DHW sensor setpoint. If an aquastat is used to supply the DHW demand the heaters
Page 42
Page 42
BRADFORD WHITE CORP.
firing rate is controlled by the DHW setpoint temperature and the water temperature at the heat exchanger outlet. Once the DHW call is supplied the control starts the boiler and DHW pumps and begins the ignition process. The ignition process consists of a prepurge, trial for ignition, and run period. The prepurge period starts on a call for heat once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which the direct spark ignition system and gas valve are energized. At the end of the trial for ignition period the flame signal is compared with the preset flame threshold value. If the flame signal is higher than the flame threshold the Brute Elite enters "run". If the flame signal is below the threshold the Brute Elite returns to prepurge and starts the ignition process over. In "run" the Brute Elite monitors the flame signal, call for heat, safeties, and water temperatures modulating as needed between 100% and 20% of rate to satisfy the call for heat.
9.9 Domestic Hot Water Heating Using External Modulation Control
When using the Brute Elite for DHW heating with
external modulation control a call for heat must be supplied to the "T-T or Interlock" terminal. By supplying a call to the "T-T or interlock" terminal the operating temperature setpoint defaults to the hydronic heating setpoint, so all of the temperature adjustments must be made to the hydronic setpoint. Once the call is supplied, the control starts the boiler and system pumps and begins the ignition process.
The ignition process consists of a prepurge, trial for ignition, and run period. The prepurge period starts on a call for heat once the fan RPM reaches a preset level. The trial for ignition period follows once the start-up RPM of the fan is reached. The trial for ignition period lasts 4 seconds during which the direct spark ignition system and gas valve are energized. At the end of the trial for ignition period the flame signal is compared with the preset flame threshold value. If the flame signal is higher than the flame threshold the Brute Elite enters "run". If the flame signal is below the threshold the Brute Elite returns to prepurge and starts the ignition process over. In "run" the Brute Elite monitors the flame signal, call for heat, safeties, and water temperatures. The heater setpoint is used to limit the maximum water temperature leaving the boiler only. The modulation rate is controlled by a 4-20mA (0-10Vdc using converter) signal supplied by an external control. When setting up a system using an external control care must be taken to set the external control algorithms to prevent the boiler from short cycling or "hunting " to prevent prema­ture component failure.
9.10 Domestic Hot Water Heating Using Local Lead-Lag/Cascading Feature
When using multiple Brute Elites to supply
Domestic hot water only the heaters should be setup as stated in Section 8.12 “Lead/Lag Cascading,” and Section 9.5 “Hydronic Heating Using Local Lead/Lag Cascading Feature.” When the heaters are installed in this fashion, all of the setpoints and adjustments are done through the Lead Lag menus.
Page 43
Brute Elite
Page 43
SECTION 10. Operating Instructions
10.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all bleeding devices and open make-up water valve. Allow system to fill slowly.
2. If make-up water pump is employed, adjust pressure switch on pumping system to provide a minimum of 12 psi (81.8 kPa) at the highest point in the heating loop.
3. If a water pressure regulator is provided on the make-up water line, adjust the pressure regulator to provide at least 12 psi (81.8 kPa) at the highest point in the heating loop.
4. Open bleeding devices on all radiation units at the high points in the piping throughout the system, unless automatic air bleeders are provided at such points.
Note that there is an air bleed located on the left side of Brute Elite, on top of the water manifold.
5. Cycle the boiler pump on and off 10 times, 10 seconds on and 10 seconds off to remove all air from the heat exchanger. Then run system and appliance pump for a minimum of 30 minutes with the gas shut off.
WARNING
Failure to remove all air from the heat exchanger could lead to property damage, severe injury or death.
13. Check gauge for correct water pressure and also check water level in the system. If the height indicated above the boiler insures that water is at the highest point in the circulating loop, then the system is ready for operation.
14. Prime condensate trap with water (not required for BNTH 600, 750, 850).
15. Refer to local codes and the make-up water valve manufacturer’s instructions as to whether the make-up water valve should be left open or closed.
16. After placing the unit in operation, the ignition system safety shutoff device must be tested.
First, shut off the manual gas valve, and call the unit for heat. Main gas terminals will be energized, attempting to light, for four (4) seconds, and then will de-energize. The unit will go into lockout after the required number of trial for ignition periods.
Second, turn the power off, press the manual reset button on the boiler control, or the user display, open the manual gas valve and allow the unit to light. While the unit is operating, close the manual gas valve and ensure that power to the main gas valve has been cut.
17. Within three (3) days of start-up, recheck all air bleeders and the expansion tank as described in Steps 4 and 8 above.
Important Note: The installer is responsible for identifying to the owner/operator the location of all emergency shutoff devices.
6. Open all strainers in the circulating system, check flow switch operation (if equipped), and check for debris. If debris is present, clean out to ensure proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the system full of water and under normal operating pressure, the level of water in the expansion tank should not exceed ¼ of the total, with the balance filled with air.
9. Start up boiler according to the procedure in this manual. Operate the entire system, including the pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If the water level exceeds ¼ of the volume of the expansion tank, open the tank drain, and drain to that level.
11. Shut down the entire system and vent all radiation units and high points in the system piping, as described in Step 4.
12. Close make-up water valve and check strainer in pressure reducing valve for sediment or debris from the make-up water line. Reopen make-up water valve.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that may have been under water.
10.2 Operating the Burner and Set Up
Initial setup must be checked before the unit is put in operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to improper setup. Damage to the boiler resulting from improper setup is not covered by the limited warranty.
