Installation, Operation and Maintenance Instructions Document 2143
C O R P O R A T I O N
BW
RADFORDHITE
®
Installation, Operation
and Maintenance
Instructions for
Copper Brute
Volume Water Heaters
Model B4
Sizes 175-400
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water heater installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a re or explosion may result
causing property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency, or gas
supplier.
This manual provides installation, operating, and
maintenance instructions for Copper Brute Volume
Water Heaters, Sizes 175 through 400. Review all
application and installation procedures completely
before proceeding with the installation. Experience
has shown that most operating problems are caused by
improper installation.
1.2 Warranty
The Copper Brute heaters are sold with a limited
factory warranty.
Make all warranty claims to an authorized
Bradford White representative or directly to the
factory. Claims must include the heater serial number
and model (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Inspect everything for damage immediately
upon delivery, and advise the transporter of any
shortages or damage. Any such claims should be led
with the transporter. The transporter will not accept a
claim from the shipper, Bradford White.
The warranty does not cover damage caused by
improper installation, operation, or eld modication.
1.3 Technical Assistance
Consult Bradford White or your local wholesaler
with any questions or problems involving the
specication, installation and operation of Bradford
White equipment. An experienced technical support
staff is ready to assist in assuring the proper
performance and application of Bradford White
products.
Dimensions shown in inches cm.
Gas Connection
Size Water C C V
Connect. U.S. Only (Indoor) Vent
Nat. Propane Size A B (Outdoor) Dia.
Size in. mm in. mm in. mm in. cm in. cm in. cm in. cm in. mm
Follow local regulations with respect to installation
of carbon monoxide (CO) detectors and
manufacturer's maintenance schedule of the heater.
Install the Copper Brute heaters in accordance
with the procedures in this manual (or the warranty
may be voided), local codes and ordinances. In the
absence of such codes, install the heaters in accordance
with the latest edition of the National Fuel Gas Code,
ANSI Z223.1. In Canada, the installation must be
in accordance with CAN1-B149.1 or .2 and local
codes. The authority having jurisdiction may require
the installation conform to the Standard for Controls
and Safety Devices for Automatically Fired Heaters,
ANSI/ASME CSD-1. Any changes to the heater, gas
controls, gas orices, wiring or draft diverter may void
the warranty. If eld conditions require a change to
any of the above, consult the factory.
All gas-red products require correct installation
to assure safe operation. The requirements for heaters
include the following:
1. Field assembly of drafthood or vent cap (see
Section 2.2).
2. Appropriate site location (clearances) and
ooring.
3. Sufcient combustion and ventilation air.
4. Adequate venting of combustion products.
5. Adequate water ow.
6. Properly sized gas meter and piping.
7. Proper electrical wiring.
This manual provides the information needed to
meet these requirements. Review all application and
installation procedures completely before continuing
the installation.
a. Remove the top ller plate, stamped “HOT”, by
slipping a ne-blade screwdriver into the slot at
the rear of the plate and gently prying it up (see
Figure 2).
b. Remove the two screws attaching the adapter
plate to the top assembly and lift it out (see
Figure 3).
c. Remove the vent cap or drafthood from its
package.
d. Disengage the ue transition ring from the stack
extension and place it on top of the collector
assembly as shown in Figure 4.
Figure 2. Top ller plate. Figure 3. Adapter plate.
Figure 4. Flue transition Figure 5. Vent cap with
ring. adapter plate
(outdoor).
2.2 Field Assembly
The Copper Brute heater is shipped from the
factory with the top assembly in the low-prole
conguration for outdoor installations.
The Copper Brute heater is design certied
for indoor installation when equipped with a
special drafthood, which must be installed without
modication. The part number for the drafthood is on
the heater rating plate. Follow this procedure to make
the conversion:
stack extension as shown in Figure 5. Fit the
stack extension down over the ue transition
ring. Seat the adapter plate on the top assembly
and secure it with two screws (see Figure 6).
f. Indoor models, size 175 and 250 only, require
an adapter cable (included with product). The
cable connects the blocked vent safety switch
(BVSS) on the bell of the external draft hood to
the 6-position Molex plug on the side of the unit
(see Figure 7). Refer to instruction sheet included
with cable.
2.3 Site Location
2.3.1 Installation Information
Closet Installation
(unacceptable)
A closet is any 4 sided enclosure
which is less than 16* times the
total volume of all the gas red appliances within the enclosure.
Page 5
Room Installation
(acceptable)
A room is any enclosure which is
at least 16* times greater than the
total volume of all the gas red appliances within the enclosure
WARNING
Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide
in ue gases which could result in severe injury,
property damage, or death.
Avoid placing the heater in locations where it can
be damaged by water or condensate leakage. If this is
not possible, provide a suitable drain pan to catch and
divert any leakage. The pan must not block natural
ow of air around the heater.
Locate the heater to provide adequate clearance
on all sides for inspection, service and to provide
adequate air circulation for proper operation.
Locate the heater so the clearances from
combustible surfaces shown in Table 1 and Figure 8
are met.
Locate the heater on a waterproof oor with a
oor drain and a 6 inch (152 mm) minimum curb on
all four sides to protect the building if heater repairs
are needed.
Indoors Outdoors
Clearance from: inch mm inch mm
Top 37 940 Unobstructed
Water conn. side 12 305 Unobstructed
Opposite side 6 152 6 152
Front Alcove Unobstructed
Rear 6 152 6 152
Vent* 6 152 —
Flooring Combustible Combustible
Service clearance = 36 inches (914mm) at front of heater,
and 18 inches (457mm) at water connection side.
*1" (25mm) if double wall vent is used.
Table 1. Minimum Boiler Clearances
from Combustible Surfaces.
Alcove Installation
(acceptable)
An alcove suitable for the installation of a heater is a restricted section of a room not separated from
the room by a door or partition and
which meets the minimum clearances specied in this manual.
* When the ceiling height exceeds 8 feet, you are only allowed to consider 8 feet when calculating the total volume of the enclosure.
Figure 8. Alcove installation.
2.3.2 Outdoor Installation
Caution
Outdoor installations are not recommended in areas
where the danger of snow blockage exists. Copper
Brute heaters can be installed in the standard lowprole, grate top conguration as received from the
factory, or with an optional vent cap.
Locate the heater in an open, unroofed area.
Do not locate the heater below or adjacent to any
doors, windows, louvers, grills, etc., which connect
in any way with an inhabited area of a building, even
though the access might be through another structure
such as a garage or utility room (see Figure 9 and
Table 1). There must be a minimum of 4 feet (1.22
m) horizontally and vertically between the heater and
any door, window, or gravity inlet to a building (see
Figure 10).
If the heater is installed close to a structure,
protect it from rain water runoff with rain gutters on
the roof or other measures. Do not locate the heater
near sprinkler systems that could spray water on it.
Avoid locations where wind deection off nearby
structures might cause wind loading and downdraft
conditions. Where downdraft conditions exist, locate
the heater at least 3 feet (0.91 m) from the structure.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 7
WINDOW
OR GRILL
INDOOR
ROOM
WRONG
4 ft
(1.2m)
4 ft
(1.2m)
4 ft
(1.2m)
Page 6
Figure 9. Incorrect outdoor installation.
BRADFORD WHITE
Concrete slab must extend out
a minimum of 12 in. (305mm) on
all sides.
Bradford White
UNIT
(Side View)
Base For Combustible Floors
Roof - Wood and Steel Construction
Figure 11. Standard base for combustible oor.
Mounting Platform must extend
out a minimum of 12 in. (305mm)
on all sides.
Figure 10. Outdoor location installation.
2.3.3 Flooring - Typical Installation
Do not install the heater directly on carpeting
without placing a non-combustible platform between
the carpeting and the heater. If the heater is installed in
a carpeted alcove, the entire oor of the alcove must
be covered by a non-combustible panel. The panel
must be strong enough to carry the total weight of the
heater and all piping, pumps, and any other equipment
attached to the heater. For rooftop installation, see
Figure 11 through Figure 13.
Bradford White
20 Gauge
Galvanized
Sheet Metal
Cap
Roong
Figure 12. Typical roof mounting.
Base For Combustible Floors
Bradford White
(Side View)
UNIT
(Side View)
Raised Mounting
Platform (Wood)
UNIT
Base Rail
Flashing
Roof
Base Rail
20 Gauge
Galvanized
Sheet Metal
Cap
2.4 Combustion and Ventilation
Air Supply
All indoor installations must have openings to
outside air for combustion, ventilation and dilution of
ue gases from inside the building (see Figure 14 and
Table 2 ). Bradford White does not recommend indoor
installations that do not provide combustion air from
outside the building.
Base For Combustible Floors
Flashing4x4 Stringer
Figure 13. Typical roof mounting with standard
combustible mount base.
Roof
Roong
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
10 ft.
(3.0m)
2 ft. (0.6m)
Listed
Vent
Cap
Storm Collar
Roof Jack
Adequate
Air Supply
To
Room
To
p and
Botom
1/14 in. (6mm)
Minimum Pitch
Per Foot of
Horizontal Pipe
Draf
thood
12 in.
