Bosch Worcester GR8700iW 30 S NG, Worcester GR8700iW 35 S LPG, Worcester GR8700iW 35 SB NG, Worcester GR8700iW 30 S LPG, Worcester GR8700iW 30 SB LPG Installation And Maintenance Instructions Manual

...
Installation and Maintenance Instructions
Gas fired condensing system boiler
Greenstar 8000 Style
GR8700iW 30 S | GR8700iW 35 S | GR8700iW 30 SB | GR8700iW 35 SB
6720883855 (2019/01) UK/IE
Table of contents
1 Explanation of symbols and safety instructions . . . . . . . . . . . 3
1.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . 4
2 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 About the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Misuse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Appliance type overview . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.7 Pipe work positions and flue outlet. . . . . . . . . . . . . . . . . 8
3.8 Designation of components. . . . . . . . . . . . . . . . . . . . . . . 9
3.9 Product data for energy consumption. . . . . . . . . . . . . . 10
3.10 Standard accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Pre-Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.1 System preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.1.1 Artificially softened water . . . . . . . . . . . . . . . . . . . . . . . 11
4.1.2 Water systems and pipe work . . . . . . . . . . . . . . . . . . . .11
4.1.3 System layouts examples. . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.4 System fill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 Mains supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4.2.1 Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2.2 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4.3 Appliance location and clearances . . . . . . . . . . . . . . . . 14
4.3.1 Appliance location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.2 Rooms containing a bath or shower . . . . . . . . . . . . . . . 15
4.3.3 Appliance clearances. . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.4 Flue systems considerations . . . . . . . . . . . . . . . . . . . . . 16
4.4.1 Flue length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.4.2 Flue options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.4.3 Plume management system. . . . . . . . . . . . . . . . . . . . . . 19
4.4.4 Flue terminal positions . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4.5 Plume re-direct and plume management terminal
positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.5 Condensate discharge . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.5.1 Appliance siphonic condensate trap. . . . . . . . . . . . . . . 24
4.5.2 Condensate pipe work. . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.5.3 Internal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.5.4 External connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.6 Pressure relief discharge. . . . . . . . . . . . . . . . . . . . . . . . 27
4.6.1 Pressure relief pipe work. . . . . . . . . . . . . . . . . . . . . . . . 27
4.6.2 Alternative PRV connections - Combined PRV/
condensate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.7 Cleaning primary systems . . . . . . . . . . . . . . . . . . . . . . . 28
4.7.1 Flushing the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1 Position the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.1.1 Mounting frame fixing . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2 Appliance connections . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3 Hanging the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4 Flue turret/adaptor installation . . . . . . . . . . . . . . . . . . . 35
5.5 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.5.1 Installer connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.5.2 Cable preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5.3 External controls - domestic installations. . . . . . . . . . . 38
6 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.1 Pre-Commissioning checks . . . . . . . . . . . . . . . . . . . . . . 39
6.2 Water treatment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.2.1 Filling the appliance and adding Inhibitor. . . . . . . . . . . 39
6.2.2 Adjusting the operating pressure of the heating
system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3 Starting the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3.1 Control panel overview . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3.2 Turn on the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3.3 Siphon filling mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.4 Chimney sweep mode . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.5 Parameters when optional integral diverter valve
kit is fitted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.6 Checking gas inlet pressure. . . . . . . . . . . . . . . . . . . . . . 42
6.6.1 Checking the gas supply pressure. . . . . . . . . . . . . . . . . 42
6.7 Checking the gas rate. . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.8 Checking for gas leaks during operation. . . . . . . . . . . . 43
6.9 CO and combustion check. . . . . . . . . . . . . . . . . . . . . . . 43
6.10 Checking flue integrity. . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.11 Flue gas analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.12 Finishing commissioning . . . . . . . . . . . . . . . . . . . . . . . . 45
6.12.1 Fitting the combustion casing . . . . . . . . . . . . . . . . . . . . 45
6.12.2 Fitting the appliance casing. . . . . . . . . . . . . . . . . . . . . . 46
6.12.3 Appliance/product guarantee . . . . . . . . . . . . . . . . . . . . 47
7 Settings in the service menu . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.1 Operating the service menu . . . . . . . . . . . . . . . . . . . . . 47
7.2 Service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.2.1 Overview of the service menu . . . . . . . . . . . . . . . . . . . . 48
7.2.2 Benchmark and Info menu. . . . . . . . . . . . . . . . . . . . . . . 50
7.2.3 Settings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.2.4 Function check menu. . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.2.5 Reset menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.3 Thermal disinfection . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8 Inspection and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.1 Inspection and maintenance considerations . . . . . . . . 55
8.2 Resources for inspection and maintenance . . . . . . . . . 55
8.3 Inspection and maintenance steps . . . . . . . . . . . . . . . . 55
8.4 Component access . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.5 Fan pressure test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.6 Check working gas inlet pressure . . . . . . . . . . . . . . . . . 57
8.7 Flue gas analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.8 Checking the flue integrity. . . . . . . . . . . . . . . . . . . . . . . 57
8.9 Cleaning the siphon and heat exchanger . . . . . . . . . . . 57
8.9.1 Checking the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.9.2 Checking the non-return valve in the air-gas
manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.9.3 Fan removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.9.4 Cleaning the heat exchanger . . . . . . . . . . . . . . . . . . . . . 59
8.9.5 Checking electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.9.6 Cleaning the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.10 Setting the air/gas ratio . . . . . . . . . . . . . . . . . . . . . . . . . 62
2
Greenstar 8000 Style – 6720883855 (2019/01)
Table of contents
8.10.1 Checking and, if required, adjusting the gas/air
ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
9 Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
9.1 Draining the appliance . . . . . . . . . . . . . . . . . . . . . . . . . .64
9.2 Overheat thermostat removal . . . . . . . . . . . . . . . . . . . .65
9.3 Pressure sensor removal . . . . . . . . . . . . . . . . . . . . . . . .65
9.4 Pressure relief valve removal . . . . . . . . . . . . . . . . . . . . . 65
9.5 Replacing the gas valve . . . . . . . . . . . . . . . . . . . . . . . . .65
9.6 Checking/replacing the motor of the 3-way valve. . . . .66
9.7 Replacing the optional 3-way valve . . . . . . . . . . . . . . . .66
9.8 Following inspection/maintenance . . . . . . . . . . . . . . . .66
10 Fault finding and diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
10.1 Operating and fault displays . . . . . . . . . . . . . . . . . . . . .67
10.1.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
10.1.2 Fault code table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
10.1.3 Faults that are not displayed . . . . . . . . . . . . . . . . . . . . . 69
11 Environmental protection and disposal . . . . . . . . . . . . . . . . .69
12 Technical Specifications/Logs . . . . . . . . . . . . . . . . . . . . . . . . .70
12.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
12.1.1 Specifications System . . . . . . . . . . . . . . . . . . . . . . . . . .70
12.2 Ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
12.3 Component resistance characteristics . . . . . . . . . . . . .71
12.3.1 Sensor values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
12.4 Code plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
12.5 Pump characteristic map of the heating pump. . . . . . .71
12.6 Setting values for central heating/DHW output . . . . . .72
12.7 Electrical wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
12.8 Gas boiler system commissioning checklist . . . . . . . . .75
12.9 Inspection and maintenance checklist . . . . . . . . . . . . .76
12.10 Service record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
1 Explanation of symbols and safety instructions
1.1 Explanation of symbols
Warnings
In warnings, signal words at the beginning of a warning are used to indicate the type and seriousness of the ensuing risk if measures for minimising danger are not taken.
The following signal words are defined and can be used in this document:
DANGER:
DANGER indicates that severe or life-threatening personal injury will
occur.
