Bird Technologies 8890-320 User Manual

Page 1
TERMALINE® LOAD RESISTOR
SERIES 8890
©
Copyright 2012
Instruction Book Part Number 920-8890S Rev. D
by Bird Electronic Corporation
®
and Tenuline® are Registered Trademarks
of Bird Electronic Corporation
Page 2
I am not blank
Page 3

Safety Precautions

The following are general safety precautions that are not necessarily related to any specific part or procedure, and do not necessarily appear elsewhere in this publication. These precautions must be thoroughly understood and apply to all phases of operation and maintenance.
WARNING
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety precautions. Do not replace
components or make adjustments to the inside of the test equipment with the high voltage
supply turned on. To avoid casualties, always remove power.
WARNING
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is present.
WARNING
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure for the purpose of
service or adjustment of equipment except in the presence of someone who is capable of
rendering aid.
WARNING
Safety Earth Ground
An uniterruptible earth safety ground must be supplied from the main power source to test
instruments. Grounding one conductor of a two conductor power cable is not sufficient
protection. Serious injury or death can occur if this grounding is not properly supplied.
WARNING
Resuscitation
Personnel working with or near high voltages should be familiar with modern methods of
resuscitation.
WARNI NG
Remove Power
Observe general safety precautions. Do not open the instrument with the power on.

Safety Symbols

WARNING
Warning notes call attention to a procedure, which if not correctly performed, could result
in personal injury.
CAUTION
Caution notes call attention to a procedure, which if not correctly performed, could result
in damage to the instrument.
Note: Calls attention to supplemental information.
i
Page 4
This symbol indicates that a shock hazard exists if the precautions in the instruction manual are not followed.
The caution symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
This symbol indicates that the unit radiates heat and should not be touched while hot.
This symbol appears on the equipment and indicates the requirement for separate collection of discarded electrical and electronic equipment in accordance with the European Union Directive 2002/96/EC.

Warning Statements

The following safety warnings appear in the text where there is danger to operating and mainte­nance personnel, and are repeated here for emphasis.
WARNING
The vent plug must be used at all times when the unit is operating or cooling. Failure to do
so could result in an explosion or severe burns.
On page 5 and 6.
WARNI NG
Never attempt to connect or disconnect RF equipment from the transmission line while RF
power is being applied. Leaking RF energy is a potential health hazard.
On page 7, 9, 11, 13 and 14.
WARNING
Turn off AC power and RF power when attaching the power cable.
On page 8.
WARNING
Disconnect the blower assembly from supply voltage before performing any maintenance.
On page 13
WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized
from multiple sources. The potential for electric shock exists.
On page 14, 15, 16 and 17.
WARNING
Do not operate with side panel removed. Doing so could result in personal injury.
On page 14.
ii
Page 5

Caution Statements

The following equipment cautions appear in the text and are repeated here for emphasis.
CAUTION
This load is designed for operation in a horizontal position only, with the vent plug up. Do
not use in any other manner.
On page 5.
CAUTION
Do not contaminate the coolant with pipe sealant.
On page 6.
CAUTION
If installed, connect optional interlock before applying RF power.
On page 6.
CAUTION
Check the local electrical code for proper AC hookup prior to operation of the unit. Make
sure the neutral or return hookup is only used for that purpose.
On page 8.
CAUTION
Make sure the interlock is properly connected when overloaded to prevent damage to the load.
On page 9.
CAUTION
Maximum power is 1,250 W when the blower is not running. If the indicator light should
turn off, immediately reduce RF power to less than 1,250 W.
On page 11.
CAUTION
Use only Bird coolant, P/N 5-1070, to prevent damage to the load.
On page 15.
iii
Page 6

Safety Statements

USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT ENDOMMAGER LE DISPOSITIF DE PROTECTION DE L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
iv
Page 7
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE - TRAINED PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
v
Page 8
CONNECT INTERLOCK TO TRANSMITTER BEFORE OPERATING.
BRANCHER LE VERROUILLAGE À L'ÉMETTEUR AVANT EMPLOI.
CONECTE EL INTERBLOQUEO AL TRANSMISOR ANTES DE LA OPERACION.
VOR INBETRIEBNAHME VERRIEGELUNG AM SENDER ANSCHLIESSEN.
PRIMA DI METTERE IN FUNZIONE L'APPARECCHIO, COLLEGARE IL DISPOSITIVO DI BLOCCO AL TRASMETTITORE.
vi
Page 9

