Bosch CRC200 Installation Instructions For Contractors

Page 1
Installation instructions for contractors
CRC200
6 720 811 153-00.1O
Comfort Room Controller
6 720 821 651 (2017/05)
Page 2
6 720 821 651 (2017/05) CRC200
Contents
1 Explanation of symbols and safety instructions . . . . 3
1.1 Guideline to symbols . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Product Information . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1Control types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2Possible applications in different heating systems 5
2.2 Important instructions for use . . . . . . . . . . . . . . . . 6
2.3 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Applicability of the technical documentation . . . . 7
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Power connection . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Attaching or removing the user interface . . . . . . 10
4 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Basic settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Checklist: Important settings for commissioning 14
6 Switching off power . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 System data menu . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.2 Heating zone menu . . . . . . . . . . . . . . . . . . . . . . . . 19
8.3 Function test menu . . . . . . . . . . . . . . . . . . . . . . . . 23
8.4 Info menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.5 Maintenance menu . . . . . . . . . . . . . . . . . . . . . . . . 25
8.6 System info menu . . . . . . . . . . . . . . . . . . . . . . . . . 25
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10 Environmental protection/disposal . . . . . . . . . . . . . . 28
11 Setup log (Service menu/contractor) . . . . . . . . . . . . 29
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Page 3
6 720 821 651 (2017/05)CRC200
Explanation of symbols and safety instructions | 3
1 Explanation of symbols and safety
instructions
1.1 Guideline to symbols
Warnings
The following keywords are defined and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
Important information
Additional symbols
1.2 Safety instructions
These installation instructions are intended for competent persons who are skilled in dealing with water installations, heating and electrical systems.
▶ Read the installation instructions
(heat sources, modules, etc.) before starting the installation.
▶ Observe safety instructions and
warnings.
▶ Observe national and regional
regulations, technical rules and guidelines.
▶ Document all work performed.
Designated use
▶ Use the product only to control
heating systems in single- or multi­family dwellings.
Any other use is considered improper. Any resulting damage is excluded from the manufacturer's warranty.
Installation, commissioning and maintenance
Installation, commissioning and maintenance may be performed only by a licensed contractor.
▶ Never install the product in wet areas. ▶ Install only genuine spare parts.
Electrical work
Electrical work may be carried out only by qualified electricians.
▶ Before starting electrical work:
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
This symbol indicates important information where there is no risk to people or property.
Symbol Function
Sequence of steps Cross-reference to other points in this
document or to other documents
Listing/list entry – Listing/list entry (2nd level)
Outdoor temperature dependent function Flashing display (e. g. flashing 1)
Table 1 Additional symbols
6 720 811 156-11.1O
HC assignment
HC assignment
Page 4
6 720 821 651 (2017/05) CRC200
4 | Product Description
– Isolate all poles and secure against
unintentional reconnection.
– Ensure the system has been
disconnected from the power supply.
▶ Never connect the product to line
voltage.
▶ Also observe the connection
diagrams for other system components.
Handing over to the operator
Installing contractor - Please train the end user in proper use of this product.
▶ Explain operation – especially all
safety-related actions.
▶ Point out that conversion or repair
may be carried out only by a licensed contractor.
▶ Provide a copy of these installation
and operating instructions to the end user for future reference.
Risk of damage from frost
The system can freeze if it is switched off:
▶ Observe the instructions for frost
protection.
▶ Always leave the system switched on
for additional functions, e. g. water heating or anti-seize protection.
▶ Immediately correct any faults that
occur.
2 Product Description
2.1 Product Information
The user interface is used to control a heating zone and a DHW tank charging circuit for water heating directly at the heat source.
The user interface incorporates a time program: – Preset for the heating zone, but freely adjustable with 6
switching times per day
– Water heating may be controlled with or without time
program.
The user interface displays information about the heat source and heating system and is used to change the settings.
Installation options: On the wall with a BUS connection to a heat source or CZM100 module with an EMS-BUS Interface (Energy Management System).
After operating for 1½ hours, the user interface has a power reserve of at least four hours. If the power failure lasts longer than the power reserve, the time and date will be deleted. All other settings are retained.
The functional scope and thus the menu structure of the user interface are determined by the structure of the system. Your attention is drawn to the importance of the system structure at the relevant places in these instructions. The control ranges and factory settings may differ from the information in these instructions.
2.1.1 Control types
The following control options are available:
Outdoor reset operation ( ):
simple outdoor reset control
optimized outdoor reset control.
This operation requires additional optional outdoor sensor accessory
Room temperature-dependent operations:
supply temperature control
power output control
The supply temperature is adjusted using the heating curve in outdoor reset controls ( ) (with or without room
Functions that are relevant only in conjunction with the outdoor temperature are identified by a corresponding symbol ( ).
There are boilers that have integrated outdoor reset controls. In such boilers, the outdoor reset control must be deactivated.
Page 5
6 720 821 651 (2017/05)CRC200
Product Description | 5
temperature influence). Simple and optimized variants are available. In the simple outdoor reset control ( ) the heating curve is a straight line. In the optimized outdoor reset control ( ) the heating curve is an actual curve. The relationship between the outdoor temperature and the supply temperature is therefore very precise.
Supply temperature control and output control are available for room temperature-dependent control. With supply temperature control, the CRC200 reacts to a difference between the current and the required room temperature by changing the supply temperature. This method of control is suitable for apartments and residential houses. With power output control, which is possible only in systems with one heating zone and no CZM100, the CRC200 reacts to a difference between the current and the required room temperature by changing the heat output of the heat source. There are fewer burner starts and shorter pump runtimes. This saves energy and enhances the boiler’s and the pump’s lifetime.
2.1.2 Possible applications in different heating systems
Heating system with one CRC200
Fig. 1 Example of a heating system with one heating zone
HC 1 and a CRC200 as controller (single-family home)
The CRC200 serves as the controller for heating systems with one heating zone and water heating ( Fig. 1). The user interface is installed in a suitable living space.
Heating systems with several CRC200
Fig. 2 Example of a heating system with three heating
zones with one CZM100 and one CRC200 per zone as the controller.
Usually, in heating systems with several heating zones, each zone is individually controlled by a CRC200 ( Fig. 2). In this case, the following applies:
Each CRC200 controls its heating zone independently. In other words, the CRC200 controls the assigned heating zone completely (e. g. HC 3, Fig. 2) in terms of room temperature, time program, vacation program and immediate tank charging. In addition to the automatic mode, manual operation is also possible.
Central settings are adopted from the CRC200 in the first heating zone. This includes parameterization of water heating and the low loss header / header sensor. This means that water heating settings for the storage tank temperature and thermal disinfection are made in heating zone 1 on the CRC200. On the CRC200 for heating zones 2 ... 8, it is possible to set one operating mode for water heating. The heat source selects the highest value from the set point values received. In addition, manual override for tank charging is possible. When the system is operating, all requests from the individual CRC200 are processed, i. e. each request for hot water is implemented. If the vacation program is active in the CRC200 for heating zone 1, only the assigned first heating zone and the hot water set point in the CRC200 for heating zone 1 are affected. Water heating is still based on the set point values in the CRC200 for heating zones 2 ... 8. This ensures on-demand heating and availability of hot water for each heating zone based on the settings in each individual CRC200.
