Blodgett BCM-101E Service Manual

GB
For BCM Electric Oven
“Manual Control”
Table of Contents
Data Plate 3 Installation and connection
-Water connection 4
-Drain connection 5
-Electrical connection/survey of supply lines 6
Start Menu 7
Oven set-up 8 Set –up Mode U 9-10
Test Mode 11
Test Mode D0-D6 12 Test Mode D7-D15 13 Test Mode D16-D20 14 Test Mode D21-D28 15
User Menu 17 User Menu B1-B7 18 User Menu B8-B13 19 User Menu B14-B21 20 User Menu B22-B24 21
Error Codes 22
-Error Code List 23
-Error Codes Guide
Notes 24
Sequence of operation
-Off / On Mode Operation 1
-Hot Air / CombiOptima Operation 2
-Steam / Reheating Operation 3
-Cooling down / Preheat operation 4
Manual Controller
Water level Sensor
BCM Start up Guide
Diagnostic Mode D-Level
Wire Diagram
-Wire Schematic_Diagram 1-8
-Understanding Wire Schematic 2-8
- 2 -
Installation and Connections
Data Plate
When communicating with BLODGETT, we kindly ask you inform us of the serial number of the oven that is stated on the approval plate. The approval plate is located on the right-hand corner post of the oven cabinet, as shown below.
The BLODGETT Technical Support, whose experience and expert knowledge are at your disposal, can be contacted at tel. # 800-331-5842 and fax # 802-652-2814.
Drain connection
From the factory, the BLODGETT ovens are equipped with a drain system that removes surplus water from the oven chamber. This water may be condensed water from the products, or it may occur when the oven chamber is cooled down with cold water, or when the oven chamber is cleaned.
Connection authorised plumber, to an open or to a closed drain.
It is recommended that a water outlet is available/established in the floor of the room where the oven is located.
must
be carried out by an
The drain must never end directly beneath
the oven.
The drain must be of
-resistant material, have a diameter of at least 2” (50mm) and a fall of at least 3° or 5%.
copper
or an equally temperature
Water Connections
BLODGETT ovens have one or two water connections. Two is most common.
To facilitate cleaning and service, the oven should be connected with an approved flexible ¾” hose and the permanent installations should be fitted with a stop-tap and a non-return valve. Before connecting the oven to water, flush the tubes thoroughly. Connect the oven.
Hardness of the water: 80-100 PPM pH level 7.0-8.0 Total Dissolvable Solids: 100 PPM Chloride: max. 0 PPM Sulfate: max. 40 PPM/Gal Conductivity: min. 75 microsiemens Water pressure: min. 36 PSI (2.5 bar) dynamic pressure (when CombiClean activated.
When CombiWash not activated: min. 22 PSI (1.5 bar), max. 87 PSI (6 bar).
Water temperature: max. 70°F (20°C)
If the water temperature exceeds 70°F (20°C), problems with regard to ClimaOptima calibration and cooling of the oven may occur.
The water connection must be carried out by an authorised plumber in accordance with existing rules and regulations
To ensure that the water quality is in conformity with the above requirements, the installation of a water filter in front of the water connection to the oven is recommended.
1) 1 connection for raw water for the condensation jet (cold water). Located at the back.
2) The installation of a particle filter (0.25mm) is also recommended.
3) 1 connection for the steam generator and the jet in the oven chamber. Must meet the requirements applying to water supplied to household appliances; however, hot water with a temperature not exceeding 125°F (50°C) can be used. Located at the front.
Electrical Connections
When you connect the oven, you should:
Comply with federal, state and local rules and regulations.
The electrical connection existing rules and regulations.
An approved plug outlet or a safety cut-out
oven can be disconnected during installation and repair. The safety cut-out must be able to cut off all poles with a total distance of break of at least 3 mm. Each of the two units in a stacked arrangement (Combi-Plus) must have its own plug outlet or safety cut-out.
The warranty does not cover incorrect connection.
must
be carried out by an authorised electrician in accordance with
must be located close to the oven so that the
- 4 -
Installation and Connection
Drain connection
From the factory, the BLODGETT ovens are equipped with a drain system that removes surplus water from the oven chamber. This water may be condensed water from the products, or it may occur when the oven chamber is cooled down with cold water, or when the oven chamber is cleaned.
Connection plumber, to an open or to a closed drain.
It is recommended that a water outlet is available/established in the floor of the room where the oven is located.
The drain must never end directly beneath
the oven.
The drain must be of an equally temperature-resistant material, have a diameter of at least 2” (50 mm) and a fall of at least 3° or 5%.
must
be carried out by a license
stainless steel, cooper
or
Installation and Connection
Electrical connection/survey of supply lines
The electrical connection rules and regulations.
The wiring diagram is located in the motor compartment.
The terminal for the electrical connection is located behind the right side plate.
An approved plug outlet or a safety cut-out
oven can be disconnected during installation and repair. The safety cut-out must be able to cut off all poles with a total distance of break of at least 3 mm. Each of the two units in a stacked arrangement (CombiPlus) must have its own plug outlet or safety cut-out.
The warranty does not cover incorrect connection.
When you connect the oven, you should:
must
be carried out by an authorised electrician in accordance with existing
must be located close to the oven so that the
Follow the installation instructions and the information given on the rating plate.
Comply with federal, state and local rules and regulations.
Checking before Use
The oven should be checked before you start using it.
On the outside
Check that the oven has not been damaged in transit (dents, scratches, etc.)
Check/adjust the height and check that the oven is placed level (horizontally)
Check/adjust oven door
• Connections
Check for correct water connection
Turn on water supply
Check for leaks
Turn off water supply
Check and clean dirt filter
Turn on water supply again
Check hand shower
Check for correct electrical connection
Check connection to drip tray
Check for correct mounting of drip tray
Check for correct fall of hose from drip tray, and check for leaks
Check for correct exhaust and drain connection
Clean oven
Apply steel oil
• Oven chamber
Check that filter housing is mounted correctly
Check interior light
Clean oven
• Operation panel
Check and adjust, if necessary, each of the preset values
Heat up the oven at 485°F (250°C) for approx. 5 min.