About This Manual

This manual covers the operating and maintenance instructions for the following models
Note: When used in the rest of the manual, 8890 series refers to all models. 889x–300 refers only to loads without a blower. –315 and –320 refer to loads with attached blowers.
Model Number
Connector
Female LC 8890-300 8890-315 8890-320 3-1/8" EIA Flanged 8891-300 8891-315 8891-320 1-5/8" EIA Flanged 8892-300 8892-315 8892-320 1-5/8" EIA Unflanged 8895-300 8895-315 8895-320 3-1/8" Unflanged, Flush Center, 51.5 3-1/8" Unflanged, Flush Center 8897-300 8897-315 8897-320 3-1/8" Unflanged, Recessed Center 8898-300 8898-315 8898-320 Digital, 3-1/8" EIA Flanged 8891D300 Digital, 1-5/8" EIA Flanged 8892D300 8892D320 Digital, Female 13-30 8892D13-30
Ω 8896-300
Without
Blower
Blower,
115 VAC
Blower,
230 VAC

Changes to this Manual

We have made every effort to ensure this manual is accurate. If you discover any errors, or if you have suggestions for improving this manual, please send your comments to our Solon, Ohio fac­tory. This manual may be periodically updated. When inquiring about updates to this manual refer to the part number and revision on the title page.

Literature Contents

Chapter Layout

Introduction - Describes the features of the Bird SignalHawk, lists equipment supplied and
optional equipment, and provides power-up instructions.
Theory of Operation - Describes how to use the SignalHawk’s PC Tool for the Vector Net-
work Analysis function and how to transfer readings from the SignalHawk to the computer and back again.
Operation without Blower - Describes procedures require for operating the load resistor. Operation with Blower - Describes procedures require for operating the load resistor
equipped with a blower unit.
Maintenance - Lists routine maintenance tasks as well as troubleshooting for common prob-
lems. Specifications and parts information are also included.
vii
Page 10
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Warning Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii
Changes to this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii
Literature Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii
Chapter Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii
Chapter 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Items Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Items Required but not Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Chapter 2 Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Load Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Thermal Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Blower Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Setting Up the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installing the Thermoswitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installing the Interlock Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connecting RF Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using a “QC” Connector Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using a 13-30 Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using a Swivel Flanged Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Using a Unflanged Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Using an AC Power Hookup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 4 Operating Instructions, No Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating Under Abnormal Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shutting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 5 Operating Instructions, With Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Blower Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating Under Abnormal Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Shutting Down the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
viii
Page 11
Chapter 6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cleaning the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cleaning the Load Resistor q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cleaning the Blower Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Inspecting the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Measuring the DC Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Inspecting the Coolant Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Repairing the Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Replacing the RF Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Replacing the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Replacing the Indicator Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Replacing the Load Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Replacing the Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Storage and Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Storing the Load Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Shipping the Load Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Available “QC” Type Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ix
Page 12
x
Page 13

Chapter 1 Introduction

The Bird 8890 series loads are portable, 50 ohm, coaxial RF transmission line terminations, designed for frequency ranges of DC – 2.4 GHz. The 8890 series D loads are designed for use in the UHF (470 – 860 MHz) band, otherwise they are identical to the stanard series. These loads provide accurate and dependable low reflection line termina­tions. Power is dissipated at a level of up to 2500 watts of RF, 5000 watts if the optional blower assembly is used.
The 8890 series –300 is the basic load. The –315 and –320 models consist of a load with an installed blower assem­bly for 115 or 230 VAC lines, respectively.
The load has a coolant chamber surrounded by radiator fins. The front and rear fins form mounting flanges which can be used as supports for freestanding use or as brackets for fixed mounting. A vent plug at the top of the unit relieves internal pressure from coolant expansion. The load’s simple and rugged design minimizes maintenance requirements.

Items Supplied

Load Resistor
Note: Pre-filled with coolant at the factory
Shipping Plug
Vent Plug
Instruction Manual

Items Required but not Supplied

Coupling Kit: Connects the load to the RF line

Optional Accessories

Bird BA-310 Blower Assembly: Doubles the RF power capacity of the load. Includes control thermoswitch
and detachable 3-wire power cable (without male plug for 230 Vac cable)
Note: The blower and control thermoswitch are standard on the –315 and –320 loads.
Interlock Thermoswitch: Automatically shuts off the transmitter to prevent overheating of the load.
1
Page 14