HC 1
CRC200
HC 1
6 720 811 153-03.1O
CRC200
HC 2
HC 3
HC 1
6 720 811 156-01.1O
CZM100
CRC200
CRC200
Page 6
6 720 821 651 (2017/05) CRC200
6 | Product Description
2.2 Important instructions for use
The user interface may be connected only to heat sources with Bosch EMS-BUS or CZM100 for multi-zone applications.
This user interface is intended only for wall-mounted installation ( Chapter 3, starting at page 7).
2.3 Scope of delivery
Fig. 3 Scope of delivery
[1] User interface [2] Technical documentation [3] Screws and anchors
WARNING: Risk of scalding! ▶ If hot water temperatures are set above
140 °F (60 °C) or thermal disinfection is switched on, a mixer must be installed.
NOTICE: Risk of damage to the floor! ▶ Radiant floor heating must be installed
only as a heating zone with mixer and an additional temperature switch to protect the floor from overheating, by delivering too hot supply water.
6 720 811 156-02.1O
B U S
B U S
i
i
1
2
3
Page 7
6 720 821 651 (2017/05)CRC200
Installation | 7
2.4 Technical Data
Fig. 4 Dimensions
2.5 Accessories
Function modules of the EMS control system:
CZM100: Zone module for up to three heating zones
Outdoor temperature sensor for outdoor reset control
types or WWSD (Warm Weather Shut Down) and frost protection.
Only compatible with the following products:
CRC100 and CZM100
Applicability of these instructions to EMS-capable modules
These instructions also apply to the user interface when used in conjunction with CZM100 (accessory).
2.6 Applicability of the technical documentation
All information related to BUS systems and heating controllers contained in the technical documentation of e.g. heat sources applies also to the present user interface.
3 Installation
The detailed system schematics for mounting the hydraulic assemblies and the associated control devices can be found in the installation manual of CZM100.
3.1 Installation location
The room in your home where the controller is installed is the reference room. If room temperature-dependent control is active, the room temperature in this room serves as the reference variable for the entire system. If the outdoor reset control is enabled to factor in the room temperature, the room temperature functions as an additional reference variable.
The control quality depends on the installation location.
6 720 811 153-08.1O
3 3/4"
95 mm
3 3/4"
95 mm
63/64"
25 mm
1 5/16" 33 mm
Dimensions (W × H × D) 3 3/4" × 3 3/4" × 1 5/16"
(95 × 95 × 33 mm) ( Fig. 4)
Rated voltage 8 ... 16 V DC Nominal current 6 mA BUS interface EMS (2-wire BUS) Control range 41 ... 86 °F (5 ... 30 °C) Permissible ambient
temperature
32 ... 122 °F (0 ... 50 °C)
Protection class III Protection IP20
Table 2 Technical Data
DANGER: Risk of electric shock! ▶ Before installing this product:
Disconnect the heat source and all other BUS users from the line voltage across all poles.
This user interface is intended only for wall­mounted installation. Do not install in the heat source.
Page 8
6 720 821 651 (2017/05) CRC200
8 | Installation
The installation location (= reference room) must be suitable for controlling the zone ( Fig. 5, Page 8).
The user interface must be installed on an interior wall.
Do not place obstructions within 2 1/2' (0.75 m) below CRC200.
Fig. 5 Installation location in the reference room
If there is no suitable reference room, we recommend changing the settings to a purely outdoor temperature dependent control.
6 720 811 153-03.1O
≥ 4'
(≥ 1.2 m)
2'
(0.6 m)
≥ 3 1/4' (≥ 1 m)
2 1/2'
(≥ 0.75 m)
Page 9
6 720 821 651 (2017/05)CRC200
Installation | 9
3.2 Installation
Fig. 6 Mounting the base
3.3 Power connection
Power is supplied to the user interface via EMS BUS.
Connections are not polarity specific.
Maximum total length of the BUS connections with AWG18 (0.75 mm
2
): 492 ft. (150 m)
▶ If several BUS users are installed, maintain a minimum
clearance of 4" (100 mm) between the individual BUS users.
▶ If several BUS users are installed, connect the BUS users in
series or in a star pattern.
▶ To avoid inductive interference: Make sure all low-voltage
cables are routed separately from line voltage cables (min. clearance 4" / 100 mm).
▶ In the case of outside inductive effects, use shielded cable
and ground one end of the shield. Do not connect the shield to the connecting terminal for the ground conductor in the module; use the building ground instead, e.g. unused grounded terminal or water pipe.
▶ Establish a BUS connection to the heat source.
Fig. 7 Connection of the user interface to a heat source
1) Terminal identification: On heat sources with an EMS BUS system terminals are: BUS or BB
The outdoor temperature sensor (accessory) needs to be connected to the heat source.
▶ Observe the instructions for the heat source when
connecting the electrical supply.
When sensor leads are extended, apply the following lead cross-sections:
Up to 66 ft. (20 m) with AWG18 (0.75 mm
2
)
66 ft. (20 m) to 330 ft. (100 m) with AWG16 (1.50 mm
2
).
The installation surface on the wall must be flat. ▶ Install the base on a wall. ( Fig. 6).
If the maximum total length of the BUS connections between all BUS users is exceeded or the BUS system has a ring structure, commissioning of the system is not possible.
6 720 811 156-05.1O
18-2 AWG (2x 1mm²)
1/4" (6.35 mm)
1/4" (6.35 mm)
9/64" (3.5 mm)
CRC200
6 720 811 156-06.1O
BUS/
BB
1)
B U S
Page 10
6 720 821 651 (2017/05) CRC200
10 | Installation
3.4 Attaching or removing the user interface
Attaching the user interface
1. Attach the user interface at the top.
2. Snap the bottom of the user interface into the base.
Fig. 8 Attaching the user interface
Removing the user interface
1. Push the knob on the underside of the base.
2. Pull the bottom of the user interface forwards.
3. Remove the user interface by lifting upward.
Fig. 9 Removing the user interface
6 720 809 984-06.1O
1.
1.
2.
6 720 809 984-07.1O
3.
1.
2.
Page 11
6 720 821 651 (2017/05)CRC200
Controls | 11
4 Controls
Fig. 10 Controls
Item Element Designation Explanation
1 Dial ▶ Turn to change a setting value (e. g. temperature), or select from among the menus or
menu items.
▶ Press to open a menu or menu item, confirm a set value (e. g. temperature) or a
message.
2 auto button ▶ Press to activate the automatic mode with the time program.
3 man button ▶ Press to activate hold mode (manual operation) for a permanent room temperature set
point.
4 Back button ▶ Press to return to the higher menu level or discard a changed value.
▶ Hold down to switch from a menu to the standard display.
