Blue-White A-100NV Operating Manual

Page 1
INJECTOR
®
MODEL A-100NV (external signal input)
Variable Speed Peristaltic Injector Pump
E mail: sales@blue-white.com or techsupport@blue-white.com
Operating Manual
R
Blue-White
Industries, Ltd.
5300 Business Drive
Huntington Beach, CA 92649
USA
Website: www.blue-white.com
Page 2
A-100N A-100N
SECTION HEADING PAGE 1 Introduction 2 2 Specifications 3 3 A-100NV Features 3 4 How to install the A-100N 4
4.1 Mounting location 4
4.2 Electrical connections 6
4.3 How to install the tubing and fittings 8
5 How to operate the A-100N 10
5.1 Description of Pump Output Adjustment Controls 10
5.2 Mode 1 - Manually Adjusting the output 11
5.3 Mode 2 - 4-20 mA input 11
5.4 Mode 3 - 0-10 VDC input 13
TABLE OF CONTENTS
Page 2 Page 3
5.5 Mode 4 - Frequency/Pulse (Hz) input 14
6 Alarms 15
6.1 Tube Failure Detection (TFD) system 15
7 How to maintain the A-100N 16
7.1 Routine inspection and cleaning 16
7.2 How to clean and lubricate the A-100N 16
7.3 500 hour service warning timer 16
7.4 How to replace the pump tube 17
Replacement parts drawing 18 Replacement parts list 19
1.0 Introduction
Congratulations on purchasing the A-100NV variable speed Peristaltic Metering Pump. The A-100NV is designed to inject chemicals into piping systems. The pump has been tested by NSF International for use with 12 ½% Sodium Hypochlorite. The A-100NV is equipped with external input control circuitry which allows the pumps output to be externally controlled by either a 4-20mA input signal, a 0-10V DC input signal or a pulsed frequency input signal.
Page 3
2.0 Specifications
Maximum Working Pressure 100 psig / 6.9 bar* Maximum Fluid Temperature 130 F / 54 C Ambient Temperature Range 14 to 110 F / -10 to 43 C Duty Cycle Continuous Maximum Solids 50% by volume Maximum Viscosity 5,000 Centipoise Maximum Suction Lift up to 30 ft. water Power Requirements 115V60Hz, 220V50Hz, 230V60Hz Shipping Dimensions 18” x 14” x 10” Shipping Weight 14 lb.
o o
o o
3.0 A-100NV Features
!
Peristaltic Pump Tube does not require valves.
!
High outlet pressure capability of 100 psig.*
!
High inlet suction lift capability of 30 feet.
!
Tube Failure Detection (TFD) system (patent pending).
!
Quick-Disconnect inlet and outlet fittings available.
!
Easy servicing.
!
Includes suction tube strainer, tube weight, suction tubing, discharge tubing and injection fitting with internal back-flow check valve and mounting hardware.
1
9
2
VARIABLE SPEED PUMP
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
2 - 4-20mA
1 - MANUAL
RUN PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
DIGIT MODE
DISPLAY
3 - 0-10VDC 4 - PULSE (Hz)
!
Digital electronic feed rate control.
!
Pump Tube failure warning timer.
!
20:1 adjustment turn down ratio.
!
Corrosion proof Valox housing.
!
Tamper resistant electronic control panel cover.
!
Output verification sensor system.
1
9
8
6.0
Pumptube Assembly
Rotor Assembly
* Most models. ** Slide both top & bottom clamps to the left only far enough to open the control cover.
Slide Clamps**
Control
FIG. 3.0 PARTS LOCATOR DRAWING
Pumphead Cover
Control Cover
Pumphead
Junction Box
Rear Plate
Page 4
A-100N A-100N
Page 4 Page 5
4.0 How To Install the A-100NV
Note: All diagrams are strictly for guideline purposes only. Always consult an expert before installing the A-100NV into specialized systems. The A-100NV should be serviced by qualified persons only.
4.1 Mounting Location
Choose an area located near the chemical supply tank, chemical injection point and electrical supply. Although the pump is designed to withstand outdoor conditions, a cool, dry, well ventilated location is recommended. Install the pump where it can be easily serviced.
!
Mount the pump to a secure surface or wall using the enclosed hardware. Wall mount to a solid surface only. Mounting to drywall with anchors is not recommended.
!
Keep the outlet (discharge) tubing as short as possible. Longer tubing increases the back pressure at the pump tube.
!
Do not mount the pump directly over your chemical container. Chemical fumes may damage the unit. Mount the pump off to the side or at a lower level than the chemical container.
!
Mounting the pump lower than the chemical container will gravity feed the chemical into the pump. This “flooded suction” installation can reduce the time required to prime the pump. Install a shut-off valve, pinch clamp or other means to halt the gravity feed to the pump during servicing.
!
Your solution tank should be sturdy. Keep the tank covered to reduce fumes.
!
Be sure your installation does not constitute a cross connection with the drinking water supply. Check your local plumbing codes.