Figure 1 Bird 8890 Series Outline Drawing - No Blower

MTG. HOLE
DETAIL
3/8”
(9 mm)
3/16”
(5 mm)
3/8”
(10 mm)
!
4.5”
(114 mm)
7.5”
(190 mm)
(4) MTG. HOLES
SEE DETAIL
21.5”
(546 mm)
17.25”
(437 mm)
3”
(75 mm)
DEPENDS ON CONNECTOR
VENT PLUG
INTERLOCK THERMOSWITCH (OPTIONAL)
FAN CONTROL THERMOSWITCH
POWER CORD 20 ft (6 m) LONG APPROX.
!
BLOWER
ON
AUTOMATIC
MANUAL
MANUAL /
AUTOMATIC
SWITCH
INDICATOR
LIGHT
21-7/8”
(556 mm)
4-7/8”
(124 mm)
7-7/8”
(199 mm)

Figure 2 Outline Drawing With Blower

2
Page 15

Chapter 2 Theory of Operation

O-ring seal
O-ring seal
DETAIL “A” ­Shipping Plug
DETAIL “B” ­Vent Plug

Load Resistor

Bird 8890 series loads consist of a thin-film-on-ceramic resistor immersed in a dielectric coolant. The resistor, individu­ally selected for its accuracy, is enclosed in a special housing. When surrounded by the coolant, this produces a uni­form, practically reflectionless line termination over the specified frequencies.

Coolant

The load is cooled by natural fluid and air convection currents. The coolant, chosen for its dielectric and thermal characteristics, carries heat from the resistor to the walls of the cooling tank, where radiator fins surrounding the tank transfer the heat to the air.
When the coolant is heated, thermal expansion causes an increase in the internal pressure. The vent plug (Figure 3, Detail “B”) relieves this pressure while protecting the opening from dirt or other contaminants.

Thermal Interlock

When installed, a passive, normally closed over-temperature thermoswitch opens above the maximum safe load temperature of 236 °C (457 °F), turning off transmitter power. The interlock will not permit use of the transmitter until the load has reached a safe temperature.

Blower Assembly

When installed, the blower assembly provides forced airflow with two blowers. Baffles direct the airflow from the blowers over the radiator fins, doubling the heat transfer efficiency.
Example - A 2.5 kW load will safely dissipate 5 kW. A passive, normally open control thermoswitch closes when the coolant reaches 155 °C (311 °F), turn­ing the fans on.
The baffles interfere with the free flow of normal air currents, causing a 50% reduction in heat transfer efficiency if the forced airflow is stopped. Thus, a 2.5 kW load will have its maximum power dissipation reduced to 1.25 kW.

Figure 3 Blower Plugs

3
Page 16
4
Page 17

Chapter 3 Installation

Unpacking and Inspection

1. Carefully inspect shipping container for signs of damage.
2. Do one of the following:
If the shipping container is damaged, do not unpack the unit.
Note: Immediately notify the shipping carrier and Bird Technologies Group.
If the shipping container is not damaged, unpack the unit. Save shipping materi-
als for repackaging.
3. Inspect unit for visual signs of damage.
Note: If there is damage, immediately notify the shipping carrier and Bird Elec­tronic Corporation.

Setting Up the Load

Note: Before first using the load, get a resistance baseline for future maintenance. Refer to "Measuring
the DC Resistance" on page 14.
1. Remove the shipping plug from the load.
2. Install the vent plug.
Note: Refer to Figure 3 on page 3 for pictures of the plugs.
WARNING
The vent plug must be used at all times when the unit is operating or cooling. Failure to
do so could result in an explosion or severe burns.

Mounting the Load

CAUTION
This load is designed for operation in a horizontal position only, with the vent plug up. Do not use in any other manner.
Bird 8890 series Loads are equipped for either portable use or fixed installation. The mounting brackets on the front and rear faces have four mounting slots arranged in a 4
3
a
⁄8" (9.53 mm) diameter max.
1
⁄2" x 2023⁄32" rectangle (114.3 x 526.3 mm). Use a screw with
Place the load in a dry, dust and vibration free environment.
Do not use outdoors or in areas of condensing humidity.
Allow at least 12" (30 cm) of clearance on all sides of the load.
5
Page 18

