Bird Technologies 8630B User Manual

INSTRUCTION BOOK
MODULOAD
SERIES 8630 AND 8630B
®
RF LOAD RESISTOR
Bird® Electronic Corporation 30303 Aurora Road Cleveland (Solon), Ohio 44139
Sales email: sales@bird-technologies.com
Technical Support email: techsupport@bird-technologies.com
Moduload
866-695-4569 toll free
©Copyright 2006 by Bird Electronic Corporation
Instruction Book P/N 920-8630S Rev. G
®
, Econoload®, Econoline®, and Thruline® are
registered trademarks of Bird Electronic Corporation
I am not blank

Safety Precautions

The following are general safety precautions that are not necessarily related to any specific part or procedure and do not necessarily appear elsewhere in this publication. These precautions must be thoroughly understood and applied to all phases of operation and maintenance.
Keep Away From Live Circuits
Operating personnel must at all times observe normal safety regulations. Do not replace components or make adjustments inside the equipment with high voltage turned on. To avoid casualties, always remove power.
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is present.
Do Not Service Or Adjust Alone
Under no circumstances should any personnel reach into an enclosure for the purpose of service or adjustment of equipment except in the presence of someone who is capable of rendering aid.
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the main power source to test instruments. Grounding one conductor of a two conductor power cable is not sufficient protection. Serious injury or death can occur if this grounding is not properly supplied.
Chemical Hazard
Dry cleaning solvents for cleaning parts may be potentially dangerous. Avoid inhalation of fumes or prolonged contact with skin.
Resuscitation
Personnel working with or near high voltages should be familiar with modern methods of resuscitation.
i
Bird 8630B Series Moduload RF Load Resistor
Safety Symbols
Warning notes call attention to a procedure, which if not correctly
performed, could result in personal injury.
Caution notes call attention to a procedure, which if not correctly
performed, could result in damage to the instrument.
This symbol indicates that a shock hazard exists if the precautions in the instruction manual are not followed.
The caution symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
WARNING
CAUTION
This symbol indicates that the unit radiates heat and should not be touched while hot.
NOTE: Calls attention to supplemental information.
Warning Statements
The following safety warnings appear in the text where there is danger to operating and maintenance personnel and are repeated here for emphasis.
WARNING
Never attempt to connect or disconnect RF equipment from the
transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
WARNING
Ethylene glycol is a toxic material. Do not take internally. Avoid eye
contact. Inhaling the vapors may be irritating to the lungs.
Caution Statements
The following equipment cautions appear in the text whenever the equipment is in danger of damage and are repeated here for emphasis.
CAUTION
This equipment is designed for operation in a horizontal position only,
with mounting brackets down. Do not operate in any other manner.
ii
CAUTION
Before any RF operation of the load is attempted, the transmitter
interlock and ac line attachment to the equipment must be made. First
attach the transmitter interlock connections to the two binding posts on
the front panel and then connect the power cable.
CAUTION
The 115 V or 230 Vac line may be connected, but the ac power must not
be turned on unless coolant is in the system and filled to the correct
level. Damage to the pump will result otherwise.
CAUTION
Operation without sufficient coolant can damage the unit.
CAUTION
Do not use any sealant, leak-stopping material, or automotive antifreeze
in the coolant. Use only distilled water and pure ethylene glycol.
CAUTION
Do not attempt to alter the flow switch setting or disturb the coolant pump.
CAUTION
Do not operate the load without connecting the interlock. Even
momentary application of power to the load while the cooling
circulation is off, or possibly functioning improperly, will cause almost
immediate destruction of the resistor element.
CAUTION
Do not apply more than the rated RF power to the load. Excessive RF
power will damage the load resistor.
CAUTION
Do not block air flow. Air enters the housing through the circular fan
openings and exhausts through the grille opposite.
CAUTION
Do not disconnect the line power first. Even a momentary application of
RF power to the load while the cooling circulation is off will cause
almost immediate destruction of the resistor element.
iii
Bird 8630B Series Moduload RF Load Resistor
CAUTION
Do not remove any fittings from the water chamber. The elbows could
be damaged, and it may be difficult to restore them to their original
positions while keeping a water-tight seal. Check the switch for free
operation. Flush and clean with mild detergent if necessary, and rinse
thoroughly in clear water
CAUTION Before storing the unit, follow the storage instructions in the Storage section of the Maintenance chapter. Failure to follow the instructions
may result in damage to the unit.
CAUTION
Before shipping the unit, follow the shipping instructions in the
Maintenance chapter. Failure to properly prepare the unit for shipping
may result in damage to the unit.
iv
Safety Statements
USAGE ANY USE OF THIS INSTRUMENT IN A MANNER NOT
SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE
INSTRUMENT’S SAFETY PROTECTION. USO EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA
POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM
HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
UTILISATION TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS
EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT ENDOMMAGER LE DISPOSITIF DE PROTECTION DE L’INSTRUMENT.
IMPIEGO QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO
DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
SERVICE SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE -
TRAINED PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO
DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
v
Bird 8630B Series Moduload RF Load Resistor
WARTUNG ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR
FÜR GESCHULTES FACHPERSONAL. ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS,
SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE
RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE
ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
vi

About This Manual

This instruction book covers the 8630B Series Moduload RF Load Resistors, which specificaly covers the models listed below:
8631-115 8631-115-5-N 8635-115-5 8638-115 8638-230-6 8631-230 8631-230-6-N 8635-230-6 8638-230 8638-115-5-N 8631-115-5 8635-115 8635-115-5-N 8638-115-5 8638-230-6-N 8631-230-6 8635-230 8635-230-6-N
8631B-115 8635B-115-5 8638B-115 8631B-230 8635B-230-6 8638B-230 8631B-115-5 8635B-115 8638B-230-6 8631B-230-6 8635B-230 8638B-115-5
This instruction book is arranged so that essential information on safety is in the front of the book. Reading the Safety Precautions before operating the equipment is strongly advised. The remainder of this instruction book is divided into Chapters and Sections.
Operation
First time operators should read Chapter 1 - Introduction, Chapter 2 ­Theory of Operation, and Chapter 3 - Installation to get an overview of equipment capabilities and how to install it. An experienced operator can refer to Chapter 4 - Operating Instructions. All instructions necessary to operate the equipment are contained in this chapter.
Maintenance
All personnel should be familiar with preventative maintenance found in Chapter 5 - Maintenance. If a failure should occur, the trouble-shooting section will aid in isolating and repairing the failure. Parts lists and repair instructions are also in this chapter.
Changes To The Manual
We have made every effort to ensure this manual is accurate at the time of publication. If you should discover any errors or if you have suggestions
vii
Bird 8630B Series Moduload RF Load Resistor
for improving this manual, please send your comment to our factory. This manual may be periodically updated. When inquiring about updates to this manual, refer to the part number and revision level on the title page.
viii
Naming Conventions
The following terms will be used throughout this manual to refer to certain components of the Moduload:
Moduload: The entire unit.
Load: The component which connects to the RF line. It is connected to the HEAT
EXCHANGER with two hoses. It contains the RESISTOR.
Heat Exchanger: The component containing the pump, blower, coolant
reservoir, control panel, and electrical access box. It is connected to the LOAD with two hoses.
Resistor: A subcomponent of the LOAD. This is the ceramic resistor which
actually absorbs the RF power.
ix
Bird 8630B Series Moduload RF Load Resistor
x

Table of Contents

Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
About This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Purpose and Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Performance Characteristics and Capabilities . . . . . . . . . . . . . . . . . . . . . . . 1
Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Power and Utility Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Items Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Items Required but not Supplied. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Optional Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Heat Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Flow Interlock Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Site and Shelter Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Filling Coolant Reservoir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Blower Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DC Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Interlock Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
AC Line Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connecting RF Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model 8631 and 8631B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model 8635 and 8635B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model 8638 and 8638B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
xi
Preliminary Equipment Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Meter Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 15
Use and Function of Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Initial Adjustments and Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Equipment Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Normal Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Performance Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Radiator Surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connector and Outside . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Measure Load DC Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Routine Service Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Flushing the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
RF Load Resistor Unit Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pump/Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Time Delay Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Replace Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Load Resistor Internal Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Resistor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Resistor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Replacement of Fractured Resistor or Damaged Internal Parts. . . . . . . . . . . . 31
Resistor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Input Center Conductor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Final Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
xii
Storage and Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
xiii
xiv

