Bosch SS-SRK Specsheet

Fire Alarm Systems | SS‑SRK Two‑wire, Wall‑mount Outdoor Strobe (red)
SS‑SRK Two‑wire, Wall‑mount Outdoor Strobe (red)
www.boschsecurity.com
u Plug‑in design with tamper-resistant, rainproof
(NEMA 3R) construction
The SS‑SRK Strobe, one of the System Sensor SpectrAlert Advance notification appliances, simplifies installations with features such as plug‑in designs, instant feedback messages to ensure correct installation of individual devices, and field‑selectable candela settings. This strobe is designed for outdoor wall‑mounted applications. SpectrAlert products can be used in either DC or full‑wave rectified (FWR) systems (12 V or 24 V). If required, the SSMDL module can be used to provide synchronization.
Notice
Full‑wave Rectified (FWR) voltage is a non‑regulated, time‑varying power source that is used on some power supply and panel outputs.
75 cd, 95 cd, 110 cd, and 115 cd
u Shorting spring on mounting plate for continuity
check before installation
u Outdoor wall mounting
Notice
SpectrAlert products set at 15 cd and 15/75 cd automatically work on either 12 V or 24 V power supplies. The products are not listed for 12 V operating voltages when set to any other candela settings.
Functions
Strobe
When wired as a primary‑signaling notification appliance, the strobe complies with the Americans with Disabilities Act (ADA) requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light consists of a xenon flash tube and associated lens and reflector system. For 24 V applications, the total number of strobes on a single NAC must not exceed 40, with a maximum loop resistance of 120 Ω. For 12 V applications, the total number of strobes must not exceed 12, with a maximum loop resistance of 30 Ω.
2 | SS‑SRK Two‑wire, Wall‑mount Outdoor Strobe (red)
Certifications and approvals
System Sensor holds these Listings and Approvals:
Region Certification
USA UL UVAV: Visual Signal Appliances for Fire
Protective Signaling Systems (UL1638)
FM SS-SRK
CSFM see our website
Installation/configuration notes
Mounting Considerations
Notice
These strobes are for wall mounting only!
For outdoor use, these strobes wall mount on the supplied outdoor back box.
Wiring Considerations
The input terminals on the universal mounting plate accept solid wires between 12 AWG and 18 AWG (ISO 4 mm2 and 0.75 mm2).
Parts included
Quant. Component
1 Strobe
1 Universal mounting plate (MP120K)
1 Outdoor back box (SA-WBB)
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Current Draw, UL maximum at 8 V to 17.5 V
DC FWR
15 cd: 123 mA 128 mA RMS
15/75 cd: 142 mA 148 mA RMS
Current Draw, UL maximum at 16 V to 33 V
Voltage
Nominal: Regulated 12 VDC/FWR or
Operating Range: 12V nominal: 8 V to 17.5 V or
Regulated 24 VDC/FWR
24 V nominal: 16 V to 33 V
Environmental
Temperature (operating): -40°F to +151°F (-40°C to +66°C)
Mechanical
Candela Selections: 15 cd1, 15/75 cd1, 30 cd2, 75 cd2,
Dimensions (Height x Width x Depth):
1
When set at these settings, the devices automatically
95 cd2, 110 cd2, and 115 cd
5.6 in × 4.7 in × 2.5 in (142 mm × 119 mm × 64 mm)
2
work on both 12 V and 24 V power supplies. The 15/75 cd selection is listed at 15 cd but provides 75 cd on axis.
2
The strobe is not listed for 12 V operating voltages when set to these selections. When using a 12 V control panel, this device yields required light output only in the 15 cd and 15/75 cd settings.
Strobe Output (cd)
Listed Candela Candela rating at -40°F (-40°C)
15 cd Do not use below +32°F (0°C)
15/75 cd Do not use below +32°F (0°C)
30 cd Do not use below +32°F (0°C)
75 cd 44 cd
95 cd 70 cd
110 cd 110 cd
115 cd 115 cd
1
When these strobes are used at low temperatures,
1
listed candela ratings must be reduced in accordance with this table.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
DC FWR
15 cd: 66 mA 71 mA RMS
15/75 cd: 77 mA 81 mA RMS
30 cd: 94 mA 96 mA RMS
75 cd: 158 mA 153 mA RMS
95 cd: 181 mA 176 mA RMS
110 cd: 202 mA 195 mA RMS
115 cd: 210 mA 205 mA RMS
Ordering information
SS‑SRK Two‑wire, Wall‑mount Outdoor Strobe (red)
Designed for outdoor wall‑mounted applications
Order number SS-SRK
Loading...