Expanded (Locked) Auxiliary Tubes:
These tubes support the coil with ns and refrigerant
carrying tubes. They do not carry refrigerant and are
tightly tted on end supports and center supports.
Free Floating Circuited Coil Tubes:
These tubes carry refrigerant and never touch
and sheet metal (end supports and center
supports).
Air Discharge Condensing Units
All BLV, BDVS, JLD and JDDS
units include a limited
Five Year Warranty
against condenser leaks at tube sheets
and center supports.
All condensers use the Floating Tube™ coil design to eliminate refrigerant leaks at the tube
sheets. Additional tubes are added to the condenser coil. These tubes are expanded into the
aluminum ns and condenser tube sheets. These anchor tubes support the weight of the coil,
but are not a part of the refrigerant circuit.
The tubes in the refrigerant circuit are expanded into the ns, but “oat” through oversized
holes in the tube sheets. Tube sheet leaks are virtually eliminated, since the tubes which carry
refrigerant never come in contact with the tube sheet.
3
Beacon II
™
™
Limitizer
®
Beacon II™ Refrigeration System is a patented pre-
assembled, factory installed refrigeration system featuring an
integrated microcomputer-based electronic control board. Beacon
™
II
oers:
• Complete factory installation, wiring and testing which
saves time and money!
• Simplied eld electrical connections and 24 volt wiring
between condensing and evaporator coil.
• Preset factory superheat allowing the system to run more
eciently and reducing future adjustments.
• Monitors and controls box temperature,
evaporator superheat, system status and
defrost.
• Monitor and make system changes
remotely via modem and exclusive
Beacon II
Smart Controller.
• Data logging capabilities with Smart
Controller.
™
Smart II software with
Beacon II™ Smart Controller is an optional system monitoring
and programming control device. It allows for adjustments to be made
at the push of a button from a conveniently mounted location. Beacon
™
II
Smart Controller also allows you to monitor
and make changes to the refrigeration system
via modem connection from anywhere in the
world. One Smart Controller can program and
control up to four condensing units with up to
four evaporators on each system. That’s more
control in your hands!
The patented Beacon II
Smart Controllers is uniquely designed to predict frost accumulation
and initiates defrosts only when they are needed. It also initiates
defrosts to react to operation anomalies, like product deliveries and
product pull-down. Typical electric defrost systems have 4 defrosts per
day. Using the Smart Defrost system can reduce the number of defrosts
to 0, 1, or 2 per day. That’s a 75% reduction on average. This greatly
reduces the amount of energy used and
in turn reduces operating costs.
™
Smart Defrostsystem, available with
The Need For Head Pressure Control
Refrigeration condensing units must eciently perform at varying
ambient conditions. A properly sized unit will adequately perform
at even the highest summer ambient temperatures. However, in
situations where the system must operate the majority of the time at
less than design temperature, a means of providing adequate head
pressure for refrigerant ow is desirable. The BLV & JLD units have an
adjustable Limitizer® method of head pressure control.
The Bohn Limitizer® System
The Limitizer® system is a factory assembled system utilizing a Limitizer®
control to maintain a constant head pressure at the air cooled
condensing unit during all climatic conditions when the ambient
temperature drops below 75°F (typical).
When the ambient is above 75°F, the condenser pressure is above
the Limitizer® valve setting and therefore, the valve remains in the full
open position.
As the temperature drops below 75°F, the pressure at the condenser
also drops below the setting of the Limitizer® valve. The Limitizer®
valve, sensing the reduction in condensing pressure, modulates
toward the closed position, thus restricting the ow of liquid from the
condenser. The liquid backs up into the condenser and oods a portion
of the tubes, thus reducing the overall capacity of the condenser. The
Limitizer® valve will continue to ood the condenser until the pressure
setting has been reached, thus providing proper head pressure at all
ambient temperatures.
While the condenser oods, a second line pressurizes the receiver
through another valve. Therefore, the refrigerant flow from the
condenser to the receiver modulates with conditions. However, the
bypass from the discharge line maintains a minimum receiver pressure.
