Blueridge BM24Y17, BM12Y19, BM18Y19, BM09Y18 User Manual

4 (1)

Installation Manual

19 SEER Single Zone

BM09Y18

BM12Y19

BM18Y19

BM24Y17

Table of Contents

Installation Manual

0

Safety Precautions...........................

4

1

Accessories........................................

6

2

Installation Summary - Indoor Unit........

8

3

Unit Parts..........................................

10

4 Indoor Unit Installation........

11

1.

Select installation location..........................

11

2.

Attach mounting plate to wall....................

12

3.

Drill wall hole for connective piping............

12

4.

Prepare refrigerant piping...........................

14

5.

Connect drain hose....................................

15

6.

Connect signal cable..................................

17

7.

Wrap piping and cables..............................

18

8.

Mount indoor unit.....................................

18

5 Outdoor Unit Installation...20

1.

Select installation location..................

20

2.

Install drain joint................................

21

3.

Anchor outdoor unit..........................

22

4.

Connect signal and power cables.......

23

6 Refrigerant Piping Connection........

25

A. Note on Pipe Length................................................

25

B. Connection Instructions –Refrigerant Piping.............

25

1.

Cut pipe..............................................................

25

2.

Remove burrs......................................................

26

3.

Flare pipe ends....................................................

 

4.

Connect pipes.....................................................

 

7 Air Evacuation...................

29

1.

Evacuation Instructions......................

29

2.

Note on Adding Refrigerant...............

30

8

Electrical and Gas Leak Checks........

31

9

Test Run............................................

32

10 European Disposal Guidelines........

34

11 Impedance Information..................

35

Safety Precautions

Read Safety Precautions Before Installation

Incorrect installation due to ignoring instructions can cause serious damage or injury.

The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

This symbol indicates that ignoring instructions may cause death or serious injury.

WARNING

This symbol indicates that ignoring instructions may cause moderate injury to your person, or damage to your unit or other property.

CAUTION

This symbol indicates that you must never perform the action indicated.

WARNING

Do not modify the length of the power supply cord or use an extension cord to power the unit.

Do not share the electrical outlet with other appliances. Improper or insufficient power supply can cause fire or electrical shock.

When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,

and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.

Do not allow children to play with the air conditioner. Children must be supervised around the unit at all times.

1.Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire.

2.Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire.

(In North America,installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.)

3.Contact an authorized service technician for repair or maintenance of this unit.

4.Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.

5.Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.

Page 4

WARNING

6.For all electrical work, follow all local and national wiring standards, regulations, and the

Installation Manual. You must use an independent circuit and single outlet to supply power. Do not connect other appliances to the same outlet. Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire.

7.For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock.

8.All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.

9.In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.

10.If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

11.This appliance can be used by children aged from 8 years and above and persons with reduced Physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

CAUTION

For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.

Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.

Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.

1.The product must be properly grounded at the time of installation, or electrical shock may occur.

2.Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.

Note about Fluorinated Gasses

1.This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.

2.Installation, service, maintenance and repair of this unit must be performed by a certified technician.

3.Product uninstallation and recycling must be performed by a certified technician.

4.If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.

5.When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

Page 5

Accessories

1

 

 

 

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.

Name

Shape

Quantity

Mounting plate

 

1

 

 

Clip anchor

 

5

Mounting plate fixing

 

5

screw ST3.9 X 25

 

 

 

Remote controller

 

1

Fixing screw for remote

 

2

controller holder ST2.9 x 10

 

 

Optional

 

 

Remote controller holder

 

Parts

 

 

 

 

1

Dry battery AAA.LR03

 

2

 

 

Seal

 

1

 

 

 

 

(for cooling & heating

 

 

models only)

Drain joint

 

 

Page 6

 

 

Name

Shape

Quantity

 

 

 

 

Owner’s Manual

 

Aurora Series

 

All Model Numbers

Owner’s manual

1

 

Installation Manual

Installation manual

Aurora Series

All Model Numbers

 

1

 

Remote controller

 

REMOTE CONTROLLER ILLUSTRATION

 

 

 

 

 

 

AIR CONDITIONER

 

 

 

 

illustration

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

IMPORTANT NOTE:

 

 

 

 

 

 

Read this manual carefully before installing

 

 

 

 

 

 

or operating your new air conditioning

 

 

 

 

 

 

unit. Make sure to save this manual for

 

 

 

 

 

 

future reference.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

 

Φ6.35( 1/4i n)

 

 

 

Connecting pipe

 

 

 

 

 

 

Φ9.52( 3/8in)

Parts you must purchase.

