Biddle HR 25, HR 35, HR 45 User Manual

Page 1
Manual
Heat recovery unit
Model HR 25/35/45
Version 4.1 Original Manual
a
English
Page 2
HEAT RECOVERY UNIT
. . . Contents
1 Introduction 4
1.1 About this manual 4
1.2 How to read this manual 4
1.3 About the unit 5
1.4 Components and accessories 10
1.5 Safety instructions 11
2 Installation 13
2.1 Inspection on delivery 13
2.2 Hanging the unit up 13
2.3 Connecting the unit to the ventilation system 17
2.4 Connecting the unit to the central heating and heat recovery system 18
2.5 Installing condensate drain 19
2.6 Connecting components to electronics module 20
2.7 Connecting the unit to Modbus 21
2.8 Installing the b-touch control panel (accessory) 22
2.9 Connecting the temperature sensor (accessory) 24
2.10 Installing sensors for control (accessory) 24
2.11 Installing external controls 25
2.12 Connecting the unit to the mains supply 27
2.13 Switching on and checking operation 29
3Operation via b-touch 37
3.1 Control panel 37
3.2 The Home screen 38
3.3 Main menu 40
3.4 Preferences 41
3.5 Settings 42
3.6 Configuration 43
3.7 Maintenance 48
3.8 USB 50
4 Operation via Modbus 52
4.1 Frequently used register addresses 52
4.2 All register addresses 58
5Errors 59
5.1 Resolving simple problems 59
5.2 Remedying errors that are accompanied by an error message 60
5.3 Reading out errors 60
5.4 Error codes registers 60
5.5 Error messages on the control panel 61
5.6 Remedying errors that are not accompanied by an error message 62
en-2 B
Page 3
HR MANUAL
6 Maintenance 64
6.1 Introduction 64
6.2 Replacing the filter 64
6.3 Cleaning the unit 65
6.4 Scheduled maintenance 65
7 Service 66
7.1 Cleaning the plate heat exchangers 66
7.2 Removing the control circuit board 68
7.3 Connecting the control circuit board 68
7.4 Fuses 69
7.5 Setting the unit code 69
7.6 Resetting the PIN code 70
7.7 Copying the settings 71
7.8 Updating the software 72
7.9 Composition of the Biddle control cable 74
8 Dismantling 75
9 Addresses 76
Keywords 77
Manual version 4.1 (26-07-2018)
en-3
Page 4
Note:
Caution:
Warning:
Danger:
1. . Introduction

1.1 About this manual

1.2 How to read this manual

This manual describes the installation, operation and mainte­nance of the heat-recovery unit HR. The manual also provides instructions and information for servicing activities.

1.2.1 Designations used in the manual

The following symbols are used in the manual:
n Refers to an important section in the text.
c If you do not carry out the procedure or action
correctly, you may cause damage to the unit.
Follow the instructions precisely.
w If you do not carry out the procedure or
action correctly, you may cause physical injury and/or damage.
Follow the instructions precisely.
d Is used to designate actions that are not
permitted.
en-4
Ignoring this prohibition may lead to serious damage or to accidents resulting in physical injury.
Page 5
HR MANUAL INTRODUCTION

1.2.2 Symbols used on the unit and in the manual

The following symbols indicate possible risks or hazards. The same symbols will also be found on the unit.
YMBOL DESCRIPTION
S
w You have accessed a section of the unit containing components which carry
a voltage.
Access restricted to qualified maintenance staff only.
Caution is required.
w This surface or component may be hot. Risk of burns on contact.
w You have accessed a section of the unit with running fans.
Caution is required.

1.3 About the unit

1.2.3 Images

The images in this manual can deviate from your specific device type. The functioning is the same, unless indicated oth­erwise.

1.2.4 Related documentation

In addition to this manual, the following documentation is also supplied with the unit:
• wiring diagram for installation and servicing.

1.3.1 Application

Manual version 4.1 (26-07-2018)
The unit is designed to use heat recovery on ventilation air, with or without additional heating.
en-5
Page 6
Warning:
INTRODUCTION HEAT RECOVERY UNIT

Other versions and intended use

w Applications other than those described
above are deemed to be ‘usage other than for the intended purpose’. Biddle is not liable for damage or loss resulting from usage other than for the intended purpose. Usage for the intended purpose also entails observance of the instructions in this manual.

1.3.2 Type designation

In combination, the type designations constitute the type code.
Type code basic units
The type code of a basic unit is, for example, HR 35
TYPE CODE ELEMENT DESIGNATION MEANING
product series HR general designa-
tion for the series
capacity 25 2500 m3/h
35 3500 m3/h
45 4500 m3/h
Type code additional modules
The type code for additional modules is a combination of the type code for the corresponding basic unit, combined with the indication for the additional module.
For example, for a recirculation module this is HR 35-RM
en-6
TYPE CODE ELEMENT
battery type HC6 water heating,
accessory RM recirculation
ADDITIONAL DESIGNATION
DX heating via direct
MEANING
cooling and/or ventilation
expansion
module
Page 7
HR MANUAL INTRODUCTION