Chapter 1 Introduction

This publication refers to the Moduload RF Load Resistor Series 8630 and 8630B. The differences between models are listed in the specifications. All models will generally be referred to as a load throughout this manual.
The information in this instruction book pertains to all models except noted differences referred to in the text.
This chapter contains intoductory information including items supplied, items required, unpacking, inspecting, and the specifications.
Purpose and
Function
Performance
Characteristics
and Capabilities
The Bird Moduload Loads are self-cooling, low reflection, non­radiating terminations for high power 50 ohm RF transmission lines.
They are for use on CW, AM, FM, SSB, and TV modulation envelopes, and within certain limits on radar or pulse modes. Information for use involving pulse type signals should be obtained directly from Bird Electronic Corporation.
The 8630 and 8630B series Loads are capable of continuous power dissipation of 10 kW with a voltage standing wave ratio (VSWR) of less than 1.1 to 1.0 from 1 kHz to 1000 MHz. The respective models provide direct connection to 3-1/8 inch and 1-5/8 inch 50 ohm coaxial lines.
The equipment consists of three basic systems: the RF load assembly, the control system, and the heat exchanger system. The load assembly contains the resistor element with its internal water cooling system. The control system includes the electrical circuitry required to prevent damage to the transmitter in case of malfunction of the load, and to protect the RF load should the water flow slow down. The heat exchanger components consist essentially of the pump/motor, the side blower, the coolant collector tank, and a finned cooling coil unit opposite the blower.
When used in conjunction with the appropriate Bird Model Thruline Wattmeter, such as those in the 4600A, 4800A or 4712 series, the Moduload Coaxial Load may be used for direct RF power measurements within the equipment ratings.
1
Bird 8630B Series Moduload RF Load Resistor
Dimensions and
Weight
Power and Utility
Requirements
Environmental
Requirements
The 8630 and 8630B Series load is 22-1/8 inches long, exclusive of the connector, 15-13/16 inches wide, and 15-15/16 inches high (562 x 402 x 405 mm). Its net weight, filled with 100 percent water as coolant, is 113 lb (51.3 kg) and the shipping weight is 125 lb (56.7 kg).
The 8630 and 8630B Series loads are offered in four standard forms which differ in the ac input power requirements.
y -115 for 115 V, 60 Hz, 9 Amp, single phase. y -230 for 230 V, 50 Hz, 4.5 Amp, single phase. y -115-5 for 115 V, 50 Hz, 9 Amp, single phase. y -230-6 for 230 V, 60 Hz, 4.5 Amp, single phase.
The 8630 and 8630B Series loads are not intended for use outdoors where they would be exposed to the elements. They should be used indoors in a clean, dry, dust and vibration-free environment. The ambient temperature range is determined by the coolant. For 100 percent water the range is +5°C to +45°C (+41°F to +113°F). For a mixture of 65 percent water and 35 percent ethylene glycol the range is -20°C to +35°C (-4°F to +95°F).
It is important that the room temperature remain within these limits for proper operation of the unit, otherwise a derating of its load value will be necessary. To avoid this derating, it may be necessary to arrange for venting of the air flow from the load to the outside. Consult Bird Electronic Corporation for more details.

Items Supplied The 8630 and 8630B Series loads are equipped with standard RF

connectors.
y Model 8630 and 8631B — 3-1/8 inch EIA flanged connector. y Model 8630 and 8635B — 1-5/8 inch EIA flanged connector. y Model 8630 and 8638B — 3-1/8 inch unflanged connector.
They are supplied with a container of ethylene glycol, for making the coolant mixture, when ordered.
Items Required but
not Supplied
The required items are:
y A mating connector on the coaxial transmission line. y A conveniently located ac power receptacle to plug in the power
cable.
y Distilled water for coolant, or coolant mixture.
2
Tools and Test
Equipment
Only simple tools such as screwdrivers and wrenches are needed for disassembling a Moduload load resistor. A multimeter or an ohmmeter with an accuracy of 1 percent or better at 50 ohms is suggested for checking the DC resistance of the RF load resistor. A basic VOM will suffice for checking the rest of the circuitry.

Optional Items Dolly, P/N 6771-011 — For ease in moving the load. Consult Bird

Electronic Corporation for more information.
3
Bird 8630B Series Moduload RF Load Resistor
Figure 1
Bird 8630 and
8630B Series
Outline Drawing
GENERANT
NOMINAL
20-5/16 (516mm)
22-1/8 (562mm)
21-5/16 (541mm)
10' AC CABLE
PROVIDED
(405mm)
15-15/16
VENT PLUG
FILLER PLUG
R.F.LOAD
3-1/8" FLANGED
3-1/2
(89mm)
(402mm)
15-13/16
AIR
FLOW
29/32 (23mm)
GENERANT
7-29/32 (201mm)
NOMINAL
15-13/16 (402mm)
AC ON
INTERLOCK
230VAC 8AMP
60Hz 3AB
3/32
14"
SEE DETAIL FOR (4)
(356mm)
MOUNTING HOLES
FREQUENCY RANGE 1KHz-1GH z
WATTS 10,000 OHMS 50
MODEL 8631-230-6 SERIAL
1 PHASE 60Hz 4.5 AMPS
AC LINE SUPPLY 230 VOLTS
CAUTION
(2.4mm)
3/8
(10mm)
DETAIL: FULL SCALE
4

Chapter 2 Theory of Operation

The 8730 Series style Econoload Coaxial load resistor installed in this unit is unique in having its water supply primarily directed over the outer, wet film type, resistive coating of the substrate. This eliminates the need for an intermediate heat transfer system, reducing the load size to a minimum. The absence of intermediate cooling fluids considerably simplifies the construction and sealing of this unit. It can be readily disassembled in the field for resistor element replacement (refer to the Chapter 5 - Maintenance).

Heat Transfer The 50 ohm resistor consists of a substrate which has a permanently

deposited resistive film, covered by a thin layer of electrically nonconductive material. The heat generated by the absorped RF power is transferred from the film to the water which flows over it through a restricted chamber surrounding the resistor body. This water, first carried to the front of the load resistor, passes over the entire length of the resistor and discharges through the sealed water chamber at the rear. The composite dielectric characteristics and the distinctive design of these enclosures provide an accurate 50 ohm termination over the specified frequency range of this load - 1 kHz to 1000 MHz.
Flow Interlock
Control Circuit
The interlock control circuit provides instantaneous fail-safe protection of the transmitter and Moduload in the event of even momentary interruption of the coolant supply. This protection is necessary because dissipation of the heat generated by the RF power is critically dependent on a required minimum water flow of 2.5 gallons (9.5 liters) per minute at all times, regardless of the coolant temperature.
CAUTION
Do not attempt to alter the flow switch setting or disturb the
coolant pump.
The water flow switch, installed directly on the coolant input line to the load resistor, is a “normally open” type; i.e. its electrical contacts open when deactivated. Closed during equipment operation, the switch is adjusted to open when the coolant flow drops below the minimum. When the water flow switch contacts open, the time delay switch is deactivated, which at once opens the interlock switch, causing immediate transmitter shutdown. Also, the centrifugal impeller of the pump is carefully selected for the necessary flow rate.
5
Bird 8630B Series Moduload RF Load Resistor
The proper operation of this equipment depends on these conditions being maintained.
The time delay relay keeps the interlock switch open for a predetermined interval (set at about 2 seconds, nominal), to allow the minimum flow of 2.5 gallons per minute to be established. This safeguard feature ensures proper operation of the cooling system before RF power is applied to the load, preventing resistor damage or burnout. As an additional safeguard, an over temperature thermoswitch, normally closed at or below +85°C (+185°F) for the 8630 series and at or below +79°C (+174°F) for the 8630B series, is wired in series with the flow switch for protection from overheating due to overloading of the load.
6

Chapter 3 Installation

This chapter provides information for on-site requirements, unpacking, inspection, and preparing the load for use.
CAUTION
This equipment is designed for operation in a horizontal position only,
with mounting brackets down. Do not operate in any other manner.
The 8630 and 8630B series load is to be installed, and operated, in a horizontal position. The unit is shipped horizontal, and normally stands on its attached base brackets.
Unpacking and
Inspection
Site and Shelter
Requirements

Mounting

1. Carefully inspect the shipping container for signs of damage. If damage is noticed, do not unpack the unit. Immediately notify the shipping carrier and Bird Electronic Corporation.
2. If the container is not damaged, unpack the unit. Save the packing materials in case the unit should need to be shipped again.
3. Inspect all of the components for visible signs of damage. Immediately notify the shipping carrier and Bird Electronic Corporation of equipment damage or missing parts.
The load may be operated anywhere that adequate ac line power and ventilation are available, and ambient temperatures do not exceed those given in the specifications.
Note: 10 kW being equivalent to 34,000 Btu/h (8568 kilogram- calories/
hr), a sufficient quantity of air must be provided. Allow room for unobstructed air intake on the side facing the fan grille, and a clearance of two or three feet beyond the grille outlet opposite.
For installation of the equipment, mounting angle brackets are attached to the front, and back edges of the enclosure. They may be removed by unscrewing the four 8-32 Phillip Truss head screws holding each bracket. These brackets have two slots each on the 14" x 21-15/16" (356 x 557 mm) centers to accommodate four 1/4" screws that may be used for mounting the unit.