(305mm)
All Sides
Vent terminated at
least 24 in.
(610mm) above
any object within
10 ft. (3.0m)
Page 7
Required Net Free Opening Area
Directly from Outside
1. The drafthood must sit directly on top of the heater
as shown and must not be altered in any manner.
2. An Underwriters' Laboratories listed vent cap is re quired to eliminate downdraft and allow the heater
to function properly.
3. Use approved roof tting.
Figure 14. Indoor installation and venting.
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
In the United States, the most common
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1:
Two permanent openings, one commencing
within 12" (30 cm) of the top and one commencing
within 12" (30 cm) of the bottom of the enclosure
shall be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces that
freely communicate with the outdoors. When directly
communicating with the outdoors directly, or through
vertical ducts, each opening shall have a minimum
free area of 1 square inch per 4000 Btu/hr (550 square
mm/kW) of total input rating of all equipment in the
enclosure. When communicating to the outdoors
through horizontal ducts, each opening shall have a
minimum free area of not less than 1 square inch per
2000 Btu/hr (1100 square mm/kW) of total input rating
of all equipment in the enclosure.
Method 2:
One permanent opening, commencing within
12" (30 cm) of the top of the enclosure shall be
permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces
that directly communicate with the outdoors, and shall
have a minimum free area of 1 square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of
all equipment located in the enclosure. This opening
must not be less than the sum of the areas of all vent
connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in ANSI Z223.1, or applicable
codes.
In Canada, Table 2 does not apply. Consult
local building and safety codes or, in absence of such
requirements, follow CAN/CGA B149.
NOTE: Check with louver manufacturers for net
free area of louvers. If screens or louvers are installed,
add 50 percent for each screen/louver to the net free
area Check all local codes applicable to combustion
air.
2.4.1 Outdoor Air Supply
When combustion air comes directly through an
outside wall, each opening must have a minimum free
area of at least one square inch for each 4,000 BTU/h
input of the total input rating of all appliances in the
enclosed area. (In Canada, refer to CGAB149.1 and .2.)
2.4.2 Indoor Air Supply
Conned and non-conned areas have different
requirements for installation. Consult the latest edition
of the National Gas Code for installation requirements.
2.4.3 Exhaust Fans or Vents
Any equipment which uses air or removes air
from the heater room can use up the combustion air
supply or reverse the natural draft action of the venting
system. This could cause ue products to build up in
the heater room. More air must be supplied to make up
for the decrease.
Internet Version for Reference Only
Page 8
Copper Brute B4 Volume Water Heaters
Page 9
BRADFORD WHITE
2.5 Venting of Combustion Products
2.5.1 General Information
When installed indoors, the drafthood must be
connected to a venting system. The venting system
must be installed by a qualied installer and in
accordance with the latest edition of ANSI Z223.1. In
Canada, the installation must be in accordance with
CAN1-B149.1 or .2, and any local codes that apply.
The vent pipe must have a listed vent cap, and
extend at least 2 feet (0.6 m) above any object within a
10 foot (3.0 m) radius.
NOTE: Do not use sheet metal screws at the
snap lock joints of Type B double-wall gas vents.
Do not weld or bolt the vent pipe to the heater
drafthood. The weight of the stack must not rest on the
heater. The drafthood and heater top must be easily
removable for normal heater service and inspection.
WARNING
Avoid ending heater vents near air conditioning or
air supply fans. The fans can pick up exhaust ue
products from the heater and return them inside the
building, creating a possible health hazard.
Avoid horizontal runs of the vent pipe and 90
degree elbows, reductions, and restrictions. Horizontal
runs should have at least a 1/4 inch (6.3 mm) rise per
foot in the direction of ow. Support a vent connector
for the design and weight of the material used to
maintain clearances and physical damage and separate
of joints.
Always use double-wall or insulated vent pipe
(Type B or equivalent).
WARNING
In cold weather, uninsulated outside vents can
chill the rising ue products, blocking the natural
draft action of the venting system. This can create
a health hazard by spilling ue products into the
heater room.
Avoid oversize vent piping or extremely long
runs of the pipe which may cause too much cooling
and condensation of ue gasses.
When the installation of a power vent or draft
fan in the venting system is necessary, qualied
personnel should design the installation following
good engineering practices and all applicable codes.
A suitable draft switch must be wired into the heater
control circuit at the terminal designated Field
Interlock to keep the heater from ring unless there is
a positive draft.
2.5.2 Replacement of Existing Heater
When a heater is removed from a common
venting system, the venting system may be too large
for proper venting of the other appliances connected
to it.
If replacing an existing heater with a Copper
Brute heater and the existing heater was connected
to a common venting system, the common venting
system must comply with ANSI Z223.1/National Fire
Protection Association (NFPA) 54. When resizing any
portion of the common venting system, the common
venting system should be resized to approach the
minimum size as determined using the tables in
ANSI Z223.1/NFPA 54, Appendix G. In Canada, the
common venting system should be resized so the
installation will be in accordance with CAN/CGA
B149.1 or .2.
2.6 Water Flow
2.6.1 Reversible Water Connections
Bradford White ships the heater with the
water connections on the right side. The heater can
be installed with the water connections on either
side. It could be necessary, or helpful, to switch the
connections to the left side to improve access for
installation service. Have a professional service
technician perform this modication before installing
the heater using the following procedures:
1. Remove the front cover.
2. If there is a vent cap or drafthood installed, they
must be removed before removing the grate top
assembly. On indoor installations (sizes 175-
250), the drafthood switch must be disconnected
at the left side of the heater.
3. If the unit is in the low-prole outdoor
conguration, remove the hex-head screws
(see Figure 15) and lift the grate top assembly
straight up.
4. Remove the screws that fastens the ue collector
holddown clamps and remove the clamps (see
Figure 16).
5. Remove the ue collector assembly by lifting it
out of the chassis.
6. Remove the screws that fastens the gap closures
and put them aside.
7. Remove the three grommets.
8. Remove the drain valves and plug. There is one
hex plug on the left side, near the rear of the
jacket. The drain valves are located on the left
side and right side of the heater (see Figure 15).
9. Remove the four screws that fastens the metal
channels covering the capillary tube on the right
side of the jacket, and lay the channels aside.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Clamp
Bracket
Heat
Exchanger
Bracket
In/Out Header
Clamp
Flue Collector
REAR TILE COVER
FLOW SWITCH
CONDUIT
GAP CLOSURE
GROMMET
DRAIN
VALV
E
METAL CHANNEL
(FOR CAPILLAR
Y TUBE)
TERMINAL STRIP
HEAT EXCHANGER
ASSEMBLY
GAP CLOSURE
DRAIN PLUG
DRAIN VALV
E
REAR TILE
COVER
HEX HEAD
SCREWS
MANUAL RESET
HIGH LIMIT
SWITCH BOX
Page 9
Figure 15. Heat exchanger reversal.
Figure 16. Flue collector Holddown Clamps.
Internet Version for Reference Only
Page 10
Copper Brute B4 Volume Water Heaters
Page 11
3.1 in.
(79mm)
2.4
in.
(61mm)
2.4
in.
(61mm)
Attach Capillary
Covers
on
Left Side
LEFT
0.9 in.
dia
(23mm)
(Two holes)
FRONT
1.9 in.
(48mm)
Retaining
Clip
2-Stage/
Operating
Controller
Header
Modulating (if
installed)
InletOulet
High Limit
BRADFORD WHITE
10. In the control compartment, nd the manual reset
high-limit switch box (see Figure 15) and loosen
the screw on the top to remove the cover.
11. Loosen the screw that fastens the white wire and
remove it from the terminal. Pull it out through
the top of the case and separate the other white
wire from the red wire coming from the fuse
Figure 17. Sensory bulb locations.
Figure 18. Retaining clip removal.
Figure 19. Hole location, left side.
holder. Gently pull the two white wires out of the
control compartment and coil them on top of the
heat exchanger.
12. A temperature control sensing bulb is located
in the front of the header on the inlet side and a
manual reset hi-limit sensing bulb is located on
the back side of the header on the outlet side (see
Figure 17). Remove these sensing bulbs from the
header. The following steps for removal apply to
all sensing bulbs:
a. If there is more than one capillary tube coming
out of the header, label the capillary tubes.
b. Loosen the screw on the capillary tube
retaining clip, then gently pry the clip apart
until it comes free from the temperature
control (see Figure 18).
c. Pull the sensing bulbs out of the temperature
control.
d. Gently pull the capillary tubes into the control
compartment.
e. Pull the temperature sensing bulb out of the
header, and temporarily route it to the front of
the heater.
13. Use a pair of diagonal cutters to cut the plastic
tie around the wire bundle in the control
compartment.
14. On the terminal strip, disconnect the two brown
wires from No. 5 and No. 6 terminals.
15. Remove the ow switch conduit retaining clip
and the elbow leading into the jacket.
16. Reach inside the control compartment and
release the retaining nut in the upper right corner.
The nut should only be nger-tight.
17. When the conduit is pulled away from the jacket,
pull the two brown wires out of the control
compartment. Coil the conduit and wires on top
of the heat exchanger.