1.3.3 Symbols on the unit

The modules are equipped with stickers and symbols. These symbols provide information on:
•function
•airflow
components
FUNCTION SYMBOL
heat exchanger
recirculation damper
fan
filter
heating/cooling
airflow
AIRFLOW SYMBOL
supply air
extract air
exhaust air
Manual version 4.1 (26-07-2018)
fresh air
en-7
Page 8
Note:
Warning:
INTRODUCTION HEAT RECOVERY UNIT

1.3.4 Type plate

The type plate is located on the side of the basicunit.
Supplemental modules have their own type plate.
Designations on the type plate
DESIGNATION MEANING
Type complete type code of the unit
o
N
Mweight of unit
Medium medium
p
max
U power supply voltage
I
max
P
motor
serial number, production week and year
maximum permissible operating pressure
max. current
max. power consumption by fans

1.3.5 Field of application

Observe the following limits for the unit:
Operating limits for all models
Ambient conditions Temperature 5 °C to 40°C
Relative air humidity
Power supply voltage see type plate
Power see type plate
Parameters of use for water-heated models
20% - 95%, not condensing
n Consult Biddle if you want to connect a unit to a
water flow-path with higher temperatures and higher pressure.
w The unit may not be used in potentially
explosive environments, outdoors or in very dusty or aggressive air conditions.
en-8
Biddle shall not be held liable for damage caused by use under these conditions.
Page 9
HR MANUAL INTRODUCTION

Sound levels

Maximum sound power level in ducts
SOUND POWER LEVEL
(LW RE. 10
-12
W)
OCTAVE BAND CENTRE FREQUENCY (HZ)
63 125 250 500 1000 2000 4000 8000
L
WA
DB(A)
HR 25
supply air 69.8 65.6 76.4 75.1 78.8 80.4 78.5 74.1 85.5
extract air 65.7 60.5 70.6 69.9 67.4 70.8 70.9 66.7 76.6
exhaust air 69.8 65.6 76.4 75.1 78.8 80.4 78.5 74.1 85.5
fresh air 65.7 60.5 70.6 69.9 67.4 70.8 70.9 66.7 76.6
HR 35
supply air 75.8 70.7 78.6 78.4 81.3 81.2 78.3 75.4 86.6
extract air 68.6 65.8 75.5 72.3 69.2 70.2 68.2 67.2 76.7
exhaust air 75.8 70.7 78.6 78.4 81.3 81.2 78.3 75.4 86.6
fresh air 68.6 65.8 75.5 72.3 69.2 70.2 68.2 67.2 76.7
HR 45
supply air 71.9 74.0 86.7 78.8 80.3 79.8 77.5 71.5 86.2
extract air 69.1 70.3 81.8 74.1 68.7 70.1 67.8 62.8 78.0
exhaust air 71.9 74.0 86.7 78.8 80.3 79.8 77.5 71.5 86.2
fresh air 69.1 70.3 81.8 74.1 68.7 70.1 67.8 62.8 78.0
Maximum sound power level in unit housing
D
TECHNICAL SPEED
B(A)
(LWA RE.10
-12
W)
HR 25 HR 35 HR 45
10 V DC (high speed) 74 74 78
8 V DC 68 69 75
6 V DC 63 64 68
5 V DC 58 60 62
Maximum sound pressure level in standard room
D
B(A)
(L
RE.2X10-5 N/M2)
TECHNICAL SPEED
PA
HR 25 HR 35 HR 45
10 V DC (high speed) 66 66 70
8 V DC 60 61 67
6 V DC 55 56 60
5 V DC 50 52 54
Manual version 4.1 (26-07-2018)
en-9
Page 10
Note:
INTRODUCTION HEAT RECOVERY UNIT

Maximum number of units to be connected

The number of ventilation units that can be connected to the heat recovery unit depends on the unit’s capacity and the effective capacity of the ventilation units that are to be con­nected. If in doubt, consult your Biddle advisor.
See also:
1.3.4 "Type plate" on page 8

1.3.6 CE declaration

The unit is compliant with the applicable CE standards. The complete CE Declaration of Conformity can be found at: www.biddle.info.

1.3.7 Modifications and changes

Without the approval of Biddle, no changes or modifications may be made to the unit that could adversely affect safety. The CE declaration is no longer valid if the unit has been modified or changed in any way.

1.4 Components and accessories

1.4.1 Components supplied

n The illustration shows the unit from above, whereby
• Modules:
• Electronics module 6
• Air dampers to fresh air 7
the air exchange with the interior takes place on the left side and the air exchange with the fresh air takes place on the right side.
- supply fan 1
- extract air filter 2
- extract fan 3
-fresh air filter 4
-heat exchanger 5
en-10
• Pressure switch over the heat exchanger 8
• Pressure switch over the fresh air filter 9
• Fastening material for linking the modules to each other.
Page 11
HR MANUAL INTRODUCTION
Warning:
Warning:
Warning:
Caution:

1.4.2 Accessories

• Recirculation module 0
• Heating/cooling module !
• Flexible manchets @
• Pressure switch over extract air filter #
• Dirty filter warning lamp (during transport, this is stored in the electronics module)
• b-touch operating panel with Biddle control cable
• Water-side control:
- valve and drive
-temperature sensor
•Sensor for control:
-CO
•Smoke detector
sensor
2

1.5 Safety instructions

1.4.3 Components not supplied

The following components required for installation must be obtained from third parties:
• threaded rods M10
• mains power cable
• control cable to building management system
• drain pipe with trap for condensate drainage

