Black Box crcw-12, crcw24 User Manual

Cold Row™ Chilled Water (CW) Engineering Manual
This precision data center air-conditioning system uses the latest, state-of-the-art control technology.
CRCW-24
Customer
Support
Information
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical support 24 hours a day, 7 days a week: Call 724-746-5500 or fax 724-746-0746 Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018
Web site: w ww.blackbox.com • E-mail: info @blackbox.com
724-746-5500 | blackbox.com
Trademarks Used in this Manual
Trademarks Used in this Manual
Black Box and the Double Diamond logo are registered trademarks, and Cold Row is a trademark, of BB Technologies, Inc.
Armaflex is a registered trademark of Armacell Enterprise GmBH.
UL is a registered trademark of Underwriters Laboratories.
Any other trademarks mentioned in this manual are acknowledged to be the property of the trademark owners.
Page 2
724-746-5500 | blackbox.com
Table of Contents
Table of Contents
1. About the Cold Row CW ......................................................................................................................................................4
2. Features ...............................................................................................................................................................................5
3. Configurations ....................................................................................................................................................................... 7
4. Technical Data ....................................................................................................................................................................... 8
5. Performance, Electrical, and Sound Data ...............................................................................................................................9
6. Dimensional Data ................................................................................................................................................................13
7. Product Features .................................................................................................................................................................. 15
8. Product Guide Specifications ...............................................................................................................................................16
724-746-5500 | blackbox.com
Page 3
724-746-5500 | blackbox.com
Chapter 1: About the Cold Row CW
1. About the Cold Row CW
Designed for scalability, reliability, and seamless integration into new or existing data centers; the rack cooling systems are suitable for use in open and contained hot-aisle and cold-aisle configurations. The models covered in this manual are ideal for hot-spot cooling in small- to enterprise-size data centers.
Typical applications include:
• Internet/Web hosting
• Telecommunications
• Financial/banking
• Insurance
• Airlines/mass transit
• Legal services
• Entertainment
• Government
• Colleges/universities
• Data centers
• Computer/LAN rooms
• Telecommunications rooms
• Co-location centers
• Internet service providers (ISPs)
• Applications service providers (ASPs)
• Hospital operating and isolation rooms
Page 4
724-746-5500 | blackbox.com
Chapter 2: Features
2. Features
Chilled water (CW) is supplied to the Cold Row CW unit via a building chiller or other chilled water plant. Chilled water has high
affinity for heat, making it a very efficient cooling method. The E² controller enables independent valve and fan control so the unit can adjust immediately, and precisely, to varying heat loads and optimize energy efficiency.
Two models are available:
Table 2-1. Available models.
Produc t Code Produc t Name
CRCW-12 Cold Row CW, 12"
CRCW-24 Cold Row CW, 24"
The Cold Row CW offers the following features:
• Highest cooling capacities in the industry.
• 12" and 24" cabinet width.
• 3 EC fans: Independently and infinitely adjustable EC fans ensure maximum efficiency.
• Used in containment, open architecture, and hot spot reduction applications.
• Adapts to both high- and low-density IT environments.
• Wide range of cooling capacities available.
• 100% front and rear service access.
• Adapts to all major manufacturers' racks and rack containment systems.
• Integrates seamlessly with all Building Management Systems (BMS) platforms.
• Private VLAN (pLAN) link to 8 units without a BMS.
• High airflow with low noise.
• Built-in redundancy and capacity assist functions.
• Top and bottom piping options.
• Casters and leveling feet included.
• Indoor use only.
• Installation on raised and non-raised floors.
724-746-5500 | blackbox.com
Page 5
724-746-5500 | blackbox.com
Chapter 2: Features
Chiller
(Full Capacity
or Tr im )
Cold Row CW
Chilled Water
Pump
Closed Loop
Cooling Tower
Figure 2-1. Traditional cooling example.
Chiller
Cooling Tower Pump
Chilled Water Pump
Cold Row CW
Page 6
Figure 2-2. Hybrid-free cooling diagram.
724-746-5500 | blackbox.com
Open Aisle
Containment with
Side Discharge
Chapter 3: Configurations
3. Configurations Open Aisle Configuration
Open aisle configuration organizes racks in a single row or in hot and cold aisle rows, but without containment. The Cold Row CW draws hot air from the external environment or hot aisle, removes the heat, and supplies cooled air to the front of IT equipment in the cold aisle.
Cold Aisle
Containment with
Front Discharge
Cold Aisle Containment
Cold aisle containment captures cooled air from the Cold Row CW and prevents it from mixing with hot air. The front of IT equipment is accessed in the contained cold aisle. The Cold Row CW draws hot air from the external environment, removes the heat, and supplies cooled air back into the contained cold aisle.
724-746-5500 | blackbox.com
Page 7
724-746-5500 | blackbox.com
Chapter 4: Technical Data
4. Technical Data
Table 4-1. CW System Technical Data.
Model 12" Chilled Water, CRCW-12 24" Chilled Water, CRCW-24
Chilled Water Control Valve
2-Way (Standard) — Modulating
Valve Pressure Rating — psi 400 400
Close-off Pressure Rating — psi 200 200
3-Way (optional) — Modulating
Valve Pressure Rating — psi 400 400
Close-off Pressure Rating — psi 200 200
Chilled Water Coil — Aluminum Fin, Copper Tube
2
Rows/ Face Area (ft.
) 4/5.8 4 /11 .6
Face Velocity, fpm 500 500
Blower/Motor — Backward Curved Direction Driven EC
Horsepower (Each) 1 /4 H . P. 1- 1/ 4 H .P.
CFM 2,900* 5,800
Quantity of Blowers 3 3
Drive Method Direct Direct
Humidification: Electrode Steam Canister Humidifier with Adjustable Output (Optional)
lb./ hr. (KW input) N/A 5 (1.7)
Std Control N/A Proportional
Washable Filters
Nom. Size (in.) (Qty,) 10.5 x 37.38 x 0.43 (2) 22.0 x 37.37 x 0.43 (2)
Connection Sizes (Copper)
Condensate Drain (w/pump) 1/2" FP T 1/2" FPT
Humidifier Inlet N/A 1/4" OD
Water In/ Out 1-1/4" NP T 1-1/ 2" N PT
Physical Data
Approx. Weight (lb.) 384 550
Dimensions: (H" x W" x D") 78.5" x 11.6" x 42.1" 78.5" x 23.4" x 42.1"
Approx. Shipping Weight 570 7 11
Approx. Shipping Dimensions:
(H" x W" x D")
84" x 22" x 4 8" 84" x 32" x 48"
*NOTE: When 110v/Ph/60 Hz power input is selected, unit airflow is reduced by 200 CFM, which will result in capacity reduction
of 3.5% or less.
724-746-5500 | blackbox.com
Page 8