These valves are adjustable and the minimum receiver pressure may
be reset higher or lower depending upon application situations of a
particular job. The Limitizer® system uses this two-valve, adjustable
design.
Beacon II™ Smart II Software makes it easy to adjust and
monitor one or more refrigeration systems as well as capture minute
by minute system conditions. This Windows-based software allows
you to connect to the Beacon II
the world to monitor the systems, make adjustments and log minute
by minute system conditions.
This data logging capability
is critical in the food service
industry.
™
Smart Controller from anywhere in
4
L
U
®
C
US
Single Vertical Air Discharge Condensing Unit
The B*V Outdoor Discus® Condensing Unit features a
leak resistant design which includes:
1. The Floating Tube™ coil design. Refrigerant-carrying copper
tubes do not contact any metal support sheets; instead,
the coil is constructed with expanded anchor tubes that
support the coil construction and do not carry refrigerant.
The coil design eliminates one of the major causes of leaks in
refrigeration systems.
2. Limited ve-year warranty against condenser tube sheet and
center support leaks.
3. Designed for use with R-404A, R-507, or R-22
4. Polyol ester oil charge on all units.
5. Prebent copper tubes minimize welded joints on
internal piping.
6. All sweat type connections, no are joints to leak.
7. Fixed high pressure switch eliminates capillary tubes.
8. Electronic oil pressure control.
9. Service Mate
™
module to assist troubleshooting.
Standard Features
1. High eciency Copeland Discus® compressors
with POE oil.
2. Spring mounted compressor with suction and discharge
vibration eliminators.
3. Crankcase heater.
4. Thermally protected, permanently lubricated ball bearing
condenser fan motors.
5. Separate subcooling circuit in condenser for added capacity
and vapor-free liquid.
6. Receivers are sized for sucient pumpdown capacity with inlet
and outlet service valves.
7. Pressure relief valve on receiver.
8. Sealed liquid line lter drier and sight glass.
9. Electrical controls, including compressor contactor and
optional defrost control, are located in easily accessible control
box with a hinged cover.
10. Service Mate
11. Pumpdown Switch.
™
module to assist troubleshooting.
12. Cabinet is constructed from prepainted galvanized steel.
13. Convenient access panels for easy servicing to internal
components.
Factory-Installed Optional Features
1. Replaceable core liquid lter drier.
2. Liquid line solenoid valve.
3. Suction lter.
4. Replaceable core suction lter.
5. Suction accumulator.
6. Oil separator with discharge line check valve.
7. Air defrost timer.
8. Electronic defrost kits, including timer, evaporative fan
controller with fusing, defrost heater contactor(s),
lockout relay and terminal strip.
9. Fusing for defrost kits.
10. Evaporator holdout relays for systems with multiple electric
defrost evaporators.
11. Low ambient kit with heated and insulated receiver
with time delay.
