Power supplies
Electronic circuit breakers
2
Electronic circuit breaker with thermomagnetic characteristic
ECONOMY SMART
General Data
Nominal input voltage 12 / 24 / 48 Vdc
Output channels 2 / 4 / 8
Tripping current 1 - 6 A / 2 - 10 A
Thermomagnetic characteristic
Ambient temperature -25 °C to +70 °C
Protection index IP 20
Efficiency typ. 99 %
Advantages
Adjustable tripping current for each output channel via current selector switch
Ability to turn-on high load capacitance at each channel
Sequential and load-dependent switching-on of channels
Comprehensive single-channel-diagnostics and remote switching on/off of each output channel via 2-wire-interface
LED signalisation and remote request for each output channel
Group alarm contact
StandardsZ
Applications
ECONOMY SMART circuit breakers with a thermomagnetic characteristic represent an economical alternative to the classic circuit breaker. They also ensure reliable tripping even in the case of high line resistance. This makes the circuit breakers ideal for use in standard machine production. The electronic circuit breaker distributes and monitors the load current over several current circuits. Overloads and short circuits on an output are reliably recognized. The electronics permit brief current peaks and switch longer overloads off. The rated current for each output can be individually set with a current selector switch accessible from the front. The outputs are activated depending on the time delay and load to avoid an overload current. If the rated current is exceeded for a certain amount of time, the output will be switched off automatically and can be reactivated after a waiting time (thermal relaxation) using the pushbutton or the remote signal input S1. The pushbutton can also be used to switch the output manually. It is possible to read out the state of each output using the three signal contacts. The state of each output is also indicated with a multi-colored LED.
Approvals o J U # Z
Electronic circuit breaker UL 508, UL 2367
Safety: EN 60950-1, EN 50178, EN/IEC 60204-1
EMC: EN 61000-6-2, EN 61000-6-3
Safety extra-low voltage (SELV/PELV): IEC 60364-4-41 (DIN VDE 0100-410)
CE acc. to 2004/108/EG (EMC-Directive)
UL 2367 (E-File: E356250)UL 508 (E-File: E219022)GL
Subject to change
369
+
-
Electronic circuit breaker with thermomagnetic characteristic
ECONOMY SMART
Typ PM-0724-240-0 PM-0724-400-0 PM-0724-400-2 PM-0748-200-0
Input
Input rated voltage 24 Vdc 24 Vdc 24 Vdc 48 Vdc
Input voltage range 18 - 30 Vdc 18 - 30 Vdc 18 - 30 Vdc 32 - 58 Vdc
Maximal residual ripple of supplied input voltage 3 % 3 % 3 % 3 %
Required input voltage for turning-on of outputs 19.5 V (Turn-off Threshold 18 V) 19.5 V (Turn-off Threshold 18 V) 19.5 V (Turn-off Threshold 18 V) 35 Vdc
Max. total input current 24 A 40 A 40 A 20 A
Max. input current for each pole of terminal 40 A 40 A 40 A 40 A
Over voltage protection Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 68 V
Stand-by current 35 mA @ 24 V 35 mA @ 24 V 35 mA @ 24 V
Power losses in stand-by mode 0.84 W @ 24 V 0.84 W @ 24 V 0.84 W @ 24 V
Output
Output rated voltage 24 Vdc 24 Vdc 24 Vdc 48 Vdc
Output rated current 4 x 1 - 6 A 4 x 2 - 10 A 4 x 2 - 10 A 2 x 2 - 10 A
Maximum voltage drop between input and output 120 mV @ 4 x 6 A 200 mV @ 4 x 10 A 200 mV @ 2 x 10 A
Initialization time of module 250 ms 250 ms 250 ms 250 ms
Turn-on delay of outputs Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s
Waiting periode after switch-off of an output 500 ms (short circuit) ... 10 s (overload) 500 ms (short circuit) ... 10 s (overload) 500 ms (short circuit) ... 20 s (overload) 500 ms (short circuit) ... 20 s (overload)
Max. power losses 4.2 W @ 4 x 6 A 10 W @ 4 x 10 A 10 W @ 4 x 10 A
Efficiency 99.0 % 99.0 % 99.0 % 99.0 %
Internal output fuse 15 A 15 A 15 A 15 A
Resistance to reverse feed max. 35 Vdc 35 Vdc 35 Vdc 58 Vdc
Parallel use of outputs Not allowed Not allowed Not allowed Not allowed
Serial use of outputs Not allowed Not allowed Not allowed Not allowed
Signaling
Status indicator LED (red, green, orange) LED (red, green, orange) LED (red, green, orange) LED (red, green, orange)
Signal input S1 DC 24 V (On/Off/Reset) DC 24 V (On/Off/Reset) DC 24 V (On/Off/Reset) 15 - 58 Vdc (On / Off / Reset)
Signal output S2 DC 24 V, max. 25 mA
(status output channels)
DC 24 V, max. 25 mA (status output channels)
"13": Solid State Relais; max. 58 Vdc / 40 Vac / 100 mA