 

 

 

 

 

assembly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Φ9.52( 3/8in)

Consult the dealer about

 

 

 

 

 

 

the pipe size.

 

 

Gas side

 

Φ12.7( 1/2in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Φ16( 5/8in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Φ19( 3/4in)

 

 

 

 

 

 

 

 

 

 

Page 7

Installation

Overview

Installation Summary - Indoor Unit

2

 

 

1

 

 

 

15cm (5.9in)

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12cm

12cm

(4.75in)

(4.75in)

 

2.3m (90.55in)

 

 

 

Select Installation Location

 

Determine Wall Hole Position

(Page 11)

 

(Page 12)

3

4

Attach Mounting Plate

Drill Wall Hole

(Page 12)

(Page 12)

Page 8

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect Piping

 

 

 

Connect Wiring

Prepare Drain Hose

 

 

 

 

 

(Page 25)

 

 

 

 

 

(Page 17)

 

(Page 14)

8

Wrap Piping and Cable

(not applicable for some locations in the US ) (Page 18)

9

Mount Indoor Unit

(Page 18)

Installation

Overview

Page 9

Blueridge BM24Y17, BM12Y19, BM18Y19, BM09Y18 User Manual

Installation

Overview

Unit Parts

3

 

 

 

NOTE: The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

1

1

 

2

 

3

 

 

 

 

4

 

 

2

 

 

4

 

 

6

 

5

 

 

 

 

 

 

 

5

 

 

7

 

 

 

8

 

9 10

Air-break switch

3

6

7

8

11

11

 

1

 

 

2

 

 

Fig. 2.1

 

 

1

Wall Mounting Plate

5

Functional Filter (On Front of

9

Remote Controller

Main Filter - Some Units)

2

Front Panel

 

 

Remote controller Holder

6

Drainage Pipe

10

3

Power Cable (Some Units)

7

 

 

(Some Units)

Signal Cable

11

Outdoor Unit Power Cable

4

Louver

8

Refrigerant Piping

 

(Some Units)

NOTE ON ILLUSTRATIONS

Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.

Page 10

Indoor Unit Installation

4

 

 

 

Unit Indoor

Installation

Installation Instructions – Indoor

Unit

PRIOR TO INSTALLATION

Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.

Step 1: Select installation location

Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.

Proper installation locations meet the following standards:

Good air circulation

Convenient drainage

Noise from the unit will not disturb other people

Firm and solid—the location will not vibrate

Strong enough to support the weight of the unit

A location at least one meter from all other electrical devices (e.g., TV, radio, computer)

DO NOT install unit in the following locations:

Near any source of heat, steam, or combustible gas

Near flammable items such as curtains or clothing

Near any obstacle that might block air circulation

Near the doorway

In a location subject to direct sunlight

NOTE ABOUT WALL HOLE:

If there is no fixed refrigerant piping:

While choosing a location, be aware that you should leave ample room for a wall hole (see

Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units.

The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to both the left and right.

Page 11

Refer to the following diagram to ensure proper distance from walls and ceiling:

15cm (5.9in) or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12cm (4.75in)

 

12cm (4.75in)

or more

 

or more

 

Unit Indoor

Installation

2.3m (90.55in) or more

Fig. 3.1

Step 2: Attach mounting plate to wall

Step 3: Drill wall hole for connective piping

The mounting plate is the device on which you will mount the indoor unit.

1.Remove the screw that attaches the mounting plate to the back of the indoor unit.

2.Place the mounting plate against the wall in a location that meets the standards in the Select Installation Location step. (See Mounting Plate Dimensions for detailed information on mounting plate sizes.)

3.Drill holes for mounting screws in places that:

have studs and can support the weight of the unit

correspond to screw holes in the mounting plate

4.Secure the mounting plate to the wall with the screws provided.

5.Make sure that mounting plate is flat against the wall.

NOTE FOR CONCRETE OR BRICK WALLS:

If the wall is made of brick, concrete, or similar material, drill 5mm-diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors provided. Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors.

You must drill a hole in the wall for refrigerant piping, the drainage pipe, and the signal cable that will connect the indoor and outdoor units.

1.Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions on the next page to help you determine the optimal position. The wall hole should have a 65mm (2.5in) diameter at least, and at a slightly lower angle to facilitate drainage.

2.Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower

than the indoor end by about 5mm to 7mm (0.2-0.27in). This will ensure proper water drainage. (See Fig. 3.2)

3.Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

CAUTION

When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

Page 12