Bosch FCS‑320‑TP1, FCS‑320‑TP2 Operation Manuals

Aspirating Smoke Detector
FCS‑320‑TP1 | FCS‑320‑TP2
en
Operation Guide
Aspirating Smoke Detector Table of contents | en 3
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
1
Safety 6
2
General 7
2.1 Introduction 7
2.2 Warranty 7
2.3 Copyright 7
2.4 Disposal 7
3
Technical Specifications 8
3.1 Product Description 8
3.2 Areas of application 9
3.3 System Overview 12
3.4 Functions 12
3.5 FCS-320 Series Aspirating Smoke Detectors and Accessories 14
3.5.1 Overview 14
3.5.2 FCS-320 series connections 15
3.5.3 FCS-320-TP1/FCS-320-TP2 displays 16
3.5.4 FCS-320-TT1/FCS-320-TT2 displays 17
3.5.5 FAS-ASD-DIAG Diagnostic Software 18
3.5.6 Remote indictors 18
3.5.7 Device mounting 19
3.5.8 Measures for Reducing Operating Noise 19
3.6 Pipe system components 20
3.6.1 Overview 20
3.6.2 Air sampling openings 21
3.6.3 Ceiling Lead-through Adapter 22
3.6.4 Air-Return Pipe for Pressure Areas and Atmospheric Loads 23
3.6.5 Air filters for dusty areas 24
3.6.6 Water Separator for Humid Areas 24
3.6.7 Detonation Safety Barrier for Potentially Explosive Areas 25
3.7 Scope of Delivery: Smoke Aspiration System 26
3.8 Technical data 28
3.8.1 FCS-320 Series Aspirating Smoke Detectors 28
3.8.2 Pipe System 29
3.8.3 Smoke Aspiration System Components 29
4
Planning 32
4.1 Regulations 32
4.2 Principles of Pipe Planning 33
4.3 Airflow monitoring 36
4.4 Defining the Response Sensitivity 37
4.5 Planning Limits 38
4.6 Standard Pipe Planning 39
4.6.1 Determining the Necessary Accessories 39
4.6.2 Pipe Planning with Pipe Accessories 39
4.7 Pipe Planning for Single-Hole Monitoring 49
4.8 Simplified Pipe Planning 55
4.9 Planning for Long Pipe Feed Lines 58
4.10 Planning with Acceleration Openings 59
4.11 Planning for Forced Airflow 69
4.12 Project planning with branch pipes 72
4 en | Table of contents Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
4.13 Planning with air sampling hose 74
4.14 Planning with air return 75
4.15 Power Supply 76
5
Installing the Aspirating Smoke Detector 78
5.1 General 78
5.2 Installing the Detector Module 78
5.3 Settings on the Unit Motherboard 79
5.3.1 Setting the Fan Voltage 79
5.3.2 Number of Detector Modules 80
5.4 Installing the Unit 80
5.5 Installing the Reset Board 83
5.5.1 Installing the reset board 83
5.5.2 Installing the reset board 84
5.5.3 Electrical connection of the reset board 85
5.6 Connection to the Fire Panel 85
5.6.1 Electrical Connection 85
5.6.2 FCS-320-TP1 / FCS-320-TT1 Connection to the Fire Panel 87
5.6.3 FCS-320-TP2 / FCS-320-TT2 Connection to the Fire Panel 87
5.7 DIP switch settings 87
5.8 Connecting an External Detector Alarm Display 89
5.9 Data Logging 89
5.10 Replacing a Detector Module 89
6
Installation of the Pipe System 91
6.1 Length Change of the Pipe System 92
6.2 Air Sampling Openings 93
6.3 Ceiling Lead-through 95
6.4 Monitoring with Forced Airflow 95
6.4.1 Detection at Intake and Exhaust Openings 95
6.4.2 Detection in the Bypass 96
6.5 Air Filter 97
6.5.1 Installing the Air Filter Box 97
6.5.2 Filter Change on the Air Filter Box 97
6.6 Air-return Pipe 98
6.7 Three-way Tap 99
6.8 FAS‑ASD‑WS Water Separator 100
6.9 Detonation Safety Barrier 101
6.10 Test Adapter 101
7
Commissioning 103
7.1 Preparation 103
7.2 Calibrating the Airflow Sensor 104
7.2.1 Air-Pressure-Independent Calibration 104
7.2.2 Air-Pressure-Dependent Calibration 105
7.3 Testing the Detector Module and Alarm Transfer 105
7.4 Checking Malfunction Transmission 106
7.5 Checking Airflow Monitoring 106
7.6 FCS-320 Functional Test 107
7.6.1 Preparations for the Functional Test 107
7.6.2 Conducting the Functional Test 108
8
Maintenance 110
Aspirating Smoke Detector Table of contents | en 5
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
8.1 Visual check 110
8.2 Flash Code Table 110
8.2.1 1 Flash - Error: Internal Voltage Monitoring 1 110
8.2.2 2 Flashes - Error: Internal Voltage Monitoring 2 111
8.2.3 3 Flashes - Error: Fan Voltage Monitoring 111
8.2.4 4 Flashes - Error: Air Pressure Correction Voltage Monitoring 112
8.2.5 5 Flashes - Error: Programming Error 113
8.2.6 6 Flashes or 7 Flashes - Error: Internal Error 1 or Internal Error 2 113
8.2.7 8 Flashes: Unit Initialization 113
8.3 Detector Module and Alarm Transmission 113
8.4 Pipe system 114
8.5 Checking the Airflow Sensor Calibration 114
8.6 Airflow Monitoring 116
8.7 Malfunction Transmission 116
8.8 Maintenance Intervals 116
9
Appendix 118
9.1 Air Pressure Correction Tables for Airflow Sensor Calibration 118
9.1.1 Equipment protection 118
9.1.2 Space Protection (I-pipe System) 119
9.1.3 Space Protection (U, Double U, and H-pipe System) 121
9.2 Planning without filter 123
9.2.1 Without any other pipe accessories 123
9.2.2 With water separator 124
9.2.3 With detonation safety barrier 124
9.3 Planning with air filter 125
9.3.1 Without any other pipe accessories 126
9.3.2 With water separator 126
9.3.3 With detonation safety barrier 127
9.4 Test Log FCS-320 Series Aspirating Smoke Detectors 127
Index 130
6 en | Safety Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
1 Safety
The following symbols identify points in this operation guide that require particular attention in order to guarantee smooth operation and prevent damage.
