Bosch W 325 K..T1, W 400 K..T2 User Manual

Instantaneous gas water heater
Models
W 325 K..T1 W 400 K..T2
· Installation
· Operation
· Maintenance
The Bosch instantaneous water heater is a high efficiency, space saving answer to your water heating needs. All Bosch instantaneous water heaters heat water only as required; noenergy is lost maintaining a large voluma of water at elevated temperatures as in tanktype storage water heaters. Suitable for heating potable water. Certified for space heating in combination with potable water only. Not certified for heating only.
READ INSTRUCTIONS CAREFULLY BEFORE INSTALLING
NOTICE TO INSTALLER: Please leave this manual
with the owner or affix adjacent to appliance.
ASTRAVAN DISTRIBUTORS, LTD.
123 Charles Street
6 720 601 783 CA (03.11) AL
North Vancouver, B.C. V7H 1S1
Phone Canada: (604) 929-5488 Phone USA: (206) 860-8448 Web Site: www.astravan.com
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
−−
Do not store or use gasoline or other flammable
−−
vapors and liquids in the vicinity of this or any other appliance.
−−
WHAT TO DO IF YOU SMELL GAS
−−
••
Do not try to light any appliance.
••
••
Do not touch any electrical switch; do not use
••
any phone in your building.
••
Immediately call your gas supplier from a
••
neighbor’s phone. Follow the gas supplier’s instructions.
••
If you cannot reach your gas supplier, call the
••
fire department.
−−
Installation and service must be performed by a
−−
qualified installer agency or the gas supplier.
Note: In case of problems please contact your salesman or installer
DIMENSIONS
Figure 1
Maximum hydrostatic water pressure – 1.03 Mpa (150 p.s.i.) Maximum recommend working pressure – 0.69 Mpa (100 p.s.i.) Minimum working pressure – 0.0138 Mpa (2 p.s.i.) at 2 Litres/min. (0.5 U.S. Gallons/min) free discharge Minimum recommended inlet water pressure for use with showers 30 p.s.i.g.
Dimensions in Milimetres (inches)
Model A B C D E F G H
W325
W400
Model Type of gas Altitude Input
W325
W325
W400
W400
400 755 250 155 85 130 410 320
17 1/4" 29 3/4" 9 3/4" 6" 3 1/4" 5" 16 1/8" 12 5/8"
440 770 250 155 85 130 410 320
17 1/4" 30 1/4" 9 3/4" 6" 3 1/4" 5" 16 1/8" 12 5/8"
Main Burner orifices
Size, mm Qt.
Natural
Propane 0.79 diam. 14
Natural
Propane 0.79 diam. 14
Natural
Propane 0.82 diam. 16
Natural
Propane 0.82 diam. 16
standard 29.30kW (100,000Btu/hr) 1.25 diam. 14
(0 - 2,000 ft.) 27.83 kW (95,000Btu/hr)
high** 26.37kW (90,000Btu/hr) 1.25 diam. 14
(2,000 - 4,500 ft.) 25.05 kW (85,000Btu/hr)
standard 34.28 kW 1.25 diam. 16
(0 - 2,000 ft.) (117,000Btu/hr)
high** 30.85 kW 1.25 diam. 16
(2,000 - 4,500 ft.) ( 105,000Btu/hr)
* The wall bracket is only required for the WR 325 K … when mounted directly to combustible construction. The WR
400 K… T2 may be mounted directly to combustible construction.
** The high altitude ratings listed are Canadian Gas Association high altitude ratings and are only valid in Canada. In the
U.S., the National Fuel Gas Code, ANSI Z223.1/NFPA 54, recommends for high altitude installations above 2,000 feet, that the input rate be reduced 4% for each 1,000 feet above sea level. – See page 8.
2
FORWARD
This design complies with CAN1-4.3-77 and ANS1Z21.10.3b 1994 as an instantaneous gas water heater. In addition the unit complies with CAN1-2.17-M80 for use at high altitude,
2.000-4.500 feet above sea level.
Installation, operation and maintenance information is provided in this manual. Installation and operation instrution should be thoroughly reviewed before proceeding with installation of the BOSCH instantaneous gas water heater.
The BOSCH instantaneous gas water heater is designedto operate on natural or propane gas; however, make sure that gas onwhich heater is to operate is to operate is the same as specified on the heater’s model/rating plate.
In addition to these instructions, the water heater shall be installed in accordance with CAN1-B149 Installation Code (in Canada) or ANSI Z223-1/NFFA 54 National fuel Gas Code (in U.S.) and/or local installation codes. These shall be carefully folowed in all cases.
