BMC GTC60S2-ADNX, GTC60S2-ADCX, GTC36S2-ADNX, GTADP-3642-B, GTADP-3642-C User Manual

...
MIS-2830
WATER SOURCE HEAT PUMP
MODELS:
INSTALLATION INSTRUCTIONS
GTB1-A Blower Section
GTA3600UD1AA Coil Section GTA4860UD1AA Coil Section GTADP-3642-B Coil Section GTADP-3642-C Coil Section GTADP-4860-C Coil Section GTC36S2-ADCX Compressor Section GTC48S2-ADCX Compressor Section GTC60S2-ADCX Compressor Section GTC36S2-ADNX Compressor Section GTC48S2-ADNX Compressor Section GTC60S2-ADNX Compressor Section
BMC, Inc. Bryan, Ohio 43506
Earth Loop Fluid
Temperatures 25° - 110°
Ground Water Temperatures 45° - 75°
Manufactured under the following
U.S. patent number:
8,127,566
Manual 2100-537 Page 1 of 54
I
CONTENTS
Getting Other Informations and Publications ..............3
General Information Geo-Trio (GT Series)
Water Source Nomenclature .................................................... 4
Blower Conversion & Line Power Connect ............................ 15
Application and Location
General ............................................................................ 18
Shipping Damage ................................................................... 18
Application ............................................................................ 18
Dual Fuel Heating / Cooling
Location ............................................................................ 18
Ductwork ............................................................................ 18
Filters ............................................................................ 19
Condensate Drain .................................................................. 19
Piping Access to Unit ..............................................................19
................................................... 18
Wiring Instructions
General ............................................................................ 22
Control Circuit Wiring.............................................................. 22
Wall Thermostats & Low Voltage Connections
....................... 22
Ground Loop (Earth Coupled Water Loop Applications)
Note ............................................................................ 24
Circulation System Design ..................................................... 24
Start Up Procedure for Ground Loop System ........................ 25
Ground Water (Well System Applications)
Note ............................................................................ 27
Water Connections .................................................................27
Well Pump Sizing ...........................................................27 & 28
Start Up Procedure for Ground Water System ....................... 29
Water Corrosion .............................................................29 & 30
Remedies of Water Problems ................................................. 30
Lake and/or Pond Installations .......................................30 & 31
Desuperheater
Description ............................................................................ 32
Location ............................................................................ 32
Electrical Connection .............................................................. 32
Installation Procedure - General ............................................. 32
Oper. of Heat Recovery Unit ..................................................33
Start Up & Checkout ............................................................... 33
Maintenance & Control Board Seq. of Operation ...........33 & 37
Sequence of Operation
Blower ............................................................................ 38
Part / Full Load Cooling
Part / Full Load Heating .......................................................... 38
Supplementary Electric Heat .................................................. 38
Geothermal Logic Controls ..................................................... 38
High / Low Pressure Switch
Freeze Stat ............................................................................ 39
Condensate Overow ............................................................ 39
Under/Over Voltage Protection ...............................................39
Intelligent Reset ...................................................................... 39
Alarm Output Pressure Service Ports
System Start Up ..................................................................... 39
.......................................................................... 39