Notice!
Operational malfunction can be prevented and operational improvements can be achieved by observing these instructions.
!
Caution!
This symbol warns against actions and behavior which, if disregarded, could cause property damage.
!
Warning!
This symbol warns against actions and behavior which, if disregarded, could cause personal injury.
Aspirating Smoke Detector General | en 7
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
2 General
2.1 Introduction
This operation guide describes the smoke aspiration systems featuring FCS-320 series aspirating smoke detectors and the associated aspiration pipe system. The FCS-320 designation in this operation guide refers to all FCS-320 versions (FCS-320‑TP1, FCS-320‑TP2, FCS-320‑TT1 und FCS-320‑TT2). Specific references are made to differences between the individual versions. The "FAS/FCS" designation in the illustrations and graphics also refers to all models in the FCS-320 series (FCS‑320‑TP1, FCS‑320‑TP2, FCS‑320‑TT1, FCS‑320‑TT2), and also applies to LSN models of aspirating smoke detectors. This operation guide describes the smoke aspiration systems featuring FCS-320 series Aspirating Smoke Detectors and the associated aspiration pipe system. The FCS-320 designation in this operation guide refers to all FCS-320 series versions. Specific references are made to differences between the individual versions.
2.2 Warranty
The operation guide is subject to technical modification without prior notice and makes no claim to completeness. Our "delivery and installation conditions" apply as a matter of principle. Warranty and liability claims in case of personal injury and property damage cannot be asserted if they are based on one or more of the following causes: – Insufficient attention to the instructions with respect to planning, installation of the
aspirating smoke detector, installation of the pipe system, commissioning and
maintenance – Use of the smoke aspiration system contrary to the regulations – Insufficient monitoring of wearing parts – Faulty repairs – Arbitrary constructional changes to the smoke aspiration system – Acts of God. Bosch Sicherheitssysteme GmbH, hereinafter referred to as Bosch, assumes no liability for damage or malfunction arising through failure to comply with this operation guide.
!
Caution!
The equipment may only be installed by authorized and qualified personnel!
2.3 Copyright
The copyright to this operation guide remains with Bosch. This operation guide is intended exclusively for installation engineers and their employees. Reprinting this operation guide or extracts thereof is permitted for internal purposes only.
2.4 Disposal
Unusable electrical and electronic devices or modules must not be disposed of with normal household refuse. They must be disposed of in compliance with the applicable regulations and directives (e.g. WEEE in Europe).
8 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
3 Technical Specifications
3.1 Product Description
Aspirating smoke detectors from the FCS-320 series are active fire detection devices that are connected directly to conventional lines for early smoke and fire detection. They are used for room and equipment protection as well as for monitoring air-conditioning units or ducts.
Variants
The FCS-320‑TP1 and FCS-320‑TP2 models feature LED displays indicating operating mode, malfunction and alarm (the FCS-320‑TP2 has two alarm displays). The FCS-320‑TT1 and FCS-320‑TT2 models offer differentiated alarm displays (info, pre and main alarm) as well as a 10-level smoke display (on the FCS-320‑TT2, all alarm and smoke level displays are doubled). The FCS-320‑TP1 and FCS-320‑TT1 variants are each fitted with a detector module. Both FCS-320‑TP2 and FCS-320‑TT2 have two integrated detector modules each. Two aspiration pipes can be connected, enabling two areas to be monitored. This effectively doubles the monitoring area.
Dual-detector dependency
The use of two detector modules in variants FCS-320-TP2 and FCS-320-TT2 also enables a dual-detector dependency to be realized. This means that one area can be monitored by two pipe systems.
Two alarm stages
Alternatively, the FCS-320-TP2 and FCS-320-TT2 can have two alarm stages configured. A pipe system is connected via a pipe adapter on two detector modules. Selecting different response sensitivities for the detector modules enables the time-staggered triggering of two main alarms.
Sensitivity
Three detector module versions are available for the FCS-320 aspirating smoke detector series: – DM‑TP‑50(80) with a response sensitivity of up to 0.5%/m (0.8%/m) light obscuration – DM‑TP‑10(25) with a response sensitivity of up to 0.1%/m (0.25%/m) light obscuration – DM‑TP‑01(05) with a response sensitivity of up to 0.015%/m (0.05%/m) light obscuration. Depending on the detector module used, the FCS-320‑TT1 and FCS-320‑TT2 models can achieve a resolution ten times higher for displaying up to 0.05%/m (0.08%/m), 0.01%/m (0.025%/m) or 0.0015%/m (0.005%/m) light obscuration.
Notice!
The sensitivity value is based on measurements with standard test fires (old value in brackets).
The new High-Power-Light-Source technology permits a broad detection spectrum over all standardized fires.
LOGIC×SENS
The intelligent signal processing LOGIC·SENS distinguishes between deception variables and fire events in order to prevent false alarms.
