Bohn BBL10 Service Manual

Page 1
Replaces BN-RITB, January 2004
REACHIN UNIT COOLERS
Technical Guide
Models TA • TL • C • VA • BBM • BBL • KMK • RAMK • BTO • U
BNRITB
June 2009
www.thecoldstandard.com
Page 2
TABLE OF CONTENTS
Model TA Thin Prole Air Defrost .......................................................................................................................... 3
Model TL Thin Prole Electric Defrost .................................................................................................................4
Model C High Prole ................................................................................................................................................. 5
Model VA Vee-Aire ...................................................................................................................................................... 6
Models BBM/BBL Back Bar....................................................................................................................................... 7
Model KMK Kompact Mullion ................................................................................................................................ 8
Model RAMK Reverse Air Flow Kompact Mullion ........................................................................................... 9
Model BTO Twin Flow .............................................................................................................................................10
Model U Dual Aire Standard Coil ........................................................................................................................11
In order to ensure our products function reliably even in corrosive environments, Bohn oers coated coil options on many of our Reach-In products. These coatings provide superior protection in most common refrigeration environments. If you have a question about a specic application, please contact your Bohn representative.
E Solutions™ branded products and options are designed to exceed current energy and environmental standards. We have made a conscious commitment to developing environmentally innovative products that allow our customers to make energy ecient, eco-conscious choices. Products included in the E Solutions portfolio reduce costs, improve bottom lines, and enhance both equipment performance and service life. EC motors are an E Solutions option available on some models contained in this catalog. This oering reduces energy consumption and saves money.
©2009 Heatcraft Refrigeration Products, LLC
Page 3
MODEL TA
Thin Profile Air Defrost Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• Molded Lexan® guards and fans
• Drain tting mounted at 45-degree angle so drain can be run through back or bottom of refrigerator
• Expansion valve can be mounted inside the cabinet
• Stainless steel screws
• Motors are thermally protected and permanently lubricated
• Convenient, moistureproof motor plug
• Compact design! Does a big job in a small space
• Optional coated coil available (Model TAK) for enhanced protection in corrosive environments
• Internal junction box for electrical connection
• All models are UL listed for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection standard to reduce leaks
(are connection available as a ship loose option)
Application
Model TA
refrigerator and makes the entire top shelf area usable. The attractive low silhouette makes the unit particularly desirable for display type refrigerators. It can also be used in back bars, under counter cabinets, or wherever space is at a premium.
For 35° to 45°F xtures at 10° to 15° TD applications with 16 hours maximum compressor run time per day.
is a thin prole unit which mounts in the top of a
Nomenclature
TA K 17 B G
Model Coil Option Model Size Electrical Code Vintage
Thin Prole Air Defrost
Blank = Standard K = Coated
10-55 A = 115/1/60
B = 208-230/ 1/60
Performance & Electrical Data
Model
TA(K)10 1,000 120 1 0.8 0.4 3/8 3/8 1/2 14 TA(K)13 1,300 170 2 1.6 0.8 3/8 3/8 1/2 17 TA(K)17 1,700 210 2 1.6 0.8 3/8 3/8 1/2 21 TA(K)23 2,300 330 3 2.4 1.2 3/8 3/8 1/2 28 TA(K)30 3,000 360 3 2.4 1.2 3/8 1/2 1/2 33
TA(K)43* 4,300 540 4 3.2 1.6 1/2 5/8 1/2 44 TA(K)55* 5,500 650 5 4.0 2.0 1/2 5/8 1/2 53
* Models 43 and 55 require an external equalized expansion valve
BTUH
10°F TD
CFM Qty.
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil Inlet
OD
SuctionIDDrain
OD
Ship Wt.