18. Use a chassis punch to put two 7/8 inch (22
mm) holes in the front left side of the jacket (see
Figure 19).
19. Remove the front and rear tile covers (see
Figure 15).
20. Lift out the heat exchanger assembly, turn it 180
degrees, and reseat the unit in the heater with the
water connections on the left side.
21. Reinstall the front and rear tile covers.
22. Push the capillary tube(s) out through the lower
hole in the left side of the jacket.
23. Install the sensing bulb(s) into the appropriate
temperature control (keep in mind that the
positions of the inlet and outlet have been
reversed. The inlet is now behind the outlet).
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 11
24. Fasten the capillary tube(s) by squeezing the
retaining clip together, then tighten the screw.
25. Feed the two brown wires through the top hole
on the left side until the conduit elbow is against
the jacket.
26. Fasten the conduit by sliding the retaining nut
over the two brown wires (inside the control
compartment) then screwing it down nger-tight
on the conduit elbow.
27. Straighten the capillary tubing and fasten it to the
side of the heater under the channel. Use the selftapping screws to fasten the channel to the jacket.
28. Feed the two white wires into the control
compartment. Attach one wire to the terminal
in the manual reset hi-limit switch. If one is not
installed, attach it to terminal No. 1. Connect the
other wire to the red wire attached to the fuse
holder.
29. Attach the two brown wires to terminals No. 5
and 6 on the terminal strip. Keep all wiring away
from surfaces that will get hot during heater
operation.
30. Replace the gap closures and tighten the screws
securely.
31. Replace the three grommets and the cap.
32. Reinstall the drain plug and drain valves.
33. Slip the ue collector assembly back down inside
the enclosure.
34. Carefully slip a hand inside to make sure there
are no gaps between the heat exchanger and the
ue collector.
35. Check to make sure the wiring is not pinched
against sharp edges, or resting on the collector
assembly.
36. Replace the two ue collector holddown clamps.
37. Replace the top assembly and fasten it with the
hex-head screws.
38. Replace the front cover.
39. Reinstall the vent cap or drafthood if one was
removed.
40. On indoor installations (sizes 175-250), insert the
draft hood switch plug into the receptacle on the
left side of the heater.
2.6.2 Water Chemistry
Bradford White equipment is designed to be used
in a variety of water conditions. With the proper pump,
the water velocity in the heat exchanger tubes is kept
high enough to prevent scaling from hard water, yet
low enough to avoid erosion by soft water.
NOTE: It is possible to have hard and soft
water in the same city. Check with the local water
companies.
If an installer sees damage to any water handling
equipment at the installation site, it should be repaired
as soon as possible to help reduce maintenance costs.
If there is erosion, resize the pump to reduce water
velocity before the tube ruptures. If scaling is bad,
set up a heat exchanger tube-cleaning maintenance
schedule to prevent heat exchanger tube cracking
and wear. Not xing the condition will mean serious
damage to the heater and the water system.
NOTES:
• In areas where the water supply is soft or
corrosive, the heater must have cupronickel tubes
in the heat exchanger.
• Bradford White does not warrant heat exchangers
damaged by scaling, corrosion, or erosion.
2.6.3 Freeze Protection
Although Copper Brute heaters are design
certied for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures unless proper precautions are taken.
Consult the local factory representative or Bradford
White for additional information.
2.6.4 Water Hardness
Consider the water hardness when selecting a
pump for the heater (see Table 3). Hard water needs a
pump which can provide high ow to prevent scaling,
while soft water needs low ow to prevent erosion.
2.6.5 Pump Requirements
The Copper Brute heater has a factory installed
pump which is for heater-to-tank circulation only.
Pump performance is shown in Table 4.
The pump that is mounted on the heater is sized
for the heat exchanger and 30 feet (9.1m) of 1-1/2"
pipe, including six (6) 90° elbows. If more piping is
needed, contact Bradford White for options.
The water temperature entering the Copper Brute
must be at least 110°F (43°C).
Figures 20, 21 and 22 show typical piping
arrangements. For assistance with other piping
methods, contact Bradford White.
Hardness Grains per Parts
Category Gallon per Million
Soft 1 through 7.5 17 through 128
Normal 7.6 through 17 129 through 291
Hard Over 17 Over 291
Table 3. Water Hardness.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 13
To
Drain
Heater
T1
A
B
Remote
Temperature
Control for Heater
Page 12
Heat Flow Pressure* Water Temp
Exch. Water Rate Drop Rise
Model Passes Category
*Pressure drop includes head loss of heat exchanger and through 30 feet (9.1 m) of pipe and normal ttings when heater
is installed with storage tank. Pipe and ttings are assumed to be 1-1/2 inch (38 mm).
Table 4. Pump Performance Requirements.
Adjustment Procedure
1. Turn on heater and open gate
valves A and B.
2. After 15 minutes, read T1.
3. If T1 is less than 110°F (43°C),
slowly close valve B until T1
climbs to 110°F (43°C).
4. If T1 is greater than 110°F (43°C),
slowly close valve A until T1
drops to 110°F (43°C).
5. Check after 5 minutes
operation and make nal
adjustments.
Main Circulating Loop
(With Own Pump)
Water Maintained
Less Than 110°F (43°C)
Figure 20. Cold water application.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Conventional
Tank
Heater
To
Drain
Drain
24-inch
Min.
Service
Valves
Cold
Water
Hot Water
to Building
Hot Water
Return from
Building
Check
Valve
Bldg.
Loop
Circ.
Pump
Hot Water
Return from
Building
Throttling
Valve
Check
Valve
Bldg.
Loop
Circ.
Pump
Cold
Water
Conventional
Tank
To
Drain
Hot Water
to Building
Optional Cold
Water Supply
When Adequate
Tank Opening
Not Available
Heater
Pump
To
Drain
Service
Valves
Page 13
Figure 21. Hot water supply with vertical tank.
Note:
Heavy lineindicates heater-to-tank circulation loop.
Figure 22. Hot water supply with horizontal tank.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 15
Flow
Switch
Pressure
Relief
Valve
High-Limit
Dry
Well
Page 14
2.6.6 Pressure Buildup in Water System
The water utility supply meter may contain a
check valve, back ow preventer, or water pressure
reducing valve that will create a closed water supply
system. Contact the water supplier or local plumbing
inspector on how to control this situation.
During the heating cycle of the heater, the water
expands creating a pressure buildup in the water
system. The pressure relief valve may discharge hot
water under these conditions, causing a loss/waste of
energy and a buildup of lime on the relief valve seat.
NOTE: Do not plug the relief valve.
There are two methods to prevent the relief valve
from discharging hot water in a closed water system:
1. Install a pressure relief valve on the cold water
supply line. Make sure that the discharge of this
valve is directed to an open drain and protected
from freezing.
2. Install a properly sized thermal expansion tank
on the cold water supply line.
2.6.7 Pressure Relief Valve
The pressure relief valve must be installed in the
tapped opening provided in the boiler header with its
outlet piped to a drain or oor sink. Special attention
must be given to relief valve settings in installations
where the boiler is located on the ground oor of a
tall building, or where the operating temperature of
the boiler is above 210°F. In both instances, the static
pressure of the system is elevated, and could cause
the relief valve to leak. Where no special setting of
the relief valve is ordered, the factory will furnish a
125 psi setting.
WARNING
Hot water can scald! Hot water can produce
third degree burns in 6 seconds at 140°F (60°C)
and in 30 seconds at 130°F (54°C).
2.6.8 Water Pressure
Keep the water pressure in the system above
30 psi (207 kPa). If the system pressure drops below
30 psi (207 kPa), it could damage the heater through
lack of circulation. If for any reason, the water is
turned off temporarily, to service the equipment for
example, airlock could be a problem when the heater
is turned back on. To eliminate the airlock, open the
pressure relief valve (see Figure 23) and allow the air
to bleed out until water starts to ow. As soon as full
circulation is restored, the trapped air will be released
through the hot water faucets.
BRADFORD WHITE
Figure 23. Pressure relief valve.
2.6.9 Storage Tank Installation
1. Be sure the oor is structurally capable of
supporting the tank when it is lled with water,
and is waterproof.
2. Place the tank so that manholes, inspection
covers, nameplates and drain valves are
accessible.
3. Be sure the tank is suitable for the water in the
system. Some water is corrosive and requires
a protected tank. Most tanks are available with
glass, plastic, or galvanized linings.
4. If the tank is glass-lined, it should be equipped
with a suitable magnesium anode. It is a
good practice to replace the anode when it is
approximately 50 percent used. The factory
warranty on a glass-lined tank may be void if a
satisfactory anode is not in place at the time of a
failure or if it is consumed by cathodic action.
5. The tank must be lined if a water softener is
installed in the system.
6. Make sure the tank connections in the heatertank circulating loop are the proper size (see
Section 2.6.5). If tappings are smaller than the
recommended pipe size, a larger pump may be
required. Consult the factory if in doubt.
7. Install a pipe in the tank drain tting that goes to
a oor sink, and install a drain valve. If a oor
sink is not available, install a hose bib.
8. Hot water tanks in an existing installation
are likely to have silt deposits on the bottom.
