All belt drive models (except 575V) are
Underwriter’s Laboratories, Inc. listed.
Belt Drive Fluid Coolers
Belt Drive Fluid Coolers
Model BFF
Model BFF
Specification Data
Specification Data
BOHN DIRECT DRIVE FLUID COOLERS
BOHN DIRECT DRIVE FLUID COOLERS
Belt Drive Fluid Coolers
Multiple fans, carefully matched to the coil surface cover a large
percentage of the face area providing uniform air distribution.
Energy efficient, three phase 1750 RPM motors with drip-proof,
grease lubricated ball bearings. Each motor is inherently
overcurrent protected providing built-in protection against single
phasing. All motors are factory wired with leads marked and
terminated in a single weatherproof junction box on outside of
the unit casing.
Convenient access panels are provided on each fan section for
ease in maintaining fans.
Casing is constructed of heavy gauge aluminum, or galvanized
steel.
Multiple fan sections, each powered by a separate motors, are
separated by a full width baffle to prevent air bypass during fan
cycling.
Motors are positioned within unit casing for weather protection.
Adjustable base provides ease in belt tension adjustment.
Each fan is equipped with heavy duty pillow block ball bearings.
Bearings are supplied with lubrication fittings shown. Fan shafts
are polished steel, precision machined to assure smooth
operation, minimum bearing wear. Shafts are coated with a
corrosion resistant dressing.
Fan guards are constructed of heavy gauge, close meshed, steel
wire zinc plated and iridite dipped to minimize corrosion.
Selection Formulas
Design Load (in BTUH) = GPM * (Ent. Fluid Temp. — Leaving Fluid Temp.) x (Fluid Constant Table 1)
Average Fluid Temperature =
T.D. = Entering Fluid Temperature — Entering Air Temperature
Base Capacity =
1,000 x T.D. x Table 2 Factor x Table 4 Factor
Entering Fluid Temp. + Leaving Fluid Temp.
2
Design Load (in BTUH)
= MBH/˚T.D.
Capacity (Actual) = Capacity (Catalog) x 1,000 x T.D. x Table 2 Factor x Table 4 Factor
PD/F (Actual) = PD/F (Catalog) x Table 3 Factor
2
Selection Procedure
Given Conditions:
BOHN DIRECT DRIVE FLUID COOLERS
BOHN DIRECT DRIVE FLUID COOLERS
Belt Drive Unit — BFF140˚F Entering Fluid Temp.
200 GPM120˚F Leaving Fluid Temp.
30% Ethylene Glycol Solution10 Ft. Water Max. P.D.
90˚F Ambient AirSea Level
Solution:
1.
Calculate Design Load
A. Determine average fluid temperature for factor selection
in Tables 2 and 3.
Average Fluid Temp. =
B. Design Load = 200 x (140—120) x 470 = 1,880,000
2.
Calculate Base Capacity
A. Determine T.D.
T.D. = 140—90 = 50˚F
140 + 120
2
= 130˚F
Fluid Cooler Correction Factor Tables
Table 1.
B. Determine Capacity Correction from Table 2
Capacity Correction Factor = 1.032
C. Determine Altitude Correction from Table 4
Altitude Correction Factor = 1.0
D.
Base Capacity =
3.Make selection from capacity tables using given conditions.
Model BFF 096, capacity of 37.57 MBH/˚T.D. meets the
requirements with “C” circuiting.
4.Convert pressure drop of selection to design condition P.D.
6.1 x .950 = 5.8 ft. water pressure drop at design condition.
5.Calculate actual unit rating at design conditions 37.57 x 1,000
x 50 x 1.032 x 1.0 = 1,938,612 BTUH.
1,880,000
1,000 x 50 x 1.032 x 1.0
= 36.43
Table 4. Altitude Correction Factors
%Fluid
GlycolConstant
0500
Fluid20480
Constants30470
40450
50433
Table 2.
% Average Fluid Temp. (˚F)
Glycol90100110120130140
01.079 1.081 1.083 1.086 1.090 1.095
Capacity201.030 1.035 1.042 1.047 1.054 1.058
Correction301.005 1.009 1.012 1.023 1.032 1.034
Factor40.928.943.960.9841.000 1.010
50.918.926.935.939.941.973
Table 3.
% Average Fluid Temp. (˚F)
Glycol90100110120130140
0.868.853.843.819.795.789
Pressure20.980.959.935.915.893.866
Drop301.055 1.025 1.000.975.950.923
Correction401.120 1.080 1.060 1.034 1.000.974
501.200 1.165 1.128 1.093 1.058 1.024
For average fluid temperatures below 90˚F or above 140˚F, contact the
factory for special application.