u 24 VDC, filtered or FWR

u Continuous or temporal (Code 3) horn tones

u Selectable dBA settings (high, medium, or low) u Easy wall mounting on a variety of back boxes

These Wheelock horns are UL Listed for indoor wall mount applications. They provide a choice of continuous horn tone or temporal (Code 3) horn tone with three selectable sound output (dBA) settings for each tone. The temporal tone can be synchronized by using an SM (single) or DSM (dual) Synchronization Module or a compatible control panel. These horns can also be used on coded systems where the applied voltage is cycled on and off.

Certifications and approvals

Cooper Wheelock, Inc. holds these Listings and Approvals:

Region

Certification

 

 

 

USA

UL

ULSZ: Audible Signal Appliances

 

 

(UL464)

 

CSFM

see our website

 

 

 

Installation/configuration notes

Compatible Products

The following products are compatible with the HS 24 Horns:

Category

Product ID

Product Description

Control

D70221

Conventional FACP

Panels

 

 

 

D70242

Addressable FACP

 

D7024

Conventional FACP

 

D80241

Analog FACP

 

D91241

Addressable FACP

 

D10024A1

Analog FACP

 

FPD-70242

Addressable FACP

 

FPD-7024

Conventional FACP

Modules

SM 12/24 R

Synchronization module (red)

 

DSM 12/24 R

Dual synchronization module

 

 

(red)

 

RSSP 241575W FR

Fixed candela retrofit strobe

 

 

plate

 

RSSP 24MCW FR

Multi candela retrofit strobe

 

 

plate

 

RSSP 24MCWH FR

High candela retrofit strobe

 

 

plate

2 | HS Horns

1 For synchronization, use the SM or DSM Synchronization Modules. The synchronization module must be set for 24 VDC operation. When used, the D7022 must be set for 24 VDC operation.

2 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).

Mounting Considerations

Indoor Applications

Mount these HS 24 R and HS 24 W Horns on the indicated back boxes for the indicated applications:

 

Conduit

Surface

Flush

 

Applications

Mounted

Mounted

Double gang

 

 

Four inch square

 

 

100 mm European

 

 

IOB1

 

SHBB-R

 

1 Although the IOB Back Box is an indoor or outdoor box, the HS24 Series Horns are only UL Listed for indoor applications.

Use as Combination Appliance

Where combination appliances are required, the HS Horns can be used with the RSSP 241575W FR (15/75 cd), RSSP 24MCW FR (15 cd, 30 cd, 75 cd, or 110 cd), or RSSP 24MCWH FR (135 cd or 185 cd) Retrofit Strobe Plates that are designed to meet or exceed the latest requirements of NFPA 72,

ANSI 117.0 and UL 1971. The horns and retrofit strobe plates are also compatible with the SBL2 R Retrofit Device Back Box.

Wiring

The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).

Parts included

Quant. Component

1Horn

1Hardware pack

1Literature pack

Technical specifications

Electrical

Current (maximum) VDC:

High dBA: 110 mA

 

Medium dBA: 68 mA

 

Low dBA: 27 mA

 

 

Current (maximum) VFWR:

High dBA: 94 mA

 

Medium dBA: 50 mA

 

Low dBA: 41 mA

 

 

Voltage (input)

24 VDC nominal filtered or FWR

 

16 VDC to33 VDC

 

 

Environmental

Relative Humidity:

 

Up to 85%, non condensing

 

 

 

Temperature (Operating):

+32°F to +120°F (0°C to +49°C)

 

 

 

 

 

Mechanical

 

 

 

 

 

Dimensions

 

4.125 in. x 4.125 in. x 1.25 in.

(H x W x D):

 

(10.5 cm x 10.5 cm x 3.2 cm)

 

 

 

Material:

 

Molded plastic enclosure

 

 

 

Horn Ratings at 24 VDC

 

 

 

 

 

Continuous Horn

 

 

 

 

 

Reverberant dBA at 10 ft (3 m) per

High: 91 dBA

UL464:

 

 

Medium: 88 dBA

 

 

 

 

Low: 83 dBA

 

 

 

 

Temporal (Code 3) Horn

 

 

 

 

 

Reverberant dBA at 10 ft (3 m) per

High: 87 dBA

UL464:

 

 

Medium: 84 dBA

 

 

 

 

Low: 79 dBA

 

 

 

 

 

Notice

The sound output for the Temporal (Code 3) mode is rated lower than in Continuous mode because the time that the horn is off is averaged into the sound output rating. When the horn produces a tone in Temporal mode, its sound pressure is the same as the Continuous mode.

Ordering information

HS 24 R Two wire Horn (red)

Red, 24 VDC, two wire horn with three selectable sound output (dBA) settings and a choice of continuous or temporal (Code 3) horn

Order number HS-24-R

HS 24 W Two wire Horn (white)

White, 24 VDC, two wire horn with three selectable sound output (dBA) settings and a choice of continuous or temporal (Code 3) horn

Order number HS-24-W