Therefore, it is important to extend the pump
suction pipe in the tank to a position near the top.
Pipe the return from the heater to the bottom of
the tank.
Incorrect installation can cause rapid failure
of water tanks due to electrolysis. Tanks must
be installed with dialectric connections to
electrically isolate the tank from stray current.
Note that use of brass or bronze connectors does
not replace the need for dialectric connections.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
MANUAL SHUT-OFF
VALV
E
GAS
SUPPLY
INLET
T-FITTING
3" (76 mm)
MIN.
UNION
NIPPLE
CAP
TO
BOILER
INLET
Page 15
2.6.10 Thermal Circulation of Hot Water
in Cold Water Supply Lines
Under certain circumstances, thermal circulation
will occur in the cold water pipe supplying the water
to the heating system. This happens in a multi-story
building when the cold water pipe rises from its
connection to the system. To correct the problem, a
check valve in the cold water line supplying the heater
will prevent thermal circulation, and a small expansion
tank will permit heated water to expand without
popping off the relief valve.
2.7 Gas Supply and Piping
2.7.1 General Instructions
Review the following instructions before
continuing the installation.
1. Gas piping installation must be in accordance
with the latest edition of ANSI Z223.1. In
Canada, the installation must be in accordance
with CAN1-B149.1 or .2 and all local codes that
apply.
2. Check the rating plate to make sure the heater
is tted for the type of gas being used. Bradford
White heaters are normally equipped to operate
below a 2000 foot (609 m) altitude. Heaters
equipped to operate at higher altitudes have
appropriate stickers or tags attached.
3. If a gas pressure regulator is required, the
installation must be in accordance with the latest
edition of ANSI Z223. In Canada, the installation
must be in accordance with CAN1-B149.1 or .2
and all local codes that apply.
4. The gures in Table 5 should be used to size the
gas piping from the gas meter to the heater.
5. Install a sediment trap (drip leg) ahead of the
gas controls (see Figure 24 ). Fit the trap with a
threaded cap which can be removed for cleaning.
6. Install a manual gas shutoff valve for service and
safety. Check the local codes.
7. Disconnect the heater and its individual shutoff
valve from the supply gas system during pressure
test of the system at pressures higher than 1/2 psi
(3.4 kPa).
8. Gas supply pressures to the heater are listed in
Table 6.
NOTE: The heater and all other gas appliances
sharing the heater gas supply line must be ring at
maximum capacity to properly measure the inlet
supply pressure. Low gas pressure could indicate
an under-sized gas meter and/or obstructed gas
supply line.
Distance from Gas Meter or Last Stage Regulator
0-100 feet 100-200 feet 200-300 feet
0-30 m 30-60 m 60-90 m
Boiler Nat. Nat. Nat.
Size in. mm in. mm in. mm
1. These numbers are for natural gas (0.65 Sp. Gr.) and
are based on inch (13mm) water column pressure
drop. Check supply pressure with a manometer, and
local code requirements for variations. For liqueed
petroleum gas, reduce pipe diameter one size, but
maintain a inch (13mm) minimum diameter.
2. Check supply pressure and local code requirements
before preceding with work.
3. Pipe ttings must be considered when determining gas
pipe sizing.
4. For propane gas: Reduce pipe diameter one size, but
maintain a inch (19mm) minimum diameter.
Table 5. Natural Gas and Propane,
Pipe Size Requirements.
Figure 24. T-Fitting and sediment trap.
Supply Pressure Natural Gas Propane Gas
Water Column in. mm in. mm
Minimum 6.5 165 11 279
See Rating Plate
Maximum 9 229 14 356
Table 6. Gas Supply Pressure Requirements.
9. Do not exceed the maximum inlet gas pressures
specied. Excessive pressure will result in
damage to the heater's gas controls. The
minimum pressures specied is for gas input
adjustment.
10. The correct burner manifold gas pressure is
stamped on the rating plate. The regulator on the
gas valve is preset at the factory, and does not
normally need adjustment.
Internet Version for Reference Only
Page 16
Copper Brute B4 Volume Water Heaters
Page 17
Mixing Valve
Out —
Mixed
Water
For Potable Use
Hot
Water
From
Water Heater
or Storage Tank
Cold
Water
Supply
BRADFORD WHITE
11. Before operating the heater, test the complete gas
supply system and all connections for leaks using
a soap solution.
Caution
Since some leak test solutions (including soap and
water) may cause corrosion or stress cracking, rinse
the piping with water after testing.
2.7.2 Special Precautions
for Propane Gas
Liqueed petroleum (LP) gas is heavier than
air. Therefore, do not install heaters using LP gas in
a pit or locations where gas might collect. Locate
heaters a safe distance from LP gas storage and lling
equipment. Consult local codes and re protection
authorities about specic installation restrictions.
2.8 Electrical Wiring
WARNING
Electrically ground the heater in accordance with
the latest edition of the National Electrical Code,
ANSI/NFPA 70. In Canada, use C22.1. Do not rely
on the gas or water piping to ground the metal
parts of the heater. Often, plastic pipe or dielectric
unions isolate the heater electrically. Service and
maintenance personnel who work on or around the
heater may be standing on wet oors and could be
electrocuted by an underground heater.
1. Check heater wiring and pump for correct
voltage, frequency, and phase. Check to make
sure heater is wired for 120 volts alternating
current (VAC). If 240 VAC, contact local factory
representative or Bradford White.
2. Wire the heater and pump exactly as shown in
the wiring diagram supplied with the heater.
See Figure 26 and 27 for a typical example of a
wiring diagram.
3. Electrically interlock the pump and heater so
the heater cannot come on unless the pump is
running.
4. Connect all eld-installed devices (draft
switches, relays, timers, outdoor temperature
reset devices, etc.) to the heater wiring at points
labeled Field Interlock (see Figures 26, 27, 28
and 29).
2.9 Combined Space Heating/Potable
Water Heating Systems
2.9.1 Combined Space Heating
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating. Do not use solder
containing lead in the potable water lines.
This water heater when used to supply potable
water shall not be connected to any heating system
or components(s) previously used with a non-potable
water heating appliance.
When the system requires water for heating
at temperatures higher than required for other
uses, an anti-scald mixing or tempering valve (see
Figure 25) shall be installed to temper the water
for those uses in order to reduce scald hazard
potential. Some jurisdictions may require a backow
preventer in the cold water line. In such cases, the
temperature and pressure relief valve may discharge
water due to expansion. A diaphragm type expansion
tank will normally eliminate this condition. Follow
the manufacturer's instructions for installation of the
expansion tank.
SECTION 3.
Operating Instructions
3.1 Normal Operating Sequence
NOTE: Safe lighting and other performance
criteria were met with the gas manifold and control
assembly installed on the heater during tests specied
in ANSI Z21.13.
Figure 25. Installation of tempering valve.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
IGNITION SYSTEM NO. 1 (SIZES 175-250)
W
3
W
6
2
1
R
O
P
4
5
Y
R
10
11
12
Y
TR
Y
TH
8
9
6
7
4
5
2
3
BR
BR
BR
R
R
R
115V
1
Y
R
24V
ON/OFF WITH EM2
R
4
6
5
3 2
G
1
W
BK
BK
BK
R
1
3
P
BK
BK
W
BL
1
3
2
BR
54
BRBK
BR
W
BK
BR
Y
T
A
B
O
FLOW
SWITCH
GAS VALV
E
ALTERNATE WIRING FOR INDOOR INSTALLATION ONLY
PLUG
VENT DAMPER
VENT DAMPER
JUMPER
VENT DAMPER
RECEPT
ACLE
FUSIBLE
LINK
FIELD INTERLOCK
(REMOVE JUMPER
WHEN USED)
2 AMP
FUSE
HI-LIMIT
CONTROL
TEMP
RESET
MANUAL
STRIP
TERMINAL
TRANSFORMER
VENT DAMPER
ACTUATOR
M
VENT DAMPER
AND DRAFTHOOD
SWITCH, M. RESET
PILOT BURNER WITH
THERMOCOUPLE
SWITCH
POWER
LOW WATER
CUT-OFF (OPTIONAL)
GROUNDING
CONDUCTOR
PUMP
HOT
NEUTRAL
POWER SUPPL
Y
115/60HZ
PUMP
RELA
Y
BK
G
BK - BLACK
W - WHITE
R - RED
Y - YELLOW
BL
- BLUE
BR
- BROWN
O - ORANGE
G - GREEN
P - PURPLE
FACTORY WIRING
24V
115V
FIELD WIRING
24V
115V
Page 17
IF ANY OF THE ORIGI NAL WIRE AS SUPPLIED
WITH T HE HEATER MUST BE REPLACED, IT
MUST BE REPLACED WITH APPLIAN CE WIRING
MATERIAL 10 5°C (220°F ) OR ITS EQUIVALENT.
WHITE WIRES TO FUSIBLE LINK MUST BE
REPLAC ED WITH WIRE HAVING INSULATIO N
RATED AT 200°C (390°F). (AVAILABL E FROM
FACTORY).
Figure 26. Typical example of wiring schematic, System 1, Sizes 175-250.