Floor Mount
Wall Mount
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
4 Places
3-1/2”
FIG. 4.0 INJECTOR MOUNTING
7-5/8”
7-3/8”
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
2 Places
Note: For wall-mounting, recommend drill & thread into solid wood only.
8-3/16”
Page 5
22
33
44 66
55
VARIABLE SPEED PUMP
RUN
1
MODE
PROGRAM
VDC
mA Hz
% SPEED
STAND-BY PRIME
1000
MINIMUM
SERVICE
ALARM
MAXIMUM
DIGIT MODE
FIELD
RUN
STANDBY
PRIME
DISPLAY
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
1 - MANUAL
77
11
88
99
ol
o
P
1010
1. Strainer 7. Injector
2. Circulation Pump
3. Filter
4. Heater
5. Check Valve
6. Flowmeter Blue-White F-300
®
Blue-White A-100N
8. Solution Tank
9. Injection Fitting
10. Return Line
®
FIG. 4.1 SWIMMING POOL INSTALLATION
¼"
&
½"
N
P
T
In
FIG. 4.2 TYPICAL INSTALLATION
Discharge
Tube
jec
to
r
RUN
STANDBY
1 - MANUAL
Suction
Tube
VARIABLE SPEED PUMP
MODE
VDC
mA Hz
% SPEED
1000
SERVICE
ALARM
DIGIT MODE
FIELD
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
RUN
1
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
DISPLAY
Pumping unit
R
Chemical Container
Page 6
A-100N
4.2 Electrical Connections
4.2.1 Input Power Connections -
Be certain to connect the pump to the proper supply voltage. Using the incorrect voltage will damage the pump and may result in injury. The voltage requirement is printed on the pump serial label.
Jumper pins on the circuit board are factory preset for the correct voltage. See Fig. 4.4, page 7 for details.
The A-100NV is supplied with a ground wire conductor and a grounding type attachment plug (power cord). To reduce the risk of electric shock, be certain that the power cord is connected only to a properly grounded, grounding type receptacle.
Note: When in doubt regarding your electrical installation, contact a licensed electrician.
4.2.2 External Input Signal Connections -
Page 6
The A-100NV will accept any one of three different types of external input signals; 4-20 mA, 0-10 VDC, or frequency. Two types of frequency inputs, AC sine waves (magnetic coils type outputs) and Digital Square waves (Hall Effect signals, contact closures), are acceptable. A jumper plug located on the circuit board is factory pre-set for AC sine wave signals, the jumper must be re-positioned when digital square wave signals are being used. (See Fig. 4.4, page 7, “Hz input jumper settings”)
All wiring connections are to be made inside of the junction box located on the side of the A-100NV. A liquid-tite connector is supplied and should be used for the external signal cable. The signal input wires are color coded to the type of signal being used.
INPUT SIGNAL TYPE
4-20 mA
0-10 V DC
AC sine wave, Digital square wave
POSITIVE
WIRE COLOR
BLUE
ORANGE
WHITE
NEGATIVE
WIRE COLOR
BLACK BLACK BLACK
FIG. 4.3 WIRING CHART - INPUT SIGNAL WIRE COLORS
Page 7
Page 7
A-100N
SIGNAL INPUT MODES / FUNCTIONS & WIRING COLOR CODES
INPUT MODE / FUNCTION
MANUAL
4-20 mA 0-10 VDC
FREQUENCY
ALARM RELAY
FLOW VERIFICATION SENSOR
(Digital square waves) MOTOR ON SIGNAL
EXTERNAL INPUT CABLE
ACCEPTABLE CABLE JACKET RANGE:
RED (+20VDC) BLACK (Ground)
BLUE (4-20 mA input) ORANGE (0-10 VDC input) WHITE (frequency input)
YELLOW (verification sensor input) BROWN (motor-on contact output)
PURPLE X2 (alarm relay contacts)
.118 - .255 INCH .( 3,0 - 6,5 MM)
JUNCTION BOX
WIRES REQUIRED
NO CONNECTIONS
BLUE (+) & BLACK (-)
ORANGE (+) & BLACK (-)
WHITE (+) & BLACK (-)
PURPLE & PURPLE
RED (+ 20VDC) & BLACK (-) & YELLOW (signal)
BROWN (+) & BLACK (-)
(open - factory default)
AC LINE VOLTAGE SETTINGS
Hz INPUT JUMPER SETTINGS
Located under connector
AC sine waves
Jumper Not Installed
Digital square waves
Jumper Installed
INPUT SIGNAL CONNECTOR
7 wire bundle
LIQUID-TIGHT CONNECTOR
ALARM OUTPUT
(CONTACT CLOSURE)
connect 2-conductor plug to either
normally open (NO) (factory default)
or normally closed (NC) side of receptacle.
1 AMP MAX @ 125VAC (24VDC)
TUBE FAILURE SENSOR PROBE INPUT
Connect 2-conductor plug to receptacle.
