Bosch CLIMATE 5000 VRF RDCI, RDCI10/28-3, RDCI8/25-3, RDCI12/33-3, RDCI16/45-3 Installation Manual

...
Page 1
Before using your air conditioner unit, please read this manual carefully and keep it for future reference.
6 720 862 437 (2016/10)
Installation manual
CLIMATE 5000 VRF
RDCI Series – All DC Inver ter Outdoor Units
RDCI8/25-3, RDCI10/28-3, RDCI12/33-3, RDCI14/40-3, RDCI16/45-3
Page 2
RDCI Series – All DC Inverter Outdoor Units
2 | PRECAUTIONS
1. PRECAUTIONS
Read all installation manuals prior to installation.
This Installation manual is for the outdoor unit.
When installing indoor units please refer to indoor unit installation manual.
Prior to installation of this unit, please ensure correct power supply is available. Only qualified personal to undertake these works.
When installing a heat recovery switch box, ensure you consult the switch box manual.
The safty precautions listed here are divided into two categories. Ensure you read both categories prior to installation.
WARNING
Failure to observe a warning may result in serious injury.
CAUTION
Failure to observe a caution may result in injury or damage to the equipment.
After completing the installation, ensure the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual along with the owner‘s manual for future reference.
WARNING
Only trained and qualified service personnel to install, repair or service the equipment as per the service and installation manual.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
When installing the unit in a room, ensure you meet the requirement of national regulations.
Excessive refrigerant in a closed environment can lead to oxygen deficiency.
Only use authorised accessories and parts are to be used, failure to do so may invalidate your warranty.
If required consult a structural engineer for advice on suitable installation and load bearing area.
The appliance must not be installed in a laundry room.
Before obtaining access to electrical terminals, all power supply circuits must be safely isolated.
The condenser must have a local isolation within accordance of UK wiring regulations.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the refrigerant flow.
All electrical work must comply with the local national wiring regulations and the instructions set out in this manual.
If National regulations are not followed this may cause injur y, damage or fire to property.
When installing refrigerant pipework, ensure all pipes are protected to avoid any unwanted particles entering.
If the refrigerant leaks during installation, ventilate the area immediately.
Toxic gas may be produced should refrigerant comes into contact with a naked flame.
CAUTION
When installing this unit ensure you check installation guidelines to meet the requirements.
Ensure correct earthing of all appliances as per national electrical guidelines.
The unit should only be operated by authorised personnel.
Do not install the air conditioning unit in the following locations:
Where flammable gases, liquids or materials are stored.
Where there is salty air surrounding (near the coast).
Where there is caustic gas (sulfide, for example) existing in the air.
Where electrical voltage fluctuates.
Where there is strong electromagnetic waves exist.
Where there is acid or alkaline liquid evaporating.
2. INSTALLATION CHECKS
Acceptance and Unpacking
Before accepting delivery, ensure you check all of the equipment for damage. If damage is found please contact your supplier.
Check whether the model, specification and quantity of the equipment conform what has been ordered.
After removing the outer packaging, please keep the operation instructions safe and count the accessories.
Refrigerant pipework
Prior to installation, check the correct model numbers have been delivered.
Project schematic must be consulted for all refrigerant pipe sizes and correct diameters.
The refrigerant pipework should be sufficiently insulated. This will prevent condensation occurring.
After installation of the pipework is complete, ensure a full strength/ tightness test and vacuum test has performed.
Strength/tightness test The new refrigerant pipework must undergo a strength test (with 40kgf/cm
2
nitrogen). For tightness testing, please refer to F Gas
Regulations.
Creating a vacuum Ensure you vacuum the system down to 1.5 Torr, to ensure all moisture is extracted.
CONTENTS PAGE
1. PRECAUTIONS .................................................................... 2
2. INSTALLATION CHECKS ....................................................... 2
3. ACCESSORIES .................................................................... 3
4. OUTDOOR UNIT INSTALLATION ............................................ 3
5. REFRIGERANT PIPE ............................................................. 8
6. CONNECTING PIPES TO SBOX ............................................ 13
7. SBOX WIRING NAMEPLATE ................................................ 14
8. ELECTRIC WIRING ............................................................. 15
9. TEST RUN ......................................................................... 21
Page 3
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
ACCESSORIES | 3
Refrigerant replenishment
Additional refrigerant must be added prior to turning the units on. Correct refrigerant charge must be calculated using the guidelines within this manual.
On completion of the refrigerant installation you must record the exact additional refrigerant charge.
Electric wiring
When selecting the size of the power supply cable, consult this manual along with national regulations. When selecting communication wiring follow guidelines set out in this manual.
When installing communication cabling, ensure you read electrical installation guideline in this manual.
Test Run
Before operation, remove the six pieces of PE foaming which are used at the rear of the unit for protecting the condenser. Be careful not to damage the fins. Otherwise, the heat exchange performance may be affected.
Prior to test run, ensure the power has been on for a minimum of 12 hours.
3. ACCESSORIES
Table.3-1
Model
Name
All of units Outline Function
Outdoor unit
installation manual
1
___________
Outdoor unit owner’s
manual
1
Upon completion leave with customer
Indoor unit owner’s
manual
1
On completion leave with customer
90° elbow
1 (8HP, 10HP)
2 (12HP
16HP)
________ For connecting pipes
Seal plug 8 ________ For pipe cleaning
Connective pipe
accessory
1
(used in 8HP16HP)
Connect to the high-pressrue gas balance side
Connective pipe
accessory
1
(used in 8HP16HP)
Connect to the liquid pipe side
Connective pipe
accessory
1
(used in 8HP, 10HP, 12HP)
Connect to the high­pressure gas pipe side
Connective pipe
accessory
1
(used in 14HP, 16HP)
Connect to the high­pressure gas pipe side
Connective pipe
accessory
2
(used in 12HP)
Connect to the low-pressure gas pipe or liquid pipe side
Screw bag 1 ________ Stored for service
Cable clip kit
1
(Optional)
For cable fastening
4. OUTDOOR UNIT INSTALLATION
4.1 Outdoor unit combination
Table.4-1
HP Mode
Max Qty. of indoor
unit
HP Mode
Max Qty. of indoor
unit
8 8HP×1 13 26 10HP+16HP 43 10 10HP×1 16 28 14HP×2 46 12 12HP×1 20 30 14HP+16HP 50 14 14HP×1 23 32 16HP+16HP 53 16 16HP×1 26 34 10HP×2+14HP 56 18 8HP+10HP 29 36 10HP×2+16HP 59 20 10HP+10HP 33 38
10HP+12HP+16HP
63
22 10HP+12HP 36 40
10HP+14HP+16HP
64
24 10HP+14HP 39 42 14HP×3 64
Table.4-2
HP Mode
Max Qty. of indoor
unit
HP Mode
Max Qty. of indoor
unit
44 14HP×2+16HP 64 56
10HP+14HP+16HP×2
64
46 14HP+16HP×2 64 58 14HP×3+16HP 64 48 16HP×3 64 60 14HP×2+16HP×2 64 50
8HP+10HP+16HP×2
64 62 14HP+16HP×3 64
52
10HP×2+16HP×2
64 64 16HP×4 64
54
10HP+12HP+16HP×2
64
4.2 Dimensions of outdoor unit
4.3 Selecting installation location
Ensure that the outdoor unit is installed in a well-ventilated location.
Ensure that the noise and exhaust ventilation of the outdoor unit does not affect the neighbours of the property owner or its surroundings.
Where possible ensure the shortest pipe route.