5 menu button ▶ Press to open the main menu.
▶ Hold down to open the service menu.
Table 3 Controls
6 720 809 984-40.1O
2
3
5
4
1
auto
man
menu
Page 12
6 720 821 651 (2017/05) CRC200
12 | Commissioning
5 Commissioning
▶ First make all electrical connections and then carry out the
commissioning.
▶ Observe the installation instruction for all components and
assemblies in the system.
▶ Switch on the power supply only after all modules are
coded.
▶ Set the heat source to the maximum supply temperature
and DHW temperature needed and activate the automatic mode.
▶ Switch on the system.
Commission the user interface as shown in Table 4.
The date, time and commissioning date are still present in the user interface when commissioning after a reset.
You can find an overview of all settings in Chapter 7, starting at page 15.
5.1 Basic settings
During the initial commissioning: Fill out the commissioning report in the operating instructions and in Chapter 11, Page 29.
Basic settings
Once the user interface is connected to the power supply, the language selection appears on the display. The current setting starts to flash.
▶ Turn the dial to set the language and then press the dial.
The display switches to the date setting. The current setting starts to flash. The user interface may obtain the current date automatically via the BUS system.
▶ Turn the dial to set the date and then press the dial. The format for displaying the date can
be changed ( operating instructions).
The display switches to the time setting. The current setting starts to flash. The user interface may obtain the current time automatically via the BUS system.
▶ Turn the dial to set the time and then press the dial. The format for displaying the time can
be changed ( operating instructions).
The display switches to the heating zone assignment. The current setting starts to flash.
▶ Press the dial in order to confirm the setting.
-or-
▶ If several CRC200 are installed in the system:Turn the dial to assign one of the heating
zones 2 to 8 and then press the dial.
The display switches to automatic configuration. The current setting starts to flash.
▶ Turn the dial to select YES and then press the dial.
Automatic configuration starts to detect the connected modules and temperature sensors. During automatic configuration the Auto-Config. display flashes
Without automatic configuration following menu items have to be configured additionally:
Pump conn. (only heating zone 1), Control type, Ext.RoomSens. and Solar module
Table 4 Basic settings
6 720 811 156-22.1O
english
english
6 720 811 156-21.1O
07/20/2014
07/20/2014
6 720 811 156-20.2O
Time of Day
Time of Day
6 720 811 156-11.1O
HC assignment
HC assignment
6 720 811 156-12.1O
Auto-Config.
Auto-Config.
Page 13
6 720 821 651 (2017/05)CRC200
Commissioning | 13
Following automatic configuration, the display switches to guided system configuration. Which settings are available during guided system configuration depends on the installed system.
While in guided system configuration you can press the Back button to switch to the previous menu item. A flashing display means you should turn the dial to change the setting or press the dial to confirm the shown setting.
Available only on the user interface for heating zone 1 (not visible when a combi boiler is used). DHW appears on the display. You can set wether a hot water system is installed or how it is installed. For further details see table 5.
▶ If the display is not flashing, press the dial. ▶ Turn the dial to change the setting. ▶ Press the dial to switch to the next setting.
Available only on the user interface for heating zone 1. LLH Sensor appears on the display. You can set wether a low loss header is installed and where its temperature sensor is connected. For further details see table 5.
▶ Press the dial to make the flashing default setting appear. ▶ Turn the dial to change the setting. ▶ Press the dial to switch to the next setting.
Available only on the user interface for heating zone 1. Recirculation appears on the display. You can set wether a recirculation pump is installed. For further details see table 5.
▶ Press the dial. ▶ Turn the dial to change the setting. ▶ Press the dial to switch to the next setting.
Heat. System appears on the display. You can set wether high temperature or low temperature heat radiation applies. For further details see table 5.
▶ Press the dial to make the flashing default setting appear. ▶ Turn the dial to change the setting. ▶ Press the dial to switch to the next setting.
Max. Suppl.T. appears on sthe display. You can set the maximum supply temperature. For further details see table 9.
▶ Press the dial. ▶ Turn the dial to change the temperature. ▶ Press the dial to switch to the next setting.
Frost protect appears on the display. You can set wether frost protection depends on room temperature or outdoor temperature. Outdoor temperature sensor must be installed for outdoor dependent frost protection. For further details see table 9.
▶ Press the dial to make the flashing default setting appear. ▶ Turn the dial to change the setting. ▶ Press the dial to switch to the next setting.
Basic settings
Table 4 Basic settings
6 720 811 156-30.1O
DHW
DHW
6 720 811 156-31.1O
No
No
6 720 811 156-32.1O
Recirculation
Recirculation
6 720 811 156-33.1O
High Temp
High Temp
6 720 811 156-34.1O
Max. Suppl. T.
Max. Suppl. T.
6 720 811 156-35.2O
by Room Temp.
by Room Temp.
Page 14
6 720 821 651 (2017/05) CRC200
14 | Switching off power
5.2 Checklist: Important settings for commissioning
Always perform commissioning so that the system operates as needed. Based on experience, the following settings are very important to satisfy the system user:
Control type: outdoor reset ( ) with or without the
influence of the room temperature, or room temperature­dependent
Heating curve ( ): Adapted with reference to the
design temperature, minimum outdoor temperature and other settings
DHW priority: A heat demand for hot water has priority or
hot water and heating have the same priority (if possible hydraulically)
Time program: Determines when heating is active, see
user manual for details.
How to change settings in the service menu is described in Chapter 8. Alternatively see the user manuals.
6 Switching off power
The user interface is powered via the BUS system and is always on. The system is switched off only for maintenance work, for example.
▶ Disconnect power from the entire system and all BUS
users.
Available only when outdoor sensor is connected and Frost protect is set to by Outdoor Temp or Room - Outside. Frost thresh. appears on the display. You can set the threshold outdoor temperatur for frost protection. For further details see table 9.
▶ Press the dial. ▶ Turn the dial to change the temperature. ▶ Press the dial to switch to the next setting.
Heating Start appears on the display. ▶ Press the dial. ▶ Turn the dial to select YES and press the dial.
Configuration has been completed. The installation date of the CRC200 is set automatically.
-or-
▶ Turn the dial to select NO and press the dial.
The system configuration continues.
Upon selecting YES the CRC200 is configured as a controller. The heating system and possibly water heating are operating. Following configuration, only the menu items relevant for the configured system are displayed.
Basic settings
Table 4 Basic settings
6 720 811 156-36.1O
Frost thresh.
Frost thresh.
6 720 811 156-14.1O
Heating start
Heating start
The installation date of the CRC200 is set automatically when the configuration is confirmed initially by starting the heating system.
After a prolonged power failure or extended period of idleness, the date and time may need to be reset. All other settings are retained permanently.
Page 15
6 720 821 651 (2017/05)CRC200
Main menu | 15
7 Main menu
▶ If the standard display is active, press the menu button
briefly to open or close the main menu.
▶ Turn the dial to select a menu item or change the value of a
setting.