2 Grey wires connect to pump head sensors.
RED (+)
DC
MOTOR
BLACK (-)
Ground (green)
MOTOR RED (+)
MOTOR
BLACK (-)
NC NO
AC LINE
NEUTRAL
10
1
220
10
1
E B
TS
RO P
1 AMP
250V AC
AC LINE
HOT
Earth Ground (green)
230 VAC
One Jumper Installed
on center position
(ends open)
Two Jumpers Installed
THERMAL SWITCH
.187 push tab connectors
2 conductors
PROTECTOR FUSE
1 Amp, 250 Volt AC
(Littlefuse #239001
or Equivalent)
Hot
Common
Input
Power
115 VAC
on end positions
(no open pins)
AC
FIG. 4.4 WIRING DIAGRAM - MODEL V CIRCUIT BOARD
Page 8
A-100N
Page 8
4.3 How To Install the Tubing and Fittings
4.3.1 Inlet Tubing - Locate the inlet fitting of the Pump Tube, see fig 4.6. Remove the tube nut. Push the
clear PVC suction tubing onto the compression barb of the fitting. Use the tube nut to secure the tube. Hand tighten only.
4.3.2 Strainer -Trim the inlet end of the suction tubing so that the strainer
will rest approximately two inches from the bottom of the solution tank. This will prevent sediment from clogging the strainer. Slip the ceramic weight over the end of the suction tube. Press the strainer into the end of the tube. Secure the ceramic weight to the strainer. Drop the strainer into the solution tank.
4.3.3 Outlet Tubing - Locate the outlet fitting of the Pump Tube, see fig
4.6. Remove the tube nut. Push the opaque outlet (discharge) tubing onto the compression barb of the fitting. Use the tube nut to secure the tube. Hand tighten only. Trim the other end of the outlet tube leaving only enough slack to connect it to the injection/check valve fitting. Increasing the outlet tube length increases the pressure at the pump tube, particularly with viscous fluids.
Tubing Suction 3/8"
Ceramic Weight # 90008-068
Foot Strainer # 90002-200
Keep the outlet tube as short as possible.
Outlet Adapter
Pump Head
VARIABLE SPEED PUMP
MODE
% SPEED
1000
ALARM
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
2 - 4-20mA
1 - MANUAL
1
VDC
mA Hz
SERVICE
DIGIT MODE
DISPLAY
3 - 0-10VDC 4 - PULSE (Hz)
RUN PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
FIG. 4.5
Inlet Adapter
FIG. 4.6
Page 9
Page 9
4.3.4 Injection/Check Valve Fitting Installation - The Injection/Check valve fitting is designed to install
directly into either 1/4” or 1/2” female pipe threads. This fitting will require periodic cleaning, espe­cially when injecting fluids that calcify such as sodium hypochlorite. These lime deposits and other build ups can clog the fitting increasing the back pressure and interfering with the check valve operation. See section 7.0.
Install the Injection/Check valve directly into the piping system. Do not use a pipe stud with a tee for insertion of the injection valve. The solution must inject directly into the flow stream.
Use Teflon thread sealing tape on the pipe threads. Push the opaque outlet (discharge) tubing onto the compression barb of the Injection/Check valve fitting. Use the tube nut to secure the tube. Hand tighten only.
A-100N
FIG. 4.7 INJECTION FITTING INSTALLATION AND EXPLODED VIEW
Page 10
A-100N
5.0 How To Operate The A-100NV
5.1 Description of Pump Output Adjustment Controls -
Open the control panel door by sliding the upper and lower slide clamps to the left. FIG. 5.2
!
RUN/STANDBY Button -
4
Press to start and stop the pump. The ARROW next to the word RUN will light when in the run mode. The ARROW next to the word
STAND-BY will blink when in the stand-by mode.
4
Press to clear ALARM.
4
When pressed with the FIELD Button, initiates a 99 second prime cycle which temporarily overrides the mode setting and runs the pump motor at 100% speed. The ARROW next to the word PRIME will blink.
4
When pressed with the DIGIT button, resets the 500 hour service warning timer to zero.
4
When pressed with the MODE button, initiates the programming mode. The ARROW next to the word PROGRAM will blink.
!
FIELD Button -
4
In the programming mode, selects the digit to be changed.
VARIABLE SPEED PUMP
1
VDC
mA Hz
SERVICE
DIGIT MODE
PROGRAM
3 - 0-10VDC 4 - PULSE (Hz)
RUN
STANDBY
1 - MANUAL
MODE
% SPEED
1000
ALARM
FIELD
PRIME
RESET SERVICE
INPUT MODES
2 - 4-20mA
Page 10
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
DISPLAY
!
DIGIT Button -
4
In the programming mode, increases the selected digit.
4
When pressed with the MODE Button, toggles the display from % motor speed to input signal value.
!
MODE Button -
4
Used to select one of four operating modes.