WARNING:
WARNING indicates that severe to life-threatening personal injury may
occur.
CAUTION:
CAUTION indicates that minor to medium personal injury may occur.
NOTICE:
NOTICE indicates that material damage may occur.
Important information
The info symbol indicates important information where there is no risk to people or property.
Additional symbols
Symbol Meaning
a step in an action sequence a reference to a related part in the document
a list entry – a list entry (second level)
Table 1
Greenstar 8000 Style – 6720883855 (2019/01)
3
Explanation of symbols and safety instructions
1.2 General safety instructions
H Please read these instructions carefully before
starting installation.
• These instructions are applicable to the Worcester appliance model(s) stated on the front cover of this manual only and must not be used with any other make or model of appliance.
• These instructions apply in the UK and Ireland only and must be followed except for any statutory obligations.
• This appliance must be installed by a competent registered gas engineer, such as a Gas Safe registered engineer including a British Gas engineer. Failure to install correctly could lead to prosecution.
• If you are in any doubt, contact the Worcester Technical help-line (0330 123 3366).
• Distance learning and training courses are available from Worcester.
• The BENCHMARK Commissioning Checklist can be found on page 75 of this Installation manual.
H Notes for the target group
These installation instructions are intended for gas, plumbing, heating and electrical contractors. All instructions must be observed. Failure to comply with instructions may result in material damage and personal injury, including danger to life.
▶ Read the installation instructions (heat source,
heating controller, etc.) before installation.
▶ Observe the safety instructions and warnings. ▶ Observe national and regional regulations,
technical rules and guidelines.
▶ Record all work carried out.
H Intended use
The appliance may only be used for heating water or domestic hot water in domestic properties.
▶ Observe the details on the data plate and the
specifications (installation manual) to ensure correct use of this appliance.
▶ Worcester Bosch offer flue gas systems which are
suitable for use with the appliance. It is the responsibility of the designer/installer of the flue to ensure this flue gas system operates correctly and in a safe manner.
H If you smell gas
A gas leak could potentially cause an explosion. If you smell gas, observe the following rules:
▶ Prevent flames or sparks:
– Do not smoke, use a lighter or strike matches. – Do not operate any electrical switches or unplug
any equipment.
– Do not use the telephone or ring doorbells. ▶ Turn off the gas at the meter or regulator. ▶ Open windows and doors. ▶ Warn your neighbours and leave the building. ▶ Prevent anyone from entering the building. ▶ Move well away from the building: call the National
Gas Emergency Service on 0800 111 999. ▶ L.P.G. boilers: Call the supplier’s number on the
side of the gas tank.
H Risk to life from carbon monoxide poisoning There is a risk to life from escaping flue gases
▶ Do not modify the flue gas system. ▶ Ensure that flue pipes and gaskets are undamaged.
If flue pipes are damaged or leaking:
▶ Turn off and isolate the appliance. ▶ Open windows and doors. ▶ If necessary, leave the building and warn your
neighbours. ▶ Prevent anyone from entering the building. ▶ Rectify any damage to the flue system immediately.
H Installation and maintenance
Installation and maintenance must only be carried out by a competent registered gas engineer, such as Gas Safe registered engineer or British Gas engineer.
▶ Carry out a gas tightness test after completing work
on gas-carrying components. ▶ Only use original spares.
H Electrical work
Electrical work must only be carried out by a qualified electrician:
▶ Before starting electrical work;
– Ensure that the electricity supply is safely
Isolated and secured to prevent inadvertent re­connection. Information on safe isolation can be found in the Health and Safety Executive guidance HSG85.
– Using test equipment approved to GS38 to
confirm that the electricity supply is disconnected.
▶ Refer to the manufacturer’s information when
installing non Worcester components and systems
to the Worcester appliance.
4
Greenstar 8000 Style – 6720883855 (2019/01)
Explanation of symbols and safety instructions
H Handover to the user
When handing over, instruct the user how to operate the heating system and inform the user about its operating conditions.
▶ Explain how to operate the heating system and draw
the user's attention to any safety relevant action.
▶ Explain that modifications and repairs must only be
performed by a competent, registered gas engineer, such as a Gas Safe registered engineer or British Gas engineer.
▶ Leave the installation instructions with the
completed Benchmark Checklist (or a certificate confirming compliance with IS 813, Eire only) and the operating instructions with the user or at the gas meter.
H Servicing
Advise the user to have the system serviced annually by a competent, registered gas engineer, such as a Gas Safe registered engineer or British Gas engineer. Approved spares must be used to help maintain the efficiency, safety and reliability of the appliance.
H Benchmark Service Record
The service engineer must complete the Benchmark Service Record at the back of this manual after each service.
Benchmark places responsibilities on both manufacturers and installers.
The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer's instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot water Industry Council who manage and promote the scheme. Visit centralheating.co.uk for more information.
H Health and safety
The appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations
(Control of Substances Hazardous to Health
Regulations 1988).
H Combustion and corrosive materials
Do not store or use any combustible materials (paper,
thinners, paints etc.) inside or within the vicinity of the
appliance.
Chemically aggressive substances can corrode the
appliance and invalidate any warranty.
H Fitting and modification
Fitting the appliance and any controls to the appliance
may only be carried out by a competent engineer in
accordance with the current Gas Safety (Installation
and Use) Regulations.
Flue systems must not be modified in any way other
than as described in the fitting instructions. Any
misuse or unauthorised modifications to the
appliance, flue or associated components and
systems could invalidate the warranty. The
manufacturer accepts no liability arising from any such
actions, excluding statutory rights.
H General manual handling guidelines
▶ Only remove packaging at the time of the final
installation.
▶ Always use Health and Safety guidance for manual
handling of an appliance. – Never lift or carry more than the safe guidance
limit on your own.
– Always use appropriate methods and equipment
when lifting/carrying an appliance. ▶ Never lift or carry packages by the shipping straps. ▶ During handling and unpacking, wear safety gloves
to prevent injuries to your hands through sharp­edged appliance components.
▶ Dispose of packing materials appropriately.
H Important handling instructions
Care should be taken when transporting, lifting and carrying the appliance.
▶ Use a means of transport suitable for handling
appliances (e.g. sack truck with strap, stair climbing or step trolley).
▶ When handling appliances, secure them against a
fall. ▶ Let only trained personnel undertake the handling. ▶ The correct method for handling heavy objects
should be strictly observed, at all times.
Greenstar 8000 Style – 6720883855 (2019/01)
5
Regulations
2 Regulations
Installation regulations
Current Gas Safety (Installation and Use) Regulations:
All gas appliances must be installed by a competent, registered gas engineer, such as a Gas Safe registered engineer or British Gas engineer in accordance with the current regulations. Failure to install appliances correctly could lead to prosecution.
The appliance must be installed in accordance with, and comply to, the current:
Gas Safety Regulations, IET Regulations, Building Regulations, Building Standards (Scotland) (Consolidation),
Building Regulations (Northern Ireland), local water by-laws,
Health and Safety Document 635 (The Electricity at Work Regulations
1989) and any other local requirements.
EU Regulations No. 811/2013 - Energy Labelling.
Building Regulations Part L1A 2013 - new dwellings
If the installation is in a new build property or it is a first time installation in an existing property, the heating systems must conform to current building regulations Part L1A.
The exception to this are single storey, open plan dwellings where the living area is more than 70% of the total usable floor area. Then this type of dwelling can be controlled as one zone.
An alternative would be individual electronically controlled TRVs.
2
For dwellings with a floor area over 150m temperature control for each zone is required. It is best practice to fit Thermostatic Radiator Valves (TRV's) to all radiators except the area where the room thermostat is sited.