Reliable airflow monitoring
Analogous to point-type smoke detectors, which are monitored electronically for wire breaks and short-circuits, highly sensitive and dependable airflow monitoring is required for smoke aspiration systems. The airflow sensors used in the FCS-320 series reliably detect malfunctions such as pipe breakage or obstructions in the air sampling openings. Airflow monitoring is temperature-compensated and can be set depending on the air pressure.
Aspirating Smoke Detector Technical Specifications | en 9
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
The small airflow unit also contains a dynamic airflow sensor that enables a response to small and fast changes in the airflow.
Patented air sampling openings
The air sampling openings of the pipe system require clearly defined bore diameters that depend on the planning and design. These precise air sampling openings are created using patented aspiration reducing film sheets, marking tape, and clips, which not only permit easy installation, but also prevent "whistling" noises. Another advantage is the quick and easy detection and checking of the air sampling opening diameters.
Point-type detector projection
The system’s aspiration points can be equated with point-type smoke detectors. The monitoring areas can therefore be planned in accordance with the applicable national regulations.
Diagnostics
There is a system available with the FAS-ASD-DIAGdiagnostic software that enables quick and convenient error containment for maintenance and service. The current and stored unit status is read out via cable data transmission to the PC.
Selecting the fan voltage
The fan voltage for special planning can be increased from 6.9V to 9V by relocating the fan jumper. This increases the air transport speed and therefore reduces detection time.
3.2 Areas of application
Thanks to their detection principle, FCS-320 aspirating smoke detectors represent an extremely versatile fire protection solution.
Principle
Air samples are taken from the monitoring range by a pipe system with defined aspiration borings and then fed to the detection module. This is especially well-suited for areas in which point-type detectors cannot be used or can only be used under certain circumstances. These include: – Areas that are difficult to access, in which point detectors are difficult to install and
maintain – Air-conditioned areas – Areas that require the earliest detection possible – Areas with a height greater than that allowed for point detectors – Areas in which point detectors are not desired for aesthetic reasons – Areas in which strong electromagnetic fields occur – Areas that are exposed to high or low temperatures – Areas with contaminated air that require filter elements – Areas that must be protected against vandalism.
Space protection
The FCS-320 series is suitable for monitoring areas such as – Those with double floors, false ceilings – Tunnels, ducts, barely accessible hollow spaces – Storage, high-rise warehouses, elevator shafts – Museums, cultural institutions – Hotel rooms, hospital rooms, offices, prison cells, train compartments – Freezer storage
10 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
FAS / FCS
1
2
TITANUS MICRO·SENS ®
E
D
C
B
A
10 9 8 7 6 5 4 3 2 1
TITANUS MICRO·SENS ®
E
D
C
B
A
10 9 8 7 6 5 4 3 2 1
Principle of area monitoring with FCS-320 series Aspirating Smoke Detectors
1 Room pipe system
2 Double-floor pipe system
Area monitoring with air-conditioning
Area monitoring occurs – In rooms with air-conditioning for server rooms etc. – In ventilation ducts – In double floors, false ceilings – In IT rooms, e-distributor rooms, transformer cells – On air-conditioning units (see figure below) or – In the bypass in air-conditioning ducts.
FAS / FCS
FAS / FCS
FAS / FCS
1
2
Monitoring options for an air-conditioning unit or an air­conditioning duct (depiction of principle)
1 Air-conditioning duct
2 Air-conditioning unit
The FCS-320 Aspirating Smoke Detector can be used for early fire detection in areas with special-purpose air conditioning.
Aspirating Smoke Detector Technical Specifications | en 11
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Thanks to its high sensitivity, expensive goods and equipment can be monitored reliably. The aspirating smoke detectors from the FCS-320 series are therefore especially suitable for areas of application: – Where early intervention is essential due to a high value concentration – Where equipment must always be operational – Where highly sensitive detection is necessary (e.g. in areas where, due to built-in filter
elements, the air contains a low concentration of smoke particles) – Where high air-exchange rates prevail.
Area monitoring with air-conditioning
Area monitoring occurs – In rooms with air-conditioning for server rooms etc. – In ventilation ducts – In double floors, false ceilings – In IT rooms, e-distributor rooms, transformer cells – On air-conditioning units (see figure below) or – In the bypass in air-conditioning ducts.
FAS / FCS
FAS / FCS
FAS / FCS
1
2
Monitoring options for an air-conditioning unit or an air­conditioning duct (depiction of principle)
1 Air-conditioning duct
2 Air-conditioning unit
The FCS-320 Aspirating Smoke Detector can be used for early fire detection in areas with special-purpose air conditioning. Thanks to its high sensitivity, expensive goods and equipment can be monitored reliably. The aspirating smoke detectors from the FCS-320 series are therefore especially suitable for areas of application: – Where early intervention is essential due to a high value concentration – Where equipment must always be operational
12 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
Where highly sensitive detection is necessary (e.g. in areas where, due to built-in filter
elements, the air contains a low concentration of smoke particles)
Where high air-exchange rates prevail.
3.3 System Overview
The smoke aspiration systems comprise an aspirating detector and pipe system. The aspirating smoke detector comprises the detector module for detecting the smoke aerosols, the aspiration unit for transporting the air samples to the detector module and the airflow sensor for monitoring the pipe system for breakage and obstructions. The pipe system comprises essentially pipe and fittings. The standard pipe system is made from PVC or ABS. The pipes used for equipment monitoring should be halogen-free. Each air sampling opening in the pipe system represents a point detector in the planning.