The installation checklist and the instruction checklist (appendices 1 and 2) should be filled in and returned to BLODGETT 30 days after the installation, at the latest.
Blodgett Fax # 802-652-2814
- 6 -
Start Menu
Program key
Step key
Alarm key
Start/Stop
Power Switch
Change oven temperature with turn switch
Change time with turn switch
Core temperature on C and K models. Injection time on B model.
PRG
HOT AIR selected if control lamp on
COMBI STEAMING selected if upper or middle control lamp is on. REHEATING is selected if lower
control lamp is on
Steaming on C and K, preheating on B
.
Exhaust open if control lamp on
Fan speed can be set between 20 and 100%. Control lamp is on when speed < 100.
Set temperature
(press temperature key, temperature flashes, set temperature with turn
switch, press temperature key again to save).
Set time
(press time key, time flashes, set time with turn switch).
Set core temperature
(press core temperature key, set temperature with turn switch).
Set injection time
(press injection key, time flashes, set injection time with turn switch). B
model only.
Turn switch
Oven set-up
Power Switch
Display shows setting
Not active
Display shows "U" No.
Display shows description of "U" function
Display shows setting
Confirmation of special settings
PRG
Press HOT AIR and STEAMING for 2 sec.
Possible to change to "d" test mode with combi steam key
Press STEAMING/ PREHEATING and HOT AIR for 2 sec.
Not active
Not active
Select "U" settings with turn switch
Not active
To enter set-up mode, press hot-air key and steaming/preheating key for 2 sec.
To leave set-up mode, turn switch to the left. Change between set-up and test mode by
pressing combi-steam key.
The set-up mode is only intended for service engineers who wish to change the set-up of the
computer control of the oven model in question.
The program display shows a description of the "U" function in question.
Set-up Mode U
In the set-up function, it is possible to set the oven controller to match the mechanical set-up and the choice of software.
If the set-up has been changed in U1, U4 or U15, the oven will be reset.
U1 Oven model
You select the oven model (B, C or K) by pressing the step key. 1= K, 2= C, 3= B. You press the temperature key to select a PassThrough model (two doors). 1= one door (standard) 2= two doors When you have selected the oven model, confirm by pressing the alarm key if the control lamp flashes. After that, the controller initializes.
NOTE: ALL settings and programs are reset.
U2 Oven size
You choose the oven size by pressing the step key: 0-7.0= 1.06, 1= 1.08, 2= 1.10, 3= 1.12, 4=
1.16, 5= 1.20, 6= 2.10, 7= 2.14.
The oven size you have chosen is shown in the field next to the temperature key.
U3 CombiWash
You activate or deactivate CombiClean by pressing the step key. 0=OFF, 1=ON.
U4 Temperature scale
You choose between Celsius and Fahrenheit as scale of temperature by pressing the step key. 0= Celsius 1= Fahrenheit. You can ”even out” the current temperature by pressing the temperature key. 0=OFF, 1=ON When you have chosen the temperature scale, confirm by pressing the alarm key if the control lamp flashes. After that, the controller initializes.
NOTE: ALL settings and programs are reset.
U5 Not in use
U6 Low-temperature steaming
You activate and deactivate low-temperature steaming by pressing the step key. 0= OFF, steaming only possible at 100°C, 1= ON, steaming only possible between 30°C and 120°C.
NOTE: This function is available on K models only. If chosen on a B or C model, nothing happens.
U7 Preheating at 300°C
You activate and deactivate preheating by pressing the step key. 0= OFF, 1= ON.
NOTE: Preheating at temperatures above 250°C is only possible for max. 15 minutes.
U8 Setting water level sensor
When you press the temperature key, the water level value starts flashing and can then be set between 40 and 80 (default 70). If the conductivity of the water is low, set the water level higher.
U9 Automatic restart
You activate and deactivate automatic restart by pressing the step key. 0= OFF, 1= 10 minutes, 2= 30 minutes, 3= 60 minutes. This means that if there is a power cut, the program that was interrupted will be reassumed provided that the power returns within the time set.
- 9 -
U10 Programs
You activate the program mode by pressing the step key. 0= OFF, 1= 10 programs with 3 process steps.
NOTE: It is still possible to activate the cleaning program even though the program mode is not active. 0= OFF.
U11 Core temperature probe
You activate and deactivate the core temperature probe by pressing the step key. 0= OFF, 1= ON.
U12 Drain cooling
You activate and deactivate drain cooling by pressing the step key. 0= OFF, 1= ON.
U13 Timer start
You activate or deactivate timer start by pressing the step key. 0= OFF, 1= ON.
U14 Demo
You activate or deactivate the demo mode by pressing the step key. 0= OFF, 1= ON.
NOTE: If the demo mode is on (1= ON), the oven will run without heating elements and steam generator being switched on. When the oven starts, it will let you know whether the demo mode is on.
U15 Initialising
You reset the controller by pressing the alarm key.
- 10 -
Power Switch
Display shows setting
Display shows setting
Test Mode
For test mode, press HOT AIR and COMBI STEAMING for 2 sec.
For test mode, press COMBI STEAMING and HOT AIR for 2 sec.
Display shows "d" No.
Possible to change to "U" setting by pressing STEAMING/PRE­HEATING
Display shows a description of the "d" function
PRG
Not active
Display indicates whether the function is active
Not active
Activates each function briefly
Possible to choose a "d" function with turn switch
Not active
To enter test mode, press hot-air key and combi-steam key for 2 sec.
To exit test mode, turn switch left. Change between set-up mode and test mode by pressing
steaming/preheating key.
