Bird Technologies 8329-300 User Manual

Page 1
INSTRUCTION BOOK
OPERATING INSTRUCTIONS
TENULINE®ATTENUATOR
MODEL 8329-300
Electronic Corporation
Cleveland (Solon) Ohio US
©Copyright 1998 by Bird Electronic Corporation
Instruction Book Part Number 920-8329-300 Revision A
Tenuline®is a Registered Trademark of
Bird Electronic Corporation
Page 2
Page 3
Safety Precautions
The following are general safety precautions that are not necessarily related to any specific part or procedure, and do not necessarily appear elsewhere in this publication. These precautions must be thoroughly understood and ap­plied to all phases of operation and maintenance.
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety precautions. Do not replace components or make adjustments to the inside of the test equip­ment with the high voltage supply turned on. To avoid casualties, always re­move power.
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is pres­ent.
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure for the purpose of service or adjustment of equipment except in the presence of some­one who is capable of rendering aid.
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the main power source to test instruments. Grounding one conductor of a two conduc­tor power cable is not sufficient protection. Serious injury or death can occur if this grounding is not properly supplied.
Resuscitation
Personnel working with or near high voltages should be familiar with modern methods of resuscitation.
Safety Symbols
WARNING
Warning notes call attention to a procedure, which if not correctly
performed, could result in personal injury.
i
Page 4
CAUTION
Caution notes call attention to a procedure which if not correctly
performed, could result in damage to the instrument.
This symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
Note: Calls attention to supplemental informa-
+
tion.
Warning Statements
WARNING
The vent plug must be used at all times when the unit is in operation
or cooling. Failure to do this could result in damage to the equipment
and endanger the operator’s safety. Be sure to check the plug.
WARNING
Using this attenuator in the upper end of its power dissipation range
will cause the housing to become hot. Care should be exercised in
touching it.
WARNING
Never attempt to disconnect the equipment from the transmission line
while RF power is being applied. Leaking RF energy is a potential
health hazard.
Caution Statements
CAUTION
This equipment is designed for operation in a horizontal position only,
with mounting brackets down. Do not operate in any other manner.
CAUTION RF power rating must always be cut in half when the blower assembly is installed but is not running. Under this conditiona2kWattenuator
will be limited to approximately 1 kW.
ii
Page 5
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ES­PECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRU­MENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS EXPLICITEMENT PRÉVUE PAR LE FABRI­CANT PEUT ENDOMMAGER LE DISPOSITIF DE PRO­TECTION DE L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZ­ZATO IN MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERV­ICE - TRAINED PERSONNEL ONLY. TO AVOID DAN­GEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO DEL PERSONAL DE SERVICIO CA­PACITADO. PARA EVITAR EL PELIGRO DE DESCAR­GAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
iii
Page 6
Bird Model 8329-300 Tenuline Attenuator
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERV­ICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRA­TIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE ESCLUSIVAMENTE PER IL PERSONALE OP­PORTUNAMENTE ADDESTRATO. PER EVITARE PERI­COLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
CONNECT INTERLOCK TO TRANSMITTER BEFORE OPERATING.
BRANCHER LE VERROUILLAGE À L’ÉMETTEUR AVANT EMPLOI.
CONECTE EL INTERBLOQUEO AL TRANSMISOR AN­TES DE LA OPERACION.
VOR INBETRIEBNAHME VERRIEGELUNG AM SENDER ANSCHLIESSEN.
PRIMA DI METTERE IN FUNZIONE L’APPARECCHIO, COLLEGARE IL DISPOSITIVO DI BLOCCO AL TRAS­METTITORE.
iv
Page 7
About This Manual
This instruction manual covers the Model 8329-300 Tenuline Attenuator. This instruction book is arranged so that essential information on safety is contained in the front of the book. Reading the Safety Precautions section be­fore operating the equipment is strongly advised.
The remainder of this instruction book is divided into chapters and sections.