12. Fused disconnect switch.
13. Non-fused disconnect switch.
14. Phase-loss protection.
15. Manual-reset high pressure switch.
16. Anti-short cycle timer.
17. Compressor circuit breakers.
18. Condenser fan cycling (standard on BDVS).
19. Three-way heat reclaim valve (n/a on BDVS).
20. Coated condenser coils for protection against corrosion
Nominal Horsepower
1200/1201 - 12 HP 2600 - 25 HP
1500/1501 - 15 HP 2700/2701 - 27 HP
2000/2001 - 20 HP 3000/3001 - 30 HP
2200/2201 - 22 HP 3500/3501 - 35 HP
2500/2501 - 25 HP 4000/4001 - 40 HP
®
, vertical discharge
Electrical Characteristics
C - 208-230/3/60
D - 460/3/60
K - 230/3/60
E - 575/3/60
Refrigerant
6 - R-404A or R-507, or R-22
Application
L - Low (0°F to -40°F suction)
H - High (+40°F to +10°F suction)
M - Medium (30°F to -10°F suction)
Single Vertical Air Discharge Condensing Unit
5
Electrical Box Features
Condenser Fan
Contactor and Fuses
Compressor Contactor
Single Compressor
Control Circuit Fuses
& Pumpdown Switch
All Service Control are located in a
separate electrical panel allowing
eld adjustments without
disconnecting power to the unit
Disconnect (not pictured) is
located in this area when supplied
(Not Shown) (Optional)
Single Vertical Air Discharge Condensing Unit
Prepainted Galvanized
Steel Cabinet
Phase Loss Monitor
(Optional)
Compressor Circuit
Breaker (Optional)
(Optional)
Evaporator Fan
Contactors & Fuses
Defrost Heater
Contactors & Fuses
3/8" Floating Tube
™
Coil Design
Condenser Coil
Internal Piping
Prebent Internal Piping
Eliminates Braze Joints
Electronic Oil
Pressure Control
Defrost Time Clock
(Optional)
Adjustable Low
Pressure Control
Fan Cycle Pressure Control and
Unloader Pressure Controls
(Optional)
Control Circuit
Terminal Board
Main Power Block
®
Limitizer
Pressure Valve
Liquid Receiver with
Roto-Lock Connections
and Service Valves Allow
Charge Isolation
6
Suction Accumulator
Oil Separator
(Optional)
Rigid Galvanized Steel
Base with Rigging Points
Electrical Service
Knockouts
Easily Accessible
®
Discus
Compressor
Medium Temperature - R-22
R-22
Model
B*V1500M6
B*V2000M6
B*V2500M6
B*V2600M6
B*V3000M690
B*V3500M690
B*V4000M690
Notes: For 50 cycle capacity, multiply values by .86
Notes: For 50 cycle capacity, multiply values by .86
All units will work in 120ºF / 48.9ºC ambient
Demand Cooling option needs to be ordered for Low Temperature R-22 operation
B*V =BLV is Limitizer®, BDVS is Beacon II™
BLV is Limitizer®, BDVS is Beacon II™
MCA = Minimum Circuit Ampacity
MOP = Maximum Overcurrent Protection
Beacon II™ and Air Defrost Units do not carry any of the evaporator fan or heater loads.
Power is brought directly to the evaporators and does not go through the condensing unit.
Mounted Electric Defrost Kits for BLV condensing units include:
Defrost timer, terminal strip, (1) evaporator fan contactor and:
One (1) defrost heater contactor for 1L and 1H codes
Two (2) defrost heater contactors for 2L and 2H codes
Four (4) defrost heater contactors for 4L and 4H codes
An evaporator heater hold out relay (option) is recommended when two or more evaporators are connected to a single (BLV)
condensing unit to allow termination on coils that have already defrosted to prevent unnecessary steaming.
This option is not needed on Beacon II™ (BDVS) systems wired for a Master / Slave operation.
Power is brought to each Beacon evaporator.
Each coil terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.
Contact factory for 575 volt electrical specication.
BLV is Limitizer®, BDVS is Beacon II™
MCA = Minimum Circuit Ampacity
MOP = Maximum Overcurrent Protection
Beacon II™ and Air Defrost Units do not carry any of the evaporator fan or heater loads.
Power is brought directly to the evaporators and does not go through the condensing unit.
Mounted Electric Defrost Kits for BLV condensing units include:
Defrost timer, terminal strip, (1) evaporator fan contactor and:
One (1) defrost heater contactor for 1L and 1H codes
Two (2) defrost heater contactors for 2L and 2H codes
Four (4) defrost heater contactors for 4L and 4H codes
An evaporator heater hold out relay (option) is recommended when two or more evaporators are connected to a single (BLV)
condensing unit to allow termination on coils that have already defrosted to prevent unnecessary steaming.
This option is not needed on Beacon II™ (BDVS) systems wired for a Master / Slave operation.
Power is brought to each Beacon evaporator.
Each coil terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.
Contact factory for 575 volt electrical specication.
Compressor
RLALRA
Condenser
No.
FLAMCAMOPMCAMOPMCAMOP
Fans
Beacon or
Air Defrost
Evap
Fan
Amps
Remote Loads: Four Contactors
Low Amps “4L”
Defrost
Htrs.
Amps
Elec. Defrost
Evap
Fan
Amps
Remote Loads: Four Contactors
Low Amps “4L”
Defrost
Htrs.