▶ Press the dial to open the selected menu item, activate the
input field for a setting or confirm a setting.
Fig. 11 Main menu summary
1) Set language.
2) Available only on the user interface for heating zone 1.
3) Service menu ( Chapter 8)
Further information on operation/navigation in the main menu can be found in the operating instructions.
Main Menu
Heating Holiday Settings
Temperatures Holiday Prog. deutsch
1)
Heating Info Time/Date
Setback Heating Time of Day
Time program Outdoor Temp. Date
Reset Sched. Operat. stats Time correc.
Summer/Winter Room Temp. Format
Temp.thresh. DHW Date format
DHW Operat. stats Time Format
Tank loading Set temp. Temp. Format
Mode Actual Temp. Sensor calib.
Recirculation
2)
Contrast
Disinfection
2)
Service
3)
6 720 821 651-17.1O
Page 16
6 720 821 651 (2017/05) CRC200
16 | Service menu
8 Service menu
▶ If the standard display is active, press and hold the menu
button for about three seconds until the service menu appears in the main menu.
▶ Press the dial to open the already highlighted service
menu .
▶ Turn the dial to select a menu item or change the value of a
setting.
▶ Press the dial to open the selected menu item, activate the
input field for a setting or confirm a setting.
Fig. 12 Overview of the service menu
1) Available only on the user interface for heating zone 1.
2) Available if supported by heat source.
Main Menu PID charact. Room Temp.
Service Opt. pump run DHW Operation
System Data Room influence Set DHW Temp
HC assignment Contin. heat
DHW Temp.
Auto-Config. Frost protect Maintenance
Pump conn.
1)
Frost thresh. Maint.message
1)
Heat. System DHW Priority Maint. date
1)
Control type Function Test Reset Maint.
1)
Ext.RoomSens. Activation Current Fault
DHW
2)
System pump Fault History
LLH Sensor
1)
HC Pump Clear Fault
Recirculation
1)
Info System info
Solar module Outdoor Temp. Install.date
WWSD
1)
Appl. oper. Control unit
Min.outs.temp Appl.set sply Control SW
Damping Appl.act.sply SW controller
Building Type
Appl.max.sply HC Module SW
Reset All LLH Temp.
Heating circ. HC Operation
Design Temp. HC set.sply
Base line HC act. sply.
Base point
Set Room Temp
Max. Suppl.T.
6 720 821 651-18.2O
Page 17
6 720 821 651 (2017/05)CRC200
Service menu | 17
8.1 System data menu
The heating system is configured automatically or manually in this menu. With automatic configuration, important data are preset.
Menu item Default
setting
Control range Functional description
HC assignment 1 1 ... 8 Number of the assigned heating zone Auto-Config. NO NO | YES NO: Manual configuration of the system
YES: Automatic system configuration, detects connected modules and temperature sensors and presets important data.
Pump conn. see
desciption
Heat Source | HC Module
Heat Source: Heating pump connected to heat source (only for heating zone 1). Heat Source is default if no CZM100 is detected.
HC Module: Heating pump connected to CZM100. HC Module is default if CZM100 is detected.
Heat. System High Temp High Temp |
Low Temp.
Assign the heating system to the heating zone to cancel the factory default.
Control type Room supply External simple |
External opt. | Room supply | Room output
Select control type (details in Chapter 2.1.1, Page 4)
Outdoor reset operation ( ): External simple: simple outdoor reset control External opt.: optimized outdoor reset control
Room temperature-dependent operations: Room supply: supply temperature control Room output: power output control (not possible if CZM100 is detected).
Ext.RoomSens. NO NO | YES NO: The room temperature is determined by the internal temperature
sensor of the user interface. YES: An additional room temperature sensor connected to the user
interface (future feature; currently not available).
DHW
(factory settings depend on installed heat source)
No | Yes, 3-wy vlv | Yes, pr. pump
DHW is only available if supported by the heat source (not visible at combi boilers)
No: No hot water system installed in conjunction with boiler Yes, 3-wy vlv: Hot water system is supplied via 3-way valve Yes, pr. pump: Hot water system is supplied via indirect tank
LLH Sensor / System Supply Sensor
No No | Yes, on mod. LLH Sensor / System Supply Sensor is only available for heating zone 1
No: No low-loss header installed Yes, on mod.: Low-loss header installed (even if temperature sensor is
connected at heat source).
Recirculation NO NO | YES Recirculation is only available for heating zone 1
NO: The recirculation pump cannot be controlled by the heat source. YES: If the recirculation pump is to be controlled by the heat source, the
recirculation pump must be activated here as well.
Solar module NO NO | YES NO: No solar module connected.
YES: No function in US/CA; no solar module available
WWSD 70 °F (21 °C) OFF | 50...86 °F
(10...30 °C)
Heating is off in the entire system at this set outdoor temperature. This saves energy at higher outdoor temperatures. (only for heating zone 1)
Table 5 Settings in the system data menu
Page 18
6 720 821 651 (2017/05) CRC200
18 | Service menu
Minimum outside temperature (outdoor design)
The minimum outside temperature is the average value of each of the coldest outside temperatures or recent years, and it has an influence on the heating curve. The value of the region can be taken from the required heat load calculation that should be done for every building, or from the climate zone chart
▶ Set the minimum outside design temperature for the
heating system.
Min.outs.temp ()
14 °F ( – 10 °C)
– 31...50 °F ( – 35...10 °C)
Minimum outdoor temperature is the outdoor design temperature used in the heat loss calculation; only available when an outdoor temperature sensor is connected and outdoor reset mode is enabled.
Damping ( ) ON ON | OFF This setting is only available when an outdoor temperature sensor is
connected and outdoor reset mode is enabled. ON: The set type of building affects the measurement of the outside
temperature. The outside temperature is delayed (dampened). OFF: The measured outside temperature is included undampened in the
outdoor reset control.
Building Type ()
Medium Tight | Medium |
Loose
A measure of the thermal storage capacity of the heated building Tight: High storage capacity such as a brick house with thick walls
(significant damping of the outdoor temperature) Medium: Medium storage capacity Loose: Low storage capacity such as a non-insulated weekend house made
of wood (low damping of the outdoor temperature)
Reset All NO NO | YES NO: The current settings have been retained.
YES: The factory settings are being restored (except time and date).