Mode 1 - Manual Adjustment (external input disabled) Mode 2 - 4-20mA input Mode 3 - 0-10VDC input Mode 4 - Frequency (Hz) input
VARIABLE SPEED PUMP
MODE
mA Hz
% SPEED
1000
ALARM
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
2 - 4-20mA
1 - MANUAL
RUN
1
PROGRAM
VDC
STAND-BY PRIME MINIMUM
SERVICE
MAXIMUM
DIGIT MODE
DISPLAY
3 - 0-10VDC 4 - PULSE (Hz)
FIG. 5.1
Slide both top & bottom clamps to the left only far enough
(as shown) to open the control cover
FIG. 5.2
SLIDE CLAMP
Page 11
Page 11
5.2 OPERATING MODE 1 - Output adjusted manually -
In this mode, the pump’s motor speed is adjusted manually using the front panel touch pad. The motor speed can be adjusted from 0-100%. To adjust the speed:
4
Set the pump for mode 1. Press the MODE button until MODE 1 is shown on the LCD display. The %SPEED icon will light. The large 3-DIGIT LCD will indicate the currently programmed percentage of speed.
4
Enter the programming mode. At the same time, press the RUN/STANDBY button and the MODE button. A blinking ARROW will point to the word PROGRAM indicating the program mode has been activated.
4
Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The arrow next to the word PROGRAM will disappear.
[
NOTE: If while in the program mode no buttons are pressed within 20 seconds, the circuitry will automatically return to the run mode, without saving changes.
A-100N
RUN MODE 1
MODE
% SPEED
1
100
PROGRAM MODE 1
constant speed % setting
MODE
% SPEED
1
000
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
5.3 -
OPERATING MODE 2 - Output adjusted by 4-20 mA input signal
In this mode, the pump’s motor speed is adjusted automatically based on the value of the 4-20 mA input signal. Any motor speed can be assigned to either the minimum or maximum milliamp input values. However, the programmed
minimum mA value must be less than the programmed maximum mA value.
The ALARM and SERVICE icons will blink if the programming is in error. To assign the minimum and maximum motor speed and the minimum and maximum mA input signal values:
4
Set the pump for mode 2. Press the MODE button until MODE 2 is shown on the LCD display. The %SPEED or mA icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the current mA input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY and MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
4
Enter the motor speed at the minimum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon will blink indicating the minimum mA value is ready to be programmed. The currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum mA input signal value. Note: this value must be less than the maximum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
RUN MODE 2
MODE
2
mA
04.0
PROGRAM MODE 2
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 2
minimum input value
MODE
mA
04.0
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
RUN
2
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
2
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
Page 12
A-100N
4
Press the mode button. The Ma icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon will blink indicating the maximum mA value is ready to be programmed. The currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum mA input signal value. Note: this value must be greater than the minimum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected..
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The PROGRAM arrow will disappear.
Page 12
PROGRAM MODE 2
% speed at the maximum input
RUN
MODE
% SPEED
PROGRAM MODE 2
MODE
20.0
2
100
maximum input value
2
mA
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
Example 1
4 mA = 0% OUTPUT
20 mA = 100% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
6
8
4
Milliamp input (mA)
4 mA = 0% OUTPUT
20 mA = 75% OUTPUT
100
75
12
10
Example 3
MODE 2 PROGRAMMING EXAMPLES
Example 2
4 mA = 100% OUTPUT
20 mA = 0% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
6
14
16
18
20
4
Milliamp input (mA)
4 mA = 20% OUTPUT
20 mA = 50% OUTPUT
100
75
8
12
10
Example 4
14
16
18
20
50
25
Pump Motor Speed (%)
0
6
8
4
Milliamp input (mA)
10
12
14
16
18
20
50
25
Pump Motor Speed (%)
0
6
8
4
10
Milliamp input (mA)
12
14
16
18
20
Page 13
Page 13
5.4 - OPERATING MODE 3 - Output adjusted by 0-10VDC input signal
In this mode, the pump’s motor speed is adjusted automatically based on the value of the 0-10VDC input signal. Any motor speed can be assigned to either the minimum or maximum DC input signal values. However, the programmed
minimum VDC value must be less than the programmed maximum VDC value. The ALARM and SERVICE icons will blink if the programming is in
error. To assign the minimum and maximum motor speed and the minimum and maximum VDC input signal values:
4
Set the pump for mode 3. Press the MODE button until MODE 3 is shown on the LCD display. The % SPEED or VDC icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the VDC input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY and MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
4
Enter the motor speed at the minimum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the VDC icon will blink indicating the minimum VDC value is ready to be pro­grammed. The currently programmed minimum value is shown on the 3- DIGIT LCD.
4
Enter the minimum VDC input signal value. Note: this value must be less than the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The VDC icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the VDC icon will blink indicating the maximum VDC value is ready to be pro­grammed. The currently programmed maximum value is shown on the 3- DIGIT LCD.
4
Enter the maximum VDC input signal value. Note: this value must be greater than the minimum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The PROGRAM arrow will disappear.