How to operate the selected component: You turn the component on (1) and off (2) by pressing
the step key. Or, you press the alarm key, and the component is active for as long as you press the key.
The set-up mode is only intended for service engineers who wish to test the various
modes/functions.
Test Mode D0-D6
In the test mode, it is possible to activate all electrical components. This is very useful in connection with fault detection and the testing and adjusting of replacement parts.
D0 Main contactor(s)
This function activates contactor K1. You activate or deactivate the function by pressing the step key. The function can, however, only be activated when the fan is on. To pulse, press the alarm key. 0= OFF, 1= ON. Status for the main alarms appear in the display as follows: Digit 1 fan Digit 2 oven Digit 3 generator Digit 4 Solid State Relay If ER28 appears, the alarm sensor circuit board or wiring harness is defective.
D1 Oven heat
This function activates contactor K2. You activate or deactivate the function by pressing the step key. Humidity pulsing is possible by pressing the alarm key. 0= OFF, 1= ON.
D2 Steam generator heat
Available on K models only This function activates contactor K3. You activate or deactivate the function by pressing the step key. However, this function can only be activated when there is water in the steam generator. To pulse, press the alarm key. 0= OFF, 1= ON.
D3 Fan, right-hand, high/low
This function activates the frequency exchanger. You can test the speed of the motor by pressing the step key. 0= OFF, 2= ON By pressing the time key, it is possible to adjust the speed of the motor from 0 to 100%. The RPM appears in the temperature display.
Note: The main contactor K1 must be active for this function to work, as the frequency transformer is connected via K1
D4 Fan, left-hand, high/low
This function activates the frequency exchanger. You can test the speed of the motor by pressing the step key. 0= OFF, 2= ON By pressing the time key, it is possible to adjust the speed of the motor from 0 to 100%. The RPM appears in the temperature display.
Note: The main contactor K1 must be active for this function to work, as the frequency transformer is connected via K1
D6 Solenoid valve
This function activates solenoid valve MV1. You activate or deactivate the function by pressing the step key To pulse, press the alarm key. 0= OFF, 1= ON.
- 12 -
Test Mode D7-D15
D7 Filling valve Available on K models only.
This function activates solenoid valve MV2. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D8 Drain pump Available on K models only.
This function activates motor M2. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D9 Drain cooling This function is not available on B models.
This function activates solenoid valve MV3. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D10 Damper motor
This function activates motor M3. In the display next to ”Time”, it is possible to read the status of the damper motor switch. OFF= damper open, ON= damper closed. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D11 Exhaust
This function activates the outlet for controlling the external ventilation, terminals 4 and 5. In the display next to ”Time”, it is possible to read which outlet is active. OFOF= both outlets are off, ONOF= outlet 4 is active and outlet 5 is off. OFON= outlet 4 is off and outlet 5 is active. ONON= both outlets are active. You activate or deactivate the function by pressing the step key. 0= OFOF, 1= OFON, 2= ONOF, 3= ONON.
D12 Cooling fan
This function activates motors M7 and M7A. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D14 Interior light
This function activates H1. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D15 Oven temperature
Here it is possible to read the current oven temperature, P1. In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor circuit is defective. In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown. To adjust the temperature, press the time key until the digit in the display flashes. Then adjust upwards or downwards until the correct temperature is shown. Finally, press the time key again to save the setting. The temperature can be adjusted by +- 50°F (10°C).
- 13 -
Test Mode D16-D20
D16 Core temperature This function is not available on B models. C and K models can use only one core temperature probe, it is possible, however, to test core temperature probes 1 and 2.
Here it is possible to read the current temperature of the core temperature sensor, P2 + P2A. In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor circuit is defective. In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown. To adjust the temperature, press the time key until the digit in the display flashes. Then adjust upwards or downwards until the correct temperature is shown. Finally, press the time key again to save the setting. The temperature can be adjusted by +- 50°F (10°C). You change between the various measuring points of the core temperature probe by pressing the step key. 1= Core temp probe 1, point 1, 2= Core temp probe, point 2, 3= Core temp probe 1, point 3. 4= Core temp probe 2, point 1, 5= Core temp probe, point 2, 6= Core temp probe 2, point 3.
D17 Steam generator temperature Available on K models only.
Here it is possible to read the current steam generator temperature, P3. In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor circuit is defective. In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown. To adjust the temperature, press the time key until the digit in the display flashes. Then adjust upwards or downwards until the correct temperature is shown. Finally, press the time key again to save the setting. The temperature can be adjusted by +- 50°F (10°C).
D18 Drain temperature
Here it is possible to read the current steam generator temperature, P4. In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor circuit is defective. In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown. To adjust the temperature, press the time key until the digit in the display flashes. Then adjust upwards or downwards until the correct temperature is shown. Finally, press the time key again to save the setting. The temperature can be adjusted by +- 50°F (10°C) (approx. 2°F (.5°C) per step).
D20 Door sensor
Here it is possible to read the status of and calibrate door sensor 1 = SE1 and 2 = SE1A. You change between door sensor 1 and 2 by pressing the step key. After some time, the text “DOOR SENSOR” changes to show the status of the sensor: >CLOSED<, >OPEN<, >SENS ERROR<. You start the calibration by pressing the exhaust key. How to calibrate:
1. Press the damper key
2. >CLOSE< flashes
3. Close the door
4. Press the damper key
5. >OPEN< flashes
6. Open door in the first step
7. Press the damper key
8. >CALIB OK< or >CALIB ERR< appears
9. Press the damper key to confirm
In the display next to the temperature key, it is possible to read the current value (0 – 120). In the display next to the time key, it is possible to read the set point.
- 14 -
Test Functions D21-28
D21 Water level Available on K models only.
Here it is possible to read the status of SE2. In the display next to ”Time”, the conductivity is shown and it is indicated whether the water level is high or low XX|LO= low water level, XX|HI= high water level. XX = conductivity of the water. Default setting is approx. 80 with no water and 40.60 with water. The better the conductivity, the lower the measured value.