Installing the Thermoswitch

Bird 8890 series series Loads can be equipped with an optional interlock thermoswitch, P/N 8890-008. It is normally closed, opening at 236 °C (457 °F), with a rating of 10A at 120VAC and 5A at 230VAC.
Note: A control thermoswitch, P/N 2450-085, is used to control the optional blower assembly. It is normally open, closing at 155 °C (311 °F), with a rating of 10A @ 120VAC and 5A @ 230VAC.
WARNING
The vent plug must be used at all times when the unit is operating or cooling. Failure to do so could result in an
explosion or severe burns.
1. Remove the vent plug.
2. Install the shipping plug.
3. Stand the unit on its back with the connector end up.
Note: In this position there is no danger of the coolant pouring out through the socket plug hole.
4. Do one of the following:
For Interlock Thermoswitch:
Remove the socket plug just above the connector assembly with a wrench. See “Installing the Interlock Connection” on page 6.
9
⁄16" hex
For Control Thermoswitch:
Remove the top socket plug with a
5. Replace the plug with the thermoswitch.
6. Apply pipe sealing compound sparingly to ONLY the external threads of the thermo­switch.
9
⁄16" hex wrench.
7. Check for coolant leaks upon completion.

Installing the Interlock Connection

If installed, connect optional interlock before applying RF power.
1. Unscrew the large knurled ring-nut (A) at the lower end of the coupling jack assembly.
2. Pull the large knurled nut off the thermoswitch jack (B).
3. Unscrew the small knurled cover fitting from the base plug (D) of the connector to release the base.
4. Thread the control switch wires through the clamp (E) with the washers (F) inside and with its threaded fitting in place.
5. Service the control switch wire with short tips and put spaghetti sleeves over the wire ends if necessary.
CAUTION
Do not contaminate the coolant with pipe sealant.
CAUTION
6
Page 19
6. Securely solder the control switch leads to the lugs (G) of the connector base.
Note: The ring-nut (A) must be in place over the base plug (D) with the knurled end facing out.
7. Screw on the cover ring, then fasten the cable clamp (E) in place and tighten both yoke screws (H).
8. Put the plug back on the thermoswitch and tighten the nut (A).
Figure 4 Thermoswitch Assembly

Connecting RF Power

Note: After installing the load, the RF transmission line can be attached using standard coaxial line cou-
pling kits.
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being
applied. Leaking RF energy is a potential health hazard.

Using a “QC” Connector Coupling

Use a 50 ohm coaxial cable such as RG-218/U or -220/U (-17A or -19A), appropriate for the frequency and power level of operation.
Note: Use a cable connector which will mate with the one on the load.

Using a 13-30 Coupling

Use 50 ohm coaxial cable such as RG-8A/U, RG-9U, RG-213/U, or equivalent with a male 13-30 plug.
7
Page 20

Using a Swivel Flanged Coupling

BOLT BULLET LOADRF COAXIAL LINE
RF COAXIAL
LINE
CLAMPING
BANDS
CONNECTOR
SLEEVE
BULLET
LOAD
1. Insert the center bullet.
2. Push it in until it is fully seated.
3. Connect the coaxial input in a straight line
4. Push, carefully, on the center conductor to close.
5. Insert the bolt sets and tighten evenly all around to transmission line manufacturer’s recommended torque.
Figure 5 Swivel Flanged Coupling

Using a Unflanged Coupling

1. Insert the center bullet
2. Push until it sets the midpoint nibs.
3. Position the outer sleeve, with clamping bands, over the input connector.
4. Set the transmission line snugly against the coupling stops.
5. Position the clamping bands evenly about 3/4” from the ends of the sleeve.
6. Tighten the clamping bands.
Figure 6 Unflanged Coupling
Note: The swivel flange on the load makes connection independent of the orientation of the fixed flange on the coaxial input outer conductor.
Note: Use all of the bolts.

Using an AC Power Hookup

WARNING
Turn off AC power and RF power when attaching the power cable.
CAUTION
Check the local electrical code for proper AC hookup prior to operation of the unit. Make sure the neutral or return
hookup is only used for that purpose.
AC power is only required if the blower assembly is installed. The AC power supply required is 115/230 V, depending on the blower, @ 50/60 Hz, 1φ. The blower is equipped with an IEC 320 “cold” (65 °C) AC inlet.
8
Page 21

Chapter 4 Operating Instructions, No Blower

Normal Operation

Bird 8890 series– 300 loads have no indicators or operating controls. They require no special operating procedures or sur­veillance when their performance limits are not exceeded. Follow the instructions for the specific transmitter equipment.

Operating Under Abnormal Conditions

The load can be moderatly overloaded for short periods.
CAUTION
Make sure the interlock is properly connected when overloaded to prevent damage to the load.

Shutting Down

Note: These loads are passive devices, so have no way of being turned off. Turn off RF power at the source.
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.

