Bird Technologies 8201 User Manual

Page 1
INSTRUCTION BOOK
OPERATING INSTRUCTIONS
TERMALINE®COAXIAL
LOAD RESISTOR
MODELS 8201 & 8203
Electronic Corporation
Cleveland (Solon) Ohio USA
©Copyright 1998 by Bird Electronic Corporation
Termaline® is a Registered Trademark
of Bird Electronic Corporation
Page 2
Page 3
Safety Precautions
The following are general safety precautions that are not necessarily related to any specific part or procedure and do not necessarily appear elsewhere in this publication.
Keep Away From Live Circuits
Operating personnel must at all times observe general safety precautions. Do not replace components or make adjustments inside equipment with the high voltage supply turned on. To avoid casualties, always remove power.
Do Not Service or Adjust Alone
Under no circumstances should any person reach into an enclosure for the purpose of service or adjustment of equipment except in the presence of some­one who is capable of rendering aid.
Shock Hazard
Do not attempt to disconnect an RF transmission or any other high voltage line while power is present. Radiated RF power is a potential health hazard.
Resuscitation
Personnel working with or near high voltage should be familiar with modern methods of resuscitation.
Safety Symbols
WARNING
Warning notes call attention to a procedure which, if not correctly
performed, could result in personal injury.
CAUTION
Caution notes call attention to a procedure which, if not correctly
performed, could result in damage to the instrument.
This symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
+
Note: Calls attention to supplemental informa­tion.
i
Page 4
Warning Statements
The following safety warnings will appear in the text and are repeated here for emphasis.
WARNING
When power is in the upper range of the load’s capacity, the radiator
will become hot - care should be used in touching the equipment.
WARNING
Do not attempt to disconnect these loads from the coaxial cable while
RF energy is still being applied. Leaking RF power is a potential
health hazard.
Caution Statements
The following equipment cautions appear in the text and are repeated here for emphasis.
CAUTION
The load is designed for operation in a horizontal plane only, with
mounting brackets down. Do not operate in any other position.
CAUTION
Do not operate this equipment continuously above the rated 500 W for
Model 8201, or 600 W for Model 8203. Load failure will result.
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
ii
Page 5
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS EXPLICITEMENT PRÉVUE PAR LE FABRI­CANT PEUT ENDOMMAGER LE DISPOSITIF DE PRO­TECTION DE L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SER­VICE - TRAINED PERSONNEL ONLY. TO AVOID DAN­GEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
iii
Page 6
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
iv
Page 7
About this Manual
This instruction book covers the Models 8201 and 8203 Termaline Load Re­sistors.
This instruction book is arranged so that essential information on safety is contained in the front of the book. Reading the Safety Precaution section be­fore operating the equipment is strongly advised.
The remainder of this Instruction Book is divided into chapters and sections.
Operation
First time operators should read Chapter 1 - Introduction, Chapter 2 - Theory of Operation, and Chapter 3 - Installation, to get an overview of equipment capabilities and how to install it. An experienced operator can refer to Chap­ter 4 - Operating Instructions. All instructions necessary to operate the equipment, are contained in this section.
Maintenance
All personnel should be familiar with calibration and repair information found in Chapter 5 - Maintenance. If a failure should occur, the troubleshoot­ing section will aid in isolating and repairing the failure.
Parts
For location of major assemblies or parts refer to the part lists and associated drawings in Chapter 5.
Changes To This Manual
We have made every effort to ensure this manual is accurate. If you should discover any errors, or if you have suggestions for improving this manual, please send your comments to our factory. This manual may be periodically updated. When inquiring about updates to this manual refer to the part num­ber and revision level on the title page.