Ensure that the outdoor unit is installed in a cool location without direct sunshine exposure or direct radiation.
Fig. 4-1
Unit: mm
Page 4
RDCI Series – All DC Inverter Outdoor Units
4 | OUTDOOR UNIT INSTALLATION
Do not install the outdoor unit in a dirty or severely polluted location, to avoid blockages in the heat exchanger of the outdoor unit.
Do not install the outdoor unit in a location with oil pollution, high salt content air or high content of harmful gases such as sulfurous gas.
4.4 Base for outdoor unit
Base types
Steel structure base
Ensure you consult a construction engineer before installation. Ensure the base has been installed to the correct dimensions set out in this manual. Raise the unit at least 200mm from the floor.
Position illustration of screw bolt (Unit: mm)
Table.4-3 Unit: mm
HP
SIZE
816
A 1120
B 1250
C 736
D 765
Centering position illustration for each connective pipe (Unit: mm)
1) 8HP, 10HP
2) 12HP
Ø10 Expansion bolt
Rubber shocking proof mat
Concrete base h=200mm
Solid ground or roofing
200 mm
Fig. 4-2
B A
C
D
15×23long U-shape hole
Fig. 4-3
R
Fig. 4-4
250
205
245
290
230
205
200
170
Fig. 4-5
High-pressure
gas balance valve
Low-pressure gas
side of shut-off valve
High-pr
essure gas
side of shut-off valve
L
iquid side of
shut-off valve
Oil balance valve
R amplification
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø22.2
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø12.7
For the Cascaded Units
R
Fig. 4-6
Page 5
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
OUTDOOR UNIT INSTALLATION | 5
3) 14HP, 16HP
4.5 Outdoor Unit Cascade Sequence
A system with one or more outdoor units installed, will need to follow this method: Outdoor units should be placed from large capacity to small capacity. The largest should be installed nearest to the first branch joint. You need to set the largest capacity as the master unit.
1) Place the 16HP at a side of the first branch joint site.
2) Place the unit from the large capacity to the small (See the detail placement illustration)
3) Set 16HP as the main unit, while the 12HP and the 10HP as the slave unit.
4.6 Installation space for outdoor unit
When installing the unit, leave a space for maintenance shown in Fig.4-12 Install the power supply at the side of the outdoor unit. For correct installation procedure, read installation manual.
In case there are obstacles surrounding the unit, refer to 4-17.
4.7 Layout
When the outdoor unit is higher than the surrounding obstacle
One row
250
205
245
290
230
205
200
170
Fig. 4-7
High-pressure
gas balance valve
L
ow-pressure gas
side shut-off valve
High-pr
essure gas
side shut-off valve
L
iquid side
shut-off valve
Oil balance valve
R amplification
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø25.4
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø15.9
For the Cascaded Units
R
Fig. 4-8
250
205
245
290
230
205
200
165
Fig. 4-9
High-pressure
gas balance valve
L
ow-pressure gas
side shut-off valve
High-pr
essure gas
side shut-off valve
L
iquid side
shut-off valve
Oil balance v
alve
R amplification
The connective pipe
diameter Ø19.1
The connective pipe
diameter Ø28.6
The connectiv
e pipe
diameter Ø22.2
The connective pipe
diameter Ø15.9
F
or the Cascaded Units
Fig. 4-10
Outdoor unit
(38HP)
16HP
The 1st branch joint
12HP 10HP
SBOX SBOX SBOX
Indoor unit A Indoor unit B Indoor unit C
Fig. 4-12
100mm~500mm 100mm~500mm
>1000mm
>1000mm
>1000mm
>1000mm
Top view of the outdoor unit
Fig. 4-13
Front
100-500mm
Front
>1m
>1m>1m
>800mm
Page 6
RDCI Series – All DC Inverter Outdoor Units
6 | OUTDOOR UNIT INSTALLATION
Two rows
More than two rows
If the minimum clearance of 800mm above the unit can not be met, see the figure below.
Ensure the surroundings are no more than 800mm high. If this is not possible install mechanic exhaust device.
4.8 Set the snow-proof facility
In snowy areas, precautions should be taken to avoid unit failure or lack of performance.
4.9 Explanation of valve
Table.4-4
Low-pressure gas pipe
Oil balance pipe
High-pressure gas balance pipe
Liquid pipe
High-pressure gas pipe
Installation illustration
Fig. 4-14
Front
100-500mm
Front
Front Front
>1m
>1m
>1m
>1m
>800mm
Fig. 4-15
Front
100-500mm
Front Front
Front Front
Front
>1m
>1m
>800mm
>1m>1m>1m
Fig. 4-16
Front
100-500mm
Front
>1m
>1m>1m
A
B
C
D
B
A
B
A
C
D
B
A
Fig. 4-17
Front view
Front view
Side view
Front view
>45° >300mm
>1000mm Airflow deflector
1
2
3
4
5
Fig. 4-19
Notes: 16HP as an example
1210
C
A
725
B
001
Fig. 4-20
Fig. 4-21
Example A
Support
Radius
Air outlet louver dimension (optional)
Page 7
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
OUTDOOR UNIT INSTALLATION | 7
Curve diagram of static pressure, air flow volume.
Table.4-5 Unit: mm Table.4-6 Unit: mm
A A≥300 A A≥300 B B≥250 B B≥250 C C≤3000 C C≤3000 D 750≤D≤760
θ
θ≤15°
θ
θ≤15°
NOTE
Before installing the air deflector, please ensure the fan grill has been taken off.
Once air deflector has been installed, the air volume, cooling/ heating capacity will decrease. The maximum angle allowed for the shutter is 15 degrees.
Only one bend set is allowed.
Install anti vibration pads in between the unit and air deflector.
Fig. 4-22
12 ST3.9 self-threading screws
Remove the fan grills
10
01
12-Ø3.2
393
567
1250
411 411213
411 411213
Fig. 4-23
9500
10000
10500
11000
11500
12000
12500
0 5 10 15 20 25
Fig. 4-24
8/10HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
10500
11000
11500
12000
12500
13000
13500
0 5 10 15 20 25
Fig. 4-25
12HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
12500
13000
13500
14000
14500
15000
15500
0 5 10 15 20 25
Fig. 4-26
14/16HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
B
0921
C
1210
A
Fig. 4-27
Example B
Support
Radius
Air outlet louver dimension (optional)
725
Ø3.2
393
567
1250
411 411
213
411 411213
Fig. 4-28
Fig. 4-29
12 ST3.9 self-threading screws
Remove the fan grills
Page 8
RDCI Series – All DC Inverter Outdoor Units
8 | REFRIGERANT PIPE
5. REFRIGERANT PIPE
5.1 Length and drop height permitted for the refrigerant pipework
Note: Ensure a distance of at least 0.5m between branch pipes.
