Bosch Residential Geothermal Heat Pump, SM, SM 48, CDI User Manual

CDI series
Engineering
Model SM Residential Geothermal Heat Pump
Overview and Certifi cations
Submittal
Sheet
Standard Features, Factory Installed Options, and Field Installed Accessories
Standard Features
White Pre-Painted Sheet Metal Cabinets
No visible screws — Appliance White for a Clean - Durable Look — Door Handles - for Easy Removal for Service — LCD Display - for Easy View of Unit Operation
High Efficiency
Up to 32.0 EER @ PL GLHP — Up to 22.0 EER @ FL GLHP — Compliant with Energy Start Tier 3
Electronically Communicated Motors
Your choice of Variable Speed ECM or Fix-Torque ECM — Constant Torque High Efficiency ECM — Constant CFM Variable Speed High Effi cient ECM
Field Configurable
Supply Air Connection - Top, Side, and Back (Kit required) — Return Air Connection - Right or Left Side — Electrical Control Box Relocation — Patent: Blower Configurability — Can Also Order Right Hand Or Left Hand Return From
Factory
Closed Cell (Fiber Free) Insulation
Less than 2% Air Leakage Rate
1 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Improved Indoor Air Quality — Sound Ratings as Low as 52 DBA — Patent: Floating Base Pan
Reliability - Durability - Serviceability
Tin Plated Evaporator Coil — Alert Communicating Circuit Board
Electronic Circuit Board
LCD Display - for Easy View of Unit Operation — Low Pressure Switch Protection — High Pressure Switch Protection — Alarm Output — Condensate overflow protection — Anti-Short Cycling — 5 minute Delay — Low Pressure Bypass at Start Up — Random Start of Unit — Brown Out Protection — Evaporator Freeze Protection — Water Coil/Coaxial Coil/Condenser Freeze
Protection
Standard Warranty
10 Year All Parts Limited Warranty — 10 Year Labor Limited Warranty
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
Standard Features, Factory Installed Options, and Field Installed Accessories continued..
Engineering Submittal Sheet
Factory Installed Options
Cupro-nickel Coil:
Recommended in conditions anticipating moderate
scale formation or in brackish water.
Internal Electric Heat:
Can be factory mounted or field installed. Choices
include 5, 10, 15, or 20 kilowatt back up or an emergency heater depending on the size of the
geothermal heat pump.
Domestic Hot Water Heat Recovery Package:
Used to heat domestic hot water using the wasted heat
from the hot compressed gas of the compressor.
Dehumidification:
Lower the humidity in your home allowing you to turn
up the thermostat in the summer.
SmartStart:
A factory installed start up device that improved start
up effieciency as much as 65% and helps reduce wear and tear on the compressor during start up.
Field Installed Accessories
Thermostats:
Bosch thermostats are fully customized to meet your
individual needs. True Communicating thermostat that displays the alert messages without having to go to the unit.
DDC Control:
Field Conversion Kit
2 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
Model Nomenclature
SM 48 - 1 VT C - F L T T T A - X H G X X X X X D 7 X X X X 5
1-2 3-5 6 7 8-9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Engineering Submittal Sheet
MODEL:
SM
NOMINAL CAPACITY: 024
036
048
060
070
ELECTRICAL CONFIGURATION:
1
- 208-230/1/60
CABINET CONFIGURATION:
- Vertical
VT
- Horizontal
HZ
- Counterflow
CF
COAX OPTIONS:
C
- Copper
N
- Cupro-nickel*
*Only coils are cupro-nickel.
