Bosch SS-SW, SS-SCWH, SS-SR, SS-SCRH, SS-SCW Specsheet

...
Fire Alarm Systems | SS‑S Two‑wire Indoor Strobes
SS‑S Two‑wire Indoor Strobes
www.boschsecurity.com
u Plug‑in design with tamper-resistant construction
u Field‑selectable standard candela (15 cd, 15/75 cd,
30 cd, 75 cd, 95 cd, 110 cd, or 115 cd) settings or high candela settings (135 cd, 150 cd, 177 cd, or 185 cd)
The SS‑S System Sensor SpectrAlert Advance notification appliances simplify installations with features such as plug‑in designs, instant feedback messages to ensure correct installation of individual devices, and field‑selectable candela settings. While there are products specifically designed for use on the ceiling or the wall, these products are listed to be used in either application, and the same mounting plate is used for wall- and ceiling‑mount units. SpectrAlert products can be used in either DC or full‑wave rectified (FWR) systems (12 V or 24 V). If required, the SSMDL or SSMDLW module can be used to provide synchronization.
Notice
Full‑wave Rectified (FWR) voltage is a non‑regulated, time‑varying power source that is used on some power supply and panel outputs.
u Shorting spring on mounting plate for continuity
check before installation
u Wall or ceiling mount models
Notice
SpectrAlert products set at 15 cd and 15/75 cd automatically work on either 12 V or 24 V power supplies. The products are not listed for 12 V operating voltages when set to any other candela settings.
Functions
Strobe
When wired as a primary‑signaling notification appliance, the strobe complies with the Americans with Disabilities Act (ADA) requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light consists of a xenon flash tube and associated lens and reflector system. For 24 V applications, the total number of strobes on a single NAC must not exceed 40, with a maximum loop resistance of 120 Ω. For 12 V applications, the total number of strobes must not exceed 12, with a maximum loop resistance of 30 Ω.
Certifications and approvals
System Sensor holds these Listings and Approvals:
2 | SS‑S Two‑wire Indoor Strobes
Region Certification
USA UL UUKC: Signaling Appliances and Equip-
ment for the Hearing Impaired (UL1971)
FM SS-S Family
CSFM see our website
Installation/configuration notes
Mounting Considerations
These strobes mount on a standard 4‑inch square back box, a 4‑inch octagon back box, a single‑gang back box, or a double‑gang back box.
Wiring Considerations
The input terminals on the universal mounting plate accept solid wires between 12 AWG (2.3 mm) to 18 AWG (1.2 mm).
Parts included
Quant. Component
1 Strobe
1 Universal mounting plate (MP120K)
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Current Draw, UL maximum at 8 V to 17.5 V
Standard‑candela Models only
DC FWR
15 cd: 123 mA 128 mA RMS
15/75 cd: 142 mA 148 mA RMS
Current Draw, UL maximum at 16 V to 33 V
Standard‑candela Models
DC FWR
15 cd: 66 mA 71 mA RMS
15/75 cd: 77 mA 81 mA RMS
30 cd: 94 mA 96 mA RMS
75 cd: 158 mA 153 mA RMS
95 cd: 181 mA 176 mA RMS
110 cd: 202 mA 195 mA RMS
115 cd: 210 mA 205 mA RMS
135 cd: 228 mA 207 mA RMS
150 cd: 246 mA 220 mA RMS
177 cd: 281 mA 251 mA RMS
185 cd: 286 mA 258 mA RMS
Voltage
Nominal: Regulated 12 VDC/FWR or
Operating Range: 12V nominal: 8 V to 17.5 V or
Regulated 24 VDC/FWR
24 V nominal: 16 V to 33 V
Environmental
Relative Humidity: 10% to 93%, non‑condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical
Candela Selections: 15 cd1, 15/75 cd1, 30 cd2, 75 cd2,
Dimensions
• Ceiling‑mount (Diameter x Height):
• Wall‑mount (Height x Width x Depth):
1
When set at these settings, the devices automatically
95 cd2, 110 cd2, and 115 cd
6.8 in × 2.5 in (173 mm × 64 mm)
5.6 in × 4.7 in × 2.5 in (142 mm × 119 mm × 64 mm)
2
work on both 12 V and 24 V power supplies. The 15/75 cd selection is listed at 15 cd but provides 75 cd on axis.
2
The strobe is not listed for 12 V operating voltages when set to these selections. When using a 12 V control panel, this device yields required light output only in the 15 cd and 15/75 cd settings.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
SS‑SR Wall‑mount, Standard‑candela Strobe (red)
Red, wall‑mount strobe with field‑selectable strobe intensities of 15 cd, 15/75 cd, 30 cd, 75 cd, 95 cd, 110 cd, or 115 cd
Order number SS-SR
SS‑SW Wall‑mount, Standard‑candela Strobe (white)
White, wall‑mount strobe with field‑selectable strobe intensities of 15 cd, 15/75 cd, 30 cd, 75 cd, 95 cd, 110 cd, or 115 cd
Order number SS-SW
Current Draw, UL maximum at 16 V to 33 V
High‑candela Models
DC FWR
3 | SS‑S Two‑wire Indoor Strobes
SS‑SCR Ceiling‑mount, Standard‑candela Strobe (red)
Red, ceiling‑mount strobe with field‑selectable strobe intensities of 15 cd, 15/75 cd, 30 cd, 75 cd, 95 cd, 110 cd, or 115 cd
Order number SS-SCR
SS‑SCW Ceiling‑mount, Standard‑candela Strobe (white)
White, ceiling‑mount strobe with field‑selectable strobe intensities of 15 cd, 15/75 cd, 30 cd, 75 cd, 95 cd, 110 cd, or 115 cd
Order number SS-SCW
SS‑SCRH Ceiling‑mount, High‑candela Strobe (red)
Red, ceiling‑mount strobe with field‑selectable strobe intensities of 135 cd, 150 cd, 177 cd, or 185 cd
Order number SS-SCRH
SS‑SCWH Ceiling‑mount, High‑candela Strobe (white)
White, ceiling‑mount strobe with field‑selectable strobe intensities of 135 cd, 150 cd, 177 cd, or 185 cd
Order number SS-SCWH
Accessories
SS‑BBS‑2 Wall Back Box Skirt (red)
Red back box skirt. Not Available.
Order number SS-BBS-2
SS‑BBSW‑2 Wall Back Box Skirt (white)
White back box skirt
Order number SS-BBSW-2
SS‑BBSC‑2 Ceiling Back Box Skirt (red)
Red back box skirt. Not Available.
Order number SS-BBSC-2
SS‑BBSCW‑2 Ceiling Back Box Skirt (white)
White back box skirt. Not Available.
Order number SS-BBSCW-2
SSMDL Synchronization Module (red)
Red, 24VDC device that can connect to two Style Y (Class B) circuits or one Style Z (Class A) circuit and synchronize System Sensor SpectrAlert horns, strobes, and horn strobes. Not Available.
Order number SSMDL
SSMDLW Synchronization Module (white)
White, 24VDC device that can connect to two Style Y (Class B) circuits or one Style Z (Class A) circuit and synchronize System Sensor SpectrAlert horns, strobes, and horn strobes. Not Available.
Order number SSMDLW
4 | SS‑S Two‑wire Indoor Strobes
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2722462987 | en, V2, 02. Sep 2014
Loading...