10.2.1 Burner Operation
REQUIRED TOOLS: differential pressure gauge
capable of reading negative 0.01 inches W.C. (0.002kPa), screw drivers, torx bits, combustion analyzer.
1. Using this manual, make sure the installation is
complete and in full compliance with the
instructions and all local codes.
2. Determine that the appliance and system are filled
with water and all air has been bled from both.
Open all valves.
3. Observe all warnings on the Operating Instructions
Page 44
Page 44
BRADFORD WHITE CORP.
label and turn on gas and electrical power to appliance.
4. Brute Elite will enter the start sequence. Blower and pump will energize for pre-purge, then the ignition sequence starts. After all safety devices are verified, the gas valve opens. If ignition doesn’t occur, turn off the Brute Elite, check that there is proper gas supply. Wait 5 minutes and start the unit again.
5. Turn Brute Elite on.
6. After placing the appliance in operation, the Burner Safety Shutoff Device must be tested:
(a) Close gas shutoff valve with burner operating. (b) Flame will go out and blower will continue to
run for the post purge cycle. One or three additional attempts to light will follow including pre-purge, ignitor on, valve/flame on and post purge. Ignition will not occur as the gas is off. The ignition control will lockout.
(c) Open gas shutoff valve. Reset the boiler
control by pressing the
RESET button on the
control or on the display. Restart the appliance. The ignition sequence will start again and the burner will start. The appliance will return to its previous mode of operation.
in Table 16. If the CO2 is not within the range shown, adjustments may be made. To adjust the low fire CO
, locate the low fire adjuster screw
2
according to the appropriate figure. Slowly make adjustments in 1/16 of a revolution increments until the CO2 is within the range identified.
4. Repeat steps 2 and 3 to confirm that the CO
2
ranges are within the required ranges. Adjust if necessary.
5. Confirm that the differential pressure is still within the appropriate range.
6. If any of the measurements cannot be adjusted
to the specified ranges or the CO levels are above 150ppm when adjusted please consult the factory for further information.
7. Remove the differential pressure gauge from the air and gas pressure taps making sure to close all ports after the gauge has been removed.
WARNING
Improper adjustment may lead to poor combustion quality, increasing the amount of carbon monoxide produced. Excessive carbon monoxide levels may lead to personal injury or death.
Caution
Should any odor of gas be detected, or if the gas burner does not appear to be functioning in a normal manner, CLOSE MAIN SHUTOFF VALVE. Do not shut off switch. Contact your heating contractor, gas company, or factory representative.
10.2.2 Boiler Setup and Adjustment
1. Connect a manometer capable of reading 0.01"wc to the gas valve locations shown in Figure 33. The positive side of the manometer should be connected to the location labeled “air pressure tap.” The negative side of the manometer should be connected to the location labeled "gas pressure tap." This differential pressure should be slightly negative (see Table 16).
2. Measure the CO
in the flue products at high
2/O2
fire. The Brute Elite can be forced to high fire to allow for easier setup. Refer to Section 8.1, Table
14 for instructions on how to access the forced rate
menu. The CO values shown in Table 16. If the CO
readings should be between the
2
is not within the
2
range shown, adjustments may be made. To adjust the high fire CO
, locate the high fire adjuster screw
2
according to the appropriate figure. Slowly make adjustments in 1/16 of a revolution increments until the CO
3. Measure the CO
is within the range identified.
2
in the flue products at low
2/O2
fire. Brute Elite can be forced to low fire to allow for easier setup. Refer to Section 8.1, Table 14 for instructions on how to access the forced rate menu. CO
readings should be between the values shown
2
GAS TYPE HIGH FIRE, CO
Natural 9.0 to 8.8%
Propane 10.0 to 9.8%
Table 16. CO2 Range and Pressure Differential.
LOW FIRE, CO
2
0.5% lower than -.005 to high fire setting -.015" wc
2
DIFFERENTIAL
PRESSURE
10.3 Shutting Down Brute Elite
1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain Brute Elite and be sure to also protect building piping from freezing. All water must be removed from heat exchanger or damage from freezing may occur.
This step to be performed by a qualified service person.
10.4 To Restart Brute Elite
If drained, follow Section 10.1 in this manual
for proper filling and purging.
1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual reset high limit, etc.).
7. Set the temperature controller to the desired temperature setting and switch on electrical power.
8. Burner will go through a prepurge period and ignitor warm-up period, followed by ignition.
Page 45
Brute Elite
Page 45
80–285
399
500
600
750, 850
Figure 33A. Brute Elite Gas Valves (285, 399 and 500).
Figure 33B. Brute Elite Gas Valves (600, 750 and 850).
Page 46
Page 46
BRADFORD WHITE CORP.
SECTION 11. Maintenance
WARNING
Disconnect all power to the appliance before attempting any service to the appliance. Contact with electricity can result in severe injury or death.
11.1 System Maintenance
(yearly, unless otherwise noted)
1. Lubricate the system water-circulating pump, if required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six moBNTHs.
3. Inspect the venting system for obstruction or leakage at least once a year. Periodically clean the screens in the vent terminal and combustion air terminal (when used).
4. Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
5. If the appliance is not going to be used for extended periods in locations where freezing normally occurs, it should be isolated from the system and completely drained of all water.
6. Low water cutoffs, if installed, should be checked every year. Float type low water cutoffs should be flushed periodically.
