Features & Benets ...............................................................................................................................................................................................
3
Performance Data & Specications
Air Defrost ....................................................................................................................................................................................................4-5
Electric Defrost ...........................................................................................................................................................................................6-7
Hot Gas Defrost .......................................................................................................................................................................................... 8-9
Dimensional Data ................................................................................................................................................................................................10
Replacement Parts by InterLink™ ..................................................................................................................................................................10
Physical Data .........................................................................................................................................................................................................11
Standard Nozzle Selection ...............................................................................................................................................................................
We have made a commitment to customer needs, innovation and environmental stewardship and have dedicated
ourselves to delivering energy-ecient choices. PSC and EC motors will reduce costs, improve the bottom line and
enhance equipment performance and service life.
11
Choose the most energy-ecient motor available for evaporators.
Nomenclature
The EC motor is an Energy Solutions® option on new Bohn Low Velocity
Center Mount evaporators. Available on all new equipment or as an easyto-install, drop-in replacement aftermarket part from InterLink™
Commercial Refrigeration Parts. Because they’re a drop-in replacement
for existing shaded pole and PSC motors, installation is quick and easy.
It’s a high impact, quick payback solution for reducing costs and
achieving green initiatives without replacing the entire system.
EC motors by InterLink are up to 75% ecient - that’s a 51-59% increase
over shaded pole motors and a 30-35% increase over permanent-split
capacitor (PSC) motors. With all of this added eciency, you can count
on more energy savings and lower operational costs while taking a
step in the right direction toward conserving our planet’s resources.
To learn more about EC motors, visit www.interlinkparts.com/ec.
WK100
Model SeriesCapacityElectrical CodeDesign Revision
WK = Bohn Low Velocity Center
Mount, air defrost
WKE = Bohn Low Velocity Center
Mount, electric defrost
WKG = Bohn Low Velocity Center
Mount, hot gas defrost
2
AC
# x 100 = BTUHA = 115/1/60
B = 208-230/1/60
AH = 115/1/60 (PSC)
BH = 208-230/1/60 (PSC)
AE = 115/1/60 (EC)
BE = 208-230/1/60 (EC)
Low height makes it ideal for low ceiling coolers - larger models are only 15 inches tall, allowing for maximum headroom
•
and more product storage
Unit designed to be mounted flush against the ceiling or suspended on rods
•
Heavy gauge grained aluminum cabinet cleans easily and looks attractive
•
Stainless steel screws prevent rust streaks
•
Liquid line solenoid wire harness is factory-installed for quick installation
•
Wire fan guards with PVC coating for durability
•
All electrical components factory wired to terminal board and identified, making it easy to field wire the unit
•
Cabinet design features access panels on each end for easy access to electrical and refrigeration components
•
Fan panel is lightweight and can easily be lowered for easy servicing and installation
•
Expansion valve mounts inside the cabinet
•
Coils
Sweat connections to reduce potential for leaks
•
Coils are dehydrated and sealed at the factory
•
Internally enhanced tubing and fin design for higher efficiency
•
Electric defrost models incorporate high quality tubular heaters and a standard fixed defrost termination thermostat
•
Hot gas defrost models come with a shipped-loose adjustable fan delay and defrost termination thermostat
•
Drain Pan
Double drain pan eliminates drain pan sweating•
Motors
Motor rail is design for maximum strength and durability
•
Motors are life lubricated and thermal overload protected
•
EC Motors (optional) available factory-installed or as a drop-in replacement through InterLink™ Commercial Refrigeration
•
Parts in 115/1/60, 208-230/1/60
PSC are optional for 115/1/60, 208-230/1/60 voltages
•
PSC are required for 50 Hz operation
•
Options
Unit Configurations: mounted components, pre-assembled, pre-charged and Beacon II™
•
- Units available with mounted TXV and mounted TXV / solenoid valve
- Pre-assembled units come with mounted TXV, liquid line solenoid valve and room thermostat