A-100N
RUN MODE 3
MODE
3
VDC
00.0
PROGRAM MODE 3
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 3
minimum input value
MODE
VDC
00.0
PROGRAM MODE 3
% speed at the maximum input
MODE
% SPEED
100
PROGRAM MODE 3
maximum input value
MODE
VDC
10.0
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
RUN
3
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
3
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
3
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
3
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
Page 14
A-100N
5.5 - OPERATING MODE 4 - Output adjusted by frequency (Hz) input signal
In this mode, the pump’s motor speed is adjusted automatically based on the frequency (Hz) of the input signal. Any motor speed can be assigned to either the minimum or maximum Hz input signals. However, the programmed minimum
Hz value must be less than the programmed maximum Hz value. The ALARM and SERVICE icons will blink if the programming is in error. To assign
the minimum and maximum motor speed and the minimum and maximum Hz input signal values:
4
Set the pump for mode 4. Press the MODE button until MODE 4 is shown on the LCD display. The % SPEED or Hz icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the Hz input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY and MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
4
Enter the motor speed at the minimum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the Hz icon will blink indicating the minimum Hz value is ready to be programmed. The currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum Hz input signal value. Note: this value must be less than the maximum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The Hz icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
4
Enter the motor speed at the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the Hz icon will blink indicating the maximum Hz value is ready to be programmed. The currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum Hz input signal value. Note: this value must be greater than the minimum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. Programming is complete.
4
To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The PROGRAM arrow will disappear.
Page 14
RUN MODE 4
MODE
4
000
PROGRAM MODE 4
% speed at the minimum input
MODE
% SPEED
000
PROGRAM MODE 4
minimum input value
MODE
000
PROGRAM MODE 4
% speed at the maximum input
MODE
% SPEED
82.5
PROGRAM MODE 4
minimum input value
MODE
628
RUN
PROGRAM
Hz
STAND-BY PRIME MINIMUM MAXIMUM
RUN
4
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
4
PROGRAM
Hz
STAND-BY PRIME MINIMUM MAXIMUM
RUN
4
PROGRAM STAND-BY PRIME MINIMUM MAXIMUM
RUN
4
PROGRAM
Hz
STAND-BY PRIME MINIMUM MAXIMUM
Page 15
Page 15
Example 1
0 Hz = 0% OUTPUT
1000 Hz = 100% OUTPUT
100
MODE 4 PROGRAMMING EXAMPLES
Example 2
0 Hz = 100% OUTPUT
1000 Hz = 0% OUTPUT
100
A-100NA-100N
Example 3
0 Hz = 10% OUTPUT
275 Hz = 75% OUTPUT
100
75
50
25
Pump Motor Speed (%)
0
200
0
Frequency input (Hz)
400
600
800
1000
75
50
25
Pump Motor Speed (%)
0
6.0 ALARMS -
6.1 Tube Failure Detection System (TFD)
The A-100NV is equipped with a Tube Failure Detection System which is designed to stop the pump and provide a contact closure output in the event the pump tube should rupture and chemical enters the pump head. This patent-pending system is capable of detecting the presence of a large number of chemicals including Sodium Hypochlorite (chlorine), Hydrochloric (muriatic) Acid, Sodium Hydroxide, and many others. The system will not be triggered by water (rain, condensation, etc.) or silicone oil (roller and tubing lubricant).
Confirm Chemical Detection -
To determine if your chemical will be detected by the system, remove the pump tube and roller assembly, place a small amount of the chemical in the bottom of the pump head, just enough to cover the sensors, and turn on the pump. If the TFD system detects the chemical, the pump will stop after a five second confirmation period and the ALARM icon will light on the display. If the TFD system does not detect the chemical, the pump will continue to run after the confirmation period. Carefully clean the chemical out of the pump head being sure to remove all traces of chemical from the sensor probes. Press the RUN/STAND-BY button to clear the alarm condition and restart the pump.
400
600
200
0
Frequency input (Hz)
800
1000
75
50
25
Pump Motor Speed (%)
0
200
0
Frequency input (Hz)
600
400
RUN MODE 1
MODE
% SPEED
000
ALARM
800
1
1000
RUN PROGRAM STAND-BY
PRIME MINIMUM MAXIMUM
To Disable the Chemical Detection -
If the TFD system cannot detect your chemical, no further action is necessary. However, if there is a concern about possible false triggering by chemical contaminants, the system can be disabled by un­plugging the sensor probe wires from the circuit board. See Fig. 4.4, page 7 for the sensor probe’s plug location on the internal circuit board.
Contact Closure Alarm Output Signal -
A contact closure output is provided with the TFD system. The output can be configured for normally open (factory default) or normally closed operation by properly positioning the connector plug on the circuit board (See fig. 4.4, page 7). The contacts will change states while an alarm condition exists. Two wires (purple), located in the junction box, are provided for connections. 20mA minimum / 1 amp maximum load @ 125V AC /24V DC.