WATER CONNECTIONs:
F
- Front (HZ Only)
S
- Side
RETURN AIR CONFIGURATION:
- Left
L
- Right
R
DISCHARGE AIR LOCATION:
T
- Top (VT only)
E
- End Blow (HZ only)
B
- Bottom (CF only)
AIR FILTRATION:
5
- MERV13 - 2" w/ 4-Side Filter Rack
OPEN:
X
- None
ECONOMIZER:
- None
X
WATER FLOW CONTROL OPTIONS:
X
- None
CONTROLS:
- Standard
X
TRANSFORMER:
- 75VA
7
REFRIGERATION:
X
- None
H
- Hot Gas Reheat On/O
1
- Heat Recovery Package
ELECTRICAL OPTIONS:
A
- EMS Relay
E
- Pump/valve Relay
H
- Flow Proving Switch
N
- Comfort Alert Module
S
- Start Assist
X
- As default for non-used electrical codes
APPLICATION:
G
- EXTENDED RANGE (Geothermal)
FAN/MOTOR OPTION:
A
- Constant CFM Motor
T
- Constant Torque Motor
AIR COIL:
- Tinned
T
REVISION LEVEL:
- Rev A
A
3 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
CABINET CONSTRUCTION:
H
- Painted Steel / 1/2" Closed Cell Foam
ELECTRIC HEAT:
- None
X
- 5 kW
A
- 10 kW
C
- 15 kW
D
- 20 kW
E
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
Engineering Submittal Sheet
SM Series
Residential Geothermal Heat Pumps
Physical Data
Description Unit
Compressor Type (Qty 1) Scroll Scroll Scroll Scroll Scroll
Refrigeration Charge VT/HZ Oz. 58/58 98/85 88/77 110/100 114/114
Max Water Working Pressure PSIG/kPa 450/3100 450/3100 450/3100 450/3100 450/3100
Constant Torque High Effi ciency Motor
Fan Motor Type/Speeds
Fan Motor HP 0.33 0.75 0.75 1.00 1.00
Blower Wheel Size
Variable Speed Constant CFM High Effi ciency Motor
Fan Motor Type/Speeds
Fan Motor HP 0.33 0.75 0.75 1.00 1.00
Blower Wheel Size
Water Connection Size
FPT Swivel Connection Inch 1.0 1.0 1.0 1.0 1.0
Coaxial Coil Volume Gal 0.33 1.18 0.62 1.07 1.12
Condensate Connection Inch FPT
Vertical Cabinet
Air Coil Dimensions (H x W)
Nominal size of Standard Filter - 2" MERV13
Weight - Operating lbs 250 360 340 410 440
Weight - Shipping lbs 350 475 450 530 560
Horizontal Cabinet
Air Coil Dimensions
Nominal size of Standard Filter - 2" MERV13
Weight - Operating (lbs) lbs 260 375 355 430 460
Weight - Shipping (lbs) lbs
Inch
(Dia. x W)
Inch
(Dia. x W)
Inch
(H x W)
Inch
(L x H)
Inch
(H x W)
Inch
(L x H)
SM024 SM036 SM048 SM060 SM070
Const Torque
Motor / 5 speed
10 X 8 11 X 9 11 X 9 11 X 11 11 X 11
Variable Speed
Const CFM
10 X 8 11 X 9 11 X 9 11 X 11 11 X 11
Const Torque
Motor / 5 speed
Variable Speed
Const CFM
¾¾¾¾¾
24 X 20 32 X 26 32 X 26 38 X 26 38 x 26
24 X 24 (1) 16 X 30 (2) 16 X 30 (2) 20 X 30 (2) 20 X 30 (2)
18 X 31.5 20 X 42 20 X 42 20 X 49 20 X 49
18 X 18 (2) 20 X 24 (2) 20 X 24 (2) 18 X 20 (3) 18 X 20 (3)
360 495 470 550 580
Value
Const Torque
Motor / 5 speed
Variable Speed
Const CFM
Const Torque
Motor / 5 speed
Variable Speed
Const CFM
Const Torque
Motor / 5 speed
Variable Speed
Const CFM
4 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
Engineering Submittal Sheet
SM Series