7. Inspect and clean the condensate collection, float switch and disposal system yearly.
8. When a means is provided to neutralize condensate, ensure that the condensate is being neutralized properly.
9. Inspect flue passages, and clean with brushes/ vacuums, if necessary. Sooting in flue passages indicates improper combustion. Determine the cause and correct.
10. Inspect the vent system and air intake system, and ensure that all joints are sealed properly. If joints need to be resealed, completely remove existing sealing material, and clean with alcohol. Apply new sealing material, and reassemble.
11.2 Appliance Maintenance and
Component Description
Use only genuine Bradford White replacement
parts.
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
Brute Elite gas and electric controls are engineered
for long life and dependable operation, but the safety of equipment depends on their proper functioning. Only a
qualified service technician should inspect the basic items listed below every year:
a. Appliance control f. Flow switch b. Automatic gas valve g. Low water cutoff c. Pressure switches h. Burner d. Blower i. Heat exchanger e. Pump
11.2.1 Burner
Check the burner for debris. Remove the blower arm assembly to access the burner. Remove the 4 bolts connecting the blower to the arm (see Figure 34). Remove the 5 bolts, which hold the burner arm in place. Pull burner up and out. Clean burner, if necessary, by blowing compressed air from the outside of the burner into the center of the burner, and wipe the inside of the burner clean with glass cleaner. A dirty burner may be an indication of improper combustion or dirty combustion air. Determine the cause, and correct. If damaged, replace the burner gasket when replacing the burner.
NOTE: When installing the burner, make sure the flange is aligned with the mating surface, as each is keyed to control fit.
11.2.2 Modulating Gas Valve / Venturi
The modulating gas valve consists of a valve body that incorporates the ON/OFF gas flow control and a negative pressure regulator. It provides the air/gas ratio control in combination with the venturi to the unit. It is designed to operate with gas supply pressure between 4 and 13 inches w.c.. To remove the gas valve and or venturi, shut off the 120 Volt power supply to the boiler. Turn off all manual gas valves connecting the boiler to the main gas supply line. Remove the front door of the boiler to gain access to the gas valve and venturi. Disconnect the four (4) flange bolts connecting the gas manifold pipe to the gas valve. Remove the electrical connections to the gas valve. Remove the bolts connecting the venturi flange to the blower. This allows the entire gas valve/venturi assembly to be removed as an assembly to facilitate inspection and cleaning.
After the valve has been removed, reassemble in reverse order making sure to include all gaskets and O­rings. Turn on the manual gas valves and check for gas leaks. Turn on the 120 Volt power. Place the unit in operation following the instructions in Section10. Once the boiler is operating check for leaks again and confirm all fasteners are tight.
Check appliance setup according to Section 10.
11.2.3 Appliance Control
Brute Elite has an integrated control that incorporates manual reset high limit control, operating temperature control, modulating control, ignition control, outdoor reset control, pump control and many other features. If any of these features are thought to be defective, please consult the factory for proper trouble shooting practices prior to replacing the control. If control replacement is required, turn off all power to the
Page 47
Brute Elite
Page 47
appliance and shut off all manual gas valves to the appliance. Remove the front door to the appliance and the control panel plastic bezel. Remove all wire connections from the control board. The control board connections are keyed to only allow connection in the proper location, but proper handling techniques should be used to avoid damage to the wiring or connectors. To remove the control push in on the two tabs on the left side of the board to unlatch the clips from the control panel. Rotate the control around the fastening points on the right side of the control to remove the hooks from the control panel. To replace the control repeat the steps above in the reverse order making sure to connect all wires in the proper location. Place the appliance in operation following the steps outlined in Section 10.
11.2.4 Ignitor Assembly
The ignitor assembly is a two rod system that consists of a ground rod and a sense rod. To remove the ignitor assembly, shut off the 120 Volt power supply to the appliance. Turn off all manual gas valves connecting the appliance to the main gas supply line. Remove the front door of the boiler to gain access to the ignitor assembly. Remove the two wires connected to the assembly. Then remove the two bolts connecting the
ignitor assembly to the burner door. Remove and replace the old ignitor assembly gasket. Reinstall a new ignitor assembly in the reverse order if the old assembly is determined defective. Replace gasket if necessary.
11.2.5 Flame Sensor
The flame sensor is a single rod system. To replace the flame sensor electrode, shut off the 120 Volt power supply to the boiler. Turn off all manual gas valves connecting the boiler to the main gas supply line. Remove the front door of the boiler to gain access to the flame sensor electrode. Remove the flame sensor wire from the electrode. Remove the two bolts fastening the electrode to the burner doors. Remove and replace the old flame sensor gasket. Reinstall a new flame sensor electrode in the reverse order if the old electrode is determined defective.
Caution
Igniters and sensors get hot and
can cause burns or injury.
Figure 34. Burner Service.
Page 48
Page 48
BRADFORD WHITE CORP.
11.2.6 Transformer with Integral Circuit Breaker
The appliance has a 24Vac transformer with integral 4 amp circuit breaker installed for supplying the control voltage required for the appliance only. The transformer is sized for the appliance load only and should not be used to supply power to additional field devices. If additional loads are added or a short occurs during installation the integral circuit breaker may trip. If this happens make sure to reset the circuit breaker prior to replacing the transformer.
Depending upon the revision of the appliance the transformer may be mounted to the back or underneath the control panel. In either case, if the transformer must be replaced turn off the 120Vac power to the appliance. Remove the transformer wires from terminal blocks. Remove the fasteners holding the transformer and remove the transformer. Replace with a new transformer in reverse order.