"S2“: 24 Vdc, 20 mA, short circuit proof, status report of outputs
Signal output S3 DC 24 V, max. 25 mA
(Common signalling output)
DC 24 V, max. 25 mA (Common signalling output)
"14": Solid State Relais; max. 58 Vdc / 40 Vac / 100 mA
"S3“: 24 Vdc, 20 mA, short circuit proof; high = OK, low = min. one channel tripped
Approvals
Approvals cURus, cULus, GL cURus, cULus, GL cURus, cULus, GL cURus, cULus, GL
Environment
Storage temperature -25 °C to +85 °C -25 °C to +85 °C -25 °C to +85 °C -25 °C to +85 °C
Ambient temperature -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C
Derating - - - -
Type of cooling Natural convection Natural convection Natural convection Natural convection
Required minimum spacing (left/right) 0 mm 0 mm 0 mm 0 mm
Required minimum spacing (over/under) 40 mm 40 mm 40 mm 40 mm
Safety and protection
Protection index
IP 20 IP 20 IP 20 IP 20
Safety class
III, without PE connection III, without PE connection III, without PE connection III, without PE connection
Degree of pollution 2 2 2 2
Order numbers
Order Number PM-0724-240-0 PM-0724-400-0 PM-0724-400-2 PM-0748-200-0
+
-
Power supplies
Electronic circuit breakers
2
Electronic circuit breaker with thermomagnetic characteristic
ECONOMY SMART
Typ PM-0712-200-0 PM-0712-400-0 PM-0724-120-0 PM-0724-200-0
Input
Input rated voltage 12 Vdc 12 Vdc 24 Vdc 24 Vdc
Input voltage range 10 - 16 Vdc 10 - 16 Vdc 18 - 30 Vdc 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 % 3 % 3 % 3 %
Required input voltage for turning-on of outputs 10.5 V (Turn-off Threshold 10 V) 10.5 V (Turn-off Threshold 10 V) 19.5 V (Turn-off Threshold 18 V) 19.5 V (Turn-off Threshold 18 V)
Max. total input current 20 A 40 A 12 A 20 A
Max. input current for each pole of terminal 40 A 40 A 40 A 40 A
Over voltage protection Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 33 V
Stand-by current 44 mA @ 12 V 44 mA @ 12 V 35 mA @ 24 V 35 mA @ 24 V
Power losses in stand-by mode 0.53 W @ 12 V 0.53 W @ 12 V 0.84 W @ 24 V 0.84 W @ 24 V
Output
Output rated voltage 12 Vdc 12 Vdc 24 Vdc 24 Vdc
Output rated current 2 x 2 - 10 A 4 x 2 - 10 A 2 x 1 - 6 A 2 x 2 - 10 A
Maximum voltage drop between input and output 200 mV @ 2 x 10 A 200 mV @ 4 x 10 A 120 mV @ 2 x 6 A 200 mV @ 2 x 10 A
Initialization time of module 250 ms 250 ms 250 ms 250 ms
Turn-on delay of outputs Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s Load dependent, min. 50 ms / max. 5 s
Waiting periode after switch-off of an output 500 ms (short circuit) ... 10 s (overload) 500 ms (short circuit) ... 10 s (overload) 500 ms (short circuit) ... 10 s (overload) 500 ms (short circuit) ... 10 s (overload)
Max. power losses 5.3 W @ 2 x 10 A 10 W @ 4 x 10 A 2.5 W @ 2 x 6 A 5.5 W @ 2 x 10 A
Efficiency 99.0 % 99.0 % 99.0 % 99.0 %
Internal output fuse 15 A 15 A 15 A 15 A
Resistance to reverse feed max. 35 Vdc 35 Vdc 35 Vdc 35 Vdc
Parallel use of outputs Not allowed Not allowed Not allowed Not allowed
Serial use of outputs Not allowed Not allowed Not allowed Not allowed
Signaling
Status indicator LED (red, green, orange) LED (red, green, orange) LED (red, green, orange) LED (red, green, orange)
Signal input S1 DC 12-24 V (On/Off/Reset) DC 12-24 V (On/Off/Reset) DC 24 V (On/Off/Reset) DC 24 V (On/Off/Reset)
Signal output S2 DC 12 V, max. 25 mA
Signal output S3 DC 12 V, max. 25 mA
Approvals
Approvals - cURus, cULus, GL cURus, cULus, GL cURus, cULus, GL
Environment
Storage temperature -25 °C to +85 °C -25 °C to +85 °C -25 °C to +85 °C -25 °C to +85 °C
Ambient temperature -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C
Derating - - - -
Type of cooling Natural convection Natural convection Natural convection Natural convection
Required minimum spacing (left/right) 0 mm 0 mm 0 mm 0 mm
Required minimum spacing (over/under) 40 mm 40 mm 40 mm 40 mm
Safety and protection
Protection index
Safety class
Degree of pollution 2 2 2 2
Order numbers
Order Number PM-0712-200-0 PM-0712-400-0 PM-0724-120-0 PM-0724-200-0
(status output channels)
(Common signalling output)
IP 20 IP 20 IP 20 IP 20
III, without PE connection III, without PE connection III, without PE connection III, without PE connection
DC 12 V, max. 25 mA (status output channels)
DC 12 V, max. 25 mA (Common signalling output)
DC 24 V, max. 25 mA (status output channels)
DC 24 V, max. 25 mA (Common signalling output)
DC 24 V, max. 25 mA (status output channels)
DC 24 V, max. 25 mA (Common signalling output)
Subject to change