Installation guide
Billi B-5000 Sparkling
Tap option XL
Installation requirements.
XL
Unpacking your Billi B-5000 Sparking Unit
Before commencing installation, carefully
check for any damage to outer carton, inner
liner, appliance metalwork, pipework fittings
and electrical power cord. If damage is found,
please photograph and record details for use
if a claim is to be made.
WARNINGS relating to this appliance must be
read before commencing installation. Refer
to page 8.
When unpacking your appliance, ensure you
have identified the following components:
1. Boiling water module
2. Chilled water module
cylinder
3. CO
2
regulator
CO
2
4. Dispenser
5. Tube spring clamps x 2
6. Natural and 2 x black Ø6 mm PE tubes
with stem elbows fitted
7. Extra 6mm stem elbow fitting
8. 600mm flexible braided hose
9. Filter cartridge (installed)
10. User guide
11. Warranty registration card
12. Warning label
13. Plastic Ø6mm tube cap
14. 5mm door spacer pads
15. Ventilation grille - cupboard base
Determine Unit Location
Plan the installation carefully, taking into
consideration dispenser tube lengths,
position of power and water outlets,
ventilation airspace requirements and access
for service. Refer to diagrams 1, 2, 3a, 3b and
4. Diagram 4 shows minimum clearances
required around the units for ventilation
Water Supply
A single cold water supply point with a ½” BSP
stop tap is required. Stop tap is to be installed in
an easily accessible position, within 600 mm of
the inlet to the boiling water module. Sparkling
chilled water module is supplied from an outlet
fitting on the Boiling water module.
Dynamic supply pressure: Min. 250 kPa, max,
1000 kPa
Supply temp: Min. 5°C, max. 30°C
Power Requirements
B-5000 Sparkling requires 2 single or 1
double 10 amp GPO, installed in an accessible
position. Refer to Diagram 1. Power
circuits must be fitted with an earth leakage
protection device (RCD). Both boiling and
chilled water module are supplied with
a 1 meter flex cord and plug. Cupboard
ventilation fan kits require an extra 10A GPO
outlet.
Ventilation Grilles
A ventilation kit including lower cupboard
vent grille and 5mm door spacers is
supplied with each Billi Sparkling/Chilled
water unit.Separate installation instructions
are provided within the vent kit packaging.
For lower usage, domestic installations,
sufficient ventilation may be provided by
natural air movement through the cupboard
airspace. Minimum area of lower and upper
air vent openings is 100 cm²
Fan assisted vent kit
For units installed in higher usage or warm
climate areas, including office or commercial
installations, additional cupboard ventilation
should be provided. Billi provides a fan
assisted air circulating vent kit which
draws air in through the cupboard base in
front of the kickboard. Billi part no 990715
Installation instruction are provided with kit
packaging. Ventilation fan kits require an
extra 10A GPO outlet.
Stop Tap
(Installed by Plumber)
Max 600mm from Unit
20mm
175mm
205mm
10mm
bench
thickness
1mm-48mm
Tubing
removed
for clarity
Tubing
removed
for clarity
800mm
Tube Length
Supplied
60mm min
clearance
35mm 70mm
Diagram 1
130mm
Diagram 2
Do not install with water that is
microbiologically unsafe or with water of
unknown quality without adequate disinfection
before or after the system. Systems certified
for cyst reduction may be used on disinfected
water that may contain filterable cysts.
2
Installation requirements.
XL
Chilled Water Module Dimentions
255mm
410mm
B-5000 Sparkling Suggested Layout
420mm
Diagram 3a
Boiling Water Module Dimentions
180mm
365mm
340mm
Diagram 3b
Note: Shaded area shows minimum ventilation clearance
Diagram 4
3