Physical & Dimensional Data
Model
TA(K)10 14-5/8 14 15/16 13-1/2 10-1/2 11-3/8 4-1/2 8-7/8 2-1/2 15/16 4-3/8 16-1/2 TA(K)13 18-5/8 14 15/16 13-1/2 10-1/8 10-1/4 4-1/2 8-3/8 9-1/2 15/16 4-3/8 20-1/2 TA(K)17 22-1/8 15 15/16 14-1/2 11-1/8 12 4-1/2 9-3/8 11-1/4 15/16 4-3/8 24 TA(K)23 29-3/4 15 15/16 14-1/2 13 20-7/8 4-1/2 10-3/4 10-1/4 15/16 4-3/8 31-5/8 TA(K)30 38-1/8 15 15/16 14-1/2 13 29-3/4 4-1/2 10-3/4 9-3/4 15/16 4-3/8 40 TA(K)43 51-1/2 15 15/16 14-1/2 13 48-3/4 4-1/2 10-3/4 13-1/4 15/16 4-3/8 53-3/8 TA(K)55 51-1/2 15 15/16 14-1/2 13 49 6-3/4 10-3/4 11 15/16 4-3/8 53-3/8
A B C D E F H J K L M W
Dimensions (in.)
(lbs.)
3
Page 4
Model TL
Thin Profile Electric Defrost Reach-In Unit Cooler
Features
• Electric defrost ensures positive heat source
• Built-in fan delay allows coil to be chilled before returning to the normal cooling cycle
• Defrost terminates on coil temperature eliminating excessive defrost period
• Textured aluminum cabinet
• Molded Lexan® guard
• Knockouts provided on sides for electrical connections - opening in rear for coil connections
• Expansion valve can be mounted inside the cabinet
• Stainless steel screws
• Motors are thermally protected and permanently lubricated
• Internal junction box for electrical connection
• Plate type aluminum ns with full collars on expanded copper tubes
• Coils are dehydrated and sealed
• Easy to install and maintain
• All models UL listed for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection to reduce leaks
(are connection available as a ship loose option)
Application
Model TL low temperature unit cooler has a completely
automatic defrost system. Mounted in the top of a refrigerator, its extremely compact cabinet makes it possible to utilize the entire top shelf area for storage. Having a normal operating range of 15°F to -20°F, this unit is ideally suited for such applications as commercial freezers, ice cream boxes and bakery freezers.
Nomenclature
TL 12 B G
Model Size Electrical Code Vintage
Thin Prole Electric Defrost
09-53 A = 115/1/60
B = 208-230/1/6
Performance & Electrical Data
BTUH 10˚F TD Motor Data Heater Data Connections (in.) Approx.
Model
TL09 1,050 900 110 1 0.8 0.4 475 4.1 2.1 3/8 3/8 1/2 14 TL12 1,380 1,200 210 2 1.6 0.8 600 5.2 2.6 3/8 1/2 1/2 19 TL16 1,780 1,600 210 2 1.6 0.8 700 6.1 3.0 3/8 1/2 1/2 23
TL21^ 2,400 2,100 240 1 1.0 0.5 1,100 9.6 4.8 3/8 1/2 1/2 24
TL28 3,200 2,800 335 3 - 1.2 1,430 - 5.7 3/8 1/2 1/2 27 TL35^* 4,000 3,500 420 2 - 1.0 1,600 - 7.0 1/2 5/8 1/2 38 TL53^* 6,100 5,300 595 3 - 1.5 1,950 - 8.5 1/2 7/8 1/2 53
^ Model available with EC motors * Models 35 and 53 require an external equalized expansion valve
20˚F
SST
-10˚F SST
CFM Qty.
115/1/60
Total FLA
208-230/1/60
Total FLA
Watts
115/1/60
Amps
208-230/1/60
Amps
Coil InletODSuctionIDDrain
OD
Ship Wt.
(lbs.)
