Test Run............................................ 32
10
European Disposal Guidelines........ 34
11
Impedance Information.................. 35
Safety Precautions
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury.
The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
This symbol indicates that ignoring instructions may cause death or serious
WARNING
CAUTION
injury.
This symbol indicates that ignoring instructions may cause moderate injury
to your person, or damage to your unit or other property.
This symbol indicates that you must never perform the action indicated.
WARNING
Do not modify the length of the power supply cord or use an extension cord to power the unit.
Do not
can cause fire or electrical shock.
When connecting refrigerant piping, do not
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
Do not
unit at all times.
1.
Installation must be performed by an authorized dealer or specialist. Defective installation can
cause water leakage, electrical shock, or fire.
2.
Installation must be performed according to the installation instructions. Improper installation can
cause water leakage, electrical shock, or fire.
(In North America,installation must be performed in accordance with the requirement of NEC and
CEC by authorized personnel only.)
Contact an authorized service technician for repair or maintenance of this unit.
3.
Only use the included accessories, parts, and specified parts for installation. Using non-standard
4.
parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
share the electrical outlet with other appliances. Improper or insufficient power supply
let substances or gases other than the specified
allow children to play with the air conditioner. Children must be supervised around the
5.
Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot
support the unit’s weight, or the installation is not done properly, the unit may drop and cause
serious injury and damage.
Page 4
WARNING
6.
For all electrical work, follow all local and national wiring standards, regulations, and the
Installation Manual. You must use an independent circuit and single outlet to supply power. Do
not connect other appliances to the same outlet. Insufficient electrical capacity or defects in
electrical work can cause electrical shock or fire.
7.
For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to
prevent external forces from damaging the terminal. Improper electrical connections can overheat
and cause fire, and may also cause shock.
8.
All wiring must be properly arranged to ensure that the control board cover can close properly. If
the control board cover is not closed properly, it can lead to corrosion and cause the connection
points on the terminal to heat up, catch fire, or cause electrical shock.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed
9.
air-conditioning units is highly recommended.
10.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
11.
This appliance can be used by children aged from 8 years and above and persons with reduced
Physical, sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
CAUTION
For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of
any combustible materials.
Do not
gas accumulates around the unit, it may cause fire.
Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit.
1.
The product must be properly grounded at the time of installation, or electrical shock may occur.
2.
Install drainage piping according to the instructions in this manual. Improper drainage may cause
water damage to your home and property.
Note about Fluorinated Gasses
1.
This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas
and the amount, please refer to the relevant label on the unit itself.
2.
Installation, service, maintenance and repair of this unit must be performed by a certified
technician.
3.
Product uninstallation and recycling must be performed by a certified technician.
4.
If the system has a leak-detection system installed, it must be checked for leaks at least every 12
months.
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly
recommended.
install the unit in a location that may be exposed to combustible gas leaks. If combustible
Page 5
Accessories
1
The air conditioning system comes with the following accessories. Use all of the installation
parts and accessories to install the air conditioner. Improper installation may result in water
leakage, electrical shock and fire, or cause the equipment to fail.
Name
Mounting plate
Clip anchor
Mounting plate fixing
screw ST3.9 X 25
Remote controller
Fixing screw for remote
controller holder ST2.9 x 10
Remote controller holder
ShapeQuantity
1
5
5
1
2
Optional
Parts
Dry battery AAA.LR03
Seal
Drain joint
Page 6
1
2
1
(for cooling & heating
models only)
Name
SPLIT-TYPE ROOM AIR CONDITIONER
Owner’s Manual
Aurora Series
All Model Numbers
ShapeQuantity
Owner’s manual
Installation manual
Remote controller
illustration
Connecting pipe
assembly
CS78421-548-754
IMPORTANT NOTE:
Read this manual carefully before installing
or operating your new air conditioning
unit. Make sure to save this manual for
future reference.
SPLIT-TYPE ROOM AIR CONDITIONER
Installation Manual
Aurora Series
All Model Numbers
IMPORTANT NOTE:
Read this manual carefully before installing
or operating your new air conditioning
unit. Make sure to save this manual for
future reference.
AIR CONDI TIONE R
REMOTE CONTROL LER IL LUSTR ATION
IMPORTANT NOTE:
Read this manual carefully before installing
or operating your new air conditioning
unit. Make sure to save this manual for
future reference.
Liquid side
Gas side
CS78421-548-754
6.35( 1/ 4 i n)
Φ
Φ
9.52( 3/ 8in)
Φ
9.52( 3/ 8in)
Φ
12.7( 1/ 2in)
Φ
16( 5/8in)
1
1
1
Parts you must purc hase.
Consult the dealer about
the pipe size.