Operation
First time operators should read Chapter 1 - Introduction, Chapter 2 - Theory of Operation, and Chapter 3 - Installation to get an overview of equipment ca­pabilities and how to install it. An experienced operator can refer to Chapter 4 - Operating Instructions. All instructions necessary to operate the equip­ment are contained in this chapter.
Maintenance
All personnel should be familiar with preventive maintenance found in Chap­ter 5 - Maintenance. If a failure should occur, the troubleshooting section will aid in isolating and repairing the failure.
Parts
For the location of major assemblies or parts, refer to the parts lists and asso­ciated drawings in Chapter 5 - Maintenance.
Changes To This Manual
We have made every effort to ensure this manual is accurate at the time of publication. If you should discover any errors, or if you have suggestions for improving this manual, please send your comments to our factory. This man­ual may be periodically updated, when inquiring about updates to this man­ual refer to the part number and revision level on the title page.
v
Page 8
Bird Model 8329-300 Tenuline Attenuator
vi
Page 9
Table of Contents
Safety Precautions. ......................i
Warning Statements. ......................ii
Caution Statements........................ii
Introduction. ........................1
Purpose and Function. ...................1
Description.........................1
Dimensions and Weight. ..................1
Items Supplied. ......................1
Items Required. ......................2
Optional Items. ......................2
Specifications. .........................3
Theory of Operation. .....................5
Operating Instructions. ....................7
Site and Shelter Requirements. ...............7
Unpacking and Inspection. .................7
Tools Required. ......................7
Mounting. ........................8
Vent Plug. ........................8
Thermoswitch. ......................9
Blower Assembly......................11
Operating Instructions. ...................13
Initial Adjustments.....................13
Connection. .......................13
vii
Page 10
Bird Model 8329-300 Tenuline Attenuator
Normal Operation. ....................14
Operation Under Abnormal Conditions. ...........15
Shutdown. ........................15
Emergency Shutdown. ...................15
Maintenance. ........................17
Troubleshooting. ........................17
Cleaning. ...........................17
Preventive Maintenance. ....................18
Measure dc Resistance. ..................18
RF Connector. .........................19
Coolant. ...........................20
Adding Coolant. .....................20
Replacing Coolant. ....................20
RF Load Resistor. .......................22
Thermoswitch. .........................22
Repairs. ...........................22
Customer Service. .......................23
Sales / Repair Facilities. ..................23
Sales Facilities. .....................23
Shipment............................23
RF Section Assembly. ...................23
Complete Unit. ......................23
Storage. ...........................24
Replacement Parts List......................24
viii
Page 11
Chapter 1
Introduction
This publication refers to the Tenuline Attenuator Model 8329-300. This chapter contains introductory information including product specifications, items supplied, and acces­sory items available.
Purpose and
Function
Description Relying only on ambient air currents, this Tenuline
The Model 8329-300 Attenuator is a low-reflection resis­tance network for application in reducing RF power by known and controlled amounts. It is a self-contained instru­ment that requires no external source of power (except if blower equipped) or utility service. The radiator has rhom­bic shaped cooling fins spaced evenly along its length for the most efficient cooling. This attenuator is useful for lowering a high input RF power to a level suitable for feeding into an oscilloscope, frequency counter or similar device. The attenuator is designed to match the most commonly used 50 ohm transmission line systems.
Attenuator will safely absorb, and dissipate harmlessly as heat, up to 2000 watts of input power. When equipped with an optional blower, Model BA-300, the increased air flow will allow a doubling of the rated load capacity to 4000 watts. Over the frequency range of dc to 500 MHz, the power output will be reduced by 30dB (99.9%) ±0.5dB. Up to 500 MHz, the input VSWR will not exceed 1.1 and the out­put VSWR 1.15.
This attenuator is a passive device that is self-contained and does not need any external source of power or utilities to function. The exception would be the use of the optional BA-300 blower for a higher cooling rate. The BA-300-115 re­quires 115V at 50/60 Hz and the BA-300-230 requires 230V at 50/60 Hz.