Amps
Elec. Defrost
Evap
Fan
Amps
High Amps: “4H”
Defrost
Htrs.
Amps
High Amps: “4H”
Defrost
Amps
Elec. Defrost
Elec. Defrost
Htrs.
15
Single Vertical Air Discharge Condensing Unit
High Eciency Models with Oversized Condensers
Remote Loads: One ContactorsRemote Loads: Two Contactors
Remote Loads: One ContactorsRemote Loads: Two Contactors
Low Amps “1L”
Evap
Htrs.
Amps
Elec. Defrost
MCAMOPMCAMOPMCAMOPMCAMOP
High Amps: “1H”
Evap
Htrs.
Amps
High Amps: “1H”
Evap
Htrs.
Amps
Elec.Defrost
Elec.Defrost
208-230 Volts
Low Amps “2L”
Fan
Amps
460 Volts
Low Amps “2L”
Fan
Amps
Evap
Htrs.
Amps
Evap
Htrs.
Amps
Elec. Defrost
Elec. Defrost
Electrical Data
High Amps: “2H”
Evap
Fan
Amps
Fan
Amps
Htrs.
Amps
High Amps: “2H”
Evap
Htrs.
Amps
Elec. Defrost
Elec. Defrost
BLV is Limitizer®, BDVS is Beacon II™
MCA = Minimum Circuit Ampacity
MOP = Maximum Overcurrent Protection
™
Beacon II
and Air Defrost Units do not carry any of the evaporator fan or heater loads.
Power is brought directly to the evaporators and does not go through the condensing unit.
Mounted Electric Defrost Kits for BLV and BBV condensing units include:
Defrost timer, terminal strip, (1) evaporator fan contactor and:
One (1) defrost heater contactor for 1L and 1H codes
Two (2) defrost heater contactors for 2L and 2H codes
Four (4) defrost heater contactors for 4L and 4H codes
An evaporator heater hold out relay (option) is recommended when two or more evaporators are connected to a single (BLV)
condensing unit to allow termination on coils that have already defrosted to prevent unnecessary steaming.
This option is not needed on Beacon II
™
(BDVS) systems wired for a Master / Slave operation.
Power is brought to each Beacon evaporator.
Each coil terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.
Contact factory for 575 volt electrical specication.
BLV is Limitizer®, BDVS is Beacon II™
MCA = Minimum Circuit Ampacity
MOP = Maximum Overcurrent Protection
Beacon II
™
and Air Defrost Units do not carry any of the evaporator fan or heater loads.
Power is brought directly to the evaporators and does not go through the condensing unit.
Mounted Electric Defrost Kits for BLV and BBV condensing units include:
Defrost timer, terminal strip, (1) evaporator fan contactor and:
One (1) defrost heater contactor for 1L and 1H codes
Two (2) defrost heater contactors for 2L and 2H codes
Four (4) defrost heater contactors for 4L and 4H codes
An evaporator heater hold out relay (option) is recommended when two or more evaporators are connected to a single (BLV)
condensing unit to allow termination on coils that have already defrosted to prevent unnecessary steaming.
This option is not needed on Beacon II
™
(BDVS) systems wired for a Master / Slave operation.
Power is brought to each Beacon evaporator.
Each coil terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.
Contact factory for 575 volt electrical specication.
Beacon or
Air Defrost
Evap
Fan
Amps
Remote Loads: Four Contactors
Low Amps “4L”
Defrost
Htrs.
Amps
Elec. Defrost
Evap
Fan
Amps
Remote Loads: Four Contactors
Low Amps “4L”
Defrost
Htrs.
Amps
Elec. Defrost
Evap
Fan
Amps
High Amps: “4H”
Defrost
Htrs.
Amps
High Amps: “4H”
Defrost
Htrs.