If the transformer is replaced with parts other than the OEM transformer, be sure to add circuit protection if it is not integral to the new transformer.
WARNING
Failure to include proper circuit protection may lead to premature component failure, fire, injury or death.
11.2.7 Blower
The combustion air blower is a high-pressure centrifugal blower with a variable speed motor. Speed of the motor is determined by the control logic. 120 Volts remain on to the blower at all times. If a blower change is required, turn off the 120 Volt power and gas supply to the unit. Take the front panel off. Disconnect the 120 Volt and control signal connections from the blower. Disconnect the bolts connecting the venturi to the blower housing. Disconnect the fan outlet bolts from the burner door blower arm. If the fan is determined to be defective replace the existing fan with a new one reversing the steps above. Make sure to install all of the required O-rings and gaskets between the blower arm and the blower and blower face and venturi flange.
11.2.8 Heat Exchanger Coils
Black carbon soot buildup on the external surfaces of the heat exchanger is caused by one or more of the following; incomplete combustion, combustion air problems, venting problems and heater short cycling. Soot buildup or other debris on the heat exchanger may restrict the flue passages.
If black carbon soot buildup on the heat exchanger is suspected, disconnect electrical supply to the unit, and turn off the gas supply by closing the manual gas valve on the unit. Access the heat exchanger through the burner door at the front of the boiler, and inspect the tubing using a flashlight. If there is a buildup of black carbon soot or other debris on the heat exchanger, clean per the following:
Caution
Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or flame. To prevent this from happening, dampen the soot deposits with a wet brush or fine water spray before servicing the heat exchanger.
1. Shut off the 120 Volt power supply to the boiler
2. Turn off all manual gas valves connecting the boiler to the main gas supply line.
3. For NT 600 models only (all other sizes please skip to step four). NT 600 models will require the gas valve to be removed in order to remove the burner door. To do this, remove the wire connections from the gas valve. Remove the flange bolts from the gas supply pipe connected to the gas valve (1B). Remove the flange bolts connecting the gas train to the venturi (1A). Remove the gas train assembly keeping gaskets and o-rings.
4. Remove the four bolts connecting the blower flange to the burner door arm.
5. Remove the nuts located on the outside diameter of the burner door to the heat exchanger.
6. Remove the burner door/burner assembly from the heat exchanger.
7. Disconnect the condensate drain line.
8. Attach a longer hose to drain and run to a bucket.
9. Clean the heat exchanger by brushing light accumulations of soot and debris. Use a brush with soft bristle (non metal) to avoid damaging the surface of the heat exchanger tubes.
10. Once the tubes have been brushed clean rinse the tubes and combustion chamber with a small amount of water to rinse all of the debris out of the bottom of the flue collector and into the longer condensate trap line, which is being diverted into a separate container.
NOTE: The Warranty does not cover damage caused by lack of required maintenance, lack of water flow, or improper operating practices.
WARNING
Failure to rinse the debris from the heat exchanger and temporary drain line may lead to clogged condensate lines, traps and neutralizers. Condensate pumps (if used) may also be damaged from the debris left behind, possibly causing property damage.
11. Install all components removed in the reverse order to place the appliance back in operation. Make sure all gaskets are in place as components are installed. Replace any damaged gaskets. Do NOT reuse damaged gaskets.
12. Place the appliance in operation according to
Section 10 checking all gas connections for leaks.
Confirm all fasteners are tight.
Page 49
Brute Elite
Page 49
11.2.9 Gas Pressure Switches (optional)
The high and low gas pressure switches are 24V manual reset switches that act to cut power to the gas valves if the gas pressure is too low or too high for proper operation. The gas pressure switches used are integrally vent limited, and do not require venting to atmosphere. To remove a switch, remove the screw on the plastic housing and pull the clear cover off. Disconnect the two wires from the screw terminals. Twist the switch off the pipe nipple. Reassemble in reverse order. For natural gas, set the low gas pressure switch to 3" w.c. For propane, set the low gas pressure switch to 5" w.c. For natural and propane, set the high gas pressure switch to 14".
11.2.10 Gas Conversion
Brute Elite units can be converted from natural to propane gas or from propane to natural gas easily in the field. Some units require the addition of a gas orifice along with proper gas valve adjustment. Other units require no additional parts, only proper gas valve adjustment. Please contact the Bradford White factory for specific information regarding the gas conversion of an appliance. If a gas conversion is performed, the unit must be identified with the appropriate gas labels and a conversion sticker to allow technicians performing maintenance in the future to properly identify the gas type of the appliance.
SIZE (MBTU) KIT NUMBER
80 CA006201
105 CA006202
150 CA006203
199 CA006204
210 CA006204
285 CA006205
399 CA006207
500 CA006207
600 CA006207
750 CA006207
850 CA006207
Table 17. Propane Gas Conversion Kits.
SECTION 12. Trouble Shooting
12.1 Sequence of Operation
Brute Elite is a cold start appliance that should start only on a call for heat from a tank aquastat, room thermostat, zone valve end switch or other space temperature control device.
1. Upon a call for heat: (a) the internal pump and
system pump will start; (b) the blower will begin a
30 second pre-purge.
2. Following the prepurge cycle the direct spark
ignition will spark and will begin a 4 second trial
for ignition. The unit is allowed one or three
ignition retries.
3. The gas valve will then be energized and a reduced
rate ignition will occur. The unit will remain in a
reduced rate start-up period for several seconds.
4. After the reduced rate start time is over, the unit
will be in normal operation. Firing rate will
modulate based on the heating load via the
temperature controller settings and readings.