2
7
6
5
3
1
A
4
Overview of the aspirating smoke detector
A Pipe system
FCS-320 Aspirating smoke
detector
1 Smoke aspiration pipe
2 Air intake
3 Air sampling openings
4 Detector module
including airflow monitoring
5 Housing
6 Aspiration unit
7 Air outlet
To guarantee reliable operation even under the most difficult conditions (clean rooms, recycling area), there are numerous accessories available, such as air filters, water separators and detonation safety barriers.
3.4 Functions
Air samples are taken from the area to be monitored via the aspiration unit. They are fed via a pipe system with defined air sampling openings to the sensitive detection module.
Detector module
Depending on the response sensitivity of the detector module in use and programmed alarm threshold, the FCS-320 series aspirating smoke detector triggers the alarm when the corresponding light obscuration threshold is reached. With the FCS-320‑TP1 and the FCS-320‑TP2, the alarm is displayed via the alarm LED and/or two alarm LEDs on the unit and transmitted to a connected fire panel. The FCS-320‑TT1 and FCS-320‑TT2 versions offer differentiated LED displays for info, pre and main alarm. Pre and main alarms are transmitted to the fire panel (with FPA‑5000 Rel 2.1; additionally with info alarm from Rel 2.5 or above). Various delay times can be programmed for the alarm thresholds, as well as for displaying and transferring malfunctions. Alarm messages are saved and are reset after the cause has been eliminated. LOGIC·SENS
Aspirating Smoke Detector Technical Specifications | en 13
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
The LOGIC·SENS intelligent signal processing compares the measured smoke level with known disturbance variables and decides between alarm and deception.
Detector module monitoring
Each detector module is monitored for contamination, signal malfunction and removal. Soiling of the detector module has no effect on its sensitivity. With all variants, any malfunction is displayed via the malfunction LED and transferred to the fire panel. Malfunctions caused by brief environmental fluctuations can be eliminated with a time-delayed setting.
Airflow Monitoring
An airflow sensor checks the connected pipe system for breakage and obstruction. The airflow sensor can – depending on the configuration of the pipe system – detect at least a 50% obstruction to a complete obstruction of the air sampling openings and a breakage in the pipe system that results in a 50% loss from the air sampling openings. Should the fan fail, the airflow in the pipe system is interrupted and this causes a blockage message. Airflow monitoring is temperature-compensated and can be set depending on the air pressure. On expiry of a defined delay, the malfunction is displayed on the aspirating smoke detector and the message is transmitted to the fire panel. The monitoring window thresholds can be modified to suit the environmental conditions (see Airflow Monitoring). The principal signal curve of the airflow sensor is indicated in Airflow Monitoring.
S
t
4
7 8
6
1
2
5
3
Example of the signal process of the Airflow sensor in case of malfunctions
S Airflow sensor signal
t Time
1 Normal airflow
2 Airflow too weak
3 Airflow too strong
4 Breakage
5 Obstruction
6 Monitoring window
7 Delay
8 Malfunction message
Fault Indication
An imminent detector module or airflow malfunction generates a malfunction message that is displayed on the FCS-320.
Flash code for malfunction detection
Malfunctions and certain device statues are displayed using various LED flash codes on the detector module's electronics PCB. Thus it is possible to differentiate quickly among malfunctions that can be caused by a defective detector module, an obstruction, or a break in the pipe system.
Resetting via fire panel
A malfunction message is reset via the connected fire panel. The panel resets alarm and malfunction messages on the unit while simultaneously resetting the detector line via the reset board.
Calibrating the airflow sensor
Automatic airflow sensor calibration makes it significantly easier to start the FCS-320. The initialization phase is carried out according to or independently of the air pressure as desired.
14 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
To set the FCS-320 to the airflow typical for the pipe network, an airflow initialization (flow­init) procedure is carried out. This must be done for each unit once at the start after installation, each time the pipe system is replanned/redesigned and after changing the fan voltage. This enables the unit to determine and save the airflow typical for the pipe network.
Pipe System
A pipe system with an overall length of up to 300m can be connected to FCS-320 series aspirating smoke detectors over a maximum of 32 aspiration points. Two pipe systems can be connected to both the FCS-320‑TP2 and FCS-320‑TT2 variants. The entire pipe system then has a total length of 2 x 280m and a maximum number of 2 x 32 aspiration points.
3.5 FCS-320 Series Aspirating Smoke Detectors and Accessories
3.5.1 Overview
2
A
3
C
E
G
F
1
B
D
FAS / FCS
Overview of FCS-320 series aspirating smoke detectors and accessories
1 Pipe system(s)
2 Connections to fire panel/power supply
3 Air-return pipe
A Vibration absorber (sold separately)
B MT-1 unit mounting
C Detector module
D DIAG Diagnostic Software with connection
cable
E Cable bushings (1xM20, 2xM25)
F Test pipe
G Test adapter
FCS-320 series aspirating smoke detectors comprise the following components: – Plastic housing – Plastic connection pieces – Integrated air-return pipe – Connection for pipe with 25mm external diameter – Aspiration unit with optimized air supply – Motherboard with interface for diagnostics system, LSN connections, connection for
shield wire, as well as DIP switch for address setting – Supplementary package with cable bushings (1xM20, 2xM25) – FCS-320-TP1 /FCS-320-TP2: optical displays for alarm, malfunction and operation – FCS-320-TT1 /FCS-320-TT2: smoke level display(s), optical displays for info, pre and main
alarm, malfunction and operation – 1 detector module (for FCS-320-TP1 and FCS-320-TT1) and/or 2 detector modules (for
FCS-320-TP2 and FCS-320-TT2).
Aspirating Smoke Detector Technical Specifications | en 15
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Notice!