v
Page 8
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
vi
Page 9
Table Of Contents
Safety Precautions. .......................i
Warning Statements. ....................ii
Cautions Statements. ....................ii
Safety Statements .....................ii
About This Manual .....................v
Introduction. ..........................1
Purpose and Function. ...................1
Description. ........................1
Performance and Capabilities. ................1
Dimensions and Weight. ...................2
Power and Utility Requirements. ...............2
Environmental Requirements. .................2
Items Supplied. ......................2
Items Required. ......................2
Tools and Test Equipment...................2
Specifications. .......................3
Theory of Operation. ......................5
General. .........................5
Cooling. .........................5
Installation. ..........................7
Location. .........................7
Mounting. .........................7
Operating Instructions. .....................9
Use and Function of Controls. ................9
vii
Page 10
Initial Adjustments. .....................9
Start-up. .........................9
Normal Operation. .....................9
Operating Under Emergency, Adverse, or Abnormal Conditions....9
Shutdown. ........................10
Emergency Shutdown. ...................10
Maintenance. .........................11
Cleaning. ........................11
Inspection. ........................12
Preventive Maintenance. ..................12
DC Resistance. ......................12
Disassembly...........................13
RF Connector Replacement..................13
Diaphragm and Coolant Oil. .................13
RF Load Resistor Assembly. ................13
Assembly. ...........................14
RF Connector. ......................14
Diaphragm and Coolant Oil. .................14
RF Load Resistor Assembly. ................14
Repairs.............................14
Preparation For Shipment. .................15
Storage. .........................15
Customer Service. .......................15
Sales /Repair Facilities....................15
Sales Facilities. ......................15
Replacement Parts List. .....................16
viii
Page 11
Chapter 1
Introduction
This publication refers to the Termaline Load Resistors Models 8201 and 8203. The differences between the models are listed in the specifications. Both models will generally be referred to as a load throughout this manual.
Purpose and
Function
These loads are portable, general purpose 50 ohm coaxial transmission line terminations. They are self-contained units requiring no outside power source or additional equip­ment. The Model 8201 load provides an accurate, depend­able, and practically nonreflective termination for testing and adjusting transmitters under nonradiating conditions from dc to 2500 MHz and the Model 8203 from dc to 1000 MHz.
Some examples of the uses of these loads are:
As a substitute antenna.
s s For tuning RF transmitters - under
nonradiating conditions.
s
For making routine tests and adjustments.
s As a substitute for any 50 ohm circuit loading
element.
s
To measure, with a suitable indicating device, the power output of any coaxially transmitted RF signal within its rating.
Description These models are rectangular in shape with transverse fins
encasing an oil-dielectric-filled coolant cylinder. A retract­able handle is recessed in the radiator fins. Extra thick fins at the front and rear are bent 90° to form bottom mounting flanges. These flanges are supports for free standing use or brackets for fixed mounting. Flange holes are provided for this purpose.
Performance
Capabilities
and
The Model 8201 Termaline Load Resistor can absorb and dissipate up to 500 W of RF power continuously over a fre­quency range of dc to 2500 MHz. It will show a maximum VSWR of 1.1 to 1.0 from dc to 1000 MHz and 1.25 to 1.0 from 1000 to 2500 MHz.
The Model 8203 Termaline Load Resistor will take a load of up to 600 W, over a frequency range of dc to 1000 MHz. Its
1
Page 12
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
maximum VSWR rating is 1.1 to 1.0 over this frequency range.
Note: The specifications for the Model 8203 ap-
+
ply only as long as the ambient temperature remains at 30°C (+86°F) or lower.
Dimensions
and Weight
Power and
Requirements
Environmenta
Requirements
Utility
Items
Supplied
The Models 8201 and 8203 are 16-13/16 inches L x 5-15/16 inches W x 8-1/2 inches H (427 x 151 x 216 mm). They have a net weight of 20.4 lb (9.2 kg) and a shipping weight of ap­proximately 26 lb (12 kg).
As load resistors, the Models 8201 and 8203 are passive de­vices that are self contained and do not require a source of power or utility service to perform their function, other than the RF input power.
The load should be operated in an environment as free of
l
dust and vibration as possible. For proper operation the am­bient temperature should remain within the range of -40°C to +45°C (-40°F to +113°F) for Model 8201 and -40°C to +30°C (-40°F to +86°F) for Model 8203. Allow at least six inches of clear space around the load to provide an unim­peded flow of convection air currents for adequate heat dis­sipation.
The load is equipped with:
s Model 8201 — Female N connector of a pat-
ented “Quick-Change” design.
s
Instruction Manual.
s
Model 8203 — Double Male N adapter, and a connector dust cap.
s
Instruction Manual.
Required
Tools and
Equipment
2
Items
Test
Because these load resistors are self contained, they have no additional parts.
Only a coaxial cable with the appropriate connector plug (normally a Male N or, with the Model 8203, a Female N), is needed for connecting these load resistors to the source of RF power.
s
Screwdrivers — for disassembly of this equip­ment.
s
An ohmmeter with an accuracy of 1 percent or better at 50 ohms is recommended for check­ing the resistance value of the resistor.
