Bosch W-HNR, W-HNW Specsheet

Fire Alarm Systems | W‑HN Wall‑mount Horns
W‑HN Wall‑mount Horns
www.boschsecurity.com
u Sleek modern aesthetics
u Multiple voltages (12 VDC or 24 VDC)
u Voltage test points
The Cooper Wheelock Exceder Series Horns feature a sleek modern design that incorporates high reliability to minimize current draw. The reduced current draw allows for a greater number of devices on the two‑wire notification appliance circuit. This, in combination with no tools needed for changing settings, voltage test points, 12 V or 24 V DC operation, the universal mounting base, and multiple mounting options results in a reduced cost of ownership. These horns provide three sound settings on each appliance. All the switches to change these settings can be set without a tool and are located behind the appliance to prevent tampering. The separate universal mounting base can be easily mounted to five industry‑standard back box types. They can also be pre‑wired to allow full testing of the circuit wiring before the appliance is installed and the surface finished. These wall‑mounting horns also feature voltage test points for taking readings with a volt meter for troubleshooting or AHJ inspection.
Certifications and approvals
Cooper Wheelock holds these Listings and Approvals:
u Universal mounting base
Region
Certification
USA UL ULSZ: Audible-signal Appliances
(ANSI/UL 464)
CSFM see our website
Canada ULC ULSZC: Audible Signal Appliances and
Accessories, Fire Alarm (CAN/ULC­S525, ULC-S527)
Installation/configuration notes
Compatibility
Horn: These horns provide a selectable Continuous or Code 3 horn tone when connected directly to the Fire Alarm Control Panel (FACP). They can also provide a synchronized Code 3 Horn tone when used in conjunction with an FACP that incorporates the Cooper Notification sync protocol, a Cooper Notification Sync Module, or the Cooper Notification Power Supply. The Horn Appliances can be field set for High (HI), Medium (MED), or Low (LO) dBA sound output. Compatible Products
2 | W‑HN Wall‑mount Horns
The following Bosch Security Systems, Inc. products are compatible with the Cooper Wheelock Exceder Series Horns:
Category Product ID Product Description
Control Panels FPA-1000
1
Analog Addressable Fire Panels
FPD-7024
1
Conventional or Addressable2 FACP
D10024A
D8024
D9124
D7024
3
3
3
3
Analog FACP
Analog FACP
Addressable FACP
Conventional or Addressable2 FACP
D7022
3
Conventional FACP
Modules SM‑12/24‑R Synchronization module
(red)
DSM‑12/24‑R Dual synchronization
module (red)
Power Supplies FPP-RNAC-8A-4C
1
Remote Notification Appliance Circuit (RNAC) Power Supply
PS‑24‑8MC
1
Power supply with built-in synchronization protocol
1
These products have built‑in Cooper Notification
synch protocol.
2
When used with a D7039 Multiplex Expansion Module, the FPD‑7024 and the D7024 become addressable FACPs.
3
For synchronization, use the SM or DSM modules with these control panels.
Mounting Considerations
The Universal Mounting Base supplied with each horn can be pre-wired. With the supplied Contact Cover in place, the pre‑wired circuit can be checked for continuity before the horns are mounted. The horns snap onto the pre-installed Universal Mounting Bases with the Contact Covers removed and can be secured to the base with an optional securing screw. The Universal Mounting Base flush mounts on single-gang, double-gang, 4 in. square, 4 in. octal, 3.5 in. octal, and 100 mm European-type back boxes.
Wiring Considerations
The wiring terminals on the Universal Mounting Base accept two appliance wires with diameters between 12 AWG and 18 AWG (ISO 4 mm2 and 0.75 mm2) at each terminal.
Parts included
1 Contact cover
1 Hardware pack
• Two pan head mounting screws
• One securing screw
1 Literature – Installation Instructions
Technical specifications
Electrical
Volume Setting
3
8.0 V to 17.5 V 16.0 V to 33.0 V
Horn Current Draw
Voltage Type
DC: High: 47 mA 64 mA
Medium: 26 mA 44 mA
Low: 17 mA 22 ma
FWR: High: 73 mA 86 mA
Medium: 48 mA 74 mA
Low: 36 mA 54 mA
Voltage (input)
Regulated Range
12 VDC 8.0 V to 17.5 V
24 VDC or Vrms 16.0 V to 33.0 V
3
Current Draw is the same for the Continuous Horn
and Code 3 Horn Settings.
Environmental
Environment: Indoor, dry
Relative Humidity: 93±2% maximum, non‑condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical
Dimensions: 5.24 in. x 4.58 in. x 1.6 in.
(133.1 mm x 116.4 mm x 40.7 mm)
Material: Molded plastic enclosure
Volume Settings: 90 db, 95 db, or 99 db
Audible Patterns and Ratings
Pattern Volume
Sound Output
1
Setting
8.0 V 12.0 V 17.5 V
Continuous: High: 83 dBa 88 dBa 91 dBa
Medium:79 dBa 82 dBa 86 dBa
Quant. Component
1 Horn appliance
1 Universal mounting base
Low: 72 dBa 76 dBa 79 dBa
Code 32: High: 80 dBa 84 dBa 86 dBa
3 | W‑HN Wall‑mount Horns
Medium 74 dBa 78 dBa 82 dBa
Low: 68 dBa 72 dBa 76 dBa
16.0 V 24.0 V 30.0 V
Continuous: High: 91 dBa 93 dBa 96 dBa
Medium:86 dBa 89 dBa 92 dBa
Low: 78 dBa 82 dBa 85 dBa
Code 32: High: 86 dBa 89 dBa 91 dBa
Medium 81 dBa 85 dBa 84 dBa
Low: 74 dBa 78 dBa 80 dBa
1
Sound output is a minimum UL rating based on sound power measurements at a distance of 10 ft (3 m) in a reverberant test room per UL464.
2
The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 second off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling.
Notice
The Code 3 temporal pattern should be used only for fire evacuation signaling and not for any other purpose.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
W‑HNR Wall‑mount Horn (two‑wire, 12/24 V, red)
Rectangular red two‑wire horn field‑selectable for three volume options.
Order number W-HNR
W‑HNW Wall‑mount Horn (two‑wire, 12/24 V, white)
Rectangular white two‑wire horn field‑selectable for three volume options.
Order number W-HNW
Accessories
DSM‑12/24‑R Dual Synchronization Module (red)
A 12/24 VDC Cooper Wheelock module that synchronizes notification appliances on a single Class A or two Class B circuits.
Order number DSM‑12/24‑R
SM‑12/24‑R Single Synchronization Module (red)
A 12/24 VDC Cooper Wheelock module that synchronizes notification appliances on Class B alarm circuits. Not Available.
Order number SM‑12/24‑R
4 | W‑HN Wall‑mount Horns
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2713564427 | en, V2, 20. Aug 2014