Physical & Dimensional Data
Model
TL09 14-5/8 14 15/16 13-1/2 10-1/2 11-3/8 4-1/2 8-7/8 2-1/2 15/16 4-3/8 - 1 16-1/2 TL12 18-5/8 14 15/16 13-1/2 10-1/8 10-1/4 4-1/2 8-3/8 9-1/2 15/16 4-3/8 - 1 20-1/2 TL16 22-1/8 15 15/16 14-1/2 11-1/8 12 4-1/2 9-3/8 11-1/4 15/16 4-3/8 - 1 24 TL21 22-1/8 16-1/2 15/16 16-1/2 14-1/2 18-7/8 6-3/4 11-7/8 17-1/4 15/16 4-3/8 - 1-1/2 24 TL28 29-3/4 15 15/16 14-1/2 13 20-3/4 6-3/4 9-3/4 9-7/8 15/16 4-3/8 - 1 31-5/8 TL35 35-3/4 16-1/2 15/16 16-1/2 14-1/2 33-1/4 6-3/4 11-5/8 18-3/8 15/16 6 5-1/8 1-1/2 38-3/8 TL53 46-1/2 16-1/2 1-1/8 16-1/2 14-1/2 44 6-3/4 11-5/8 30-3/8 1-1/2 6 5-1/8 1-1/2 49-1/8
A B C D E F H J K L M N P W
Dimensions (in.)
Page 5
MODEL C
High Profile Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• Molded Lexan® guard
• Drain tting at 45-degree angle so drain can be run through bottom or back of refrigerator
• Aluminum hangers automatically space the unit to the correct distance from the back wall
• Stainless steel screws prevent rust streaks
• Room for expansion valve inside the unit
• Knockouts in sides and top plus openings in rear provide maximum exibility for electrical connection
• Expansion valve can be mounted inside the cabinet
• Full collar aluminum ns on expanded copper tubes
• Internal junction box with pigtail leads for electrical connection
• Motors are thermally protected and permanently lubricated
• All models UL listed for US and Canada
• UL classied to NSF standards
• Optional coated coil available (Model CK) for enhanced protection in corrosive environments
• Sweat inlet connection standard to reduce leaks
(are connection available as a ship loose option)
Application
Model C is the ideal unit for refrigerated reach-ins. It mounts to
the top of the refrigerator and discharges cold air against the back wall. With this air ow pattern, the air is not blasted on the product but is diused along the back wall and then gently drawn across the product as it returns to the unit. Thus uniform temperatures are maintained throughout the refrigerator. In addition, door sweating and refrigeration loss due to door opening is greatly reduced because the air is not discharged against the doors.
Nomenclature
C K 43 B G
Model Coil Option Model Size Electrical Code Vintage
High Prole Unit Cooler
Blank = Standard K = Coated
13-43 A = 115/1/60
B = 208-230/
1/60
Performance & Electrical Data
Model
C(K)13^ 1,300 235 1 1.0 0.5 3/8 3/8 1/2 16 C(K)17^ 1,700 250 1 1.0 0.5 3/8 1/2 1/2 17 C(K)23^ 2,300 265 1 1.0 0.5 3/8 1/2 1/2 22 C(K)30^ 3,000 480 2 2.0 1.0 3/8 1/2 1/2 27
C(K)43^* 4,300 520 2 2.0 1.0 1/2 1/2 1/2 40
^ Model available with EC motors * Model 43 requires an external equalized expansion valve
BTUH
10°F TD
CFM Qty.
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil Inlet
OD
SuctionIDDrain
OD
Ship Wt.
Physical & Dimensional Data
Model
C(K)13 12-5/8 12-3/8 11-7/16 1-3/8 14-1/4 C(K)17 15-5/8 12-3/8 14-7/16 1-3/8 17-1/4 C(K)23 21-1/8 12-3/8 21-1/16 7/8 22-3/4 C(K)30 26-1/8 12-3/8 25-13/16 1 27-3/4 C(K)43 36-5/16 - - - 38
A B C D W
Dimensions (in.)
(lbs.)
5
Page 6
MODEL VA
Vee-Aire Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• Molded Lexan® fan guard
• Improved drain pan overlaps coil surface to catch all condensate
• Stainless steel screws prevent rust streaks
• Plate-type aluminum ns with full collars on expanded copper tubes
• Expansion valve can be mounted inside the cabinet
• Internal junction box for electrical connection
• Pigtail leads in junction box
• Motors are thermally protected and permanently lubricated
• Top quality throughout in a compact size
• All models UL listed for US and Canada
• UL classied to NSF standards
• Optional coated coil available (Model VAK) for enhanced protection in corrosive environments
• Sweat inlet connection standard to reduce leaks
(are connection available as a ship loose option)
Application
Model VA is a deluxe unit designed for use in small reach-ins, back
bar and under counter refrigerators, and many other applications where a small, compact unit is required. The thermal expansion valve mounts inside the unit. The unit can be mounted from the ceiling or o the back wall or end walls.