Page 13
Introduction
Specifications
Impedance 50 ohms nominal
VSWR: Model 8201: 1000-2500 MHz Model 8203: dc-1000 MHz
Connectors: Female N “QC” type normally supplied
Power Range
Model 8201 Model 8203
Frequency Range
Model 8201 Model 8203
Dimensions 16-13/16"L x 5-15/16" W x 8-1/2"H
Ambient Temperature
Model 8201 Model 8203
Coolant Method Convention air currents
Weight 20.4 lb (9.2 kg)
Operating Position Horizontal only
Finish Grey Powder Coat
1.1:1.0 Maximum
1.25:1.0 Maximum
500 W continuous 600 W continuous
dc-2500 MHz dc-1000 MHz
(427 x 151 x 216 mm)
-40°C to +45°C (-40°F to +113°F) 40°C to +30°C (-40°F to +86°F)
1
1
Model 8203 also includes a double Male N adapter and a dust cap.
3
Page 14
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
Figure 1
Model 8201
ELECTRONIC
4240-062
4
Page 15
Chapter 2
Theory of Operation
General The Models 8201 and 8203 Termaline Load Resistor consist
essentially of a carbon film-on-ceramic resistor immersed in a dielectric coolant. The resistor, individually selected for its accuracy, is enclosed in a special exponentially tapered housing. This provides a linear reduction in surge imped­ance directly proportional to the distance along the resistor. When surrounded by the dielectric coolant, the characteris­tic impedance is therefore 50 ohms at the front (connector end), 25 ohms at the mid-point to compensate for the resis­tance already passed over, and zero ohms at the rear where the resistor joins the housing, forming the return conductor of the coaxial circuit. This produces a uniform and practi­cally reflectionless line termination over the stated frequen­cies for the load resistor.
Cooling The dielectric coolant is chosen for its desirable dielectric
and thermal characteristics. Cooling of the Models 8201 and 8203 is accomplished by natural fluid and air convection currents. The 0.7 gallon of dielectric coolant carries the elec­trically generated heat from the resistor to the walls of the cylindrical cooling tank. This tank is encased in a set of ra­diating fins constructed from heavy gauge aluminum alloy and firmly pressed onto the cylinder. The heat from the di­electric fluid is transferred to the surrounding air by the fins.
Expansion of the coolant, caused by the rise in its tempera­ture, is allowed by means of a synthetic rubber diaphragm (not visible) inside the rear cover dome of the unit.
5
Page 16
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
6
Page 17
Chapter 3
Installation
Location
CAUTION
The load is designed for operation in a horizontal plane
only, with mounting brackets down. Do not operate in
any other position.
Install the Model 8201 or 8203 Termaline Load Resistor in a location that:
Has sufficient room to provide at least six
s
inches of free space around and above the unit.
s Is the shortest possible distance, or cable
length from the transmitting equipment. Ensures the operation of the load in a horizon-
s
tal position only, with the handle on top.
Mounting The load may be used for portable operation or for fixed in-
stallation, that is, it may stand free or may be secured to a bench or any convenient flat surface. The front and rear fins are made of heavier gauge material bent outward 90 de­grees to form mounting flanges. At each corner of these flanges is a rubber bumper foot attached with an acorn nut. To fasten the load by means of its base mounting flanges:
1. Remove the four rubber bumpers
2. Fasten the load with four screws. Put one screw in each of the four 9/32 inch holes.
Note: Use screws up to 1/4 inch diameter.
The holes are arranged in a 5-1/8 x 12-17/32 inch rectangle (130.2 x 318.3 mm).
7
Page 18
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
8
Page 19
Chapter 4
Operating Instructions
Use and
Function of
Controls
Initial
Adjustments
Because these are passive devices, there are no operating controls on the Models 8201 and 8203 Load Resistors.
No initial adjustments are required other than to connect the load to the RF source by means of a coaxial cable equipped with a suitable matching connector plug.
Start-up 1. Connect a Male N type plug, which mates with
the RF input connector, to the load.
2. Connect the Model 8201 or 8203 Termaline Load Resistor to the transmitting equipment under test with 50 ohm coaxial cable.
3. After the transmitter has been connected to the load, proceed according to the transmitter manu­facturer’s instructions.