Coolant

Before shipment, the Moduload is drained of coolant to avoid possible damage in transit from freezing. The system must be refilled with coolant before it can be put into operation. The unit operates with 10
7
Bird 8630B Series Moduload RF Load Resistor
pints (4.74 liter) of coolant. The coolant must be either; distilled water or a mixture of distilled water and ethylene glycol.
Ethylene glycol is toxic. Do not take internally. Avoid contact with
eyes, skin, and clothing. Avoid breathing vapor. Wash thoroughly
Use only distilled water or the supplied ethylene glycol as coolant.
Do not use tap water, automotive antifreeze, sealants, or leak
stopping material. Use of these materials will damage the
Distilled water is the primary coolant for the Bird 8630 and 8630B. Ethylene glycol should be added to prevent bacterial growth and freezing; 10% – 35% ethylene glycol is recommended. Using at least 10% will prevent bacteria growth and 35% will protect against freezing to –20°C.
WARNING
after handling.
CAUTION
instrument and void all warranties.
Filling Coolant
Reservoir
Figures 3 and 4 shows the coolant’s freezing point for a given percentage of ethylene glycol in the mix. The following example shows the weights to make a 65% distilled water to 35% ethylene glycol mixture in 1 and 5 gallon quantities.
Ingredient 1 Gal. (3.78 L) 5 Gal. (18.9 L) Distilled Water Ethylene Glycol
5.6 lb (2.54 kg) 28.0 lb (12.7 kg)
3.0 lb (1.39 kg) 15.2 lb (6.9 kg)
The load’s electrical and thermal performance is impaired by impurities or additives in the coolant. Impurities which accumulate as scale on the resistor surface are especially damaging. Only use distilled water or a mixture of distilled water and ethylene glycol as coolant. To ensure proper mixing add the water first, then the ethylene glycol.
The Bird 8630 and 8630B has a coolant capacity of about 10 pints (4.74 liter). To fill the coolant, follow these steps:
CAUTION
Operation without sufficient coolant can damage the unit.
1. Make sure the drain plug is in place. Check that the hose connections are correct and properly tightened.
2. Remove the filler cap on top of the unit.
8
Installation
3. Pour approximately 4 pints (2.0 Liters) of coolant in the unit.
4. Turn on the motor, for only a few seconds, to pull the liquid into the system and draw the coolant level down to the bottom of the tank. Do not run the pump too long, as partially dry operation may damage its mechanism.
Note: A convenientt method is to watch the coolant level through
the reservoir filler. Stop the pump when the coolant level approaches the bottom of the tank.
5. Repeat filling in the above manner twice more, with about 3 pints (1.5 liters) each time, or until the fluid remains steady at the proper level. The unit should be full to a level of about 2-7/8 inches (73 mm) below the top face of the filler tube opening, or to the high mark on the gauge. Add coolant if necessary to bring to the required level.
6. Run the unit for about five minutes to remove any trapped air in the system.
7. Recheck the fluid level before applying RF power.
Note: The filler plug is equipped with a breather vent to relieve internal
pressure caused by the heated coolant. It is normally closed, but is set to open at 2 lb/in impurities or other chemical additives in the cooling liquid. Therefore, the cooling liquid should be distilled water, with pure industrial grade ethylene glycol added if required, and should be kept clean at all times.
Introducing contaminates from unsuitable coolant liquids could coat the cooling system components, particularly the resistor surface. This would unfavorably affect the thermal performance and VSWR of the load. When this is suspected always check the VSWR. General scale accumulation is not likely unless the load resistor is used outside the unit, with an improper water supply. If the coolant system has been contaminated, flush it out according to the instructions in the Maintenance Chapter.

Blower Fan The fan is wired direct to the ac line input and will always operate

along with the pump when the ac line power is turned on.

DC Resistance Before the unit is put into operation, check the DC resistance. Refer

to the Maintenance chapter for complete details and instructions.
2
. The electrical performance of the load is affected by
9
Bird 8630B Series Moduload RF Load Resistor
0
y
0
C
0
Figure 2
4
Freezing Point of
Ethylene Glycol / Water Mixture °F
20
0
-20
-40
Specifications for ethylene glycol
Temperature, Degrees Fahrenheit
-60 having: specific gravity 1.125 @
32°F; specific heat .575 @ 68°F
-80
10 20 30 40 50 60
% Eth
lene Glycol
Figure 3
Freezing Point of
Ethylene Glycol /
Water Mixture °C
-10
-20
elsius
-30
-40
Temperature, Degrees
Specifications for ethylene glycol
-50 having: specific gravity 1.125 @
32°F; specific heat .575 @ 68°F
-60
10 20 30 40 50 6
% Ethylene Glycol
10
Installation
Interlock
Connections
AC Line
Attachment
A terminal strip provides connection to the transmitter’s internal safety interlock circuitry. An active interlock state occurs as a result of either high coolant temperature or no coolant flow. It will also be active for about 2 seconds after power up.
Interlock connections are made to the terminal strip on the front of the unit.
1. Use number 22 AWG (or heavier) wire for interlock connections. Attach solderless ring terminals to the wire ends to ensure safe operation, and to ease installation.
2. Connect the interlock wires to the interlock terminal strip as required for the transmitter in use.
CAUTION Before any RF operation of the load is attempted, the transmitter interlock and ac line attachment to the equipment must be made.
First attach the transmitter interlock connec tions to the two
binding posts on the front panel and then connect the power cable.
CAUTION
The 115 V or 230 Vac line may be connected, but the ac power must
not be turned on unless coolant is in the system and filled to the
correct level. Damage to the pump will result otherwise.
Before applying ac power to the unit, make sure:
y Coolant is in the system. y Coolant is filled to the correct level. y The green wire at the supply end is fastened to ground.
The ac power supply may be either 115 or 230 V depending on the unit requirements. AC line power is supplied to the 3-wire ac panel module socket by means of the 10 foot cable and matching socket that is furnished with the equipment. The third wire in the cable, coded green, is the ground. For proper protection, if a 3-wire type plug and outlet is not used, fasten the green wire at the supply end to a satisfactory ground.
11
Bird 8630B Series Moduload RF Load Resistor

Connecting RF Power

After installing the load, the RF transmission line can be attached using standard coaxial line coupling kits.
Never attempt to connect or disconnect RF equipment from the
transmission line while RF power is being applied.
Connect the coaxial RF transmission line to the unit. For the respective 8630 and 8630B Series models the connections are as follows:
WARNING
Leaking RF energy is a potential health hazard.
Model 8631 and
8631B
Model 8631 and 8631B - 3-1/8" EIA, 50 ohm, swivel flanged. Refer to Figure 4 while following the instructions below.
1. Use 3-1/8" EIA Coupling Kit, Bird P/N 4600-020, which includes six 3/8-16 x 1-1/2" bolt and nut sets, O-Ring, and insulated center bullet.
2. Insert the center bullet, push into seat insulator in facing, and install the O-Ring in the groove if required.
3. Connect the coaxial input in a straight line, push in carefully to close. The swivel flange on the load makes connection independent of a fixed flange on the coaxial input line.
4. Insert bolt sets around the flange connection, and tighten evenly.
Figure 4
Connecting RF
Power Model 8631
and 8631B
RF Coaxial Line 3/8-16 x 1-1/2 Bolt Bullet RF Load Connector
Model 8635 and
12
8635B
Model 8635 and 8635B - 1-5/8" EIA Coupling Kit, Bird P/N 4712-020, which includes four 5/16-18 x 1-1/2" large bolt and nut sets, O-Ring, and anchor bullet. The assembly procedure is the same as for Model 8631 and 8631B. Refer to the paragraph Connecting RF Power ­Model 8631 and 8631B, above.
Installation
Model 8638 and
8638B
Model 8638 and 8638B - 3-1/8" unflanged, 50 ohm impedance. Refer to Figure 5 while following the instructions below.
1. Use the Bird Coupling Kit P/N 5-726, consisting of two clamping bands, an outer sleeve, and the center conductor coupling bullet.
2. Insert the center bullet, and bottom it on the midpoint nibs.
3. Position the outer sleeve, with clamps, over the input connector.
4. Introduce the transmission line and seat snugly against the coupling stops.
5. Position clamp bands evenly about 1-3/4" apart, and tighten.
Figure 5
Connecting RF
Power Model 8638
and 8638B
RF Coaxial Line Clamping Bands Connector Sleeve Bullet RF Load Connector
Preliminary
Equipment Check