Dimensions
and Weight
Items
Supplied
This attenuator is 23-1/4"L x 7-1/8"W x 17-3/16"H (591 x 181 x 437mm). It has a net weight of 57 lbs. (26kg) and a ship­ping weight of approximately 68 lbs. (31 kg). Equipped with a blower assembly the net weight is 70.5 lbs. (32kg) and the shipping weight is 85 lbs. (39kg).
The following items are supplied with the Model 8329-300.
s
LC Female connector - input end
s
N Female connector - output end
1
Page 12
Bird Model 8329-300 Tenuline Attenuator
Instruction Manual
s
Items
Required
Optional
Items
The following items are required to put the Model 8329-300 into service.
Multimeter
s
Screwdrivers
s
Matching connectors on the coaxial transmis-
s
sion line.
The following items are available as optional equipment.
Overload thermoswitch, P/N 8329-028, for pro-
s
tection against burnout. Quick-Change connectors for convenient and
s
easy interchange with other “AN” type “QC” connectors. Refer to the list in the Mainte­nance Chapter.
2
Page 13
Specifications
Impedance: 50 ohms nominal VSWR:
Input (dc-500MHz) Output (dc-500MHz)
Connectors:
Input
1.1:1.0 maximum
1.15:1.0 maximum
Bird “QC” Type, Female LC nor­mally supplied
Introduction
Output
Power Range:
Without blower assembly: With blower assembly: With blower, but not running:
Frequency Range: dc-500MHz Attenuation: 30dB ±0.5dB, dc-500MHz* Calibration Frequencies (to ±0.2dB) 30, 100, 200, 300, 400 and
Dimensions: 23-1/4"L x 7-1/8"W x 17-3/16"H
Ambient Temperature: -40°C to +45°C (-40°F to +113°F) Cooling Method:
Without blower assembly With blower assembly
Weight:
Without blower assembly With blower assembly
Operating Position: Horizontal only Finish: Grey Powder Coat
*Special Attenuation Data to 1000MHz is available at time of order.
Bird “QC” Type, Female N normally supplied.
2000W 4000W 1000W maximum
500MHz
(591 x 181 x 437mm)
Convection currents Forced draft
57 lbs. (26kg)
70.5 lbs. (32kg)
3
Page 14
Bird Model 8329-300 Tenuline Attenuator
FILLER AND VENT VALVE
Interlock Thermoswitch (Optional)
Input Connector Per Customer Order Female "LC" Normally Supplied
Model 8329-300 Outline Drawing
Figure 1
<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<
2-61/64 (75mm)
<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<
20-23/32 ±1/32
(526 ±.8mm)
MTG. HOLE CENTERS
THIS DIMENSION DEPENDENT UPON Q.C. CONNECTOR USED. (1-5/8 (41mm) FOR FEMALE "LC")
21-45/64 (551mm)
20-15/16 (532mm)
21-5/8
(549mm)
<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<
17-3/16
(437mm)
<<<<<<<<<<<<<<<<<<
4-1/2 ±1/64
(114 ±.4mm)
MTG. HOLE
CENTERS
7-1/8
(181mm)
4
Page 15
Chapter 2
Theory of Operation
The Model 8329-300 Attenuator is a symmetrical “T” pad, with the power distribution on the legs being different. Therefore, the value of the resistance on each leg is different according to the power it is to absorb. On the input resistor element, a proportionately larger resistor is of course re­quired for its much greater power dissipation. A “T” configu­ration is used to provide equal input and output impedance’s for the 50 ohm transmission line attenuation.
The input resistor is joined by the “T” leg joint in an expo­nentially tapered housing to provide a linear reduction in surge impedance of 50 ohms. This arrangement produces a uniform and practically reflectionless attenuation character­istic over the stated frequencies of the attenuator.
This system of carbon-film-on-ceramic cylindrical resistors immersed in a dielectric coolant constitutes the RF section assembly. The cooling liquid and the tapered input resistor housing provide the proper electrical characteristics of the coaxial line termination.
The dielectric coolant is carefully chosen for its desirable di­electric properties, to which the diameters of the resistors and housings are matched, and for its high thermal stability characteristics. Expansion of the coolant, when power is ap­plied to the attenuator, is accomplished by allowing the air, which is compressed by the expanding coolant, to escape through the vent plug located near the top and front face of the unit.