Emergency Shutdown

Turn off RF power at the source.
Note: If the interlock thermoswitch is properly connected, RF power will be automatically turned off when the coolant temperature reaches an unsafe level.
9
Page 22
10
Page 23

Chapter 5 Operating Instructions, With Blower

CAUTION
Maximum power is 1,250 W when the blower is not running. If the indicator light should turn off, immediately
reduce RF power to less than 1,250 W.
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being
applied. Leaking RF energy is a potential health hazard.

Blower Controls

Bird 8890 series –310 and –320 Loads are equipped with a control switch and indicator light on the front of the blower assembly. The switch is labelled MANUAL/AUTOMATIC.
When the switch is set to MANUAL, the fans run continuously.
When set to AUTOMATIC, the fans turn on when the coolant reaches a preset temperature.
Note: The indicator light, labeled BLOWER ON, turns on whenever the unit is connected to AC power.

Normal Operation

1. Ensure the indicator light is on.
2. Set the switch to MANUAL for a few moments.
3. Ensure the fans are working properly.
4. Set the switch back to AUTOMATIC.
5. Apply RF power.

Operating Under Abnormal Conditions

The load can be subjected to higher power levels for short intervals. If this is likely, make sure the interlock is properly con­nected to prevent damage to the load.
Note: A properly connected interlock will prevent overload.
If the indicator light turns off or the fans stop unexpectedly, do one of the following:
Immediately turn off RF power.
Reduce the RF power to less than 1,250 W.
Note: Refer to "Troubleshooting" on page 13 to correct the problem.

Shutting Down the Load

1. Turn off RF power at the source.
2. Wait approximately 15 minutes, or for the fans to stop running.
Note: This will allow the load to cool without causing heat stress.
3. Turn off the blower.

Emergency Shutdown

Turn off RF power at the source.
Note: If the interlock thermoswitch is properly connected, RF power will be automatically turned off when the coolant temperature reaches an unsafe level.
11
Page 24
12
Page 25

Chapter 6 Maintenance

This chapter covers cleaning, inspection, trouble-shooting, and specifications for the Bird 8890 series Loads.
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being
applied. Leaking RF energy is a potential health hazard.
WARNING
Disconnect the blower assembly from supply voltage before performing any maintenance.

Troubleshooting

The table below contains troubleshooting information for problems which can occur during normal operation. This manual cannot list all malfunctions that may occur, or their corrective actions. If a problem is not listed or is not cor­rected by the listed actions, notify a qualified service center.
Problem Possible Cause Correction
No air flow from blowers; “BLOWER ON” light off.
No air flow from blowers; “BLOWER ON” light on.
Air flow from blowers; “BLOWER ON” light off.
Leaking coolant. Loose clamping band. Tighten the clamping band.
High or low DC resistance.
Overheating radiator. RF power too high. Lower RF power. See “Specifications” on page 20 for
Unplugged power cable. Connect the power cable. No AC power. Make sure AC power is properly connected and turned
Fuse burnout. Replace fuse after correcting the burnout cause. See
Fan obstructed by bent grill. Straighten the grill. Fan motors overheated. Clean the grill and fan blades. See “Cleaning the Load
Fan motors burnt out. Replace the fan motors (See “Replacing the Fan” on
Lamp burnout. Replace lamp. See “Replacing the Indicator Light” on
Defective or improperly installed O-ring.
Loose RF input connector. Tighten connector. Faulty RF input connector. Model 8890: Replace connector. See “Replacing the RF
Faulty resistor. Replace the resistor. See “Replacing the Load Resistor”
Coolant level too low. Check the coolant level. Add coolant if necessary. See
Coolant degraded. Replace the coolant. See “Inspecting the Coolant Level”
Faulty control thermoswitch (blower only).
Faulty resistor. Replace the resistor. See “Replacing the Load Resistor”
on.
“Replacing the Fuse” on page 16.
Resistor” on page 14.
page 17).
page 16.
Replace the O-ring. See “Replacing the Load Resistor” on page 17.
Connector” on page 16. All other models: Return the unit for service.
on page 17.
maximum RF power.
“Inspecting the Coolant Level” on page 15.
on page 15. Replace control thermoswitch. See “Installing the
Thermoswitch” on page 6.
on page 17.
13
Page 26

Maintenance

Cleaning the Load

Cleaning the Load Resistor

The outside surface of the instrument should be wiped free of dust and dirt when necessary.
Clean the cooling fins.
Note: Excessive dust on the cooling fins will interfere with heat dissipation.
Clean the RF connector, both metallic and insulating surfaces, with a dry, non-residue forming solvent.