1.5.1 Safety in use

w Do not put any objects into the inlets and
outlets.
Manual version 4.1 (26-07-2018)
w Do not obstruct the unit’s inlets or outlets. w The upper surface of the unit becomes hot
during operation.
c In exceptional situations, water may run out of the
unit. Therefore, do not place anything under the unit that could be damaged as a result.
en-11
Page 12
Danger:
Warning:
Caution:
Warning:
INTRODUCTION HEAT RECOVERY UNIT
1.5.2 Safety issues relating to installation, mainte­nance and servicing
d The unit may only be opened by qualified
technical staff.
w Perform the following actions before opening
the unit:
1. Switch the unit off,.
2. Allow the unit to cool down.
c The heat exchanger or, as the case may be, the
heating elements, can get very hot.
3. Disconnect the mains supply (switch off the isolat
swi
tch).
4. If you are going to carry out maintenance or repairs on
el
ectrical components: switch the mains supply group off.
5. For water-heated models:
s
hut off the central heating feed (if possible).
ion
w The fins of the heat exchanger are sharp.
en-12
Page 13
2. . Installation
Warning:
Warning:
w Installation activities may only be performed w Before starting installation: read the safety
See also:
1.5 "Safety instructions" on page 11
by technical staff qualified for this purpose.
instructions.

2.1 Inspection on delivery

2.2 Hanging the unit up

• Check the unit and the packaging to ensure that they have been delivered in good order. Notify the driver and
plier immediately if any shipping damage is detected.
sup
• Ensure that all components are present. Notify supplier of any missing parts immediately.
See also:
1.4 "Components and accessories" on page 10

2.2.1 Determining the location of the unit

• Make sure that the structure from which the unit is about to be suspended can bear at least 4 times the weight of th unit. The un
• The distance between the floor and the unit’s undersid
ust be more than 2.7 m due to the accessibility of th
m in
spection hatch.
it’s weight is indicated on its type plate.
the
e
e
e
Manual version 4.1 (26-07-2018)
• Make sure that the electronics and the pressure meters on the unit’s long side remain easily accessible.
For this, keep 50 cm of space free on the side of the elec­tronics box.
en-13
Page 14
Note:
Note:
INSTALLATION HEAT RECOVERY UNIT
• The plate heat exchangers are wedged between the side panels. To be able to remove them, space must be cr
y removing a side panel.
b
Keep 30 cm of space free on the side of the unit.
eated
• In exceptional situations, water may Mak
e sure that this cannot cause any damage or danger-
ous situations.
• For models with heating: The distance between the ceilin an
d the top of the unit must be more than 25 mm.
• Consult the symbols on the unit for the right position:
-
-
See also:
1.3.4 "Type plate" on page 8

2.2.2 Hanging the unit up

This manual explains how to suspend the unit for each mod­ule. Depending on the situation, a different sequence of sus­pending the units may be selected.
Consult the overview sticker (bottom view) for the module positions in the specific composition of your unit. If required, tick the applicable modules.
and and
: channels to the interior space : channels to the outside
run out of the unit.
g

Fixing the threaded rods

Fix threaded rods M10 in accordance with the dimensions in the table. Make sure the threaded rods are perpendicular.
n Only fix the threaded rods for the modules in the
specific composition of your unit. See the overview sticker.
n The illustration shows the unit from above, whereby
the air exchange with the interior takes place on the left side and the air exchange with the exterior takes place on the right side.
en-14
Page 15
HR MANUAL INSTALLATION
Note:
Note:
Caution:
SIZE TYPE DIMENSIONS
A HR 25 1558 mm
HR 35 2158 mm
HR 45 2758 mm
B all models 1450 mm
C all models 450 mm
x all models 54 mm
n The threaded rods must be secured, otherwise the
unit may fall down.

Hanging the unit up

1. Mount the electronics module on the side of the exchanger module
2. Move the heat exchanger module into position.
3. Attach the module to the threaded rods with nuts 1.
.
heat
n Make sure the rubbers and rings 2 for damping stay
in the right place.
c Make sure that the module is hanging level in both
directions.
With type HR 45, the heat exchanger can sag slightly. After all the modules are linked, this will be minimalised.
Manual version 4.1 (26-07-2018)
4. To each threaded rod, apply a lock nut 3.
en-15
Page 16
Note:
Caution:
INSTALLATION HEAT RECOVERY UNIT
5. Move the recirculation damper module into position.
n Ensure that the wiring is on the side of the
electronics module.
6. Attach the module in the same way as the heat exchange m
odule (steps 3 and 4).
7. Connect the modules to each other with the coupling ele­ments at top and bottom.
c Adjust the modules individually before they are
connected to each other.
8. Connect the supply fan module and the extract air fil­ter module M5 to each other with the coupling ele­ments at top and bottom.
9. Connect the extract fan module and the fresh air fi
ule F7 to each other with the coupling elements
mod top an
d bottom.
10. Repeat steps 5 to 7 for both linked assemblies.
lter
at
r
11. Only applicable to units with a heating module
- Mount the coupler elements supplied on the fan mod-
ule.
- Mount and connect the heating module in th
wa
y as for the other modules.
e same
en-16
Page 17
HR MANUAL INSTALLATION
Warning:
Note:
12. Place manchets (accessory)
- Mount the clamping profiles 5. To do so, use the sup-
plied screws.
- Install the manchet 6.
- Tighten the clamping screws 7.