Table.5-1
Permitted
value
Pipework
Pipe length
Total pipe length (Actual)
1000m
(Please refer to
the caution 5 of
conditions 2)
L1+(L2+L3+L4+L5+L6+L7 +L8+L9+L10+L11+L12+ L13)×2+a+b+c+d+e+f+g+ h+i+j+k+l+m+n
Maximum
pipework (L)
Actual length
175m
L1+L7+L9+L11+j+k+n
Equivalent
length
200m
(Please refer to
caution 1)
Pipework (furthest from the first line pipe branch)
equivalent length
40m/90m
(Please refer to
caution 5)
L7+L9+L11+j+k+n
SBOX to indoor unit
equivalent length
40m j+k+n
Drop height
Indoor unit
to outdoor
unit drop
height
outdoor
unit up
70m*
(Please refer to caution 3)
outdoor unit
down
110m
(Please refer to caution 4)
Indoor unit to indoor unit
drop height
30m _____________
N3
(140)
N5
(140)
N6
(71)
N7
(71)
N9
(56)
N8
(28)
N2
(71)
N4
(28)
N1
(71)
N10 (56)
A
B
C
E
F
b
c
d
f
g
j
h
i
l
k
m n
e
L
1
L2
L9
L13
L11
L10
L12
L3
a
SB1
SB2
SB3
SB4
SB5
SB6
L4
L5
L6
D
N11
(140)
p
N12
(140)
q
N13 (56)
r
L
8
L7
SB7
Fig. 5-1
Indoor unit
The first line branch pipe
Maximum height between outdoor and indoor units
unit and outdoor unit H≤110m
Maximum height from indoor unit to indoor unit.
drop height H≤30m
Outdoor unit
(one or more outdoor units)
Max pipework equivalent length L≤200m
(From the first line branch pipe) Maximum pipework equivalent length L≤40m/90m
SBOX to indoor unit equivalent length L≤40m
* A system with a height difference above 70m is not supported as standard but is available on request for customisation.
Fig. 5-2
≥300m
≥300m
Page 9
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
REFRIGERANT PIPE | 9
CAUTION
1. The length between the branch pipes should be a minimum of 0.5m.
2. When the outdoor unit is installed above the indoor units and the distance
is greater than 20m, you must install oil return taps every 10m. Refer to 5-2.
3. When the outdoor unit is installed below the internal units and the length
exceeds 40m, the liquid pipe needs to be increased one size.
4. When the outdoor unit is installed below the internal units, the first
branch joint connection should be shorter than 40m. However when certain conditions are met, the length can increase up to 90m.
Conditions
1. For all pipe sizing and limitations please follow the conditions below.
Conditions
L7+L9+L11+j+k+n≤90m L2L13 Increasing the pipe diameter of the distribution pipe
To increase the pipe size, see below
Ø9.5 → Ø12.7 Ø12.7 → Ø15.9 Ø15.9 → Ø19.1 Ø19.1 → Ø22.2 Ø22.2 → Ø25.4 Ø25.4 → Ø28.6 Ø28.6 → Ø31.8 Ø31.8 → Ø38.1 Ø38.1 → Ø41.3 Ø41.3 → Ø44.5 Ø44.5 → Ø54.0
5.2 Select the refrigerant pipework type
Conditions
2. When calculating actual length of pipe, follow the example below. L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11+L12+L13) x2+a+b+c +d+e+f+g+h+i+j+k+l+m+n<1000m
Examples
Reference Figure. 5-1
Conditions
3. The length from the indoor unit to the nearest branch joint assembly or SBOX ≤40m; b, c, d, e, f, h, i, l, m, n, p, q, r ≤40m(Pipe diameter requirements, please refers to table.5-8).
Examples
Reference Figure. 5-1
Conditions
4. The distance between [the outdoor unit to the furthest indoor unit] and [the outdoor unit to the nearest indoor unit] is ≤40m.
The furthest indoor unit N10
The nearest indoor unit N11 (L1+L7+L9+L11 +j+k+n)-(L1 +L7+L8+p) <40m
Examples
Reference Figure. 5-1
L1
M
L
g1
j j j j j j
g2 g3
G1
N3
(140)
N5
(140)
N6
(71)
N7
(71)
N9
(56)
N8
(28)
N2
(71)
N4
(28)
N1
(71)
N10 (56)
A
B
C
E
F
b
c
d
f
g
j
h
i
l
N11
(140)
p
N12
(140)
q
N13 (56)
r
k
m n
e
L
2
L9L8
L7
L13
L11
L10
L12
L3
a
SB1
SB2
SB3
SB4
SB5
SB6
L4
L5
L6
D
SB7
W3 (10)W2(12)W1(16)
Fig. 5-3
Page 10
RDCI Series – All DC Inverter Outdoor Units
10 | REFRIGERANT PIPE
Table.5-2
Pipe name
Code (As per
the Fig. 5-2)
Main pipe L1
Indoor unit main pipe L2~L13
Indoor unit aux. pipe a, b, ...r
Indoor unit main pipe branching pipe assembly A, B, C, D, E
Indoor unit aux. pipe branching pipe assembly I, II, III, IV
Outdoor unit branching pipe assembly L, M
Outdoor unit connective pipe g1, g2, g3, G1
SBOX equipment SB1, ...SB7
5.3 Size of joint pipes for indoor unit
Table.5-3 Size of joint pipes for R410A indoor unit
Capacity of
indoor unit A
(×100W)
Indoor unit main pipe (inches)
Low-pressure
gas side
High-pressure
gas side
Liquid
side
Available
branching pipe
A<56 Ø12.7 Ø9.5 Ø6.4 IDU-BJR01
56≤A<166 Ø19.1 Ø15.9 Ø9.5 IDU-BJR01
166≤A<230 Ø22.2 Ø19.1 Ø9.5 IDU-BJR02
230≤A<330 Ø22.2 Ø19.1 Ø12.7 IDU-BJR02
330≤A<460 Ø28.6 Ø22.2 Ø12.7 IDU-BJR03
460≤A<660 Ø28.6 Ø22.2 Ø15.9 IDU-BJR03
660≤A<920 Ø34.9 Ø28.6 Ø19.1 IDU-BJR04
920≤A<1350 Ø41.3 Ø34.9 Ø19.1 IDU-BJR05
1350≤A Ø44.5 Ø38.1 Ø22.2 IDU-BJR05
e.x.1: Refer to Fig.5-2, the capacity of downstream units to L2 is 71×2+140+28=310, i.e. low pressure gas pipe for L2 is Ø22.2, high pressure gas pipe is Ø19.1, high pressure liquid pipe is Ø12.7.
5.4 Size of joint pipes for outdoor unit
Based on the following tables, select the diameters of outdoor unit main connective pipe. When the main pipe accessory is larger on the indoor unit, use the larger pipe accessory.
Table.5-4 Size of joint pipes for R410A outdoor unit
Model
When the equivalent length of all liquid
pipes < 90m, the size of main pipe (inches)
Low-pressure
gas side
High-pressure
gas side
Liquid
side
The 1st
branching pipe for
indoor unit
8HP Ø22.2 Ø19.1 Ø9.5
IDU-BJR02
10HP Ø22.2 Ø19.1 Ø12.7
IDU-BJR02
12HP Ø25.4 Ø19.1 Ø12.7
IDU-BJR03
14~16HP Ø28.6 Ø22.2 Ø15.9
IDU-BJR03
18~22HP Ø31.8 Ø28.6 Ø15.9
IDU-BJR03
24HP Ø34.9 Ø28.6 Ø15.9
IDU-BJR04
26~32HP Ø34.9 Ø28.6 Ø19.1
IDU-BJR04
34~48HP Ø41.3 Ø34.9 Ø19.1
IDU-BJR05
50~64HP Ø44.5 Ø38.1 Ø22.2
IDU-BJR05
Table.5-5 Size of joint pipes for outdoor unit (R410a)
Model
When the equivalent length of all liquid
pipes ≥ 90m, the size of main pipe (inches)
Low-pressure
gas side
High-pressure
gas side
Liquid
side
The 1st
branching pipe for
indoor unit
8HP Ø22.2 Ø19.1 Ø12.7
IDU-BJR02
10HP Ø22.2 Ø19.1 Ø12.7
IDU-BJR02
12HP Ø25.4 Ø19.1 Ø15.9
IDU-BJR03
14~16HP Ø28.6 Ø22.2 Ø15.9
IDU-BJR03
18~22HP Ø31.8 Ø28.6 Ø19.1
IDU-BJR03
24HP Ø34.9 Ø28.6 Ø19.1
IDU-BJR04
26~32HP Ø34.9 Ø28.6 Ø22.2
IDU-BJR04
34~48HP Ø41.3 Ø34.9 Ø22.2
IDU-BJR05
50~64HP Ø44.5 Ø38.1 Ø25.4
IDU-BJR05
5.5 Branch pipes for outdoor unit
Table.5-6
Model
Outdoor unit pipe connective opening dimension (inches)
Low-pressure gas
side
High-pressure gas
side
Liquid side
8~12HP Ø22.2 Ø19.1 Ø12.7
14, 16HP Ø28.6 Ø22.2 Ø15.9
5.6 Multi pipe connection assembly and pipe diameter for outdoor unit
Based on Table 5-7 select the branch pipe assembly for the outdoor unit. Before installation, please read the Outdoor Unit Branching Pipe Installation Manual carefully.