Internet Version for Reference Only
Page 18
Copper Brute B4 Volume Water Heaters
Page 19
115V
24V
TRANSFORMER
1
2
3
4
5
6
7
8
9
10
11
12
RR
FUSE
2 AMP
FIELD INTERLOCK
(REMOVE JUMPER
WHEN USED)
Y
FLOW
SWITCH
STRIP
TERMINAL
Y
BR
BR
1
23
6
4
5
W
W
O
P
Y
R
VENT DAMPER
JUMPER
HI-LIMIT
RESET
MANUAL
RECEPTACLE
VENT DAMPER
1
23
6
4
5
R
G
W
M
BK
ACTUATOR
VENT DAMPER
BK
BK
VENT DAMPER
PLUG
ALTERNATE WIRING FOR INDOOR INSTALLATION ONLY
VENT DAMPER
AND DRAFTHOOD
SWITCH, M. RESET
ON/OFF WITH EM2
IGNITION SYSTEM NO. 12 (SIZES 175-250)
BR
R
R
CONTROL
TEMP
LOW WATER
CUT-OFF (OPTIONAL)
BK
P 1
3BR24 5
Y
SENSOR
PILOT BURNER
WITH SPARK
ELECTRODE
SPARK
O
BR
Y
GAS VALVE
PV
MV/PV
MV
Y
O
LINK
FUSIBLE
WW
TR
TH-TR
GAS VALVE
ALTERNATE
TH
O
Y
BR
POWER
SWITCH
T
B
3
RELAY
PUMP
A
1
R
W
BK
BL
GROUNDING
BK
PUMP
BR
BR
CONDUCTOR
POWER SUPPLY
115/60HZ
W
BK
NEUTRAL
HOT
W
W
BK
IGNITION
CONTROL
1 M
V
2 MV/PV
3 P
V
4 GND
5 24V (GND)
6 24V
7 TH-W
8 M
V
9 S
PARK
BK
- BLACK
W - WHITE
R - RED
Y - YELLOW
BL
- BLUE
BR
- BROWN
O - ORANGE
G - GREEN
P - PURPLE
FACTORY WIRING
24V
115V
FIELD WIRING
24V
115V
BRADFORD WHITE
IF ANY OF THE ORIGI NAL WIRE AS SUPPLIED
WITH T HE HEATER MUST BE REPLACED, IT
MUST BE REPLACED WITH APPLIAN CE WIRING
MATERIAL 10 5°C (220°F ) OR ITS EQUIVALENT.
WHITE WIRES TO FUSIBLE LINK MUST BE
REPLAC ED WITH WIRE HAVING INSULATIO N
RATED AT 200°C (390°F). (AVAILABL E FROM
FACTORY).
Figure 27. Typical example of wiring schematic, System 12, Sizes 175-250.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
2 AMP
FUSE
TRANSFORMER
MANUAL
RESET
HI-LIMIT
LOW WATER
CUT-OFF (OPTIONAL)
POWER
SWITCH
HOT
115/60 HZ
POWER SUPPL
Y
PUMP
GROUNDING
CONDUCTOR
NEUTRAL
TEMP
CONTROL
TERMINAL
STRIP
PUMP
RELA
Y
FIELD INTERLOCK
(REMOVE JUMPER
WHEN USED)
FLOW
SWITCH
BK
- BLACK
W - WHITE
R - RED
Y - YELLOW
BL
- BLUE
BR
- BROWN
O - ORANGE
G - GREEN
P - PURPLE
FACTORY WIRING
24V
115V
FIELD WIRING
24V
115V
GAS VALVE
PILOT BURNER WITH
THERMOCOUPLE
1
2
3
4
5
6
7
8
9
10
11
12
R
R
R
R
R
R
Y
Y
Y
Y
BK
BK
BK
BK
BR
BR
BR
BR
BR
BR
BR
O
W
W
W
W
BL
BK
P
12
3
4
5
G
A
T
B
1
3
24V115V
TH
TR
IGNITION SYSTEM NO. 1 (SIZES 325-400)
ON/OFF WITH Em2
Page 19
Figure 28. Typical example of wiring schematic, System 1, Sizes 325-400
IF ANY OF THE ORIGI NAL WIRE AS SUPPLIED
WITH T HE HEATER MUST BE REPLACED, IT
MUST BE REPLACED WITH APPLIAN CE WIRING
MATERIAL 10 5°C (220°F ) OR ITS EQUIVALENT.
WHITE WIRES TO FUSIBLE LINK MUST BE
REPLAC ED WITH WIRE HAVING INSULATIO N
RATED AT 200°C (390°F). (AVAILABL E FROM
FACTORY).
Internet Version for Reference Only
Page 20
Copper Brute B4 Volume Water Heaters
Page 21
IGNITION SYSTEM NO. 12 (SIZES 325-400)
ON/OFF WITH EM2
2 AMP
FUSE
TRANSFORMER
LOW WATER
CUT-OFF (OPTIONAL)
POWER
SWITCH
HOT
PUMP
RELA
Y
TERMINAL
STRIP
MANUAL
RESET
HI-LIMIT
TEMP
CONTROL
200°F MAX
FIELD INTERLOCK
(REMOVE JUMPER
WHEN USED)
PILOT BURNER
WITH SP
ARK
ELECTRODE
SENSOR
GAS VALV
E
SPARK
FLOW
SWITCH
115V/60HZ
POWER SUPPL
Y
PUMP
NEUTRAL
GROUNDING
CONDUCTOR
1
2
3
4
5
6
7
8
9
10
11
12
BK - BLACK
W -
WHITE
R -
RED
Y -
YELLOW
BL - BLUE
BR - BROWN
O -
ORANGE
G -
GREEN
P -
PURPLE
FACTORY WIRING
24V
115V
FIELD WIRING
24V
115V
R
R
24V
115V
BK
BR
W
Y
Y
W
R
R
R
BR
O
Y
BK
BL
W
R
R
BR
BR
BR
Y
O
BR
BR
BK
W
BK
BK
W
G
Y
BR
O
Y
Y
P
12
3
4
5
A
T
B
1
3
IGNITION
CONTROL
1 M
V
2 MV/PV
3 P
V
4 GND
5 24V (GND)
6 24V
7 TH-W
8 M
V
9 S
PARK
TH-TR
TR
TH
BRADFORD WHITE
IF ANY OF THE ORIGI NAL WIRE AS SUPPLIED
WITH T HE HEATER MUST BE REPLACED, IT
MUST BE REPLACED WITH APPLIAN CE WIRING
MATERIAL 10 5°C (220°F ) OR ITS EQUIVALENT.
WHITE WIRES TO FUSIBLE LINK MUST BE
REPLAC ED WITH WIRE HAVING INSULATIO N
RATED AT 200°C (390°F). (AVAILABL E FROM
FACTORY).
Figure 29. Typical example of wiring schematic, System 12, Sizes 325-400.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Manual Reset Temp. Control
Temperature Controller
WARNINGS
Vent pipes, drafthoods, and heater tops get
hot! These surfaces can cause serious burns.
Do not touch these surfaces while the heater
is in operation. Adding a vent cap reduces the
temperature on the top.
For your safety, when starting the heater, keep your
head and face well away from the lower rebox
opening to prevent any risk of personal injury.
LP GAS: To avoid possible injury, re and
explosion, read and follow these precautions and
all instructions on this heater before lighting. This
heater uses LP gas which is heavier than air and
will remain at ground level if there is a leak. Before
lighting, sniff at ground level.
If you smell gas, follow these rules:
1. DO NOT light matches. DO NOT turn electric
lights or switches on or off in area. DO NOT use
an electric fan to remove the gas from area.
2. Shut off gas at LP tank.
3. Telephone gas company and re department
for instructions. Give your name, address and
phone number.
If your LP tank runs out of fuel, turn off gas at the
heater. After the tank is relled, the heater must be
relit in accordance with the instructions found on the
inside of the heater. DO NOT attempt repairs on the
gas control or heater. Tampering is dangerous and
voids all warranties.
Page 21
7. Turn manual gas valve on.
8. Reset all safety devices (some units have manual
resets on hi-limit switch, low water cutoff, etc.).
9. Set temperature control to desired setting.
10. Replace control access panel.
11. Turn electric power to the heater on.
12. If the heater will not operate:
a. Turn gas to heater off following the
instructions found on the inside of the heater
and call a qualied service technician or gas
supplier.
b. Turn main electrical switch off.
c. Close all manual gas valves.
3.3 Setting the Temperature Controls
The hi-limit switch is factory set, and should not
be adjusted above the factory setting.
WARNING
Adjusting the temperature control past the
recommended setting can result in a scalding
injury. Hot water can produce third degree burns
in 6 seconds at 140°F (60°C) and in 30 seconds at
130°F (54°C).
3.2 Start-Up Procedure
Lighting instructions can be found on the inside
of the heater. To start up the heater:
1. Make sure the system pump is running and there
is water ow.
2. Remove the control access panel.
3. Set the temperature control (see Figure 30) to its
4. Turn electric power to the appliance to off.
5. Turn manual gas valve off.
6. Wait 5 minutes to clear out any gas, then smell
lowest setting.
for gas, including near the oor. Be sure to smell
next to the oor because some types of gas are
heavier than air and will settle on the oor.
