Bird Technologies 8251D208 User Manual

INSTRUCTION BOOK
OPERATING INSTRUCTIONS
TERMALINE
COAXIAL LOAD RESISTOR
MODEL 8251D208
Electronic Corporation
Cleveland (Solon) Ohio US
Copyright 1998 by Bird Electronic Corporation
Instruction Book Part Number 920-8251D208 Rev. A
Termaline
is a Registered Trademark of
Bird Electronic Corporation
Safety Precautions
The following are general safety precautions that are not necessarily related to any specific part or procedure, and do not necessarily appear elsewhere in this publication. These precautions must be thoroughly understood and apply to all phases of operation and maintenance.
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety precautions. Do not replace components or make adjustments to the inside of the test equip­ment with the high voltage supply turned on. To avoid casualties, always re­move power.
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is pres­ent.
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure for the purpose of service or adjustment of equipment except in the presence of some­one who is capable of rendering aid.
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the main power source to test instruments. Grounding one conductor of a two conduc­tor power cable is not sufficient protection. Serious injury or death can occur if this grounding is not properly supplied.
Resuscitation
Personnel working with or near high voltages should be familiar with modern methods of resuscitation.
Safety Symbols
WARNING
Warning notes call attention to a procedure, which if not correctly
performed, could result in personal injury.
i
CAUTION
Caution notes call attention to a procedure which if not correctly
performed, could result in damage to the instrument.
This symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
Note: Calls attention to supplemental informa-
+
tion.
Warning Statements
The following safety warnings appear in the text where there is danger to op­erating and maintenance personnel and are repeated here for emphasis.
WARNING
The vent plug must be used at all times when the unit is in operation
or cooling. Failure to do this could result in damage to the equipment
and endanger the operator’s safety. Be sure to check this plug.
WARNING
Using this load in the upper end of its power dissipation range will
cause the housing to become hot! Care should be exercised in touching
it.
WARNING
Never attempt to connect or disconnect RF equipment from the
transmission line while RF power is being applied. Leaking RF energy
is a potential health hazard.
Caution Statements
The following equipment cautions appear in the text whenever the equipment is in danger of damage, and are repeated here for emphasis.
CAUTION
This equipment is designed for operation in a horizontal position only,
with mounting brackets down. Do not operate in any other manner.
CAUTION
Do not operate this equipment over the rated 1000 watts continuously.
Damage to the resistive element will result.
ii
CAUTION
The unit is factory filled to the proper level with 1.1 gallons (4.2 liter)
of Bird P/N 5-1070. No other coolant should be used
CAUTION
Do not leave out the O-Ring seal, P/N 5-504 when interchanging the
vent and shipping plugs.
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ES­PECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRU­MENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS EXPLICITEMENT PRÉVUE PAR LE FABRI­CANT PEUT ENDOMMAGER LE DISPOSITIF DE PRO­TECTION DE L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZ­ZATO IN MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
iii
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERV­ICE - TRAINED PERSONNEL ONLY. TO AVOID DAN­GEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO DEL PERSONAL DE SERVICIO CA­PACITADO. PARA EVITAR EL PELIGRO DE DES­CARGÉAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERV­ICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRA­TIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE ESCLUSIVAMENTE PER IL PERSONALE OP­PORTUNAMENTE ADDESTRATO. PER EVITARE PERI­COLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
iv
About This Manual
This instruction book covers the model 8251D208 Termaline Coaxial Resis­tor.
This instruction book is arranged so that essential information on safety is contained in the front of the book. Reading the Safety Precautions Section be­fore operating the equipment is strongly advised.
The remainder of this instruction book is divided into Chapters and Sections.
Operation
First time operators should read Chapter 1 - Introduction, Chapter 2 - Theory of Operation, and Chapter 3 - Installation to get an overview of equipment ca­pabilities and how to install it. An experienced operator can refer to Chapter 4 - Operating Instructions. All instructions necessary to operate the equip­ment, are contained in this chapter.
Maintenance
All personnel should be familiar with preventive maintenance found in Chap­ter 5 - Maintenance. If a failure should occur, the troubleshooting section will aid in isolating and repairing the failure.
Parts
For location of major assemblies or parts, refer to the parts lists and associ­ated drawings in Chapter - Maintenance.