INSTALLATION INSTRUCTIONS
Note: Proper plumbling, venting, gas connections and an adequate supply of combustion air are required for safe and reliable operatrion. Ability equivalent to that of a licensed tradesman in the field involved is required for installation and/or servicing of these heaters.
AIR REQUIREMENTS
For safe operation ,sufficient air for combustion, ventilation and dilution of flue gases must be available. An insufficient supply of air will result in a yellow luminous burner flame, causing carboning or sooting of the heat exchanger.
LOCATION
Before installation the BOSCH instantaneous gas water heater consideration must be given to proper location. Location should be as close to a chimney or gas vent as practicable, in an area with an adequate air supply and as centralized with the piping system as possible. The heater should not not be located in area where it will be subject to freezing. The heater should be located in an area where leakage of the heater or its connections will not result in damage to the area adjacent to the heater or to lower floors of the structure.
In order to prevent corrosion, make sure that the combustion air kept free of aggressive substances. Subtances that especially contribute to corrosion are halogenated hydrocarbons (e.g. chlorine and fluorine), which are contained in solvents, paint, adhesives, propellant gases, various house hold cleaners, etc. Take precautionary measures as necessary.
If plastic pipes are used , a 1.5 m metal connection must be provided on the cold and hot sides.
Note: When such loctions cannot be avoided, it is
recommended that a suitable drain pan, adequately drained, be installed under the water heater. The pan
must not restrict combustion air flow.
In unconfined spaces, in buildings of normal construction, infiltration normally is adequate to provide air for combustion, ventilation and dilution of flue gases. However, a confined space must be provided with two permanent openings to provide combustion and ventilation air to the appliance. Each opening shall have a free area of one square inch per 1000 BTU/Hr* of total input rating os all appliances in the enlosure.One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
* SPECIAL NOTE
When the W 400 K… T2 is installed in a confined space of minimum size the openings described above must be increased to a size of 1 ½ square inches per 1000 BTU/Hr. In other words, for the W400 K..T2 installed in a minimum sized confined space the two openings that are to be made in the enclosure within 12 inches of the top and 12 inches of the bottom must each have a minimum free area of, (11/ 2”) x (117) = 175.5 square inches.
3
For either confined or unconfined space in a building of tight construction with inadequate infiltration, air must be drawn from the outdoors or from spaces that freely communicate the outdoors. Two permanent openings located as indicated above are to be provided as follows:
1. When communicating with outdoor directly, or by means of vertical ducts, each opening shall have a free area of not less than one square inch per 4000 BTU/Hr of total input of all appliances in the space.
2. When communicating with outdoors by means of horizontal ducts, each opening shall have a free area of not less than one square inch per 2000 BTU/Hr of total input of all appliances in the space.
For detailed reqirements see
- in Canada, CAN 1-B 149 Installation Codes
- in U.S., ANSI Z223.1/NFPA 54 National Fuel Gas Code.
MOUTING
The W 325 K.. and W 400 K.. are design certified for mounting to a wall. A wall bracket, see figure 1 is provided with the W 325 K.. and must be used when the heater mounted on a combustible wall. Heaters may not be installed directly on a carpeted wall.
The heater, or the wall bracket, must be mounted to the wall using appropriate anchoring materials.
WARNING
Failure to use the wall bracket with the W 325 K… when installing the unit on combustible construction will cause an unsafe condition and possible fire. In addition, failure to use the wall bracket when installing the W 325 K… on combustible construction will be in violation of A.G.A. and C.G.A. certification of the unit.
WARNING
1. Flammable materials, gasoline, pressurized containers, or any other items or articles that are potentially fire hazards must never be placed on or adjacant to the heater. The appliance area must be kept free of all combustible materials, gasoline and other flammable vapors and liquids.
2. Do not obstruct the flow of combuston and ventilation air to the appliance.
CLEARENCE
In Canada The W 325 and the W 400 are design certified for installation on a combustible wall (for the W 325 the wall bracket supplied with the unit must be used for mounting to combustible construction), and for installation in an alcove or closet with minimum clearances to 0 mm from back, 102 mm (4 inches) from sides, 305 mm (12 inches) from top and bottom, and 102 mm (4 inches) from front. A minimum of 305 mm (12 inches) shall be allowed for maintenance of serviceable parts. Clearence from vent is dependant upon the clearence rating of the venting material used; that is, type B-1 vent is approved for 1 inch clearence, B-2 vent for 2 inch, etc.