Only DM-TP-50(80), DM‑TP‑10(25) and DM-TP-01(05) detector modules certified to VdS may be used in the FCS-320 series. The detector modules must be ordered separately.
See also
FAS-ASD-DIAG Diagnostic Software, page 18 – Remote indictors, page 18 – Device mounting, page 19 – Ceiling Lead-through Adapter, page 22 – Water Separator for Humid Areas, page 24 – Detonation Safety Barrier for Potentially Explosive Areas, page 25
3.5.2 FCS-320 series connections
1
2
3
1
4
5
FAS-420 series
FAS-420 series
FAS / FCS
Figure3.1: FCS-320 connections (see table on next page for explanations)
Position in
figure
Function Explanation
FCS-320 series 1 Cable bushing for connection of fire panel
and additional power supply (input/ output)
1 x M20, for cable diameters of 8-12mm
2 Pipe system 1 connection For Ø 25mm pipe system
3 Pipe system 2 connection
(for FCS-320-TP2 and FCS-320-TT2 only)
For Ø 25mm pipe system
4 Connection for air-return pipe
5 Cable bushing for connection of fire panel
and additional power supply (input/ output)
2 x M25 for cable diameters of 9-14mm (expandable to 14­18mm)
16 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
3.5.3 FCS-320-TP1/FCS-320-TP2 displays
FAS-420-TP1 / FCS-320-TP1
FAS-420-TP2 / FCS-320-TP2
1
2
Figure3.2: FAS‑420‑TP1/TP2, FCS‑320‑TP1/TP2 displays
FCS-320-TP Display LED Explanation
Operation Green Operation display
Alarm
1
Red Alarm indication
Fault Yellow Fault
in the pipe system – of a detector module – caused by fan failure
1
Two alarm displays on the FCS-320-TP2
Aspirating Smoke Detector Technical Specifications | en 17
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
3.5.4 FCS-320-TT1/FCS-320-TT2 displays
i
1
2
3
4
5
6
7
8
9
10
FAS-420-TT1 / FCS-320-TT1
FAS-420-TT2 / FCS-320-TT2
i
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
12
Figure3.3: FAS‑420‑TT1/TT2, FCS-320-TT1/TT2 displays
FCS-320‑TT Display LED
1
Explanation
Operation Green Operation display
Fault Yellow Fault
in the pipe system – of a detector module – caused by fan failure
Main alarm Red 100% smoke level
Pre-alarm
1
Red 66% smoke level
Info alarm
1
Red 33% smoke level
Smoke level display 1 to 10
1
10 yellow LEDs Current smoke level
1
All displays doubled on the FCS-320-TT2
18 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
3.5.5 FAS-ASD-DIAG Diagnostic Software
DIAG
Figure3.4: Diagnostic software for reading out unit status
The diagnostic software enables the saved and the current unit status, as well as the error messages to be displayed on the PC or laptop. The supplied diagnostics cable connects the aspirating smoke detector ("DIAG" connection on the motherboard) to the PC. The FAS-ASD-DIAG version is connected to the PC via a USB port, earlier DIAG versions via a COM port. Diagnostic messages remain saved in the unit for at least 3 days in order to be able to evaluate even short, sporadically occurring errors (e.g. in case of changed operating conditions). Resetting the device via the diagnostic software deletes all saved diagnostic messages. The software also allows the deletion of error messages.
Notice!
The diagnostic software can be used to save in file format all the stored and current diagnostic data as well as any settings made. To be able to compare the data read out, save each file under a different file name.
3.5.6 Remote indictors
A remote indicator must be connected if the aspirating smoke detector is not directly visible or has been mounted in false ceilings or floors. The external detector alarm display is installed in an obvious place in halls or entrances of the building section or areas concerned.
Aspirating Smoke Detector Technical Specifications | en 19
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
3.5.7 Device mounting
1
2
FAS
-420 series
FAS-420
series
Mounting for FCS-320 series Aspirating Smoke Detector
1 Horizontal installation
2 Vertical installation
The MT-1 unit mounting is used if a direct wall installation is not possible, e.g. installation on racks.
3.5.8 Measures for Reducing Operating Noise
1
1
2
3
4
FAS-420 series
Absorption of the operating noises caused by airflows
1 Smoke aspiration pipe
2 Flexible hose
3 Fitting
4 Vibration absorbers
Vibration absorbers
The fans of the aspirating smoke detectors cause a noise level of approx.45dB(A). Mounting the FCS-320 onto vibration absorbers can effectively reduce noise transmission through the installation elements. This results in a reduction in the noise level from 1to 2dB(A). Additional operating noises may be caused by vibrations on the pipe system, which are generated by the air flowing through it. This can be remedied by inserting a corrugated hose (approx.15cm long) between pipe system and aspirating smoke detector to create a flexible transition. In noise-sensitive areas, the sound level can also be reduced by installing a piece of plastic pipe approximately 100mm long into the air outlet opening of the unit. This is done by breaking out the pre-punched opening in the protective grille (e.g. using a small edge cutter).
20 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
3.6 Pipe system components
3.6.1 Overview
FAS-420-TM
ser
ies
A
A
A
4
5
3
2
7
6
8
9
10
11
12
13
1
14
A
B
Pipe system components
A Pipe system connection
B Smoke aspiration pipe
1 Connection for test
adapter
2 T-fitting
3 Air filter
4 Water separator
5 Detonation safety barrier
(not permitted for EN54‑20 or ISO 7240-20)
6 90° pipe bend
7 Aspiration hose for
ceiling lead-through
8 Ceiling Lead-through
9 Fitting
10 Double threaded joint
11 90° pipe elbow
12 45° pipe elbow
13 Aspiration reduction
14 End cap
During planning/design, a distinction is drawn between area monitoring and equipment monitoring. For both applications, PVC pipes and halogen-free pipes can be used but the restrictions of EN 54.20 must be observed. The pipes used for equipment monitoring should be halogen-free. The figure shows essential accessory components that can be selected for the application concerned. The pipe system must be constructed using pipes with an external diameter of 25 mm and the associated fittings. If the maximum permissible pipe lengths are used, then for the pipe returns, pipes with an exterior diameter of 40mm and the appropriate fittings must be used.