Securing the unit

1. Secure the suspension to the threaded rods by tightening
all lock nuts 3.
w The threaded rods must be secured,
otherwise the unit may fall down.

2.3 Connecting the unit to the ventilation system

Using channel sections, connect the unit to the fresh air, the inside air and to the ventilation units.
n Take into account any sensors for the controls which
have to be placed in the ducts.
See 2.10 Installing sensors for control (accessory)
Manual version 4.1 (26-07-2018)
When opting for the duct cross-section, take into account:
• The maximum allowable pressure difference fo equired capacity. (see diagram under 2.13.5
r
vo
lume)
• The desired maximum air velocity.
r the
Calibrate air
en-17
Page 18
Note:
Note:
Note:
Caution:
Note:
INSTALLATION HEAT RECOVERY UNIT
n If the duct cross-section is too small, this may lead
to reduced capacity and/or noise nuisance.
n When adapting to different duct diameters, use
sufficient length in order to prevent turbulence.
n In order to prevent condensation, Biddle
recommends insulating the channel sections between the HR unit and the fresh air.
See also:
2.13 "Switching on and checking operation" on page 29
2.4 Connecting the unit to the central heating and heat recovery sys-
tem

2.4.1 Connecting the water-side control (accessory)

Only for models with water heating/cooling module:
The heating/cooling module can be fitted with a water-side control to control the temperature of the water battery.
c Biddle supplies suitable 2-way and 3-way valves as
accessories.
1. Connect the control valve and the driv excha
nger, in accordance with the diagram. In doing so, fol-
low the instructions given in the control valve manual.
e to the heat
n Ensure that the axis of the valve is in the correct
position when connecting the drive. See the control valve manual.
en-18
Page 19
HR MANUAL INSTALLATION
Caution:
WIRING DIAGRAM 2-WAY VALVE WIRING DIAGRAM 3-WAY VALVE
2. Connect the drive to the valve in accordance with the wir­ing diagram.

2.5 Installing condensate drain

3. Connect the drive to the building management system another contr

2.4.2 Connecting the unit

1. Connect the unit to the central heating system.
2. Vent the heat exchangers.
3. Check the connections for leakage.
The cooling of the air can cause condensation. The unit is fit­ted with a drain tray(s) to catch condensation water.
1. Connect one of the connection points 1 (15 mm) of the heat exchanger to a drainage system.
ol system.
or
c On models that are used for cooling, also connect
the connection point of the cooling module 2 (15
a drainage system.
) to
mm
Manual version 4.1 (26-07-2018)
en-19
Page 20
Caution:
Caution:
Note:
INSTALLATION HEAT RECOVERY UNIT
Pay attention to the following installation criteria:
- Make sure the drainage pipe has a drop of at least 1:50.
- Fit the drainage pipe with a trap with dimensions sho
wn in the illustration. Fill this with water before the
unit is used for the first time.
A 160 mm
B 110 mm
c The trap must always be filled with water.
2. Cap off other connection points.
as
c If the connection points are not shut off, water may
run out of the unit.

2.6 Connecting components to electronics module

1. Connect the various unit components to the electronics mod
ule in accordance with the wiring diagram:
n Some components are optional (accessories).
- supply fan module :
- p
ower supply: X1 1 (via cable gland in box)
-
control system + input valve: 2
- extract fan module :
- p
ower supply: X1 3 (via cable gland in box)
trol system: 4
- con
- recirculation damper module : 5
-heat exchanger module :
y-pass damper: 6
- b
- p
ressure difference meter: 7
-temperature sensors: 8
- fresh air filter module : 9
en-20
See also:
1.3.3 "Symbols on the unit" on page 7
Page 21
HR MANUAL INSTALLATION
Note:
Note:

2.7 Connecting the unit to Modbus

2.7.1 Communication parameters

Standard values of the communication parameters for Mod­Bus are:
COMMUNICATION PARAMETER VALUE
Baud rate 9600
DATA 8
Parity none
Stop bits 1
The turnaround time between the unit and Modbus is 4.2 msec.
The default value for the Modbus node address is 1.
n You can modify the parameters via b-touch
menu > Maintenance > Modbus settings or
via Modbus register addresses 460-464.

2.7.2 Wiring

A twisted-pair cable must be used for connection to the Mod­bus system. The cable must also have a third core for the GND (grounding). Normally, a four-pole, twisted-pair cable is used; one pair is used for communication and one core from the other pair is used as the GND.
Modbus A = -
Modbus B = +
GND = ground
Manual version 4.1 (26-07-2018)
n If there is no communication, this may be caused by
incorrectly connected wiring. Swap the A- and B+ wires.
en-21
Page 22
Note:
Note:
Note:
Note:
INSTALLATION HEAT RECOVERY UNIT

2.7.3 Connecting the unit to Modbus

1. Lay a cable between the Modbus system and the unit.
2. Connect the cable to the electronics module 1, in accord- ance with the wiring diagram.
n For a more reliable signal, it is possible to connect a
120 Ohm resistor. For this purpose, place a bridge between positions 1 and B of terminal 52X3 on the control circuit board in the unit.
n The b-touch control panel is no longer necessary for
the operation. After going through the installation guide, it can be removed. However, make sure to keep it to be able to adjust the settings in a later stage.