Changes To This Manual
We have made every effort to ensure this manual is accurate. If you should discover any errors, or if you have suggestions for improving this manual, please send your comments to our factory. This manual may be periodically updated. When inquiring about updates to this manual refer to the part number and revision level on the title page.
v
Bird Model 8251D208 Termaline Coaxial Load Resistor
vi
Table Of Contents
Safety Precautions. ......................i
Warning Statements. ......................ii
Caution Statements........................ii
Safety Statements. .......................iii
About This Manual. .......................v
Introduction. ........................1
Purpose and Function. ...................1
Applications. .......................1
Performance Characteristics and Capabilities. .........1
Power and Utility Requirements................1
Environmental Requirements. ................2
Items Supplied. ......................2
Items Required. ......................2
Tools and Test Equipment . .................2
Specifications. .........................3
Theory of Operation. .....................5
Cooling. .........................5
Installation. .........................7
Location. .........................7
Shipping and Vent Plugs. ..................7
Connecting to Transmitter. ....................8
Operating Instructions. ....................9
Normal Operation. .....................9
vii
Bird Model 8251D208 Termaline Coaxial Load Resistor
Operation Under Abnormal Conditions. ............9
Shutdown. ........................9
Emergency Shutdown. ...................10
Maintenance. ........................11
Troubleshooting. ........................11
Cleaning. ...........................11
Inspection. ..........................12
Preventive Maintenance. ....................12
Checking Coolant Level. ..................12
DC Resistance Measurement. ..................13
Preparation and Tools Required. ..............13
Checking the DC Resistance . ...............13
Disassembly. .........................14
Tools Required.......................14
RF Connector. ......................14
Rear Seal and Coolant. ..................15
RF Load Resistor Assembly. ................15
Radiator Handle. .....................15
Assembly............................16
RF Connector. ......................16
Diaphragm and Coolant Oil. ................16
RF Load Resistor Assembly. ................16
Radiator Handle. .....................16
Storage. ...........................17
Customer Service. .......................17
Sales/Repair Facilities. ..................17
viii
Sales Facilities. .....................17
Preparation for Shipment. ....................17
Replacement Parts List......................18
ix
Bird Model 8251D208 Termaline Coaxial Load Resistor
x
Chapter 1
Introduction
This publication covers the Termaline Coaxial Load Resistor Model 8251D208. The Termaline Coaxial Load Resistor will generally be referred to as a load thoughout this manual.
This chapter contains introductory information including product specifications; items supplied; and accessory items available.
Purpose and
Function
The Bird Termaline Coaxial Load Resistor is a portable, general purpose 50 ohm coaxial transmission line termina­tion. The load is a low reflection, nonradiating termination for coaxial transmission lines operating in the UHF (470 ­860 MHz) band.
The load is rectangular in shape with transverse fins encas­ing a dielectric coolant cylinder. A retractable handle is re­cessed in the radiator fins. The front and rear fins are made of heavier gauge material and are bent 90° to form bottom mounting flanges. These flanges are supports for free stand­ing use, or brackets for fixed mounting. Holes are provided in the flanges for fixed mounting.
Applications Use these loads:
s
s
s
Performance
Characteristics
Capabilities
The Model 8251D208 load can absorb up to 1000 watts con­tinuously and dissipate it harmlessly as heat over a fre-
and
quency range of 470 to 860 MHz. The actual VSWR, “voltage standing wave ratio”, will not exceed 1.065:1 over the fre­quency range stated.
As a substitute antenna for tuning transmit­ters under nonradiation conditions or making routine test and adjustments.
As a substitute for any circuit loading ele­ment.
To measure, with a suitable indication device, the power output of any coaxially transmitted signal within their range.
Power and
Requirements
Utility
This load is a passive device that is self-contained and re­quires only RF input to function.
1
Bird Model 8251D208 Termaline Coaxial Load Resistor
Environmental
Requirements
Items Supplied
Items
Required
Tools and
Test
Equipment
The load should be operated in a dust and vibration free, dry environment. Allow at least 6 inches (153 mm) of clear­ance around the unit to permit adequate heat dissipation.
Load Resistor
s
Instruction Book
s
Matching connector on the coaxial transmission line to which the load will be attached.
Screwdriver and an adjustable wrench will be necessary for disassembly of this equipment.
A resistance bridge or ohmmeter with an accuracy of one percent or better at 50 ohms is useful for checking the resis­tance value of the RF section assembly.