Page 16
A-100N
7.0 How to Maintain the A-100NV
7.1 Routine Inspection and Maintenance
The A-100NV requires very little maintenance. However, the pump and all accessories should be checked weekly. This is especially important when pumping chemicals. Inspect all components for signs of leaking, swelling, cracking, discoloration or corrosion. Replace worn or damaged components immediately.
Cracking, crazing, discoloration and the like during the first week of operation are signs of severe chemical attack. If this occurs, immediately remove the chemical from the pump. Determine which parts are being attacked and replace them with parts that have been manufactured using more suitable materials. The manufacturer does not assume responsibility for damage to the pump that has been caused by chemical attack.
7.2 How to Clean and Lubricate the A-100NV
Page 16
The A-100NV will require occasional cleaning and lubricating. The amount will depend on the severity of service.
]
When changing the pump tube assembly, clean the pump head chamber, TFD sensors, roller assembly and pump head cover.
]
The pump head cover bearing may require grease periodically. Apply a small amount of grease (Aeroshell aviation grease #5 or equivalent) when necessary.
]
Silicone oil ONLY may be used on the roller assembly and tube assembly.
]
The injection/check valve assembly must be cleaned periodically, especially when injecting fluids that calcify such as sodium hypochlorite. These lime deposits and other build ups can clog the fitting increasing the back pressure which can interfere with the check valve operation and possibly damage the fitting and/or the pump. See section 4.3.4. Fig. 4.7.
]
Periodically clean the suction strainer. Fig.4.5.
]
Periodically inspect the air vents located under the motor compartment and on the rear panel. Clean if necessary.
7.3 500 Hour Service Warning Timer
The A-100NV is equipped with a service warning timer. After 500 hours of accumulated running time, the SERVICE icon will light. This is a reminder that the pump tube is nearing its minimum life expec­tancy and should be replaced. Your actual tube life will depend on many factors such as the chemical
used, back pressure, temperature, viscosity, and motor RPM.
Simultaneously press the RUN/STANDBY and DIGIT buttons to reset the service timer to zero. Note: Pressing the FIELD and DIGIT buttons will display the currently accumulated time value.
Page 17
Page 17
7.4 How to Replace the Pump Tube
The pump tube assembly will eventually break if not replaced. The tube has been designed for a minimum service life of 500 hours. However, the life of the tube is affected by many factors such as the type of chemical being pumped, the amount of back pressure, the motor RPM, temperature and others. The pump tube assembly must be inspected and replaced regularly.
After replacing the pump tube, press the RUN/STANDBY button and the DIGIT button at the same time to reset the service warning timer.
7.4.1 How to Remove the Old Pump Tube
The pump roller assembly spins in a counter clockwise direction. The pump head inlet (suction) side is located at the bottom of the pump and the outlet (discharge) is located at the top of the pump head.
A-100N
7.4.1.1 Release any pressure that may be in the
discharge tubing.
Outlet Adapter
Pump Head
7.4.1.2 Disconnect the suction and discharge tubes
from the pump tube.
7.4.1.3 Remove the pump head cover.
7.4.1.4 With the pump running, pull the inlet fitting
out of the pumphead. Guide the tube counter clockwise away from the rollers. Pull the
VARIABLE SPEED PUMP
MODE
mA Hz
% SPEED
1000
ALARM
SERVICE
FIELD
RUN
STANDBY
PRIME
RESET SERVICE
PROGRAM
INPUT MODES
3 - 0-10VDC 4 - PULSE (Hz)
2 - 4-20mA
1 - MANUAL
1
PROGRAM
VDC
STAND-BY
MINIMUM MAXIMUM
DIGIT MODE
DISPLAY
RUN
PRIME
outlet fitting out of the pump head.
7.4.2 How to Install a New Pump Tube
Inlet Adapter
FIG. 7.1
Be sure the pump head chamber is clean and free of any debris. Remove and inspect the roller assem­bly. Be sure the rollers spin freely. If required, apply a small amount of grease to the pump head cover bearing. Silicone oil only may be used on the tubing and rollers. See section 7.2.
6.4.2.1 With the pump running, insert the inlet (suction) side of the Pump Tube fitting into the lower retaining
slot in the pump head. Fig. 7.2.
6.4.2.2 Carefully guide the Pump Tube into the pump head. Stretch the tube slightly and insert the outlet
(discharge) fitting into the upper retaining slot in the pump head. Fig. 7.3.