2.8 Installing the b-touch control panel (accessory)

2.8.1 Special points regarding the control panel

Positioning

• You can attach the control panel to the electronics mod­ule, to the wall or to a standard junction box.

Cabling

n Take the following into account, otherwise errors
may occur:
- The length of the control cable between the contro p
anel and the unit connected may not exceed 50 m.
- Keep control cables away from electromagnetic fi
d interference sources such as high-voltage ca
an an
d fluorescent light starters.
- Lay control cables out straight or roll them in a bifi­lar coil by folding cables in half before rolling them. As a result, the magnetic fields will cancel each othe
to an important extent.
out
l
elds
bles
r
en-22
n Use Biddle control cables only. Standard modular
t
elephone cable is NOT suitable.
Page 23
HR MANUAL INSTALLATION
Caution:

2.8.2 Mounting and connecting the control panel

1. Lay the control cable.
2. Slide the control panel out of the wall holder.
3. Connect the control cable to terminal X397.
4. Screw the wall holder onto the electronics module, the junction box or against the wall.
c Ensure that the wall behind the wall holder is even.

2.8.3 Connecting the b-touch panel to the unit

1. Connect the control cable to the electronics module 1 according to the wiring diagram.
Manual version 4.1 (26-07-2018)
en-23
Page 24
Caution:
Note:
INSTALLATION HEAT RECOVERY UNIT

2.9 Connecting the temperature sensor (accessory)

Only for models with HC6 heating/cooling module with water-side control
A temperature sensor is included with the water-side control valve.
1. Position the temperature sensor in the channel for the su
pply air 1.
c Insofar as is possible, position the sensor in the
centre of the channel.
Place the sensor as far as possible from the heating/ cooling module. Bear in mind the cable length of the sensor.
2. Feed the cable of the sensor through a cable gland in
ectronics module.
el
3. Connect the sensor at positions 24 and 25 of terminal 2, in accor
dance with the wiring diagram:
n If required, remove any existing connections to
positions 24 and 25 of terminal X2.

2.10 Installing sensors for control (accessory)

For some controls, a sensor is required to provide the input:
•automatic CO
Connect the sensor that is to be used to the appropriate con­nection point in the electronics module.
control
2
to the
X2
en-24
Page 25
HR MANUAL INSTALLATION
Note:
Caution:
Note:

2.10.1 Installing CO2 sensor

2.11 Installing external controls

With automatic CO building management system (BMS). If this information is not available, a CO
1. Place the CO accor
dance with the supplied instructions.
2. Connect the sensor to X3 (G UI 24VAC) 2 in the elec­tronics module in accordance with the wiring diagram.
n The CO
once per week so that the sensor can maintain a good calibration level.
If this situation does not occur naturally, you can make it happen by (for example) having the unit start up an hour earlier once per week.
control, the CO2 level is supplied by the
2
sensor must be connected.
2
sensor (accessory) in extract channel 1, in
2
level in the room must be optimal at least
2

2.11.1 Special points regarding external controls

Unit input

The unit has an input signal interface. As examples, a smoke detector or fire alarm can be connected to this.
Connection X3 1 is suitable for input signals that are exter­nally powered.
Connection X1 2 is suitable for supplying the sensor that is to be connected with a 230V power supply from the unit. When using this, link connection X1 to X3 with a bridge.
c The input is designed for controls with potential-free
contacts and must not be loaded.
n When using the input, indicate what response must
be given to an input signal. (Via the b-touch control panel: menu > Configuration > 60. Function of inputs or via the building management system: register address 337 Alarm functions)
Manual version 4.1 (26-07-2018)
en-25
Page 26
Caution:
Note:
INSTALLATION HEAT RECOVERY UNIT

Unit output

The unit has an output signal interface (X3). A warning lamp for dirty filters can be connected to this.
c Keep the cable length to a maximum of 3 metres.
2.11.2 Installing smoke detector or fire alarm (acces­sory)
In emergencies, the unit can emit an alarm signal or even actively deal with the problem by functioning in a special mode. (See menu > Configuration > 60. Function of inputs)
This function can be activated by the building management sys­tem (register address 435) or by an external sensor.
If an external sensor is used:
1. Place a smoke detector or fire alarm (not supplied) at
su
itable location.
2. Without using the power supply (230V) from the unit:
- Connect the sensor to X3 1 in the electronics mod-
ule in accordance with the wiring diagram
3. Using the power supply (230V) from the unit:
- Connect the sensor to X1 2 in the electronics mod-
ule in accordance with the wiring diagram
- Place a bridge between X1 and X3
a
n When starting the unit, indicate what response must
be given to a signal from the sensor. (Via the b-touch control panel: menu > Configuration > 60. Function
of inputs or via the building management system:
register address 337 Alarm functions)
en-26
Page 27
HR MANUAL INSTALLATION
Note:
Caution:
Note:
Warning:
Warning:
Caution:

2.11.3 Installing dirty filter warning lamp (accessory)

The b-touch control panel gives an alert if one of the filters is dirty. If the control panel is not available or is hung out of sight, a warning lamp must be installed.
n During transport, the warning lamp is stored in the
electronics module.
1. Place the warning lamp in a position where it is visible.
2. Using a two-core cable, connect the lamp to terminal X3
1 of the electronics module, in accordance with the
wiring diagram.
c Keep the cable length to a maximum of 3 metres.
n The positions of the + and – contacts in the lamp
are indicated by: + 28V -

2.12 Connecting the unit to the mains supply

2.12.1 Special points regarding the mains supply

w The unit must be earthed. w The unit must be connected in accordance
with the applicable local requirements.
c For emergency situations and maintenance, it must
be possible to render the entire system electrically dead.
Manual version 4.1 (26-07-2018)
Every unit has an isolation switch in order to render the unit electrically dead in the event of emergency situations and for maintenance.
en-27
Page 28
Note:
Warning:
Caution:
Warning:
Caution:
INSTALLATION HEAT RECOVERY UNIT
n The circuit breaker (if modified) must be at least
type B.
To prevent rapid disconnection, type K is recom­mended preferably with 300 mA.
w However, do make sure to switch the mains
supply off if you are going to conduct maintenance on or repair electrical components.
c Do not turn the unit on and off at the power supply.
Use the control panel of the building management system for that.

2.12.2 Connecting the unit

w Make sure that the mains supply is switched
off.
1. Bring the mains power cable to the unit.
2. Feed the cable into the electronics module.
3. Connect the cable on terminal X0 1, in accordan
the wiring diagram
.
ce with
c Do not switch on the mains supply yet.
See also:
2.12.1 "Special points regarding the mains supply" on page 27
en-28
Page 29
HR MANUAL INSTALLATION
Danger:

2.13 Switching on and checking operation

2.13.1 Introduction

d Make sure that all channel sections are
connected to fresh air, inside air and ventilation units before you test the operation of the unit.

2.13.2 Visual checking

1. Check the following attachments:
- lock nuts of the suspension;
- coupling elements between the modules;
- channel sections correctly connected and in the righ positions.
t
2.
Check that the trap of the condensate drain is fill wat
er.
3. Check the connections to the electronics module.
4. For models with heating/cooling module
Check whether:
- the heat exchanger is connected correctly.
- the temperature sensor in the supply channel is con­nected.
- the heating/cooling system is switched on.

2.13.3 Switching ON

1. Switch on the mains supply.
2. Set the isolation switch to 1.
3. Check that no error messages are given.

2.13.4 Checking operation

ed with
Manual version 4.1 (26-07-2018)
1. Check the operation of the pressure switch 7 over the
heat exchanger:
1. Check in menu > Maintenance > Unit control value of th
2. Open the pressure switch.
e fourth input (1-2-3- 4) is a nil: x-x-x-0
that the
en-29
Page 30
Caution:
Note:
Note:
INSTALLATION HEAT RECOVERY UNIT
3. Make a bridge between the two switch contacts (NO/ NC).
c Do not allow the bridge to remain for longer than 1
minute. Check the input value (step 4) within that time. If this takes longer, the unit must be powered down to reset the pressure switch.
4. Check that the value of the fourth input (1-2-3-4) a one is: x-x-x-1
5. Remove the bridge.
2. Open the indicated panels to check the dampers and f
3. Connect a pressure difference meter over the extrac
2.
4.
Check the operation of differ
est mode. Use the table below for this purpose.
t
ans.
ent fans and dampers in each
operation of the
t fan
n The extract fan 2 and the exhaust air damper 4 are
not visible. Check this with reference to the pressure difference over the extract fan.
In the final test mode (7), the fan runs but there is no pressure difference because the air damper is closed.
en-30
n The opening and closing of the dampers can take a
little while.
Page 31
HR MANUAL INSTALLATION
Note:
MODE FANS (SPEED) VALVES
NO. DESCRIPTION
1 unit off off off
2heat recovery
speed 1
3heat recovery
speed 2
4heat recovery
speed 3
5recirculation1 off
6 night cooling 2 2
7 exhaust air
damper closed
1
SUPPLY
11
22
33
off 1
2
EXTRACT
(no pressure difference)
(pressure dif­ference)
(pressure dif­ference)
(pressure dif­ference)
(no pressure difference)
(pressure dif­ference)
(CAUTION: no pressure difference)
3
FRESH AIR
closed closed
open open
closed closed
open open
closed closed
4
EXHAUST AIR
(no pressure difference)
(pressure dif­ference)
(no pressure difference)
(pressure dif­ference)
(no pressure difference)
5
RECIRCU- LATION
open closed
closed closed
open closed
closed open
open closed
6
BY-PASS
Manual version 4.1 (26-07-2018)
5. Close the inspection panels.
n Leave the pressure difference meter on the extract
fan.