By convection, the coolant carries the heat generated in the various resistor elements to the walls of the coolant hous­ing. This housing is encased in a set of radiating fins which are attached to its outer surface. These radiating fin sur­faces dissipate the heat of the coolant into the surrounding air.
The Model 8329-300 may be used for isolation of power sources up to 2000 W and for low level monitoring. The low power value obtained at the output of the attenuator can easily be read on an oscilloscope or terminated in a small RF load resistor.
5
Page 16
Bird Model 8329-300 Tenuline Attenuator
Note: At the full power and frequency capabil-
+
ity of this model, refer to the Specifications, only type LC, LT (Female or Male) or 7/8" EIA (air line) connectors will be adequate on the in­put line.
6
Page 17
Chapter 3
Operating Instructions
This chapter provides information for on-site requirements, unpacking, inspection, and preparing the equipment for use.
Site and
Shelter
Requirements
Unpacking
and
Inspection
The Model 8329-300 Attenuator should be operated in a dry, dust, and vibration free environment. The ambient tempera­ture range should remain between -40°C and +45°C (-40°F and +113°F) for proper operation. Allow at least 12" (300mm) of clearance around the unit, 6" (150mm) if it is equipped with a blower, to permit unimpeded access of con­vection air currents for adequate heat dissipation. To permit the shortest possible cable length, place the attenuator as close as possible to the transmitting equipment.
Follow the steps below when unpacking the equipment.
1. Inspect the shipping container for signs of damage. If damage is noticed, do not unpack the equipment. Immedi­ately notify the shipping carrier and Bird Electronic Corporation of the damage.
2. If the shipping container is not dam­aged, unpack the unit. Save all ship­ping materials for repackaging.
3. Inspect all components for visual signs of damage. Immediately notify the shipping carrier and Bird Electronic Corporation of equipment damage or missing parts.
Tools
Required
The following tools and supplies will be required to prepare the unit for use.
s
Wrenches
s
Standard screwdrivers
s
9/16 Hex wrench (for thermoswitch installa­tion)
s
Pipe sealing compound (for thermoswitch in­stallation)
s
Soldering Iron and solder (for thermoswitch in­stallation)
7
Page 18
Bird Model 8329-300 Tenuline Attenuator
Bolt and nut sets or lag screws (for mounting)
s
Mounting
This equipment is designed for operation in a
horizontal position only, with mounting brackets down.
Do not operate in any other manner.
The attenuator may stand free, may be secured to a bench, or any convenient flat surface. The front and rear face plates are made of heavier gauge material bent outward 90° at the bottom to form mounting flanges. At each corner of these flanges is a 3/8 inch hole for use with suitable fasten­ers up to 3/8 inch. The holes are arranged in a 20-23/32 inch x 4-1/2 inch rectangle (526.3 x 114.3mm). The front and rear face plates of the attenuator are also bent over on the top to form convenient carrying handles. The following instruc­tions are for mounting the unit to a suitable surface.
1. Place the unit on a flat surface.
2. Insert the fasteners, up to 3/8 inch, through the bench and the holes.
3. Secure the bolts with nuts and lock washers.
CAUTION
8
Vent Plug
WARNING
The vent plug must be used at all times when the unit
is in operation or cooling. Failure to do this could
result in damage to the equipment and endanger the
operator’s safety. Be sure to check the plug.
Before placing the attenuator into service, the solid shipping plug must be removed and replaced by the spring loaded vent plug. The vent hole for these plugs is located at the top left hand side near the front. The two plugs are linked to­gether by a short length of bead chain. The shipping plug should be placed back in the vent hole whenever the attenuator is to be shipped. Be careful not to lose the O­Ring seal. Refer to figures 2 and 3 for plug identification.