5. When the call for heat is complete, or the unit reaches
its setpoint temperature, the gas valve will close, and
the fan will continue to run for its 20 second post-
purge. If a pump delay time is used, the pump will
continue to run for the specified amount of time
(adjustable from 0.1 to 10 minutes).
12.2 Short Cycling
Because Brute Elite is a modulating boiler, and its input will decrease when there is a reduction in heating load, short cycling is greatly reduced. If the heating load drops below the minimum input of the boiler for an extended period, the boiler will have a tendency to short cycle. This can be a symptom of improper control strategy or setpoints, or a load distribution problem. Brute Elite has a built-in anti-short cycle (ASC) feature. ASC is a timed setting that will delay the boiler start for a specified time after one call for heat is completed. ASC time may be adjusted as desired (see Section 8 for more information).
12.3 Error Codes - See Table 18.
Page 50
Page 50
CODE# PROBLEM PROBABLE CAUSE SOLUTION
COMMON LOCKOUT CODES
BRADFORD WHITE CORP.
27 Internal error Flame rod to ground Check wiring / probe grounded, dirty probe
47 Flame rod to ground leakage Faulty flame detector Clean or replace flame detector
49 24VAC voltage low/high Faulty transformer Check/correct supply line voltage; replace faulty
transformer
52 Motor tachometer fault Faulty fan / fan wiring Check fan harness wiring for continuity; replace faulty
fan circuit
53 AC inputs phase reversed Reverse 24V hot/neutral - use common ground
61 Anti short cycle Call for heat will be held Change ASC timer setting
until timer resets
62 Fan speed not proved Dirty / defective fan Clean or replace fan; check wiring
63 LCI off Safety chain interrupt Check flow switch, aux high limit, LWCO, gas
pressure switches, condensate level and correct problem
69 Outlet high limit High limit tripped Determine cause: low/no flow, valves closed, settings
and correct
79 Outlet high limit
80 DHW high limit High limit reached
Check pump, time delay, valves closed, etc. and correct overtemp
81 Delta T inlet/outlet limit
82 Stack limit High limit reached Could be caused by high ambient temperature, or
high return water temperature
88 Outlet T-rise limit
90 Heat exchanger high limit
High limit reached Diagnose / repair cause of high temperature
91 Inlet sensor fault
92 Outlet sensor fault
93 DHW sensor fault
Faulty sensor or wiring Check wiring / replace sensor; condition can be
caused by short
95 Stack sensor fault
96 OAT temperature sensor fault Faulty outdoor air Check wiring and sensor for short; replace sensor
temperature sensor is open or shorted
105 Flame detected Flame exists at burner Clean burner of soot or other debris that could
out of sequence when it should not be maintain flame
106 Flame lost in MFEP
Unstable flame during
107 Flame lost early in Run lighting / flame proving Check venting, gas supply pressure, burner, fan, etc.
108 Flame lost in Run
sequence
109 Ignition failed Problem with ignitor, or Check / replace ignitor, wiring; check for shorting
other ignition-related device in ignitor cable
113 Flame circuit timeout Flame not established Check all combustion components; purge gas;
within expected time limit check ignition source
122 Lightoff rate proving failed
123 Purge rate proving failed
128 Fan speed failed / prepurge Fan did not reach Check fan wiring; replace fan
129 Fan speed failed / preignition
expected RPM
130 Fan speed failed / ignition
131 Fan movement detected Fan should not be moving Check for common venting problems or otherwise
during standby when not powered forced air
132 Fan speed failed during run Fan lost or gained speed Fan overheating or otherwise failing; check cable;
during run sequence away replace fan from control spec
137 ILK failed to close No power at interlock ILK Check J5 pin 1 for power - if no power, confirm
safeties are closed
continued next page >
Page 51
Brute Elite
CODE# PROBLEM PROBABLE CAUSE SOLUTION
ALERT CODES
49 Maximum cycle count Control operates correctly,
was reached however the cycle count will
50 Maximum hours count Control operates correctly,
was reached however the hours count will
248 CH outdoor temperature
was invalid
251 CH ODR max outdoor temp- Confirm outdoor reset
erature setpoint was invalid settings. An invalid
252 CH ODR min outdoor temp-
erature setpoint was invalid
253 CH ODR min water temp-
erature setpoint was invalid
254 CH ODR temperature range Increase Outdoor air temp-
was too small erature min and max values (min. 12°C / 22°F) to a difference greater than
255 CH setpoint minus ODR Increase Outdoor water
min water temperature was temperature min and max too small (min. 12°C / 22°F) values to a difference greater Increase setpoint or than 22°F (12°C) decrease min water temp.
565 Heat exchanger T-rise limit Heat exchanger temperature Check for correct water flow
was exceeded rise exceed
not increment any higher than 999,999 cycles
not increment any higher than 999,999 hours
adjustment has been made
22°F (12°C)
MISCELLANEOUS
Replace controller or adjust the count using blue display
Adjust setting to within appropriate range
Page 51
Boiler will not stay lit Indicates lack of flame signal, Check flame detector wiring; clean / replace flame
check fault code on display detector
Boiler bangs, knocks, hisses Insufficient water flow / Check for proper flow, follow piping guidelines in
pump failure; improper piping manual; replace pump; improper glycol percentage
(see Section 4.3)
Flame pulsates, venting Insufficient / improper Ensure venting complies with Section 2 noise or has difficulty lighting venting; dirty burner; air in
gas line; dirty heat exchanger
980 Display error Communication error Check wiring and connectors. Possible software
between the control revision incompatibility. and display.