Menu item Default
setting
Control range Functional description
Table 5 Settings in the system data menu
Minimum outside temperature in °F ( °C)
Atlantic City 5 ( – 15) Montreal – 9 ( – 23) Anchorage New Orleans 19 ( – 7) Bermuda 59 (15) New York 0 ( – 18) Boston 0 ( – 18) Ottawa – 9 ( – 23) Buffalo – 5 ( – 21) Philadelphia 0 ( – 18) Cleveland – 4 ( – 20) Phoenix 25 ( – 4) Chicago – 9 ( – 23) Pittsburgh – 4 ( – 20) Dallas 10 ( – 12) Portland – 5 ( – 21) Detroit – 9 ( – 23) Quebec – 15 ( – 26) Honolulu 59 (15) Richmond 15 ( – 9) Houston 19 ( – 7) San Diego 35 (2) Indianapolis – 10 ( – 23) San Francisco 36 (2) Los Angeles 36 (2) St. Louis 0 ( – 18) Miami 36 (2) Toronto – 9 ( – 23) Minneapolis – 20 ( – 29) Washington 0 ( – 18)
Table 6 Minimum outdoor temperature for USA
Page 19
6 720 821 651 (2017/05)CRC200
Service menu | 19
8.2 Heating zone menu
Settings for the heating zone are made in this menu. With automatic configuration, important data are preset. Afterwards, only the relevant menu items appear in this menu.
Example: In case of outdoor reset control, the menu item for room temperature-dependent control is not displayed.
NOTICE: Risk of damaging or destroying the screed!
▶ If radiant floor heating (Low Temp.) is
installed, observe the maximum supply temperature recommended by the manufacturer.
Menu item default setting Control range Functional description
Design Temp ()
113 °F (45 °C) 86...140 °F (30...60 °C)
(with Low Temp. heating) | 86...185 °F (30...85 °C) (only High Temp)
Only visible if Control type = External opt. (Optimized outdoor reset control) is selected:
This is the supply temperature requested at the outdoor design temperature (see setting Min.outs.temp). The control range depends on the heating system selected.
Base point ()
77 °F (25 °C) 68 °F (20 °C) ... End
point (with Low Temp. heating)
Only visible if Control type = External simple (simple outdoor reset control) is selected:
This is the supply temperature at fixed outside temperature of 68 °F (20 °C). The range is limited by the setting of the End point.
End point ( ) 113 °F (45 °C)
(with Low Temp. heating)
Base point ... 140 °F (60 °C) (with Low Temp. heating)
Only visible if Control type = External simple (simple outdoor reset control) is selected:
This is the supply temperature requested at the outdoor design temperature (see setting Min.outs.temp). The range is limited by the setting of the Base point.
167 °F (75 °C) (with High Temp heating)
Base point ... 185 °F (85 °C) (with High Temp heating)
Max. Suppl.T. 118 °F (48 °C)
(Low Temp. heating) | 167 °F (75 °C) (only High Temp)
86...140 °F (30...60 °C) (with Low Temp. heating) | 86...185 °F (30...85 °C) (only High Temp)
Maximum supply temperature; the control range depends on the heating system selected.
PID charact. Medium Fast | Medium | Slow Control characteristics (only visible when room temperature-
dependent control is selected):
Fast: Fast (2k P range), older home, loose construction, limited insulation
Medium: Average (3k P range), Minimum building requirements, medium construction
Slow: Slow (4k P range), newer home, tight construction, well insulated
Opt. pump run NO NO | YES YES: Optimized pump operation active: The heating pump runs
as little as possible on the basis of the supply temperature (available only with supply temperature control). This saves energy but may also reduce comfort.
NO: If the system has more than one heat source installed (e. g. a hybrid system) or a buffer storage tank is installed, this function must be deactivated.
Table 7 Settings in the heating zone menu
Page 20
6 720 821 651 (2017/05) CRC200
20 | Service menu
Threshold temperature for frost (frost protection limit temperature)
Room Feedback ()
6 °F (3 °C) OFF | 2 ... 18 °F
(1...10 °C)
The outdoor reset control functions independent of the room temperature.
The higher the setting value, the greater the influence of the room temperature on the heating curve.
Contin. heat ()
OFF OFF | – 22...50 °F
( – 30...10 °C)
At this set outdoor temperature, setback no longer occurs. The system operates in the heating mode to prevent greater cooling.
Frost protect by Room Temp. OFF |
by Outdoor Temp ( ) | by Room Temp. | Room ­Outside ( )
Note: To ensure frost protection for the heating zone, set outdoor temperature-dependent frost protection. This setting is independent of the set control type.
Outdoor temperature-dependent settings are only shown with connected outdoor temperature sensor.
OFF: Frost protection off Other: Frost protection is deactivated/activated on the basis of
the temperature selected here ( Threshold temperature for frost (frost protection limit temperature), Page 20)
Frost thresh. 41 °F (5 °C) – 4...50 °F
( – 20...10 °C)
Threshold temperature for frost (frost protection limit temperature), Page 20
DHW Priority ON ON | OFF ON: Water heating is activated, the heat demand of the heating
system is canceled OFF: Water heating is activated, the heat demand of the heating
system is being met simultaneously (only possible if the hot water system is supplied via the tank pump)
Menu item default setting Control range Functional description
Table 7 Settings in the heating zone menu
NOTICE: Risk of destroying hot water­conducting system components if the threshold temperature for frost is set too low and room temperatures are below 32 °F (0 °C)!
▶ Only contractors are permitted to adjust
the factory setting of the frost threshold temperature (41 °F / 5 °C) for the system.
▶ Do not set the threshold temperature too
low. Damage resulting from a frost threshold temperature set too low is not covered under warranty!
▶ Assured frost protection of the system is
not possible without an outdoor temperature sensor.
Outdoor temperature-dependent settings are only shown with connected outdoor temperature sensor.
Page 21
6 720 821 651 (2017/05)CRC200
Service menu | 21
With an outdoor temperature-dependent frost threshold temperature ( ) with or without the effect of room temperature , the following applies:
If the outdoor temperature exceeds the set threshold temperature by 2 °F (1 K / °C) and there is no heat demand from the heating system, the heating pump switches off.
If the outdoor temperature drops below the set threshold temperature, the heating pump switches on (system frost protection).
With a room temperature-dependent frost threshold temperature, the following applies:
If the room temperature exceeds 45 °F (7 °C) and there is no heat demand from the heating system, the heating pump switch is off.
If the room temperature drops below 41 °F (5 °C) the heating pump switches on (no system frost protection).
With a room- /outdoor temperature-dependent frost threshold temperature ( ), the following applies:
If the room temperature drops below 41 °F (5 °C) or if the outdoor temperature drops below the set threshold temperature, the heating pump switches on (system frost protection).
Set the heating system and heating curve for outdoor reset control
▶ Heating type (High Temp or Low Temp. heating) in the
System Data > Heat. System menu. Adjust the system.
▶ Set the control mode (optimized or simple heating curve) in
the System Data > Control type menu ( ). Menu items that are not required for the selected heating system and control mode are hidden.
The heating curve is the decisive basic factor for an economic and convenient operation of the heating system with outside temperature compensated control. To calculate the heating curve, the control system requires you to enter a number of parameters for the heating system, from which it automatically calculates the optimum heating curve by means of a mathematical formula.
This calculation takes into account the “damped” outside temperature and the room control temperature. The room control temperature is an internal parameter based on the desired room temperature (set room temperature) and the room influence factor.
This allows the end customer to influence the heating curve directly by modifying the set room temperature.
The most important settings are the design temperature, maximum supply temperature and minimum outdoor temperature.
