Bosch EVX-25EM, EVX-25E, EVX-2ZA, EVX-25, EVX-100EM Specsheet

Fire Alarm Systems | Bosch Voice Evacuation Systems
Bosch Voice Evacuation Systems
Digitally-recorded automatic evacuation message (up
to 4 minutes of message capacity)
Alarm and alert signals
Live microphone override of message and tone
Compatible with 12 V or 24 V, analog‑addressable or
microprocessor-based fire alarm control panels (FACPs)
Clean dead-front construction
Easy installation and operation
24-hour backup with 7 Ah batteries installed
(batteries not supplied)
The Bosch Voice Evacuation systems and expansion panels provide a variety of options that can be easily added to an existing fire alarm control panel system for area of assembly applications and for high-rise voice evacuation not requiring firemens' phones. Choose up to 2000 W of audio amplifier power to meet your speaker power requirements. You can supervise multiple zones through your choice of zone splitters.

Functions

Digital Message Repeater
Each of the Bosch voice evacuation systems (EVAX25, EVAX50, EVAX100, EVAX150, and EVAX200) includes a digital message repeater (DMR). The systems come with the following standard 15-second message programmed: "Attention, please. There has been a report of an emergency. Proceed calmly to the nearest exit and leave the building immediately. Do not use the elevators; use stairwells where necessary. All handicapped occupants shall use the building evacuation plan." The voice evacuation message is broadcast until the FACP resets or until emergency personnel interrupt the broadcast with a manual page. When the FACP resets, the voice evacuation system automatically returns to normal operating condition.
The closure of a contact from either the FACP or from any normally-open contact device can cause the broadcast of a chime tone followed by the message "All clear." Optional primary and secondary messages are available. For further information, refer to the Bosch Voice
Evacuation System's Optional Messages Technical Service Note (P/N: F01U500869).
Remote Paging Microphones
Remote paging microphones (up to five per EVX-SC supervisory card) are supported through a supervised circuit. Remote microphones may be mounted up to 5000 ft (1.5 km) away from the EVAX voice evacuation panel. An ideal use for a remote microphone is when the FACP and voice evacuation system panels are in an electrical room and you need a microphone in the lobby.
System Settings
Control system operation by DIP switch settings:
Configure three DIP switches to determine alert tones
of Temporal Slow Whoop (default), Hi Lo, Horn, Bell, or 1 kHz. Turn the Diagnostic Mode on or off (default).
Set the AC Power Failure Report for no delay (default)
or for a six-hour delay.
www.boschsecurity.com
2 | Bosch Voice Evacuation Systems
Indicate if batteries are connected to the system. The
default setting is batteries are connected. Indicate if a microphone is connected to the system.
The default setting is a microphone is connected. Set the initial delay before a message starts for no
delay, 4-second delay, 8-second delay (default), 12­second delay, 16-second delay, 20-second delay, 24­second delay, or 28-second delay. The chosen tone sounds during the delay. Set the delay between repeats of the message for a
4-second delay, 8-second delay, 12-second delay (default), or 16-second delay. Indicate if the message plays or not. Message on is
the default. Set the number of times the message plays to one
play, two plays, three plays (default), or continuous play.

System Overview

BOSCH Voice Evacuation Systems
All Bosch voice evacuation systems include all the necessary features to provide an effective voice evacuation system:
Audio amplifier
Digital message repeater (DMR)
120 VAC power transformer and battery charger
Tone generator
Paging microphone
Surface-mount or semi-flush-mount enclosure with a
hinged, key-locked door in charcoal-gray (standard)
or red (optional) The EVAX25, EVAX50, and EVAX100 respectively provide 25 W, 50 W, and 100 W of audio amplifier power in a standard-size enclosure. The EVAX150 has one 50 W audio amplifier and one 100 W audio amplifier in a double-size enclosure. The EVAX200 has two 100 W amplifiers in a double-size enclosure. Customize these systems to satisfy most application requirements by adding expander panels, expander modules, or zone splitters. Expanders can be grouped together in any combination to provide up to 2000 W of audio power.
Tone generator
Paging microphone
Standard-size enclosure with a hinged, key-locked
door The EVAX150E and EVAX200E expander panels provide the same features with additional power in a double-size enclosure housing two amplifier modules. Use the EVAX25EM, EVAX50EM, or EVAX100EM expander panel when a 25 W, 50 W, or 100 W audio expander is needed with its own enclosure. Use the EVAX150EM and EVAX200EM for expansion when greater power is required in the larger enclosure configuration. The EM models have all the features of the E models except they are without a paging microphone.
Optional Expander Modules
The expander modules (EVX- models) can increase the capacity of any Bosch voice evacuation system or expander panel. They do not have paging microphones and are intended for installation in UL Listed enclosures (not supplied). Features of these modules:
Audio amplifier
Power regulator and battery charger
Tone generator
Optional Zone Splitters
The EVX-4Z and EVX-2ZA zone splitters allow the supervised output of any Bosch audio amplifier to supervise multiple zones. Features of these zone splitters:
Manual selection of any or all voice evacuation zones
for emergency paging
Automatic selection of voice evacuation zones by
connecting normally-open contacts from the FACP or
other auxiliary control system
Annunciation of either active or faulted zone status by
individual LEDs
Compatibility with jumper-selectable 25 V and 70 V
amplifier outputs The EVX-4Z has four Class B zones. The EVX-2ZA has two Class A zones.