981 Display error Communication error Check wiring and connectors. Possible software
between the control revision incompatibility. and display.
Table 18. Error Codes.
Page 52
Page 52
BRADFORD WHITE CORP.
To order or purchase parts for the Brute Elite, contact your nearest Bradford White dealer or distributor. If they cannot supply you with what you need,
SECTION 13.
Replacement Parts
Use only genuine Bradford White replacement parts.
13.1 General Information
contact Customer Service (see back cover for information).
BNTV 150 BNTV 199 BNTV 285 BNTV 399 BNTV 500 BNTV 600 BNTV 750 BNTV 850
SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE
13.2 Parts List
Jacket Components – See Figure 35
ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850
1 Front Panel Assembly R60D3200 R60D3200 R60D3200 R60D3200 R60D3200 R60D3201 R60D3202 R60D3202 R60D3202 R60D3202
2 Front Panel Handle R50D3204 R50D3204 R50D3204 R50D3204 R50D3204 R50D3204 R50D3204 R50D3204 R50D3204 R50D3204
3 Rear Panel R50D3101 R50D3101 R50D3101 R50D3101 R50D3101 R50D3101 R50D3101 R50D3101 R50D3101 R50D3101
4 Left Side Panel R15D3002 R15D3002 R15D3002 R30D3002 R30D3002 R40D3002 R50D3002 R50D3002 R75D3002 R85D3002
5 Right Side Panel R15D3001 R15D3001 R15D3001 R30D3001 R30D3001 R40D3001 R50D3001 R50D3001 R75D3001 R85D3001
6 Left Top Panel R8D3327 R10D3327 R15D3303 R20D3303 R30D3312 R40D3303 R50D3308 R60D3303 R75D3303 R85D3303
(Left Hand) (Left Hand) (2) BNTV
R15D3102 R15D3102 R51D3102
(Right Hand) (Right Hand) (2) (2) (2) (2) (2) BNTH (2) (2) (2)
Left Stanchion
Right Stanchion
10 Jacket Support, R50D3003 R50D3003 R50D3003 R50D3003 R50D3003 R50D3003 R50D3003 R50D3003 R50D3003 R50D3003
7 Middle Left Top Panel R8D3328 R10D3328 R15D3402 R20D3403 R30D3311 R40D3401 R50D3401 R60D3302 R75D3302 R85D3302
7A Middle Right Top Panel R8D3329 R10D3329 R15D3403 R20D3402 R30D3313 —————
8 Right Top Panel R8D3330 R10D3330 R15D3401 R20D3301 R30D3314 R40D3402 R50D3402 R60D3301 R75D3301 R85D3301
9 Jacket Angle Support R8D3102 R8D3102 R15D3102 R30D3102 R30D3102 R40D3102 R50D3102 R50D3102 R75D3102 R85D3102
11 Jacket Support, R50D3004 R50D3004 R50D3004 R50D3004 R50D3004 R50D3004 R50D3004 R50D3004 R50D3004 R50D3004
12 Front Bezel R50D7101 R50D7101 R50D7101 R50D7101 R50D7101 R50D7101 R50D7101 R50D7101 R50D7101 R50D7101
Internal Components – See Figure 36
Stanchion
20 Base Assembly R15D1100 R15D1100 R15D1100 R30D1100 R30D1100 R40D1100 R50D1100 R60D1100 R75D1100 R85D1100
21 Left Rear Support R50D1001 R50D1001 R50D1001 R50D1001 R50D1001 R50D1001 R50D1001 R50D1001 R50D1001 R50D1001
Support Stanchion (2) (2) (2) (2) (2) (2)
22 Left Front/Right Rear R50D1002 R50D1002 R50D1002 R50D1002 R50D1002 R50D1002 R50D1002 R50D1002 R50D1002
23 Cantilevered Base R15D1002 R15D1002 R15D1002 R40D1001 R40D1001 R40D1001 R40D1001 R50D1003 R75D1002 R75D1002
Stanchion
Page 53
Brute Elite
Page 53
(2) (2)
(2)
SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE
BNTV 150 BNTV 199 BNTV 285 BNTV 399 BNTV 500 BNTV 600 BNTV 750 BNTV 850
(2) (2) (2) (2) (2) (2) (2)
(2) (2) (2)
BNTV
R21D2000
BNTH
ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850
HX Stanchion
24A Brace, Rear, R50D1005 R50D1005 R20D1007 R20D1007 R50D1005 R85D1005 R85D1005 R85D1005 R85D1005 R85D1005
24 Brace, Front, R20D1005 R20D1005 R20D1005 R20D1005 R85D1005 R85D1005 R85D1005 R60D1005 R85D1005 R85D1005
HX Stanchion
26A Diagonal Brace ————————R75D1006 R75D1006
25 Mounting Rail R15D1004 R15D1004 R15D1004 R30D1004 R30D1004 R40D1004 R50D1004 R50D1004 R75D1004 85D1004
or Coupling
27 Condensate Trap Assy R20D4020 R20D4020 R20D4020 R20D4020 R50D4020 R50D4020 R50D4020 RA2116300 RA2116300 RA2116300
28 Heat Exch. Rail Clip R50D1006 R50D1006 R50D1006 —————
30 PVC Reducer RP2053000 RP2053000 RP2052900 RP2052800 R50D4027 RP2052800 RP2052800 RP2052800
30b 2" Dia. Pipe, CPVC RD2010212 RD2010212 RD2010213 RD2010213 ——————