D22 Thermo-switch oven
Here it is possible to read the status of Q1 and Q1A. In the display next to ”Time”, it is shown whether the circuit is connected or disconnected. OF= disconnected ON= connected. In the event of defects, it is possible to reset thermo-switches Q1 and Q2 that are located at the bottom of the oven below the operation panel.
Note: Q2 is only found in ovens with 2 fan motors (1.16 and 1.20). Q1 and Q1A are series connected which is why there is only one input signal.
D23 Thermo-switch fan
Here it is possible to read the status of S2 and S2A In the display next to ”Time”, it is shown whether the circuit is connected or disconnected. OF= disconnected ON= connected. In the event of defects, wait for 10 – 20 minutes, then try again.
Note: Q2 is only found in ovens with 2 fan motors (1.16 and 1.20). S1 and S1A each have their own input on the IO board hence 2 x status (On On / OFF OF / On OF / OF On).
D24 Damper switch
Here it is possible to read the status of M3. In the display next to ”Time”, it is possible to read the status of the damper motor switch. OF= damper open, ON= damper closed.
D27 Pump for detergent Only possible on ovens with CombiWash
This function activates pump M5. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D28 Pump for rinse aid Only possible on ovens with CombiWash
This function activates pump M6. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
- 15 -
Test Mode D29-D47
D29 CombiWash water Only possible on ovens with CombiWash.
This function activates solenoid valve MV4. You activate or deactivate the function by pressing the step key. To pulse, press the alarm key. 0= OFF, 1= ON.
D34 Water pressure sensor
Here it is possible to read the status of P7. OF|HI= water pressure adequate, ON|LO= water pressure inadequate.
D36 Steam generator thermo-switch
Here it is possible to read the status of Q3 In the display next to ”Time”, it is shown whether the circuit is connected or disconnected. OF= disconnected ON= connected. In the event of defects in the oven, it is possible to reset thermo-switch Q3 which is located at the bottom of the oven below the operation panel.
D37 Motor RPM 1
Here it is possible to read the number of revolutions for fan motor 1. The number of revolutions is shown in the display next to the temperature key.
D38 Motor RPM 2 Available on 1.16 and 1.20 models only.
Here it is possible to read the number of revolutions for fan motor 2. The number of revolutions is shown in the display next to the temperature key.
D46 Temperature CPU board
Here it is possible to read the temperature of the CPU board. In the display next to ”Temperature”, the temperature of the CPU board is shown. Max 140°F (60°C).
D47 Temperature IO board
Here it is possible to read the temperatures of the IO board. In the display next to ”Temperature”, the temperature of the IO board is shown. Max 140°F (60°C).
- 16 -
Turn switch
Main switch
Start/Stop
User Menu
Display shows setting
Display shows setting
Display shows "b" No.
Display shows description of "b" function
Display shows setting
Press key for 5 sec. to access user menu
Not active
Not active
Not active
PRG
Not active
Not active
To enter user menu, press alarm key for 5 sec.
To exit user menu, turn the switch to the left.
The user menu can be operated by the end-customer as well as by the service engineer.
User Menu B1-B7
B1 Save pre-settings
In this function, you save the preset time and temperature. If, for instance, the end user uses HOT AIR at 180°C for 30 minutes, the standard setting can be changed as follows:
1. Change time and temperature.
2. Enter user menu (keep pressing alarm key for 5 sec.)
3. Select B1 (save pre-settings).
4. Press alarm key to accept.
You can only save the settings when the control lamp next to the alarm key flashes.
B2 Timer start
(Please see user manual)
B3 Sound level low
In this function, you adjust the sound that is heard when a key is activated. The sound level can be adjusted from 0 to 9 (0 is no sound at all). You adjust the sound level by pressing the step key.
B4 Sound level high
In this function, you adjust the sound that comes from the alarm. The sound level can be adjusted from 1 to 9 (1 is very low). You adjust the sound by pressing the step key.
B5 Sound frequency
In this function, you adjust the sound frequency. The sound frequency can be adjusted from 1 to 9. You adjust the sound by pressing the step key. You test the sound by pressing the alarm key.
B6 Interior light
In this function, you adjust the interior light. The light can be set at 0 or 5. 0= Light is always on. 5= Light goes out when the oven has been idle for 5 minutes. You adjust the interior light by pressing the step key.
B7 Current temperature
In this function, you choose whether the oven should display the current temperature or the preset temperature. You choose between 0 and 1 0= The preset temperature is shown. 1= The current temperature is shown. You change the setting with the step key.
- 18 -
User Menu B8-B13
B8 Exhaust
In this function, you choose whether the oven should start up the extraction hood. 0= Extraction hood not controlled by oven 1= Extraction hood runs for 10 minutes after oven has stopped. This applies to an extraction hood mounted on the oven as well as for an external extraction hood.
B9 Time graphics
In this function, you determine whether the oven should be able to show graphically how long time has passed of a cooking sequence. You choose between 0 and 1. 0= No graphics 1= Graphics, for instance ”llllll------”, appear You change the setting with the step key.
B10 Minutes
In this function, you set the minutes of the oven’s clock.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired setting of minutes.
3. Press the key next to the temperature display (digit stops flashing) You can set the minutes from 0 to 59. The oven’s clock may appear as screen saver.
B11 Hours
In this function, you set the hours of the oven’s clock.
1. Press the key next to the temperature display (digit flashes)
2. Turn the switch to the desired setting of hours.
3. Press the key next to the temperature display (digit stops flashing) You can set the hours from 0 to 23. The oven’s clock may appear as screen saver.
B12 Day/weekday
In this function, you set the day of the month and of the week.