2
Introduction
Specifications
Impedance, Nominal 50 ohms VSWR: 1.065:1 Connector: 1-5/8" EIA flanged Power Range: 1000 watts continuous Frequency Range: 470 to 860 MHz Ambient Temperature: -40°C to +45°C (-40°F to +133°F) Cooling Method Oil dielectric and convection currents Dimensions: 17-29/32"L x 5-15/16"W x 8-1/2"H
(455 x 151 x 216 mm)
Weight:
Net Shipping
Operating Position: Horizontal only - vent plug up Finish: Grey Powder Coat European Safety: Meets European Standard EN 61010-1:1993 -
25 lb. 8 oz. (11.6 kg) 30 lb. (13.6 kg)
Safety, Group II. In accordance with Council Di­rective 73/23/EEC and 93/68/EEC.
3
Bird Model 8251D208 Termaline Coaxial Load Resistor
4
Chapter 2
Theory of Operation
This load consists essentially of a carbon film resistor on a ceramic substrate immersed in a dielectric coolant. The re­sistor, individually selected for its accuracy, is enclosed in a special exponentially tapered housing. This provides a lin­ear reduction in surge impedance directly proportional to the distance along the resistor. When surrounded by the di­electric coolant, the characteristic impedance is therefore: 50 ohms at the front (connector end), 25 ohms at the mid­point (to compensate for the resistance already passed over), and zero ohms at the rear where the resistor joins the hous­ing, forming the return conductor of the coaxial circuit. This produces a uniform, practically reflectionless line termina­tion over the stated frequencies of the load resistor.
Cooling The dielectric coolant was chosen for its desirable dielectric
and thermal characteristics. Cooling of the load is accom­plished by natural fluid and air convection currents. The 1.1 gallons (4.2 liters) of dielectric coolant carries the electri­cally generated heat from the resistor to the walls of the cy­lindrical cooling tank. This tank is encased in a set of radiating fins, constructed from heavy gauge aluminum al­loy, and firmly pressed into the cylinder. The heat from the dielectric oil is transferred to the surrounding air by the fins.
Expansion of the coolant, caused by the rise in its tempera­ture, is allowed for by the use of an expansion tank located on the upper rear of the load. The expansion tank is equipped with a spring loaded vent for relief of the internal pressure.
5
Bird Model 8251D208 Termaline Coaxial Load Resistor
Figure 1
Shipping Plug
O-ring seal
Figure 2
Vent Plug
O-Ring Seal
6
Chapter 3
Installation
CAUTION
This equipment is designed for operation in a
horizontal position only, with mounting brackets down.
Do not operate in any other manner.
The load is to be installed, and operated in a horizontal posi­tion. The load is shipped horizontal, and normally stands on its base brackets.
The load may be used for portable operation and stand free, or it may be secured to a bench top or other flat surface for a fixed installation. Mount the load with four screws of up to 1/4 inch diameter. Fasten the screws through the four 9/32 inch holes in the mounting brackets that arranged in a 5-1/8 inch x 15 inch (130.2 x 381 mm) rectangle.
Location For operation above 300 watts allow at least six inches (153
mm) of clearance on each side. Operate the load in a hori­zontal position only, with the handle on top.
Shipping and
Vent Plugs
WARNING
The vent plug must be used at all times when the unit
is in operation or cooling. Failure to do this could
result in damage to the equipment and endanger the
operator’s safety. Be sure to check this plug.
CAUTION
Do not leave out the O-Ring seal, P/N 5-504 when
interchanging the vent and shipping plugs.
Before placing the unit into operation, remove the shipping plug on the top of the radiator and replace with the vent plug supplied. Refer to figures 1 and 2 for identification of the plugs. Don’t forget to use the O-Ring seal, P/N 5-504. The shipping and vent plugs are connected with a short length of bead chain to prevent the mislaying or loss of the unused plug.
7
Bird Model 8251D208 Termaline Coaxial Load Resistor
Connecting to
Transmitter
the
Connect the load to the transmitting equipment under test with 50 ohm coaxial cable (RG-8A/U, RG-9/U, RG-213/U or equivalent). After the transmitter has been connected to the load, proceed according to the transmitter manufacturer’s instructions. When reconnecting the antenna, it may be nec­essary to slightly readjust the transmitter due to possible differences in VSWR between the load and the antenna sys­tem.
The 1-5/8 inch EIA flange connector is fastened to the trans­mission line by four 5/16-18 x 1-1/2 bolt sets. The center con­ductors must be joined with a bullet for 50 ohm 1-5/8 inch coaxial lines. Bird P/N 4712-020 Bullet Kit includes the bolt sets, O-Ring, and center conductor bullet.
