The EVX-BA provides a means to switch in a backup amplifier in the event of a primary amp failure. One backup amp can be provided in reserve for several primary amps. Amplifier outputs are connected at TB2, and speaker field wiring at TB1. Supervisory and 24 VDC power inputs are provided at TS1. The LED on-board activates when the backup amp has been switched in. All wiring is power-limited. Mounts to snaptrack or 5/8” nylon standoffs.
The EVX-BA is compatible with both 25VRMS and 70VRMS audio signals.
Mounting: The EVX-BA is mounted in the same cabinet that houses the primary amplifier. It is designed to be mounted into standard 3” snap track material. The board also has mounting holes at the corners for stand-off mounts where necessary. 5/8” nylon standoffs are required.
TS1:
Ter. 1 - Ckt. Neg Ter. 2 - +24 VDC Ter. 3 - Gen Input Ter. 4 - +24 VDC
TB1:
Ter. 1 & 2 - Audio Output
TB2:
Ter. 1& 2 - Audio Input from backup
amplifier
Ter. 3&4 - Audio Input from primary amplifier
JUMPERS: J1: jumps TS1-2 to TS1-4
LED
TB1
TS1
J1
Fig. 1 - Board
4 3 2 1
1
2
SPECIFICATIONS:
Power: 24 VDC Current: 40 mA Standby 10 mA Active
1
+
-
2
3
+
4
-
TB2
BA-100 Rev C
P/N 1-5030 REV. B
Fig. 2 - Typical Connection Detail
LED activates when
backup audio is
switched in
Install jumper J1
to eliminate
TS1 2 - 4 connection
+
-
Speaker Output
FROM PRIMARY AMP
TB-2
TB-3#7TB-2
#10
TS1
4 3 2 1
LED
J1
TB1
#1
+
-
+
-
NOTE:
If primary amplifier is an
EVX-25, EVX-50, or EVX-100
place dipswitch #5 on SN-2
of that amp DOWN
If primary amplifier is an
EVX-25E, EVX-50E, or EVX-100E
place dipswitch #5 on SN-1
of that amp DOWN
Backup amp
EOLR at last EVX-BA
Input from backup amplifier (TB-1 #5-6)
Input from primary amplifier (TB-1 #5-6)