2.13.5 Calibrate air volume

Set the three speeds for each airflow.
en-31
Page 32
INSTALLATION HEAT RECOVERY UNIT
en-32
Page 33
HR MANUAL INSTALLATION
Caution:
Note:
Note:
Note:
Note:
Calibrate the extract fan:
1. Set the unit to ‘manual’ and to ventilate screen of the b-touch control panel.
2. In the b-touch control panel, open the fu
menu
> Maintenance > Calibrate air volume.
3. Enter the PIN code and press .
4. Calibrate the extract fan:
K via the home
nction
c Adjust the highest speed (3) maximally to the
capacity of the unit (2500/3500/4500 m3/h).
For cooling with a cooling module use 500 m
3
(2000/3000 m
/h).
3
/h less
n Use the pressure difference meter over the extract
fan 5 .
n Use the chart to establish which pressure difference
gives the required flow rate.
Make sure to use the curve for the unit type that is being used. (See type plate.)
n Always set all three settings. Even if you only want to
change one setting.
- Set all and any connected ventilation units to the set-
ting appropriate to setting 1 (low) of the HR unit.
- Set the desired flow rate for setting 1 (low) by adjust-
ing the percentage until the appropriate pressure differ­ence is reached.
- Store by pressing .
- In the same way, set the desired flow rate for setting
(medium) and setting 3
- Check if all speeds are set correctly.
(high).
2
n Note the flow that is used for fan speed 3 of the
extract fan. This will be used later to calibrate the pressure switch.
Manual version 4.1 (26-07-2018)
en-33
Page 34
Note:
Note:
INSTALLATION HEAT RECOVERY UNIT
Calibrate the supply fan:
1. Connect the pressure difference meter to the pressure
measurement points 1 of the supply fan .
2. Calibrate the supply fan. Use the same method for this described for the extract fan.

2.13.6 Setting the pressure switch

The unit is fitted with freezing protection for the plate heat exchangers. If ice formation is identified, the unit will defrost the exchangers by blowing warm indoor air over the exchang­ers. The airflow from outside in will be turned off.
This function will be active if the pressure difference across the plate heat exchanger becomes too great.
as
n The pressure difference must be measured in fan
speed 3 (high).
At outside temperatures that form the risk of freez­ing, the unit will carry out a check by measuring the pressure difference at fan speed 3.

Adjust pressure switch

Adjust the pressure switch 7 to fan speed 3 (high):
1. Use the flow rate that is used for fan speed 3 of the extract fan (see 2.13.5 Calibrate air volume).
2. Determine the corresponding pressure difference for pr
essure switch. To do so, use the graphic.
n Use the curve for the unit type that is being used.
(See type plate.)
the
en-34
Page 35
HR MANUAL INSTALLATION
Manual version 4.1 (26-07-2018)
en-35
Page 36
Note:
INSTALLATION HEAT RECOVERY UNIT
3. Set the pressure switch 7 to the pressure difference as specified in step 2.
4. Check whether the frost protection is not unnecessarily active:
1. Set the unit to fan speed 3.
n If the unit was at a different speed, it will take
approximately two minutes before the valve positions are adjusted.
2. Check in menu > Maintenance > Unit control that the
value of the fourth input (1-2-3- 4) is a nil: x-x-x-0

2.13.7 Checking temperature sensors

The unit contains temperature sensors.
1. Check in menu > Maintenance > Unit control that the sen­sors measure realistic values (Tfresh-Tsupply, Textract-Tex­haust)
2.13.8 Checking the CO
If a CO
1. Check in menu > Maintenance > Unit control that the sen-
2.13.9 Checking the heating / c
1. Check that the heating/cooling module responds to the
con-nected heating/cooling system.
2. Limit the minimum temperature for cooling to prevent
condensation on the outside of the device and channels. (menu > Settings > 7. Minimum air temperature cooling)
sensor is used:
2
sor is measuring a realistic value (Analog in)
sensor (accessory)
2
ooling (accessory)
en-36

2.13.10 Finishing the unit

1. Close all inspection hatches.
2. Place the b-touch control panel in the holder.
Page 37
3. . Operation via b-touch
Note:
The unit can be operated via the b-touch control panel and via Modbus. This chapter describes operation with the b-touch control panel
n Some settings and functions can only be used via the
b-touch control panel or, conversely, only via Modbus.

3.1 Control panel

The b-touch control panel is equipped with a touchscreen (touch screen) with which all the functions can be set:
• Turning the unit ON and OFF;
• Adjusting the strength of the unit;
• Switching the heating ON and OFF;
• Enter settings to adapt the function of the unit to your sit­uation.

3.1.1 Settings

Manual version 4.1 (26-07-2018)
Select to save the settings and return to the previous screen.
Select to return to the previous screen without saving the changes.
en-37
Page 38
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT

3.2 The Home screen

On the home screen, information can be read and entered by touching the symbols:
• 1 on/off
• 2 main menu
• 3 extra information about the current point in the con-
trol panel.
• 4 manual or automatic control
• 5 temperature
• 6 fan strength
• 7 recirculation/ventilation
• 8 brief information on the operation of the unit

3.2.1 Symbols

The symbol
The symbol ‘i’ indicates that there is currently a tip to be read. Touch the symbol in order to read the tip.