Note: Avoid the use of adapters and elbows
+
whenever possible.
Refer to figure 3 while following the instructions below.
1. Seat the bullet so that half of the thickness of the insulator is nested in the counterbore of each connector flange.
2. Place the load resistor so that it will be aligned with the coaxial input line.
3. Push in on the center contact.
Figure 3
Connection to
Transmitting
Equipment
8
4. Tighten the flange nuts evenly all around (finger tight).
5. Tighten the nuts evenly with wrenches.
RF Coaxial Line
Bolt
Bullet
Flange
Normal
Operation
Operation
Under
Abnormal
Conditions
Chapter 4
Operating Instructions
CAUTION
Do not operate this equipment over the rated 1000
watts continuously. Damage to the resistive element
will result.
The load has no indicators or operating controls, therefore it requires no special operating procedures or surveillance when the stated performance limits are not exceeded. Fol­low the instructions pertaining to the specific transmitting equipment.
WARNING
Using this load in the upper end of its power
dissipation range will cause the housing to become hot!
Care should be exercised in touching it.
These units will sustain an input moderately greater than 1000 watts for short periods of time. Such loading must be spaced at reasonable intervals to allow sufficient time for the load to cool to a safe temperature. The load can, for in­stance, sustain an input of 1200 watts for a maximum of five minutes with an interval of at least 30 minutes between each power application.
Shutdown These loads, being passive devices, have no way of being
turned off. Their source of RF power must be turned off in­stead.
9
Bird Model 8251D208 Termaline Coaxial Load Resistor
Emergency
Shutdown
WARNING
Never attempt to connect or disconnect RF equipment
from the transmission line while RF power is being
applied. Leaking RF energy is a potential health
hazard.
Turn off RF power at the source.
10
Chapter 5
Maintenance
This chapter contains information for cleaning, inspection, troubleshooting, and performance of this load.
Troubleshooting
Refer to this table when troubleshooting the load for aid in isolating the problem, and for possible causes and remedies.
Table 1
Troubleshooting
Problem Possible Cause Remedy
Coolant oil leak around clamping bands or radiator housing
Overheating of the radiator
Clamping bands not tight
Faulty O-Ring (front)
Faulty O-Ring (rear) Replace O-Ring Transmitter power
too high Coolant oil level too
low
Accumulation of dirt on cooling fins
Faulty RF section assembly, check dc resistance
Tighten screw slightly with a screwdriver
Replace O-Ring
Reduce transmit­ter power
Add more cool­ant oil to the ra­diator
Clean cooling fins
Replace if needed
Cleaning
The outside surface of the load should be wiped free of dust and dirt when necessary. The principal maintenance re­quired by the operator will be to periodically wipe off the ac­cumulated dust and lint from the radiator fins. Excessive collection of dust and lint on the cooling fins will interfere with the efficient dissipation of heat. If the teflon insulator or metallic contact surfaces of the connector should become dirty, wipe them off with a soft cloth. If it becomes neces­sary to use a cleaner, use a contact cleaner that is self­drying and leaves no residue on the inaccessible internal parts of the connector.
11
Bird Model 8251D208 Termaline Coaxial Load Resistor
Inspection
With the rugged and simple construction of the loads, peri­odic inspection will be necessary at only about six month in­tervals. Inspection should include the items listed below:
1. Oil Leakage - check for coolant oil leaking around the radiator tank, particularly at the front and back around the underside of the clamping band. If leakage is observed, refer to the troubleshooting section and, check tightness of the front and rear clamping bands.
2. Inspect the load for dirt or dust buildup.
3. Inspect the load for completeness and general condition of the equipment.
Preventive Maintenance
Due to the basic simplicity of construction, the major re­quirement for preventive maintenance is to keep the equip­ment clean, particularly the radiator fins. It is important to maintain the heat transfer efficiency of the cooling fins. Also, occasionally check the coolant level in the radiator tank.
Checking
Coolant Level
12
CAUTION
The unit is factory filled to the proper level with 1.1
gallons (4.2 liter) of Bird P/N 5-1070. No other coolant
should be used
1. Remove the vent plug from the socket on the top surface of the expansion tank. Unscrew the vent plug using a 3/4 inch wrench.
+
Note: The coolant level, at room temperature, should not be more than 1/8 inch above the bot­tom surface of the expansion tank.