Residential Geothermal Heat Pumps
Full Load - ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Models
Models Load
SM024 25500 17.4 29200 5.6 29000 26.5 23500 4.9 26600 19.9 18000 4.1
Full 25500 17.4 29200 5.6 29000 26.5 23500 4.9 26600 19.9 18000 4.1
SM036 39600 19.3 42800 5.6 44000 28.3 35900 5.1 41400 22.3 28400 4.3
SM024
SM036
SM048
SM060
SM070
Partial 18500 18.9 21200 6.5 21700 33.6 16700 5.1 21000 28.1 14400 4.4
SM048 49200 16.6 56100 5.3 55300 25.3 46300 4.7 51300 19.3 36900 4.0
Full 39000 19.0 42800 5.6 43300 28.0 35900 5.1 40800 22.0 28400 4.3
SM060 63800 17.0 73300 5.2 70200 24.4 60300 4.6 65100 18.9 48000 3.9
Partial 29000 22.2 31000 6.5 32600 37.0 25200 5.2 31900 32.0 22400 4.7
SM070 71600 16.3 84000 5.1 78700 23.1 70000 4.5 73700 18.5 55300 3.8
Full 49200 16.6 56100 5.3 55300 25.3 46300 4.7 51300 19.3 36900 4.0
Partial 36700 18.9 40900 6.2 42000 33.8 33700 5.2 39900 27.8 29800 4.5
Full 63800 17.0 73300 5.2 70200 24.4 60300 4.6 65100 18.9 48000 3.9
Partial 47500 18.7 53600 5.8 53300 31.2 44300 4.8 51600 26.5 39800 4.4
Full 71600 16.3 84000 5.1 78700 23.1 70000 4.5 73700 18.5 55300 3.8
Partial 55200 17.8 64900 5.7 60800 28.5 52900 4.8 60300 25.4 46900 4.3
Cooling 86 deg.F Heating 68 deg.F Cooling 59 deg.F Heating 50 deg.F Cooling 77 deg.F Heating 32 deg.F
Cooling 86 deg.F Heating 68 deg.F Cooling 59 deg.F Heating 50 deg.F
Capacity
Btuh
Capacity
Btuh
EER
Btuh/W
EER
Btuh/W
Capacity
Btuh
Capacity
Btuh
COP
COP
Capacity
Btuh
Capacity
Btuh
EER
Btuh/W
EER
Btuh/W
Capacity
Btuh
Capacity
Btuh
COP
COP
Cooling
Full Load 77 °F
Capacity
Part Load 68 °F
Btuh
Capacity
Btuh
EER
Btuh/W
EER
Btuh/W
Capacity
Part Load 68 °F
Btuh
Capacity
Btuh
Heating
Full Load 32 °F
COP
COP
Electrical Data
Models
SM024 1 208-230/1/60 197/253 1 11.7 58.3 2.8 17.4 25 2.8 17.4 25
SM036 1 208-230/1/60 197/253 1 15.3 83.0 6.0 25.1 40 6.8 25.9 40
SM048 1 208-230/1/60 197/253 1 21.2 104.0 6.0 32.4 50 6.8 33.2 50
SM060 1 208-230/1/60 197/253 1 27.1 152.9 7.6 41.5 60 9.1 43.0 70
SM070 1 208-230/1/60 197/253 1 29.7 179.2 7.6 44.7 70 9.1 46.2 70
Voltage
Code
Voltage/Phase/HzVoltage
Min/Max
Compressor
QTY RLA LRA FLA
Total Unit Constant Torque High
Effi ciency Motor
Min Circuit
Amps
Max Fuse/
HACR
Total Unit Variable Speed Constant
CFM High Effi ciency Motor
Min Circuit
FLA
Amps
Units with Factory Installed Electric Heat option
will have two separate data plates for each electrical circuit.
1st Data plate for units with EH option - compressor power connection
Models Voltage Code
SM024 1 208-230/1/60 197/253 1 11.7 58.3 14.6 25
SM036 1 208-230/1/60 197/253 1 15.3 83.0 19.1 30
SM048 1 208-230/1/60 197/253 1 21.2 104.0 26.5 45
SM060 1 208-230/1/60 197/253 1 27.1 152.9 33.9 60
SM070 1 208-230/1/60 197/253 1 29.7 179.2 37.1 60
Voltage/Phase/HzVoltage Min/
Max
QTY RLA LRA
Compressor
Min Circuit
Amps
Bosch Thermotechnology Corp.