6.4.2.3 Place the clear cover on the pump head and secure with three screws.
FIG. 7.2 FIG. 7.3
Page 18
A-100N
Page 18
Replacement Parts Drawing
20
BRUSH KIT
1
4
5
54
53
7
52
9
56
55
2
3
10
18
22
6
8
21
42
23
2
25
24
26
17
27
12
19
z)
SE (H
MODE
PUL
4 =
R
IT
DIG
0-10 VDC
ING TIME
3 =
T MODE
RESET
E
LD
LIFE WAR
INPU
E
= 4-20mA
FIE
TUBE
L 2
PRIM
99 SEC.CYCL
ANUA
1 = M
STANDBY
3
11
41
14
28
13
29
32
33
OPTIONAL
QUICKCONNECT
35
30
40
31
15
16
36
46
34
37
49
39
38
45
48
Page 19
Page 19
A-100N
A-100N PARTS LIST
A-008-2 Gearbox, 30 Rpm 1
A-008-3 Gearbox, 45 Rpm 1
A-008-4 Gearbox, 60 Rpm 1
A-008-5 Gearbox, 125 Rpm 1
26 A-008-1 Gearbox, 14 Rpm 1
27 76001-488 Pumphead, A-100N w/TFD sensors 1
28 C-324N Screw, Pumphead, 10-32 X .50 Phil Pan Black 4
A-002N-6T Pump Tube, .37 O.D., Compression Barb Type 1
A-002N-7T Pump Tube, .43 O.D., Compression Barb Type 1
29 A-031 Spacer, Rotor 1
30 A-002N-4T Pump Tube, .25 O.D., Compression Barb Type 1
A-002N-6Q Pump Tube, .37 O.D., Quick-connect W/ O-ring 1
31 C-330-6 Nut, Tube Compression Type, .37 O.D. Tubing 2
32 A-002N-4Q Pump Tube, .25 O.D., Quick-connect W/ O-ring 1
33 90003-007 O-ring, Quick-connect Pump Tubes, Viton 2
34 90008-299 Adapter, Quick-connect Inlet, .37 O.D. Tube 1
35 90008-300 Adapter, Quick-connect Outlet, .37 O.D. Tube 1
36 C-335-6 Tubing, Outlet, .37 O.D. X 5ft, Polyethylene 1
37 C-334-6 Tubing, Inlet, .37 O.D. X 5ft, Clear PVC 1
38 C-346 Weight, Inlet Tubing, Ceramic 1
71000-350 Roller Assembly -7 tubes (black rollers) 1
39 C-342-2 Strainer, Inlet Tube, Polypropylene 1
40 71000-159 Roller Assembly -4, -6 tubes (white rollers) 1
41 90012-245 Label, A-100NV front panel controls 1
42 90011-074 Washer, #8 splitlock 2
45 71000-156 Cover, Pumphead With Sleeve Bearing 1
46 76001-003 Bearing, Sleeve, Pumphead Cover 1
48 90011-160 Screw, Pumphead Cover, 8-32 X .62 Cap 3
49 A-014HD-6A Injection Valve Assy, .5-.25 MPT X .37OD Tube 1
52 90007-515 Bushing, Junction Box Connector, Alum. 1
53 76001-254 Junction Box A-100NV 1
54 90011-129 Screw, Cover, 6-32 X .25 Phil Pan SS Black 2
55 71000-133 Cover, Junction Box with Gasket and Label 1
56 90008-199 Connector Liquid-tight 1
A-023N-V-230 Circuit board A-100NV 220V/230V 1
Item Part No Description Qty Item Part No Description Qty
1 71000-489 Enclosure Back Plate With Gasket, Valox 1
2 90011-094 Washer, Mounting, #10 Stainless 2
3 90011-091 Mounting Screw, #10 X 1.0” Phillips Steel 4
4 76001-001 Tubing Spacer A-100N digital 2
5 90010-036 Wire Nut, Blue 1
6 90006-580 Gasket, Enclosure Back Plate 1
7 A-023N-V-115 Circuit board A-100NV 115V 1
71000-176 Power Cord, 220v50hz, Digital Models 1
71000-177 Power Cord, 230v60hz, Digital Models 1
8 90010-235 Fuse, A-100NV Circuit Board, 1A 250VAC 1
9 71000-175 Power Cord, 115v60hz, Digital Models 1
10 70000-589 Cord Inlet Bushing 1
70002-251 Gearmotor, 30 Rpm, 24V DC 1
70002-252 Gearmotor, 45 Rpm, 24V DC 1
70002-253 Gearmotor, 60 Rpm, 24V DC 1
70002-254 Gearmotor, 125 Rpm, 24V DC 1
11 90003-559 Mounting Feet, Rubber 4
12 76001-000 Slide Clamp, Enclosure Rear 1
13 76000-999 Slide Clamp, Enclosure Front 1
14 76001-253 Enclosure A-100NV 1
15 90006-579 Gasket, Enclosure Front 1
16 90002-191 Door, Electronic Controls Cover 1
17 70002-250 Gearmotor, 14 Rpm, 24V DC 1
18 90010-246 Wire set w/plug, Alarm relay 1
19 90010-245 Wire set w/plug, TFD sensor 1
N/s 90010-247 Wire set w/plug, input signals 1
20 C-1814N-4 Motor Brush kit (2 ea), 24V DC 1
21 90011-023 Screw, Motor, 8-32 x .50 2
22 90010-244 Motor, 24V DC 1
23 90011-024 Screw, Green Ground, 8-32 x .25 1
24 90011-078 Washer, Ground Screw, #8 Star 1
25 90010-222 Wire, Motor ground, Digital Timers, Green 1
Page 20
LIMITED WARRANTY
Your new pump is a quality product and is warranted to be free of defects as set down in this policy. All parts, including rubberized goods, and labor are covered under warranty for 90 days from the date of purchase. Used peristaltic pump tube assemblies are not warranted. Parts, excluding rubberized goods, are covered under warranty for 12 months from the date of purchase. Warranty coverage does not include damage to the pump that results from misuse, carelessness, abuse or alteration. Only the repair or the replacement of the pump is covered. Blue-White Industries does not assume responsibility for any other loss or damage. Warranty status is determined by the pump’s serial label and the sales invoice or receipt. The serial label must be on the pump and the pump must be accompanied by the sales invoice or receipt to obtain warranty coverage. The warranty status of the pump will be verified by Blue-White or a factory authorized service center.