When reconnecting the antenna, it may become necessary to slightly readjust the transmitter due to possible differences in VSWR between the load and the antenna system.
Normal
Operation
WARNING
When power is in the upper range of the load’s
capacity, the radiator will become hot - care should be
used in touching the equipment.
Operating
Under Emergency, Adverse, or
Abnormal
Conditions
Having no indicators or controls, these loads require no spe­cial operating procedures or surveillance when properly used.
CAUTION
Do not operate this equipment continuously above the
rated 500 W for Model 8201, or 600 W for Model 8203.
Load failure will result.
9
Page 20
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
Shutdown Because both the Models 8201 and 8203 are passive devices,
there is no way to turn them off. Power must be shut off at the source of the RF energy.
Emergency
Shutdown
WARNING
Do not attempt to disconnect these loads from the
coaxial cable while RF energy is still being applied.
Leaking RF power is a potential health hazard.
Turn off the RF power at the source.
10
Page 21
Chapter 5
This chapter contains operator maintenance instructions, troubleshooting, and parts information.
Troubleshooting
Problem Possible Cause Remedy
Leakage of coolant oil around band or radiator housing.
Overheating of the radi­ator.
High or low dc resis­tance values.
Maintenance
Clamping band not tight.
Faulty o-ring (front). Replace per the RF
Faulty diaphragm (rear). Replace per the Dia-
Transmitter power is too high.
Coolant level is too low. Add more coolant per
Faulty RF section. Replace the RF section
Faulty RF input connec­tor.
Loose RF input connec­tor.
Faulty RF section as­sembly.
Tighten clamping band with a screwdriver.
Load Resistor para­graph.
phragm and Coolant Oil paragraph.
Reduce the transmitter power.
the Diaphragm and Coolant Oil paragraph.
per the RF Load As­sembly paragraph.
Replace per the RF connector replacement paragraph.
Tighten the connector with a screwdriver.
Replace the RF section per the RF Load As­sembly paragraph.
Cleaning
The principle maintenance required by the operator will be the cleaning of the radiator fins. Periodically wipe away the accumulated dust and lint. If the insulator or metallic con­tact surfaces of the connector should become dirty or grimy, wipe them off with a soft cloth and use a contact cleaner that is self drying and leaves no residue to clean the inac­cessible internal parts.
11
Page 22
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
Inspection With the rugged and simple construction of the Models 8201
and 8203 Load Resistors, periodic inspection will be neces­sary at only about six-month intervals. Inspection should in­clude the items listed below:
1. Oil Leakage - Check for coolant oil seepage around the radiator tank, particularly at the front and back around the underside of the clamping band.
2. Inspect the Load for completeness and general condition of the equipment.
The Troubleshooting Chart lists the symptoms of commonly encountered troubles, their causes, and suggested corrective measures. Use the chart as a guide when analyzing symp­toms.
Preventive
Maintenance
Resistance
Measurement
DC
Figure 2
DC
Resistance
Because of the basic simplicity of construction, no special maintenance procedures are required. Keep the equipment clean, and occasionally check the coolant level in the radia­tor tank.
Check the condition of the load resistor by accurate mea­surement of the dc resistance between the inner and outer conductors of the RF connector. Use an ohmmeter with an accuracy of 1 percent or better at 50 ohms for this purpose. The measured resistance should be a nominal 50 ohms, ±2 ohms. Perform this test only when the load has cooled down to room temperature. Refer to figure 2.
12
Page 23
Maintenance
Disassembly
There are no special techniques required for the repair or replacement of components in the Models 8201 and 8203 loads. A screwdriver is the only tool needed.
RF Connector
Replacement
Diaphragm
and Coolant
Oil
The connector is a patented “Quick Change” design which permits easy interchange with the use of only a screwdriver. This process does not interfere with the essential coaxial continuity of the load resistor RF input or the coolant oil seal. For replacement, proceed as follows:
1. Remove the four 8-32 x 5/16 inch round head machine screws from the corners of the RF con­nector.
2. Pull the connector straight out of its socket.
Remove the diaphragm to replace or examine the coolant oil. Replacement of the diaphragm and coolant are listed in the steps below:
1. Stand the load vertically, with the back end up. Brace it carefully to avoid tipping it over.
2. Loosen the clamp screw until the clamping band is released.
3. Remove the diaphragm cover and lift the dia­phragm from the back end of the radiator tank. Inspect the diaphragm. It should be soft and pli­able. If it has hardened or shows signs of surface cracks, replace it.