.......................................................... 38
................................................... 39
........................................................... 39
Refrigerant Charge
Line Set Installation (GTA Coil Sections) ................................ 42
Charge Adjustment ..............................................................42
Refrigerant Fitting Attachment Checking Charge Quantity
General / GTADP Coi Sections .............................................. 43
Line Set Installation (GTADP Coil Sections) ........................... 43
General / Topping Off System / Safety Practices ................... 44
............................................ 42
..................................................... 42
Service
Service Hints .......................................................................... 47
Unbrazing System Components ............................................. 47
Compressor Solenoid ............................................................. 47
Troubleshooting GE ECM 2.3 Motors .............................48 & 49
Troubleshooting Table ............................................................ 50
Power Connector T able ..........................................................50
Ground Source Heat Pump
Performance Report ................................................51-52
Wiring Diagrams
......................................................53-54
Figures
Fig u r e 1 A GTA****UD1AA Dimensions ................................. 7
Figure 1B GTADP Fossil Fuel ADP Coil Dimensions ............ 8
Figure 1C GTB1-A Dimensions ............................................. 9
Figure 1D GTC**S2-D Dimensions .....................................10
Figure 1E Assembled Upow/Counterow App. .................11
Figure 1F Horizontal App. Dimensions ............................... 12
Figure 2A Upow & Counterow Ducting Cong. ................. 13
Figure 2B Horiz. & Counterow Ducting Cong. .................. 14
Figure 3 Blower Conguration ..........................................16
Figure 4 Blower Power Connections ................................17
Figure 5A Upow Air Filter Applications .............................. 21
Figure 5B Counterow Air Filter Applications ...................... 21
Figure 5C Horiz. Left Discharge Air Filter App. .................... 21
Figure 5D Horiz. Front Discharge App. ............................... 21
Figure 6 Thermostat Wiring ..............................................23
Figure 7 Circulation System Design .................................24
Figure 8 Temperature & Pressure Measurement .............. 26
Figure 9 Perf. Model DORFC-1 Flow Ctr. ......................... 26
Figure 10 Perf. Model DORFC-2 Flow Ctr. ......................... 26
Figure 11 Water Connection Components.......................... 28
Figure 12 Cleaning Water Coil ............................................ 30
Figure 13 Lake or Pond Installation ....................................31
Figure 14 Wiring Diagram ...................................................34
Manual 2100-537I Page 2 of 54
Figure 15A Desuperheater Single Tank System ...................... 35
Figure 15B Desuperheater Dual Tank System ....................... 36
Figure 16 Thermistor ..........................................................37
Figure 17 Component Location ..........................................40
Figure 18 Control Panel ......................................................40
Figure 19 Refrigerant Flow Diagrams .................................41
Figure 20 Coil Spacer .........................................................43
Figure 21 Pressure Tables .................................................. 45
Figure 22 Control Disassembly ........................................... 49
Figure 23 Winding Test ....................................................... 49
Figure 24 Drip Loop ............................................................49
Figure 25 Control Connector Motor Half .............................50
Tables
Table 1 Indoor Blower Performance .................................. 5
Table 2 Flow Rates for Various Fluids ...............................5
Table 3 Specications ....................................................... 5
Table 4 Water Coil Pressure Drop ..................................... 6
Table 5 Electrical Heat Specications ............................. 19
Table 6 Filter Sizing Chart ............................................... 20
Table 7 Control Circuit Wiring .......................................... 22