30a CPVC Reducer RD2010501 RD2010501 RP2065600 RP2065600 R40D4020 R40D4020 R75D4020 R75D4020
31 Hose Barbed Adapter RP2067100 RP2067100 RP2056100 RP2056100 RP2056100 —————
33 Air Inlet/Exhaust Bracket R8D3005 R10D3005 R20D3120 R20D3120 R30D3505 R40D3005 R85D3005 R85D3005 R85D3005 R85D3005
Gas Train Components – See Figure 37
40 Combustion Air Blower RA2113700 RA2113700 RA2107500 RA2114200 RA2114200 RA2113100 RA2113100 RA2108500 RA2108500 RA2108500
41 Gas Valve/Venturi RV2017900 RV2017901 RV2017902 RV2017903 RV2017904 —————
44 Manual Gas Valve —————RV2000200 RV2003000 RV2003000 RV2003200 RV2003200
42 Gas Valve —————RV2019200 RV2019600 RV2019700 RV2019700 RV2019700
43 Gas/Air Venturi ——————RA2116700 RA2115000 RA2115000 RA2115000
44A Manual Gas Valve ——————RV2000200 RV2003000 RV2003000
Cork Gasket
46 Gas Valve/Venturi ——————RS2104900 RS2104900 RS2104900 RS2104900
45 Gas Valve Flange Kit ——————RV2050100 RV2050100 RV2050100 RV2050100
47 Gas Valve O-Ring R30-227 R30-227 R30-227 R30-227 R30-227 —————
48 Venturi O-Ring —————RS2105200 RS2105200 RS2105200 RS2105200 RS2105200
49 High Gas Pressure Switch ——————R50D5014 R50D5013 R75D5014 R75D5014
50 Low Gas Pressure Switch ——————R50D5015 R50D5012 R75D5015 R75D5015
Page 54
Page 54
BRADFORD WHITE CORP.
SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE
BNTV 150 BNTV 199 BNTV 285 BNTV 399 BNTV 500 BNTV 600 BNTV 750 BNTV 850
BNTH
RS2111000
BNTV
BNTH BNTH BNTH BNTH
R20D4040 R50D4040 R50D4040 R50D4040
BNTV BNTV BNTV BNTV
R2069400 R2069400 R2069400 R2069400 R2069400 R2069400 R2069400 R2069400 R2069400 R2069400
(burner door)
51 Duct/Venturi Transition R10D5021 R10D5021 R10D5021 R105013 R30D5013 R50D5017 R60D5052 R60D5052 R85D5052
ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850
Formed Nipple
Heat Exchanger Components – See Figure 38
52 Gas Supply Pipe RP2051700 RP2051400 RP2051400 RP2051400 RP2051500 RP2054300 RP205200 RP205200 RP2064200 RP2064200
53 Gas Pipe, 3/4" NPT —————RP2056500 ————
55 Air Inlet Flex Hose RD0091402 RD0091402 RD0091402 RD0091401 RD0091401 RD0091202 RD0091301 RD0091201 RD0091203 RD0091203
56 Air Inlet Collector —————RV2019400 ————
57 Electrical Connector w/Cable —————RE2331700 RE2331700
58 Elbow Adapter —————RV2019300 RV2019300
59 Blower Gasket W/Fasteners ———————RS2107500RS2107500RS2107500
60 Heat Exchanger RS2106900 RS2105500 RS2105800 RS2105700 RS2111100 RS2111200 RS2111300 RS2111300 RS2111400 RS2111500
61 Pump Assembly R8D4110 R10D4110 R10D4110 R20D4140 R30D4110 R40D4110 R50D4110
62 Low Water Cutoff Switch ——————RE2076500 RE2076500 RE2076500 RE2076500
63 Water Temp Sensor RE2320600 RE2320600 RE2320600 RE2320600 RE2320600 RE2320600 RE2320600 RE2320600 RE2320600 RE2320600
64 Duplex Water RE2319900 RE2319900 RE2319900 RE2319900 RE2319900 RE2319900 RE2319900 RE2319900 RE2319900 RE2319900
Temperature Sensor
Temperature Sensor
BNTH (30 PSI) (30 PSI) (30 PSI) (30 PSI) (75 PSI) (75 PSI) (75 PSI) (75 PSI) (75 PSI) (75 PSI)
Pressure Relief Valve, RA2114802 RA2114802 RA2114802 RA2114802 RA2114802 RA2114802 RA2114802 RA2114802
65 Duplex Stack RE2319700 RE2319700 RE2319700 RE2319700 RE2319800 RE2319800 RE2319800 RE2319800 RE2319800 RE2319800
66 Pressure Relief Valve, R51-182 R51-182 R51-182 R51-182 RA2113602 RA2113602 RA2113602 RA2113602 RA2113602 RA2113602
BNTV (125 PSI) (125 PSI) (125 PSI) (125 PSI) (125 PSI) (125 PSI) (125 PSI) (125 PSI)
67 Air Vent R1-592 R1-592 R1-592 R1-592 R1-592 R1-592 R1-592 R1-592 R1-592 R1-592
68 Burner Door w/gaskets RS2108300 RS2108300 RS2108300 RS2108300 RS2108300 RS2108300 RS2108300 RS2108300 RS2108300 RS2108300
68A Gaskets-only
69 Burner Gasket RS2108500 RS2108500 RS2108500 RS2108500 RS2108500 RS2108500 RS2108500 RS2108500 RS2108500 RS2108500
(burner, ignitor, sensor & door gaskets)
69A Gasket Set RS2109100 RS2109100 RS2109100 RS2109100 RS2109100 RS2109100 RS2109100 RS2109100 RS2109100 RS2109100
