Quick Start Guide
560/583 DDC
Please refer to the included Hardware User’s Guide and BACview Installation and
Operation Manual for more detailed information on setting up and using the controllers.
8733914716(2014/02)
![](/html/d3/d311/d311de275d7c7467b220ac44f02bc347f8027fee40ec16e708072dc12ed72eb0/bg2.png)
2 |
Quick Start Guide
8733914716 DDC (2014/02) Subject to change without prior notice Quick Start Guide
![](/html/d3/d311/d311de275d7c7467b220ac44f02bc347f8027fee40ec16e708072dc12ed72eb0/bg3.png)
Quick Start Guide
CONTENTS
Quick Start Guide – Hardware Setup .................4
Controller Features .............................4
Getting Started ...................................5
Jumper Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DIP Switch Settings ...............................6
Rotary Dial Settings ...............................7
Power Up .......................................7
Quick Start Guide – Software Setup ..................8
Software Conguration Tools ....................8
Handheld BACview Module Features ..............8
Virtual BACview Module Features .................9
Getting Connected ...............................10
Conguring Application Parameters using BACview ...11
Modifying Parameter Values Using BACview .........11
Customizing Program Features Using BACview ......12
Useful Shortcuts for Tweaking Program Features
Using BACview ...............................12
Congurable I/O Port Assignments (SW 7.03.06) ......13
Wiring Diagram .................................14
Typical FHP560 Wiring Diagram ...................14
Table of Contents
| 3
Quick Start Guide Subject to change without prior notice 8733914716 DDC (2014/02)
![](/html/d3/d311/d311de275d7c7467b220ac44f02bc347f8027fee40ec16e708072dc12ed72eb0/bg4.png)
4 |
Hardware Setup
Quick Start Guide – Hardware Setup
Controller Features
Battery
Quick Start Guide
Network
LON Connector
Rotary Switch
Jumper Bank
RNET
Connector
Universal
Inputs
IN-1 to IN-6
Local Access Port
(see page 10)
24VAC
DIP Switch
Bank
Analog
Outputs
(583 only)
Digital
Outputs
Part Number
8733914716 DDC (2014/02) Subject to change without prior notice Quick Start Guide
©Copyright 2014 Bosch, Inc All rights reserved
FHP 560 Controller
![](/html/d3/d311/d311de275d7c7467b220ac44f02bc347f8027fee40ec16e708072dc12ed72eb0/bg5.png)
Quick Start Guide
Input Selection Jumpers for IN-1 & IN-2
(e.g. for a 0-5V CO2 Sensor
connected to IN-1, the jumper
should be set in bottom position)
IN-1 & IN-2 Jumper
Settings Label
Communications Selection Jumper
(i.e. jumper in bottom position for
BACnet over ARC156, or, jumper in top
position for EIA-485 using BACnet over
MS/TP, LON, Modbus, or N2 protocols)
Communications Selection label
Getting Started
| 5
GETTING STARTED
Perform a quick visual inspection to ensure the
controller has no external damage and all connectors
are intact. Ensure wiring is per desired application
(see sample FHP 560 wiring diagram on page 14).
Refer to I/O port conguration (page 13) for further
details on wiring inputs and outputs.
JUMPER SETTINGS
Verify that hardware conguration for jumpers
match corresponding Heat Pump system
application. If the controller is networked, ensure
communications jumper is set to EIA-485, unless
the network protocol is BACnet over ARC156.
Quick Start Guide Subject to change without prior notice 8733914716 DDC (2014/02)
In the above diagram, IN-1 and IN-2 are set to Thermistor/Dry
Contact, and Communications is set to BACnet over ARC156.