Amps
Elec. Defrost
Elec. Defrost
17
Single Vertical Air Discharge Condensing Unit
L
U
®
C
US
Dual Vertical Air Discharge Condensing Unit
Dual Vertical Air Discharge Condensing Unit
The JBD/JLD Series of dual compressor outdoor condensing
units are designed for use in commercial refrigerated
warehouse and light industrial applications. The units utilize
the Floating Tube™ coil design air cooled condenser design
and oer a premium warranty against tube sheet and
center support leaks. The JLD consists of two independent
refrigeration circuits in a single housing which can reduce
Design Features
• These condensing units can be congured
with Limitizer
control systems.
• A generous amount of clearance under the
condenser section of the unit has been provided
to allow ease of service to the coil section and
liquid and suction lters.
®
head pressure
requirements and installation and rigging costs. Standard
models are available in even horsepower congurations
from 24 to 80 horsepower; however, unequal horsepower
and other customer features can be designed to suit the
application. The JLD***PP models consist of one combined
refrigerant circuit.
• A minimal number of standard accessories
have been pre-congured into the base
design of the unit. Customization of the product
is made easily.
• All common serviceable controls are located in
a separate electrical compartment from the main
electrical box. Service is made easy without
disconnecting power to the unit.
18
The Electrical Box is divided into two compartments.
All serviceable controls are access without disconnecting power to the unit.
L
U
®
C
US
Standard and Optional Features
Standard FeaturesFactory-Installed Optional Features
1. High eciency Copeland Discus® compressors
with POE oil.
2. Thermally protected permanently lubricated ball
bearing condenser fan motors.
3. Electrical controls, including compressor contactor
and optional defrost control, are located in easily
accessible control box with a hinged cover.
4. Limitizer® (JLD) or head pressure
control systems.
5. Receivers are sized for sucient pumpdown
capacity with inlet and outlet service valves.
6. Cabinet is constructed from prepainted
galvanized steel.
7. Convenient access panels for easy servicing
to internal components.
8. Suction and discharge vibration eliminators.
9. Separate subcooling circuit in condensers
for added capacity and vapor-free liquid.
10. Sealed liquid line lter drier and sight glass.
11. Service Mate™ module to assist troubleshooting.
Additional Standard Features
for Parallel Piped Units
1. Replaceable core liquid line lter drier.
2. Replaceable core suction lter.
3. Suction accumulator.
4. Oil management system.
5. Not available with Beacon II
TM
System.
1. Replaceable core liquid line lter driers with
sight glasses.
2. Liquid line solenoid valves.
3. Suction lters.
4. Replaceable core suction lters.
5. Suction accumulators.
6. Oil separators with discharge line check valves.
7. Air defrost timers.
8. Electronic defrost kits, including timer, evaporative fan controller with fusing, defrost heater contactor(s), lockout relay and terminal strip.
9. Low ambient kits with heated and insulated
receiver with time delay.
10. Compressor loading.
11. External discharge line muers.
12. Phase-loss protection.
13. Manual-reset high pressure switches.
14. Anti-short cycling timers.
15. Compressor circuit breakers.
16. Condenser fan cycling (standard on JDDS).
17. Three way heat reclaim valve with mounted check valves.
18. Coated condenser coils for protection
against corrosion in harsh environments.
J*D = JLD is Limitizer®, JDDS is Beacon II™, JLD*PP is Parallel Piped
† Minimum Circuit Ampacity
†† Maximum Overcurrent Protection
** Loads are shown per compressor circuit.
***Number of contactors per compressor
Contact factory for 575 volt electrical specication.
J*D = JLD is Limitizer®, JDDS is Beacon II™, JLD*PP is Parallel Piped
† Minimum Circuit Ampacity
†† Maximum Overcurrent Protection
** Loads are shown per compressor circuit.
*** Number of contactors per compressor
Contact factory for 575 volt electrical specication.
MOP
††
25
Notes:
26
Notes:
27
For more information on Bohn refrigeration products, contact
your sales representative or visit us at www.heatcraftrpd.com.
A Brand of Heatcraft Refrigeration Products LLC
2175 West Park Place Blvd. • Stone Mountain, GA • 30087
(800) 537-7775 • FAX (770) 465-5990
www.heatcraftrpd.com
Since product improvement is a continuing eort, we reserve the right to
make changes in specications without notice.