Table.5 -7 Outdoor unit branch pipe assembly (Illustration)
Outdoor unit Qty.
Illustration
Outdoor unit
connective pipe
diameter
Parallel connect with
the branching pipes
2 units
L
g1g2
g1, g2: 8~12HP: Ø22.2/Ø19.1/Ø12.7 14, 16HP: Ø28.6/Ø22.2/Ø15.9
L: ODU-BJR02
3 units
L
M
g1g2
G1
g3
g1, g2, g3: 8~12HP: Ø22.2/Ø19.1/Ø12.7 14, 16HP: Ø28.6/Ø22.2/Ø15.9 G1: Ø34.9/Ø28.6/ Ø19.1
L+M: ODU-BJR03
4 units
L
M
N
g1g2
G1 G2
g3g4
g1, g2, g3, g4: 8~12HP: Ø28.2/Ø19.1/Ø12.7 14, 16HP: Ø28.6/Ø22.2/Ø15.9 G1: Ø34.9/Ø28.6/Ø19.1 G2: Ø41.3/Ø34.9/Ø22.2
L+M+N: ODU-BJR04
5.7 Example
1) Take (10+12+16) HP for the three modules as an example to clarify the
pipe selection.
2) Take Fig.5-2 as an example, providing that the equivalent length of all
pipes in this system is larger than 90m.
Table.5-8
Capacity
of indoor unit A
(×100W)
Indoor unit aux. pipe (between branch joint and branch
joint/SB) (inches)
The branch pipe assembly of indoor
unit aux. pipe
Gas side Liquid side
A<160 Ø15.9 Ø9.5 IDU-BJR01
Capacity
of indoor unit A
(×100W)
Indoor unit aux. pipe (between indoor unit and branch joint/SB) (inches)
When branching
pipe’s length ≤10m
When branching pipe’s length>10m
Gas side Liquid side Gas side Liquid side
A<56 Ø12.7 Ø6.4 Ø15.9 Ø9.5
160≥A≥56 Ø15.9 Ø9.5 Ø19.1 Ø12.7
Main pipe
Main pipe
Main pipe
Page 11
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
REFRIGERANT PIPE | 11
A Branching pipe at the inside of the unit.
There are b, c, d, e, f, h, i, l, m, n, p, q, r branching pipes at the inside of the unit, the branching pipe diameter should be select as per Table 5-8.
B Main pipe and aux. pipe at the inside of the unit (Refer to Table 5-3
and Table 5-8)
1) The aux. pipe a with N1, N2 downstream indoor units that total capacity is 71×2=142, the pipe a diameter is Ø15.9/Ø9.5, thus select IDU-BJR01 for the branching pipe I.
2) The main pipe L3 with N1, N2 downstream indoor units that total capacity is 71×2=142, the pipe L3 diameter is Ø19.1/Ø15.9/Ø9.5, thus select SBOX02-1 for SB1.
3) The main pipe L5 with N3 downstream indoor units that total capacity is 140, the pipe L5 diameter is Ø19.1/Ø15.9/Ø9.5, thus select SBOX02-1 for SB2.
4) The main pipe L6 with N4 downstream indoor units that total capacity is 28, the pipe L6 diameter is Ø12.7/Ø9.5/Ø6.4, thus select SBOX02-1 for SB3.
5) The main pipe L4 with N3, N4 downstream indoor units that total capacity is 140+28=168, the pipe L4 diameter is Ø22.2/Ø19.1/ Ø9.5, thus select IDU-BJR02 for the branching pipe C.
6) The main pipe L2 with N1~N4 downstream indoor units that total capacity is 71×2+140+28=310, the pipe L2 diameter is Ø22.2/ Ø19.1/Ø12.7, thus select IDU-BJR02 for the branching pipe B.
7) The main pipe L12 with N5 downstream indoor units that total capacity is 140, the pipe L12 diameter is Ø19.1/Ø15.9/Ø9.5, thus select SBOX02-1 for SB4.
8) The aux. pipe g with N6, N7 downstream indoor units that total capacity is 71×2=142, the pipe g diameter is Ø15.9/Ø9.5, thus select IDU-BJR01 for the branching pipe II.
9) The main pipe L13 with N6, N7 downstream indoor units that total capacity is 71×2=142, the pipe L13 diameter is Ø19.1/Ø15.9/ Ø9.5, thus select SBOX02-1 for SB5.
10) The main pipe L10 with N5~N7 downstream indoor units that total capacity is 140+71×2=282, the pipe L10 diameter is Ø22.2/ Ø19.1/Ø12.7, thus select IDU-BJR02 for the branching pipe F.
11) The aux. pipe k with N9, N10 downstream indoor units that total capacity is 56×2=112, the pipe k diameter is Ø15.9/Ø9.5, thus select IDU-BJR01 for the branching pipe III.
12) The aux. pipe j with N8~N10 downstream indoor units that total capacity is 28+56×2=140, the pipe j diameter is Ø15.9/Ø9.5, thus select IDU-BJR01 for the branching pipe IV.
13) The main pipe L11 with N8~N10 downstream indoor units that total capacity is 28+56×2=140, the pipe L11 diameter is Ø19.1/Ø15.9/ Ø9.5, thus select SBOX02-1 for SB6.
14) The main pipe L9 with N5~N10 downstream indoor units that total capacity is 140+56×2+71×2+28=422, the pipe L9 diameter is Ø28.6/Ø22.2/Ø12.7, thus select IDU-BJR03 for the branching pipe E.
15) The main pipe L8 with N11~N13 downstream indoor units that total capacity is 140×2+56=336, the pipe L8 diameter is Ø28.6/Ø22.2/ Ø12.7, thus select SBOX04-1 for SB7.
16) The main pipe L7 with N5~N13 downstream indoor units that total capacity is 140×3+71×2+56×3+28=758, the pipe L7 diameter is Ø34.9/Ø28.6/Ø19.1, thus select IDU-BJR04 for the branching pipe D.
17) The main pipe L1 with N1~N10 downstream indoor units that total capacity is 140×4+71×4+56×3+28×2=1064, thus select IDU­BJR05 for the branching pipe A.