The heating curve ( fig. 13 and 14) is determined by the base point and end point. The base point exists with an adjusted outside temperature of 68 °F (20 °C) with a supply temperature of 77 °F (25 °C) (at a room temperature of 70 °F (21 °C)). The end point of the heating curve must be set according to the design temperature of the heating system.
The gradient of the characteristic heating curve (slope) is determined by the parameters Min.outs.temp (the lowest outdoor temperature expected in a particular region; page 18) and the Design Temp (the supply temperature which is to be reached at the minimum outside temperature) ( fig 13 and 14, left).
The heating curve can be shifted up or down in parallel by matching the set room temperature ( fig 13 and 14, right).
The by Room Temp. setting does not offer absolute frost protection, because piping installed in soffits, for instance, can freeze. This can happen even though the temperature in the reference room is considerably above 41 °F (5 °C) as the result of outside heat sources. If an outdoor temperature sensor is installed, frost protection can be assured for the entire heating system regardless of the control type set:
▶ In the Frost protect menu, set either by
Outdoor Temp or Room - Outside ().
Page 22
6 720 821 651 (2017/05) CRC200
22 | Service menu
Optimized heating curve
The optimize heating curve (Control type: External opt.) is a curve that curves upward and is based on the precise
correlation between the supply temperature and the relevant outside temperature ( ).
Fig. 13 Settings for heating curve with Low Temp. heating
Left: Slope changed by adjusting design temperature T
AL
and minimum outdoor temperature T
A,min
Right: Parallel shifting over desired room temperaturer
T
A
Outdoor temperature
T
VL
Supply temperature
[1] Setting: T
AL
= 113 °F (45 °C), T
A,min
= 14 °F (–10 °C) (base curve), limited to T
VL,max
= 118 °F (48 °C)
[2] Setting: T
AL
= 104 °F (40 °C), T
A,min
= 14 °F (–10 °C), limited to T
VL,max
= 118 °F (48 °C)
[3] Setting: T
AL
= 95 °F (35 °C), T
A,min
= –4 °F (–20 °C), limited to T
VL,max
= 118 °F (48 °C)
[4] Parallel shifting of the base curve [1] by increasing the desired room temperature, limited to T
VL,max
= 118 °F (48 °C)
[5] Parallel shifting of the base curve [1] by increasing the reducing room temperature
Fig. 14 Settings for heating curve with High Temp heating
Left: Slope changed by adjusting design temperature T
AL
and minimum outdoor temperature T
A,min
Rechts: Parallel shifting over desired roomtemperaturer
T
A
Outdoor temperature
T
VL
Supply temperature
[1] Setting: T
AL
= 167 °F (75 °C), T
A,min
= 14 °F (–10 °C) (base curve ), limited to T
VL,max
= 167 °F (75 °C)
[2] Setting: T
AL
= 176 °F (80 °C), T
A,min
= 14 °F (–10 °C), limited to T
VL,max
= 176 °F (80 °C)
[3] Setting: T
AL
= 158 °F (70 °C), T
A,min
= –4 °F (–20 °C), limited to T
VL,max
= 167 °F (75 °C)
[4] Parallel shifting of the base curve [1] by increasing the desired room temperature, limited to T
VL,max
= 176 °F (80 °C)
[5] Parallel shifting of the base curve [1] by increasing the reducing room temperature, limited to T
VL,max
= 167 °F (75 °C)
T
A
T
VL
T
A
T
VL
6 720 811 135-29. 1O
+32
+50+68
+14
-4
68
86
104
122
140
F
20
30
40
50
60
F
0
+10+20
-10
-20
C
C
+32
+50+68
+14
-4
68
86
104
122
140
F
20
30
40
50
60
F
0
+10+20
-10
-20
C
C
1
2
3
1
4
5
+32
+50
+68
+14
-4
68
86
104
122
140
158
176
194
F
20
30
40
50
60
70
80
90
F
0
+10+20
-10
-20
C
6 720 811 153-19. 1O
C
+32
+50+68
+14
-4
68
86
104
122
140
158
176
194
F
20
30
40
50
60
70
80
90
F
0
+10+20
-10
-20
C
C
T
A
T
VL
T
A
T
VL
1
2
3
1
4
5
Page 23
6 720 821 651 (2017/05)CRC200
Service menu | 23
Simple heating curve
The simple heating curve (Control type: External simple) is a simplification of the curved heating curve as a straight line. The straight line is described by two points ( ).
8.3 Function test menu
Using this menu, the pump/valve for each assigned heating zone can be tested. They are tested by setting various setting values. You can check whether the pump/valve responds appropriately by observing the response of the corresponding component. If Activation is set to YES in this menu, the normal heating mode is interrupted in the entire system. All settings are saved. The settings in this menu are only temporary and revert to the respective default settings as soon as Activation is set to NO or the Function Test menu is closed.
Low Temp.
heating
High Temp
heating
Minimum outside temperature T
A,min
14 °F (–10 °C) 14 °F (–10 °C)
Base point 77 °F (25 °C) 77 °F (25 °C) End point 113 °F (45 °C) 167 °F (75 °C) Maximum supply
temperature T
VL,max
118 °F (48 °C) 167 °F (75 °C)
Table 8 Factory settings for the simple heating curve
CAUTION: Risk of scalding if tank temperature limiter is deactivated during the function test!
▶ Close all DHW taps. ▶ Inform occupants of the premises of the
risk of scalding.
Menu item default
setting
Control range Functional description
Activation NO | YES NO: The actuators revert to their previously stored position so that the system starts
up again after the function tests in the same condition as when shut down. YES: The instantaneous operating status (mixer: actuation stroke; pump: stage or
speed) of the actuators in the system is saved. All actuators in the system switch to the test mode.
System pump 0 (in %) 0 | 100 (in %) 0: System pump for heating zones with valves not running (switched off).
100: System pump for heating zones with valves running at maximum speed.
HC Pump 0 (in %) 0 | 100 (in %) 0: Heating pumps not running/zones valves closed (off).
100: Heating pumps running/zones valves open (on).
Table 9 Settings in the function test menu
Page 24
6 720 821 651 (2017/05) CRC200
24 | Service menu
8.4 Info menu
Heating system settings and measurements are displayed in this menu. No changes can be made.
Menu item Possible values Description
Outdoor Temp. ()
– 40...122 °F ( – 40...50 °C)
The currently measured outdoor temperature is available only if an outdoor temperature sensor is installed.