Table 8 Constant Flow Valves .........................................27
Table 9 Pre-Charged Line Set Qty .................................. 42
Quick Reference Troubleshooting Chart ................................46
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code .......................ANSI/NFPA 70
Standard for the Installation ...............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for W arm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ......ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ..............ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
Closed-Loop/Ground Source Heat Pump ........IGSHPA
Systems Installation Guide
Grouting Procedures for Ground-Source .........IGSHPA
Heat Pump Systems
Soil and Rock Classication for ......................IGSHPA
the Design of Ground-Coupled Heat Pump Systems
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Ground Source Installation Standards .............IGSHPA
Closed-Loop Geothermal Systems ..................IGSHPA
– Slinky Installation Guide
IGSHPA International Ground Source Heat Pump Association 490 Cordell South
Stillwater, OK 74078-8018
Manual 2100-537I Page 3 of 54
Geo-Trio™ GT Series Geothermal / Water Source Heat Pump Nomenclature
“A” Coil Section
GT A 3600 UD 1 A A
Geo-Trio
“A” = Coil Section
3600 (3 Ton) 4860 (4 & 5 Ton)
Series
Revision Level
A = E Coated Coils
Fossil Fuel “A” Coil Section
GT ADP – 3642 – B
Geo-Trio
ADP = Advanced Distributor Products
3642 (3 Ton) 4860 (4 & 5 Ton)
B = 17.50" Wide Furnace C = 21.00" Wide Furnace
Blower Section
GT B 1 – A
Option
Geo-Trio
B = Blower Section
Revision Level
Option
A = 230 Volt 1-Phase
Compressor Section
GT C 36 S 2 A D C X
Geo-Trio
C = Compressor Section
Manual 2100-537I Page 4 of 54
Nominal Capacity
S = Step Capacity
36 = 36K 48 = 48K 60 = 60K
Revision Level
Option
A = 230 Volt 1-Phase
D = Desuperheater
C = Copper Coil N = Cupronickel Coil
X = Future Use
TABLE 1 — INDOOR BLOWER PERFORMANCE (RATED CFM)
MODEL
GTC36S2 0.15 0.60 600 700 850 1200 1300 2.6 GTC48S2 0.20 0.60 750 875 1075 1500 1600 3.2 GTC60S2 0.20 0.60 900 1050 1300 1800 1800 3.6
Rated
ESP
MAX
ESP
Continuous
Airow
Mild Climate
Operation
in Part Load
Cooling
Part Load
Airow
Full Load
Airow
Electric Heat
Airow
Minimum Air
Filter Face
Area Ft.2
 Motorwillautomaticallystepthroughthevariousairowswiththermostaticcontrol ESP = External Static Pressure (inches of water)  Maximum allowable duct static ContinuousairowistheCFMbeingcirculatedwithmanualfanoperationwithoutanyadditionalfunctionoccurring. Willoccurautomaticallyforrst5minutesofPartLoadCoolingOperation. WilloccurautomaticallyafterveminutesofPartLoadCoolingOperation. Will occur automatically with control signal input. As per ASHRAE Guidelines of 500 FPM Velocities.
NOTE: All values can be changed + 10% via the + adjustment dip switches on the tap select control inclusive in the GTB1-A Blower Section (see instructions later in this manual, or on wiring diagram in blower section).
TABLE 2 — FLOW RATES FOR VARIOUS FLUIDS
APPLICATION
Ground Loop (15% Methanol, Propylene Glycol, etc.) 8 12 15 Ground Water 6 7 9 Water Loop (Cooling Tower) 9.2 12.1 14.3
GTC36S2 GTC48S2 GTC60S2
MODELS
TABLE 3 — SPECIFICATIONS
MODEL GTC36S2 GTC48S2 GTC60S2
Electrical Rating (60HZ/1PH) 230/208-60-1 Operating Voltage Range 253-197 VAC Minimum Circuit Ampacity 24.5 33.1 39.7 +Field Wire Size #10 #6 #4 Ground Wire Size #10 #10 #10 ++Delay Fuse or Circuit Breaker Max. 35 50 60
COMPRESSOR
Volts 230/208-60-1 Rated Load Amps (230/208) 10.6 / 11.9 15.3 / 17.0 20.2 / 22.7 Branch Circuit Selection Current 15.3 21.2 25.6 Locked Rotor Amps (230/208) 82 / 82 104 / 104 153 / 153
BLOWER MOTOR
Horsepower (ECM Motor) 3/4 Variable Speed Volts 230/208-60-1 Motor Amps (Stage #2 @ Rated CFM) 3.4 4.3 4.4
FLOW CENTER (Based on DORFC-2)
Volts 230/208-60-1 Amps 2.14 2.14 2.14
DESUPERHEATER PUMP MOTOR
Volts 230/208-60-1 Amps 0.15 0.15 0.15
+75°C copper wire ++ HACR type circuit breaker
Manual 2100-537I Page 5 of 54
TABLE 4
WATER COIL PRESSURE DROP
Model GTC36S2 GTC48S2 GTC60S2
GPM PSID Ft. Hd. PSID Ft. Hd. PSID Ft. Hd.
3 0.1 0.23 4 0.5 1.15 0.9 2.08 5 1.2 2.77 1.4 3.23 6 1.7 3.92 2.3 5.31 7 2.3 5.31 3.2 7.38 2 4.61 8 3.1 7.15 4.1 9.46 2.5 5.77
9 4.1 9.46 5.1 11.77 3.2 7.38 10 6.1 14.07 3.9 9.00 11 7.1 16.38 4.7 10.84 12 8.2 18.92 5.5 12.69 13 9.4 21.69 6.4 14.76 14 10.6 24.45 7.3 16.84 15 8.1 18.69 16 9 20.76 17 9.9 22.84 18
Manual 2100-537I Page 6 of 54
2 3/16"
3 5/16"
5 1/8"
15 11/16"
17 5/8"
1 1/2"
10 15/16"
7 1/4"
2 3/4"
MIS-2818
HORIZ. MAIN DRAIN K.O.