1. Press the key next to the temperature display (digit flashes)
2. Turn the switch to the desired day of the month (1-31).
3. Press the key next to the temperature display (digit stops flashing)
4. Press the key next to the time display (digit flashes)
5. Turn the switch to the desired day of the week (1-7).
6. Press the key next the time display (digit stops flashing) You select automatic updating to summer time. 0= No automatic updating to summer time. 1= Automatic updating to summer time. If you choose not to have the oven update to summer time automatically, you cannot set the weekday. Automatic updating to summer time only functions correctly in Western Europe.
B13 Month
In this function, you set the month.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired month.
3. Press the key next to the temperature display (digit stops flashing).
You can set the month from 1 to 12.
- 19 -
User Menu B14-B21
B14 year
In this function, you set the year.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired setting.
3. Press the key next to the temperature display (digit stops flashing).
You set the year from 6 to 20.
B15 CombiWash
In this function, you activate or deactivate CombiWash. 0= Manual cleaning 1= CombiWash Press step key to change setting.
B16 Pulsing interval, reheating
In this function, you set the pulsing time in the reheating mode.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired time.
3. Press the key next to the temperature display (digit stops flashing)
You set the time from 5 – 50 sec.
B17 Pulsing interval, Combi Steam 1
In this function, you set the pulsing time for Combi Steam 1.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired time.
3. Press the key next to the temperature display (digit stops flashing)
You set the time from 2 to 50 sec.
B18 Pulsing interval, Combi Steam 2
In this function, you adjust the pulsing time for Combi Steam 2.
1. Press the key next to the temperature display (digit flashes).
2. Turn the switch to the desired time.
3. Press the key next to the temperature display (digit stops flashing) You set the time from 1 sec. to the number of seconds specified to be the pulsing time for Combi Steam 1.
B19 Save all (Backup)
In this function, you save set-up and programs to the IO board for subsequent restoration. This can be used as backup when set-up and programs are correct. Press alarm key to save.
B20 Restore all
In this function, you restore set-up and programs you have saved earlier.
B21 Restore original
In this function, you restore the original programs from 0 to 4.
1. Press step key to select program.
2. Press alarm key when program has been found.
- 20 -
User Menu B22-B24
B22 Screen saver
In this function, you set the time that should pass until the clock appears in the display. Press step key to select time. 0= no screen saver 1= 10 sec. 2= 30 sec. 3= 60 sec. 4= 180 sec. 5= 600 sec. The screen saver appears when the oven has been idle for a particular period of time.
B23 Language
In this function, you change the language of the computer. Press step key and select 1, 2, 3 or 4. There are also four language variants: A – D (see below).
To change the language, you need to update again (see B24)
B24 Software update
In this function, you update the computer software by means of a special memory key (not a USB key).
1. Insert memory key.
2. Press alarm key to view software version and language variants.
3. Press step key to select language variant.
4. Press alarm key again to start updating process. The software version of the oven in question is also shown in the start-up sequence when the oven is switched on.
1 Danish English English English
2 Swedish German French Estonian
3 English Kroatian Spanish Hungarian
4 Finnish Slovenian Italian Russian
A B C D
Display shows error "Er" No
Display shows description of error
PRG
Error codes
Main switch
Start/Stop
All keys can be used to acknowledge an error message.
Turn switch
by pressing button under oven.)
by pressing button under oven.)
minutes and try again.
Drain too hot
(Drain temperature has been above 75
°
C for more
than 5 min. Check that jet in drain is working.)
working properly.)
probe has been selected but probe has not been connected.)
working.)
be used.)
Check that the water has been turned on.)
130°C. If fault recurs, descale generator)
Error code 14:
FAN SPEED
Fan running too slow
Error code 18:
DATA ERROR
Error in set
-
up data
Error code 19:
WRONG LANG
Wrong language
board.)
Error code 22:
NO RESTART
Restart not possible
(Oven has been without power too long.)
Error code 23:
OVEN WARM
Oven too hot at CombiWash start
-up
the core temperature probe defective.)
Error code 28:
ALARM ERR
Configuration error in main alarms
(3, 4, 5, 12) (warning)
Error code 34:
WATER PRES
Water pressure too low
(Check that water is turned on.)
Error code 40:
IO BRD HOT
Temperature in IO board critical
(Warning after program run.)
Error code 43:
WRONG SW
Wrong software version
(Visual Cooking I oven)
Error code 44:
DAMPER ERR
Failure during initialisation of exhaust at oven start
-up
Error code 3: GENRA HOT
Error code 4: OVEN HOT
Error code 5: FAN HOT
Error code 6: DRAIN > 75
Error code 7: OVEN SENS
Error code 8: PROBE SENS
Error code 9: GENER SENS
Error code 10: DRAIN SENS
Error code 11: WATER SHOR
Error code 12:
Error code 13: GENER > 130
SSR HOT SSR too hot (Solid-state relay too hot.)
Error codes
Generator too hot (Generator thermo switch has tripped. Reconnect
Oven too hot (Oven chamber thermo switch has tripped. Reconnect
Fan too hot (Thermo switch in motor has tripped. Wait for 10
Oven sensor defective (Temperature sensor in oven chamber not
Core temp. probe not connected (A program using core temp.
Generator sensor defective (Temperature sensor in generator not
Drain sensor defective (Sensor in drain not working. Oven can still
Water shortage (Steam generator was not filled within two minutes.
Generator too hot (Temperature in steam generator higher than
Error code 15: Error code 16: IO BRD HOT IO board too hot (> 60°C)
Error code 20: NO COM IO
Error code 24: DRAIN ERR
Error code 25: PROBE ERR
Error code 29: DOOR SENS Wrong door sensor signal (warning)
CPU HOT CPU board too hot (> 60°C)
Internal defect (Failure in communication between computer and IO
Draining failure (Drain blocked or failure of drain pump. Water level
in generator still high after 10 seconds of draining.)