In United States The W 325 and the W 400 are design certified for installation on a combustible wall (for the W 325 the wall bracket supplied with the unit must be used for mounting to combustible construction), and for installation in an alcove with minimum clearences to combustible construction of 0 mm from back, 102 mm (4 inches) from sides, 305 mm (12 inches) from top and bottom. In addition, the WR 325 has also been design certified for closet installation with minimum clearences to combustible construction of 0 mm from back, 102 mm (4 inches ) from sides, 305 mm (12 inches) from top and bottom, and 102 (4 inches) from front. A minimum of 305 mm (12 inches) shall be allowed for maintenance of serviceable parts.Clearence from vent is dependent upon the clearence rating of the venting material used, that is, type B-1 vent is approved for 1 inch clearence, B-2 vent for 2 inch, etc.
Note: If wall is a stud wall sheethed with plasterboard it is
recommended that support board(s), either 1 x 4’s or ½ (minimum) plywood first be attached across a pair of studs and then heater, in the case of the W 400 K…, or the wall bracket, in the case of the W 325 K…, be attached to the support boards. See figure 2.
WALL STUDS
WALL BRACKET
1” X 4” SUPPORT
Figure 2
BOARDS
Expansion and contraction of piping due to changing water temperature in pipes imparts movement to heater which, if mounted directly to a brittle, friable board such as plasterboard can cause failure of mounting.
4
DRIP TRAY
If the water heater is being mounted above a floor of combustible construction, the drip tray ( shipped loose in the water heater) must be attached to the bottom of front cover of the water heater at time of installation. The drip tray should be attached to the front cover, using screws provided, as shown in figure 3. Failure to use drip tray when installing unit above a floor of combustible construction will cause an unsafe condition and possible fire and will be in violation of A.G.A. and C.G.A. sertification of the unit.
DRIP TRAY
For high altitude use the adaptor must be installed as shown in figure 4, without alternation, before connecting the six inch flue to the unit. The adaptor must be secured to the draft diverter outlet with a minimum of two screws. Also, in Canada, the gas pressure regulator supplied with the water heater is factory preset to deliver gas to the water at the proper pressure settting for high altitude operation, see PRESSURE REGULATION section of this manual.
WARNING
Failure to increase vent size on W 400 to six inches and/or to assure that manifold pressure is set to proper value listed on rating plate for applications at altitudes in range 2,000 to 4,500 ft. above sea level will cause unsafe venting, asphyxiation, and voids C.G.A. certification.
WATER CONNECTIONS
The W series instantaneous water heatrs are provided with two S-bend water connectors/adaptors that must be connected to inlet and oulet and outlet connections on water valve assembly, see figure 1 and figure 5 below.
Figure 3
VENTING
The BOSCH instantaneous water heaters have builtin draft diverters and are designed for indoor installation only. The draft diverter outlet must be connected to a clear, unobstructed vent of the same size, or lerger, refer to:
- In Canada, CAN1-B149 Installation Code for detailed requirements.
- In U.S.A., ANSI Z223.1/NFPA 54 – National Fuel Gas Code for detailed requirements.
The flue connection for both the W 325 K… and W 400 K… is 130 mm (5 inches); however, in Canada for installations at high altitude (2,000-4,500 ft. above see level) a six inch (6”) flue is required for the W 400 K.
5” x 6” adaptor used on high altitude model W 400 only
Water valve and S-bends, top view
Figure 5
The purpose of the S-bend water connectors/adaptors is to provide threaded water connections that meet standards used in North America, ANSI Standard Taper Pipe Thread (1/2” NPT). The cold water supply should be connected to S-bend attached to inlet of water valve and hot water connection should be made to S-bend attached to outlet of water valve.
Figure 4
Note: A shut-off valve should be placed in the cold water
supply line to the heater to facilitate servicing the heater.
5
RELIEF VALVE
The listed pressure relief valve supplied must be installed near the hot water outlet at time of installation of the heater. No valve is to be placed between the relief valve and the heater. A line must be connected to the relief valve to direct discharge to a safe location. Do not install reducing coupling or any other restriction in the discharge line must be installed so as to allow complete drainage of the valve and the line. See figure 6.
Figure 6
GAS CONNECTIONS
Before connecting the gas supply to the heater check heater’s model/rating plate to make sure that gas on which heater is to operate is the same as specified on the model/ rating plate.
The W 400 K and the W 325 K instantaneous gas water heaters are supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line, see figure 7. Failure to install the pressure regulator, or the failure to install it in the sequence shown in figure 7 will be of A.G.A. and C.G.A. certification of the unit.
BOSCH water heaters are shipped from the factory with the gas pressure regulators preset for tte gas shown on the rating plate to the correct pressure:
- in Canada, for high altitude operation;
- in U.S., for standard altitude operation unless specially marked as a high altiude unit.
