E mail: sales@blue-white.com or techsupport@blue-white.com
Operating Manual
R
Blue-White
Industries, Ltd.
5300 Business Drive
Huntington Beach, CA 92649
USA
Website: www.blue-white.com
Page 2
A-100NA-100N
SECTIONHEADINGPAGE
1Introduction2
2Specifications3
3A-100NV Features3
4How to install the A-100N4
4.1Mounting location4
4.2Electrical connections6
4.3How to install the tubing and fittings8
5How to operate the A-100N10
5.1Description of Pump Output Adjustment Controls10
5.2Mode 1 - Manually Adjusting the output11
5.3Mode 2 - 4-20 mA input11
5.4Mode 3 - 0-10 VDC input13
TABLE OF CONTENTS
Page 2Page 3
5.5Mode 4 - Frequency/Pulse (Hz) input14
6Alarms15
6.1Tube Failure Detection (TFD) system15
7How to maintain the A-100N16
7.1Routine inspection and cleaning16
7.2How to clean and lubricate the A-100N16
7.3500 hour service warning timer16
7.4How to replace the pump tube17
Replacement parts drawing18
Replacement parts list19
1.0Introduction
Congratulations on purchasing the A-100NV variable speed Peristaltic Metering Pump. The A-100NV is
designed to inject chemicals into piping systems. The pump has been tested by NSF International for
use with 12 ½% Sodium Hypochlorite. The A-100NV is equipped with external input control circuitry
which allows the pumps output to be externally controlled by either a 4-20mA input signal, a 0-10V DC
input signal or a pulsed frequency input signal.
Page 3
2.0Specifications
Maximum Working Pressure 100 psig / 6.9 bar*
Maximum Fluid Temperature 130 F / 54 C
Ambient Temperature Range 14 to 110 F / -10 to 43 C
Duty CycleContinuous
Maximum Solids50% by volume
Maximum Viscosity5,000 Centipoise
Maximum Suction Liftup to 30 ft. water
Power Requirements115V60Hz, 220V50Hz, 230V60Hz
Shipping Dimensions18” x 14” x 10”
Shipping Weight14 lb.
o o
o o
3.0A-100NV Features
!
Peristaltic Pump Tube does not require valves.
!
High outlet pressure capability of 100 psig.*
!
High inlet suction lift capability of 30 feet.
!
Tube Failure Detection (TFD) system (patent
pending).
!
Quick-Disconnect inlet and outlet fittings available.
!
Easy servicing.
!
Includes suction tube strainer, tube weight, suction tubing, discharge tubing and injection fitting with
internal back-flow check valve and mounting hardware.
1
9
2
VARIABLE SPEED PUMP
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
2 - 4-20mA
1 - MANUAL
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
DIGIT MODE
DISPLAY
3 - 0-10VDC 4 - PULSE (Hz)
!
Digital electronic feed rate control.
!
Pump Tube failure warning timer.
!
20:1 adjustment turn down ratio.
!
Corrosion proof Valox housing.
!
Tamper resistant electronic control panel cover.
!
Output verification sensor system.
1
9
8
6.0
Pumptube
Assembly
Rotor
Assembly
*Most models.
** Slide both top & bottom clamps to the left only far enough to open the control cover.
Slide Clamps**
Control
FIG. 3.0 PARTS LOCATOR DRAWING
Pumphead
Cover
Control Cover
Pumphead
Junction Box
Rear Plate
Page 4
A-100NA-100N
Page 4Page 5
4.0How To Install the A-100NV
Note: All diagrams are strictly for guideline purposes only. Always consult an expert before installing
the A-100NV into specialized systems.
The A-100NV should be serviced by qualified persons only.
4.1Mounting Location
Choose an area located near the chemical supply tank, chemical injection point and electrical supply.
Although the pump is designed to withstand outdoor conditions, a cool, dry, well ventilated location is
recommended. Install the pump where it can be easily serviced.
!
Mount the pump to a secure surface or wall using the enclosed hardware. Wall mount to a solid surface
only. Mounting to drywall with anchors is not recommended.
!
Keep the outlet (discharge) tubing as short as possible. Longer tubing increases the back pressure at the
pump tube.
!
Do not mount the pump directly over your chemical container. Chemical fumes may damage the unit.
Mount the pump off to the side or at a lower level than the chemical container.
!
Mounting the pump lower than the chemical container will gravity feed the chemical into the pump. This
“flooded suction” installation can reduce the time required to prime the pump. Install a shut-off valve,
pinch clamp or other means to halt the gravity feed to the pump during servicing.
!
Your solution tank should be sturdy. Keep the tank covered to reduce fumes.
!
Be sure your installation does not constitute a cross connection with the drinking water supply. Check
your local plumbing codes.