Caution
This heater is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
Figure 30. Temperature controls.
3.3.1. Remote Water Heater Temperature
Control:
The water heater can be used with a eldsupplied tank aquastat, sequencing control, or other
temperature control device, which will call the unit for
heat when the temperature goes below the controller’s
setpoint. For the most efcient setting, set the tank
temperature at the lowest possible setting for adequate
hot water in the application.
Internet Version for Reference Only
Page 22
Copper Brute B4 Volume Water Heaters
Page 23
BRADFORD WHITE
After a setting has been chosen for the tank
temperature control, set the heater temperature control
10°F (6°C) higher. The heater’s temperature control
senses the inlet water temperature to the heater. The
heater’s manual reset high limit (and automatic
reset high limit, if applicable) senses heater outlet
temperature.
If the unit is equipped with an automatic reset
high limit, set the automatic reset high limit 20°F
(11°C) above the outlet temperature to avoid nuisance
lockouts. Set the manual reset high limit 5°F (3°C)
above the automatic reset high limit.
For units that only have a manual reset high limit
(no automatic reset high limit), set the manual reset
high limit 20°F (11°C) above the outlet temperature to
avoid nuisance lockouts.
Example, Imperial units: If the tank temperature
is set to 140°F, set the heater’s temperature control to
150°F (140°F + 10°F). Further, if the temperature rise
through the heater is 25°F, the outlet temperature will
be 175°F (150°F + 25°F). Therefore, set the automatic
reset high limit to 195°F (170°F + 20°F), and the
manual reset high limit to 200°F (195°F + 5°F).
Example, Metric units: If the tank temperature
is set to 60°C, set the heater’s temperature control to
66°C (60°C + 6°C). Further, if the temperature rise
through the heater is 15°C, the outlet temperature will
be 81°C (66°C + 15°C). Therefore, set the automatic
reset high limit to 92°C (81°C + 11°C), and the
manual reset high limit to 95°C (92°C + 3°C).
Example, Metric units: If the heater’s
temperature control is set to 55°C, and the
temperature rise through the heater is 14°C, the outlet
temperature will be 69°C (55°C + 14°C). Set the
automatic reset high limit to 80°C (69°C + 11°C) and
set the manual reset high limit to 83°C (80°C + 3°C).
3.4 Adjustment for Minimum Input Rate
(models with modulating gas valve)
Adjust the red knob on the modulating gas valve
to the dial number for the desired water temperature
(see Table 7). Adjusting the red knob to number
"1" sets the gas ow rate to minimum. The control
is factory set at "2" which is satisfactory for most
installations.
When an external control is not used, the
circulator between the heater and the storage tank
must run continuously, so that the heater’s temperature
control can detect and control the water temperature
in the storage tank. The water heater’s temperature
control is adjusted to its lowest temperature position
(130°F, 54°C) when shipped from the factory. This is
the preferred starting point for setting the temperature
control.
If the unit is equipped with an automatic reset
high limit, set the automatic reset high limit 20°F
(11°C) above the outlet temperature to avoid nuisance
lockouts. Set the manual reset high limit 5°F (3°C)
above the automatic reset high limit.
For units that only have a manual reset high limit
(no automatic reset high limit), set the manual reset
high limit 20°F (11°C) above the outlet temperature to
avoid nuisance lockouts.
Example, Imperial units: If the heater’s
temperature control is set to 130°F, and the
temperature rise through the heater is 25°F, the outlet
temperature will be 155°F (130°F + 25°F). Set the
automatic reset high limit to 175°F (155°F + 20°F) and
set the manual reset high limit to 180°F (175°F + 5°F).
3.5 Hi-Limit Switch Checkout
After running the heater for a long enough
period, bring the water temperature within the range of
the hi-limit switch and slowly back off the high limit
setting until the heater shuts off. The main burners
should reignite when the hi-limit switch is reset and
turned back up to its original setting. The heater should
now run until it shuts off automatically on operating
control.
Should overheating occur or the gas supply fail
to shut off, turn off the manual gas control valve to the
heater.
3.6 Shut-Down Procedure
Shut down the heater following the instructions
found on the inside of the heater.
Where there is a danger of freezing, shut off the
water supply and remove the drain plugs on both sides
of the heater jacket. Drain every part of the system
subject to damage from freezing temperatures.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 23
SECTION 4.
Maintenance
4.1 General Instructions
1. Oil the water circulating pump in accordance
with the manufacturer's instructions.
2. If a strainer is used in a pressure reducing valve
or in the piping, clean it every 6 months in
accordance with the manufacturer's instructions.
3. At startup and every 6 months after, look at
the pilot and main burner ame (see Figure
31). If the ame has the appearance of sooting
tips, check for debris near orices. Call service
technician.
4. Inspect the venting system for blockage, leakage,
and corrosion at least once a year.
5. Keep the heater area clear of combustible
material, gasoline, and other ammable liquids
and vapors.
6. Be sure all combustion air and ventilation
openings are not blocked.
7. Check for black carbon soot buildup on the
external surfaces of the heat exchanger every 6
months.
8. Do not use the heater if any part has been under
water. Replace any part of the control system and
any gas control which has been under water.
NOTE: After installation and rst startup, check
the heat exchanger for black carbon soot buildup after
the following periods of operation: 24 hours, 7 days,
30 days, 90 days, and once every 6 months thereafter.
4.2 Replacement of Gas Controls
The gas and electric controls installed on the
heaters are designed for both dependable operation and
long life. Safe operation of the heater depends on their
proper functioning.
NOTE: The warranty does not cover damage
caused by lack of required maintenance or improper
operating practices.
WARNING
Never attempt to repair the gas valve. Such
attempts will void the warranty, and could lead to
dangerous results.
If the gas valve is found to be defective, replace
it by following these instructions.
1. Turn off electrical power to the heater.
2. Turn off the main gas supply at the manual gas
cock outside the heater jacket or at the meter.
Electronic PilotStanding Pilot
Figure 31. Flame patterns.
3. Remove the front access door on the heater.
4. Disconnect the service union in the gas line, and
unscrew the main gas pipe from the gas valve
(see Figure 32).
5. Remove the two screws that fastens the antirotation bracket on the left side of the gas valve
(see Figure 32), and the three screws attached to
heater.
6. Remove the pilot gas tube and copper
thermocouple shield, if present, from the gas
valve.
Caution
Label all wires prior to disconnection. Wiring errors
can cause improper and dangerous operation.
7. Tag and remove all wires from the gas valve
terminals.
8. Pull the burner tray out of the heater (see
Figure 32).
9. Screw the new gas valve onto the manifold pipe.
Make sure the arrow on the bottom of the gas
valve that indicates the direction of gas ow is
in the proper direction. Also make sure the brass
tting is on the right side.
10. Connect the pilot gas tube to the pilot assembly
and thermocouple to the gas valve.
Internet Version for Reference Only
Page 24
Copper Brute B4 Volume Water Heaters
Page 25
Gas Line
Gas Line
NOTE:
Gas line is connected
to pilot igniter
, not pilot burner.
Anti-Rotation
Bracket
BRADFORD WHITE
Figure 32. Gas valve/burner replacement.
NOTE: Due to sharp edges on the metal burners, wear
protective gloves for the next steps.
11. Hold the gas burner or pilot burner rmly, and
push it away from the manifold until it is clear of
the orice. Slide the burner to be replaced out of
the burner tray (see Figure 33).
12. To replace the gas burner, insert the burner into
the slot at the rear of the burner tray, line it up
with the proper orice and snap it into position.
13. To replace the pilot burner, install the pilot
assembly on the new pilot burner and install it in
the burner tray.
14. Slide the burner tray back into the heater and
fasten it with two screws.
15. Install the anti-rotation bracket to the inner panel
and fasten with two screws (see Figure 32), and
the three screws to heater.
16. Connect the service union in the gas line, and
screw the main gas pipe to the gas valve (see
Figure 32).
17. Turn on gas valve following the lighting
instructions found on the inside of the heater.
18. Turn on the main gas supply at the manual gas
cock or the meter.
19. Check the system for leaks using a soap solution.
Figure 33. Burner removal.
Caution
Since some leak test solutions (including soap and
water) may cause corrosion or stress cracking, rinse
the piping with water after testing.
20. Reconnect the electrical wires to the gas valve in
accordance with the wiring diagram found on the
inside of the heater.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 25
21. Install the front access door on the heater.
22. Turn all electrical power to the heater on.
4.3 HEAT EXCHANGER
4.3.1 Inspecting the Heat Exchanger
To check the scale buildup, periodically inspect
the tube having the highest temperature as follows:
1. Open the drain valve on the left side of the
heater.
2. Remove the hex-head plug located on the right
side of the heater under the in/out header (see
Figure 34). Perform this inspection after 60 days
of and after 120 days of operation. This will
establish a regular inspection routine.
4.3.2 Cleaning the Heat Exchanger
An inspection and cleaning of the complete heat
exchanger can only be done by removing it from the
heater.
1. To remove the heat exchanger, refer to Section
2.6.1.