Nomenclature
VA K 08 A G
Model Coil Option Model Size Electrical Code Vintage
V Prole Unit Cooler
Blank = Standard K = Coated
06-17 A = 115/1/60
B = 208-230/1/60
Performance & Electrical Data
Model
VA(K)06 600 135 1 0.8 0.4 3/8 3/8 1/2 9 VA(K)08 800 130 1 0.8 0.4 3/8 3/8 1/2 9 VA(K)12 1,200 265 2 1.6 0.8 3/8 3/8 1/2 14
VA(K)17^ 1,700 245 1 1.0 0.5 3/8 3/8 1/2 11
^ Model available with EC motors
BTUH
10°F TD
CFM Qty.
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil Inlet
OD
SuctionIDDrain
OD
Ship Wt.
Physical & Dimensional Data
Model
VA(K)06 4-5/16 13-1/4 4-5/16 - - 3-3/8 6-7/8 5-1/4 8-1/8 12-1/2 VA(K)08 4-5/16 13-1/4 4-5/16 - - 3-3/8 6-7/8 5-1/4 8-1/8 12-1/4 VA(K)12 4-1/2 18-3/4 5-5/16 - - 3-3/8 8 4-7/8 8-1/8 18 VA(K)17 5-1/4 14-3/4 5-1/4 9 2-1/2 4 9-3/4 6-13/16 10-1/2 14
A B C D E F H J K W
Dimensions (in.)
(lbs.)
Page 7
MODELS BBM/BBL
Back Bar Reach-In Unit Cooler
Features
• Molded Lexan® fan guards
• Coils have copper tubes with aluminum ns, mechanically­bonded for ecient heat transfer. The coils are dehydrated and sealed
• Textured aluminum cabinet
• Knockouts are conveniently located for refrigerant lines
• Screws are hardened, stainless steel
• Expansion valve can be mounted inside the cabinet and connections are sweat-type
• Motors are thermally protected and permanently lubricated
• Master units include the basic unit plus factory mounted expansion valve, solenoid, and temperature control. Also right-hand piping extended 8" - 12" outside the housing, sealed and pressurized to 20 - 30 PSI. A 1/4" OD liquid feed to slave is included
• Slave units include the basic unit plus factory mounted expansion valve with left-hand piping extended 8" - 12" outside the housing, sealed and pressurized to 20 - 30 PSI
• Sweat inlet connection to reduce leaks
(are connection available as a ship loose option)
Application Models BB are compact, wall-mounted units whose low height makes them
ideal for undercounter reach-in or drawer-type xtures. The unit draws air in at the bottom and discharges out the front. An optional air deector is included and can be mounted over the center of the fan to direct air up and out. The deector can be eld-formed to direct the air where needed, usually onto drop-in trays of condiments in salad bar or sandwich preparation xtures. An S-type mounting angle is included to position the unit 3/4" o the wall which gives optimum air circulation and performance.
The BBM (medium temperature) model is designed for 35° to 40°F xture temperature with o-cycle defrost. The unit is designed to operate at 10° to 17° TD and 16 hours per day compressor run time.
The BBL (low temperature) model is designed for 0° to -10°F xture temperature, and has automatic electric defrost. The unit is designed to operate at 8° to 15° TD with 18 hours per day compressor runtime. The BBL has an incoloy sheath heater embedded in the bottom n surface for ecient and fast defrosting. A drain pan heater is included to ensure complete condensate drainage. A disc-type sealed defrost termination/fan delay control is mounted and wired. Field connectors are located at the terminal board.