Please be advised; injection and metering devices are not intended as a means of treating water to render it suitable for human consumption. When used as hypochlorinators, they are meant to destroy bacteria and algae contamination, before it’s removal by filtration. Acid and soda injectors are used for PH control (balance). Blue-White injectors are factory tested with water only for pressure and performance. Installers and operators of
these devices must be well informed and aware of the precautions to be taken when injecting various chemicals -especially those considered hazardous or dangerous.
Should it become necessary to return an injector for repair or service, you must attach information regarding the chemical used as some residue may be present within the unit which could be a hazard to service personnel. Blue-White Industries will not be liable for any damage that may result by the use of chemicals with their injectors and it’s components. Thank you.
PROCEDURE FOR IN WARRANTY REPAIR
Carefully pack the pump to be repaired, include the foot strainer and injection/check valve fitting. Enclose a brief description of the problem as well as the original invoice or sales receipt showing the date of purchase. The receipt will be returned with the unit. Prepay all shipping costs. COD shipments will not be accepted. Warranty service must be performed by the factory or an authorized service center. Damage caused by improper packaging is the responsibility of the sender.
AUTHORIZED SERVICE CENTERS
ARKANSAS FLORIDA MARYLAND BT Environmental, Inc AAA Electric Motor Services Century Pool Service, Inc
Bill Thomason 1131 N.E. 45th Street 5020 Nicholson Court, #201 225 Castleberry Street Ft. Lauderdale, FL 33334 Kensington, MD 20895 Hot Springs, AR 71901 305-772-7501 301-231-8999 501-624-3837
CALIFORNIA (NORTHERN) 2021 Curry Ford Road
Howard E. Hutching company (Repair Center)
7190 Penryn Plaza Penryn, CA 95663
Pool-Tech, Inc.
401 Sunset Dr., Suite A. Antioch, CA 94509 925-754-2424
Swimco Electric Co.
753 Camden Avenue Campbell, CA 95008 408-378-2607
CALIFORNIA (SOUTHERN)
Blue-White Industries (Repair Center)
5422 Business Drive Huntington Bch. CA 92649 714-893-8529
COLORADO Denver Winpump
4845 Pontiac Street Commerce City, CO 80022 303-287-2884
CONNECTICUT Cronin-Cook & Associates
24 West Road Vernon, CT 06066 203-875-0544
All American Pool & Patio
Orlando, FL 32806 407-898-8722
Rice Pump & Motor Repair 702-384-4223 5740 N.W. 9 ave. Ft. Lauderdale FL 33309 NEW YORK 954-776-6049 Sherwood Specialties, Inc.
American Pump
7580-A W. Tennessee St. Tallahassee, FL 32304 850-575-9618
Jerry Lee Chemical Co. Southern Industrial Sales
3407 W. Old Fairfield Drive 1903 Herring Avenue Pensacola, FL 32505 Wilson, NC 27893 904-432-9929 919-237-2500
Picard Chemical
1670 S. Congress Avenue SOUTH DAKOTA W. Palm Beach, FL 33406 Son-Aqua Distributing 407-965-3434 Jim Robinson
V.J. Mini & Son, Inc. Rapid City, SD 57702 1581 N. Dixie Highway 605-343-7716 Pompano Beach, FL 33060 305-946-0920 TENNESSEE
ILLINOIS 307 3rd Avenue South
Mullarkey Associates (Repair Center)
12346 S. Keeler Ave. Alsip, IL 60658 708-597-5558
NEVADA Swim-In Enterprises, Inc.
1314 S. Main Street Las Vegas, NV 89104
412 Smith Street Rochester, NY 14608 716-546-1211
NORTH CAROLINA
2447 W. Main Street
Rock City Machine
Nashville, TN 37201 615-244-1371
TEXAS Alamo Water Refiners
13700 Hwy. 90 West San Antonio, TX 78245 512-677-8400
# 80000-381 Rev. 7/18/2003
Loading...