Page 19
Figure 2
Shipping Plug
Figure 3
Vent Plug
Operating Instructions
O-ring seal
O-Ring Seal
Thermo-
switch
As an optional item, the attenuator can be provided with a thermoswitch assembly (P/N 8329-028). When the ther­moswitch is installed, it prevents possible damage from acci­dental power overloading from the transmitter or equipment malfunction. The thermoswitch is normally closed and opens at a maximum safe temperature of +200°C
(+392°F). Since the thermoswitch is connected in series with the transmitter interlock, it cuts off the transmitter power if
the coolant temperature exceeds this value. The assembly consists of:
s
Thermoswitch body - P/N 8329-027
s
Coupling Jack - P/N 2450-018
If the thermoswitch is to be field installed, proceed as fol­lows:
1. Replace the vent plug with the ship­ping plug.
2. Stand the unit on its back end with the input connector end up.
+
Note: In this position there is no danger of the coolant pouring out through the socket plug hole.
3. Remove the socket plug located just above the connector on the front face of the radiator. Use a 9/16 hex wrench.
9
Page 20
Bird Model 8329-300 Tenuline Attenuator
Note: Be very careful removing the iron pipe
+
plug, the threads in the socket hole are alumi­num, and can be easily damaged.
4. Replace the plug with the ther­moswitch. Use an acceptable pipe seal­ing compound sparingly only on the external threads of the thermoswitch.
Note: Do not contaminate the coolant with pipe
+
sealing compound.
5. Check the unit for coolant leaks.
While following the instructions for connecting the Ther­moswitch, refer to figure 4.
1. Unscrew the larger knurled ring-nut (A) at the lower end of the coupling jack assembly. Pull it off from the thermoswitch jack (B). Unscrew the small knurled cover fitting (C) from the base plug (D) of the connector to release the base.
Figure 4
Thermoswitch
Assembly
10
A
D
F
C
E
H
B
G
Page 21
Operating Instructions
2. Thread the interlock wires through the clamp (E) with the washers (F) in­side and with its threaded fitting in place.
3. Service the interlock wires with short tips, use spaghetti sleeves over the wire ends if needed.
4. Securely solder the interlock leads to the lugs (G) of the connector base.
Note: Be sure that the larger captive clamping
+
nut (A) is in place over the base plug (D) with the knurled end outward.
5. Screw on the cover ring (C) first, then fasten the cable clamp (E) in place, and tighten the two yoke screws (H) on the cable. Push the plug back onto the thermoswitch, and tighten the captive knurled connecting ring. Do not attempt to operate the equipment without the interlock attached.
Blower
Assembly
For field installation of the blower assembly refer to the blower instruction manual.
11
Page 22
Bird Model 8329-300 Tenuline Attenuator
12
Page 23
Chapter 4
Operating Instructions
There are no operating controls for the Model 8329-300 Attenuator. However, if it is equipped with a blower assem­bly, BA-300, there will be an ON/OFF switch and a BLOWER ON indicator lamp on the assembly. Read and be­come familiar with the following instructions before operat­ing the unit.
Initial
Adjustments
Connection
Before connection of the attenuator, perform the following steps.
1. Wipe all connectors and insulator sur­faces on the transmission line face with a clean soft cloth.
2. Check the RF input connector. Clean the connector if necessary. Use a self­drying, non-residue forming contact cleaner on the inaccessible portions of the connector.
3. Check the input resistance of the attenuator. Refer to the Maintenance chapter.
WARNING
Never attempt to disconnect the equipment from the
transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
The front or input end of the attenuator is identified by the four inch (102mm) diameter die-cast aluminum disc on which the connector is mounted. The rear face of the unit has OUTPUT stenciled above the connector. Do not couple the attenuator backwards to the direction of power flow. De­struction of the output resistor will result.
1. Connect the attenuator input to the transmitter’s power output. Use 50 ohm coaxial cable.
13
Page 24
Bird Model 8329-300 Tenuline Attenuator
2. Connect the attenuator output to a suitable load with 50 ohm coaxial ca­ble (RG-8A/U, RG-9/U, RG-213/U or equivalent) equipped with connectors which mate with the RF output connector of the attenuator.
