ICP-SDI-9114 | Installation Instructions | Listings and Approvals
Listings and Approvals
UL
UL 365 Police Station Burglar Alarm Units and Systems
UL 609 Local Burglar Alarm Units and Systems
UL 864 Control Units for Fire-protective Signaling
Systems
UL 985 Household Fire Warning System Units
UL 1023 Household Burglar Alarm System Units
UL 1076 Proprietary Alarm Units
UL 1610 Central-station Burglar-alarm Units
Bosch Security Systems, Inc. | 12/15 | F01U030068-04
The ICP-SDI-9114 SDI Splitter is an accessory to the B9512G, B8512G, D9412GV4, D7412GV4, D7212GV4,
D9412GV3, D7412GV3, D7212GV3, D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, D7212G, and D9124
control panels. The SDI splitter provides the ability to set up two independent SDI buses from a single SDI
connection on the control panel. When this accessory is installed with a control panel and wired to create
separate SDI buses for fire and intrusion devices the system is a UL 864 compliant combination control panel.
The ICP-SDI-9114 is not for use with SDI2.
The D7212GV4/D7212GV3/D7212GV2/
D7212G Control Panels are not rated for
The SDI splitter has three sets of four-position SDI terminals: PANEL, FIRE, and BURG. The PANEL terminals are
used for the SDI connection to the control panel. The terminals labeled FIRE and BURG are handled equally, and
either terminal can be assigned to any collection of devices that require two separate buses. The SDI splitter
does not affect the operation of the control panel or the associated SDI devices.
Commercial Fire.
2.0 Mounting
UL requires that the SDI splitter be mounted in the same enclosure with the control panel, or in a
separate enclosure in the same room within 20 ft (6.1 m) of the control panel and connected by
conduit.
The enclosures for the GV3/GV2/G Series Control Panels have four module mounting locations. Refer to Figure 1.
Figure 1: Mounting Locations in the Control Panel Enclosure
1
2
3
4
2
5
1 - Control panel enclosure
2 - Module mounting locations
3 - ICP-SDI-9114 SDI Splitter
4Bosch Security Systems, Inc. | 12/15 | F01U030068-04
The SDI splitter operates on power from the control panel, but the DC current is limited to 550 mA for each bus
(FIRE and BURG), or enough power for two D1255 or two D1260 keypads. A total of up to 32 SDI devices can
connect to the output buses. A fault to the power or data connections of one bus does not affect the other bus.
An external power supply, connected with a common ground, is required to provide power for
devices that exceed the 550 mA limit. Refer to Figure 3 and Figure 4 for wiring when an external
power supply is used. To determine the current usage for SDI devices, use the Current Rating Chart for Standby Battery Calculations in the B9512G/B8512G Installation and System Reference Guide
(P/N:F01U303996), D9412GV4/D7412GV4 Installation and System Reference Guide (P/N:
F01U265457), D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069) or
in the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639).
Figure 2 shows the wiring for one SDI splitter with two SDI devices connected to each bus, where the DC current
drawn on each bus does not exceed 550 mA.
Figure 2: Wiring for One SDI Splitter with Two SDI Devices on Each Bus
3
Fire
Panel
Burg
SDI PWR
SDI A
SDI B
COM
SDI PWR
SDI A
SDI B
1
PERIPHERAL DEVICE CONNECTIONS
REDPOWER +
YELLOWDATA BUS A
GREENDATA BUS B
BLACKCOMMON
1 - Control panel
2 - Supervised
3 - ICP-SDI-9114 SDI Splitter
SDI PWR
SDI A
SDI B
COM
2
4 - SDI devices connected to the “Burg” bus
5 - SDI devices connected to the “Fire” bus*
COM
2
2
4
5
4
5
* Important: When the ICP-SDI-9114 SDI Splitter is used in a UL864 or NFPA72 installation, you can install only
one keypad on the Fire bus. Program this keypad as “Master” for Fire.
Figure 3 on page 6 and Figure 4 on page 7 show how to use an external power supply to isolate the
power connections between buses.
Figure 3 shows two approved methods of wiring when more than two SDI devices are installed on
one of the buses, and the DC current drawn on one of the buses exceeds 550 mA.
A maximum of two SDI splitters can be used with one control panel to increase the number of
isolated SDI buses to four. The SDI power connection on the control panel supports any two
isolated buses. A separate external power supply is necessary for each additional bus over two.
Figure 4 shows the correct wiring when two SDI splitters are connected to one control panel.
Bosch Security Systems, Inc. | 12/15 | F01U030068-045
The SDI splitter has three green LEDs that monitor bus activity. The LEDs are labeled PANEL ACTIVE, FIRE
ACTIVE, and BURG ACTIVE. During the powering up process, all LEDs flash briefly to indicate that power is
applied and the device is operating. During operation, the LEDs flash randomly to indicate active non-faulted
buses. If an LED does not show activity, the corresponding bus is faulted, is not in use, or has only unsupervised
devices connected to it.
Figure 5: SDI Splitter
ACTIVE
1 - FIRE ACTIVE LED
2 - PANEL ACTIVE LED
1
FIRE
SDI PWR SDI ASDI BCOM
FIRE
4
PANEL ACTIVE
SDI PWR SDI ASDI BCO M
PANEL
5
3 - BURG ACTIVE LED
4 - FIRE terminals
32
SDI PWR SDI ASDI BCOM
BURG
6
5 - PANEL terminals
6 - BURG terminals
BURG
ACTIVE
8Bosch Security Systems, Inc. | 12/15 | F01U030068-04
During power-up, the FIRE ACTIVE,
PANEL ACTIVE, and BURG ACTIVE
LEDs do not flash.
After power-up, the PANEL ACTIVE
LED does not flash.
PANEL ACTIVE LED flashes, but
keypads do not indicate
communication with the control
panel.
Only one of the two buses (FIRE and
BURG) operates.
Power and power wiring
Wiring between the control panel and the PANEL SDI A and SDI B
terminals
1, 2
• Connections to the FIRE and BURG SDI A and SDI B terminals. The
wiring might be reversed.
• Other wiring fault
• Control panel programming
• Wiring fault
To determine if the problem is in the SDI Splitter or the
wiring, exchange the connections to the FIRE and BURG terminals.
1, 2
1 Refer to General Wiring Troubleshooting in the D9412GV2/D7412GV2 Troubleshooting Guide (P/N: F01U011024).
2 Use the voltage values in Table 2 below.
3 Refer to the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U143071 or F01U170807) or the D7212GV3 Program Entry
Guide (P/N: F01U143077 or F01U17080) for GV3 Series Control Panels. Refer to the D9412GV2/D7412GV2 Program Entry
Guide (P/N: F01U003636) or the D7212GV2 Program Entry Guide (P/N: F01U003804) for GV2 Series Control Panels.
Table 2: Voltage Values for SDI Splitter
Terminals
Type of Terminal Normal Voltage
Power (PWR) 8 to 14 VDC, steady
Bus (SDI A) 5 to 10 VDC, moving
Bus (SDI B) 3 to 8 VDC, moving
When measuring the voltage on the SDI
terminals, set the digital voltmeter (DVM)
to read VDC. Connect the red lead to the
terminal you are reading. Connect the
black lead to the corresponding COM
terminal.
Bosch Security Systems, Inc. | 12/15 | F01U030068-049