Floor Mount
Wall Mount
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
4 Places
3-1/2”
FIG. 4.0 INJECTOR MOUNTING
7-5/8”
7-3/8”
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
2 Places
Note: For wall-mounting, recommend drill & thread into
solid wood only.
8-3/16”
Page 5
22
33
4466
55
VARIABLE SPEED PUMP
RUN
1
MODE
PROGRAM
VDC
mA Hz
% SPEED
STAND-BY
PRIME
1000
MINIMUM
SERVICE
ALARM
MAXIMUM
DIGIT MODE
FIELD
RUN
STANDBY
PRIME
DISPLAY
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
1 - MANUAL
77
11
88
99
ol
o
P
1010
1. Strainer7. Injector
2. Circulation Pump
3. Filter
4. Heater
5. Check Valve
6. Flowmeter
Blue-White F-300
®
Blue-White A-100N
8. Solution Tank
9. Injection Fitting
10. Return Line
®
FIG. 4.1 SWIMMING POOL INSTALLATION
¼"
&
½"
N
P
T
In
FIG. 4.2 TYPICAL INSTALLATION
Discharge
Tube
jec
to
r
RUN
STANDBY
1 - MANUAL
Suction
Tube
VARIABLE SPEED PUMP
MODE
VDC
mA Hz
% SPEED
1000
SERVICE
ALARM
DIGIT MODE
FIELD
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
RUN
1
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
DISPLAY
Pumping unit
R
Chemical
Container
Page 6
A-100N
4.2Electrical Connections
4.2.1Input Power Connections -
Be certain to connect the pump to the proper supply voltage. Using the incorrect voltage will damage
the pump and may result in injury. The voltage requirement is printed on the pump serial label.
Jumper pins on the circuit board are factory preset for the correct voltage. See Fig. 4.4, page 7 for
details.
The A-100NV is supplied with a ground wire conductor and a grounding type attachment plug (power
cord). To reduce the risk of electric shock, be certain that the power cord is connected only to a properly
grounded, grounding type receptacle.
Note: When in doubt regarding your electrical installation, contact a licensed electrician.
4.2.2External Input Signal Connections -
Page 6
The A-100NV will accept any one of three different types of external input signals; 4-20 mA, 0-10
VDC, or frequency. Two types of frequency inputs, AC sine waves (magnetic coils type outputs) and
Digital Square waves (Hall Effect signals, contact closures), are acceptable. A jumper plug located on
the circuit board is factory pre-set for AC sine wave signals, the jumper must be re-positioned when
digital square wave signals are being used. (See Fig. 4.4, page 7, “Hz input jumper settings”)
All wiring connections are to be made inside of the junction box located on the side of the A-100NV. A
liquid-tite connector is supplied and should be used for the external signal cable. The signal input wires
are color coded to the type of signal being used.
INPUT SIGNAL TYPE
4-20 mA
0-10 V DC
AC sine wave, Digital square wave
POSITIVE
WIRE COLOR
BLUE
ORANGE
WHITE
NEGATIVE
WIRE COLOR
BLACK
BLACK
BLACK
FIG. 4.3 WIRING CHART - INPUT SIGNAL WIRE COLORS
Page 7
Page 7
A-100N
SIGNAL INPUT MODES / FUNCTIONS & WIRING COLOR CODES
INPUT MODE / FUNCTION
MANUAL
4-20 mA
0-10 VDC
FREQUENCY
ALARM RELAY
FLOW VERIFICATION SENSOR
(Digital square waves)
MOTOR ON SIGNAL
EXTERNAL INPUT CABLE
ACCEPTABLE CABLE JACKET RANGE:
RED (+20VDC)
BLACK (Ground)
BLUE (4-20 mA input)
ORANGE (0-10 VDC input)
WHITE (frequency input)
YELLOW (verification sensor input)
BROWN (motor-on contact output)
PURPLE X2 (alarm relay contacts)
.118 - .255 INCH
.( 3,0 - 6,5 MM)
JUNCTION BOX
WIRES REQUIRED
NO CONNECTIONS
BLUE (+) & BLACK (-)
ORANGE (+) & BLACK (-)
WHITE (+) & BLACK (-)
PURPLE & PURPLE
RED (+ 20VDC) & BLACK (-) & YELLOW (signal)
BROWN (+) & BLACK (-)
(open - factory default)
AC LINE VOLTAGE SETTINGS
Hz INPUT JUMPER SETTINGS
Located under connector
AC sine waves
Jumper Not Installed
Digital square waves
Jumper Installed
INPUT SIGNAL CONNECTOR
7 wire bundle
LIQUID-TIGHT
CONNECTOR
ALARM OUTPUT
(CONTACT CLOSURE)
connect 2-conductor plug to either
normally open (NO) (factory default)
or normally closed (NC) side of receptacle.