Core temperature probe defective (1, 2 or 3 of the elements in
Notes:
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
BCP & BCM, ERROR CODES & CAUSES
3 - Generator Hot – Generator High Limit Thermostat Open(Opens at 275˚F) (Manual Reset under a
cover at the bottom of the control panel)
4Oven Hot - Oven High Limit Thermostat Open (Opens at 662˚F) (Manual Reset under a cover at the
bottom of the control panel)
5Fan Hot – Motor Thermal Limit Open (2 Gray Wires) (Opens at 320˚F) Wait 10 minutes and try again.
If 5 appears again, the cooling fans, motor bearings, or thermal switch within the motor failed.
6 – Drain Hot – RTD Probe in Drain (100 Ohm Probe) reads over 167˚F for over 5 minutes.
7Oven sensor Defect – RTD Probe in Generator (100 Ohm Probe) Shorted/Open
8 – Core Probe Missing – Control has an active Core (Meat) Probe. Deactivate both Core Probes or
insert Core Probe in the probe port on the control side.
9Gen Sensor Defect – RTD Probe in Generator (100 Ohm Probe) Shorted/Open
10Drain Sensor Defect - RTD Probe in Drain (100 Ohm Probe) Shorted/Open
11Water Shortage – Steam Generator could did fill in 5 minutes.
12 – SSR Hot – one of the two SSR Heat Sink Automatic Reset Snap Disks that are wired in series is Open
(Open at 248˚F)
13 – Generator > 265 – RTD Probe in Generator (100 Ohm Probe)reads over 265˚F.
14Fan Slow – Fan Hall Sensor (Brown, Black and Red Wires), Inverter or the Motor has failed or a
wiring issue exists.
16IO Board Hot – The IO Board senses a temperature above 140˚F.
19Internal Error–The control has sensed a failed process, restart the control.
20 – IO Com Error- Failure of communication between the CPU and IO Board.
21Invalid recipe – Indicates a recipe is programmed for a feature the oven does not have.
22 - Program Terminated – Power interrupted while a program was in progress and enough time
elapsed that the program cannot resume.
24 – Empty Error – Steam Generator water level sensor reads water 25 seconds after running the drain
pump to drain the boiler.
25CombiOptima not Calibrated – Enter the Service Menu and run the calibration.
26CombiOptima Sensor Error – The Pressure sensor gives a reading outside the range of 0.5 - 4.5.
27 – CombiOptima calibr. Fault – Calibration could not be completed, Start calibration when the oven is
cold and dry.
BCP & BCM, ERROR CODES & CAUSES
28Main Alarm Error –No 24V signal to high limit board
29 – Door Sensor Error – Wrong door sensor signal
34Water Pressure Low – Water Pressure Switch (located on the larger solenoid assembly) is closed.
(Opens at 22 PSI)
36No Detergent – Time Based detergent monitoring is disabled.
38Detergent In Oven – Combi wash interrupted while the detergent was in the oven. Run Combi
Wash in Step 0 to clear detergent prior to inserting product.
39Insufficient Memory – The units memory is not sufficient for the current operation.
40-IO Board Hot- The IO Board senses a temperature above 140°F.
41 – Main Alarm -
42Error in SW – Software Error. Reboot software to current version.
For Gas Ovens
44-Dammper Error-Failure during initialization of exhaust at oven start-up.
45-24V Error-24V missing or failure of main contactor output.
50-Switch On-Pressure switch on when gas-air control unit running (timeout 20 sec.)
51-Switch Off-Pressure switch not on when gas-air control unit running (timeout 20 sec.)
52-Gas Valve-Gas valve does not open (automatic gas burner control has failed (timeout 20 sec.))
53-No Fan RPM-Gas-air control unit does not revolve when pressure switch is on.
54-Fan Error-Gas-air control unit does not run at correct RPM just before ignition.
55-Gas Fail-Warning: Ignition failed.
56-Gas Error-Flame fails to occur after 3 attempts.
57-Gas Stop-Warning: Gas failure during operation.
BLODGETT OVEN COMBI
1
Sequence of Operation for BCP and BCM (electric)
Unit is turned “OFF”
You will have AC voltage at:
The bottom of the main contactor (T1, T2, T3)
Fuse F5 in the front
The transformer (T1) in the front of the oven
Fuse F1, F2, F3 and F4 in the front
On the CPU and the IO board (J10 pin 5 and 6)
There are no DC voltage when the unit is turned OFF
Unit is turned “ON”
The boot logo appear on the screen for about 30 sec. then ready to operate (only BCP)
Light will come on after 30 sec.(only BCP) (12 VAC between J9 pin 3 and terminal 1)
The exhaust valve will “open” and “close” after 30 sec. (24 VAC between J2 pin 12 and terminal 1) (Ground J2 pin 15 when closed)
When a mode is started
The IO board verifies the following with DC voltage:
The door sensor SE1 is closed sending either towards 0 or towards 5
DC voltage to J1 pin 34 depending on the pole of the magnet.
With door sensor SE1 open the DC voltage is 2,5 on J1 pin 34.
The IO board verifies the following with AC voltage:
The high limit stat of the motor is closed sending 24 VAC to J1 pin 10
The high limit stat of the oven is closed sending 24 VAC to J1 pin 9
The high limit stat of the boiler is closed sending 24 VAC to J1pin 12
The high limit stat of the SSR closed sending 24 VAC to J1 pin 13
Main contactor K1 is activated (24 VAC on coil of contactor A1 and A2)
output from IO board is coming from plug J2 pin 2 going through all the high limit stats and to the coil.
When the main contactor is activated the terminal L4 on the contactor provides power to the frequency inverter (terminal L/R) which controls the motor M1.
The IO board makes a connection between J2 pin 28 and 27 to terminal +12V, and Start, this will start the fan.