Building Regulations Part L1B 2010 - existing dwellings
For appliance replacements on an existing system, it is not necessary to zone the upstairs and downstairs separately, compliance with the zone requirements can be achieved by a single room thermostat or programmable room thermostat.
While the system is drained down, it is best practice to fit Thermostatic Radiator Valves (TRV's) to all radiators except the area where the room thermostat is sited.
British Standards
Where no specific instruction is given, reference should be made to the relevant British Standard codes of Practice.
• BS7074:1 – Code of practice for domestic and hot water supply
• BS6891 – Installation of low pressure gas pipe work up to 28mm (R1)
• BS5546 – Installation of gas hot water supplies for domestic purposes
• EN12828 – Central heating for domestic premises
• BS5440:1 – Flues and ventilation for gas appliances of rated heating not
exceeding 70kW (net): Flues
• BS5440:2 – Flues and ventilation for gas appliances of rated heating not
exceeding 70kW (net): Air Supply
• BS7593 – Treatment of water in domestic hot water central heating systems
• BS6798 – Installation of gas fired boilers of rated input up to 70kW (net)
• BS7671 – IET Wiring Regulations
, separate time and
Irish Standards
The current relevant Irish standards should be followed, including:
• ECTI – National rules for electrical installations
• IS 813 – Domestic Gas Installations
LPG Installations
An appliance using LPG must not be installed in a room or internal space below ground level unless one side of the building is open to the ground.
Timber framed buildings
Where the appliance is to be fitted to a timber framed building the guidelines laid down in BS5440: Part 1 and IGE “Gas Installations in Timber Frame Buildings” should be adhered to.
Potable water
All seals, joints and compounds (including flux and solder) and components used as part of the secondary domestic water system must be approved by WRAS.
CH Water
Salt based artificially softened water must not be used to fill the central heating system.
3 Product Information
3.1 About the appliance
The boiler has the following features:
• Pre-wired and pre-plumbed
• Galvanised steel inner frame
• Digital control system
• Automatic ignition
• Direct burner ignition electrodes
• Built-in frost protection
• Built-in fault finding diagnostics
• Automatic gas valve
• Modulating combustion air fan with speed regulator
• CH temperature sensor & control
• Pump anti-seizure protection
• Flue gas temperature sensor
• Condensate siphonic trap
• Plate type DHW heat exchanger
• Low Energy Modulating pump
3.2 Misuse
Appliance must be used as per the intended use statement. Operation outside the parameters of the intended use is considered misuse and could cause harm to people and damage to property.
Accessories should be as per accessories list. Minimum operational parameters are included in this document.
Using the appliance outside of its intended use may also invalidate the manufacturer's guarantee.
6
Greenstar 8000 Style – 6720883855 (2019/01)
Product Information
3.3 Scope of delivery
8
7
3.5 Appliance type overview
This appliance are for use with:
21
3
• Natural Gas or L.P.G. (Cat.II 2H3P type C13, C33 & C53)
This document refers to the following appliance types:
Appliance type Part number Gas Council number
GR8700iW 30 S NG 7 738 100 805 41-406-87 GR8700iW 35 S NG 7 738 100 806 41-406-86 GR8700iW 30 SB NG 7 738 100 837 41-406-83 GR8700iW 35 SB NG 7 738 100 838 41-406-82 GR8700iW 30 S LPG 7 738 100 854 41-406-89 GR8700iW 35 S LPG 7 738 100 855 41-406-88 GR8700iW 30 SB LPG 7 738 100 856 41-406-85 GR8700iW 35 SB LPG 7 738 100 857 41-406-84
Table 2 Type overview
The name of the appliance consists of the following parts:
• GR8700iW: Type name
• 30 or 35: Heat output in kW
• S: System appliance
• B: Black font panel
• NG: Gas type (Natural Gas)
• LPG: Gas type (Liquid Petroleum Gas)
3.6 Product identification
6
5
Fig. 1 Scope of delivery
[1] Wall mounted gas condensing boiler [2] Mounting bracket [3] Mounting plate [4] PRV Discharge pipe (including securing clips) [5] Guarantee card [6] Set of printed documents for product documentation [7] Fixing materials (screws with accessories) [8] Lower cover
3.4 Declaration of Conformity
The design and operation of this product comply with European Directives and the supplementary national requirements. Conformity has been demonstrated by the CE marking.
You can ask for a copy of the declaration of conformity for this product. For this see the contact address on the back cover of these instructions.
4
0010023673-001
Data plate
The data plate includes the product performance information, approval data and serial number. The data plate location can be found in the product overview.
Additional type plate
The product name and the most important product data are shown on the additional data plate. The additional type plate can be found on the outside of the product in an easily accessible location.
Greenstar 8000 Style – 6720883855 (2019/01)
7
Product Information
3.7 Pipe work positions and flue outlet
# Function From left
case edge
1 Condensate Outlet 58mm 22mm
2 CH Flow 90mm 22mm
3 Cylinder Return 1)155mm 15mm
4 Gas inlet 220mm 22mm
1)
5 Cylinder Flow
6 CH Return 350mm 22mm
7 PRV Discharge 384mm 15mm
1) Only available if optional integral diverter valve kit is fitted.
Table 4 Pipe dimensions
For servicing purposes, keep condensate and pressure release valve discharge pipes away from other hydraulic components.
285mm 15mm
Diameter of pipe
• Rubber push fit connection
• Compression fitting
• Compression fitting
• Compression fitting
• Compression fitting
• Compression fitting
• Compression fitting
2
1
Fig. 2 Pipe and flue outlet dimensions
Description Dimensions (mm)
X Appliance width 440 Y Appliance height 780 Z Appliance depth 365 W Flue centre from appliance left side 220 D Flue centre from rear of appliance 87
Table 3 Appliance and flue outlet dimensions
4
3
6
5
7
0010023464-001
8
Greenstar 8000 Style – 6720883855 (2019/01)
3.8 Designation of components
13
12
11
10
9 8 7
Product Information
14
15
16
17
18
19
20
6
5
4
21
22
23 24
3
25 26
2
27
1
28
29
Fig. 3 Product overview System boilers, combustion cover removed
[1] KEY accessory housing slot (wireless Gateway) [2] Condensate trap [3] Data plate 1 [4] Pressure sensor [5] Pressure gauge [6] Venturi (sealed)
Greenstar 8000 Style – 6720883855 (2019/01)
0010023657-001
[7] Schrader Valve [8] Fan [9] Expansion vessel [10] Heating flow [11] Air-gas manifold with non-return valve [12] Ignition transformer
9
Product Information
[13] Flue [14] Ignition electrodes [15] Flame sensing electrode [16] Flow temperature sensor at flow pipe [17] Heating block temperature limiter [18] Flow temperature sensor at heating block [19] Inspection cover [20] Condensate sump [21] Gas valve [22] Automatic air vent valve (pump) [23] Data plate 2 [24] Diverter valve (accessory) [25] Heating pump [26] Drain point [27] Pressure relief valve (heating circuit) [28] Central heating return [29] Control unit
3.9 Product data for energy consumption
The product data on energy consumption can be found in the operating instructions for the user.
3.10 Standard accessories
The appliance has the option to fit an integral diverter valve kit, whichhas multiple controls options for the use with vented and unvented hotwater cylinders. The details can be found in the Installation Instructionsfor the diverter valve kit.
10
Greenstar 8000 Style – 6720883855 (2019/01)
4 Pre-Installation
NOTICE:
Risk of damage to system or appliance!
Before installation
▶ All the following Pre-Installation sections must be read and
requirements met before starting appliance or flue installations.