Cleaning the Blower Assembly

The intake grills, fans, and inside of the baffles should be wiped free of dust and dirt when necessary.
Note: Excessive dust will interfere with heat dissipation.
When the blower assembly is installed, it will be necessary to partially disassemble the blower to clean the load’s radiator fins.
WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized from multiple sources.
The potential for electric shock exists.
WARNING
Do not operate with side panel removed. Doing so could result in personal injury.
1. Unscrew both 10-32 truss head screws that secure one of the side baffles and remove it.
2. Clean the load
3. Secure the side baffle with the 10-32 truss head screws.
4. Repeat Steps 1-3 for the other side baffle.

Inspecting the Load

Inspect the unit every six months.
a. Check for coolant leakage around the clamping band. b. Check for coolant leakage around the thermoswitch. c. Check for corrosion.

Measuring the DC Resistance

Measuring the dc resistance between the inner and outer conductors of the RF connector shows changes in the load over time, a good check of the load resistor’s condition. Under normal operating conditions, the resistor should pro­vide at least 5,000 hours of operation before requiring any additional service. DC resistance tracking must start before the load is put into service, and should be measured annually.
Perform the following steps and record the value for future comparison. Make sure that you have an ohmmeter with an accuracy of ±1% at 50 ohms and that the load temperature is between 20 and 25 °C (68 to 77 °F) before starting.
WARNING
Never attempt to connect or disconnect RF equipment from the transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
14
Page 27
1. Turn off the RF power and interlock circuitry.
2. Disconnect the RF line.
3. Connect the multimeter test leads to the center and outer conductor of the load resistor.
4. Compare the measured value with the previous measurement and with the baseline resistance, measured when the load was put into service.
Note: If the new value differs from either of these by more than 1 ohm this could indicate a failing resistor.
Figure 7 Measuring Resistance

Inspecting the Coolant Level

Coolant lifetime will vary greatly depending on the operating temperature.
Heavy Use (full RF power for long times, high ambient temperature, 50 Hz AC supply):
Inspect the coolant every 500 hours.
Light Use (fraction of full power, low ambient temperature, 60 Hz AC supply):
Inspect coolant every 2,000 hours.
Note: Correct any coolant leakage before inspection. See “Troubleshooting” on page 13.
WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized from multiple sources.
The potential for electric shock exists.
Coolant lifetime will vary greatly depending on the operating temperature. For heavy use (full RF power for long times, high ambient temperature), check the coolant every 500 hours. If the load has only had light duty (fraction of full power, low temperature), then inspection may only be necessary every 2,000 hours.
Note: Correct any coolant leakage before inspection. (See “Troubleshooting” on page 11).
1. Remove the load resistor (Refer to “Load Resistor” on page 18).
Use only Bird coolant, P/N 5-1070, to prevent damage to the load.
2. Inspect the coolant.
n
CAUTION
The coolant should be clear, with a faint yellow tinge, and have a slightly sweet
smell. If it is black with a burnt or acrid smell, drain it and add about 2.9 gal (11 L) of coolant.
With the load still on end, the coolant level should be 4
below the top surface of the resistor assembly mounting ring, at ambient tem­perature.
3. Add coolant if necessary.
3
⁄4 to 5 inches (125 mm)
15
Page 28

Repairing the Load

WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized from multiple sources.
The potential for electric shock exists.

Replacing the RF Connector

ONLY the Model 8890 has a special Bird “QC” connector which allows easy changing of the RF connector. This does not disturb the coolant seal or affect the electrical continuity of the load. To change the connector, proceed as follows:
1. Remove the four screws at the corners of the RF connector.
2. Pull the connector straight out.
3. Push the new connector in. Make sure that the center pin on the connector is prop­erly seated in the mating socket on the load.
4. Replace the screws.
Note: If not using the LC connector normally supplied, the frequency and power must be limited to the capabilities of the connector.

Replacing the Fuse

Note: Correct the fuse burnout cause. Common causes include stuck or blocked fans or a short circuit in the
motor or blower wiring. See “Troubleshooting” on page 13.
WARNING
Disconnect the unit from all power sources before servicing. The unit may be energized from multiple sources.
The potential for electric shock exists.
Note: The fuse is located in the AC module on the back of the blower.
1. Press the locking tab on the fuse drawer.
2. Remove the drawer.
3. Replace the fuse.
4. Push the drawer into the AC module until it locks into place.