Check to make sure that the gas listed on the rating plate is same as gas listed on the pressure regulator. See PRESSURE REGULATION of this manual for information regarding gas pressure settings.
Note: Before attaching the gas supply line, be sure that all
gas pipe is clean on the inside. To trap any dirt or foreign material in the gas suplly line, a drip leg must be incorporated in the piping. The drip leg must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas supplier.
Joint compounds (pipe dope) shall be applied sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. The joint compound used must be resistant to the action of liquified petroleum gases. Before placing water heater in operation check for gas leakage. Soap and water solution, or other material acceptable for this purpose, shall be used in locating gas leaks. Matches, candles, lighters, or other ignition sources shall not be used for this purpose.
WARNING
The heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressure in excess of 3,45 kPa (1/2 psig).
The water heater must be isolated from the gas supply piping system by closing its individual manuaql shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 3.45 kPa (1/2 psig).
Figure 7
6
PRESSURE TAP
PRESSURE REGULATOR
MANUAL GAS VALVE
The water heater, including the pressure regulator and manual valve provided with it, must not be operated at gas supply pressures in excess of 3.45 kPa (1/2 psig). If overpressure has occurred such as through improper testing of the gas lines or emergency malfunction of the supply, the gas valve and regulator must be checked for safe operation. Make sure that the outside vent valves are protected against blockage. These are part of the gas supply system, not the water heater.Vent blockage may occur during ice storms.
OPERATING INSTRUTIONS
WARNING
If the water has been damaged or exposed to fire or sooting or if any part has been underwater do not use. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater and to clean the heat exchanger assembly and water valve.
FILLING
Before proceeding with operation of the water heater make sure that system is filled with water.
- Make sure drain is closed, see figure 8, below.
- Open a nearby hot water faucet to permit the water to fill the heater and piping.
- Close the hot water faucet after the water flows freely and all air has escaped from system.
- The water heater is now ready to be lit.
Figure 8
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information, first section of the Lighting Instruction Plate on the cover.
2. The main manual gas valve must be closed (turn valve handle clockwise ) and the gas valve OFF button depressed . See figure 9.
3. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information given above on this plate. If you don’t smell gas, go to next step.
4. The pilot burner is located behind the peephole located in the front center of the jacket directlybelow this instrution plate.
5. Open main manual gas valve by turning valve handle counterclockwise .
6. Depress PILOT button and light pilot by pushing PILOT IGNITER button . This may have to be repeated.
7. Observe pilot flame though peephole. The PILOT button
- should be held down at least 10 seconds with pilot burning. When the PILOT button is released the pilot should continue to burn.
- If the PILOT button does not pop up when released stop and immediately call your service technician or gas supplier.
- If the pilot will not stay repeat lighting procedure steps 1 through 8.
- If the pilot will not stay lit after several tries, depress the OFF button , turn the manual gas valve handle clockwise to OFF position and call your service technician or gas supplier.
SERVICE HINT
The strainer (screen) in the water valve, located in the inlet of the water valve, may require occasional cleaning due to foreign material in the water supply. This will restrict the flow of may affect heater operation and prolong filling time. To inspect the strainer close the cold water supply valve ahead of the heater, disconnect S-bend from inlet of water valve, and remove strainer from inlet. Clean if required, replace strainer in inlet to water valve, reconnect S-bend and turn on water supply.
Light the water heater in accordance with the instructions on the Lighting and Operating Plate on the water heater. For your convenience, the instructions are repeated below.
8. Depress the ON button . The heater will now fire when water is drawn at arate greater than the threshold flow rate (see manual)*.
Note: If main burner should fail to ignite make sure pilot is burning. If not repeat lighting procedure steps 1 through 8.
TO TURN OFF GAS TO APPLIANCE
1. Depress OFF buton and close the main gas valve by turning handle clockwise to OFF position. See figure
9.
*see Water Flow Selector section.
7
PRESSURE REGULATION
The pressure regulator supplied with the water heater is adjusted to operate on the gas specified on the rating plate, and:
- in Canada, is factory preset to deliver gas at the high altitude pressure setting listed on the rating plate and as shown below.
- In the U.S., is factory preset to deliver gas at the standard altitude setting listed on the rating plate and as shown below.
The pressure setting of the gas pressure regulator should be checked at installation to assure that the setting is correct for the gas being used and the altitude at which the appliance is installed. See rating plate on the unit, or the chart below for proper settings.