Certifications and Approvals

Optional Expander Panels
The Bosch system expander panels provide an easy and cost-effective way to increase the output power of a Bosch voice evacuation system. They can also provide a manually-activated emergency paging panel for buildings. Features of the EVAX25E, EVAX50E, and EVAX100E:
Audio amplifier
120 VAC power transformer and battery charger
Listings and Approvals:
EVAX-25 CSFM 6911-1615: 101
EVAX-50 and 50E CSFM 6911-1615: 103
EVAX-100 and 100E CSFM 6911-1615: 104
EVX-2ZA and EVX-4Z CSFM 6912-1615: 102
UL UOXX and UOXX2: Control Unit Accessories, System (UL864)
Bosch Voice Evacuation Systems | 3

Installation/Configuration Notes

Compatible Products
The following products are compatible with the Bosch Voice Evacuation Systems:
Category Product
Expansion EVX-25 25 W Amplifier with DMR and microphone
Modules EVX-25E 25 W Amplifier without DMR, with microphone
EVX-25EM 25 W Amplifier without DMR and microphone
EVX-50 50 W Amplifier with DMR and microphone
EVX-50E 50 W Amplifier without DMR, with microphone
EVX-50EM 50 W Amplifier without DMR and microphone
EVX-100 100 W Amplifier with DMR and microphone
EVX-100E 100 W Amplifier without DMR, with microphone
EVX-100EM 100 W Amplifier without DMR and microphone
Remote EVX-RM Charcoal-gray Remote Microphone Panel
Microphone EVX-RMR Red Remote Microphone Panel
Zone EVX-2ZA Class A Zone Splitter
Splitters EVX-4Z Class B Zone Splitter
Speaker Placement
Choose speakers that deliver a minimum ambient sound of 15 dB above the normal ambient noise level. In high­ambient noise areas, speakers should be tapped at 15 dB to 21 dB above the ambient noise level and placed closer to one another to ensure that voice messages are intelligible. The best way to determine speaker placement needs is to conduct a site survey with a decibel meter to measure ambient noise levels; however, some general rules for speaker placement are:
Locate speakers at all pull stations and in main
corridors similar to the layout of conventional fire horns. Ensure that all occupied locations are within 50 ft
(15 m) of a speaker. Place additional speakers in rooms such as cafeterias and computer rooms. Be sure there are speakers in isolated areas where service personnel might be working. For ceiling-mount speakers, use 2 W of speaker power
for every 2000 ft2 (186 m2) of area covered in open areas and 2 W for every 1500 ft2 (139 m2) in divided areas. For wall-mount speakers, use 1 W of speaker power for every 2000 ft2 (186 m2) of area covered in open areas and 1 W for every 1500 ft2 (139 m2) in divided areas.
Speaker Power Requirements
System power (total wattage) must be sufficient to supply the power required by all of the speakers on the system. Speaker transformers can often be tapped for different wattages (usually, ¼ W, ½ W, 1 W, etc.). A
system rated at 25 W of audio power can power a speaker load of 25 W. This can be made up of 25 speakers each tapped at 1 W, 50 speakers each tapped at ½ W, or any mathematical combination that is less than or equal to 25 W.
Speaker Wiring Requirements
The 25 V speaker circuits of most voice evacuation systems are classified as power-limited wiring and can be run with other fire alarm wiring without ill effects. No special cabling is required. Standard power-limited fire alarm cable (FPL) is sufficient for most applications; however, certain addressable systems can generate extraneous noise from their addressable loop. Because these addressable systems cannot use shielded cable, shielding of the evacuation speaker circuit helps to eliminate noise picked up and heard in the speakers. When using 70 V circuits, separate them as described in the National Electrical Code. Generally, 18 AWG (1.0 mm) wire is adequate for speakers. Heavier wire is needed if loads are high or the runs are long. The following table indicates typical wire lengths for specific wire sizes and speaker loads. It assumes that there is an even distribution of speaker load and that a 20% drop at the last device is allowable.
25 VRMS Output:
Power 18 AWG
(1.0 mm)
10 W 1900 ft
(579 m)
15 W 1280 ft
(390 m)
25 W 760 ft
(232 m)
70 VRMS Output:
Power 18 AWG
(1.0 mm)
10 W 15200 ft
(4633 m)
15 W 10130 ft
(3088 m)
25 W 6080 ft
(1853 m)
16 AWG (1.3 mm)
3050 ft (930 m)
2030 ft (619 m)
1220 ft (372 m)
16 AWG (1.3 mm)
24200 ft (7376 m)
16130 ft (4916 m)
9680 ft (2950 m)
14 AWG (1.6 mm)
4850 ft (1478 m)
3230 ft (985 m)
1930 ft (588 m)
14 AWG (1.6 mm)
38360 ft (11692 m)
25570 ft (7794 m)
15340 ft (4676 m)
12 AWG (2.0 mm)
7700 ft (2347 m)
5140 ft (1567 m)
3080 ft (939 m)
12 AWG (2.0 mm)
61100 ft (18623 m)
40730 ft (12415 m)
24440 ft (7449 m)
System Power Requirements
All Bosch voice evacuation systems require 120 VAC connected to the system's power transformer. Standby power is supplied, in case of AC power failure, by standby batteries (not supplied). The EVAX25, EVAX50, and EVAX100 require two 12 VDC, 7 Ah standby batteries. The EVAX150 and EVAX200 require four 12 VDC, 7 Ah standby batteries.