2. Check the coolant level by carefully lifting the front end of the load and noting presence of cool­ant on the bottom surface. The coolant quantity should be sufficient to fill the radiator cylinder. The inner housing, for the resistor element, is specially shaped to match the dielectric proper­ties of the recommended coolant.
3. Replace vent plug. If coolant needs to be added, refer to the RF Load Resistor section.
DC Resistance Measurement
Maintenance
Preparation
and Tools
Required
Be sure that the vent plug is installed.
Preparation:
Tools: Common hand tools
s
Ohmmeter with an accuracy of ± 1% at 50
s
ohms. Temperature of the load between 20°C to 25°C
s
(68°F to 77°F)
Accurate measurement of the dc resistance between the in­ner and outer conductors of the RF input connector will pro­vide a good check of the condition of the load resistor. Checking the dc resistance is simply used to measure a change in the condition of the resistor over time. The track­ing of the dc resistance must start before the resistor is first put into service. Perform the following steps and record the value for future comparison. Check and record the resis­tance of the load periodically according to use.
WARNING
Never attempt to connect or disconnect RF equipment
from the transmission line while RF power is being
applied. Leaking RF energy is a potential health
hazard.
Checking the
DC Resistance
Measure the dc resistance. Follow the instructions below.
1. Turn off RF power and interlock circuitry before any electrical disconnection’s are made.
2. Disconnect the RF coaxial line.
3. Connect the multimeter test leads across the cen­ter and outer conductor of the load resistor. Refer to figure 4 for placement of the leads.
4. Record the value of the resistance before the load is put into service. Compare subsequent values with the latest reading. If the values vary more than 2 ohms this could be an indication of a fail­ing resistive element.
13
Bird Model 8251D208 Termaline Coaxial Load Resistor
Figure 4
Measuring DC
Resistance
50.0
These tests are by no means a necessity to the operation of the load but merely guidelines for the users information.
Disassembly
There are no special techniques required for the repair or replacement of components in this Termaline Load Resistor.
Tools
Required
s screwdriver
s small wrench
s
adjustable wrench (for the connector bolts)
RF Connector The Model 8251D208 has a 1-5/8 inch EIA flanged connector
and must be returned to the factory for connector replace­ment.
Rear Seal and
Coolant
Before any disassembly of the rear of the load, if the coolant has not already been drained from the tank, stand the ra­diator on end with the connector pointed down.
1. Unscrew the four 10-32 screws at the corners of the guard cover.
2. Unscrew the tube nut from the tank nozzle, us­ing a small wrench if necessary, and pull the nozzle free.
3. Loosen the clamp screw with a screwdriver from the bottom of the clamping band, same type as at the front, and remove the clamping band.
4. Remove the rear cover which includes the at­tached escape tube with captive nut, P/N 2430­088, and the diaphragm seal, P/N 2430-089.
14
RF Load
Resistor
Assembly
Maintenance
5. Inspect the diaphragm seal and replace it if it is not soft and pliable, or shows signs of surface cracks.
6. Replace the coolant if it appears contaminated, i.e., if it is not clear.
The expansion tank is vented through the vent plug, P/N 2450-094. The unit unscrews from a socket on top of the tank, but is not itself subject to disassembly.
The shipping plug is sealed by compression of an O-Ring, P/N 5-504, which should be included when replacing the vent plug.
CAUTION
Do not leave out the O-Ring seal, P/N 5-504 when
interchanging the vent and shipping plugs.
1. Replace the vent plug with the shipping plug in the fill hole of the expansion tank to prevent coolant loss. Refer to figures 1 and 2 for plug identification.
Radiator
Handle
2. Stand the unit on its back end, i.e., vertically with the RF connector up. Brace the unit in this position to prevent it from tipping over.
3. Loosen the 10-32 x 1-1/2 inch screw on the clamping band until the band is free. Remove the band.
4. Grasp the RF connector and slowly lift the load resistor assembly out of the radiator tank to al­low the excess coolant to drip back in.
5. Before replacing the load assembly check the O­Ring seal to be sure it is properly placed and is in good condition. It should be free of twists and positioned evenly around the beveled flange of the resistor housing. Also, it should still be soft and pliable and not hard or showing signs of sur­face cracks.