C Main pipe (Refer to Table 5-3, Table 5-5):
Main pipe L1 in the Fig.5-2, which upstream outdoor units total capacity is 16+12+10=38, base on table 5-5, the low pressure gas/high pressure gas/liquid pipe diameter are Ø41.3/ Ø34.9/Ø22.2, total capacity of the downstream indoor unit is
140×4+71×4+56×3+28×2=1064, base on table 5-3, the low pressure gas/high pressure gas/liquid pipe diameter are Ø41.3/ Ø34.9/Ø19.1, take the large one for your selection, final confirm the main pipe diameter is: low pressure gas/high pressure gas/liquid pipe Ø41.3/Ø34.9/Ø22.2.
D Parallel connect the outdoor units
1) The outdoor unit linked by Pipe g1 is 10HP, parallel connects with outdoor unit. the connective pipe diameter to be selected according to its connector size is Ø22.2/Ø19.1/Ø12.7; The outdoor unit linked by Pipe g2 is 12HP, parallel connects with outdoor unit. the connective pipe diameter to be selected according to its connector size is Ø22.2/Ø19.1/Ø12.7; The outdoor unit linked by Pipe g3 is 16HP, parallel connects with outdoor unit. the connective pipe diameter to be selected according to its connector size is Ø28.6/Ø22.2/Ø15.9.
2) G1 is the upstream of the two parallel connected outdoor units, refer to Table 5-5 select the two parallel connected outdoor unit, the pipe diameter is Ø34.9/Ø28.6/Ø19.1.
3) Parallel connect the three outdoor units, refer to Table 5-7 should select ODU-BJR03 for outdoor unit connective pipes (L+M).
5.8 Caution for brazing
When brazing use nitrogen to pass through the pipework. This helps stop oxidisation inside the refrigerant pipework.
Do not use anti-oxidants when brazing the pipe joints. Residue can block pipes and cause damage to the equipment.
Do not use flux when brazing. Use phosphor copper brazing filler alloy (BCuP) which does not require flux.
Flux is extremely harmful on refrigerant systems. This can cause corrosion and deterioration of the refrigerant oil.
5.9 Removing the contaminants in the pipework
Ensure there is no dirt or water in the pipework before connecting.
Ensure you flush nitrogen through to clear the refrigerant pipe work. This needs to be done before connecting to the outdoor unit.
5.10 Strength/Tightness Test
Pressure test the system with nitrogen to 40kgf/cm2. Ensure a 24 hour strength test has been completed for all new installations. For guidance on tightness testing for existing installations, please refer to F Gas Regulations.
Fig. 5-4
SBOX Indoor unit
Liquid pipe
Nitrogen
Nitrogen
Nitrogen
High-pressure gas pipe
Low-pressure gas pipe
Page 12
RDCI Series – All DC Inverter Outdoor Units
12 | REFRIGERANT PIPE
CAUTION
Pressurised nitrogen (3.9MPa; 40kgf/cm2) is used for strength testing.
Prior to connecting vacuum pump, ensure you release all the nitrogen from all three pipes.
Only Nitrogen can be used for pressure testing. Do not use any other substances.
Ensure the shut off valves are protected during brazing.
A Torr gauge must be used to measure the vacuum state.
5.11 Triple vacuum process
1) Vacuum from all three ports down to 2Torr.
2) Break vacuum with nitrogen to absorb moisture. Then repeat vacuum process down to 1.6Torr.
3) Break Vacuum for with nitrogen to absorb moisture. Repeat vacuum to achieve 1.5 Torr or lower.
CAUTION
Do not add refrigerant when nitrogen is present. Do not mix refrigerants.
Do not use refrigerant for air vacuuming.
Before adding refrigerant leave the system on a vacuum for 2 hours to see if the gauges rise. If the gauges rise please repeat strength/ tightness test and check for leaks.
5.12 Refrigerant amount to be added
1) Calculate the added refrigerant according to the diameter and the length of the liquid side pipe. The refrigerant is R410A.
Note:
1. Assume equivalent pipe length of the branching pipe header to be
0.5m.
2. The refrigerant amount to be added of SBOX02 is 0.3kg/per, of SBOX04/SBOX06 is 0.5kg/per.
Table.5-9
Pipe size on liquid
side
Refrigerant to be
added per meter Ø6.4 0.023kg Ø9.5 0.060kg
Ø12.7 0.120kg
Ø15.9 0.180kg
Ø19.1 0.270kg
Ø22.2 0.380kg Ø25.4 0.550kg Ø28.6 0.710kg
2) Add the additional quantity of calculated refrigerant from the low­pressure pipe and liquid pipe.
5.13 The Key points of installing connective pipe­work between cascaded outdoor units
1) When connecting the outdoor units, the pipes should be installed horizontally (Fig5-7, Fig 5-8). It is not permitted to use method shown in Fig 5.9.
2) All connective pipework between the outdoor units are not to be installed above the outlets of the condenser. See Fig. 5.10..
Connect manifold gauges and vacuum pump to all three pipe connections. Perform vacuum until for minimum of 2 hours.
Shut off vacuum pump and pressure with nitrogen to absorb moisture.
Repeat vacuum process for a further two hours.
Shut off vacuum pump and break vacuum for with nitrogen to absorb moisture.
Repeat vacuum process for a further 2 hours and achieve a minimum of 1.5Torr.
If 1.5Torr cannot be achieved, repeat re-pressure and find leak.
Re-peat Triple Vacuum process.
Perform a triple evacuation
Into the vacuum state
Fig. 5-7
√ Correct way
Fig. 5-8
√ Correct way
Fig. 5-9
× Wrong way
Page 13
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
CONNECTING PIPES TO SBOX | 13
3) Branch joints must be installed horizontally at an angle of no more than 10 degrees.
4) Ensure you install branch assembly joints correctly to stop the build up of oil.
6. CONNECTING PIPES TO SBOX
Fig. 5-10
× Wrong way
Fig. 5-11
U-shaped branching pipe
A direction view
Horizontal surface
Wrong Correct
Fig. 5-12
Fig. 5-13
Fig. 6-1
Gas pipe (Ø15.9/Ø12.7)
Liquid pipe (Ø9.5/Ø6.4)
Low-pressure gas pipe (Ø25.4)
High-pressure gas pipe (Ø19.1)
Liquid pipe (Ø12.7)
SBOX02-1
SBOX02E-1
Fig. 6-3
Fig. 6-2
Gas pipe (Ø15.9/Ø12.7)
Gas pipe (Ø15.9/Ø12.7)
Liquid pipe (Ø9.5/Ø6.4)
Liquid pipe(Ø9.5/Ø6.4)
Low-pressure gas pipe (Ø31.8)
Low-pressure gas pipe (Ø31.8)
High-pressure gas pipe (Ø22.2)
High-pressure gas pipe (Ø22.2)
Liquid pipe (Ø15.9)
Liquid pipe (Ø15.9)
SBOX04-1
SBOX06-1
SBOX04E-1
Page 14
RDCI Series – All DC Inverter Outdoor Units
14 | SBOX WIRING NAMEPLATE
7. SBOX WIRING NAMEPLATE
7.1 The nameplate of SBOX04-1, SBOX06-1
7.2 The nameplate of SBOX04E-1
M-O
M-I (1~4)
P Q E
P Q E P Q E
P Q E P Q E
P Q E P Q E
M-I (5,6)
T4C T4C1
Fig. 7-1
TRANS2
TO INDOOR6
BLUE
Blue
White
Black
Yellow
Black
Purple
Gray
Black
Orange
Green
Black
Blue
White
Black
Red
Brown
Black
Gray
Yellow
Black
Orange
RED
Y/G
TO INDOOR4
TO INDOOR2TO INDOOR5
TO INDOOR3
TO INDOOR1
TO OUTDOOR
POWER IN
TRANS1
M-O
M-I (1~4)
P Q E
P Q E
T4C T4C1
Fig. 7-2
TRANS2
TO INDOOR
TO OUTDOOR
POWER IN
TRANS1
Red
Brown
Black
Gray
Gray
Yellow
Yellow
Black
Black
BLUERED
Y/G
Page 15
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
ELECTRIC WIRING | 15
7.3 The nameplate of SBOX02-1
7.4 The nameplate of SBOX02E-1
Table.7-1
Model of SBOX
SBOX02-1 SBOX04-1 SBOX06-1 SBOX02E-1 SBOX04E-1
Maximum
capacity
of single group
pipe
16kW ___________
Maximum indoor units quantity of
single group pipe
4 1
Maximum
capacity of SB
28kW 45kW 28kW 56kW
Downstream of the
largest length
40m
NOTE
Single group pipe means one connecting liquid pipe and one connecting gas pipe.