Meter Rack The Meter Rack is used to hold the meter at the correct angle, for the

Check the RF load for acceptable electrical condition. Refer to the Maintenance Chapter for the procedure to determine load impedance. Below is the test equipment needed, and the critical parameters.
Equipment Needed: Digital Multimeter
Accuracy: 1 percent at 50 ohms, ± 1 digit
best possible viewing. Assemble and install as instructed below:
1. Assemble the kit using #6-32 x 1/4 screws, (supplied).
2. Remove the 2 screws from the panel at a desired mounting location.
3. Mount the assembled Meter Rack using #8-32 x 3/8 phillips truss (supplied). Refer to Figure 6.
13
Bird 8630B Series Moduload RF Load Resistor
Figure 6
Meter Rack
Assembly
14
Operating Instructions

Chapter 4 Operating Instructions

CAUTION
Do not operate the load without proper coolant levels. Operation without
sufficient coolant can damage the unit.
Use and Function
of Controls
Initial Adjustments
and Control
Settings

Equipment Startup

The Series 8630 and 8630B loads have no operating controls, other than the ON/OFF switch; therefore, they do not require an operator in attendance. The 8630 series is equipped with two indicators. One is a pilot light in the ON/OFF switch, to warn that the ac power is being applied. The other is the coolant level gauge, referred to in Chapter 3
- Installation. The 8630B series is equipped with one indicator which
is the coolant level gauge, referred to in Chapter 3 - Installation.
There are no adjustments or settings required beyond confirming that the cooling system contains an adequate level of coolant for proper operation. Refer to Chapter 3 - Installation.
WARNING
Never attempt to connect or disconnect an RF cable while power is
on at the RF power source. Radiated RF energy is a potential health
hazard.
CAUTION
Do not apply more than the rated RF power to the load. Excessive
RF power will damage the load resistor.
CAUTION
Do not block air flow. Air enters the housing through the circular
fan openings and exhausts through the grille opposite.
CAUTION
Do not operate the load without connecting the interlock. Even
momentary application of power to the load while the cooling
circulation is off, or possibly functioning improperly, will cause
almost immediate destruction of the resistor element.
1. Make sure coolant level is adequate, and verify fan operation.
2. Turn interlock supply on.
3. Turn on 115 V or 230 Vac power.
15
Bird 8630B Series Moduload RF Load Resistor
4. Apply RF power to the load.

Normal Shutdown

Do not disconnect the line power first. Even a momentary
application of RF power to the load while the cooling circulation is
off will cause almost immediate destruction of the resistor element.
1. Turn RF power to the load off.
2. Wait five minutes, allowing pump and blower to return coolant to ambient room temperature.
3. Turn ac power off.
Note: Stopping the pump automatically opens the interlock
connection.
CAUTION
Emergency
Shutdown
Performance
Notes
With the use of interlock capability, the Load will automatically turn off the transmitter’s RF power of an emergency arises.
If an emergency arises that is not a fault of the unit, always turn off the source of RF power first, and then the ac power to the Load.
The electrical performance of the Series 8630 and 8630B RF loads is affected by impurities or other chemical additives in the cooling liquid. Therefore, the cooling liquid should be the coolant supplied with the unit, or distilled water. Do not use any additives.
Thermal performance is affected by impurities, particularly those which accumulate in the form of scale on the surface of the ceramic tube and any other water passages. This results in an increase of thermal resistance of the load, and in turn, may cause the load to overheat and fail.
16

Chapter 5 Maintenance

This chapter covers cleaning, inspection, trouble-shooting, and specifications for the 8630 and 8630B Series Moduload RF Load Resistors.

Troubleshooting

The table below provides troubleshooting information for problems which may occur during normal operation. Locate the problem, review the possible causes, and perform the action listed. This manual cannot list all malfunctions that may occur, or their corrective actions. If a problem is not listed or is not corrected by the listed actions, notify a qualified service center.
PROBLEM POSSIBLE CAUSE CORRECTION
Maintenance
Transmitter won’t come on or shuts off repeatedly
Excessive reflected power
Coolant Leaking Loose connections
New or unusual noises
Insufficient coolant flow Check coolant gauge
Defective flow switch Check flow switch Defective pump Check pump Overheating Check for sufficient coolant Defective thermoswitch Check thermoswitch
Damaged resistor Check resistance value of RF section Contaminated coolant Drain, flush and refill coolant system Insufficient coolant Check for coolant leaks and add more
Worn or cracked tubing Replace defective tubing
Fans Check for loose fan blades
Pump
Check for blockage in circulatory system Check for coolant leaks
Check for excessive room temperature Check fans for jamming and grilles for
blockage
coolant
Check and tighten all connections
Check pump for signs of initial failure
Circulatory system Check for any sign of coolant leakage
17
Bird 8630B Series Moduload RF Load Resistor

Cleaning

The most important cleaning task is to remove accumulations of dust, lint, and grime that could interfere with proper air circulation and therefore efficient heat transfer. The heat exchanger surfaces, particularly on the inside, should be checked periodically for possible collection of dust and lint. When cleaning is necessary, follow these instructions.
1. Remove and retain the 18 screws from the edges of the top panel, and the top panel.
2. Clean off dust and lint, if any, with a radiator brush or stiff bristle brush. A vacuum can be used to clean the coils if necessary.
3. Check under the ribs of the exhaust grille (at the side) for dust collection. If there is a buildup, remove the grille and clean under the ribs.
4. Replace top panel and screws.
Heavy coatings of lint on any surfaces of the heat exchanger unit can impair the efficiency of the Moduload unit. Keep the surfaces of the heat exchanger clean.

Radiator Surface The radiator surface, particularly on the inside, should be checked

periodically for possible collection of dust and lint. A heavy lint coating on the inside surface of the radiator can impair the cooling efficiency of the unit. Follow the instructions below for cleaning.
1. Remove the 18 screws from the edges of the top panel and remove the panel.
2. Clean off any collected dust and lint with a radiator brush or any stiff bristle brush.
3. Replace the top panel.
Connector and
Outside
The outside surface of the unit should also be wiped free of dust and dirt at regular intervals. Use a soft, clean cloth dampened with mild detergent. Check the condition of the RF coaxial connector. If needed, clean the RF input connector using a selfdrying contact cleaner that leaves no residue on the inaccessible portions.
18

General Maintenance

Maintenance
Measure Load DC
Resistance
Preparation:
y Tools: Common hand tools y Ohmmeter with an accuracy of ± 1% at 50 ohms. y Temperature of the load between 20°C to 25°C (68°F to 77°F)
Accurate measurement of the DC resistance between the inner and outer conductors of the RF input connector will provide a good check of the condition of the load resistor. Checking the DC resistance is simply used to measure a change in the condition of the resistor over time. The tracking of the DC resistance must start before the resistor is first put into service. Perform the following steps and record the value for future comparison. Check and record the resistance of the load periodically according to use.
WARNING
Never attempt to connect or disconnect an RF cable while power is
on at the RF power source. Radiated RF energy is a potential health
hazard.
1. Turn off RF power and interlock circuitry before any electrical disconnection.s are made.
Figure 7
Meter Lead
Placement
2. Disconnect RF coaxial line.
3. Connect the multimeter test leads across the center and outer conductor of the load resistor. Refer to Figure 7.
4. Record the value of the resistance before the load is put into service. Compare subsequent values with the latest reading. If the values vary more than 2 ohms this could be an indication of a failing resistive element.
Note: It is recommended that this resistance check be performed
each time the load is to be used.
19
Bird 8630B Series Moduload RF Load Resistor

Water Flow Switch

Routine Service
Checks
The water flow switch should be inspected periodically for accumulated scale and cleaned, if necessary, to permit free movement of the sliding valve. This needs to be done after three to six months of operation, depending on the amount of use. This should be done by removing only the wired sensor plug using the following steps:
1. Drain the unit of its coolant.
2. Unscrew, counterclockwise, the 1-1/2 inch collar that holds the sensor plug in the flow switch body.
3. Carefully pull the sensor plug out of the body, do not lose the spring and sliding valve on the sensor plug stem.
4. Reverse the above steps to assemble.
The component is nonrepairable and must be replaced if its performance is faulty. Operation can be checked by monitoring the interlock circuits while starting or stopping the pump/motor with the RF power off.
When the equipment is in use inspect the coolant level at regular intervals. Normally check once or twice a week, more often if it is used continuously or under high ambient temperatures. The coolant level should remain at the upper gauge mark on the back panel, whether the unit is running or not. For test measurement and addition of liquid if required, Refer to the Coolant paragraph in chapter 3. Use only distilled water and industrially pure ethylene glycol. Do not use automotive antifreeze or deionized water.
20
Flushing the
System
Whenever maintenance work has been performed, including resistor repair, or there is a reason to suspect that contamination has been introduced or dislodged into the coolant, the system should be thoroughly flushed. Do this by:
1. Run the load with coolant but without RF power applied for a period of three to five minutes.
2. Drain the circulating system as completely as possible.
3. Fill the unit with fresh, clean, distilled water.
4. Repeat the sequence as required until the drained liquid is clear.
5. Fill the unit with distilled water and/or approved ethylene glycol mixture per the Coolant paragraph.