4.1 System preparation
4.1.1 Artificially softened water
It is possible to have an ion exchange water softener fitted to the cold water system of the property. However, the appliance requires an untreated cold water connection taken from the mains supply, before the water softener, to the primary water filling point of the heating system.
Alternatively there are water softening/treatment appliances that do not adjust or alter the pH levels of the water. With these appliances it may not be necessary to provide an untreated water by-pass to the primary water filling point of the heat system.
NOTICE:
▶ Salt based softened water must not be used to fill the central heating
system.
4.1.2 Water systems and pipe work
Pre-Installation
Hot water:
• Taps and mixing valves must be capable of sustaining a pressure up to
10 bar.
• Hot water temperature and flow rate are affected by the size and
insulation of pipe work making up the distribution system and are controlled by the hot water tap and the water main inlet pressure. A mixing valve can be fitted if a more permanent temperature setting is required.
• If using more than one outlet at once causes water flow starvation, fit
flow balancing valves or Ball-O-Fix valves to the appropriate outlets.
Primary system considerations - Combi & System appliances
Sealed system
• The CH sealed system must be filled using a WRAS approved filling
loop or comply with examples in 4.1.4 "System fill" section.
• Where the system volume is more than 100 litres or exceeds 2.5 bar
at maximum heating temperature an additional expansion vessel [2] must be fitted as close as possible to the appliance in the central heating return.
• Pressurise the extra expansion vessel [2] to the same value as the
built-in expansion vessel - refer to the Technical data page.
1
2
Primary system plastic pipework:
• Any plastic pipe work must have a polymeric barrier, complying with BS 7921 and installed to BS 5955 with 600mm (minimum) length of copper connected to the appliance.
• Plastic pipe work used for under-floor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approximately 50°C with 1000mm (minimum) length of copper or steel pipe connected to the appliance.
Primary system/connections/valves:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• It is best practice to fit Thermostatic Radiator Valves (TRV's) to all radiators, except the area where the room thermostat is sited which must be fitted with lockshield valves that are left open.
• If the circulating pump speed is fixed and system circulation can be significantly adjusted or stopped by TRV's or zone valves, a system bypass should be installed to give at least a 3 metre circuit when activated. However; any appliance fitted with a modulating pump may not require a system bypass.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
3
Fig. 4 Additional expansion vessel
[1] Appliance expansion vessel [2] Additional expansion vessel [3] Pressure relief discharge [4] Heating return [5] Heating flow
4
5
0010021117-001
Showers/Bidets:
• If a shower head can be immersed in water or comes closer than 25mm from the top edge of a bath or shower tray spill-over level then an anti-siphon appliance must be fitted to the shower hose.
• Bidets with direct hot and cold mains water can be used (with the approval of the local water authority) and must be the over rim flushing type with shrouded outlets to prevent the fitting of hand held sprays.
Greenstar 8000 Style – 6720883855 (2019/01)
11
Pre-Installation
Checking the size of the expansion vessel
To determine whether an additional expansion vessel is required: Follow the steps below:
▶ Calculate the total system volume (litres). Plotting a line vertically on
the chart ( Fig. 5).
▶ Determine the central heating maximum operating flow temprature
(73 °C for condensing). Plot a line horizontally on the chart ( Fig.
5).
▶ Determine the pre charge in the expansion vessel based on static
head, 1 meter = 0.1 bar. (default = 10 metres).
▶ Select a curve from the key below (1-5).
If the dissected lines are in area A then no additional expansion is required.
If the dissected line is in are B then an additional expansion vessel must be installed ( Fig. 4).
T[°C]
90
80
70
60
5
4
B
3
2
50
1
A
40
Sealed primary system - Cylinder and 2 x central heating zones:
Typical S-Plan Plus example
• The cylinder return must be the last connection on the common return pipe to prevent reverse circulation.
2
2
3
2
1
Fig. 7 Cylinder and 2 x heating zones
[1] Appliance [2] Zone valves [3] Hot water cylinder
Sealed primary system - 3-way valve, cylinder and central heating zone:
Typical Y-Plan example
• The cylinder return must be the last connection on the common return pipe to prevent reverse circulation.
0010021230-001
30
0 100 200 300 400 500 600 700
V[l]
0010016558-002
Fig. 5 Curves for the expansion vessel
1 Pre-charge pressure 0.5 bar (minimum) 2 Pre-charge pressure 0.75 bar 3 Pre-charge pressure 1.0 bar (default setting) 4 Pre-charge pressure 1.2 bar 5 Pre-charge pressure 1.3 bar T Maximum operating temperature [ °C] V Total System Volume [l]
4.1.3 System layouts examples
Sealed primary system - Cylinder and central heating zone:
Typical S-Plan example
• The cylinder return must be the last connection on the common return pipe to prevent reverse circulation.
2
2
3
2
3
1
Fig. 8 3-way valve, cylinder and heating zone
[1] Appliance [2] 3-Way zone valve [3] Hot water cylinder
Optional integral diverter valve kit
This appliance is designed to operate on a sealed system only. The appliance will require to fit a separate flow and return pipe from the water cylinder to the wall mounting frame and terminate in 15mm copper pipe.
Details for the connection of the integral diverter valve kit components are found within the Installation Instructions for the kit.
0010021231-001
1
Fig. 6 Cylinder and heating zone
[1] Appliance [2] Zone valves [3] Hot water cylinder
12
0010021229-001
Sealed primary system - Internal diverter valve kit:
• This appliance is designed to operate on a sealed system only. The appliance will require a second flow and return pipe from the hot water cylinder to the wall mounting frame and terminate in 15mm copper pipe. The following system layouts show a simplified example of the pipe configuration to the appliance.
Greenstar 8000 Style – 6720883855 (2019/01)
4.1.4 System fill
Filling primary sealed systems
Pre-Installation
3
1
0010021286-001
Fig. 9 Example layout - Internal diverter valve kit
[1] Appliance with internal diverter valve kit [3] Unvented hot water cylinder
Unvented cylinders
In all cases the cylinder manufacturer must be contacted for confirmation their product is suitable for the installation layout shown in figure 9.
Although the accepted common practice of a 2-port motorised valve installed in the primary flow pipe to the cylinder and wired to the dual­thermostat supplied with the cylinder. It is possible to use the integral diverter valve kit and not need the 2-port motorised valve to cut the flow of heat to the cylinder to comply with Building Regulation Part G3.
• The integral diverter valve kit cylinder sensor must be used.
• The general layout (figure 9) can be used for unvented cylinder by utilising the high limit thermal cut out of the cylinder dual-thermostat to interrupt the permanent live to the appliance, preventing any heat being produced from the appliance.
Example layout with unvented cylinder & cylinder safety valve.
If required by the cylinder manufacture to fit/use the cylinder safety valve then this can also be carried out (figure 10) with the integral diverter valve kit.
• The cylinder safety valve and dual-thermostat (control thermostat and high limit thermal cut out) are wired to interrupt the permanent live to the appliance, preventing any heat being produced from the appliance.
2
3
NOTICE:
Filling the primary sealed system
The system must not be filled with salt based softened water.
▶ Ensure the primary water filling point uses an untreated cold water
connection from the mains supply, before a water softener.
• Filling the system must comply with one of the following methods shown.
• The filling point must be at low level and must never be a permanent connection to the mains water supply.
• Filling loops must be WRAS approved.
• If the external filling link is sited away from the appliance, then a pressure gauge should be installed at the filling point.
External filling loop
1
3 3
5
6
22
4
0010012942-001
Fig. 11 External filling loop system fill example
[1] Cold mains inlet pipe [2] Stop valve [3] Check valve [4] Test point [5] Hose union [6] Central heating flow pipe
Top-up tank system fill
In situations where the cold mains pressure is not sufficient to pressurise the system to between 1 and 1.5bar an alternative can be to use a top-up tank.