1 AMP MAX @ 125VAC (24VDC)
TUBE FAILURE SENSOR PROBE INPUT
Connect 2-conductor plug to receptacle.
2 Grey wires connect to pump head sensors.
RED (+)
DC
MOTOR
BLACK (-)
Ground (green)
MOTOR
RED (+)
MOTOR
BLACK (-)
NC
NO
AC LINE
NEUTRAL
10
1
220
10
1
E
B
TS
RO
P
1 AMP
250V AC
AC LINE
HOT
Earth Ground (green)
230 VAC
One Jumper Installed
on center position
(ends open)
Two Jumpers Installed
THERMAL SWITCH
.187 push tab connectors
2 conductors
PROTECTOR FUSE
1 Amp, 250 Volt AC
(Littlefuse #239001
or Equivalent)
Hot
Common
Input
Power
115 VAC
on end positions
(no open pins)
AC
FIG. 4.4 WIRING DIAGRAM - MODEL V CIRCUIT BOARD
Page 8
A-100N
Page 8
4.3How To Install the Tubing and Fittings
4.3.1Inlet Tubing - Locate the inlet fitting of the Pump Tube, see fig 4.6. Remove the tube nut. Push the
clear PVC suction tubing onto the compression barb of the fitting. Use the tube nut to secure the tube.
Hand tighten only.
4.3.2Strainer -Trim the inlet end of the suction tubing so that the strainer
will rest approximately two inches from the bottom of the solution
tank. This will prevent sediment from clogging the strainer. Slip the
ceramic weight over the end of the suction tube. Press the strainer
into the end of the tube. Secure the ceramic weight to the strainer.
Drop the strainer into the solution tank.
4.3.3Outlet Tubing - Locate the outlet fitting of the Pump Tube, see fig
4.6. Remove the tube nut. Push the opaque outlet (discharge)
tubing onto the compression barb of the fitting. Use the tube nut to
secure the tube. Hand tighten only. Trim the other end of the outlet
tube leaving only enough slack to connect it to the injection/check
valve fitting. Increasing the outlet tube length increases the pressure
at the pump tube, particularly with viscous fluids.
Tubing
Suction 3/8"
Ceramic
Weight
# 90008-068
Foot
Strainer
# 90002-200
Keep the outlet tube as short as possible.
Outlet Adapter
Pump Head
VARIABLE SPEED PUMP
MODE
% SPEED
1000
ALARM
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
2 - 4-20mA
1 - MANUAL
1
VDC
mA Hz
SERVICE
DIGITMODE
DISPLAY
3 - 0-10VDC 4 - PULSE (Hz)
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
FIG. 4.5
Inlet Adapter
FIG. 4.6
Page 9
Page 9
4.3.4Injection/Check Valve Fitting Installation - The Injection/Check valve fitting is designed to install
directly into either 1/4” or 1/2” female pipe threads. This fitting will require periodic cleaning, especially when injecting fluids that calcify such as sodium hypochlorite. These lime deposits and other
build ups can clog the fitting increasing the back pressure and interfering with the check valve operation.
See section 7.0.
Install the Injection/Check valve directly into the piping system. Do not use a pipe stud with a tee for
insertion of the injection valve. The solution must inject directly into the flow stream.
Use Teflon thread sealing tape on the pipe threads. Push the opaque outlet (discharge) tubing onto the
compression barb of the Injection/Check valve fitting. Use the tube nut to secure the tube. Hand tighten
only.
A-100N
FIG. 4.7 INJECTION FITTING INSTALLATION AND EXPLODED VIEW
Page 10
A-100N
5.0How To Operate The A-100NV
5.1Description of Pump Output Adjustment Controls -
Open the control panel door by sliding the upper and lower slide
clamps to the left. FIG. 5.2
!
RUN/STANDBY Button -
4
Press to start and stop the pump. The ARROW next to the word RUN
will light when in the run mode. The ARROW next to the word
STAND-BY will blink when in the stand-by mode.
4
Press to clear ALARM.
4
When pressed with the FIELD Button, initiates a 99 second prime
cycle which temporarily overrides the mode setting and runs the
pump motor at 100% speed. The ARROW next to the word PRIME
will blink.
4
When pressed with the DIGIT button, resets the 500 hour service
warning timer to zero.
4
When pressed with the MODE button, initiates the programming
mode. The ARROW next to the word PROGRAM will blink.
!
FIELD Button -
4
In the programming mode, selects the digit to be changed.