The speed of the fan depends of the DC voltage on terminal Com and Speed of the inverter (IO board J2 pin 33 and 34) 0 – 10 VDC
The motor reverses direction every 2 minutes by making a connection to the terminal REV of the inverter (IO board J2 pin 29) +12VDC
BLODGETT OVEN COMBI
2
Unit set in “Hot air”
Max temperature 250°C/482°F
The SSR gets DC voltage on the terminal -/+1 (if boiler model) -/+1 and 2 (if no boiler) DC coming from J2 pin 22 and 23.
The IO board will get a resistance input from P1 (oven temperature sensor PT100) on J1 pin 37 and 38 telling the IO board when to switch off the SSR.
When the time runs out H2 (buzzer) will be activated.
Unit set in “CombiOptima”
The SSR gets DC voltage on the terminal -/+1 (if boiler model) -/+1 and 2 (if no boiler) DC coming from J2 pin 22 and 23.
The IO board will get a resistance input from P1 (oven temperature sensor PT100) on J1 pin 37 and 38 telling the IO board when to switch off the SSR.
The sensor P9 is supplied by 12 VDC from J1 pin 25 and 26.
The sensor measure pressure between 0 – 3 mbar (0,5 – 4,5 VDC)
Depending on the temperature/fan speed/pressure the computer
calculates the humidity.
The higher temperature the lower pressure (voltage)
The higher humidity the lower pressure (voltage)
Dry and cold oven gives the highest reading (voltage)
(There are no precise measures/voltages it depends on the oven. That is why it has to be calibrated.)
BLODGETT OVEN COMBI
3
Unit set in “Steam”
Max temperature 100°C/212°F, Forced steam 120°C/348°F
If P3 (temperature sensor of boiler PT100) register an Ohm value which is higher than 65°C/149°F it will start filling to HIGH level. If the value is lower than 65°C/149°F empty and flush the boiler as described below.
The empty pump M2 gets 208V/230V signal from J11 pin 4 and F6.
The boiler will now get flushed this is the sequence:
1. Empty boiler 25/35/45 sec. depends on the boiler size
2. Empty boiler 5 sec. and filling 5 sec.
3. Empty boiler 10 sec.
4. Empty boiler 5 sec. and filling 5 sec.
5. Empty boiler 10 sec.
6. Empty boiler 5 sec. and filling 5 sec.
7. Filling 5 sec.
8. Filling to high level
9. Wait 2 sec. check level again
Ready the run the boiler
The boiler will be filled by MV2 (filling valve) get 24 VAC from J2 pin 10
The level sensor SE2 is supplied by 12 VDC when the sensor give a
ground signal to J1 pin 33 the IO board will cut off the MV2 valve.
When the HIGH level is registered, the SSR gets DC voltage on the terminal -/+2 DC coming from J2 pin 22 and 25 to heat up the water.
If the level sensor register LOW level (not ground signal on J1 pin 33) during boiling the MV2 (filling valve) will be activated 3 times for X sec.
If the IO board does not register HIGH level with in the 3 tries, MV2 will be activated continuously until HIGH level is reached.
Temperature in drain P4 J1 pin 47 and 48 above 65°C/149°F, active MV3 24 VAC (J2 pin 11) will cool down until the temperature is below 60°C/140°F.
When the time runs out H2 (buzzer) will be activated.
Unit set in “Reheating”
Temperature 20°C/68°F to 180°C/356°F
Standard fan speed 50% (5 VDC on inverter terminal Com and Speed, IO board J2 pin 33 and 34)
As standard inject water every 8 sec. for 1/10 of sec. through MV1 (injection valve) 24 VAC (IO board J2 pin 8)
Temperature in drain P4 J1 pin 47 and 48 above 65°C/149°F, active MV3 24 VAC (J2 pin 11) will cool down until the temperature is below 60°C/140°F.
When the time runs out H2 (buzzer) will be activated.
*Standard settings can be changed in setup
BLODGETT OVEN COMBI
4
Unit set in “Proving” (Only BCP)
Standard fan speed 50% (5 VDC on inverter terminal Com and Speed, IO board J2 pin 33 and 34)
As standard inject water every 20 sec. for 1 sec. through MV1 (injection valve) 24 VAC (IO board J2 pin 8)
When the time runs out H2 (buzzer) will be activated.
*Standard settings can be changed in setup
Unit set in “Cooling down” (Only BCP)
The IO board registers if the door sensor is OPEN or CLOSED.
If the door sensor registers OPEN 2,5 VDC on J1 pin 34, the fan M1 will be on 100% speed (10 VDC on inverter terminal Com and Speed, IO board J2 pin 33 and 34) until the temperature selected is reached.
If the door sensor registers CLOSED either towards 0 VDC or towards 5 VDC on J1 pin 34, the fan M1 will be on 100% speed. If the temperature is above 150°C/302°F the MV1 (injection valve) will be activated 24 VAC (IO board J2 pin 8) for 0,1 sec. and then off for 1 sec. the sequence will continue until the temperature is below 150°C/302°F.
When the temperature is below 150°C/302°F the MV1 (injection valve) will be activated for 1 sec. and then off for 1 sec. it will continue to run this sequence until the temperature is reached.
When the temperature is reached H2 (Buzzer) will be activated.
Unit set in “Preheating”
Max temperature 300°C/572°F
Max time 15 min.
Standard High speed
The SSR gets DC voltage on the terminal -/+1 (if boiler model) -/+1 and 2 (if no boiler) DC coming from J2 pin 22 and 23.
The IO board will get Ohm input from P1 (oven temperature sensor PT100) on J1 pin 37 and 38 telling the IO board when the temperature is reached, when it is reached it will stay on that temperature for the time set.
When the time runs out H2 (buzzer) will be activated.