Caution
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or ame. To
prevent this happening, dampen the soot deposits
with a wet brush or ne water spray before servicing
the heat exchanger.
2. Remove the heat bafes and check for a light
accumulation of soot or corrosion on the outside
of the heat exchanger tubes.
NOTE: While the heat exchanger is out of the
heater, inspect the rewall refractory insulation blocks
for cracks, wear, and breakage. Replace if necessary.
3. Use a wire brush to remove soot and loose scale
from the heat exchanger. Do not use water or
compressed air for cleaning.
Plug
Figure 34. Scale inspection.
City
Water
Supply
NOTE: Use only the correct carbide tipped
reamers which are available from Bradford White.
4. Ream the insides of the tubes (see Figure 35).
5. Pull the reamer out frequently to remove lime
powder and prevent the drill from binding in the
tube.
6. Install new gaskets. Do not reuse the old ones.
7. Tighten the header bolts progressively, starting
with the two center bolts. Maximum torque is 20
inch pounds (27 Nm). Do not over-torque.
400-500 RPM
Drill Motor
Notes:
1. When pressure relief valve is used, it must be removed and the hole plugged, as shown.
2. Remove the plug before reinstalling the heat exchanger.
Figure 35. Heat exchanger tube cleaning.
Internet Version for Reference Only
Page 26
Copper Brute B4 Volume Water Heaters
Page 27
Suggested
Manometer
Position
Main
Line
Manifold
Regulated
Test Plugs
Test Plug
Main Line
BRADFORD WHITE
8. Pressure test the heat exchanger for leaks with
city water supply before re-installing (see
Figure 35).
9. When placing the heat exchanger back in the
heater, carefully hold the refractory insulation
blocks apart and lower the heat exchanger into
place. Be sure the sheet metal covers, which
protect the insulation blocks, are replaced
carefully.
10. If a header bolt is stripped, drive it out of the
header plate and replace it.
11. To reinstall the heat exchanger, refer to Section
2.6.1.
SECTION 5.
Troubleshooting and Service
5.1 Gas Pressure Tests
Use the following procedures to check the
main gas and manifold regulated gas pressures. A
manometer or a dry gas pressure gauge may also be
used for either test.
5.1.1 Checking the Main Line
Gas Pressure
1. Attach a manometer (or a dry gas pressure gauge)
to heater jacket (see Figure 36).
2. Open both columns on the manometer.
3. Use shutoff valve outside the heater jacket to shut
off all gas supply to the heater.
4. Remove the 1/8 inch Allen Plug on the inlet side
of the gas valve and replace it with the 1/8 inch
(3.2 mm) NPT tting from the manometer kit.
5. Attach one end of the manometer hose to the
tting on the gas valve and the other end to the
manometer.
6. Open gas supply valve to the heater to test.
7. With the main burners ring, the manometer
reading should be between 6.5 and 9 inches W.C.
for natural gas, and between 11 and 14 inches
W.C. for propane units (see Table 6).
5.1.2 Checking the Manifold
Regulated Gas Pressure
1. Attach a manometer (or a dry gas pressure gauge)
to heater jacket (see Figure 36).
2. Open both columns on the manometer.
3. Use shutoff valve, on outside of heater jacket, to
shut off all gas supply to the heater.
4. Remove the 1/8 inch (3.2 mm) NPT test plug
on the outlet side of the manifold, and replace it
with the 1/8 inch (3.2 mm) NPT tting from the
manometer kit, (see Figure 36).
5. Attach one end of the manometer hose to the
tting on the manifold and the other end to the
manometer.
6. Turn on gas supply to the heater, and set the
temperature control high enough to call for heat.
7. Turn toggle switch to ON. This should activate
the main burners.
8. The manometer reading should be 4 inches
(102mm) W.C. for natural gas and 9 inches
(229mm) W.C. for propane gas.
9. Turn the toggle switch to OFF.
10. Shut the system down following the instructions
found on the inside of the heater.
11. Disconnect the manometer tubing from the
manifold and replace the 1/8 inch (3.2 mm) NPT
tting with the original plug.
Figure 36. Gas pressure test.
5.2 Electrical Troubleshooting
This section describes procedures for checking
the electrical power and control components of the
heater. Read all of these procedures before starting
repairs.
Problems with heaters not ring are usually
caused by something reducing water ow through the
heater, causing the protective switches in the heater
system to shut down the heater.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 27
The following tools are required for proper
service and problem diagnosis of the heater and
heating system.
1. Gas pressure test kit with range from 0 to 14
inches (0 to 356 mm) W.C.
2. Electric meter(s) with the following ranges:
a. 0 to 500 volts VAC
b. 0 to 2000 ohms ()
c. 0 to 20 microamps (mA)
d. 0 to 50 millivolts (mV)
3. A pressure gauge and a thermometer with proper
ranges for heater operation.
5.2.1 Heater Does Not Come On
Important: Disconnect power to the heater
or pull the RED wire off the transformer secondary
before removing or replacing any component or wire
connection.
WARNING
If power is not disconnected, jumpering gas valve
or accidental grounding of the wire harness, or
component terminals to the heater frame or jacket
could cause the ignition control fuse to blow or
may cause the heater to re, resulting in injury or
property damage.
If the pump is circulating water, and the rest of
these items check out all right, the trouble could be in
the heater control system.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
5.2.2 Testing the Transformer
NOTE: Keep the pump running.
Testing the transformer requires an AC voltmeter
with a 50 volt (V) range. Test the transformer using the
following procedures:
1. Clip a lead from the voltmeter to the yellow wire
terminal on the transformer.
2. Touch the other lead to the red wire terminal
(see Figure 37). The voltmeter should read 24 to
28VAC.
3. If the voltmeter does not show voltage, check the
electrical power supply.
4. If the voltage is less than 20VAC, the electrical
circuit to the heater may be supplying less than
103VAC. This could be due to high pump load or
air conditioners or other appliances on the circuit.
1. Make sure the heater has been properly installed.
2. Make sure the pump is not airlocked, clogged or
otherwise inoperative.
3. Make sure the gas valve is on and there is gas
pressure in the line.
4. Check all electrical connections and wiring.
Finding a loose connection or a charred wire can
save a lot of time and money.
5. Check the fuse inside the black, twist-lock fuse
holder. If it is burned, replace it with a 2-amp
fuse (Part No. E0084400). If there is a short, the
cause of the short must be found and repaired.
Do not jumper or bypass the fuse.
6. Make sure the electrical circuit to the heater is
on.
7. Make sure the toggle switch on the right side of
the heater is on.
8. Make sure the temperature control is set high
enough to call for heat.
9. Make sure the manual reset on the safety controls
(e.g., low water cutoff, hi-limit switch, etc.) has
not tripped. If it has, reset it.
Figure 37. Testing the transformer.
Internet Version for Reference Only
Page 28
Copper Brute B4 Volume Water Heaters
Page 29
BRADFORD WHITE
5.2.5 Testing the Flow Switch
The ow switch is a safety device that senses
water ow through the heater. When the switch senses
adequate water ow, it closes, allowing the heater to
re. If the water ow is too low, the switch remains
open and prevents the heater from ring regardless of
the temperature control setting.
The ow switch is factory mounted and wired.
Never attempt to repair the ow switch. If the ow
switch is found to be defective, replace the ow
switch. To test the ow switch:
1. Remove cap from ow switch.
2. Touch a voltmeter lead to each terminal of the
ow switch.
3. If the voltmeter reads voltage at each of the
terminals, the switch is good.
4. If there is no voltage at one terminal, it indicates
an open switch. Check ow switch paddles to
determine if they are broken, missing or frozen.
Replace the ow switch.
Figure 38. Testing the manual reset hi-limit switch.
5.2.3 Testing the Electrical Power Supply
The electrical components operate with supply
voltage ranging from 103 to 126VAC at 60 Hertz (Hz).
To test the electrical power supply:
1. Measure the voltage at the hot and neutral
connections inside the heater electrical junction
box.
2. Voltage outside of the required range may be due
to poor wiring connections, to other loads (e.g.,
air conditioners, compressors) on the circuit,
to high pump load, or to an electrical utility
company problem.
5.2.4 Testing the Manual Reset
Hi-Limit Switch
To test the manual reset hi-limit switch (see
Figure 38):
1. Touch the other lead of the voltmeter to both
terminals of the manual reset hi-limit switch.
The voltmeter should read 24 to 28VAC at both
terminals.
2. If no voltage is detected at one terminal, reset the
manual reset hi-limit switch by pressing the reset
button. Check the temperature setting.
3. If after pressing the reset button there is still no
voltage indicated at one terminal, replace the
manual reset hi-limit switch. An open switch
may indicate excessive water temperatures or
improper setting.
5.2.6 Testing the Fusible Link
(ame roll-out switch)
The fusible link is a thermally fusible element
which shuts down the heater if it detects excessive
temperatures inside the heater ue collector
compartment. To test the fusible link (ame roll-out
switch, if installed):
1. Touch the voltmeter lead to the lower terminal on
the terminal block (see Figure 39).
Yellow
Red
Figure 39. Testing the fusible link.