7
9
8
2 3
1
Fig. 10 Example layout - Internal diverter valve kit with unvented
cylinder and cylinder safety valve
[1] Appliance with internal diverter valve kit [2] Cylinder safety valve (unvented cylinder) [3] Unvented hot water cylinder
Greenstar 8000 Style – 6720883855 (2019/01)
0010021233-001
6
0010012943-001
Fig. 12 Top-up tank system fill example
[2] Stop valve [3] Check valve [6] Central heating flow pipe [7] Top-up tank [8] Automatic air vent [9] Minimum height above the highest point of the system - 1000mm
(39 in)
13
Pre-Installation
4.2 Mains supply
4.2.1 Electrical supply
• Supply: 230V AC - 50 Hz
• This appliance must not be connected to a three phase supply.
• The wiring between the appliance and the electrical supply must comply with the latest IET wiring regulations that apply to wiring a fixed appliance.
• Type A RCDs must be employed where additional protection is required.
• External 3fuse to BS1362.
• The appliance must be earthed.
• Cable: PVC insulated 0.75mm
2
(24 x 0.2mm) temperature rated to
90 °C, to BS EN50525.
• Any additional components that are connected to the appliance with mains electrical supply must not have a separate supply.
• Additional equipment wired to the appliance must comply with the latest IET wiring regulations.
• Appliance IP rating - IPX4D
4.2.2 Gas supply
• Appliances using Natural Gas (NG) must be connected to a governed meter.
• Appliances using Liquid Petroleum Gas (LPG) must be connected to a regulator.
• Installation and connection of the gas supply to the appliance must be in accordance with BS6891.
• Gas pipe sizing should be calculated to ensure no more than the permitted mbar drop between the meter/governor to the appliance inlet. ( chapter 12.8).
• The meter or regulator and pipe work to the meter or regulator must be checked, preferably by the gas supplier. This is to ensure that the equipment is in good working order and can meet the gas flow and pressure requirements, in addition to the demand from any other appliance being served.
Pipe sizing (NG & LPG)
Natural Gas:
▶ When using this table to estimate the gas flow rate in pipe work of a
known length, the effective length will be increased by 0.5m for each 90° elbow and tee fitted and by 0.3m for each 90° bend. This method is only a estimate - for more complex design please refer to BS6891 2015 and training given in ACS.
Liquid Petroleum Gas (LPG):
Discharge rates for copper tube with 2.5mbar differential pressure between the ends for LPG.
Discharge rates for LPG (m3/hr & kW)
with straight horizontal copper tube
Tubing Outside diameter
Length (m) 15mm 22mm 28mm
kW m3/hr kW m3/hr kW m3/hr 3 38.4 1.49 207 8.01 412 15.92 6 26.1 1.01 135 5.21 230 8.86 9 20.5 0.79 108 4.19 215 8.33
12 17.9 0.70 94 3.62 187 7.25 15 15.5 0.60 82 3.20 168 6.51 18 13.5 0.53 74 2.86 145 5.61 21 12.9 0.50 67 2.58 135 5.24 24 12.0 0.47 61 2.58 126 4.87
Table 6 Liquid Petroleum Gas (LPG)
Liquid Petroleum Gas (LPG):
▶ When using this table to estimate the Gas flow rate in pipe work of a
known length, the effective length will be increased by 0.6m for each 90° elbow or tee and by 0.3m for each 90° bend or straight coupler. This method is only a estimate - for more complex design please refer to BS6891 2015 and training given in ACS.
Gas pipe work:
▶ Gas installation pipe work must be designed to ensure the pressure
loss between the meter outlet (NG) or storage and regulator (LPG) and the inlet to each appliance does not exceed 1mbar (NG) 2.5mbar (LPG) table ”Allowed mbar pressure drop”.
Natural Gas (NG):
Discharge rates for copper tube with 1mbar differential pressure between the ends for Natural Gas.
Discharge rates for Natural Gas (m3/hr)
with straight horizontal copper tube
Pipe Pipe Size (mm)
Length (m) 15 22 28 35
3
2.9 8.7 18 32 6 1.9 5.8 12 22 9
1.5 4.6 9.4 17
12 Discharge 1.3 3.9 8 15 15
m3/hr 1.1 3.4 7 13 20 0.95 2.9 5.9 11 25
0.92 2.5 5.2 9.5
30 0.88 2.3 4.7 8.5
Table 5 Natural Gas
4.3 Appliance location and clearances
4.3.1 Appliance location
• Follow local regulations for the location within the property that the appliance is to be installed.
• This appliance is only suitable for installing internally within a property at a suitable location onto a flat, fixed rigid surface capable of supporting the appliance weight.
• The appliance is not suitable for external installation.
No surface protection is required againat heat transfer from the appliance
DANGER:
Danger from explosive and flammable materials:
Storage of explosive and flammable materials.
▶ Do not store flammable materials (paper, curtains, clothing, primer,
paint, …) in proximity to the appliance.
14
Greenstar 8000 Style – 6720883855 (2019/01)
Pre-Installation
NOTICE:
Damage to appliance:
Contaminated combustion air.
▶ Do not use any cleaners containing chlorine or hydrogen halide (i.e.
spray cans, primers, cleaners, paint and glue). ▶ Do not store or use these substances in the appliance, room. ▶ Avoid the build up of dust.
NOTICE:
Damage to appliance:
Extreme temperatures may cause damage to the heating system.
▶ Ensure the ambient temperature is above 0 °C and below 35 °C.
NOTICE:
Damage to system:
The heating system pipe work can be damaged by frost if installed in an internal unheated area, such as a loft, basement or garage. The appliance internal frost protection only monitors the system water temperature within the appliance to provide protection for the appliance.
▶ Install a frost thermostat and pipe thermostat connected in series, to
protect the system pipe work.
We recommend that the frost thermostat is sited in the coldest
unheated area in which pipe work is located and that it is set to call for
heat at 5 °C. The Pipe stat should be located on whichever pipe is
furthest from the heated area where warmer water will be drawn from
considering the direction of flow, and set to end the demand at 15 °C. ▶ The system pipe work in the internal unheated area should be
insulated. ▶ If the appliance is to be shut down for an extended period, drain the
central heating system.
4.3.2 Rooms containing a bath or shower
CAUTION:
Risk of electric shock
▶ Any switch or appliance control using mains electricity must not be
within reach of a person using the bath or shower.
• In all cases the installation must be in accordance with the latest
amendments to the latest edition of the IET Wiring Regulations (BS7671).
• Check the IP rating of any control units to be used on this appliance.
• Circuit breaking appliances should be used in accordance with the regulations.
• Figure 13 is for guidance only.
600mm
600mm
600mm
1
1
2*
2250mm
2*
A
2
2
1
2
A
A
0010017086-001
Fig. 13 Bathroom installations
[1] Zone 1 [2] Zone 2 [2*] Without the end wall, zone 2 must extend 600mm from the bath [A] 600mm radius from the bath or shower
2250mm
The appliance must be installed where:
▶ The area is well lit, allowing to clearly see the appliance to carry out
any work or checks.
▶ An engineer can gain clear and safe access to work on the product or
component, including making adequate provision for visual inspection of flues in voids.
▶ The homeowner can gain clear and safe access to the controls, check,
top up or reset the appliance.
▶ Roof space installations must fully conform to BS 5410 part 1: roof
space installations.
▶ Products in roof spaces must have permanent fixed lighting, a
permanent fixed retractable ladder and a fixed floor area sufficient to allow access for normal use and servicing around the product and between and the access hatch. We would also recommend that a remote pressure gauge and filling loop are sited where the customer can gain easy access for checking and topping up.