Repair

Maintenance
The series 8630 and 8631B, 8635 and 8635B, 8638 and 8638B loads are designed for independent, long term, trouble-free operation. Regular mechanical maintenance procedures, other than routine checks and cleaning care described previously, are not required. In the case of malfunction of the unit or replacement of a major component, resistor repair excepted, the entire load may be returned to the factory. This applies especially to any unit still under the one year warranty. Consult the factory.
Note: Do not tamper with operational settings or perform other
unauthorized maintenance work during the first year. It could be cause to void the warranty.
Field repair of the load resistor may be performed as described in the Internal Repair of the Load Resistor paragraph. Other replacement instructions that might be needed are given in this section.
RF Load Resistor
Unit Removal
If in performing the DC resistance check a significant change in resistance is noted, or if for any reason the resistive element should fail, the element should be replaced. Inexpensive replacement resistors are available. Installation is described below.
Resistor repair in the load may be done without removing the water connections; follow procedures in the Internal Repair of the Load Resistor paragraph. They contain full dismounting and resistor change procedures. The full load assembly may be removed from the case as in the following procedure. Then follow the Internal Repair of the Load Resistor section.
Note: Notice the angular position of all elbows and associated
parts as they must be returned to relatively the same position when reassembled.
WARNING
Never attempt to connect or disconnect an RF cable while power is on at
the RF power source. Radiated RF energy is a potential health hazard.
1. Turn off RF power and interlock circuitry before any electrical disconnections are made.
2. Disconnect the RF coaxial line. Models 8631 / 8631B and 8635 / 8635B — flanged, loosen and remove the 3/8-16 bolt and nut sets that secure the flanges. Refer to Figure 4.
21
Bird 8630B Series Moduload RF Load Resistor
Model 8638 and 8638B — unflanged, loosen one clamping band on the load side of the connector sleeve. Refer to Figure 5.
3. Separate the transmission coaxial air line from the load connector. Make sure the center conductor bullet remains in the transmission line.
To remove the load resistor unit take off the top panel by removing the 18 screws around its perimeter. Lift off the top panel assembly by the handles. Continue following these instructions:
1. Remove, and retain the drain plug located near the bottom of the rear panel of the unit and allow the coolant to drain.
Note: Do not replace the drain plug with any substitute plug, use
the plug removed.
2. Unscrew the hose clamps on the hoses leading to the input elbow of the flow switch and the output elbow on the water chamber. Use an ordinary screwdriver.
3. Remove the hoses.
4. On the 8630, loosen the hex collar on the flow switch assembly and remove the collar and sensor from the flow switch body. On the 8630B, disconnect the flow switch wires at their in-line connectors. The output elbow on the side of the water chamber can now be removed by unscrewing counterclockwise.
5. Remove the six 1/4-20 x 5/8 hex head bolts (on the inside of the front panel) securing the load to the front panel.
Note: When the six bolts securing the load to the front panel are
removed the outer conductor assembly will be disconnected. Hold this assembly to keep it from falling and being damaged.
6. Temporarily reattach the outer conductor to the load body. Use two or three of the 1/4-20 bolts (finger tight) for this purpose.
7. Tip up the the unit at the back enough to unscrew the flow switch counterclockwise. The input elbow on the water chamber can be taken off after the load is removed through the front panel.
8. If the load resistor is to be returned to the factory for repair, store components with the Moduload unit until further use. Consult the factory. If the unit is to be field repaired, proceed with resistor replacement instructions as described in the Internal Repair of the Load Resistor section.
22
9. Replace the load resistor by reversal of the above procedure. Be sure to replace the coolant, per the coolant section. Check for leaks, especially at the restored connections.
Maintenance
Pump/Motor
Removal
For removal of the pump motor, it should not be necessary to remove the load resistor. Drain the unit of coolant by unscrewing the drain plug on the lower rear panel, then remove the fan panel and rear panel as follows:
1. On the 8630, release the fan panel by removing the 18 pan head screws surrounding it. When free, it should not be necessary to detach the terminal block connections to the fan; lay the panel to the side.
On the 8630B, disconnect the two flow switch connectors, the two quick-connects from the thermoswitch, the orange wire from the front panel terminal block, and the red wire from the time delay relay. Then disconnect the fan power cable connector. Be sure to note the location of each wire for reassembly. The fan panel may now be removed by removing the 18 pan head screws that attach it to the unit.
2. Detach the back panel by, using a crescent or 7/8" hex socket wrench, removing the two large hexagonal bolts that fasten the coolant level gauge to the back panel.
3. Pull the coolant gauge off the panel.
4. Remove the 16, 8/32 screws, to free the panel.
5. Make note of, or mark, all wire connections before detaching.
6. Detach the 3-wire cable from the 3-lug terminal block on the inside of the front panel. For reference, the color codes of the motor supply wires generally match the twistlock (8630) or the power (8630B) input wires, with the green going to the blue (8630) or the green/yellow (8630B) ground wire from the socket (8630) or the power entry module (8630B). Refer to Figure 8.
7. Release the hose clamp nearest the pump on the input hose and carefully loosen the hose from the 90° input elbow at the center of the helical pump head. In the same manner, loosen the output hose from the straight-up fitting on the pumps helical outlet.
8. Reach under the input elbow with a screwdriver and loosen the clamp band on the drain tube at the base of the volute. Free the tube completely from the fitting
9. Use a 9/16" hex socket extension wrench or a small flat-end wrench, to remove the two 3/8-16 nuts from the base studs holding the motor feet. Lift the motor slightly to clear the studs, then carefully inch the pump assembly forward while detaching the hoses. The freed assembly may be lifted from the equipment out the open side. Remove the wires, if needed, but make note of the connections for assembly.
23
Bird 8630B Series Moduload RF Load Resistor
10. Note the positions of the fittings. Observe the slight downward tilt of the 90° input elbow. Twist off, counterclockwise, the whole input and output fittings parts. Remove the small drain elbow also. Store the detached parts with the disassembled unit and return the pump/motor unit to the factory for replacement.
11. Replace the pump/motor and assemble the unit by reversing the disassembly procedure above. Refill the unit with coolant per the instructions in the Coolant section.
Do not remove any fittings from the water chamber. The elbows
could be damaged, and may be difficult to restore them to their
original positions while keeping a water-tight seal. Check the
switch for free operation. Flush and clean with mild detergent of
CAUTION
necessary, and rinse thoroughly in clear water.
24
Figure 8
Wiring Diagram
GREEN
BLACK
WHITE
YELLOW
CAUTION
BLACK
INTERLOCK
230VAC 8AMP
60Hz 3AB
Maintenance
AC ON
YELLOW
BLACK
YELLOW
YELLOW
WHITE
WHITE
BLACK
BLACK
BLACK
WHITE
GREEN / YELLOW
WHITE
BLACK
GREEN / YELLOW
GREEN / YELLOW
25
Bird 8630B Series Moduload RF Load Resistor

Water Flow Switch

To replace the safety control water flow switch, begin with the same process as described in the RF Resistor Load Disassembly section. Remove the flow switch carefully or damage to the connections and fittings may result.
1. With the top cover removed, and the unit drained of coolant, loosen the clamp bands on the hose connections going to the load water chamber output and the flow switch input. Remove the hoses and move them out of the way.
2. Series 8630 only. Remove the 18, 8-32 x 1/4" Phillips head screws in the perimeter of the pan panel assembly. Pull this panel out sufficiently towards the rear of the unit to gain access. Usually connection wires will not have to be disconnected.
3. Disconnect the wires that lead to the flow switch. On the 8630 series, one wire is connected to the thermoswitch located under the coolant reservoir tank. The other wire is disconnected at a connector in the wire harness.
4. On the 8630 series, unscrew the input elbow to the flow switch, counterclockwise. The flow switch can be easily unscrewed counterclockwise, depending on the orientation of the output elbow on the load.s water chamber. This elbow may have to be turned or possibly removed to allow the flow switch to swing freely when being unsrewed
On the 8630B series, unscrew the input elbow to the flow switch
(counterclockwise).
Note: If the fan interferes when removing the elbow, loosen the set
screw on the water chamber then rotate the water chamber until the elbow is free from interference.
5. The flow switch is now free for repair or replacement.
6. Replace the flow switch and assemble the unit by reversing the disassembly directions given above. When replacing the flow switch on threaded fittings, coat only the external threads sparingly with an acceptable pipe sealant compound. Coating only the external threads reduces the chances of contaminating the coolant.