- Pre-charged units come with mounted TXV, liquid line solenoid valve, room thermostat and quick connect fittings
(limited availability)
- Mounted room thermostat option
- Beacon II units come with electronic expansion valves, pressure transducer, temperature sensors and Beacon control board
Most models available with glycol circuiting (see glycol product brochure)
•
Units available with stainless steel housing and drain pan
•
Units available with copper fins. Air defrost units also available with polyester coated fins or various coil coatings options
•
All WK Series units are UL-listed for US and Canada and meet NSF standards
For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at
50 Hz will not see a reduction in performance due to the electronic control of the motor)
10°F TD
25°F SST
BTUH
6°C TD
-4°C SST
WattsBTUHWatts
15°F TD
25°F SST
-4°C SST
6
Page 7
Specifications
Model WKE Electric Defrost | 60 Hz
Shaded Pole MotorPSC MotorEC Motor
Model
WKE0501.11350.5900.5552,0008.7
WKE0751.11350.5900.5552,40010.5
WKE1002.22701.01801.01102,80012.2
WKE1302.22701.01801.01104,00017.4
WKE1552.22701.01801.01104,00017.4
WKE1803.34051.52701.51654,00017.4
WKE2104.45402.03602.02205,20022.6
WKE2704.45402.03602.02205,20022.6
WKE3405.58102.54502.52757,00030.4
230/1/60230/1/60230/1/60
AmpsWattsAmpsWattsAmpsWattsTotal Amps
Model WKE Electric Defrost | 50 Hz
PSC MotorEC Motor
Model
WKE0500.4800.5551,8308.3
WKE0750.4800.5552,20010.0
WKE1000.81601.01102,56011.6
WKE1300.81601.01103,66016.6
WKE1550.81601.01103,66016.6
WKE1801.22401.51653,66016.6
WKE2101.63202.02204,76021.6
WKE2701.63202.02204,76021.6
WKE3402.04002.52756,40029.1
220/1/50220/1/50
AmpsWattsAmpsWattsTotal Amps
Watts
Heaters
220/1/50
Defrost Heater
Watts
230/1/60
7
Page 8
Performance Data
Model WKG Hot Gas Defrost | 60 Hz
Capacity
Model
10°F TD
25°F SST
BTUH
6°C TD
-4°C SST
WattsBTUHWatts
15°F TD
25°F SST
8°C TD
-4°C SST
WKG10010,0002,93015,0004,39021,4502,465
WKG13013,0003,81019,5005,71021,4702,499
WKG15515,5004,54023,2506,81021,4602,482
WKG18018,0005,27027,0007,91032,1303,621
WKG21021,0006,15031,5009,23042,8404,828
WKG27027,0007,91040,50011,86042,8004,760
WKG34034,0009,96051,00014,94053,5005,950
Fan Data
No.CFM
m3h
Model WKG Hot Gas Defrost | 50 Hz
Capacity
Model
10°F TD
25°F SST
BTUH
6°C TD
-4°C SST
WattsBTUHWatts
15°F TD
25°F SST
8°C TD
-4°C SST
†
No.CFM
Fan Data
m3h
WKG1009,500278014,300419021,3102,227
WKG13012,400363018,500542021,3302,261
WKG15514,700431022,100647021,3202,244
WKG18017,100501025,700753031,9203,264
WKG21020,000586029,900876042,5604,352
WKG27025,700753038,5001128042,5304,301
WKG34032,300946048,5001421053,1605,372
†
For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at
50 Hz will not see a reduction in performance due to the electronic control of the motor)
Optional Liquid Line Bypass Kit For Hot Gas Defrost
The WKG may be eld piped for hot gas defrost using the optional bypass kit.
When compressor vapor, in reverse cycle defrosting, is directed back into the evaporator at the suction
connection, it condenses into liquid. The eld-installed liquid line bypass kit directs the condensed liquid
around the thermostatic expansion valve and back into the liquid line.
Bypass kits include bypass piping, check valve and instructions. Adjustable fan control is shipped loose
with hot gas units.
InterLink™ is your link to a complete line of dependable and certied
commercial refrigeration parts, accessories and innovative electronic
controls for all Bohn equipment. At InterLink, we provide our
wholesalers with a comprehensive selection of product solutions
and innovative technologies for the installed customer base.
And every product is built to ensure the same high performance
standards with which all Heatcraft Refrigeration Products (HRP)
brands are built — backed by a dedicated team to serve every
customer need, delivering at the best lead times in the industry.
Dependable. Versatile. Courteous.
Finally, one simple source for all your replacement needs from a
name you can trust.
For parts, please contact (800) 686-7278 or visit www.interlinkparts.com.
Electrical Components/Miscellaneous
22512601Terminal Strip1 - 5
2891040Room Thermostat1 - 5
10
No. FansAir DefrostElectric Defrost Hot Gas Defrost
*Also suitable for R-507, R-502, R-134A, R-401A, R-402A
NOTE: Nozzles sized for 95°F liquid temp. at expansion valve. Refer to manual H-IM-64 if liquid temp. is not 95°F
Room temperature of 35°F for air defrost models and 28°F for electric/hot gas models
Consult Bohn Application Engineering if evaporator TD is not 10° - 15°F, (room temp. - saturated suction temp.)
Distributor Tube (in.)No. of
ODLength
Circuits
R-404A*R-22
Caution: Refrigeration system will not perform properly without correct nozzle!
11
Page 12
For more information on Bohn refrigeration products, contact
your Sales Representative or visit us at www.thecoldstandard.com.
A Brand of Heatcraft Refrigeration Products LLC
2175 West Park Place Blvd. • Stone Mountain, GA • 30087
800.537.7775 • FAX 770.465.5990
www.thecoldstandard.com
Since product improvement is a continuing eort, we reserve the right to
make changes in specications without notice.
BN-LVTB-0508 | Version 000
Loading...