4. The coolant oil level should be about one inch be­low the top of the radiator cylinder. If the oil ap­pears to be contaminated; i.e., it doesn’t have a clear light yellow color, replace it.
RF Load
Resistor
Assembly
To replace the load resistor assembly, it is not necessary to drain the unit of coolant oil. Follow the steps below:
1. Stand the load vertically, with the front end up.
2. Loosen the clamp screw until the clamping band is released.
3. Hold the load assembly by the RF connector and pull the assembly slowly out of the radiator. Al­low the excess coolant to drip back into the radi­ator.
13
Page 24
Bird Models 8201 & 8203 Termaline Coaxial Load Resistor
4. Inspect the O-Ring seal which is located just in­side the mounting flange of the resistor assembly. Do not reuse the O-Ring if it is not soft and pli­able or if it shows signs of surface cracks.
Assembly
RF Connector Before pushing the RF connector in, be sure that the pro-
jecting center contact pin on the connector is carefully en­gaged and properly seated in the mating socket of the load resistor input.
Install the four 8-32 x 5/16 inch round head machine screws into the corners of the RF connector.
Diaphragm
and Coolant
Oil
RF Load
Resistor
Assembly
To assemble, follow the instructions below.
1. Fill the unit with coolant until the level is about one inch below the top of the radiator cylinder.
2. Install the diaphragm and place the diaphragm cover on the back end of the radiator tank.
3. Install and tighten the clamping band screw.
4. Check for leaks. Pay particularly close attention to the area around the clamping band.
To install the assembly:
1. Hold the load assembly by the RF connector and slowly lower the assembly into the radiator
2. Place the clamp band on and tighten the clamp screw until the clamping band is tight.
3. Place the unit on its flanges, in a horizontal posi­tion.
4. Check for leaks. Pay particularly close attention to the area around the clamping band.
REPAIRS
Preparation
For Shipment
14
Any maintenance or service procedure beyond the scope of those provided in this section should be referred to a quali­fied service center.
Wrap and tape the RF connector to keep out foreign mate­rial, then pack and brace the load in a suitable container. A sturdy corrugated paper box is recommended.
Page 25
Storage No special preparations are needed for storage other than to
cover the equipment to keep out dust and dirt. Store the unit in a clean dry environment where the ambient temper­ature will remain within the approximate working range of the instrument -40°C to +45°C (-40°F to +113°F) for Model 8201 and -40°C to +30°C (-40°F to +86°F) for Model 8203.
Customer Service
Sales /Repair
Facilities
Sales
Facilities
U.S.A Sales and Manufacturing
Service Group Bird Electronic Corporation 30303 Aurora Rd Cleveland (Solon). Ohio 44139-2794 Phone: (440) 248-1200 Fax: (440) 248-54-26
For the location of the sales office nearest you give us a call, or visit our Web site at
http://www.bird-electronic.com
15
Page 26
Replacement Parts List
Models 8201/03
Item Qty. Description Part Number
1 2 3 .7 gal
4 5 6 7 8 9 10 11 12 13
1
1
(2.65 li­ters)
1
1
1
2
1
4
4
1
1
1
Radiator assembly 2430-050 RF Section assembly 8205-002 Dielectric coolant 5-030-3
“QC” connector *see below Diaphragm 2430-015 Diaphragm cover 2430-148 Clamp band 2430-043 O-Ring seal 8110-039 Bumper foot 5-049 Acorn nut 8110-171 Radiator handle 2430-028 Adapter and chain assembly 8203-003 Dust cap (model 8203) 5-297
*Available QC Type Connectors
N-Female 4240-062 LT-Female 4240-018 N-Male 4240-063 LT-Male 4240-012 HN-Female 4240-268 C-Female 4240-100 HN-Male 4240-278 C-Male 4240-110 LC-Female 4240-031 UHF-Female
4240-050
(SO-239)
LC-Male 4240-025 UHF-Male
4240-179
(PL-259)
7/8" EIA Air Line 4240-002
16
Page 27
Maintenance
LIMITED WARRANTY
All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise spec­ified, from date of shipment and to conform to applicable specifications, draw­ings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or re­pairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transporta­tion-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writ­ing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufac­turer’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, IN­CLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGA­TION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
17
Loading...