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
2. If the voltmeter reads voltage, the safety fuse and
the fusible link are good.
3. Replace the fusible link when an open circuit is
detected. An open fuse line indicates overheating
in the ue collector or compartment.
4. Check for leaks of the ue collector, vent pipe,
gaskets, and all connections.
5. Check the ue pipe for blockage.
6. Check heat exchanger ns for partial sooting.
5.2.7 Testing the Fuse
To test the fuse:
1. Clip a lead of the voltmeter to the grounding
terminal.
2. Touch the other voltmeter lead to the 24VAC
terminal on the ignition control.
3. If there is no voltage, replace the fuse. A blown
fuse is usually an indication of a short in the
24VAC circuit. It is important that the cause of
the short be found and repaired. Do not jumper or
bypass the fuse.
5.2.8 Testing the Ignition Control
(for spark ignition)
Caution
The ignition control and igniter operate on 120V
power. Keep this in mind while servicing the heater,
and take care to avoid electrical shock.
The ignition control provides power to the pilot,
opens the gas valve when there is a call for heat, and
senses when a ame is established. To test the ignition
control for spark ignition:
1. Clip one lead from the voltmeter to the yellow
wire terminal on the transformer.
2. Touch the other voltmeter lead to the red 24V
terminal on the ignition control.
3. If the voltmeter reads voltage, the temperature
control and the manual reset hi-limit switch are
not keeping the heater from ring.
4. Make sure the pilot burner is positioned next to
the main burner (see Figure 40) and there is no
soot or dirt on it.
5. Make sure the electrode (part of pilot assembly)
is clean, the terminal connection is tight, and the
ceramic insulator lead is at least 3/8 inch (9.5
mm) from the heater chassis and other metal
parts.
6. Check for proper spark gap.
Page 29
Figure 40. Pilot location (spark ignition).
5.2.9 Testing the High Voltage
Ignition Lead
Connections must be tight, and silicone rubber
boots in place. Bare metal parts at the base of the
manifold bracket must be at least 3/8 inch (9.5 mm)
from other metal objects. To test the ignition lead:
1. Turn the control panel switch to on.
2. Make sure the temperature control is turned far
enough to call for heat. There will be a loud
clicking noise indicating the pilot electrode is
sparking.
3. If no sparking is heard, pull the ignition lead
from the ignition control and hold the bare
terminal 1/8 to 3/16 inch (3.2 to 4.8 mm) from
the ignition stud with a pair of insulated pliers
(see Figure 41).
4. If a spark does not jump the gap, replace the
ignition control.
NOTE: The ignition control cannot be repaired
in the eld. If it does not operate properly, replace it.
Figure 41. High voltage ignition test.
Internet Version for Reference Only
Page 30
Copper Brute B4 Volume Water Heaters
Page 31
BRADFORD WHITE
5.2.10 Testing the Safety Shutoff
(for standing pilot)
After lighting the heater, test the ignition system
safety shutoff.
1. With the main burners ring, turn the gas valve
control knob off.
2. Turn power to the heater off.
3. Set the temperature control to its lowest setting.
4. Wait 5 minutes.
Caution
Flame Hazard. Failure to wait 5 minutes, or not
turning the gas valve knob to OFF, may cause the
ow of unlighted main burner gas.
5. Turn the gas valve control knob to the PILOT
position.
6. Without pressing the control knob down, it
should be impossible to light the pilot.
7. Relight the pilot following the lighting
instructions found on the inside of the heater.
8. Reset the temperature control.
9. Light the heater following the instructions found
on the inside of the heater.
5.2.11 Testing the Safety Shutoff
(for automatic pilot)
1. Find the red silicone rubber insulated wire that
runs from the pilot to the ignition stud on the
ignition control module.
2. With the main burners ring, use an insulated
pair of pliers to disconnect the sensor wire from
the control module. Do not pull on the wire. The
main burner ame should immediately go out.
3. Turn the gas valve control knob to the off
position.
4. Reattach the red silicone wire to the control
module.
5.2.12 Testing the Igniter Electrode
To test the igniter electrode:
1. Make sure all of the wire connections on the
ignition control and the gas valve are tight.
2. Make sure the wiring agrees with the wiring
diagrams found on the inside of the heater.
3. Check for sparking at the igniter electrode.
4. If there is sparking at the igniter electrode, but
there is no pilot ignition after 10-20 seconds, clip
a lead from the voltmeter between the yellow
wire terminal on the transformer and the orange
wire terminal on the gas valve.
5. If the voltmeter does not show voltage, replace
the ignition control.
6. If the voltmeter reads 24 to 28VAC, but there is
no pilot ignition, check for
a: air in gas lines.
b: restrictions in gas line, valve or pilot tubing.
c: clogged pilot orice.
If these are correct then replace gas valve (see
Section 4.2).
WARNING
Never attempt to repair the gas valve. Such
attempts will void the warranty, and could lead to
dangerous results.
5.2.13 Testing the Pilot Thermocouple
(for standing pilot)
If there is voltage to the gas valve, the pilot
is lit, the thermocouple is properly positioned, the
temperature control is set high enough to call for heat;
then the gas valve or the pilot thermocouple may be
the problem. To test the pilot thermocouple:
1. Remove the pilot thermocouple tting from the
gas valve.
2. Clip one lead of a millivolt meter on the center
post of the tube and the other lead on the copper
pilot thermocouple shield. Turn the gas valve
control knob to the “Pilot” position, depress it,
and light the pilot. You will have to keep the gas
valve control knob depressed throughout this test.
3. If the millivolt meter reads about 30 millivolts,
go to step 5.
4. If the millivolt meter does not show voltage
or voltage is very low, it could indicate a dirty
or clogged pilot. Clean and recheck the pilot
thermocouple. If voltage still does not show or is
very low, replace the pilot thermocouple.
5. To test the pilot thermocouple under load, screw
the pilot thermocouple into the end of a millivolt
reading adapter (see Figure 42).
6. Clip one lead of a millivolt meter to either side
of the millivolt adapter and clip the other lead to
ground.
7. Light the pilot following the instructions found
on the inside of the heater.
8. Set the temperature control high enough to call
for heat.
9. With the heater ring, take a millivolt reading.
10. If the millivolt meter does not read about 10
millivolts, replace the pilot thermocouple.
5.2.14 Testing for Pilot Burner
(for spark ignition)
When the pilot burner lights, the sparking should
stop and the main burners should re. If the sparking
continues and the main burners do not re:
Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Page 31
Thermocouple
Figure 42. Testing the pilot thermocouple.
Thermocouple
Adapter
Gas Valve
Pilot
Millivolt
Meter
1. Check all wire connections, ignition cable, and
using a mirror, make sure there is a pilot ame.
2. If everything appears all right, measure ame
sensing current by connecting a direct current
(DC) microamp meter between terminal No.
12 and the GND (BURNER) terminal on the
ignition control (see Figure 43).
NOTE: Separate the microamp meter leads from
each other and clear the heater chassis for most of their
length to properly perform this test.
3. When the pilot lights, the microamp meter should
read 1.5 microamps or more with or without the
main burners ring. A smaller current could be
caused by poor pilot ame, the position of the
pilot electrode, or bad cable and connectors.
4. If the pilot ame and sensor electrode are all
right, but there is no main burner ignition, clip
one lead from a volt meter between the yellow
wire terminal on the transformer and the brown
wire terminal on the gas valve.
5. If the voltmeter reads between 20 to 28VAC,
but the main burners do not re, replace the gas
valve (see Section 4.2).
5.2.15 Testing for Burner Ignition
(for standing pilot)
If the pilot ame and pilot thermocouple
generator are all right, but there is no main burner
ignition:
1. Clip one lead of a volt meter between the yellow
wire on the transformer and the brown wire
terminal on the gas valve.
2. If the volt meter reads between 20 to 28VAC,
but the main burners do not re, replace the gas
valve (see Section 4.2).
Figure 43. Flame sensing current.
5.2.16 Heater Will Not Shut Off
1. If the heater stays on with the brown wire on the
gas valve disconnected, replace the gas valve
(see Section 4.2).
WARNING
Never attempt to repair the gas valve. Such
attempts will void the warranty, and could lead to
dangerous results.
2. Check electrical components for loose wires.
Disconnect one of the lead wires on the gas
valve. If the heater goes off, the wiring could be
at fault. Repair or replace as necessary.
5.2.17 On-Off Main Burner Cycling
The main burners cycling on and off can be
caused by:
1. Poor wind conditions on an outdoor installation.
2. Pilot components out of position.
3. Low gas pressure causing an improper pilot
ame.
The pilot ame may appear to be all right until
the main burners come on, then the pilot ame shrinks.
An undersized gas supply line may cause this.
5.2.18 Testing the Terminal Strip/
External Controls
The terminal strip has been included so the
heater can be operated by various external controls not
provided by Bradford White. Determine whether or
not an external control is open by checking for voltage
at each terminal. If there is voltage at one terminal
and not the other, examine the external control. It may
require service or replacement.
Internet Version for Reference Only
C O R P O R A T I O N
BW
RADFORDHITE
®
®
Ambler, PA 19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020
Warranty Service (800) 531-2111