If you disable auto mode function you can connect up to 4 units via an SBOX. If auto mode is selected then only one indoor unit can be connected.
Indoor units connected together on the same connection ports at the SBOX, auto mode cannot be selected. This will conflict modes and cause error.
Prior to installing the SBOX, ensure a suitable location is selected, as an SBOX will create operational noises.
The SBOX must be installed horizontally and level.
There must be at least 1m distance between an SBOX and a branch joint pipe assembly.
There will be 30 seconds auto-checking function after the indoor and outdoor units have been activated.
Indoor units must be manually addressed.
8. ELECTRIC WIRING
8.1 Terminal base function
M-O
M-I
P Q E
P Q E P Q E
T2C1 T2C2
CN13
Fig. 7-3
TO INDOOR2 TO INDOOR1
BLUE
RED
Y/G
TO OUTDOOR
POWER IN
TRANS
Blue
White
Black
Yellow
YELLOW
ORANGE
Black
Black
Gray
M-O
M-I
P Q E
P Q E
T2C1 T2C2
CN13
XT2
Fig. 7-4
TO INDOOR
BLUE
RED
Y/G
TO OUTDOOR
POWER IN
TRANS
Yellow
YELLOW
ORANGE
Black
Black
Gray
L1 L2 L3 N
Fig. 8-1
To 380-415V 3N~ 50Hz
Fig. 8-2
Outdoor units centralised monitoring
Network accounting
Indoor units centralised controls
Indoor units communication
Outdoor units communication
Page 16
RDCI Series – All DC Inverter Outdoor Units
16 | ELECTRIC WIRING
8.2 SW2 query instructions
Use application of the SW2 spot check
Table.8-1
No. Normal display Display content Note
1 0. -- Outdoor unit address 0, 1, 2, 3 2 1. -- Individual Outdoor unit capacity 8, 10, 12, 14, 16 3 2. -- Modular outdoor unit qty. Available for main unit 4 3. -- Operation mode 0, 2, 3, 4, 5, 6 5 4. -- Total capacity of outdoor unit Capacity requirement 6 5. -- Cooling capacity (Auxiliary unit only display) capacity for main mode 7 6. -- Heating capacity (Auxiliary unit only display) capacity for main mode 8 7. -- T4 ambient temp. revision of cooling capacity
9 8. -- T4 ambient temp. revision of heating capacity 10 9. -- The outdoor unit actual operating capacity Capacity requirement 11 10. -- Speed of fan A 0, 1, ······, 14, 15 12 11. -- Speed of fan B 0, 1, ······, 14, 15 13 12. -- T2 average temp. Actual value 14 13. -- T2B average temp. Actual value 15 14. -- T3 pipe temp. (Left pipe temp.) Actual value 16 15. -- T5 pipe temp. (Right pipe temp.) Actual value 17 16. -- T4 ambient temp. Actual value 18 17. -- Discharge temp. of inverter compressor A Actual value 19 18. -- Discharge temp. of inverter compressor B Actual value 20 19. -- Modual temp. Actual value 21 20. -- Discharge pressure corresponding to the saturation temperature Actual value+30 22 21. -- The minimum overheating temp. of discharge Actual value 23 22. -- Current of inverter compressor A Actual value 24 23. -- Current of inverter compressor B Actual value 25 24. -- State of the evaporator or condenser 0, 1, 2, 3 26 25. -- Opening angle of EXV A Actual value÷8 27 26. -- Opening angle of EXV B Actual value÷8 28 27. -- High pressure Actual value×10 29 28. -- Qty. of indoor units That can communicate with indoor units 30 29. -- Qty. of cooling indoor units Actual value 31 30. -- Qty. of heating indoor units Actual value 32 31. -- Reserve 33 32. -- Night noise control mode 0, 1, 2, 3 34
33. -- Static pressure mode 0, 1, 2, 3
35 34. -- DC voltage A Actual value÷10 36 35. -- DC voltage B Actual value÷10 37 36. -- Reserve 38 37. -- Reserve Display code 8.8.8 39 38. -- Remove fault number of times 40 39. -- Check end
The display contents as followings: Normal display: When standby, the above position displays the address of the outdoor unit, and the low position displays the Qty. of indoor units that can communicate with the outdoor unit. When it is operating, it will display the rotation frequency of the compressor. Operation mode: 0-Off; 2-Cooling; 3-Heating; 4-Forced cooling; 5-Mixed cooling; 6-Mixed Heating. Fan speed: 0-stop; 1~15 speed increase sequentially, 15 is the max. fan speed. EXV opening angle: Pulse count=Display value×8; State of the evaporator or condenser: 0-close/condenser; 1-All evaporator; 2-Left evaporator/right condenser; 3-Left evaporator/close Night noise control mode: 0-Night noise control mode; 1-silent mode; 2-Super silent mode; 3-No priority Static pressure mode: 0-static pressure is 0 Mpa; 1-Low static pressure; 2-Medium static pressrue; 3-High static pressure
Page 17
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
ELECTRIC WIRING | 17
8.3 Explanation of mainboard
ENC1 ENC3 S12 S3
S7
S1
ENC2
S4
S2
ENC4
ENC4
Fig. 8-3
Outdoor address,
dial switch
Quantity setting
dial switch
of Indoor units
Force
cooling
Outdoor power
dial switch
Query button
Page 18
RDCI Series – All DC Inverter Outdoor Units
18 | ELECTRIC WIRING
8.4 Dial codes definition
S1 definition
ON
S1
Starting time is set to 10 minutes
ON
S1
Starting time is set to 12 minutes (Default Factory setting)
S2 definition
ON
S2
Night time selection for 6h/10h (Default Factory setting)
ON
S2
Night time selection for 6h/12h
ON
S2
Night time selection for 8h/10h
ON
S2
Night time selection for 8h/12h
S3 definition
ON
S3
Night silent mode (Default the Factory Set)
ON
S3
Silent mode
ON
S3
Super silent mode
ON
S3
None silent mode
S4 definition
ON
S4
Static pressure mode is 0 MPa (Default the Factory Set)
ON
S4
Static pressure mode is low pressure (Reserve position, use for customised unit)
ON
S4
Static pressure mode is medium pressure (Reserve position, use for customised unit)
ON
S4
Static pressure mode is high pressure (Reserve position, use for customise unit)
S7 definition
ON
S7
Reserve
ENC3 and S12 definition
ENC3
ON
S12
To set the number of indoor units to 0-15
ENC3
ON
S12
To set the number of indoor units to 16-31
ENC3
ON
S12
To set the number of indoor units to 32-47
ENC3
ON
S12
To set the number of indoor units to 48-63
ENC1 definition
Outdoor unit address Set the switch to address the unit 0-3 0 Stand for main unit 1-3 Stand for slave uint
ENC2 definition
Outdoor unit capacity setting switch Set the switch to the correct HP output For outdoor unit capacity setting 0: 8HP 1: 10HP 2: 12HP 3: 14HP 4: 16HP
S3 definition
Network address setting dial switch Set the switch to the correct setting For network address setting 0: system 1 1: system 2 2: system 3 ... 7: system 8
Page 19
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
ELECTRIC WIRING | 19
Explanation of main board
Table.8-2
No. Content
1
Discharge temp. Sensor port for inverter compressor A
2
Discharge temp. Sensor port for inverter compressor B
3
Temperature of module sensor port
4
Reserve
5
Wiring port for communication between indoor and outdoor units, indoor unit network, outdoor unit network and network accounting
6
Three-phase detection port
7
Reserve
8
Power output of transformer No.1
9
Power output of transformer No.2
10
Heat output terminal of the inverter compressor A
11
Heat output terminal of the inverter compressor B
12
Exv A driving port
13
Exv B driving port
14
Four-way valve output terminal
15
One-way valve output terminal
16
Power control output terminal
17
Null line terminal
18
Power output of transformer No.1
19
Power output of transformer No.2
20
Activation port of inverter module B
21
Port for inverter module B voltage inspection
22
Port for inverter module A voltage inspection
23
Activation port of inverter module A
24
Power supply port for main control panel
25
ON/OFF signal input port for system high pressure inspection
26
ON/OFF signal input port for system low pressure inspection
27
Reserve
28
Reserve
29
Current inspection port of the inverter compressors A and B
30
Input port for system high pressure inspection
31
Communication ports between outdoor units
32
Detection port for outdoor ambient temp. and left pipe Temp.