The radiator handle slides on and is held in place by the two retaining studs that are riveted to the fins. It may be re­moved or replaced as follows:
15
Bird Model 8251D208 Termaline Coaxial Load Resistor
1. Gently pry apart the fins next to each stud just enough to clear the handle thickness.
2. With the fins pried apart sufficiently, slide each leg of the handle off its respective stud.
Assembly
Diaphragm
and Coolant
Oil
RF Load
Resistor
Assembly
To assemble the unit after replacing the diaphragm or add­ing coolant, follow the instructions below.
1. Install the diaphragm and the rear cover.
2. Install the clamping band and tighten the clamp screw with a screwdriver.
3. Install the tank nozzle and tighten the tube nut.
4. Install the guard cover with the screws previ­ously removed.
To assemble the unit after replacing the RF load resistor, follow the instructions below.
1. Grasp the RF connector and slowly lower the load resistor assembly into the radiator tank.
2. Install the clamping band and tighten the 10-32 x 1-1/2 inch screw on the clamping band.
3. Place the load in a horizontal position on a firm surface.
4. Replace the shipping plug with the vent plug in the fill hole of the expansion tank.
To install a new radiator handle, after having removed the defective handle, follow the instructions below.
16
Radiator
Handle
1. Place each leg of the new handle over the studs that the original handle was on.
2. Gently pry the fins until they are in their origi­nal position, and the handle will not come off of the studs.
Maintenance
Storage
No special preparations for storage are necessary other than to cover the equipment to keep out dust and dirt. Store the unit in a dry and dust-free environment where the ambient temperature will remain within the -40°C to +45°C (-40°F to +113°F) working range of the load.
Customer Service
Any maintenance or service beyond the scope of those pro­vided in this section should be referred to a qualified service center.
Any equipment returned must be shipped prepaid and to the attention of the Service Group.
Bird Electronic Corporation maintains a complete repair and calibration facility at the following address:
Sales/Repair
Facility
Sales
Facilities
Preparation
for Shipment
U.S.A. Sales and Manufacturing
Service Group Bird Electronic Corporation 30303 Aurora Road Cleveland (Solon), Ohio 44139-2794 Phone: (440) 248-1200 Fax: (440) 248-5426
For the sales office nearest you, call Bird Electronic Corpo­ration at the above telephone number, or visit our Web site at:
http://www.bird-electronic.com Should you need to return the load, use the original ship-
ping package if possible. Wrap the RF connector with pad­ding and tape securely in place. It is not necessary to remove the coolant to ship the load. Simply replace the vent plug with the shipping plug attached to the bead chain. Be sure the O-Ring seal is mounted on the plug to avoid leak­age.
17
Bird Model 8251D208 Termaline Coaxial Load Resistor
Replacement Parts List
Qty. Description Part Number
1
1
1
1.1 gals (4.1 liter)
1
1
2
1
1
1
1
1
2
1
RF Section Assembly 8890-050 Radiator Assembly 2430-123 Diaphragm Cover Guard 2430-078 Coolant Oil - Dielectric
1 pint container 1 gallon container 5 gallon container
5-1070-1 5-1070-2
5-1070-3 Diaphragm Seal 2430-089 Diaphragm Cover 2430-088 Clamp Band Assembly (2430-043 & screw) 2430-055 RF Section O-Ring Seal 5-230 Vent Plug 2450-094 Shipping Plug 2450-049 Radiator Handle 2430-028 Chain Assembly 8180-094 Vent and Shipping Plug O-Ring 5-504 Expansion Tank, part of Radiator 2430-080
18
Limited Warranty
All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise specified, from date of shipment and to conform to applicable specifications, drawings, blueprints and/or samples. Seller’s sole obligation under these war­ranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or re­pairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transportation-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufactur­er’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, IN­CLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGA­TION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
19
DECLARATION OF CONFORMITY
Manufacturer: Bird Electronic Corporation
Product: TERMALINE RF COAXIAL LOAD RESISTOR
The undersigned hereby declares, on behalf of Bird Electronic Corporation of Cleveland, Ohio, that the above-referenced product, to which this declaration relates, is in conformity with the provisions of the following standards;
1. European Standard EN 61010-1:1993 - Safety, Group II.
This standard is in accordance with Council Directive 73/23/EEC and 93/68/EEC.
The technical documentation file required by this directive is maintained at the corporate headquarters of Bird Electronic Corporation, 30303 Aurora Road, Cleveland, Ohio.
30303 Aurora Road Cleveland, Ohio 44139-2794
Model: 8251D208
Ken DeVore QA/Metrology Manager Bird Electronic Corporation
20
Loading...