VARIABLE SPEED PUMP
1
VDC
mAHz
SERVICE
DIGITMODE
PROGRAM
3 - 0-10VDC 4 - PULSE (Hz)
RUN
STANDBY
1 - MANUAL
MODE
% SPEED
1000
ALARM
FIELD
PRIME
RESET SERVICE
INPUT MODES
2 - 4-20mA
Page 10
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
DISPLAY
!
DIGIT Button -
4
In the programming mode, increases the selected digit.
4
When pressed with the MODE Button, toggles the display from %
motor speed to input signal value.
Slide both top & bottom clamps to the left only far enough
(as shown) to open the control cover
FIG. 5.2
SLIDE CLAMP
Page 11
Page 11
5.2OPERATING MODE 1 - Output adjusted manually -
In this mode, the pump’s motor speed is adjusted manually using the front panel
touch pad. The motor speed can be adjusted from 0-100%. To adjust the speed:
4
Set the pump for mode 1. Press the MODE button until MODE 1 is shown on
the LCD display. The %SPEED icon will light. The large 3-DIGIT LCD will
indicate the currently programmed percentage of speed.
4
Enter the programming mode. At the same time, press the RUN/STANDBY
button and the MODE button. A blinking ARROW will point to the word
PROGRAM indicating the program mode has been activated.
4
Press the FIELD button to select the digit to program. The digit will blink
when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The arrow next to the word PROGRAM will
disappear.
[
NOTE: If while in the program mode no buttons are pressed within 20 seconds,
the circuitry will automatically return to the run mode, without saving changes.
A-100N
RUN MODE 1
MODE
% SPEED
1
100
PROGRAM MODE 1
constant speed % setting
MODE
% SPEED
1
000
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
5.3 -
OPERATING MODE 2 - Output adjusted by 4-20 mA input signal
In this mode, the pump’s motor speed is adjusted automatically based on the value
of the 4-20 mA input signal. Any motor speed can be assigned to either the
minimum or maximum milliamp input values. However, the programmed
minimum mA value must be less than the programmed maximum mA value.
The ALARM and SERVICE icons will blink if the programming is in error. To
assign the minimum and maximum motor speed and the minimum and maximum
mA input signal values:
4
Set the pump for mode 2. Press the MODE button until MODE 2 is shown on
the LCD display. The %SPEED or mA icon will light depending on the
current display setting. The large 3-DIGIT LCD will indicate the current
motor speed or the current mA input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY
and MODE buttons. A blinking ARROW will point to the word PROGRAM
indicating the program mode is activated. A blinking ARROW will point to the
word MINIMUM indicating the minimum value is ready to be programmed.
The % SPEED icon will blink indicating the percentage of speed is ready to
be programmed.
4
Enter the motor speed at the minimum mA input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon
will blink indicating the minimum mA value is ready to be programmed. The
currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum mA input signal value. Note: this value must be less than
the maximum mA input signal value. Press the FIELD button to select the
digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
RUN MODE 2
MODE
2
mA
04.0
PROGRAM MODE 2
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 2
minimum input value
MODE
mA
04.0
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
2
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
2
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
Page 12
A-100N
4
Press the mode button. The Ma icon will stop blinking and the % SPEED icon
will blink. The ARROW next to the word MAXIMUM will blink indicating the
maximum value is ready to be programmed. The currently programmed
maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum mA input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon
will blink indicating the maximum mA value is ready to be programmed. The
currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum mA input signal value. Note: this value must be greater
than the minimum mA input signal value. Press the FIELD button to select the
digit to program. The digit will blink when selected..
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The PROGRAM arrow will disappear.
Page 12
PROGRAM MODE 2
% speed at the maximum input
RUN
MODE
% SPEED
PROGRAM MODE 2
MODE
20.0
2
100
maximum input value
2
mA
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
Example 1
4 mA = 0% OUTPUT
20 mA = 100% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
6
8
4
Milliamp input (mA)
4 mA = 0% OUTPUT
20 mA = 75% OUTPUT
100
75
12
10
Example 3
MODE 2 PROGRAMMING EXAMPLES
Example 2
4 mA = 100% OUTPUT
20 mA = 0% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
6
14
16
18
20
4
Milliamp input (mA)
4 mA = 20% OUTPUT
20 mA = 50% OUTPUT
100
75
8
12
10
Example 4
14
16
18
20
50
25
Pump Motor Speed (%)
0
6
8
4
Milliamp input (mA)
10
12
14
16
18
20
50
25
Pump Motor Speed (%)
0
6
8
4
10
Milliamp input (mA)
12
14
16
18
20
Page 13
Page 13
5.4 - OPERATING MODE 3 - Output adjusted by 0-10VDC input signal
In this mode, the pump’s motor speed is adjusted automatically based on the value
of the 0-10VDC input signal. Any motor speed can be assigned to either the
minimum or maximum DC input signal values. However, the programmed
minimum VDC value must be less than the programmed maximum VDC
value. The ALARM and SERVICE icons will blink if the programming is in
error. To assign the minimum and maximum motor speed and the minimum and
maximum VDC input signal values:
4
Set the pump for mode 3. Press the MODE button until MODE 3 is shown on
the LCD display. The % SPEED or VDC icon will light depending on the
current display setting. The large 3-DIGIT LCD will indicate the current
motor speed or the VDC input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY
and MODE buttons. A blinking ARROW will point to the word PROGRAM
indicating the program mode is activated. A blinking ARROW will point to the
word MINIMUM indicating the minimum value is ready to be programmed.