Replacing the Indicator Light

1. Remove the four 8-32 pan head screws from the front and back of the base frame.
2. Pull the fan guard straight off the bottom.
3. Remove the quick disconnects on the light.
4. Unscrew the retaining sleeve.
5. Remove the light unit.
6. Remove the lens while pressing both locking tabs.
7. Release the lamp by pressing the housing’s center slot with a small screwdriver.
8. Push the new lamp into the housing until it snaps into place.
9. Replace the lens.
10. Put the light unit back in place.
11. Secure the fan guard with the 8-32 pan head screws.
Note: See “Specifications” on page 20 for fuse type and current rating.
Note: If the fans still do not run or if the fuse burns out again, return the
blower assembly to the factory.
16
Page 29

Replacing the Load Resistor

1. Remove the vent plug.
2. Install the shipping plug.
3. Stand the unit on its back with the connector end up.
4. Unscrew and remove the clamping band.
5. Lift the load resistor assembly out of the tank.
6. Allow any coolant to drip back into the tank.
7. Check the O-Ring.
8. Replace the entire load resistor assembly.
9. Put the clamping band in place and tighten it.
10. Remove the shipping plug.
11. Install the vent plug.

Replacing the Fan

Note: In this position there is no danger of the coolant pouring out through
the socket plug hole.
Note: It should be free of twists and positioned evenly around the flange of the resistor housing.
Note: If the O-ring shows signs of deterioration (e.g. is no longer pliable or has surface cracks) replace it.
Note: It cannot be further disassembled.
WARNI NG
Disconnect the unit from all power sources before servicing. The unit may be
energized from multiple sources. The potential for electric shock exists.
1. Remove the four 8-32 pan head screws from the front and back of the base frame.
2. Pull the fan guard straight off the bottom.
3. Carefully unsolder the color coded connecting wires.
Note: Note the connections for resoldering.
4. Remove the four fan mounting screws.
5. Remove the defective fan.
Note: Be careful not to lose the lipped retaining washers.
6. Insert the replacement fan with the fan blade assembly facing down, towards the fan guard grill.
7. Insert the mounting screws and retaining washers into the mounting holes.
8. Turn the washers so that the lipped portion fits over the rim of the fan frame.
9. Tighten the screws.
Note: If the fan replaced is the one closest to the power socket, reattach the green ground wire to the closest mounting screw.
10. Solder the connecting wires to the solder lugs on the motor unit according to the color coding.
11. Replace the fan guard and screws.
Note: Before reattaching the blower assembly to the load, check the fans for free and unimpeded movement of the blades.
12. Connect the unit to AC power.
13. Set the switch to MANUAL.
14. Ensure that the fans work properly.
15. Set the switch back to AUTOMATIC.
17
Page 30
Figure 8 Schematic Diagram
N L
L1
L2
L1
L2
ROTATION
FANS
GRN/YEL
AC
RECEPTACLE
WHT/YEL
TO CONTROL
THERMOSWITCH
BLACK
RED
TOGGLE SWITCH
WHT/BLK
WHT/BLK
INDICATOR
LIGHT
WHT/BLK

Storage and Shipment

Storing the Load Resistor

Cover Bird 8890 Loads before storing to keep out dust and dirt.
It is not necessary to install the shipping plug.
Store in a dry, dust-free environment where the ambient temperature will remain between –40 and +45 °C
(–40 to +113 °F).

Shipping the Load Resistor

18
1. Remove the vent plug.
2. Install the shipping plug.
3. Wrap the vent plug with padding and tape it to the side of the load for protection.
Note: With the shipping plug installed, it is not necessary to empty out the coolant.
4. Wrap the connector in padding.
5. Pack and brace the load in a sturdy wooden crate for shipment.
Page 31

Customer Service

Any maintenance or service procedure beyond the scope of those in this chapter should be referred to a qualified service center.
If you need to return the unit for any reason, request an RMA through the Bird Technologies website (link shown below). All instruments returned must be shipped prepaid and to the attention of the RMA number.
Bird Service Center
30303 Aurora Road Cleveland (Solon), Ohio 44139-2794 Fax: (440) 248-5426 E-mail: bsc@bird-technologies.com
For the location of the Sales Office nearest you, visit our website at:
http://www.bird-technologies.com
19
Page 32