Time Delay Relay The time delay relay is non-adjustable and is set for a 2 second delay.

The relay contacts can be used to interrupt the transmiter circuit in the event of inadequate coolant flow or over temperature. The relay is located on the upper left inside of the front panel.
The relay is not serviceable. To remove the realy perform the following steps.
26
8630 Series
1. Loosen the 8-32 pan head screw at the top of the relay clamp, to release the retaining prongs of the clamp.
2. Pull the delay relay cartridge straight out of the socket.
3. To install the new cartridge, put the center nib into the hole provided. Rotate until the key way is engaged, and push in.
8630B Series
1. Remove the wires from the relay contacts. Note the color and location of each wire for use in reassembly.
2. Remove the screw, nut, and washers that secure the relay to the panel then remove the relay.

Replace Fuse Preparation:

Maintenance
y Observe general safety precautions. y Tools needed: Common hand tools y Disconnect ac power main.
1. Remove the fuse drawer from the ac receptacle.
2. Lift up on the tab that secures the drawer with the flat blade of a screwdriver.
3. Pull the drawer straight out.
4. Replace with the same type and rating fuse. i.e., 15 Amp for the 115V unit and 8 Amp for the 230V unit.
Series 115V 230V 8630 15 amp 10 amp 8630B 15 amp 8 amp
5. Return the drawer to the receptacle.
6. Reconnect the ac power main and check the unit for proper operation.
27
Bird 8630B Series Moduload RF Load Resistor

Load Resistor Internal Repair

The entire load resistor unit need not be removed from the Moduload unit as a piece. It is simpler to disassemble it in place by the following procedure. While following these instructions refer to Figure 9.
1. Drain coolant from the equipment by unscrewing the drain plug from the lower back face of the equipment.
2. Remove the top panel of the unit. Unscrew the 18, 8-32 x 1/4" phillips head screws and remove the coolant filler plug. Lift the lid off by its handles.
3. Use a 5/64" hex wrench to remove the 8-32 x 1/8" socket set screw on the circumference of the water chamber assembly near the load housing seam.
4. Use a 7/16" end-wrench to unscrew the six 1/4-20 x 5/8" flange mounting screws from the inside of the front panel. Take the screws out to release the exterior flanges.
5. Use a leather strap type pipe wrench, or by twisting the housing flange on the outside of the front panel, turn the housing counterclockwise while firmly holding the water chamber and flow switch at the back. A little extra torque will break the initial screw compression, and the housing should screw off easily. Unscrew the housing until the threads are disengaged and pull it out of the front panel.
6. Temporarily reattach the outer conductor assembly to the load housing to prevent displacement of the center conductor assembly. Use two 1/4 -20 mounting screws placed through diametrically opposite flange holes, fastened finger tight.
7. The Load Resistor is ready to be repaired.

Resistor Removal The removal of the resistor is to be done with the unit in a vertical

position, connector end down.
1. The water chamber complex, of the load resistor assembly, and flow switch, with the attached adapters, may be dismounted, but it is not required or recommended. Do this only by unscrewing the wired sensor plug of the flow switch, with a 1-1/2 end-wrench. Do not disconnect the wiring. Follow the instructions provided earlier in this chapter for the entire load removal.
28
2. The O-Ring inlet seal in the water chamber may be removed and replaced if necessary.
3. Remove the retainer sleeve and O-Ring sleeve backup. The inner flow tube may be removed.
Maintenance
4. Grasp the resistor ground cap and remove it by pulling with a slight rocking motion. This will expose the end of the resistor.
5. The resistor should still be nested inside the resistor fitting. If the spacer ring is displaced, it will have to be repositioned.
6. Ensure the spacer ring is bottomed.

Inspection

Inspect the resistor and visible internal parts for damage. In most cases, even in the event of a resistor failure, the resistor substrate will remain intact. If so, continue the procedure in this section. Use the special procedure for the replacement of fractured resistors or damaged internal parts, as the condition of the resistor or internal parts require.
29
Bird 8630B Series Moduload RF Load Resistor
Econoload - Cut away view
12
13
7
Figure 9
2
8
3
Resistor
Replacement
4
10
1
6
14
11
5
9
1. Housing / Ass’y
2. Chamber, Water / Ass.y
3. Conductor, Outer / Ass.y
4. Conductor, Center / Ass.y
5. Cap, Resistor / Ass.y
6. Tube, Flow, Inner
7. O-Ring
8. Contact, Sleeve
9. O-Ring
10. Cap Screw St. Stl.
11. Set Screw St. Park
12. Label, Water Chamber
13. Insulator, Sleeve
14. O-Ring
Take particular care of the outside surface of the resistor. Treat this surface gently, wiping with a soft cloth. Do not abuse it by firing, sanding, or using any abrasive action.
30
1. Insert the new resistor into the load housing until it reaches the resistor fitting.
2. Carefully rotate and rock the resistor until it starts to enter its way into the resistor fitting. Push the resistor into the fitting until it bottoms on the spacer ring. Ensure the spacer ring is in the
Maintenance
proper place. If the resistor seems to be loose, refer to the procedure for the replacement of fractured resistors or damaged internal parts below for instructions on how to tighten the resistor fitting.
3. If damaged, replace the inner flow tube. If undamaged, place the original flow tube inside the resistor and lower it until it reaches the resistor fitting. Gently work and twist the inner flow tube until it seats in the bottom of the resistor fitting.
4. Place the resistor ground cap on the exposed end of the resistor, and press it into place. Slide the O-Ring down the inner flow tube until it rests on the end of the resistor.
5. Slide the retainer sleeve down the inner flow tube until it rests on the O-Ring, ensuring that the end of the retainer sleeve with the larger inside diameter goes on first.
6. Check the O-Ring inlet seal to see that it is properly seated in its groove in the inside of the water chamber subassembly.
Note: Normally, the water chamber will not have been dismounted. Be
sure the screws are removed from the flange connecting the outer conductor assembly.
7. Place the resistor housing through the front panel opening, and into the water chamber. Gently turn the housing clockwise to thread it on, eventually bottoming it in its original position.
8. Reverse the procedure of the RF Load Dismounting paragraph, to restore the original condition. Do not replace the top panel until after this section is completed.
9. Check the DC resistance between the outer and inner conductors; it should be approximately 50 ohms. Refer to the Measure DC Resistance section, and Figure 7.
10. If the resistance check passes, fill the unit with coolant, performing the flush out procedures of the RF Load Dismounting section, and check for leaks.
Note: After the completion of this or any of the resistor repair
procedures, perform a 10 kW test on the ac line power. Perform this test with the Moduload unit in operation for at least one-half hour, and check the DC resistance before RF load use.