The % SPEED icon will blink indicating the percentage of speed is ready to
be programmed.
4
Enter the motor speed at the minimum VDC input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the VDC
icon will blink indicating the minimum VDC value is ready to be programmed. The currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum VDC input signal value. Note: this value must be less
than the maximum VDC input signal value. Press the FIELD button to select
the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The VDC icon will stop blinking and the % SPEED
icon will blink. The ARROW next to the word MAXIMUM will blink indicating
the maximum value is ready to be programmed. The currently programmed
maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum VDC input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the VDC
icon will blink indicating the maximum VDC value is ready to be programmed. The currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum VDC input signal value. Note: this value must be greater
than the minimum VDC input signal value. Press the FIELD button to select
the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The PROGRAM arrow will disappear.
A-100N
RUN MODE 3
MODE
3
VDC
00.0
PROGRAM MODE 3
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 3
minimum input value
MODE
VDC
00.0
PROGRAM MODE 3
% speed at the maximum input
MODE
% SPEED
100
PROGRAM MODE 3
maximum input value
MODE
VDC
10.0
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
3
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
3
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
3
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
3
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
Page 14
A-100N
5.5 - OPERATING MODE 4 - Output adjusted by frequency (Hz) input signal
In this mode, the pump’s motor speed is adjusted automatically based on the
frequency (Hz) of the input signal. Any motor speed can be assigned to either the
minimum or maximum Hz input signals. However, the programmed minimum
Hz value must be less than the programmed maximum Hz value. The
ALARM and SERVICE icons will blink if the programming is in error. To assign
the minimum and maximum motor speed and the minimum and maximum Hz
input signal values:
4
Set the pump for mode 4. Press the MODE button until MODE 4 is shown on
the LCD display. The % SPEED or Hz icon will light depending on the
current display setting. The large 3-DIGIT LCD will indicate the current
motor speed or the Hz input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY
and MODE buttons. A blinking ARROW will point to the word PROGRAM
indicating the program mode is activated. A blinking ARROW will point to the
word MINIMUM indicating the minimum value is ready to be programmed.
The % SPEED icon will blink indicating the percentage of speed is ready to
be programmed.
4
Enter the motor speed at the minimum Hz input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the Hz icon
will blink indicating the minimum Hz value is ready to be programmed. The
currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum Hz input signal value. Note: this value must be less than
the maximum Hz input signal value. Press the FIELD button to select the digit
to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The Hz icon will stop blinking and the % SPEED icon
will blink. The ARROW next to the word MAXIMUM will blink indicating the
maximum value is ready to be programmed. The currently programmed
maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum VDC input signal value. Press the
FIELD button to select the digit to program. The digit will blink when
selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the Hz icon
will blink indicating the maximum Hz value is ready to be programmed. The
currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum Hz input signal value. Note: this value must be greater
than the minimum Hz input signal value. Press the FIELD button to select the
digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The PROGRAM arrow will disappear.
Page 14
RUN MODE 4
MODE
4
000
PROGRAM MODE 4
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 4
minimum input value
MODE
000
PROGRAM MODE 4
% speed at the maximum input
MODE
% SPEED
82.5
PROGRAM MODE 4
minimum input value
MODE
628
RUN
PROGRAM
Hz
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
4
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
4
PROGRAM
Hz
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
4
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
4
PROGRAM
Hz
STAND-BY
PRIME
MINIMUM
MAXIMUM
Page 15
Page 15
Example 1
0 Hz = 0% OUTPUT
1000 Hz = 100% OUTPUT
100
MODE 4 PROGRAMMING EXAMPLES
Example 2
0 Hz = 100% OUTPUT
1000 Hz = 0% OUTPUT
100
A-100NA-100N
Example 3
0 Hz = 10% OUTPUT
275 Hz = 75% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
200
0
Frequency input (Hz)
400
600
800
1000
75
50
25
Pump Motor Speed (%)
0
6.0ALARMS -
6.1Tube Failure Detection System (TFD)
The A-100NV is equipped with a Tube Failure Detection System which is designed to stop the pump and
provide a contact closure output in the event the pump tube should rupture and chemical enters the pump
head. This patent-pending system is capable of detecting the presence of a large number of chemicals
including Sodium Hypochlorite (chlorine), Hydrochloric (muriatic) Acid, Sodium Hydroxide, and many
others. The system will not be triggered by water (rain, condensation, etc.) or silicone oil (roller and
tubing lubricant).