4.3.3 Appliance clearances
Appliance clearances
• The following details covering the installation, service and maintenance clearances for the appliance.
CAUTION:
Risk of damage to appliance or property
The appliance will overheat if the clearance space around the appliance is restricted by objects.
▶ Do not restrict this space with the addition of cupboards, shelves etc.
next to or around the appliance.
▶ Do not store any combustible materials on or next to the appliance,
such as clothes, towels, paper or plastic bags.
Greenstar 8000 Style – 6720883855 (2019/01)
15
Pre-Installation
0010012940-001
Fig. 14 Appliance minimum clearances
Minimum clearances
Description Dimensions (mm)
X Appliance width 440 Y Appliance height 780 Z Appliance depth 365
Installation/Maintenance
1 Overall clearance height 1,150/1,190 * 2 Overall clearance depth 965 3 In front of appliance 600 4 Overall clearance width 450 5 Above the appliance 170/210 * 6 Either side of appliance 5 7 Below the appliance 200 8 Compartment depth 385 9 Appliance to removable door 20
Table 7
[*] Height for either 60/100 flue or 80/125 flue
Appliances in compartments
Follow the latest requirements of BS6798 and BS5440 and note:
• Minimum clearances must be maintained.
• An access door is required to install, service and maintain the appliance and any ancillary equipment.
• If the appliance is installed in an unventilated airing/storage cupboard, there is no requirement to make a partition between the appliance and the storage space as long as the minimum clearances around the appliance are maintained.
4.4 Flue systems considerations
WARNING:
Flue systems
Possible flue gas escape
▶ Use Worcester, Bosch Group approved Condensfit II flue systems
only, no other manufacturer’s flue have been tested or approved for use with Worcester, Bosch Group appliances.
CAUTION:
Concealed flue systems:
▶ Where a flue system is going to be concealed, provision must be
made for service and inspection.
▶ Voids containing concealed flues must have at least one inspection
hatch no less than 300mm square.
▶ Flue joints within the void must not be more than 1.5 metres from the
edge of the inspection hatch. ▶ Inspection hatches should be located at changes of direction. ▶ If this is not possible, bends should be viewable from both directions.
Refer to the manual supplied with the Worcester, Bosch Group flue kit for complete installation instructions.
Flue kit part numbers
Part number Flue Ø Description
7 738 112 869 60/100 Telescopic horizontal flue kit (Silver) 7 716 191 082 60/100 Telescopic horizontal flue kit 7 716 191 171 60/100 Extended telescopic horizontal flue kit 7 733 600 048 60/100 Horizontal high level telescopic flue kit 7 719 003 702 80/125 Telescopic horizontal flue kit 7 719 002 430 60/100 Vertical balanced flue kit 7 719 002 431 80/125 Vertical balance flue kit
Table 8 Flue kit assembly part numbers
4.4.1 Flue length
The maximum flue length will depend on the following factors:
• 60/100mm flue system
– Vertical/horizontal flue type
– Appliance output
– Plume management length
• 80/125mm flue system
– Vertical/horizontal flue type
– Appliance output
16
Horizontal maximum flue lengths
Maximum horizontal flue lengths (L) Output 60/100 80/125
No Plume management
+ 500mm of plume management
+4500mm of plume management
No plume management
available 35kW 10,000mm 10,000mm 7,200mm 29,000mm 30kW 17,000mm 17,000mm 14,200mm 25,000mm
Table 9 Maximum flue lengths - Horizontal flues
Greenstar 8000 Style – 6720883855 (2019/01)
Pre-Installation
Vertical maximum flue lengths
Flue length [L] Flue length [L]
Output 60/100 80/125
35kW 14,000mm 29,000mm 30kW 21,000mm 25,000mm
Table 10 Maximum flue lengths - Vertical flues
Flue system bends
NOTICE:
Effective flue lengths of bends:
Each bend used has an equivalent straight flue length.
▶ Refer to the table below.
Effective flue length
Bend 60/100 80/125
45° 0.5m 0.5m 90° 1.5m 1.5m
Table 11 Effective length of bends
4.4.2 Flue options
The systems have diiferent maximum flue lengths, refer to the following example flue options for those maximum flue lengths.
Horizontal high level flue assembly
60/100 mm
383 mm - 603 mm
Horizontal fixed length flue assembly
1050 mm
330 mm Min
0010015192-001
Fig. 17 Horizontal flue option
• Flue length [L] (adaptor bend included in length calculation) – 60/100 = 330 - 1,050mm – 80/125 = N/A
Extended horizontal flue
0010015193-001
Fig. 18 Horizontal flue option
• Flue length [L] (adaptor bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths".
Horizontal flue with additional 90° elbow
130 mm Min
Fig. 15 Horizontal flue option
• Flue length [L] (initial bend included in length calculation) – 60/100 = 202 - 603mm – 80/125 = N/A
Telescopic horizontal flue assembly
60/100 mm
[A] 350 mm - 570 mm [B] 570 mm - 790 mm
130 mm Min
Fig. 16 Horizontal flue option
Telescopic horizontal flue assembly [A]
• Flue length [L] (adaptor bend included in length calculation) – 60/100 = 180 - 570mm – 80/125 = 405 - 600mm
Extended telescopic horizontal flue assembly [B]
• Flue length [L] (adaptor bend included in length calculation) – 60/100 = 570 - 790mm – 80/125 = N/A
0010015190-001
0010015194-001
Fig. 19 Horizontal flue option
• Flue length [L] (adaptor bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths" minus the 90° bend equivalent straight flue length as stated in Table 11 "Effective length of bends".
Horizontal flue with additional 90° elbows
0010015191-001
0010015195-001
Fig. 20 Horizontal flue option
• Flue length [L] (adaptor bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths" minus 2 x 90° bends equivalent straight flue length as stated in Table 11 "Effective length of bends".
Greenstar 8000 Style – 6720883855 (2019/01)
17
Pre-Installation
A
A
A
High level horizontal flue
Fig. 21 Horizontal flue option
• Flue length [L] (initial bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths".
High level horizontal flue with additional 90° elbow
0010015196-001
0010015197-001
Vertical balanced flue assembly
= 300 mm
B = 500 mm
0010015199-001
Fig. 24 Vertical flue option
• Flue length [L] – Maximum flue length as stated in "Vertical maximum flue
lengths".
Vertical balanced flue with 90° elbow offset
Fig. 22 Horizontal flue option
• Flue length [L] (initial bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths" minus the 90° bend equivalent straight flue length as stated in Table 11 "Effective length of bends".
High level horizontal flue with additional 90° elbows
Fig. 23 Horizontal flue option
• Flue length [L] (initial bend included in length calculation) – Maximum flue length as stated in "Horizontal maximum flue
lengths" minus 2 x 90° bends equivalent straight flue length as stated in Table 11 "Effective length of bends".
= 300 mm
B = 500 mm
0010015200-001
Fig. 25 Vertical flue option
• Flue length [L] – Maximum flue length as stated in "Vertical maximum flue lengths"
minus 2 x 90° bends equivalent straight flue length as stated in Table 11 "Effective length of bends".
Vertical balanced flue with 45° elbow offset
0010015198-001
= 300 mm
B = 500 mm
0010015201-001
Fig. 26 Vertical flue option
• Flue length [L] – Maximum flue length as stated in "Vertical maximum flue lengths"
minus 2 x 45° bends equivalent straight flue length as stated in Table 11 "Effective length of bends".
18
Greenstar 8000 Style – 6720883855 (2019/01)
4.4.3 Plume management system
For every extra 1000mm of plume management after the first 500mm, the internal 60/100 flue length must be reduced by 700mm, up to a maximum of 4500mm of plume management.