Front side B, C, K controller
Short
Power 5V
3.3V 24V AC
Testpins
Start IO
Keyboard
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 5
Dias 5
RS232
Encoder
CPU
reset
5V
Programming connector
flash at start-up
Com IO light diodes: Yellow transmit Green receive Must flash
Clock: Must flash (1 sec)
Power: 24V AC Start IO COM IO
Not used
Back side B, C, K controler
Buzzer
Buzzer
Keyboard
Memory key connector
Programming connector
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 6
Dias 6
Power:Power: 1,2 1,2 -- COM IO COM IO 3 3 -- GNDGND 4 4 -- Start IOStart IO 5,6 5,6 -- 24V AC24V AC
Power 1 6
Battery (3V)
Encoder
RS232 not used
BCP / BCM Water Level Switch
Wire Side
pos
Sensor Side
24Vdc
- 1
Delime Pump Black
24Vdc+
2
Delime Pump Red
-------
3
Not used
130 Q1
4 High Limit stat Motor “G”
41 Q4
5 High Limit stat Motor “G”
86 SE2
6 (
Boiler Level sensor Black
)
77 P3
7 100k Ohm Boiler Probe
76 P3
8 100k Ohm Boiler Probe
69 P1
9 100k Ohm Cavity Probe
68 P1
10 100k Ohm Cavity Probe
88 SE3A
11
Not used
87 SE3
12 Speed sensor Motor “sig”
211 SE1
13 Speed sensor Motor 5V
-
90 X90
13
Not used
210 SE1
14 Speed sensor Motor 5V+
89 X30
14
Not used
94P912V+
15 (
Boiler level sensor Brown
92P912V
- 16 (Boiler level sensor Blue
)
Test Points
)
)
Sensor Power
Empty
Full
12 VDC
1.2 VDC
0 VDC
Plug X31:
stic mode allows you to navigate through all components to test
Press and hold the Hot Air and Combi keys
t
display 1 to activate that component
Instructions to activate the chemical pump to prime it during the start up process.
Combi
the
ed
next to the
1 will be displayed
press the Stage key
without the oven
simultaneously
the
tage key again to deactivate it
and the chemical pump will activate
Diagno mode. To activate diagnostic mode, scroll the dial to the desired componen stage key will
BCM START UP GUIDE
Diagnostic Mode
d - Level
them
displayed next to the PROG key and then press
, press the s
being in a cooking for 2 seconds then
Stage key once. The
0 will be displayed.
Step 1. Press and hold the Hot Air and
The Display will now show d 0 next to
Step 2. Scroll the dial till d30 is display
The Display will show DELIME PMP
Step 3. Press the Stage key once,
When pump has been primed,
keys simultaneously for 2 seconds.
Probe key
next to the Probe key.
PROG key.
next to the stage key
once to 0 the pump will deactivate.
.
Press and
hold the Hot
Air & Combi
Keys for 2-3
seconds.
BCM Blodgett Combi Oven
Page 1
Wiring diagram:
High limit
High limit
Page 1
circuit board
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 2
Dias 2
Oven light
Cooling fan, empty pump
CombiWash pump, vent.
Output
Supply
Com. to CPU
Input
Input to IO board
To high limit components
Wiring diagram:
Page 2
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 3
Dias 3
Main contactor
Please note main connection direct on main contactor
Main fuse for transformer fase
Main fuse for transformer neutral
Main terminals neutral, earth
Ring element Ø400 motor 1
Solid state relay no. 1
Ring element Ø470 motor 1
Ring element Ø400 motor 2
Solid state relay no. 2
Please note this is only for C - CPE
Ring element Ø470 motor 2
Connection to main contactor
Solid state relay no. 1
Wiring diagram:
Page 3
Solid state relay no. 2
Solid state relay no. 3
Solid state relay no. 4
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 4
Dias 4
Please note this is only for K - KPE
Ring element Ø400 motor M1
Ring element Ø400 motor M2
Ring element Ø470 motor M1
Ring element Ø470 motor M2
Element steam boiler
Element steam boiler
Temp. sensor steam boiler
High limit steam boiler 135°C
Top element steam boiler
Element steam boiler
Connection to main fuse F5
Connection to neutral terminal
Fuse for detergent / rins pump and vent.
Fuse for interior light
Wiring diagram:
Page 4
Terminals on main contactor
Transformer
Fuse for IO and CPU board
Fuse for all 24V output
Frequency inverter
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 5
Dias 5
Interior light
Plug on IO board
Buzzer (Sound)
Plug on IO board for com.
1. Main fan
2. Main fan (only used on 1.16 and
1.20
Wiring diagram:
Page 5
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 6
Dias 6
Plug on Alarm sens print
Sensor for water pressure
Switch for exhaust
Sensor for ClimaOptima
Restart switch
Doorsensor singel door
Level sensor boiler
Oven temp. sensor
Core probe temp. sensor 1
Doorsensor if Passthrough
Core probe temp. sensor 2
Temp. sensor drain
Connection to temp. sensor boiler
Solenoid valve
SSR
filling boiler
Coil main contactor
Wiring diagram:
Page 6
Lamp in restart button
Solenoid valve CombiWash
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 7
Dias 7
Plug on alarm sens. print
High limit boiler
High limit motor 2 only used in
1.16/1.20
High limit motor 1
High limit SSR if more than 2 SSR
High limit
Connection to fuse F1
Motor for exhaust
Solenoid valve drain
Solenoid valve inject
High limit oven only when 1.16/1.20
High limit oven
Connections to solid stat relay
Connections to frequency inverter
Wiring diagram:
Connection to terminal 2 (ext. vent)
Page 7
Connection to Fuse F5
9. maj 2011
9. maj 2011
HOUNÖ A/S
HOUNÖ A/S
Dias 8
Dias 8
Connection to Fuse F3
Connection to terminal 1
Rinse pump
Detergent pump
Connection to Fuse F3
Connection to neutral terminal
Cooling fan in the top of tech. room
Connection to Fuse F5
Empty pump boiler
Cooling fan in the back of tech. room
Loading...