5 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
Max Fuse/
HACR
Max Fuse/
HACR
Engineering Submittal Sheet
SM Series
Residential Geothermal Heat Pumps
2nd data plate for units with EH option - Constant Torque ECM motor
Model
SM024 4.8 1 4,800 3,600 20.0 17.3 2.8 - 28.5 25.1 30 30
SM036 4.8 1 4,800 3,600 20.0 17.3 6.0 - 32.5 29.1 35 30
SM036 9.6 1 9,600 7,200 40.0 34.6 6.0 - 57.5 50.8 60 60
SM048 4.8 1 4,800 3,600 20.0 17.3 6.0 - 32.5 29.1 35 30
SM048 9.6 1 9,600 7,200 40.0 34.6 6.0 - 57.5 50.8 60 60
SM048 14.4 2 14,400 10,800 60 51.9 6
SM060 4.8 1 4,800 3,600 20.0 17.3 7.6 - 34.5 31.1 35 35
SM060 9.6 1 9,600 7,200 40.0 34.6 7.6 - 59.5 52.8 60 60
SM060 14.4 2 14,400 10,800 60 51.9 7.6
SM060 19.2 2 19,200 14,000 80 69.2 7.6
SM070 4.8 1 4,800 3,600 20.0 17.3 7.6 - 34.5 31.1 35 35
SM070 9.6 1 9,600 7,200 40.0 34.6 7.6 - 59.5 52.8 60 60
SM070 14.4 2 14,400 10,800 60 51.9 7.6
SM070 19.2 2 19,200 14,000 80 69.2 7.6
Electric
Heater Rated kWStage
Heater
Watts
240V 208V 240V 208V Fuses 240V 208V 240V 208V
Heater
Amps
Motor
FLA (A)
Circuit MCA MOCP
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
82.5 72.4 90 80
84.5 74.4 90 80
109.5 96.0 110 100
84.5 74.4 90 80
109.5 96.0 110 100
6 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
Engineering Submittal Sheet
SM Series
Residential Geothermal Heat Pumps
2nd data plate for units with EH option - Constant Airfl ow ECM motor
Model
SM024 4.8 1 4,800 3,600 20.0 17.3 2.8 - 28.5 25.1 30 30
SM036 4.8 1 4,800 3,600 20.0 17.3 6.8 - 33.5 30.1 35 35
SM036 9.6 1 9,600 7,200 40.0 34.6 6.8 - 58.5 51.8 60 60
SM048 4.8 1 4,800 3,600 20.0 17.3 6.8 - 33.5 30.1 35 35
SM048 9.6 1 9,600 7,200 40.0 34.6 6.8 - 58.5 51.8 60 60
SM048 14.4 2 14,400 10,800 60 51.9 6.8
SM060 4.8 1 4,800 3,600 20.0 17.3 9.1 - 36.4 33.0 40 35
SM060 9.6 1 9,600 7,200 40.0 34.6 9.1 - 61.4 54.6 70 60
SM060 14.4 2 14,400 10,800 60 51.9 9.1
SM060 19.2 2 19,200 14,000 80 69.2 9.1
SM070 4.8 1 4,800 3,600 20.0 17.3 9.1 - 36.4 33.0 40 35
SM070 9.6 1 9,600 7,200 40.0 34.6 9.1 - 61.4 54.6 70 60
SM070 14.4 2 14,400 10,800 60 51.9 9.1
SM070 19.2 2 19,200 14,000 80 69.2 9.1
Electric
Heater Rated kWStage
Heater
Watts
240V 208V 240V 208V Fuses 240V 208V 240V 208V
Heater
Amps
Motor
FLA (A)
Circuit MCA MOCP
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
F1/F2
F3/F4
83.5 73.4 90 80
86.4 76.3 90 80
111.4 97.9 125 100
86.4 76.3 90 80
111.4 97.9 125 100
7 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
Unit Supply Air Confi gurations
Engineering Submittal Sheet
Top Discharge (Default) Back Discharge Side Discharge
Unit Return Air Confi gurations
Left Air Return Right Air Return
Electrical Box can be relocated inside unit.
8 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
SM-VT Dimensions and Connections
Engineering Submittal Sheet
Application
SM060/070VT Config kit
SM024VT Config kit
SM036/048VT Config kit
Part #
8-733-938-189
8-733-938-190
Configuration Conversion Kit
8-733-938-191
9 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
SM-HZ End Blow Dimensions and Connections
Engineering Submittal Sheet
10 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
SM-HZ Straight Through Dimensions and Connections
Engineering Submittal Sheet
11 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
SM-HZ Hanging Bracket Dimensions and Connections
Engineering Submittal Sheet
12 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us
SM Series
Residential Geothermal Heat Pumps
SM-CF Dimensions and Connections
Engineering Submittal Sheet
13 of 42
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances |
BTC 760108301 G | 10.2015
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Tel: 1-866-642-3198 Fax: 1-954-776-5529 www.bosch-climate.us