Replacement of Fractured Resistor or Damaged Internal Parts

Resistor Removal The load should already be disassembled to the point of the Resistor

Removal section, step 5.
31
Bird 8630B Series Moduload RF Load Resistor
1. Turn the load on end, with the RF input connector up, to allow debris, if present, to fall out of the load housing.
2. Loosen and remove the 1/4-20 x 5/8 inch hex head screws from the flanged end of the load housing assembly as shown in Figure 9.
3. Remove the outer conductor assembly.
4. Remove the input center conductor assembly by pulling it out of the load housing assembly.
Input Center
Conductor
Assembly
Refer to Figure 10 while following the instructions below.
Model 8730A, (used in the Model 8635 and 8635B), 1-5/8 inch EIA flanged input connector only.
1. Remove the 1/4-20 x 3/4 inch pan head machine screw and 1/4 inch split lockwasher by unscrewing the screw while holding the center conductor stationary.
2. Remove the center conductor, the center conductor adapter, and the insulator from the rest of the assembly.
3. Remove the resistor fitting by pushing the exposed end of the fitting into the outer flow tube. The resistor fitting and any broken pieces of resistor will fall from the opposite end of the outer flow tube.
4. Inspect all O-Ring seals, metal and internal parts for damage. The metal parts may be discolored or oxidized and may be cleaned by rubbing them with fine abrasive cloth or silver cleaner. The Teflon parts can be cleaned with detergent and water. If any of the internal parts are damaged, they must be replaced to ensure proper electrical and/or thermal performance of the load.
5. Insert the replacement resistor into the resistor fitting. If the fitting is loose press the slotted finger contacts of the fitting together slightly and try the resistor again. Continue this procedure until a snug fit is obtained.
32
6. Reassemble the center conductor assembly by first replacing the outer flow tube seal O-Ring. If needed, insert the resistor and resistor fitting in position in the outer flow tube.
7. Replace Insulator center conductor adapter, and center conductor. Tighten in place with 1/4-20 x 3/4 Inch pan head machine screw and 1/4 inch split lockwasher.
Maintenance
Model 8731-101 Load (used in Model 8631 and 8631B), 3-1/8 inch EIA flanged and Model 8738-101 Load (used in Model 8638 and 8638B), 3­1/8 inch unflanged input connector.
1. Loosen and remove the 3/8-16 hex nut, and the 3/8" split lockwasher with a 9/16 socket or nut driver while holding the center conductor stationary.
2. Remove the center conductor and the insulator, for Models 8731 and 8738.
3. Remove the resistor fitting by pushing the exposed threaded end of the fitting into the outer flow tube. The resistor fitting and any broken pieces of resistor will fall from the opposite end of the outer flow tube.
4. Inspect all internal parts and O-Ring seals for damage. The metal parts may be discolored or oxidized and may be cleaned by rubbing them with fine abrasive cloth or silvercleaner. The Teflon parts can be cleaned with detergent and water. If any of the internal parts are damaged, they must be replaced to ensure proper electrical and/or thermal performance of the load.
5. Insert the replacement resistor into the resistor fitting. If the fitting is loose press the slotted finger contacts together slightly and try the resistor again. Continue this procedure until a snug fit is obtained.
6. Reassemble the input center conductor assembly by first replacing the outer flow tube seal O-Ring, if necessary.
7. Insert the resistor fitting in position in the outer flow tube.
8. Replace insulator and center conductor for Models 8731 and 8738. Tighten in place with the 3/8-16 hex nut and 3/8" split lockwasher.

Final Assembly 1. Replace the input center conductor assembly by lowering it into

the flanged end of the load housing assembly, and pressing it into place.
2. Remount the outer conductor assembly, for Models 8730, 8731 or 8738, by placing the flange with the threaded holes against the flange of the housing assembly. Tighten the six 1/4-20 x 5/8" hex head cap screws securely.
3. Continue with the Resistor Replacement Instructions, given earlier in this chapter.
Any maintenance or service procedure beyond the scope of those provided in this section should be referred to a qualified service center.
33
Bird 8630B Series Moduload RF Load Resistor
Figure 10
Center Confuctor Assemblies
Lockwasher
3
2
1
8738A Center
Conductor Assembly
45
2
1
8730A Center
Conductor Assembly
Lockwasher
3
4
5
34
Maintenance
Figure 11
Schematic Diagram, 8630, 10 kW Moduload, 115 V 50/60 Hz Supply
PUMP
WHITE
CAPACITOR
BROWN
YELLOW
FAN
GREEN
GREEN
RED
BROWNBROWN
BLACK
WHITE
GREEN
AC PLUG
WHITE
BLUE
ABOVE 6 GPM
NORMALLY CLOSED
FLOW SWITCH
WHITE
BLACK
o
BELOW 77 C
NORMALLY CLOSED
THERMOSWITCH
RED
BROWN
NORMALLY OPEN
1/2 - 3/4 SEC.
TIME DELAY
YELLOW
YELLOW
INTERLOCK
TRANSMITTER
BLACK
BLUE
115 VAC
35
Bird 8630B Series Moduload RF Load Resistor
CAPACITOR
GREEN
YELLOW
FAN
RED
Figure 12
Schematic Diagram, 8630, 10 kW Moduload, 230 V, 50/60 Hz Supply
PUMP
WHITE
GREEN
BROWNBROWN
BLACK
WHITE
GREEN
AC PLUG
WHITE
BLUE
ABOVE 6 GPM
NORMALLY CLOSED
FLOW SWITCH
WHITE
BLACK
o
BELOW 77 C
NORMALLY CLOSED
THERMOSWITCH
RED
BROWN
NORMALLY OPEN
1/2 - 3/4 SEC.
TIME DELAY
YELLOW
YELLOW
INTERLOCK
TRANSMITTER
BLACK
BLUE
230 VAC
36
Maintenance
Figure 13
Schematic Diagram, 8630B, 10 kW Moduload, 115 V and 230 V, 50/60 Hz Supply
FAN
WHITEWHITE
BLACKBLACK
GREEN / YELLOW GREEN / YELLOW
ORANGE
ABOVE 6 GPM
NORMALLY CLOSED
FLOW SWITCH
PUMP
BLACK
WHITE
GREEN
AC PLUG
BLACK
RED
YELLOW
WHITE
o
THERMOSWITCH
BELOW 77 C
NORMALLY CLOSED
BLACK
TIME DELAY
NORMALLY OPEN
2 SEC.
YELLOW
INTERLOCK
TRANSMITTER
BLACK
GREEN / YELLOW
INPUT VOLTAGE LINE FILTER
37
Bird 8630B Series Moduload RF Load Resistor
38

Storage and Shipment

Storage

Before storing the unit, follow the storage instructions in the
Storage section of the Maintenance chapter. Failure to follow the
If the unit is to be stored it should be stored filled with coolant if possible. If storing the unit filled is not possible, drain the unit following the drainage instructions below.

Drainage If the unit is to be stored partly drained or fully drained for two

weeks or longer, follow the drainage instructions below.
1. Flush the system as described in the manual five times if the coolant has had any ethylene glycol added. Otherwise, flush the system a minimum of one time per the manual.
Maintenance
CAUTION
instructions may result in damage to the unit.

Shipment

2. With the unit in a level position, remove the drain plug and allow the fluid to drain from the system.
3. Tip the unit approximately 10 degrees from vertical, once each side, to move more fluid out the drain opening.
4. Attach a fitting to the top of the expansion tank and plumb clean, dry, filtered air regulated to 20 psi.
5. Allow air to purge the Moduload until relative humidity of output is <20%.
6. Plumb a source of clean, dry nitrogen gas to the expansion tank fitting with a regulator set to 5-9 psi.
7. Allow nitrogen to purge the Moduload until relative humidity of output is <15%.
8. Disconnect nitrogen supply and fittings from the Moduload. Reinstall drain plug and expansion tank cap.
CAUTION
Before shipping the unit, follow the shipping instructions in the
Maintenance chapter. Failure to properly prepare the unit for
shipping may result in damage to the unit.
If the unit is to be shipped, prepare the unit for shipping using the drainage procedure below.
39
Bird 8630B Series Moduload RF Load Resistor
1. Flush the system as described in the manual five times if the coolant has had any ethylene glycol added. Otherwise, flush the system a minimum of one time per the manual.
2. With the unit in a level position, remove the drain plug and allow the fluid to drain from the system.
3. Tip the unit approximately 10 degrees from vertical, once each side, to move more fluid out the drain opening.
4. Attach a fitting to the top of the expansion tank and plumb clean, dry, filtered air regulated to 20 psi.
5. Allow air to purge the Moduload until relative humidity of output is <20%.
6. Plumb a source of clean, dry nitrogen gas to the expansion tank fitting with a regulator set to 5-9 psi.
7. Allow nitrogen to purge the Moduload until relative humidity of output is <15%.
8. Disconnect nitrogen supply and fittings from the Moduload.
When shipping the Moduload, use the original shipping package if possible. If the original package is not available, use a heavy duty corrugated box with shockabsorbing material around all sides of the unit to provide firm cushioning, and to prevent movement in the container. The container should be properly sealed.