Nomenclature
BB L S 10 A G
Model Unit Temp. Unit Type Size Electrical Code Vintage
Back Bar Unit Cooler
L = Low M = Medium
Blank = Standard S = Slave M = Master
10-16 A = 115/1/60
B = 208-230/1/60
Performance & Electrical Data
BTUH
Model
BBL10 1,000 90 1 1/150 0.8 0.4 275 2.7 1.4
BBM11 1,100 90 1 1/150 0.8 0.4 - - -
BBL15 1,500 180 2 1/150 1.6 0.8 350 3.5 1.7
BBM16 1,600 180 2 1/150 1.6 0.8 - - -
10°F
TD
CFM Qty. HP
Motor Data Defrost Heaters
115/1/60 Total FLA
208-230/1/60
Total FLA
Watts
115/1/60
Amps
Physical & Dimensional Data
Model
BBL10 19-1/8 18 17-1/2 7-1/16 - 16-5/8 19-3/4 17
BBM11 19-1/8 18 17-1/2 7-1/16 - 16-5/8 19-3/4 16
BBL15 25-5/8 24-1/2 24 4-13/16 8-5/8 23-1/8 26-1/4 20
BBM16 25-5/8 24-1/2 24 4-13/16 8-5/8 23-1/8 26-1/4 19
NOTES: All units have 3/8” OD suction, 1/2” OD sweat inlet and 1/2” OD drain
A B C D E F W
Dimensions (in.) Approx.
Ship Wt. (lbs.)
Typical Section of Sandwich Station
208-230/1/60
Amps
Model BBM
7
Page 8
MODEL KMK
Kompact Mullion Reach-In Unit Cooler
Features
• Light grained aluminum cabinets
• PVC coated fan guard
• Stainless steel hardware
• Coils have full collar aluminum ns on expanded copper tubes
• Coated coil for enhanced protection in corrosive environments
• Refrigerant connection knockouts provided on both ends of unit
• Expansion valve can be mounted inside the cabinet
• Motors are thermally protected and permanently lubricated
• Internal junction box for electrical connection
• Adjustable air deector included provides dierent air patterns. Air can be directed where it’s needed
• All models UL listed for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection to reduce leaks
(are connection available as a ship loose option)
Application
Model KMK is ideal for under-counter reach-in refrigerators.
The thin line design allows the unit to be mounted behind the mullion with sucient clearance for tray slides. A down ow fan arrangement is used with air drawn in at the top and discharged at the bottom. This design provides superior air circulation and ensures uniform temperature throughout the cabinet.
This versatile design is also adaptable for mounting on the back wall or ends of a cooler. The method of air circulation ensures minimum box temperature rise when the cabinet doors are open. Ideal for bottle goods and beverage coolers.
Nomenclature
KM K 13 A G
Model Coil Size Electrical Code Vintage
Kompact Mullion
K = Coated 13-23 A = 115/1/60
B = 208-230/1/60
Performance & Electrical Data
BTUH
Model
KMK13 1,300 180 2 1.6 0.8 3/8 3/8 5/8 19 KMK17 1,700 170 2 1.6 0.8 3/8 3/8 5/8 20 KMK23 2,300 255 3 2.4 1.2 3/8 1/2 5/8 28
10°F
TD
CFM
Motor Data Connections (in.) Approx.
Qty.
115/1/60 Total FLA
208-230/1/60
Total FLA
Coil InletODSuctionIDDrain
OD
Physical & Dimensional Data
Model
KMK13 17-3/4 16-7/8 9 15-5/8 2-3/4 5-1/2 6-15/16 KMK17 19-3/4 16-7/8 10 15-5/8 2-3/4 6-1/2 7-15/16 KMK23 19-3/4 23-1/4 10 22 2-5/16 6-1/2 7-15/16
H L M W X Y Z
Dimensions (in.)
Ship Wt.
(lbs.)
Page 9
MODEL RAMK
Reverse Air Flow Kompact Mullion Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• PVC coated fan guard
• Stainless steel hardware
• Coils have full collar aluminum ns on expanded copper tubes
• Coated coil for enhanced protection in corrosive environments
• Refrigerant connection knockouts provided on both ends of unit
• Expansion valve can be mounted inside the cabinet
• Motors are thermally protected and permanently lubricated
• Internal junction box for electrical connection
• Adjustable air deector included provides dierent air patterns. Air can be directed where it’s needed
• All models are UL listed for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection standard to reduce leaks
(are connection available as a ship loose option)
Application Model RAMK
under-counter drawer type refrigerators and salad bars. The unit is suitable for mounting behind a mullion or on a wall. An up ow air pattern is used with air drawn in at the bottom and discharged out the top. This provides optimum temperature for drop in trays on salad bars or prep tables. It also keeps drawer stored product in premium condition.