2,800
2,100
1
1,400
Pre-Installation
m
m
00
5
[mm]
700
0
500 1,500 2,500 3,500 4,500
[mm]
2
0010023114-001
Fig. 27 Reduction to flue length as plume length increases graph
[1] Reduction to flue length [mm] (maximum reduction 2,800mm) [2] Plume length [mm] (maximum plume length 4,500mm)
NOTICE:
Plume management length:
▶ The plume management length must be a minimum of 500mm and
must not exceed the maximum straight length for a horizontal Ø 60/ 100mm flue with a 60mm plume management system as stated previously.
Horizontal plume management runs
▶ The initial horizontal run from the terminal elbow must have a
minimum 10° fall back, (stop tabs in the elbow prevent less than 10°) to the appliance for proper disposal of condensate.
▶ Any further horizontal runs after an elbow can be 3°.
WARNING:
Minimum plume management length:
The minimum distance of 500mm must be maintained between air inlet and exhaust.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 28.
5
0
0
m
m
mm
00
5
±80°
0010013548-001
Fig. 28 Terminal exclusion zone
NOTICE:
Cutting the 500mm pipe
If the 500mm plume management pipe kit is cut, an additional elbow will be required to join the pipe work.
▶ The Plume management extension kit contains the components
required for such a configuration.
4.4.4 Flue terminal positions
CAUTION:
Flue terminal positions
▶ All measurements are the minimum clearances required. ▶ Terminals must be positioned so to avoid combustion products
entering the building.
Greenstar 8000 Style – 6720883855 (2019/01)
19
Pre-Installation
Vertical flue terminal positions
1/2
1/2
1500
1500
RIDGE FLUERIDGE VENT
1
600
BOUNDARY LINE
BOUNDARIES
9
1500
2
3
300
8
1200
300
2
1500
4
600
300
1
1500
500
2
600
400
7
300
5
400
600
600
7
500
5
2000
600
1500
6
Fig. 29 Vertical flue terminal positions
Key to figure 29:
[1] 1,500mm measured horizontally between a vertical flue terminal
and an opening or vented window. 500mm measured horizontally between a vertical flue terminal and an opening or vented window providing the flue terminal is at least 300mm above the opening.
[2] Minimum clearance to an additional flue, 600mm to a room
sealed flue or 1,500mm to an open flue.
[3] 300mm clearance from a vertical flue terminal adjacent to a
boundary line, unless it will cause a nuisance. BS 5440: Part 1 recommends that care is taken when siting a terminal in relation to boundary lines.
[4] 600mm minimum clearance measured from an opening or vented
skylight to a vertical flue terminal. If the terminal is within 1,500mm of the opening or vented skylight then it must be at least 300mm above the opening.
[5] 500mm clearance measured horizontally from a vertical flue to a
vertical structure.
[6] The flue must not penetrate the roof in the shaded area.
The terminal must be at least 1500mm from the opening or vent when sited below the window or 600mm when sited to either side or above.
0010021441-001
[7] 400mm measured diagonally from a pitched roof or 500mm in
regions with heavy snow fall. 300mm measured vertically from the air intake to the closest intersection with the roof.
[8] 1,200mm separation between a vertical flue measured
horizontally and a horizontal flue terminal. Not required if the horizontal flue is 1,200mm above.
[9] For the purpose of determining suitable flue terminal positions for
gas appliances, the boundary can be considered to extend to the centre line of any adjacent routes or waterways e.g. paths, streets, rights of way, canals, rivers or railways.
Note:
▶ Where a vertical flue terminates in an area that is enclosed on 3 sides,
the flue must be no more than 1,000mm below the lowest roof line. You must ensure that all clearances are maintained and that products of combustion disperse safely from the area.
20
Greenstar 8000 Style – 6720883855 (2019/01)
Horizontal flue terminal positions
Pre-Installation
11
300
300
1500
300
10
BOUNDARY LINE
OPENING
OPPOSITE
14
2000
300
3
600
TOP
TOP
600
600
SKYLIGHTDORMA
6
600
600
600
1500
6
5
1
600
200
300
10
200
1
10
300
7
5
600
10
25
300
300
8
600
13
1200
300
1000
300
300
300
11
3
300
11
300
5
1200
4
BOUNDARY LINE
200
1/2
1/2
1
100
BOUNDARIES
2
200
25
75
25
75
25
9
25
100
25
25
100
25
25
100
Fig. 30 Horizontal flue terminal positions
Key to figure 30:
[1] 200mm below eaves and 75mm below gutters, pipe and drains. [2] The dimension below eaves, gutters, pipes and drains can be
reduced to 25mm, as long as the flue terminal is extended by 100mm past any overhang. The telescopic flue joint must be sealed with suitable silicone sealant if it is external to the building.
[3] 300mm adjacent to a boundary line, unless it will cause a
nuisance. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to surfaces or boundary lines.
[4] 1,200mm separation measured between terminals facing each
other.
[5] 600m distance to a surface or boundary line facing a terminal,
unless it will cause a nuisance. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to surfaces or boundary lines.
1
BELOW GROUND OPEN LIGHT WELL
<1000
300
300
300
2
12
600
15
300150
[6] The terminal must be at least 1500mm from the opening or vent
when sited below the window or 600mm when sited to either side or above.
[7] 600mm diagonally to an opening door, air vent or opening
window.
[8] 1,200mm separation between a vertical flue measured
horizontally and a horizontal flue terminal. Not required if the horizontal flue is 1,200mm above.
[9] For the purpose of determining suitable flue terminal positions for
gas appliances, the boundary can be considered to extend to the centre line of any adjacent routes or waterways e.g. paths, streets, rights of way, canals, rivers or railways.
[10] 300mm to an internal or external corner. 300mm above a
surface, such as the ground/ floor level or roof surface. * If the terminal section is less than 150mm and has two screws securing it to the elbow, the terminal section will not require a supporting bracket.
16
100
25
10
300
0010021442-001
Greenstar 8000 Style – 6720883855 (2019/01)
21
Pre-Installation
[11] 300mm above, below and either side of an opening door, air vent
or opening window.
[12] Below ground level in an open lightwell. The flue must be at least
600mm from the opposing surface and have at least 300mm clearance either side and below. The flue terminal must be no more than 1000mm from the top of the lightwell.
[13] Flues should clear any LPG storage by 1,000mm horizontally and
300mm above.
[14] Proximity of flue duct outlet to boundaries, 2000mm distance to
an opening in adjacent building facing a terminal. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to boundary lines.
[15] 300mm from an opening or vented window, 150mm to a fixed
unvented window.
[16] The dimension below eaves, balconies and car ports can be
reduced to 25mm, as long as the flue terminal is extended to clear any overhang. The telescopic flue joint of the terminal must be sealed with suitable silicon sealant if it is external to the building.
Note:
▶ Installations in car ports are not recommended. ▶ The flue cannot be lower than 1,000mm from the top of a light well
due to the build up of combustion products.
▶ Dimensions from a flue terminal to a fanned air inlet to be determined
by the ventilation equipment manufacturer.
▶ A flue terminal guard shall be fitted whenever a terminal or air inlet is
fitted less than 2,000mm above ground, above a balcony or above a flat roof to which people have access.
4.4.5 Plume re-direct and plume management terminal positions
Maximum and minimum plume management lengths:
▶ A minimum distance of 500mm must be maintained between the
plume management outlet and the flue air intake.
▶ The maximum plume management length is 4.5 metres for the
appliances detailed on the front of this manual.
▶ The 45° bend is equivalent to 0.5 metres of straight plume
management and the 90° bend is equivalent to 1.0 metres.