HORIZ. OVERFLOW K.O.
SUCTION CONNECTION
LIQUID CONNECTION
OVERFLOW
MAIN DRAIN
19 15/16"
3 1/2"
21 5/8"
2 3/16"
CONDENSATE
OVERFLOW WIRES
27 15/16"
13 5/8"
1 13/16"
22"
30"
20.50
-.000
+.125
WIDTH
16.13
-.000
+.125
HEIGHT
DRAIN PAN
GTA Coil Dimensions If Used Without Cabinet
PRIMARY DRAIN HOLE
SECONDARYDRAIN HOLE
MIS-2876 A
COATED
COIL
.125
2.25
-.000
+
28.25
-.000
+.125
DEPTH
FIGURE 1A – GTA****UD1AA
A-COIL SECTION DIMENSIONS
Manual 2100-537I Page 7 of 54
FIGURE 1B – GTADP****-*
FOSSIL FUEL ADP COIL SECTION DIMENSIONS
FIGURE 1B - GTADP****-*
FOSSIL FUEL ADP COIL SECTION DIMENSIONS
SUCTION CONNECTION
OVERFLOW
MAIN DRAIN
3/4" TYP
1 5/8"
5 1/4" "E"
"D"
"A"
"F"
"C"
6 1/16"
"G"
LIQUID CONNECTION
OVERFLOW
MAIN DRAIN
3/4" TYP
DIMENSION GTADP-3642-B
"A" 17 5/8" 21 1/8" "B" 25 1/2" 27 1/2" "C" 7 1/4" 6 3/4" "D" 2 1/8" 2 1/2" "E" 3 7/8" 4 1/4" "F" 13 7/8" 16 7/8" "G" 15 5/8" 18 5/8"
3/4"
TYP
"B"
21 1/4"
GTADP-3642-C GTADP-4860-C
MIS-3119
Manual 2100-537I Page 8 of 54
15 5/8"
24 9/16"
MIS-2819
30"
13 1/4"
16 3/8"
LOW VOLTAGE ENTRANCE
OPENING ON BOTH SIDES
OPTIONAL SIDE RETURN
HIGH VOLTAGE K.O. FOR REMOTE APPLICATIONS ONLY
3 5/8"
18 13/16"
1 1/4"
24"
15"
3 5/16"
1 1/2"
2 7/8"
21"
22"
FIGURE 1C – GTB1-A
BLOWER SECTION DIMENSIONS
Manual 2100-537I Page 9 of 54
MODEL DIM. A DIM. B
GTC36S2 21" 4 1/8"
GTC48S2 20" 3 7/8"
GTC60S2 18 1/2" 3 3/4"
DESUPERHEATER
WATER OUT
LIQUID LINE
SUCTION LINE
WATER IN
WATER OUT
DESUPERHEATER
WATER IN
12 1/4"
3"
9 5/8"
B
2 1/2"
23 1/16"
1 7/8"
16 1/16"
6 15/16"
A
1 3/4"
22 1/16"
30"
HIGH VOLTAGE UNIT
LOW VOLTAGE WIRE ENTRANCE
POWER ENTRANCE
HIGH VOLTAGE OPTIONAL
FLOW CENTER WI RE ENTRANCE
MIS-2820 A
8"
4 13/16"
16 15/16"
1 15/16"
FIGURE 1D – GTC**S2-D
COMPRESSOR SECTION DIMENSIONS
Manual 2100-537I Page 10 of 54
15 5/8"
24 9/16"
27 7/8"
37 1/16"
51 1/4"
55"
24 9/16"
15 5/8"
VOLTAGE
LOW
VOLTAGE
LOW VOLTAGE
HIGH
LOW VOLTAGE
18 13/16"
57 7/8"
25 3/4"
28 15/16"
37 7/8"
30"
REFRIGERANT
CONNECTIONS
65 5/8"
30"
21"
23"
21 5/8"
3/4"
31 1/4"
TOP DUCT OUTLET FLANGE
27 15/16"
19 13/16"
SECURE SECTIONS TOGETHER
USING BOLT PART #1012-015
AND WASHER PART #1012-109
MAIN DRAI N OUTLET
INLET
OVERFLOW DRAIN OU TLET
WATER OUT
OUTLET
DESUPERHEATER
DESUPERHEATER
WATER IN
61 5/8"
59 11/16"
33 1/4"
22"
23 7/16"
30 9/16"
"A"
MODEL DIM. A
GTC36S2 39 7/16"
GTC48S2 40 15/16"
GTC60S2 41 15/16"
RIGHT SIDEFRONT
LEFT SIDE
(UPFLOW ONLY)
ENTRANCE
TOP
AIR
(UPFLOW ONLY)
AIR
ENTRANCE