Blowing-out system
In areas that are susceptible to dust particles or icing, it may be necessary to blow out the aspiration pipe system and its air sampling openings. The figure below shows a manual blowing-out system with a three-way tap.
Aspirating Smoke Detector Technical Specifications | en 21
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
FAS-420-TM series
A
1
2
B
Components of manual blowing-out systems
A Blast air supply connection
B Pipe system connection
1 Three-way tap
2 25mm aspiration pipe
Aspiration reducing clips
3.6.2 Air sampling openings
Aspiration reducing film sheets
An air sampling opening is a 10mm bore in the aspiration pipe that is covered with a patented aspiration reducing film sheet with the required opening diameter. The size of the opening depends on the structure of the pipe system (see Planning). The aspiration reducing film sheet is secured with marking tape to prevent it from becoming displaced. The marking tape is a transparent sticky film with red edges and a 10 mm hole. It is placed over the aspiration reducing film sheet so that the air sampling opening is not concealed and can be seen from long distances.
1
3
36
2
4
4
45
2
Air sampling opening with aspiration reducing film sheet and marking tape
1 Smoke aspiration pipe
2 Air sampling opening
with aspiration reducing film sheet
3 Marking tape for
aspiration reducing film sheet
4 Air sampling opening
5 Fire red (RAL3000)
6 Transparent
Aspiration reducing clips
In areas susceptible to obstructions or icing, special, patented ASD aspiration clips with flexible aspiration reductions are used (see figure below).
22 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
1
2
Aspiration reduction for soiled areas and deep-freeze areas
1 Aspiration reduction for
deep-freeze facilities
2 ASD aspiration clip made of
plastic
During use in deep-freeze areas, the flexible aspiration reduction expands in the air sampling openings and pushes the ice away during blowing out. The special plastic clip ensures that the aspiration reduction remains at the defined location. As the clips are more stable under pressure and the elastic rubber insert significantly improves the cleaning effect, they are used for all plans and designs which require a blow-off system due to environmental influences (e.g. increased exposure to dust).
Notice!
The standard AF-x aspiration reducing film sheets and the marking tapes are not suitable for use in low-temperature areas.
The aspiration reductions with plastic clips are available separately.
3.6.3 Ceiling Lead-through Adapter
1
2
3
4
6
7
8
9
5
Ceiling lead-throughs
1 Ceiling
2 T-fitting
3 Pipe system
4 Complete ceiling lead-
through
5 Aspiration hose for ceiling
lead-through
6 False ceiling
7 Knurled nut
8 Aspiration reducing film
sheet
9 Aspiration
Aspirating Smoke Detector Technical Specifications | en 23
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
A concealed pipe system for area monitoring can be realized by installing in a false ceiling. This requires the use of ceiling lead-throughs in the false ceiling. The ceiling lead-through can be used with a false ceiling thickness of up to approx. 35mm.According to the planning and design guidelines, the ceiling lead-throughs are fitted with aspiration reducing film sheets with defined air sampling openings and connected to the pipe system by means of aspiration hoses. If these hoses exceed a maximum of 1m in length, the plan according to Section3Planning applies. If structural circumstances dictate that lengths in excess of 1m are used, the pipe system has to be calculated accordingly.
3.6.4 Air-Return Pipe for Pressure Areas and Atmospheric Loads
P1
P2
5
1
FAS / FCS
2
3
4
Principle of air return
P1/P2 Pressure areas 1 and 2
1 Detector module
2 Airflow sensor
3 Aspiration unit
4 Air-return pipe
5 Pipe system
If the aspirating smoke detectors and the pipe system are installed in areas with varying air pressure, the aspirated air must be returned to the pressure area of the pipe system. The air­return pipe can serve to equalize pressure or to prevent atmospheric loads (e.g. odors) in neighboring spaces.
1
2
FAS-420 series
FCS-320 with air-return pipe
1 Smoke aspiration pipe
2 Air-return pipe
The air-return pipe is connected to the air exhaust duct inside the FCS-320 through the ventilation grille. This requires the pre-punched opening in the protective grille to be broken out.
!
Caution!
The air-return pipe of the smoke aspiration system should not exceed 2m. Longer returns must be checked individually.
24 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
3.6.5 Air filters for dusty areas
In areas with interference to the environment such as, e.g. dust, an air filter is to be used to protect the smoke detection system. The standard air filter used is the type FAS-ASD-FL, consisting of a plastic housing with two pipe connections. If the air filters are dirty, then the filter inserts must be changed by opening the filter housing. In order to extend the maintenance intervals, one air filter can be installed in every output pipe instead of one air filter inside the main sampling pipe. The same design specifications shall apply as stated in the projection tables in the appendix.
FAS-ASD-FLFAS-ASD-FLFAS-ASD-FLFAS-ASD-FL
FAS/FCS
Furthermore, in order to extend the maintenance intervals, several air filters can be installed in parallel in the main sampling pipe. This requires the main sampling pipe to be split into one or several pipes and to be equipped with the same air filter or the combination of air filters. The individual pipes can then alternatively be either combined again to one main sampling pipe or be separately continued into the monitoring area(s). The same design specifications for the individual air filters shall apply as stated in the projection tables in the appendix.