NOTICE:
▶ All measurements are the minimum clearances required. ▶ Refer to “Horizontal flue terminal positions” for all concentric flue
terminal positions unless the flue position is specified in figure 31 “Plume re-direct and plume management terminal positions”.
▶ Terminals must be positioned so to avoid combustion products
entering the building.
▶ Support the flue at approximately one metre intervals and at a change
of direction, use suitable brackets and fittings.
22
Greenstar 8000 Style – 6720883855 (2019/01)
Pre-Installation
180°
200
300
2
200
300
150
300
600
BOUNDARY LINE
300
±80°
9
1
200
150
1200
BOUNDARY LINE
2
TOP
3
TOP
±45°
11
12
2000
600
0
0
5
0
5
6
5
5
0
0
EXCLUSION ZONE
8
OPENING
OPPOSITE
300
7
TOP
0
±80°
600
300
300
BOUNDARY LINE
6
600
5
600
300
10
10
300
150
1,500
150
4
300
1500
300
13
≥140
0
0
≥5
EXCLUSION ZONE
25
25
150
100
14
200
600
15
300
100
00
≥5
EXCLUSION ZONE
7
10
300
150
TOP
8
300
9
150
FLUE TERMINAL GUARD
7 716 191 176
0010021676-001
Fig. 31 Plume re-direct and plume management terminal positions
Key to figure 31 - Plume re-direct terminal positions:
[1] This feature allows some basic plume re-direction options on a
standard telescopic horizontal flue terminal. 300mm minimum clearances to a opening e.g. window. However the minimum clearances to an opening in the direction that the plume management is facing, must be increased to 1,500mm. Where the flue is less than 150mm to a drainpipe and plume redirection is used the deflector should not be directed towards the drainpipe.
[2] 300mm adjacent to a boundary line, unless it will cause a
nuisance. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to surfaces or boundary lines.
[3] Where the flow of products of combustion is not at right angles to
the boundary, the 600mm dimension may be measured in the direction of flow as long as the terminal is not less than 300mm from the boundary.
[4] When redirecting the flue discharge the terminal end must be at
least 1,500mm from any opening in the direction of the discharge to prevent combustion products from entering the building.
Key to figure 31 - Plume management terminal positions:
[5] 600mm distance facing a surface or a boundary line, unless it will
cause a nuisance. BS 5440:Part 1 recommends that care is taken when siting a terminal in relation to surfaces or boundary lines.
[6] Proximity of flue duct outlet to boundaries, 2000mm distance to
an opening in adjacent building facing a terminal. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to boundary lines.
[7] 300mm adjacent to a boundary line, unless it will cause a
nuisance. BS 5440: Part 1 recommends that care is taken when siting terminal in relation to surfaces or boundary lines.
[8] 300mm distance from a boundary line to the air intake as long as
the exhaust terminal faces away from the boundary line. The exhaust terminal must have a minimum 300mm clearance to a surface below and there must be at least 600mm clearance when measured horizontally in a straight line from the exhaust terminal to any other surface.
[9] Plume Management kit air intake can be reduced to 150mm
providing the flue exhaust outlet is no less than 300mm adjacent to a boundary line.
[10] Above, below and either side of an opening door, air vent or
opening window. Using a Plume Management kit the air intake measurement can be reduced to 150mm providing the flue exhaust outlet has a 300mm clearance.
[11] Below balcony or overhange. The air intake clearance can be
reduced to 150mm providing the flue exhaust outlet has a 200mm clearance.
[12] 1,200mm between terminals facing each other
1)
.
[13] Internal/external corners. The air intake clearance can be reduced
to 150mm providing the flue exhaust outlet has a 300mm clearance.
[14] Clearances no less than 200mm from the lowest point of the
balcony or overhang.
[15] If a plume management kit is installed within the confines of a
carport or other covered, partially enclosed extension, then the
1) 600mm in case two plume management kits are used on opposing terminals.
Each terminal should use a minimum length of 500mm plume management.
Greenstar 8000 Style – 6720883855 (2019/01)
23
Pre-Installation
exhaust terminal must be positioned at least 1200mm away from any opening into the building which is sited within the footprint of the carport. If the exhaust terminal is extended at least 300mm beyond the footprint of the carport then the distance from the terminal to an opening within the carport can be reduced to 600mm. The exhaust terminal can also be routed though the roof of the carport providing 25mm clearance is provided around the flue pipe to any flammable material and that it extends at least 300mm above the roof. The air intake must have a minimum 150mm clearance to any opening in the building in order to ensure the integrity of the structure is maintained. If the exhaust terminates within the footprint of the carport then the carport must have at least 2 sides completely open. If the exhaust terminates at least 300mm beyond the footprint of the carport then the carport must have at least one completely open side. The exhaust terminal must be positioned to ensure that plume will not cause nuisance or damage to vehicles and that minimum clear distances in front of the terminal will not be impeded by vehicles.
Note:
▶ Installations in car ports are not recommended. ▶ The flue cannot be lower than 1,000mm from the top of a light well
due to the build up of combustion products.
▶ Dimensions from a flue terminal to a fanned air inlet to be determined
by the ventilation equipment manufacturer.
▶ Plume kits running horizontally must have at least a 3° fall back to the
appliance for proper disposal of condensate, except or the initial horizontal run from the terminal. The initial plume kit horizontal run will have at least a 10° fall back to the appliance, due to the terminal elbow design, for proper disposal of the condensate.
4.5 Condensate discharge
Full details on condensate discharge.
▶ Follow the latest version of BS6798 and HHIC guidance.
For correct installation and trouble free operation of the appliance the following advice should be followed:
1. To minimize the risk of freezing, wherever possible: the
condensate drain should be installed internally.
2. All condensate pipe work must ‘fall’ from the appliance by a minimum of 3° (52mm per metre) to ensure adequate condensate flow.
3. The pipe work route must allow air to be supplied back to the appliance for correct operation.
4. Connection to a rainwater down pipe must include an air break.
Also:
• The condensate pipe work connected to the condensate drain outlet on the appliance should have a minimum internal diameter (ID) of 19mm.
• Keep external pipe work as short as possible and do not exceed 3 metres length. Unless there is no means of routing the pipe internally. Further precautions against freezing must be taken if external pipe runs exceed 3m.
• External pipe work should have a minimum internal diameter (ID) of 30mm.
• Minimise the number of bends and connectors.
• Remove burrs after cutting pipe.
• Remove surplus solvent from the interior of the pipe.
• The condensate pipe work shall be run in standard drainpipe material, e.g. poly(vinyl chloride) (PVC), unplasticized (vinyl chloride) (PVC-U), acrylonitrilebutadiene.styrene (ABS), polypropylene (PP) or chlorinated poly(vinyl chloride) (PVC.C).
4.5.1 Appliance siphonic condensate trap
The appliance has a large capacity condensate trap reducing the risk of condensate discharge pipe work freezing up in prolonged cold temperatures.
The expanded siphonic operation discharges every 10 to 20 minutes. Resulting in:
• Increased velocity and flow rate.
• With less frequent siphonic actions per hour, the condensate pipe work is empty for longer.
• Significantly reducing freezing potential for a 48 hour period at ­15 °C, provided the installation parameters listed below are followed.
24
4.5.2 Condensate pipe work
NOTICE:
General consideration
▶ Where a new or replacement appliance is being installed, access to
an internal “gravity discharge” point should be one of the factors considered in determining appliance location.
▶ Condensate pipe connection at the appliance:
The condensate pipe must have a nominally outside diameter of 22mm plastic pipe.
▶ Ensure there are no blockages in the pipe run. ▶ Ensure that the discharge method for the installation can effectively
handle the condensate waste from the appliance.
Greenstar 8000 Style – 6720883855 (2019/01)
Loading...
+ 56 hidden pages