3. Follow the transmitter manufacturer’s instructions.
Note: If the attenuator is to be operated at both
+
maximum power and frequency values, use a Male LC connector with a suitable cable (RG­218/U or RG-220/U) on the input and Male N connector with appropriate cable or load on the output. These connect to the RF fittings nor­mally supplied.
Before applying any RF power to the attenuator, be certain to check that the vent plug is in place in the vent hole. Refer to the Installation Chapter.
Normal
Operation
14
WARNING
The vent plug must be used at all times when the unit
is in operation or cooling. Failure to do this could
result in damage to the equipment and endanger the
operator’s safety. Be sure to check the plug.
WARNING
Using this attenuator in the upper end of its power
dissipation range will cause the housing to become hot.
Care should be exercised in touching it.
CAUTION
This equipment is designed for operation in a
horizontal position only, with mounting brackets down.
Do not operate in any other manner.
CAUTION
RF power rating must always be cut in half when the
blower assembly is installed but is not running. Under
this conditiona2kWattenuator will be limited to
approximately 1 kW.
Page 25
Operating Instructions
Because the Model 8329-300 attenuator is a passive device and has no indicators or controls, it requires no operating procedures or surveillance when the performance limits are not exceeded. It should function faultlessly, absorbing and converting the excess RF energy into heat indefinitely, if it is properly maintained and not subjected to an overload.
Operation
Under
Abnormal
Conditions
Shutdown
The Model 8329-300 Attenuator is not intended or recom­mended for outdoor use. The attenuator may be subjected to moderate overloads for limited periods of time without over­heating. However, this should be done cautiously, and it is strongly recommended that if such a use is contemplated, the attenuator should be equipped with a thermoswitch. When interlocked with the power line to the source of RF energy, the thermoswitch becomes a fail safe device to guard the attenuator against the dangers of overheating.
WARNING
Never attempt to disconnect the equipment from the
transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
This attenuator, being a passive device, cannot be shut off. Only the optional blower can be shut off. The source of RF energy must be turned off instead.
1. Turn off the source of RF power.
2. Let the blower run of at least five min­utes to adequately cool the radiator.
3. Turn off the blower.
Emergency
Shutdown
Turn off the RF power at the source.
15
Page 26
Bird Model 8329-300 Tenuline Attenuator
16
Page 27
Chapter 5
This chapter contains operator maintenance instructions, troubleshooting, and parts information.
Troubleshooting
Problem Possible Cause Remedy
Leakage of Coolant Oil around clamping band or radiator housing.
Excessive overheating of the radiator
High or low dc resis­tance values.
Maintenance
Clamping band not tight Tighten slightly with a
screwdriver.
Faulty O-Ring (input) Replace per the instruc-
tions in this Chapter.
Faulty O-Ring (output) Replace per the instruc-
tions in this Chapter.
Transmitter power too high
Blower off or malfunc­tioning (if equipped).
Faulty RF section as­sembly
Coolant Oil level too low
Faulty RF input connec­tor
Loose RF input connec­tor
Faulty RF section as­sembly
Reduce transmitter power
Turn on blowers; con­sult troubleshooting in the blower manual.
Replace per the instruc­tions in this chapter.
Add more coolant oil to the radiator per the in­structions in this chapter
Replace per the instruc­tions in this chapter
Tighten with a screw­driver
Replace per the instruc­tions in this chapter
Cleaning
The most important cleaning task is to remove accumula­tions of dust and lint from the radiator fins. An extensive collection of dust and lint on the cooling fins will interfere with the efficient dissipation of heat.
When dirt and dust have accumulated on the radiator fin spaces it should be cleaned.
17
Page 28
Bird Model 8329-300 Tenuline Attenuator
Preparation:
Material: Lint-free cleaning cloth
s
Mild detergent
s
To clean the unit follow the instructions below.
1. Gently remove loose dirt and grime using a soft clean cloth dampened with a mild warm solution of deter­gent and water.
2. Check the condition of the RF coaxial connector. If it needs cleaning, clean the connector with a self-drying con­tact cleaner that leaves no residue on the inaccessible portions.
