Block EB-2724-2020-0, EB-2724-2040-0, EB-2724-2060-0, EB-2724-2080-0, EB-2724-2120-0 Catalog Page

...
Power supplies
1.1
1.2
5.1
1.3
2.1
2.2
3.1
3.2
3.3
5.2
4.0
Electronic circuit breakers
2
2-Channel circuit breaker
EasyB 2-Channel
General Data
Efficiency up to 99 %
Multi-coloured LED and status display button
Up to 40 fuse channels stackable side by side
With thermomagnetic characteristic
Ambient temperature -25 °C to +55 °C / +70 ° C
Protection index IP 20
Advantages
Compact design - 2 independent channels in 12 mm width
Automatic channel assignment
Additional load outputs through output expanders mountable side by side
Applications
Electronic circuit breaker with thermomagnetic characteristic with alarm signal forwarded for tripped and switched off channels to the connected channels. Starter version with fuse for 24 V loads.
StandardsZ
Safety: EN 60950-1, EN 50178, EN/IEC 60204-1
EMC: EN 61000-6-2 (interference immunity), EN 61000-6-3 (emitted interference)
CE acc. to 2014/30/EU
Approvals J Z
UL 508 (prepared), UL 2367 (prepared), GL (prepared)
Subject to change
365
+
-
2-Channel circuit breaker
EasyB 2-Channel
Typ EB-2724-2120-0 EB-2724-2160-0
Special features
Available from
Q2 2017 Q2 2017
Input
Input rated voltage 24 Vdc 24 Vdc
Input voltage range 18 - 30 Vdc 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 % 3 %
Max. total input current 12 A 16 A
Max. input current for each pole of terminal 10 A (-), 40 A (+) 10 A (-), 40 A (+)
Required input voltage for turning-on of outputs 17.5 V (Turn-off Threshold 16.7 V),
± 0.7 V
17.5 V (Turn-off Threshold 16.7 V), ± 0.7 V
Max. power losses 0,6 W 0,9 W
Over voltage protection Suppressor diode 33 V Suppressor diode 33 V
Stand-by current 12 mA @ 24 V 12 mA @ 24 V
Power losses in stand-by mode 0,3 W @ 24 V 0,3 W @ 24 V
Turn on capacity 70 mF @ 24 Vdc / 2,5 mm² / 2,5 m 70 mF @ 24 Vdc / 2,5 mm² / 2,5 m
Output
Output rated voltage 24 Vdc 24 Vdc
Output rated current 2 x 6 A 2 x 8 A
Maximum voltage drop between input and output 54 mV 72 mV
Initialization time of module 27 ms 27 ms
Turn-on delay of outputs 0 ms 0 ms
Waiting periode after switch-off of an output 500 ms (Short circuit) 5 s (Overload) 500 ms (Short circuit) 5 s (Overload)
Parallel use of outputs Not allowed Not allowed
Serial use of outputs not allowed not allowed
Resistance to reverse feed max. 35 Vdc 35 Vdc
Efficiency 99.0 % 99.0 %
Output limited current - -
Signaling
Bus communication
Collective notification signal bypassed Collective notification signal bypassed
Status indicator LED (red, green, orange) LED (red, green, orange)
Signal output Output status, short circuit proof
high = Channel on, low = Channel off, fault
Output status, short circuit proof high = Channel on, low = Channel off, fault
Signal output (ON/OFF/Reset) - -
Environment
Type of cooling Natural convection Natural convection
Ambient temperature -25 °C +70 °C -25 °C +55 °C
Storage temperature -25 °C ... +85 °C -25 °C ... +85 °C
Derating - -
Relative humidity 5 96 %, without condensation 5 96 %, without condensation
Required minimum spacing (left/right) 0 mm 0 mm
Required minimum spacing (over/under) 30 mm 30 mm
Safety and protection
Protection index
IP 20 IP 20
Safety class
III, without PE connection III, without PE connection
Degree of pollution 2 2
Order numbers
Order Number EB-2724-2120-0 EB-2724-2160-0
+
-
Power supplies
Electronic circuit breakers
2
2-Channel circuit breaker
EasyB 2-Channel