An adjustable and detachable air deector/splash protector is included. The deector can be adjusted to direct the air up and out at a 45-degree angle. This feature provides excellent air distribution over drop in trays or containers. Food in the trays and containers stays colder, lasts longer, and retains the desired appearance. The deector can be adjusted to distribute air out both sides when used as a mullion unit.
is ideal for under-counter reach-in refrigerators,
Nomenclature
RAM K 13 A G
Model Coil Size Electrical Code Vintage
Reverse Air Flow Kompact Mullion
K = Coated 13-23 A = 115/1/60
Performance & Electrical Data
BTUH
Model
RAMK13 1,300 180 2 1.6 0.8 3/8 3/8 5/8 19 RAMK17 1,700 170 2 1.6 0.8 3/8 3/8 5/8 20 RAMK23 2,300 255 3 2.4 1.2 3/8 1/2 5/8 28
10°F
TD
CFM Qty.
Motor Data Connections (in.) Approx. 115/1/60 Total FLA
208-230/1/60
Total FLA
Coil InletODSuctionIDDrain
OD
Ship Wt.
Physical & Dimensional Data
Model
RAMK13 17-3/4 16-7/8 9 15-5/8 2-3/4 5-1/2 6-15/16 RAMK17 19-3/4 16-7/8 10 15-5/8 2-3/4 6-1/2 7-15/16 RAMK23 19-3/4 23-1/4 10 22 2-5/16 6-1/2 7-15/16
H L M W X Y Z
Dimensions (in.)
B = 208-230/1/60
(lbs.)
9
Page 10
MODEL BTO
Twin Flow Reach-In Unit Cooler
Features
• Compact two-way design with medium velocity air ow
• Mounts ush to the ceiling and draws air in through the fan and discharges out both sides
• Air pattern reduces air loss when doors are opened and the medium velocity reduces product drying
• Textured aluminum cabinet
• Stainless steel fasteners
• Molded Lexan® fan guards
• Drain pan and fan panel is easily removed for installation and servicing
• Optional coated coil available (Model BTOK) for enhanced protection in corrosive environments
• Coils are constructed of copper tubing with aluminum ns
• Expansion valve can be mounted inside the cabinet
• Internal junction box is provided for electrical connection
Motors are thermally protected and permanently lubricated
• All models are UL listed for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection to reduce leaks
(are connection available as a ship loose option)
Application
Model BTO is ideal for temperatures of 35°F and higher. Box
temperatures are kept more constant throughout and fresh products last longer. Seven sizes are available with BTUH from 900 to 5,500 at 10° TD.
Larger BTO sizes are suitable for large reach-in and small step-in or walk-in coolers.