Preventive Maintenance
Measure dc
Resistance
Preparation:
s Tools: Common hand tools s Multimeter with an accuracy of ±1% at 50
ohms.
s Temperature of the load between 20°C to 25°C
(68°F to 77°F)
Accurate measurement of the dc resistance between the in­ner and outer conductors of the RF input connector will pro­vide a good check of the condition of the load resistor. Checking the dc resistance is simply used to measure a change in the condition of the resistor over time. The track­ing of the dc resistance must start before the resistor is first put into service. Perform the following steps and record the value for future comparison. Check and record the resis­tance of the load periodically according to use.
WARNING
Never attempt to disconnect the equipment from the
transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
1. Turn off RF power and interlock cir­cuitry before any electrical disconnec­tions are made.
18
2. Disconnect the RF coaxial line.
Page 29
Figure 5
Meter Lead
Placement
Maintenance
3. Connect the multimeter test leads across the center and outer conductor of the load resistor. Refer to figure 5.
4. Record the value of the resistance be­fore the load is put into service. Com­pare the subsequent values with the latest reading. If the values vary more than 2 ohms, this could be an indica­tion of a failing resistive element.
+
Note: It is recommended that this resistance check be performed each time the load is to be used.
RF Connector
Tools Required: Screwdriver
The connector is a “Quick-Change” design which permits easy interchange with the use of only a screwdriver. For re­placement, proceed as follows:
1. Remove and retain the four screws from the corners of the RF connector.
2. Pull the connector straight out of its socket.
3. Insert the new connector into the mat­ing connector. Be sure the projecting center pin on the connector is properly engaged and seated in the mating socket, then push it in firmly.
19
Page 30
Bird Model 8329-300 Tenuline Attenuator
4. Install the four screws that were pre­viously removed.
Coolant
The level of the dielectric coolant should remain constant in the unit after prolonged usage under normal operating con­ditions. As shipped, the coolant is at a factory determined level, and should be about 3-1/4" (82.5mm) below the surface of the thermoswitch hole, with the unit in a vertical posi­tion. However, loss of up to 10% of the full tank capacity should not impair the operating efficiency of the attenuator. The coolant should be a light yellow color. If it is dark and not a light yellow, it may be contaminated and should be re­placed. Occasionally inspect around the clamping band at the input end for possible coolant leakage. Tighten the clamping screw if necessary, and make certain the O-Ring seal is in good condition; i.e., soft and pliable and free from surface cracks.
Adding
Coolant
Replacing
Coolant
Add coolant through the pipe plug hole (thermoswitch hole) until it reaches the proper level, about 3-1/4 inches below the surface of the hole. Do not overfill the unit beyond the recommended level.
To replace all of the coolant use the following procedure:
1. Remove the rear (output) connector.
2. Replace the vent plug with the ship­ping plug.
3. Carefully raise the unit by its front handle and foot until it is tipped up on its back.
4. Position the load on the bench top so that the entire rear connector assem­bly, minus the connector, projects over the edge of the bench. Brace it verti­cally in this position so that it will not topple over.
5. Place a clean container for liquid just under the rear connector assembly to receive the coolant. The volume of the coolant is 2.9 gallons (11 liters), so the container must be at least a three gal­lon size, and preferably five gallons.
20
Page 31
Maintenance
6. Remove the V-band clamp from around the front (input) connector as­sembly by loosening the 10-32 holding screw sufficiently to slip the band off.
7. Carefully work the RF section assem­bly loose and lift it straight out of the resistor tank.
Note: There will be some initial resistance as
+
the O-Ring seal around the rear connector as­sembly comes loose from the housing.
As the RF section comes out of the rear connector assembly, the coolant will start to pour into the container. Work the RF section loose slowly, so that the coolant doesn’t splash.
8. Let the coolant drip for a few minutes to get as much as possible out of the radiator tank. As the RF section is raised out of the radiator tank some coolant will be trapped in the rear end cylinder. Turn the section over care­fully to empty it out.
+ Note: An alternate, but much slower, method of
draining the radiator would be to siphon the coolant out of the thermoswitch hole.