MIS-2821 B
FIGURE 1E – ASSEMBLED UPFLOW / COUNTERFLOW APPLICATION DIMENSIONS
Manual 2100-537I Page 11 of 54
36
5
8
"
38
1
2
"
1
1
2
"
2
1
8
"
Section
Blower
Section
Evaporator
GTHZ1
Horizontal
Drain Pan
(Req'd)
Horiz. Support Bracket
Low Voltage
Entrance
High Voltage
Entrance
Low Voltage
Entrance
Top View
30"
"
"
"
4311
"
4183
"
1
4
211
3
1
3
4
8"
Front View
7
"27
8
19
7
8
"
Opening
Evaporator Opening Blower
Right Side View
24"
15"
17
1
8
"
Overflow Drain
Outlet
Outlet
Main Drain
Refrigerant
Connections
7
"31
8
"
21"
8221
"
3
8
"
4433
"
8281
3
1
2
"
MIS-2824
Left Side View
Evaporator and Blower in Horizontal Position
(Remote Compressor Section)
NOTE:
Requires
horizontal
drain pan kit
Model GTHZ-1
FIGURE 1F – HORIZONTAL APPLICATION DIMENSIONS
Manual 2100-537I Page 12 of 54
Blower Air
Evap. Coil
Counterflow
Position
Cond. Coil
Water Out
Cond. Coil
Desuper.
Water In
Water In
Desuper.
Water Out
Supply
Return
Main Drain
Blower in
Alternate Position
7/8" Line Set
3/8" Line Set
Blower Air
Evap. Coil
Upflow
Cond. Coil
Position
Cond. Coil
Water Out
Desuper.
Water In
Desuper.
Water In
Water Out
Supply
Return
Return
Secondary
Return
Drain
Main Drain
Blower in
Shipped Position
7/8" Line Set
Control Panel
MIS-2828
Control Panel
3/8" Line Set
Drain
Secondary
Air Filter Required
One FR23 (16 x 25 x 1) or
field supplied equivalent
required for upflow side
return installation
Bottom return upflow and
top return counterflow filter
provision must be field
supplied
NOTE:
Requires Switch #4 on Tap Select
Control to be Turned On.
FIGURE 2A – UPFLOW & COUNTERFLOW DUCTING CONFIGURATIONS
Manual 2100-537I Page 13 of 54
Blower Air
Blower Air
Blower Air
Blower Air
Return
Remote Condenser Section
Supply
Supply
Supply
Return
Return
Return
Counterflow
Return
Main Drain
Horizontal, Left Discharge
Return
MIS-2826
Evap. Coil
Evap. Coil
Evap. Coil
Evap. Coil
Position
Optional Top
Horizontal, Right Discharge
Drain
Desuper.
Secondary Drain
Position
Upflow
Drain
Main Drain
Secondary Drain
Secondary
Main Drain
Blower in
Shipped Position
Blower in
Shipped Position
Blower in
Alternate Position
Alternate Position
Blower in
Supply
Cond. Coil
Water Out
Cond. Coil
Water In
Desuper.
Water In
Water Out
Secondary
Main Drain
Refrigerant
Return
Refrigerant
Connections
Refrigerant
Connections
Connections
Refrigerant
Connections
Model GTLID
NOTE:
Requires Switch #4
on Tap Select Control
to be Turned On.