Typ EB-2724-2020-0 EB-2724-2040-0 EB-2724-2060-0 EB-2724-2080-0
Special features
Available from
Input
Input rated voltage 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Input voltage range 18 - 30 Vdc 18 - 30 Vdc 18 - 30 Vdc 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 % 3 % 3 % 3 %
Max. total input current 2 A 4 A 6 A 8 A
Max. input current for each pole of terminal 10 A (-), 40 A (+) 10 A (-), 40 A (+) 10 A (-), 40 A (+) 10 A (-), 40 A (+)
Required input voltage for turning-on of outputs 17.5 V (Turn-off Threshold 16.7 V),
Max. power losses 0,4 W 0,4 W 0,4 W 0,4 W
Over voltage protection Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 33 V Suppressor diode 33 V
Stand-by current 12 mA @ 24 V 12 mA @ 24 V 12 mA @ 24 V 12 mA @ 24 V
Power losses in stand-by mode 0,3 W @ 24 V 0,3 W @ 24 V 0,3 W @ 24 V 0,3 W @ 24 V
Turn on capacity 70 mF @ 24 Vdc / 2,5 mm² / 2,5 m 80 mF @ 24 Vdc / 2,5 mm² / 2,5 m 80 mF @ 24 Vdc / 2,5 mm² / 2,5 m 80 mF @ 24 Vdc / 2,5 mm² / 2,5 m
Output
Output rated voltage 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Output rated current 2 x 1 A 2 x 2 A 2 x 3 A 2 x 4 A
Maximum voltage drop between input and output 24 mV 29 mV 33 mV 34 mV
Initialization time of module 27 ms 27 ms 27 ms 27 ms
Turn-on delay of outputs 0 ms 0 ms 0 ms 0 ms
Waiting periode after switch-off of an output 500 ms (Short circuit) … 5 s (Overload) 500 ms (Short circuit) … 5 s (Overload) 500 ms (Short circuit) … 5 s (Overload) 500 ms (Short circuit) … 5 s (Overload)
Parallel use of outputs Not allowed Not allowed Not allowed Not allowed
Serial use of outputs not allowed not allowed not allowed not allowed
Resistance to reverse feed max. 35 Vdc 35 Vdc 35 Vdc 35 Vdc
Efficiency 99.0 % 99.0 % 99.0 % 99.0 %
Output limited current - - - -
Signaling
Bus communication
Status indicator LED (red, green, orange) LED (red, green, orange) LED (red, green, orange) LED (red, green, orange)
Signal output Output status, short circuit proof
Signal output (ON/OFF/Reset) - - - -
Environment
Type of cooling Natural convection Natural convection Natural convection Natural convection
Ambient temperature -25 °C … +70 °C -25 °C … +70 °C -25 °C … +70 °C -25 °C … +70 °C
Storage temperature -25 °C ... +85 °C -25 °C ... +85 °C -25 °C ... +85 °C -25 °C ... +85 °C
Derating - - - -
Relative humidity 5 … 96 %, without condensation 5 … 96 %, without condensation 5 … 96 %, without condensation 5 … 96 %, without condensation
Required minimum spacing (left/right) 0 mm 0 mm 0 mm 0 mm
Required minimum spacing (over/under) 30 mm 30 mm 30 mm 30 mm
Safety and protection
Protection index
Safety class
Degree of pollution 2 2 2 2
Order numbers
Order Number EB-2724-2020-0 EB-2724-2040-0 EB-2724-2060-0 EB-2724-2080-0
Q2 2017 Q2 2017 Q2 2017 Q2 2017
17.5 V (Turn-off Threshold 16.7 V),
± 0.7 V
Collective notification signal bypassed Collective notification signal bypassed Collective notification signal bypassed Collective notification signal bypassed
high = Channel on, low = Channel off, fault
IP 20 IP 20 IP 20 IP 20
III, without PE connection III, without PE connection III, without PE connection III, without PE connection
± 0.7 V
Output status, short circuit proof high = Channel on, low = Channel off, fault
17.5 V (Turn-off Threshold 16.7 V), ± 0.7 V
Output status, short circuit proof high = Channel on, low = Channel off, fault
17.5 V (Turn-off Threshold 16.7 V), ± 0.7 V
Output status, short circuit proof high = Channel on, low = Channel off, fault
Subject to change