Appl. oper. ON Burner operating
OFF Burner not operating Appl.set sply 68...194 °F (20...90 °C) Supply temperature required at the heat source (set temperature) Appl.act.sply 68...194 °F (20...90 °C) Supply temperature measured at the heat source (actual temperature) Appl.max.sply 95...194 °F (35...90 °C) Maximum supply temperature set at the heat source LLH Temp. 68...194 °F (20...90 °C) Current hot water temperature in the low-loss header HC Operation OFF Current operating mode of assigned heating zone, User interface operating
instructions
Heating
Setback
Summer
Manual HC set.sply 68...194 °F (20...90 °C) Required supply temperature in assigned heating zone HC act. sply. 68...194 °F (20...90 °C) Measured supply temperature in heating system Set Room Temp OFF Heating switched off, e. g. in the summer
41...86 °F (5.0...30.0 °C) Desired room temperature Room Temp. 41...86 °F (5.0...30.0 °C) Measured room temperature DHW Operation ON Water heating active
OFF Water heating not active Set DHW Temp 59...176 °F (15...80 °C) Desired hot water temperature DHW Temp. 59...176 °F (15...80 °C) Measured hot water temperature
Table 10 Info menu
Page 25
6 720 821 651 (2017/05)CRC200
Service menu | 25
8.5 Maintenance menu
Service-relevant settings are made in this menu, e. g. deleting the list of faults after all faults have been rectified in the course of service.
If the service display is set directly at the heat source on the basis of the run time or burner hours, the setting Maint.message appears under ON, but the Maint. date cannot be set.
8.6 System info menu
Detailed information about the BUS users in the system can be queried in this menu. No changes can be made.
Menu item default
settings
Control range Functional description
Maint.message OFF ON | OFF Maint.message is not available for heating zone 1.
No service display appears on the user interface. A service display appears on the screen of the user interface on the set date
( Maint. date).
Maint. date 01/01/2012 –
12/31/2099
Date for next heating system maintenance. (only for heating zone 1)
Reset Maint. NO NO | YES Reset Maint. is not available for heating zone 1.
The service display is not reset. The service display is reset.
Current Fault e. g. 09/29/
2014 A11/802
All current faults are displayed, arranged in order of fault severity: the fault date appears in the text line, the fault code and sub-code flash alternately in the value display.
Fault History e. g. 07/31/
2014 A02/816
The last 20 faults are displayed, arranged in order of the time of occurrence. The fault date appears in the text line, the fault code and sub-code flash alternately in the value display.
Clear Fault NO ON | OFF The fault history is retained.
The fault history is deleted.
Table 11 Settings in the maintenance menu
Menu item Display example Functional description
Install.date 09/14/2014 The date of the first confirmed configuration is recorded automatically. Control unit xxx.x Designation of the heat source controls Control SW 1.xx Software version of the heat source controls
2.xx SW controller NFxx.xx User interface software version HC Module SW NFxx.xx CZM100 software version
1)
1) Not available if a corresponding module is installed.
Table 12 System info
Page 26
6 720 821 651 (2017/05) CRC200
26 | Troubleshooting
9 Troubleshooting
A fault appears on the display of the user interface. The cause can be a fault on the user interface, in a component, in an assembly or on the heat source. The instructions belonging to the affected component, assembly or heat source used and especially the service manual with detailed fault descriptions contain additional information on troubleshooting. Many heat source faults do not appear on the display of the user interface. They are described in the documents for the heat source used.
The last 20 faults that occurred are saved with a time stamp (fault history, Page 25).
Use only original spare parts. Damage resulting from spare parts not supplied by the manufacturer is not covered under warranty. If a fault cannot be corrected, contact the service technician responsible for your area or the nearest Bosch office.
Fault
code
Sub-
code
Cause or fault description Testing sequence/Cause Measure
A11 6004 Solar module wrongly
activated
Deactivate solar module in the service
settings ( Bild 12, Seite 16).
A12 815 Supply temperature sensor
faulty
(3201 = Heating zone 1; ... 3208 = Heating zone 8)
Check cable connecting supply temperature sensor and zone module
If there is a fault, replace cable/sensor
Check connection between zone module and supply temperature sensor
If screws or a plug is loose, rectify the contact problem
Check the supply temperature sensor against its data table
If values do not agree, replace the sensor
Check the voltage to the connection terminals of the supply temperature sensor on the zone module against its data table
If sensor values agree but the voltage values do not, replace the zone module
A31 ... A38
3101 ... 3108
Zone module has no communication to CRCx00 in the heating zone
(3101 = Heating zone 1; ... 3108 = Heating zone 8)
Check configuration on the corresponding controller
Assign the correct heating zone and set Control type to Room supply, if outdoor temperature sensor not installed.
Check heating zone assignment on other controllers
Assign the correct heating zones
Check if cable for EMS connection is damaged
Replace damaged cable
Controller defective Replace defective controller
A31 ... A38
3201 ... 3208
Zone module detects unreasonable status of the end switch
(3201 = Heating zone 1; ... 3208 = Heating zone 8)
Check corresponding zone valve and end switch for status and defects
Replace faulty zone valve or end switch
Module wrongly configured: switch is in the wrong position.
See installation instructions CZM100, chapter 2.2
Table 13 Fault table
Page 27
6 720 821 651 (2017/05)CRC200
Troubleshooting | 27
A61 ... A68
1005 System configuration not
confirmed
(A61 = Heating zone 1; ... A68 = Heating zone 8)
System configuration not completed Configure system completely and confirm
A61 ... A68
1010 No communication via BUS
connection EMS
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Check whether bus cable was connected incorrectly
Rectify wiring faults and switch controller off
and on again Check whether bus cable is faulty. Repair or replace the bus cable Remove expansion module from BUS
and switch controller off and on again. Check whether the cause of the fault is a module or module wiring
Replace faulty BUS user
A61 ... A68
1030 1034 1035 1036
Internal data error of the controller.
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Controller faulty Replace controller
A61 ... A68
1037 Outdoor temperature sensor
faulty
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Check configuration. The selected setting requires an outdoor temperature sensor.
If an outdoor temperature sensor is not
desired. Select the room temperature-
dependent configuration in the controller. Check the connecting cable between
the controller and outdoor temperature sensor for continuity
If there is no continuity, rectify the fault
Check the electrical connection of the connecting cable in the outdoor temperature sensor or on the plug in the controller
Clean corroded connecting terminals in the
outdoor sensor housing.
Check the outdoor temperature sensor in accordance with table ( Technical documentation for the heat source)
If values do not match, replace the sensor
Check the voltage at the connecting terminals of the outdoor temperature sensor in the controller in accordance with table
If the sensor values matched, but the voltage
values do not match, replace the controller
A61 ... A68
1038 Invalid time/date
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Date/time not yet set Set date/time Prolonged loss of power supply Avoid voltage failures
Fault
code
Sub-
code
Cause or fault description Testing sequence/Cause Measure
Table 13 Fault table
Page 28
6 720 821 651 (2017/05) CRC200
28 | Environmental protection/disposal
10 Environmental protection/disposal
Environmental protection is one of the fundamental company policies of the Bosch Group. We regard quality of performance, economy and environmental protection as equal objectives. Environmental protection laws and regulations are strictly adhered to. To protect the environment, we use the best possible technology and materials taking into account economic points of view.
Packaging
For the packaging, we participate in the country-specific recycling systems, which guarantee optimal recycling. All packaging materials used are environmentally-friendly and recyclable.