33
Detection port for right pipe Temp.
34
Control port of DC fan B
35
Control port of DC fan A
8.5 Electric parameters of outdoor unit
Table.8-3
System
Outdoor Unit Power Current Compressor OFM
Voltage Hz Min. Max. MCA TOCA M FA MSC RLA KW FLA
8HP 380~415 50 342 440 18.4 20.8 25
17.4
0.42 3.6 16.5
15.9
10HP 380~415 50 342 440 20.6 22.1 25
17.4
0.42 3.6 16.5
15.9
12HP 380~415 50 342 440 21.8 22.8 25
17.4
0.42 3.6 16.5
15.9
14HP 380~415 50 342 440 27.9 31.8 25
17.4+10.5
0.71 5.9 16.5+10.0
15.9+9.6
16HP 380~415 50 342 440 33.4 32.8 25
17.4+10.5
0.71 5.9 16.5+10.0
15.9+9.6
Notes:
1. The current value of combination unit is the total value of each basic model(refer to Table.8-3)
For example: 46HP=14HP+16HP*2 Power current: MCA=27.9+33.4*2=94.7
TOCA=31.8+32.8*2=97.4
MFA=35+35*2=105 Compressor: RLA=(17.4+10.5)*3 OFM: FLA=5.9+5.9*2=17.7
2. RLA is based on the following conditions.
Indoor temp. 27°C DB/19°C WB;Outdoor temp. 35°C DB
3. TOCA means the total value of each OC set.
4. MSC means the Max. current during the starting of compressor.
5. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
6. Maximum allowable voltage variation between phase is 2%.
7. Selection wire size based on the larger value of MCA or TOCA.
8. MFA is used to select the circuit breaker and the ground fault circuit
interrupter (earth circuit breaker). Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) KW: Rated Motor Output (kW)
Page 20
RDCI Series – All DC Inverter Outdoor Units
20 | ELECTRIC WIRING
8.6 Electric wiring of indoor/outdoor units
CAUTION
Install a separate power supply for indoor unit and outdoor unit.
An all-pole disconnection device which has at least 3 mm separation distance in all poles and a residual current device (RCD) shall be incorporated into the fixed wiring in accordance with national wiring regulations.
All indoor units must be connected to the same electrical power supply incorporating a leak protector and must be able to be isolated off one switch. Each indoor unit must also have an electrical isolation as per the national wiring regulations.
3 Core shielded cable must be used for communication wires.
8-6-1 Outdoor unit power wiring
With power facilities
Indoor power supply
CAUTION
Ensure the correct communication wires are with the correct system.
Electrical power supply and communication cables must be installed in separate containment. (Current capacity of power supply: less than 10A--300mm, less than 50A--500mm.)
When connecting multiple outdoor units, ensure the address settings have been done prior to powering on.
8.7 Signal wire of indoor/outdoor units
Communication wiring must be 3 core shielded cables and must be > 0.75mm in size. Communication cables are polarity sensitive.
8.8 Example for power wire connection
Fig. 8-4
Leakage protector
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Branch box
GND
GND
GND
GND
Leakage
protector
Outdoor unit
power supply
380-415V 3N~ 50Hz
Manual
switch
Manual switch
Fig. 8-5
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Branch box
GND
GND
GND
GND
GND
GND
Leakage
protector
Power facilities 1
(with leakage protector)
Power facilities 12
(with leakage protector)
Manual
switch
192103114
12
5136147158
16
Fig. 8-6
Indoor power
Leakage protector
Manual switch Branch box Indoor unit
(P Q E)
P
Q
P
Q
P
Q
P
Q
P
Q
(P Q E)
(H1 H2 E) (H1 H2 E) (H1 H2 E)
(H1 H2 E)
Fig. 8-7
Outdoor unit (master unit)
Outdoor unit (slave unit)
Outdoor unit
(slave unit)
Outdoor unit
(slave unit)
Signal wire between outdoor units
SBOX
(open)
(open)
(open)
(open)
resistor
resistor
resistorresistor
resistor
(open)
group control
The indoor unit where the communication wire ends (last leg), should have a resister (suppled) fitted between port P and port Q
Signal wire for indoor/ outdoor units
SBOX S BOX SBOX
Shielded layers must terminate to
ground.
L2 L3 NL1 P Q EEH2H1
L N EQP
L2 L3 NL1 P Q EEH2H1 L2 L3 NL1 P Q EEH2H1
C D EBA L N E C D EBA L N E C D EBAQP QP
L2 L3 NL1
C D EBA C D EBA C D EBA
L N EQP
EQP
L2
L3
N
L1
Outdoor unit (master unit)
Indoor unit
Signal wire between indoor/outdoor units
Branch Box Branch Box Branch Box Branch Box
Wire controller Wire controller Wire controller
Signal wire between outdoor units
Signal wire between indoor unit and wire controller
Power wire between indoor units
Indoor unit Indoor unit
Outdoor unit (slave unit) Outdoor unit (slave unit)
Power(380-415V 3N~ 50Hz)
SBOX
Fig. 8-8
Page 21
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
TEST RUN | 21
9. TEST RUN
9.1 Inspection and confirmation before commissioning
Check and confirm that refrigeration pipework and communication wires on the indoor and outdoor units have been connected to the correct refrigeration system.
Power voltage is within ±10% of rated voltage.
Before powering on, confirm there is no short circuit on each wire.
Ensure new installations have passed a nitrogen strength test.
Confirm the vacuum process has been carried out.
9.2 Preparation
Calculate the amount of refrigerant charge needed using table 5-12.
Have the system plan, system pipework diagram and control wiring diagram to hand.
Record the setting address codes on the system plan.
Ensure the power to the compressors has been on for a minimum of 12 hours before starting the system.
Check whether the power phase sequence of outdoor unit is correct.
