GTD10DIM & BLCD16DIM
Installation Instructions
EMERGENCY LIGHTING CONTROL DEVICE
WHEN USING ELECTRICAL EQUIPMENT, BASIC
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL
• This product is intended for use with lighting fixtures controlled by an emergency panel. Any switching
between backup power and utility power must be done upstream of this device.
• All wiring connections and mounting styles must be in accordance with the National Electrical Code (NEC),
National Fire Protection Association (NFPA), National Electrical Safety Code, state and local codes, and any
other regulations set forth by the local Authority Having Jurisdiction (AHJ).
• Per NFPA 70E, the use of Personal Protective Equipment (PPE) may be required. Check state and local codes.
• The load’s operating voltage must be the same as the emergency power input voltage.
• To reduce the risk of electrical shock, fire, and injury to persons:
1. Disconnect all sources of power before servicing,
2. Mount this device in locations and at heights where it will not be readily accessible to tampering by
unauthorized personnel,
3. Do not mount near gas or electric heaters,
4. Do not let any wires touch hot surfaces, and
5. Do not use outdoors (NEMA 1 rating only).
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this device for other than intended use. Generator or inverter supplied emergency panel is
required (120 or 277 VAC, 50/60 Hz).
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
SAVE THESE INSTRUCTIONS
CAUTION: THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE
THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE
INSTALLING OR SERVICING THIS UNIT.
SERVICE BY QUALIFIED PERSONNEL ONLY
NOTE: BEFORE INSTALLING THIS DEVICE, MAKE SURE THAT THE NECESSARY BRANCH CIRCUIT WIRING IS
AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO A
GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED.
02/25/19
Bodine © 2018 Signify Holding. All rights reserved.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com
81000171

SPECIFICATIONS
ELECTRICAL SPECIFICATIONS (GTD10DIM, BLCD16DIM)
NORMAL POWER SUPPLY VOLTAGE
NORMAL POWER CURRENT DRAW
NORMAL POWER OPERATING FREQUENCY
EMERGENCY POWER SUPPLY VOLTAGE
EMERGENCY POWER CURRENT DRAW EMERGENCY
POWER OPERATING FREQUENCY
FEEDBACK/DIMMER CONTACT SWITCHING
CAPABILITY (DRY CONTACT OUTPUT)
RELAY CONTACT (BLCD16DIM)
SPST
RELAY CONTACT (GTD10DIM)
SPST
MECHANICAL SPECIFICATIONS
HOUSING:
UL ACCEPTED FOR USE IN PLENUM, NEMA 1
120-277VAC
24MA MAX
50/60HZ
120-277VAC
118MA MAX
50/60HZ
130MA @ 250V MAX
20A MAGNETIC BALLAST @ 277V
16A ELECTRONIC BALLAST @ 277V
10A TUNGSTEN @ 120V
10A MAGNETIC BALLAST @ 277V
10A ELECTRONIC BALLAST @ 277V
10A TUNGSTEN @ 120V
WIRE:
WEIGHT:
OPERATING TEMPERATURE:
HUMIDITY RANGE:
APPROVALS:
16" 600V RATED
0.675 LBS. (BLCD16DIM)
0.40 LBS (GTD10DIM)
-35° TO 60°C (-30° TO 140° F)
5 TO 95% (NONCONDENSING)
RATED FOR DRY AND DAMP LOCATIONS ONLY
UL924 LISTED FOR THE US AND CANADA