Customer Service

Any maintenance or service procedure beyond the scope of those in this chapter should be referred to a qualified service center.
If you need to return the unit for any reason, contact the Bird Service Center for a return authorization. All instruments returned must be shipped prepaid and to the attention of Bird Service Center.
Bird Service Center
30303 Aurora Road Cleveland (Solon), OH 44139-2794 Phone: (440) 519-2298 Fax: (440) 519-2326 E-mail: bsc@bird-technologies.com
Reinstall drain plug and expansion tank cap.
40
For the location of the Sales Office nearest you, give us a call or visit our Web site at: http://www.bird-electronic.com

Specifications

Maintenance
Frequency Range Power Rating Impedance, Nominal VSWR Modes
1 kHz to 1000 MHz 10 kW Maximum 50 ohms
1.1 to 1.0 CW, AM, FM, SSB, & TV
Connectors
Model 8631 and 8631B Model 8635 and 8635B Model 8638 and 8638B
1
3-1/8" EIA flanged
1
1-5/8" EIA flanged
1
3-1/8" Unflanged
AC Power
115 VAC @ 9 Amps, 50/60 Hz 230 VAC @ 4.5 Amps, 50/60 Hz
Interlock Contact Ratings, Solid State Relay
125 VAC 10 A, resistive 230 VAC 5 A, resistive +28 VDC 5 A, resistive 125 VAC 1/4 hp Max switching voltage 250 VAC
Interlock Contact Ratings, Mechanical Relay
10 amps resistive at 30 VDC, 120 / 240 VAC
Ambient Temperature
With 100% distilled water
as coolant
With 35% ethylene glycol
as coolant
Operating Position Dimensions, Nominal
Weight, Nominal
Finish
+5°C to +45°C (+41°F to +95°F)
-20°C to +35°C (-4°F to +95°F)
Horizontal only 22-1/8" L x 15-13/16" W x 15-15/16" H (562 x
402 x 405 mm) 113 lb with distilled water (51.3 kg)
103 lb without water (46.7 kg) Grey Powder Coat
1 Suffix - 115 added for 115 V, 60 Hz, 9 Amp, single phase
Suffix - 230 added for 230 V, 50 Hz, 4.5 Amp, single phase Suffix - 115-5 added for 115 V, 50 Hz, 9 Amp, single phase Suffix - 230-6 added for 230 V, 60 Hz, 4.5 Amp, single phase
41
Bird 8630B Series Moduload RF Load Resistor

Replacement Parts

Model 8630B Series Moduload RF Load
DESCRIPTION QTY PART NUMBER
RF Load Resistor 1
Model 8631 and 8631B Model 8635 and 8635B Model 8638 and 8638B
Power Switch (illuminated)
115V
230V Power Switch (not illuminated) 1 5A2384 AC Power Receptacle 1 5-1844 Fuse Drawer
115V
123V Fuse 2
115V Model 15amp, 3AB Time-Delay Type MDA 15
230V Model 8amp, 3AB Time-Delay
230V Model 8amp, 5 mm x 20 mm Time-Delay 8A Power Cord 1
115 V
230 V Fan Guard
Model 8630
Model 8630B Fan Motor Assembly 1
Model 8630, 115V
Model 8630, 230V
Model 8630B, 115V
Model 8630B, 230V Fan Starting Capacitor (model 8630 only) 1 5-873-2 Pump/Motor Unit 1
115 / 230VAC, 60 Hz.
115 / 230VAC, 50 Hz. Flow Switch Assembly
Model 8630
Model 8630B Time Delay Relay:
Model 8630, 115V
Model 8630, 230V
Model 8630B (115V and 230V) Relay Socket (model 8630 only) 1 8640-561
1
1
6
1
1
8731-101 8730A051 8738-101
5-1842-1 5-1842-2
5-1845 5A2310
5-1828-36 5A2257-25 5A2257-25
5-1836 5-1837
5-1923 5A2789-2
8630-644-1 8630-644-2 5A2770-1 5A2770-2
5-1053-1 5-1053-2
8630-108 8630B108
5-1627 5-1625 5A2787-1
42
Maintenance
Over Temperature Thermoswitch
Model 8630
Model 8630B Coolant Tank Assembly
Model 8630
Model 8630B
1
8630-013 5A2788-1
1
8630-102
8630-089 Filler Plug 1 8630-038 Silicone Rubber Hose, 5/8" diameter 1 **8630-065 Filler Plug Seal (O-Ring) 1 5-814 Carrying Handle (kit) 2 5-375 Silicone Rubber Hose, 3/4" diameter 1 **8640-064 Drain Plug 1 8640-036 Drain Plug Seal (O-Ring) 1 5-428 Hose Clamp, 5/8" 8 5-681 Hose Clamp, Diamond 3/4" 2 5-742 Breather Vent 1 5-1350 Drain Body Assembly 1 8630B-099 Coolant Gauge Body 1 5-1200 Pump Inlet Fitting Assembly 1 8650-081 Relay Retaining Clamp (model 8630 only) 1 8630-193 Load, Outlet - elbow 1 8630-175 Pump Outlet Tube Assembly 1 8630-176 Flow Switch Inlet Fitting (elbow) 1 8630-033 Flow Switch to Load Fitting (elbow) 1 8630-178 Interlock Terminal Strip
Model 8630 Model 8630B
1
5-768-2
5A1840-2 Interlock Terminal Strip Cover (model 8630B only) 1 5A1840-2-C Line Filter (ac input) (model 8630B only) 1 5A2792-1
**Measure hose length when ordering.
For All -N Models
DESCRIPTION QTY PART NUMBER
Fan Panel Assembly:
115V 230V
Fan, Service Assembly:
115V 230V
Fan Propeller 1 5A2457
1
8630-172-3 8630-172-4
1
8630-644-3 8630-644-4
43
Bird 8630B Series Moduload RF Load Resistor
Model 8630 and 8630B Series Loads
RF Load Assembly Parts for Moduload Models 8731-101, 8738-101, and 8730A051
DESCRIPTION QTY PART NUMBER
Resistor 1 8731-031 Resistor Ground Cap Rear Seal O-Ring 1 5-176 Water Chamber Subassembly 1 8731-025 Inlet Seal O-Ring 1 5-430 Retainer Sleeve 1 8731-023 Sleeve Backup O-Ring 1 5-1142 Inner Flow Tube 1 8731-022 Resistor Ground Cap 1 8731-007 Housing Assembly 1 8731-002 Resistor Ground Cap Internal Seal O-Ring 1 5-187 8-32 x 1/8" Cup Point Socket Set Screw 1 1128-0201-25 Outer Flow Tube 1 1128-0201-25 Outer Flow Tube Seal O-Ring 1 5-099 Insulator 1 8731-018
Front Connector Parts are Assigned Per Model Type Below:
Model 8635B Load — 8730A051 - 1-5/8" EIA Flanged Connector - 50 ohms
DESCRIPTION QTY PART NUMBER
Center Conductor Assembly 1 8730-003 Resistor Fitting 1 8730-008 Center Conductor Adapter 1 8730-009 Center Conductor 1 8730-010 Outer Conductor Assembly 1 8730-002 1/4-20 x 3/4" Button Head Machine Screw 1 1121-1217-00 1/4" Split Lockwasher 1 Standard
Model 8631B Load — 8731-101 - 3-1/8" EIA Flanged Connector - 50 ohms
DESCRIPTION QTY PART NUMBER
Center Conductor Assembly 1 8731-005 Resistor Fitting 1 8731-017 Center Conductor 1 8731-015 3/8-16" Hex Nut 1 Standard 3/8" Split Lockwasher 1 Standard Outer Conductor Assembly 1 8731-004
44
Model 8638B Load — 8738-101 - 3-1/8" Unflanged Connector - 50 ohms
DESCRIPTION QTY PART NUMBER
Center Conductor Assembly 1 8738-003 Resistor Fitting 1 8731-017 Center Conductor 3/8-16" Hex Nut 1 Standard 3/8" Split Lockwasher 1 Standard Center Conductor 1 8738-005 Outer Conductor Assembly 1 8738-002
For all Models
DESCRIPTION QTY PART NUMBER
Resistor Spacer Ring 1 8731-008 1/4-20 x 5/8" Hex Head Cap Screw 6 1121-1008-00
Optional Items
Maintenance
DESCRIPTION QTY PART NUMBER
Ethylene glycol 1 gal 5-1134-3 Repair and Replacement Kit, P/N
Consists of:
Coolant and Container Assy. (8630-197), 50 ohm resistor (8731-031-1), and instruction sheet (921-8630-196).
1 8630-196
45

Limited Warranty

All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise specified, from date of shipment and to conform to applicable specifications, drawings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or repairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transportation-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. Routine (regularly required) calibration is not covered under this limited warranty. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufacturer’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHAT­SOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGATION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
Loading...