In Canada, for a heater being installed at standard altitude (o-2,000 ft. elevation) the manifold pressure should be reset at installation to value shown on the rating plate, or chart below, for standard altitude.
The gas pressures specified below refer to flow pressure taken at the pressure tap in the gas inlet pipe (just above pressure regulator), figure 9, while the heater is operating at full input.
Appliance Regulator Pressure Setting
Model Type of Gas
W325
W325
W400
W400
natural 1.36 5.5 standard
propane 2.61 10.5 (0-2,000 ft.)
natural 1.09 4.4 high *
propane 2.11 8.5 (2,000 - 4,500 ft.)
natural 1.41 5.7 standard
propane 2.61 10.5 (0-2,000 ft.)
natural 1.14 4.6 high *
propane 2.09 8.4 (2,000 - 4,500 ft.)
*Note: The high altitude ratings listed are Canadian Gas Association high altitude ratings for the appliances and are only valid in Canada. In the U.S. the National Fuel Gas Code, ANSI Z223.1/NFPA 54, recommends for high altitude installations, above 2000 feet, that the input rate be reduced 4% for each 1,000 Feet above sea level.
Pressure
kPa Inches, W.C.
Altitude
TEMPERATURE REGULATION I W325K and W400K Models only
For domestic purposes the water flow selector should be turned clockwise to stop and the gas control slide slid to right hand stop and remain in those positions. See figure 10.
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance and have the heater checked by a qualified serviceman to determine the reason for te malfunction.
GAS CONTROL SLIDE
WATER FLOW SELECTOR KNOB W325K AND W400K ONLY
WATER THROTTLE SCREW
Figure 10
WATER FLOW SELECTION With the water flow selector turned clockwise to the stop, the heater’s water valve will regulate the flow rate through the heater permitting a maximum flow rate of:
- 5.8 L/Min. (1.5 U.S. Gal./min.), for W325
- 6.8 L/Min. (1.8 U.S. Gal./min.), for W400
W400K5 MODEL ONLY
Your appliance dealer and/or your local gas supplier should be consulted in regard to any high altitude installation. If field adjustment is required it should be performed by a qualified serciveman experienced in such work.
PRESSURE TAP
PRESSURE REGULATOR
MANUAL GAS VALVE IN OFF POSITION
Figure 9
8
This setting permits a person at a remote location to control the water temperature by mixing more or less cold water with the hot water supplied by the heater.
The water flow selector regulates the hot water output by
1
(
adjustng the flow rate of the water through the heater. Below you will find listed the maximum that can be selected by adjusting the water flow selector and the minimum flow rate for main burner operation. Also listed are the temperature rises that would be expected, at flow rates indicated, when the heater is firing at full input.
WATER FLOW ADJUSTMENT RATE ALL
MODELS
Model
W 325
W 400
Maximum Flow Rate
(counter-clockwise to stop)
3 L/min.
3.4 U.S. Gal./min.) Temp. Rise 25° C (45° F)
15 L/m in. (4.0
U.S. Gal./min.) Temp.
Rise 25° C (45° F)
Minimum Flow Rate
(clockwise to stop)
5.8 L/min. (1.5 U.S. Gal./min.) Temp.
Rise 55° C (100° F)
6.8 L/min. (1.8
U.S. Gal./min.) Temp.
Rise 55° C (100° F)
*Note: If flow rate through the heater is less than the minimum flow rate shown for the heater the main burner will not fire. The minimum flow rate is the “THERSHOLD FLOW RATE” referred to in the lighting instructions.
II W400 K5 Models only
These models do not have a manual flow selector knob. Flow can be regulated using the water throttle screw on the bottom of the water control valve (see fig.8). Because this model is usually always used for full flow applications such as recirculation to storage, pressure washers, boosters, etc., this water throttle screw somes from the factory srewed in (clockwise) to maximum flow position to give flows and temperature indicated above.
GAS CONTROL SLIDE
With the gas control slide at the right hand stop the heater will fire at its full rated input when water is drawn at a rate that will cause the gas valve to open fully. The gas control slide will restrict the input down to approximately 50% of full rated input when adjusted to the left hand stop.
HIGH TEMPERATURE LIMIT SWITCH
The BOSCH W series instantaneous gas water heaters are equipped with a high temperature switch with a set point
of approx. 90° C ( 194° F). If the water temperature at the point exceeds the set point the switch will open, interrupting the safety circuit and stopping gas flow to the pilot and main burner.
Outage as a result of high limit operation indicates that the heater is not functioning properly. The heater should be checked by a qualifed serviceman and reason for malfunction corrected. To relight pilot follow instructions provided on unit.
9
Loading...
+ 19 hidden pages