Specifications

Frequency Range
8891D300, 8892D300, 8892D13-30, 8892D320
470 – 860 MHz
All other models
Power Rating
*
Peak Power for Pulse Width
1 µs
10 µs
100 µs 1000 µs 5000 µs
DC – 2.4 GHz
2500 W continuous duty 150 kW 115 kW
80 kW 54 kW 22 kW
Impedance
8896 All other models
VSWR
51.5 ohms 50 ohms
8891D300, 8892D300, 8892D13-30, 8892D320 All other models
**
1.065 DC – 1 GHz 1.1 1 – 2 GHz 1.25 2 – 2.4 GHz 1.3
Connectors
8890 8891, 8891D300 8892, 8892D300, 8892D320 8892D13-30 8895 8896 8897 8898
Female LC 3-1/8” EIA flanged 1-5/8” EIA flanged Female 13-30 1-5/8” EIA unflanged 3-1/8” unflanged (flush center) 3-1/8” unflanged (flush center) 3-1/8” unflanged (recessed center)
AC Power
–315 –320
115 V ±10% @ 50/60 Hz ±3% 230 V ±10% @ 50/60 Hz ±3%
AC Line Power Rating 460 W max
IEC (5 x 20 mm) Type T
Fuse Rating
115 Va c 230 Vac
1 A 500 mA
Thermoswitch
Interlock Fan Control
Normally closed. Opens at 236 °C (457 °F) Normally open. Closes at 155 °C (311 °F)
Thermoswitch Rating
115 Va c 230 Vac
10 A
5 A
Ambient Temperature –40 to +45 °C (–40 to +113 °F) Altitude
††
1520 m (5000 ft.)
Humidity 95% noncondensing max Cooling method Oil dielectric and convection currents Dimensions
Without blower With blower
21.75" L x 7.5” W x 17.25" H (551 x 190 x 437 mm)
21.75" L x 7.5” W x 21
7
" H (551 x 190 x 556 mm)
8
Weight, Nominal 59 lb. (27 kg) Finish Grey Powder Coat
* Power rating with blower installed and operating: 5000 W
Power rating with blower installed and NOT operating: 1250 W † Set the duty factor so that the average power rating of the load is not exceeded. ‡ VSWR measured using a female N connector.
** For models 8890-300, -315, and -320 VSWR Measured using a female N connector
†† Derate RF power by 2.5% for every 305m (1,000 ft.) above 1,520m (5,000 ft.).
20
Page 33

Replacement Parts

RF load resistor
8890 8891 8891D300 8892, 8892D300 8892D13-30 8895 8896 8897 8898
Resistor O-Ring 1 5-230 Clamping band assembly 1 2430-055 Plug
Vent Shipping
Overtemp thermoswitch 1 8890-008
Thermoswitch body 1 8890-005 Thermoswitch jack 1 2450-018
Control thermoswitch
Thermoswitch body 1 2450-086 Thermoswitch jack 1 2450-018
Coolant, 2.9 gal (11 liters) 1 5-1070 Radiator assembly 1 2450-313 Access plug 3/4"-14 hex socket 1 5020-103 Blower assembly, BA-300
115 VA C 230 VAC
Blower assembly, BA-310
115 VA C 230 VAC
Description Qty Part Number
1
8890A050 8891-050 8891-071 8892-015 8862-017 8896-015 8896-031 8897-003 8898-006
1
2450-094 2450-049
*
*
1 2450-085
1
BA-300-115 BA-300-230
1
BA-310-115 BA-310-230
* Optional on the –300, standard on the –315 and –320 † Optional on the –300
21
Page 34

Available “QC” Type Connectors

Connector Part Number
BNC-Female 4240-125
BNC-Male 4240-132
C-Female 4240-100
C-Male 4240-110
HN-Female 4240-268
HN-Male 4240-278
LC-Female
LC-Male 4240-025
Open Term.# 10-32 Nut 4240-080
LT-Female 4240-018
LT-Male 4240-012
N-Female 4240-062
N-Male 4240-063
*
4240-031
SC-Female 4240-090
SMA-Female 4240-336
SMA-Male 4240-334
7/16 Jack, IEC Type 169-4 4240-344
7/16 Plug, IEC Type 169-4 4240-363
Mini UHF-Female 4240-346
UHF-Female 4240-050
UHF-Male 4240-179
1-5/8” EIA Fixed 4240-096
1-5/8” EIA Swivel 4240-208
7/8” EIA 4240-002
TNC-Female 4240-156
TNC-Male 4240-160
* Normally supplied on the 8890
22
Page 35

Limited Warranty

All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one year, unless otherwise specified, from date of shipment and to conform to applicable specifications, draw­ings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or repairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, draw­ings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transportation-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. Routine (regularly required) calibration is not covered under this limited warranty. In addition, Seller’s warranties do not extend to the failure of tubes, transis­tors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the origi­nal manufacturer’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHAT-SOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGATION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
19
Page 36
20
Loading...