Page 55
Brute Elite
Page 55
SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE
Contact Customer Service at 800 900-9275 x11
BNTV 150 BNTV 199 BNTV 285 BNTV 399 BNTV 500 BNTV 600 BNTV 750 BNTV 850
(80-600) RS2108400 RS2108600 RS2108600 RS2108700 RS2108700 RS2108700 RS2108801 RS2108801 RS2115400 RS2115400
ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850
70 Front Refractory Tile RT2109000 RT2109000 RT2109000 RT2109000 RT2109000 RT2109000 RT2109000 RT2109000 RT2109000 RT2109000
71 Rear Refractory Tile R50D2021 R50D2021 R50D2021 R50D2021 R50D2021 R50D2021 R50D2021 R50D2021 R50D2021 R50D2021
72 Main Burner w/gasket R2069101 R2069102 R2069103 R2069104 R2069105 R2069106 R2069106 R2069107 R2069108 R2069109
73 Flame Sensor w/gasket R2069200 R2069200 R2069200 R2069200 R2069200 R2069200 R2069200 R2069200 R2069200 R2069200
74 Ignitor w/gasket R2069300 R2069300 R2069300 R2069300 R2069300 R2069300 R2069300 R2069300 R2069300 R2069300
74A Ignitor Gasket RW2013300 RW2013300 RW2013300 RW2013300 RW2013300 RW2013300 RW2013300 RW2013300 RW2013300 RW2013300
Flame Sensor
74B Screw, Ignitor/ m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm
74C Flame/Sensor Gasket RW2013400 RW2013400 RW2013400 RW2013400 RW2013400 RW2013400 RW2013400 RW2013400 RW2013400 RW2013400
Air Adapter (750-850)
Channel (5) (5) (5) (5) (5) (5) (5) (5) (5) (5)
75 Air/Gas Channel
75A Screw, Air/Gas RS2109400 RS2109400 RS2109400 RS2109400 RS2109400 RS2109400 RS2109400 RS2109400 RF2029200 RF2029200
76 Drain R10-143 R10-143 R10-143 R10-143 R10-143 R10-143 R10-143 R10-143 R10-143 R10-143
77 Sight Glass R50D2020 R50D2020 R50D2020 R50D2020 R50D2020 R50D2020 R50D2020 R50D2020 R50D2020 R50D2020
Electrical Components – See Figure 39
80 Control Panel Enclosure R50D7001 R50D7001 R50D7001 R50D7001 R50D7001 R50D7001 R50D7001 R50D7001 R50D7001 R50D7001
81 Transformer RE2108700 RE2108700 RE2108700 RE2108700 RE2108700 RE2108700 RE2108700 RE2108700 RE2108700 RE2108700
82 High Voltage Shield R50D7002 R50D7002 R50D7002 R50D7002 R50D7002 R50D7002 R50D7002 R50D7002 R50D7002 R50D7002
83 Top Panel Bracket R50D7003 R50D7003 R50D7003 R50D7003 R50D7003 R50D7003 R50D7003 R50D7003 R50D7003 R50D7003
Module, Standard
Module, CSD-1
84 Electronic Control ——————RS50D7008 RS50D7008 RS50D7008 RS50D7008
84 Electronic Control
85 Rocker Switch RE2322700 RE2322700 RE2322700 RE2322700 RE2322700 RE2322700 RE2322700 RE2322700 RE2322700 RE2322700
Control Display, CSD-1 ——————RE2334000 RE2334000 RE2334000 RE2334000
86 Control Display RE2333500 RE2333500 RE2333500 RE2333500 RE2333500 RE2333500 RE2333500 RE2333500 RE2333500 RE2333500
87 Wire Harness R50D7412 R50D7412 R50D7412 R50D7408 R50D7408 R50D7406 R50D7402 R50D7410 R50D7409 R50D7409
88 Wire Harness, CSD-1 ——————R50D7404 R50D7411 R50D7413 R50D7413
89 Air Pressure Switch RE2334700 RE2334700 RE2334700 RE2334700 RE2334700 RE2334700 RE2334700 E2334701 RE2334700
90 Water Flow Switch —————RE0013100 RE0013100 RE0013100 RE0013100 RE0013100
Page 56
Page 56
BRADFORD WHITE CORP.
Figure 35. Jacket Components.
Page 57
Brute Elite
Page 57
Figure 36A. Internal Components, Sizes 80–210. Figure 36B. Internal Components, Sizes 285–600.
Page 58
Page 58
BRADFORD WHITE CORP.
Figure 36C. Internal Components, Sizes 750-850.
Page 59
Brute Elite
Page 59
Figure 37A. Gas Train Components, Sizes 80-500.
Page 60
Page 60
BRADFORD WHITE CORP.
Figure 37B. Gas Train Components, Sizes 600-850.
Page 61
Brute Elite
Page 61
Figure 38. Heat Exchanger Components.
Page 62
Page 62
BRADFORD WHITE CORP.
Figure 39. Electrical Components.
Page 63
Brute Elite
Page 63
Page 64
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
®
Ambler, PA 19002 Tech. Service (800) 334-3393 Service Parts (800) 538-2020
www.BradfordWhite.com
Warranty Service (800) 531-2111 Litho in U.S.A. © Bradford White 1102 Document 1243
H2343100-
Loading...