9. Discard the contaminated coolant col­lected in the container.
10. Replace the RF section assembly mak­ing sure that it is smoothly and firmly seated in the rear connector assembly.
11. Replace the V-band on the front con­nector plate assembly and tighten the screw.
12. Add clean coolant to the unit. Fill the unit until the level is about 3-1/4 inches below the thermoswitch hole.
13. Coat the pipe plug or thermoswitch threads sparingly with pipe sealant. Do not contaminate the coolant.
21
Page 32
Bird Model 8329-300 Tenuline Attenuator
14. Screw the pipe plug or thermoswitch back in place carefully to avoid strip­ping the aluminum threads of the plug hole.
15. Lower the attenuator back onto its feet.
16. Check all seals for signs of leaks.
RF Load Resistor
To replace the load resistor follow the same procedure as in the Replacing Coolant section. However, inspect the O-Ring seals. Do not reuse the O-Rings if they are no longer soft and pliable or shows signs of cracks. If the coolant removed is not contaminated, it may be reused in the radiator tank with additional new coolant as required. The RF section is not field repairable and further disassembly should not be attempted. Return the entire RF assembly to the factory for repair or replacement.
Thermoswitch
To remove or replace the thermoswitch use the procedures in the Thermoswitch paragraph in Chapter 3 - Installation.
22
Repairs
Any maintenance or service procedure beyond the scope of those provided in this section should be referred to a quali­fied service center.
Page 33
Customer Service
Maintenance
Sales /
Repair
Facilities
Sales
Facilities
RF Section
Assembly
Complete
Unit
U.S.A. Sales and Manufacturing
Service Group Bird Electronic Corporation 30303 Aurora Road Cleveland (Solon), Ohio 44139-2794 Phone: (440) 248-1200 Fax: (440) 248-5426
For the location of the sales office nearest you, give us a call or visit our Web site at:
http://www.bird-electronic.com
Shipment
Wrap the RF section assembly with sufficient padding to avoid damage in shipping and tape securely. Place the wrapped RF section in a cardboard carton and pad or brace it to prevent shifting.
Should you need to return the attenuator, first remove the vent plug and replace it with the shipping plug. The unit may be shipped with its dielectric coolant; however, do not ship the unit with its dielectric coolant if the unit has devel­oped a leak. Drain the coolant first. Place the attenuator in a wooden crate or other substantial shipping container, and pack or brace it securely to prevent damage in shipping.
All instruments returned for service must be shipped pre­paid and to the attention of the Customer Service Group.
23
Page 34
Bird Model 8329-300 Tenuline Attenuator
Storage
No special preparations for storage are necessary other than to cover the equipment to keep out dust and dirt. Store the unit in a dry and dust-free environment where the ambient temperature will remain within the -40°C to +45°C (-40°F to +113°F) operational range of the load.
Replacement Parts List
Qty. Description Part Number
1 RF Section Assembly 8329-302 1 Radiator Assembly 8329-307
Coolant - 2.9 gallons (11 liters) 5-1070-2 (1
1 “QC” Connector *See Below 1 Clamp Band Assembly 2430-043 1 O-Ring Seal, Input 5-230 1 O-Ring Seal, Output 5-243 1 Vent Plug 2450-094 1 Shipping Plug 2450-049 1 O-Ring, Vent and Shipping Plug 5-504 1 Chain Assembly 8180-094
gallon)
24
*Available “QC” Type Connectors
N-Female (output)
N-Male 4240-063 LT-Male 4240-012 HN-Female 4240-268 C-Female 4240-100 HN-Male 4240-278 C-Male 4240-110 LC-Female
(input) 7/8” EIA Air
Line
Normally Supplied
4240-062 LT-Female 4240-018
4240-031 UHF-Female
(SO-239)
4240-002
4240-050
Page 35
Limited Warranty
All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise spec­ified, from date of shipment and to conform to applicable specifications, draw­ings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or repairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transporta­tion-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufac­turer’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, IN­CLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGA­TION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
Loading...