3.6.6 Water Separator for Humid Areas
If the smoke aspiration system is operated in environments where condensate can form in the aspiration system, a water separator is used. Condensate can form with sharp temperature fluctuations and in areas where fresh air is monitored.For areas with extremely high humidity, the FAS-ASD-WS Water Separator can be used, for example. The FAS-ASD-WS Water Separator is integrated at the lowest point in the pipe system downstream of the air filter and the aspirating smoke detector. The 45° pipe elbow permits optimum distance from the wall.
Aspirating Smoke Detector Technical Specifications | en 25
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
1
2
3
3
FAS-420-TM series
FAS‑ASD‑WS Water Separator for condensing water vapor and collecting condensate from the pipe system
1 Water separator
2 Pipe system connection
3 45° pipe elbow
The FAS‑ASD‑WS Water Separator can be operated in a temperature range from 0°C to +50°C. The sintered metal filter in the water separator has a pore width of 50µm and causes an additional rough absorption of soil particles.The FAS-ASD-WS is supplied with an angle support and PG cable glands. The 45° pipe elbows (4 units) must be ordered separately.
3.6.7 Detonation Safety Barrier for Potentially Explosive Areas
Ex
FAS / FCS
1
6
7
2 3 4 5
> 1 m
> 1 m
Detonation safety barrier in the aspiration pipe system and if necessary in the air-return pipe
1 Metal pipe
2 Detector module
3 Airflow sensor
4 Aspiration unit
5 Air-return pipe
6 Pipe system
7 Detonation safety barrier
Vapor/air and/or gas/air mixture ignition in the aspirating smoke detector may result in pipe explosion or detonation. This depends on the composition, concentration, temperature, and pressure of the flammable mixture. The detonation safety barrier is a flame trap that is flame-proof in the face of pipe explosions (deflagrations) and detonations.
26 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
In normal operation, the steam and gas mixtures flow in any direction through the safety barrier. An ignition of the mixture in the upstream aspirating smoke detector will cause the developing detonation to be arrested. Ignition is prevented by the flame filter. Combustion of the mixture in the flame filters may cause a rebound of the detonation front. To prevent this, a minimum pipe length of 1.0m between the installation point of the detonation safety barrier and a possible ignition source (aspirating smoke detector) must be maintained. Permanent fire prevention is thus achieved indirectly.
!
Caution!
The connecting pipe between the aspirating smoke detector and the detonation safety barrier must be made of metal. During installation, care must be taken to ensure that the threaded connections are bolted together gas-tight using synthesol or sealing tape.
3.7 Scope of Delivery: Smoke Aspiration System
Basic devices and accessories
Designation product ID
FCS-320-TP1 Standard unit F.01U.141.197
FCS-320-TP2 Standard unit F.01U.141.198
DM-TP-50(80) Detector module 4.998.143.394
DM-TP-10(25) Detector module 4.998.143.395
DM-TP-01(05) Detector module 4.998.143.396
TITANUS MT-1 MT-1 device mounting for aspirating smoke detector 4.998.143.410
FAS-ASD-DIAG DIAG diagnostic software including connection cable, for
USB port
F.01U.033.505
FCA‑320‑Reset Reset board F.01U.141.199
FCS-320-IK Installation kit F.01U.141.201
RAS Test Pipe Test pipe 4.998.148.848
RAS Test Adapter
Test Adapter 4.998.148.849
Pipe system components
Designation product ID
FAS-ASD-PHF16 Polywell aspiration hose, flexible, black, halogen-free F.01U.029.719
FAS-ASD­TRPG16
Ring nut with PG16 internal thread, 5per set F.01U.029.721
FAS-ASD-CSL Quick-lock coupling, straight, PG16 internal thread F.01U.029.720
FAS-ASD-3WT Three-way tap, incl. fittings, for 25mm pipe system F.01U.029.718
FAS-ASD-F Flange for ventilation duct F.01U.029.722
FAS-ASD-AR Aspiration reduction, with 10mm bore for attaching an
aspiration reducing film sheet, 10 per set
F.01U.029.724
Aspirating Smoke Detector Technical Specifications | en 27
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Designation product ID
FAS-ASD-CLT Ceiling lead-through, white, ABS, 10 per set F.01U.029.725
FAS-ASD-AHC Aspiration hose (PE) for ceiling lead-through F.01U.029.727
FAS-ASD-DSB Detonation safety barrier for 25mm pipe system F.01U.029.716
FAS-ASD-WS Water separator with sintered metal filter and manual
drain valve, including mounting bracket and PG cable glands for 25mm pipe system
F.01U.029.717
FAS-ASD-FL Large air filter box, for 25mm pipe system, inc. 1 filter
set and two PG29 screw connections
F.01U.029.714
FAS-ASD-RFL Replacement filter set for large air filter box F.01U.029.715
Notice!
Four 45° pipe elbows are required to install the FAS-ASD-WS water separator.