FIGURE 2B – HORIZONTAL & COUNTERFLOW DUCTING CONFIGURATIONS
Manual 2100-537I Page 14 of 54
NOTE: Requires horizontal
drain pan kit Model GTHZ-1
< >
Air Filter Required on Return Air Side for All Installations
Upowinstallationscanuse(1)FR23(16x25x1)oreldsuppliedequivalentoneithersideofthe
blower section. Use of (2) on both sides is optional.
Bottomreturnforupowandtopreturnfordownowmustbeeldsupplied.
Forhorizontalatticorcrawlspaceinstallationslterarrangementmustbeeldsupplied&should
be located in readily accessible location for the user.
See additional information on Pages 19 & 20.
BLOWER CONVERSION FROM UPFLOW TO COUNTERFLOW OR HORIZONTAL RIGHT DISCHARGE
Following the directions on Figure 3 for counterow and
horizontal right discharge, the indoor blower must be
removed and turned over in its mounting conguration.
Step 1 Remove both front service panels from the
GTB1-A.
Step 2 Remove two screws securing blower at top of GTB1-A (See Figure 3), and slide the blower forward and out of the chassis.
Step 3 Remove two screws from front ll plate on
bottom of GTB1-A, and slide both pieces of metal forward and out of chassis.
Step 4 Dip switch #4 on blower tap select control must be turned “on”. (Refer to Wiring Diagram 4117-100.)
Step 5 While turning on tap #4 above, adjust the other taps accordingly for the tonnage of unit being applied. (Refer to Wiring Diagram 4117-100.)
Step 6 Turn blower over and slide into rails of
bottom rear of the GTB1-A front ll plate
that was removed in Step 3 above.
Step 7 Remove bottom rear ll plate from bottom
front ll plate (discard rear), and resecure front ll plate into unit base and front of
blower.
Step 8 Replace GTB1-A front service doors after making line and control voltage wiring connections.
BLOWER LINE POWER CONNECTION
Power connections for the GTB1-A can be made two different ways.
The rst is in “stacked” congurations, the blower can
be plugged into an electrical connection from the bottom of the compressor (GTC**S2 Model Unit). This will
work for either upow or counterow applications. All
electrical sizing has been sized to accommodate this. The second is with “remote” blower (meaning separate
from the compressor section). Supplied in the GTB1-A is an adaptor wire harness. On the right-hand side of the GTB1-A chassis is a ½" electrical knockout. This harness can be installed through this knockout with the supplied
strain relief into a standard electrical junction box (eld
supplied). Electrical load sizing is included on the serial plate of the GTB1-A for the required separate branch circuit (See Figure 4).
Manual 2100-537I Page 15 of 54
FRONT PANELS
REMOVE BOTH
REMOVE (2) SCREWS
SECURING BLOWER
AND SLIDE BLOWER
OUT OF CABINET
1
SECURING BLOWER TO
FRONT FILL PLATE
REINSTALL (2) S CREWS
REINSTALL BOTH
FRONT PANELS
5
4
6
2
REMOVE (2) SCREWS FROM
FRONT FILL PLATE AND SLIDE
BACK FILL PLATE OUT OF CABINET
DISCARD BACK
FILL PLATE
3
ROTATE BLOWER AND SLIDE
INTO BOTTOM OFFSETS
REINSTALL
FRONT FILL PLATE
MIS-2842 A
FIGURE 3 – BLOWER CONFIGURATIONS
Manual 2100-537I Page 16 of 54
STACKED CONFIGURATIONS
UPFLOW AND COUNTERFLOW
CONDENSER BASE FOR BOTH
PLUG BLOWER POWER
CONNECTOR INTO POWER
PLUG PROTRUDING THROUGH
MOUNT FIELD
SUPPLIED SINGLE
GANG ELECTRICAL
BOX ALIGNED OVER
HIGH VOLTAGE K.O.
MIS-2843
REMOVE SUPPLIED
WIRE HARNESS AND
STRAIN RELIEF BUSHING
FROM BLOWER POWER PLUG.
ROUTE WIRE HARNESS
THROUGH STRAIN RELIEF
AND INTO ELECTRICAL BOX
TO MAKE FIELD POWER
CONNECTION
FIGURE 4 – BLOWER POWER CONNECTIONS
Manual 2100-537I Page 17 of 54
Loading...
+ 37 hidden pages