Old appliances
Old appliances contain resources that should be recycled. The components are easy to separate and the plastics are marked. This allows the various components to be sorted for appropriate recycling or disposal.
A61 ... A68
1051 ... 1058
External room sensor not available
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Wrong configuration in the controller for external room sensor.
Change to No in service menu (external room sensor is not yet available)
A61 3011 CRC200 in heating zone 1
wrongly configured
Check the configuration of controller in heating zone 1. A zone module is detected but not allowed with current settings
If a zone module is to be installed, set the setting Control type to Room supply, if outdoor temperature sensor not installed.
A61 ... A68
3011 ... 3018
CRCx00 with corresponding heating zone is missing
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Check the configuration of the controller for the corresponding heating zone
Assign the heating zone properly.
Check connection to controller and connecting cable
Connect controller properly with a functioning cable
Check if controller is faulty Replace faulty controller
A61 ... A68
3061 ... 3068
No communication with zone module
(A61 = Heating zone 1; ... A68 = Heating zone 8)
Check connection to zone module and connecting cable
Connect controller and zone module properly with a functioning cable
Check if zone module is faulty Replace faulty zone module
A61 ... A68
3091 ... 3098
Room temperature sensor faulty
(3091 = Heating zone 1; ... 3098 = Heating zone 8)
Controller faulty Replace controller
Fault
code
Sub-
code
Cause or fault description Testing sequence/Cause Measure
Table 13 Fault table
Page 29
6 720 821 651 (2017/05)CRC200
Setup log (Service menu/contractor) | 29
11 Setup log (Service menu/contractor)
__ _
Table 14 Enter the ID number on the backside of the user interface here. Removal from wall plate has to be done to look at the ID.
Customer/system user Installer
........................................................................................
........................................................................................
Date commissioned:
Menu item Selection
System data (for details see Table. 5, Page. 17)
HC assignment 1 2 3 4 5 6 7 8
Pump conn. Heat Source HC Module (CZM100)
Heat. System High Temp Low Temp.
Control type External simple External opt. Room supply Room output
DHW No Yes, 3-wy vlv Yes, pr. pump
LLH Sensor No Yes, on mod.
Recirculation NO YES
WWSD OFF | °F ( °C)
Min.outs.temp °F( °C)
Damping OFF ON
Building Type Tight Medium Loose
Table 15 Setup log
Page 30
6 720 821 651 (2017/05) CRC200
30 | Index
Index
A
Accessory .................................................................... 7
Activation (function test) .............................................. 23
Attaching the user interface .......................................... 10
Automatic configuration ............................................... 17
B
Base point .................................................................. 19
BUS connection ............................................................ 9
C
Cable ........................................................................... 9
Commissioning
– Checklist ................................................................. 14
– Important settings .................................................... 14
Commissioning report .................................................. 29
Conditions power supply .............................................. 14
Connection to the heat source ......................................... 9
Continuous heating ...................................................... 19
Control type ............................................................... 17
Controls ................................................................11, 25
Current fault ............................................................... 25
D
Design temperature ......................................................19
DHW Priority ...............................................................19
Dimensions ...................................................................7
Disposal .....................................................................28
E
EMS .............................................................................7
End point ....................................................................19
Environmental protection ..............................................28
External room sensor ....................................................17
F
Fault codes .................................................................26
Fault date
– Current fault .............................................................25
– Fault history .............................................................25
Fault history ................................................................25
Frost protection
– Heating zone ............................................................19
– System ....................................................................20
Frost thresh. .........................................................19–20
Function module ............................................................7
Functional test .............................................................16
Heating zone (for details see Table. 7, Page. 17) Design Temp °F( °C)
Base point °F( °C)
End point °F( °C)
Max. Suppl.T. °F( °C)
PID charact. Fast Medium Slow
Opt. pump run NO YES
Room Feedback K
Contin. heat OFF | °F ( °C)
Frost protect OFF by Outdoor Temp by Room Temp. Room - Outside
Frost thresh. °F( °C)
DHW Priority OFF ON
DHW
Max. DHW Temp °F( °C)
Maintenance
Maint. date
Menu item Selection
Table 15 Setup log
Page 31
6 720 821 651 (2017/05)CRC200
Index | 31
H
Heat source operating status .........................................24
Heating curve ..............................................................21
– Radiant floor heating .................................................22
– Radiator ...................................................................22
Heating pump (function test) .........................................23
Heating system ...................................................... 17, 21
Heating zone ...............................................................16
Heating zone assignment .............................................. 17
Heating zone operating mode ........................................24
Heating zone pump connection ......................................17
Hot water
– Service menu ...........................................................16
– System data .............................................................17
– via 3-way valve .........................................................17
– via tank pump ...........................................................17
Hot water operating status ............................................24
Hot water temperature
– Actual value .............................................................. 24
– Maximum value .........................................................24
– Set point ..................................................................24
I
Info (service menu) ......................................................16
Installation ....................................................................7
Installation date ...........................................................25
Installation of the base ....................................................9
L
Low-loss header ..........................................................17
M
Main menu
– Overview .................................................................15
– Settings ...................................................................15
Maint. date .................................................................25
Maintenance ......................................................... 14, 16
O
Old appliances .............................................................28
Outdoor temperature ............................................... 4, 18
P
Packaging ...................................................................28
PID charact. ................................................................19
Power connection ..........................................................9
Power failure ...............................................................14
Power reserve ......................................................... 4, 14
Product Description .......................................................4
R
Recirculation pump ......................................................17
Recycling ....................................................................28
Removing the user interface from the base ...................... 10
Reset entire user interface ............................................ 17
Reset fault ..................................................................25
RESET service ............................................................. 25
Room Feedback .......................................................... 19
Room temperature
– Actual value ............................................................. 24
– Set point ................................................................. 24
Room temperature-dependent control .............................. 4
S
Safety instructions ......................................................... 3
Scope of delivery ........................................................... 6
Service display ............................................................ 25
Service menu
– Overview .................................................................16
– Settings ................................................................... 16
Shut down .................................................................. 14
Shutdown .................................................................. 14
Software version
– Control system ......................................................... 25
– Controller ................................................................ 25
– Heating zone module ................................................. 25
Supply temperature
– Actual value at the heat source .................................... 24
– Heating zone actual value ........................................... 24
– Heating zone set point ............................................... 24
– Maximum value at the heat source ...............................24
– Maximum value in heating zone ................................... 19
– Set point on the heat source ....................................... 24
System data ............................................................... 16
System info ................................................................ 16
System pump
– Functional test ......................................................... 23
T
Tank pump ................................................................. 17
Technical Data .............................................................. 7
Temperature
– Heating supply pipe .................................................. 24
– Hot water ................................................................ 24
– on the low-loss header ............................................... 24
Temperature sensor
– on the low-loss header ............................................... 17
Thermal disinfection .................................................... 23
Troubleshooting .......................................................... 26
U
User interface ............................................................. 17
Using as a controller ....................................................... 4
Page 32
Loading...