Air sampling opening components
Designation product ID
Marking tape for aspiration reducing film sheet AF-BR, 10 units. 4.998.143.413
Aspiration reducing film sheet 2.0mm AF-2.0, 10 units. 4.998.143.416
Aspiration reducing film sheet 2.5mm AF-2.5, 10 units. 4.998.143.417
Aspiration reducing film sheet 3.0mm AF-3.0, 10 units. 4.998.143.418
Aspiration reducing film sheet 3.2mm AF-3.2, 10 units. 4.998.143.419
Aspiration reducing film sheet 3.4mm AF-3.4, 10 units. 4.998.143.420
Aspiration reducing film sheet 3.6mm AF-3.6, 10 units. 4.998.143.422
Aspiration reducing film sheet 3.8mm AF-3.8, 10 units. 4.998.143.423
Aspiration reducing film sheet 4.0mm AF-4.0, 10 units. 4.998.143.424
Aspiration reducing film sheet 4.2mm AF-4.2, 10 units. 4.998.143.425
Aspiration reducing film sheet 4.4mm AF-4.4, 10 units. 4.998.143.426
Aspiration reducing film sheet 4.6mm AF-4.6, 10 units. 4.998.143.427
Aspiration reducing film sheet 5.0mm AF-5.0, 10 units. 4.998.143.428
Aspiration reducing film sheet 5.2mm AF-5.2, 10 units. 4.998.143.429
Aspiration reducing film sheet 5.6mm AF-5.6, 10 units. 4.998.143.430
Aspiration reducing film sheet 6.0mm AF-6.0, 10 units. 4.998.143.431
Aspiration reducing film sheet 6.8mm AF-6.8, 10 units. 4.998.143.432
Aspiration reducing film sheet 7.0mm AF-7.0, 10 units. 4.998.143.433
28 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
Notice!
Plastic clips for deep-freeze facilities and blowing-out systems are sold separately.
3.8 Technical data
3.8.1 FCS-320 Series Aspirating Smoke Detectors
Electrical
Power supply 15VDC to 33VDC
auxiliary power supply 14VDC to 30VDC
Current consumption from auxiliary power supply (at24V)
FCS-320‑TP1 FCS-320-TT1
FCS-320‑TP2 FCS-320‑TT2
Starting current, fan voltage 6.9V 300mA 330mA
Starting current, fan voltage 9V 300mA 330mA
On standby, fan voltage 6.9V 200mA 230mA
On standby, fan voltage 9V 260mA 310mA
On alarm, fan voltage 6.9V 230mA 290mA
On alarm, fan voltage 9V 290mA 370mA
Mechanics
Displays on the device FCS-320-TP1/FCS-320-TP2
Operation Green LED
Fault Yellow LED
Alarm 1 red LED/2 red LEDs
Displays on the device FCS-320-TT1/FCS-320-TT2
Operation Green LED
Fault Yellow LEDs
Level display 1 x / 2 x smoke level display, each
with 10segments (1–10)
Alarm 1 x 3 / 2 x 3 red LEDs for info alarm,
pre-alarm and main alarm
Conical duct connections for Ø25mm
Aspiration pipe 1 pipe/2 pipes
Air-return pipe 1 pipe
Cable bushings 5 x M 20 and 2 x M 25
Dimensions (H x W x D) 292 x 200 x 113mm
Weight Approx. 1.5kg
Aspirating Smoke Detector Technical Specifications | en 29
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Housing material Plastic (ABS)
Housing color Papyrus white (RAL 9018)
Environmental conditions
Protection category as per EN 60529 IP 20
Permissible temperature range of aspirating smoke detector
-20°C to +60°C
Permissible relative humidity (non-condensing) 10 to 95%
Special features
sound power level 45 dB(A)
Max. response sensitivity (max. light obscuration)
DM‑TP‑50(80) Detector Module 0.5%/m (0.8%/m) *
DM‑TP‑10(25) Detector Module 0.1%/m (0.25%/m) *
DM‑TP‑01(05) Detector Module 0.015%/m (0.05%/m) *
Life cycle of the fan (12V) 43,000 hrs at 24°C
* The sensitivity value is based on measurements with standard test fires (old value in brackets).
3.8.2 Pipe System
FCS-320-TP1 FCS-320-TT1
FCS-320-TP2 FCS-320-TT2
Maximum pipe length 300m 2 x 280m
Maximum number of air sampling openings 32 2 x 32
Maximum size of monitoring area 2880m
2
5760m
2
Permissible temperature range
PVC pipe system 0°C to +60°C
ABS pipe system -40°C to +80°C
3.8.3 Smoke Aspiration System Components
Water separator (FAS‑ASD‑WS)
Features For use in areas with very high humidity
Plastic housing with manual drain valve
Sintered metal filter
PG cable glands for 25mm pipe system
Incl. assembly bracket
Dimensions (H x W x D) 210 x 170 x 90mm
Weight Approx. 1.4kg
30 en | Technical Specifications Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
Filterbox, large (FAS‑ASD‑FL)
Features For use in areas with increased exposure to dust
Incl. filter set and two PG29 cable glands
Housing material ABS plastic
Housing color Light gray RAL 7035
Dimensions (H x W x D) 194 x 122 x 96mm
Application temperature range
-30°C to +70°C
Replacement filter set, large (FAS‑ASD‑RFL)
Features Set comprising one fine, one medium and one coarse filter
insert (60ppi, 45ppi and 25ppi)
Application temperature range
-30°C to +70°C
Detonation safety barrier (FAS‑ASD‑DSB)
Type PROTEGO Type EG IIA
Explosion group II A
Flame filter 3-way
Gap width 0.7mm
Pipe connection thread G 3/4 inch, incl. transition thread on one side for connecting
to the aspiration pipe system
Length x diameter 112mm x 80mm
Certification EC type-tested
Three way tap (FAS‑ASD‑3WT)
Features With 3 transition threads for connection to a 25mmpipe
system
Operating pressure Max. 10bar
Housing material PVC plastic
Seal Teflon (PTFE)
Length 131mm
Application temperature range
0°C to +50°C
Ceiling lead-through (FAS‑ASD‑CLT) with aspiration hose (FAS‑ASD‑AHC)
Maximum false ceiling thickness
35mm
Loading...
+ 104 hidden pages