Confirm Chemical Detection -
To determine if your chemical will be detected by the system, remove the pump
tube and roller assembly, place a small amount of the chemical in the bottom of
the pump head, just enough to cover the sensors, and turn on the pump. If the TFD
system detects the chemical, the pump will stop after a five second confirmation
period and the ALARM icon will light on the display. If the TFD system does not
detect the chemical, the pump will continue to run after the confirmation period.
Carefully clean the chemical out of the pump head being sure to remove all traces
of chemical from the sensor probes. Press the RUN/STAND-BY button to clear
the alarm condition and restart the pump.
400
600
200
0
Frequency input (Hz)
800
1000
75
50
25
Pump Motor Speed (%)
0
200
0
Frequency input (Hz)
600
400
RUN MODE 1
MODE
% SPEED
000
ALARM
800
1
1000
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
To Disable the Chemical Detection -
If the TFD system cannot detect your chemical, no further action is necessary. However, if there is a
concern about possible false triggering by chemical contaminants, the system can be disabled by unplugging the sensor probe wires from the circuit board. See Fig. 4.4, page 7 for the sensor probe’s plug
location on the internal circuit board.
Contact Closure Alarm Output Signal -
A contact closure output is provided with the TFD system. The output can be configured for normally
open (factory default) or normally closed operation by properly positioning the connector plug on the
circuit board (See fig. 4.4, page 7). The contacts will change states while an alarm condition exists. Two
wires (purple), located in the junction box, are provided for connections. 20mA minimum / 1 amp
maximum load @ 125V AC /24V DC.
Page 16
A-100N
7.0How to Maintain the A-100NV
7.1Routine Inspection and Maintenance
The A-100NV requires very little maintenance. However, the pump and all accessories should be
checked weekly. This is especially important when pumping chemicals. Inspect all components for
signs of leaking, swelling, cracking, discoloration or corrosion. Replace worn or damaged components
immediately.
Cracking, crazing, discoloration and the like during the first week of operation are signs of severe
chemical attack. If this occurs, immediately remove the chemical from the pump. Determine which
parts are being attacked and replace them with parts that have been manufactured using more suitable
materials. The manufacturer does not assume responsibility for damage to the pump that has been
caused by chemical attack.
7.2How to Clean and Lubricate the A-100NV
Page 16
The A-100NV will require occasional cleaning and lubricating. The amount will depend on the severity
of service.
]
When changing the pump tube assembly, clean the pump head chamber, TFD sensors, roller assembly
and pump head cover.
]
The pump head cover bearing may require grease periodically. Apply a small amount of grease
(Aeroshell aviation grease #5 or equivalent) when necessary.
]
Silicone oil ONLY may be used on the roller assembly and tube assembly.
]
The injection/check valve assembly must be cleaned periodically, especially when injecting fluids that
calcify such as sodium hypochlorite. These lime deposits and other build ups can clog the fitting
increasing the back pressure which can interfere with the check valve operation and possibly damage the
fitting and/or the pump. See section 4.3.4. Fig. 4.7.
]
Periodically clean the suction strainer. Fig.4.5.
]
Periodically inspect the air vents located under the motor compartment and on the rear panel. Clean if
necessary.
7.3500 Hour Service Warning Timer
The A-100NV is equipped with a service warning timer. After 500 hours of accumulated running time,
the SERVICE icon will light. This is a reminder that the pump tube is nearing its minimum life expectancy and should be replaced. Your actual tube life will depend on many factors such as the chemical
used, back pressure, temperature, viscosity, and motor RPM.
Simultaneously press the RUN/STANDBY and DIGIT buttons to reset the service timer to zero.
Note: Pressing the FIELD and DIGIT buttons will display the currently accumulated time value.
Page 17
Page 17
7.4How to Replace the Pump Tube
The pump tube assembly will eventually break if not replaced. The tube has been designed for a
minimum service life of 500 hours. However, the life of the tube is affected by many factors such as the
type of chemical being pumped, the amount of back pressure, the motor RPM, temperature and others.
The pump tube assembly must be inspected and replaced regularly.
After replacing the pump tube, press the RUN/STANDBY button and the DIGIT button at the
same time to reset the service warning timer.
7.4.1How to Remove the Old Pump Tube
The pump roller assembly spins in a counter clockwise direction. The pump head inlet (suction) side is
located at the bottom of the pump and the outlet (discharge) is located at the top of the pump head.