Ensure all dial switches on the indoor and outdoor units have been set with accordance to the installation manual.
9.3 Fill the name of connected system
To clearly identify the connected systems between two or more indoor units and outdoor units, select names for every system and record them on the nameplate on the outdoor electric control box cover.
9.4 Caution on refrigerant leakage
This air conditioning unit uses R410a which is a non flammable refrigerant.
The room for the air conditioning unit should be big enough to ensure that a refrigerant leakage cannot reach a critical thickness.
Critical thickness-----the maximum exposure of refrigerant without any harm to person. R410A critical thickness: 0.3 [kg/m3].
Calculate the critical thickness using the following steps, and take necessary actions.
Calculate the sum of the charge volume (A[kg]). Total refrigerant volume=refrigerant volume when delivered (nameplate)+superaddition
Calculate the indoor cubage (B[m3]) (as the minimum cubage)
Calculate the refrigerant thickness.
A [kg]
Critical thickness: 0.3 [kg/m3]
B [m3]
Countermeasure against overhigh thickness
Install mechanical ventilator to reduce the refrigerant thickness under critical level. (ventilate regularly)
Install leakage detector alarming device related to mechanical ventilator if you can not regularly ventilate.
Fig. 9-1
Model(indoor unit)
Room Name Eg: Indoor unit (A) of the first system on second floor is recorded as:-2F-1A
Fig. 9-2
Outdoor unit
Indoor unit
Room full of leaking refrigerant (All the refrigerant has leaked)
Fig. 9-3
Indoor unit
OA
b. Leakage detector alarming device
related to mechanical ventilator
a. Ventilation peristome
Page 22
Notes
Installation Engineers Signature
Print Name
Commissioning Engineers Signature
Print Name
Commissioning Engineer
Engineers Commissioning Number
Engineers Service Number
Commissioning Date
Project Name:
Project Address
Project Reference Number
Page 23
Duration
Duration
Duration
Duration
Notes
Tripple Evacuated
Evacuation Reading (Must be 1.5 Torr or 0.5mb)
Pressure Tested Too
Strength Tested Too
Sbox Installation Condition
Sbox Acces Condition
Power Status
Indoor Unit Installation Condition
Indoor Unit Access
Leak Tested Too
Pre Commissioning Checks
Condenser Installation Condition
Condenser Access Condition
Page 24
Standard Refrigeration Charge
Power Supply
Additional Refrigerant
Outdoor Unit Address Setting
Total Pipe Length
Total Index of Indoors
Outdoor Serial Number
Compressor 1 Serial Number
Compressor 2 Serial Number
Outdoor Unit Details
Outdoor Location
Outdoor Serving Location
Outdoor Model Number
Page 25
Power Supply
Address Setting
Sbox Port Setting
Serial Number
Serial Number
Power Supply
Address Setting
Sbox Setting
Indoor Unit 4
Model Number
Model Number
Indoor Unit 2
Model Number
Serial Number
Power Supply
Address Setting
Sbox Port Setting
Indoor Unit 3
Power Supply
Address Setting
Sbox Port Setting
Serial Number
Indoor Details
Indoor Unit 1
Model Number
Page 26
Power Supply
Address Setting
Sbox Port Setting
Serial Number
Serial Number
Power Supply
Address Setting
Sbox Setting
Indoor Unit 8
Model Number
Model Number
Indoor Unit 6
Model Number
Serial Number
Power Supply
Address Setting
Sbox Port Setting
Indoor Unit 7
Power Supply
Address Setting
Sbox Port Setting
Indoor Details
Indoor Unit 5
Model Number
Serial Number
Page 27
Power Supply
Address Setting
Sbox Port Setting
Serial Number
Serial Number
Power Supply
Address Setting
Sbox Setting
Indoor Unit 12
Model Number
Model Number
Indoor Unit 10
Model Number
Serial Number
Power Supply
Address Setting
Sbox Port Setting
Indoor Unit 11
Power Supply
Address Setting
Sbox Port Setting
Indoor Details
Indoor Unit 9
Model Number
Serial Number
Page 28
Power Supply
Address Setting
Sbox Port Setting
Serial Number
Serial Number
Power Supply
Address Setting
Sbox Setting
Indoor Unit 16
Model Number
Model Number
Indoor Unit 14
Model Number
Serial Number
Power Supply
Address Setting
Sbox Port Setting
Indoor Unit 15
Power Supply
Address Setting
Sbox Port Setting
Indoor Details
Indoor Unit 13
Model Number
Serial Number
Page 29
Comms V
Return Air Cooling
Heating Off
Return Air Heating Unit Address
Indoor Unit Data
Model Number
Cooling Off
Page 30
Power V Comms V Address
Compressor Serial Num 1 & 2
Compressor Serial Num 1 & 2
Compressor Serial Num 1 & 2
Heating
Cooling
Low Pressure Reading
Low Pressure Reading
Low Pressure Reading
Cooling
Heating
Acces To Sbox
Compressor Serial Num 1 & 2
Sbox Model Number
Serial Number
Compressor Discharge Temp
Compressor Frequency
High Pressure Reading
Low Pressure Reading
Serial Number
Serial Number
Compressor Discharge Temp
Compressor Frequency
High Pressure Reading
Outdoor 4
Model Number
Heating
Cooling
High Pressure Reading
Model Number
Outdoor 2
Model Number
Serial Number
Compressor Discharge Temp
Compressor Frequency
High Pressure Reading
Outdoor 3
Outdoor/Sbox Data
Outdoor 1
Model Number
Serial Number
Heating
Cooling
Compressor Discharge Temp
Compressor Frequency
Page 31
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
| 31
Page 32
6 720 862 437 (2016/10)
RDCI Series – All DC Inverter Outdoor Units
32 | F-Gas information
Model Product Description
N.Cooling
Capacity
N.Heating
Capacity
Refrigerant GWP
CO2
equivalent
for pre-
charged
refrigerant
Pre-
charged
Refrigerant
Amount
Additionally
Charged
Refrigerant
Overall amount of refrigerant
after
charging
Overall CO2
equivalent
after charging
[kW] [kW] - - [tonnes] [kg] [kg] [kg] [kg]
RDCI8/25-3 Outdoor Unit, 3-pipe, 3ph 25,2 27 R-410A 2088 20,9 10
RDCI10/28-3 Outdoor Unit, 3-pipe, 3ph 28 31,5 R-410A 2088 20,9 10
RDCI12/33-3 Outdoor Unit, 3-pipe, 3ph 33,5 37,5 R-410A 2088 20,9 10
RDCI14/40-3 Outdoor Unit, 3-pipe, 3ph 40 45 R-410A 2088 27,1 13
RDCI16/45-3 Outdoor Unit, 3-pipe, 3ph 45 50 R-410A 2088 27,1 13
Frequency of Refrigerant Leak Checks
- If the amount of tons CO2 equivelant/circuit is from 5 to 50 tons, then frequency to check is 12 months in case system is without a leakage dedection system or 24 months in case system is with a leakage dedection system.
- If the amount of tons CO
2 equivelant/circuit is from 50 to 500 tons, then frequency to check is 6 months
in case system is without a leakage dedection system or 12 months in case system is with a leakage dedection system.
- If the amount of tons CO
2 equivelant/circuit is over 500 tons, then frequency to check is 3 months
in case system is without a leakage dedection system or 6 months in case system is with a leakage dedection system.
Page 33
Page 34
6 720 862 437 (2016/10)
RDCI Series – All DC Inverter Outdoor Units
34 |
Page 35
RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
| 35
Page 36
Loading...