Φ
19( 3/4in )
Page 7
Installation
Overview
Installation Summary - Indoor Unit
12
12cm
(4.75in)
2.3m (90.55in)
15cm (5.9in)
12cm
(4.75in)
2
Select Installation Location
(Page 11)
34
Determine Wall Hole Position
(Page 12)
Page 8
Attach Mounting Plate
(Page 12)
Drill Wall Hole
(Page 12)
567
Installation
Overview
8
Connect Piping
(Page 25)
Connect Wiring
(Page 17)
Wrap Piping and Cable
(not applicable for some locations in the US )
(Page 18)
Prepare Drain Hose
(Page 14)
9
8
STEP
Mount Indoor Unit
(Page 18)
Page 9
Installation
Overview
Unit Parts
3
NOTE: The installation must be performed in accordance with the requirement of local and
national standards. The installation may be slightly different in different areas.
1
2
4
5
3
2
6
7
8
4
5
9
11
10
1
Air-break switch
3
6
7
8
11
(1)(2)
Fig. 2.1
Wall Mounting Plate
1
2
Front Panel
Power Cable (Some Units)
3
Louver
4
Functional Filter (On Front of
5
Main Filter - Some Units)
6
Drainage Pipe
7
Signal Cable
8
Refrigerant Piping
Remote Controller
9
Remote controller Holder
10
(Some Units)
Outdoor Unit Power Cable
11
(Some Units)
NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The actual shape of your indoor
unit may be slightly different. The actual shape shall prevail.
Page 10
Indoor Unit Installation
4
Indoor Unit
Installation
Installation Instructions – Indoor
Unit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the
label on the product box to make sure that the
model number of the indoor unit matches the
model number of the outdoor unit.
Step 1: Select installation location
Before installing the indoor unit, you must
choose an appropriate location. The following
are standards that will help you choose an
appropriate location for the unit.
Proper installation locations meet the
following standards:
Good air circulation
Convenient drainage
Noise from the unit will not disturb other
people
Firm and solid—the location will not vibrate
Strong enough to support the weight of the
unit
DO NOT install unit in the following
locations:
Near any source of heat, steam, or
combustible gas
Near flammable items such as curtains or
clothing
Near any obstacle that might block air
circulation
Near the doorway
In a location subject to direct sunlight
NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, be aware that you
should leave ample room for a wall hole (see
Drill wall hole for connective piping step)
for the signal cable and refrigerant piping
that connect the indoor and outdoor units.
The default position for all piping is the right
side of the indoor unit (while facing the unit).
However, the unit can accommodate piping to
both the left and right.
A location at least one meter from all other
electrical devices (e.g., TV, radio, computer)
Page 11
Refer to the following diagram to ensure proper distance from walls and ceiling:
15cm (5.9in) or more
Indoor Unit
Installation
Step 2: Attach mounting plate to wall
The mounting plate is the device on which you
will mount the indoor unit.
1.
2.
3.
4. Secure the mounting plate to the wall with
5.
12cm (4.75in)
or more
2.3m (90.55in) or more
Fig. 3.1
Remove the screw that attaches the mounting
plate to the back of the indoor unit.
Place the mounting plate against the wall
in a location that meets the standards in
the Select Installation Location step. (See
Mounting Plate Dimensions for detailed
information on mounting plate sizes.)
Drill holes for mounting screws in places that:
•have studs and can support the weight of
the unit
•correspond to screw holes in the mounting
plate
the screws provided.
Make sure that mounting plate is flat against
the wall.
NOTE FOR CONCRETE OR BRICK WALLS:
If the wall is made of brick, concrete, or similar
material, drill 5mm-diameter (0.2in-diameter)
holes in the wall and insert the sleeve anchors
provided. Then secure the mounting plate to
the wall by tightening the screws directly into
the clip anchors.
12cm (4.75in)
or more
Step 3: Drill wall hole for connective piping
You must drill a hole in the wall for refrigerant
piping, the drainage pipe, and the signal cable
that will connect the indoor and outdoor units.
1.
Determine the location of the wall hole based
on the position of the mounting plate. Refer
to Mounting Plate Dimensions on the
next page to help you determine the optimal
position. The wall hole should have a 65mm
(2.5in) diameter at least, and at a slightly
lower angle to facilitate drainage.
2.
Using a 65mm (2.5in) or 90mm(3.54in)
(depending on models )core drill, drill a
hole in the wall. Make sure that the hole
is drilled at
a slight downward angle, so
that the outdoor end of the hole is lower
than the indoor end by about 5mm to 7mm
(0.2-0.27in). This will ensure proper water
drainage. (See Fig. 3.2)
3. Place the protective wall cuff in the hole. This
protects the edges of the hole and will help
seal it when you finish the installation process.
CAUTION
When drilling the wall hole, make sure to
avoid wires, plumbing, and other sensitive
components.
Page 12
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.