A-100N
7.4.1.1 Release any pressure that may be in the
discharge tubing.
Outlet Adapter
Pump Head
7.4.1.2 Disconnect the suction and discharge tubes
from the pump tube.
7.4.1.3 Remove the pump head cover.
7.4.1.4 With the pump running, pull the inlet fitting
out of the pumphead. Guide the tube counter
clockwise away from the rollers. Pull the
VARIABLE SPEED PUMP
MODE
mA Hz
% SPEED
1000
ALARM
SERVICE
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
1 - MANUAL
1
PROGRAM
VDC
STAND-BY
MINIMUM
MAXIMUM
DIGIT MODE
DISPLAY
RUN
PRIME
outlet fitting out of the pump head.
7.4.2How to Install a New Pump Tube
Inlet Adapter
FIG. 7.1
Be sure the pump head chamber is clean and free of any debris. Remove and inspect the roller assembly. Be sure the rollers spin freely. If required, apply a small amount of grease to the pump head cover
bearing. Silicone oil only may be used on the tubing and rollers. See section 7.2.
6.4.2.1 With the pump running, insert the inlet (suction) side of the Pump Tube fitting into the lower retaining
slot in the pump head. Fig. 7.2.
6.4.2.2 Carefully guide the Pump Tube into the pump head. Stretch the tube slightly and insert the outlet
(discharge) fitting into the upper retaining slot in the pump head. Fig. 7.3.
6.4.2.3 Place the clear cover on the pump head and secure with three screws.
FIG. 7.2FIG. 7.3
Page 18
A-100N
Page 18
Replacement Parts Drawing
20
BRUSH KIT
1
4
5
54
53
7
52
9
56
55
2
3
10
18
22
6
8
21
42
23
2
25
24
26
17
27
12
19
z)
SE (H
MODE
PUL
4 =
R
IT
DIG
0-10 VDC
ING TIME
3 =
T MODE
RESET
E
LD
LIFE WAR
INPU
E
= 4-20mA
FIE
TUBE
L 2
PRIM
99 SEC.CYCL
ANUA
1 = M
STANDBY
3
11
41
14
28
13
29
32
33
OPTIONAL
QUICKCONNECT
35
30
40
31
15
16
36
46
34
37
49
39
38
45
48
Page 19
Page 19
A-100N
A-100N PARTS LIST
A-008-2Gearbox, 30 Rpm1
A-008-3Gearbox, 45 Rpm1
A-008-4Gearbox, 60 Rpm1
A-008-5Gearbox, 125 Rpm1
26A-008-1Gearbox, 14 Rpm1
2776001-488Pumphead, A-100N w/TFD sensors1
28C-324NScrew, Pumphead, 10-32 X .50 Phil Pan Black4
171000-489Enclosure Back Plate With Gasket, Valox1
290011-094Washer, Mounting, #10 Stainless2
390011-091Mounting Screw, #10 X 1.0” Phillips Steel4
476001-001Tubing Spacer A-100N digital2
590010-036Wire Nut, Blue1
690006-580Gasket, Enclosure Back Plate1
7A-023N-V-115Circuit board A-100NV 115V 1
71000-176Power Cord, 220v50hz, Digital Models1
71000-177Power Cord, 230v60hz, Digital Models1
890010-235Fuse, A-100NV Circuit Board, 1A 250VAC1
971000-175Power Cord, 115v60hz, Digital Models1
1070000-589Cord Inlet Bushing1
70002-251Gearmotor, 30 Rpm, 24V DC 1
70002-252Gearmotor, 45 Rpm, 24V DC 1
70002-253Gearmotor, 60 Rpm, 24V DC 1
70002-254Gearmotor, 125 Rpm, 24V DC 1
1190003-559Mounting Feet, Rubber4
1276001-000Slide Clamp, Enclosure Rear1
1376000-999Slide Clamp, Enclosure Front1
1476001-253Enclosure A-100NV 1
1590006-579Gasket, Enclosure Front1
1690002-191Door, Electronic Controls Cover1
1770002-250Gearmotor, 14 Rpm, 24V DC 1
1890010-246Wire set w/plug, Alarm relay1
1990010-245Wire set w/plug, TFD sensor1
N/s90010-247Wire set w/plug, input signals1
20C-1814N-4Motor Brush kit (2 ea), 24V DC1
2190011-023Screw, Motor, 8-32 x .502
2290010-244Motor, 24V DC1
2390011-024Screw, Green Ground, 8-32 x .251
2490011-078Washer, Ground Screw, #8 Star1
2590010-222Wire, Motor ground, Digital Timers, Green1
Page 20
LIMITED WARRANTY
Your new pump is a quality product and is warranted to be free of defects as set down in this policy. All parts, including rubberized goods, and labor
are covered under warranty for 90 days from the date of purchase. Used peristaltic pump tube assemblies are not warranted. Parts, excluding
rubberized goods, are covered under warranty for 12 months from the date of purchase.