Nomenclature
BTO K 09 A G
Model Coil Option Size Electrical Code Vintage
Twin Flow Unit Cooler
Blank = Standard K = Coated
09-55 A = 115/1/60
B = 208-230/1/60
Performance & Electrical Data
Model
BTO(K)09 900 1,350 130 1 0.8 0.4 1/2 1/2 1/2 12 BTO(K)13 1,300 1,950 240 2 1.6 0.8 1/2 1/2 1/2 14
BTO(K)18^ 1,800 2,700 255 1 1.0 0.5 1/2 1/2 1/2 15 BTO(K)25^* 2,500 3,750 460 2 2.0 1.0 1/2 1/2 1/2 23 BTO(K)35^* 3,500 5,250 425 2 2.0 1.0 1/2 1/2 1/2 24 BTO(K)45^* 4,500 6,750 550 2 2.0 1.0 1/2 1/2 5/8 34 BTO(K)55^* 5,500 8,250 730 1 2.1 1.1 1/2 1/2 5/8 34
^ Model available with EC motors * Models 25, 35, 45 and 55 require an external equalized expansion valve
Physical & Dimensional Data
Model
BTO(K)09 16-1/8 19-1/8 7-9/16 4 2-5/16 9-9/16 2-3/4 4-7/8 4-1/2 8-5/8 2-1/2 2-5/8 4-9/16 10 7/8 BTO(K)13 16-1/8 19-1/8 7-9/16 4 2-5/16 9-9/16 2-3/4 5-3/4 4-1/2 8-5/8 2-1/2 2-5/8 4-9/16 10 7/8 BTO(K)18 16-1/8 19-1/8 7-9/16 4 2-5/16 9-9/16 2-3/4 5-3/4 4-1/2 8-5/8 2-1/2 2-5/8 4-9/16 10 7/8 BTO(K)25 18-1/8 26-1/8 11-1/16 4 2-5/16 13-1/16 2-3/4 6-3/4 5-1/2 12-1/8 3-1/2 2-5/8 8-1/16 10 7/8 BTO(K)35 18-1/8 26-1/8 11-1/16 4 2-5/16 13-1/16 2-3/4 6-3/4 5-1/2 12-1/8 3-1/2 2-5/8 8-1/16 10 7/8 BTO(K)45 21-1/8 29-1/8 8-3/16 7-3/4 3-7/16 10-5/8 3-1/2 9-1/4 8 13-5/8 5-15/16 4-1/4 7-9/16 14 1-3/4 BTO(K)55 21-1/8 29-1/8 8-3/16 7-3/4 3-7/16 10-5/8 3-1/2 8-1/2 8 13-5/8 5-15/16 4-1/4 7-9/16 14 1-3/4
BTUH
10°F TD
A B C D E F G H J K L M N P R
BTUH
15°F TD
CFM Qty.
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil InletODSuctionIDDrain
OD
Ship Wt.
(lbs.)
Dimensions (in.)
10
Page 11
MODEL U
Dual Aire Standard Coil Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• Full collar aluminum ns on expanded copper tubes
• Detachable drain pan that is easy to clean
• Molded 3-prong motor connector to save installation time and expense
• Motors
• Optional coated coil available (Model UK) for enhanced protection in corrosive environments
• All models are UL recognized for the US and Canada
• UL classied to NSF standards
• Sweat inlet connection to reduce leaks
(are connection available as a ship loose option)
are thermally protected and permanently lubricated
Application
Model U is used wherever a small, compact unit is required.
It can be mounted on the ceiling or wall. The model U unit draws air through the front and discharges it out both sides to ensure proper distribution of cool air and thus maintain a uniform box temperature.
Nomenclature
U K 09 0
Model Coil Option Size Electrical Code
Dual Aire Standard Coil
Blank = Standard K = Coated
09-15 0 = 115/1/60
1 = 208-230/1/60
Performance & Electrical Data
Model
U(K)09 850 1,275 190 0.45 0.55 1/2 3/8 1/2 9 U(K)12 1,150 1,725 250 0.45 0.55 1/2 3/8 1/2 10 U(K)15 1,500 2,250 310 1.10 0.55 1/2 3/8 1/2 14
BTUH
10°F TD
BTUH
15°F TD
CFM
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil InletFNSuctionIDDrain
OD
Physical & Dimensional Data
Model
U(K)09 8-1/2 11-1/2 8-7/8 6 4 3-1/2 U(K)12 8-1/2 17-1/2 8-7/8 12 4 9-1/2 U(K)15 9-1/2 17-1/2 10-7/8 12 4 9-1/2
H W D A B C
Dimensions (in.)
Ship Wt.
(lbs.)
11
Page 12
For more information on Bohn refrigeration products, contact your sales representative or visit us at www.thecoldstandard.com.
A Brand of Heatcraft Refrigeration Products, LLC
2175 West Park Place Blvd. • Stone Mountain, GA • 30087
800.537.7775
www.thecoldstandard.com
Since product improvement is a continuing eort, we reserve the right to make changes in specications without notice.
BN-RITB-0609 | Version 000
Loading...