Warranty coverage does not include damage to the pump that results from misuse, carelessness, abuse or alteration. Only the repair or the
replacement of the pump is covered. Blue-White Industries does not assume responsibility for any other loss or damage.
Warranty status is determined by the pump’s serial label and the sales invoice or receipt. The serial label must be on the pump and the pump must be
accompanied by the sales invoice or receipt to obtain warranty coverage. The warranty status of the pump will be verified by Blue-White or a factory
authorized service center.
Please be advised; injection and metering devices are not intended as a means of treating water to render it suitable for human consumption. When
used as hypochlorinators, they are meant to destroy bacteria and algae contamination, before it’s removal by filtration. Acid and soda injectors are
used for PH control (balance). Blue-White injectors are factory tested with water only for pressure and performance. Installers and operators of
these devices must be well informed and aware of the precautions to be taken when injecting various chemicals -especially those considered
hazardous or dangerous.
Should it become necessary to return an injector for repair or service, you must attach information regarding the chemical used as some residue may
be present within the unit which could be a hazard to service personnel.
Blue-White Industries will not be liable for any damage that may result by the use of chemicals with their injectors and it’s components. Thank you.
PROCEDURE FOR IN WARRANTY REPAIR
Carefully pack the pump to be repaired, include the foot strainer and injection/check valve fitting. Enclose a brief description of the problem as well
as the original invoice or sales receipt showing the date of purchase. The receipt will be returned with the unit. Prepay all shipping costs. COD
shipments will not be accepted. Warranty service must be performed by the factory or an authorized service center. Damage caused by improper
packaging is the responsibility of the sender.
AUTHORIZED SERVICE CENTERS
ARKANSASFLORIDAMARYLAND
BT Environmental, IncAAA Electric Motor ServicesCentury Pool Service, Inc
Bill Thomason1131 N.E. 45th Street5020 Nicholson Court, #201
225 Castleberry StreetFt. Lauderdale, FL 33334Kensington, MD 20895
Hot Springs, AR 71901305-772-7501301-231-8999
501-624-3837
CALIFORNIA (NORTHERN)2021 Curry Ford Road
Howard E. Hutching company
(Repair Center)
7190 Penryn Plaza
Penryn, CA 95663
Pool-Tech, Inc.
401 Sunset Dr., Suite A.
Antioch, CA 94509
925-754-2424
Swimco Electric Co.
753 Camden Avenue
Campbell, CA 95008
408-378-2607
CALIFORNIA (SOUTHERN)
Blue-White Industries
(Repair Center)
5422 Business Drive
Huntington Bch. CA 92649
714-893-8529
COLORADO
Denver Winpump
4845 Pontiac Street
Commerce City, CO 80022
303-287-2884
CONNECTICUT
Cronin-Cook & Associates
24 West Road
Vernon, CT 06066
203-875-0544
All American Pool & Patio
Orlando, FL 32806
407-898-8722
Rice Pump & Motor Repair702-384-4223
5740 N.W. 9 ave.
Ft. Lauderdale FL 33309NEW YORK
954-776-6049Sherwood Specialties, Inc.
American Pump
7580-A W. Tennessee St.
Tallahassee, FL 32304
850-575-9618
Jerry Lee Chemical Co.Southern Industrial Sales
3407 W. Old Fairfield Drive1903 Herring Avenue
Pensacola, FL 32505Wilson, NC 27893
904-432-9929919-237-2500
Picard Chemical
1670 S. Congress AvenueSOUTH DAKOTA
W. Palm Beach, FL 33406Son-Aqua Distributing
407-965-3434Jim Robinson
V.J. Mini & Son, Inc.Rapid City, SD 57702
1581 N. Dixie Highway605-343-7716
Pompano Beach, FL 33060
305-946-0920TENNESSEE
ILLINOIS307 3rd Avenue South
Mullarkey Associates
(Repair Center)
12346 S. Keeler Ave.
Alsip, IL 60658
708-597-5558
NEVADA
Swim-In Enterprises, Inc.
1314 S. Main Street
Las Vegas, NV 89104
412 Smith Street
Rochester, NY 14608
716-546-1211
NORTH CAROLINA
2447 W. Main Street
Rock City Machine
Nashville, TN 37201
615-244-1371
TEXAS
Alamo Water Refiners
13700 Hwy. 90 West
San Antonio, TX 78245
512-677-8400
# 80000-381Rev. 7/18/2003
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.