3.2.2 Turning the unit ON and OFF

You can switch the unit ON and OFF manually, using the con­trol panel.
•Touch on/off in order to turn the unit ON or OFF.
If the unit is on, the screen will become darker after some time, in order to save energy. When the screen is touched, it lights up again. This function cannot be deactivated.
If the unit is switched off, the screen will go black after some time. Touch the screen to activate it again.
@ indicates that the timer is switched on.
en-38
The unit can also be switched ON and OFF in other ways:
• Using external controls (see function 60. Fu
inputs).
•
Via the internal timer or via an external releas
it.
the un
In these cases, the ON/OFF button can be hidden via Con-
figuration > 21. User interface options > Display on/o bu
tton.
nction of
e signal on
ff
Page 39
HR MANUAL OPERATION VIA B-TOUCH
Note:
Warning:
Note:

3.2.3 Automatic or manual control

The unit has an automatic mode and a manual mode. Select the desired setting by touching the upper part of the symbol. You can restrict the user’s choice via menu > Settings > 1.
Select modes.
Manual
In manual mode, the unit operates in a variety of fan settings (which can be manually selected).
Automatic
In automatic mode, the fan setting is automatically adjusted to the CO

3.2.4 Regulating the strength

level.
2
In automatic mode, the strength of the airflow is controlled automatically.
In the manual mode, the strength can be set manually (3 set­tings).
n For minimum energy consumption, Biddle
recommends selecting the lowest strength at which the desired air quality is achieved.

3.2.5 Errors

The symbol ä indicates that there is an error. The error mes­sage is displayed alongside.
• Touch this message for further information on the erro or instructions as to how to react.
and f
r
w Some errors may cause damage or danger to
persons if they are disregarded. If ä is displayed, follow the instructions on the control panel as regards how to act.
Manual version 4.1 (26-07-2018)
n The symbol ä and the error message remain
displayed as long as the error has not been remedied.
en-39
Page 40
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT
If an error has remedied itself, a corresponding message will be displayed. Touch this message to display the Error history and to read out the errors and the times of their occurrence. This list can also be read out via Maintenance > Error history.

3.3 Main menu

To u c h menu to open the Main menu.
•Touch home in order to return to the Home screen.
• You can use the arrows to browse through the list.
If the control panel is not operated for some time, it returns automatically to the Home screen without saving the changes.
Lock screen Select to prevent unauthorised access. The
on the screen.

Unlocking

Touch the screen for 5 seconds to unlock it.
Switch temperature control on and off Only for units with HC6 module with water control or using free
(night) cooling.
The unit’s temperature control can be switched on and off manually.
Switching the temperature controloff disables the room tem­perature control and any Heating on output functions.
This function can be deactivated via setting 21 in the configu­ration menu.
If the heating has been switched on via this function, it may occur that the automatic control switches the heating off again. This may be due to an external signal, for example, or because the desired temperature has been reached.
# symbol appears
en-40
The heating can also be switched off by the control itself:
• by an external signal at the input of the un
nu > Configuration > 60. Function of inputs, settin
me Heating off;
it, see
g
Page 41
HR MANUAL OPERATION VIA B-TOUCH
Filter Dirty filters make the unit less effective. It is therefore neces-
sary to clean or replace the filters at regular intervals. The contamination of filters is measured with the optional filter sensor or calculated on the basis of the lifespan.
The lifespan of the filter is calculated on the basis of the usage of the unit if no filter sensor has been installed. You can adjust this by setting the maximum lifespan of the filter.
When the filters are contaminated or when the maximum lifespan has elapsed, a message appears on the Home screen. Also, a signal can be generated on one of the outputs.
New filters are available from Biddle.
Cleaning the display The screen can be cleaned using a damp, soft cloth.
Use this function to disable the touch screen for 20 seconds in order to be able to clean it.
Timer The b-touch control panel has a week timer. You can set two
start and stop times for each day of the week. The unit is on between the start time and the stop time. The second start and stop times are optional. When the ON/OFF button is dis­played on the screen, the unit can also be switched ON or OFF manually. From the next switching moment, the unit fol­lows the timer again. When the timer is switched on, the sym-
@ is displayed on the Home screen.
bol

3.4 Preferences

Preferences The menu Preferences allows you to make settings for the use
of the control panel.
Set language The control panel offers a choice of languages. Choose your
preferred language from the list.
Set date and time The date and time are necessary for the timer function, the
lifespan of the filter and for tracking usage statistics regarding the unit.
The automatic summer time function switches the clock to summer or winter time in accordance with the applicable European rules. If you do not use this function, you can switch to summer time manually. The clock is then set one hour for­ward.
Manual version 4.1 (26-07-2018)
en-41
Page 42
Note:
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT
Celsius / Fahrenheit Choose between a temperature display in degrees Celsius or
degrees Fahrenheit.
Display brightness Set the brightness of the screen to your personal preferences
or to the specific situation.
Show tips The control panel can show tips about the usage of the unit.
The display of these tips can be enabled or disabled.

3.5 Settings

The Settings menu allows you to enter settings which influ­ence the day-to-day use of the unit.
Sel
1.
ect modes The control panel has an automatic mode and a manual mode.
With the function Select modes, you can set which of these modes can be selected in the HOME screen.
5. Room temperature Her
nimum air temperature For units with water heating module:
6. Mi
nimum air temperature, cooling In order to increase the level of comfort, a minimum dis-
7. Mi
e, set the temperature which is to be used by default as
the room temperature when starting up the unit.
The desired room temperature can temporarily be adjusted on the home screen until the next start-up moment.
Set the minimum difference between the room temperature (extract air) and the discharge temperature (supply air).
This difference can be increased for more comfort. A smaller difference saves energy.
charge temperature for cooling can be set.
8. Night temperature The night temperatur
When the room temperature drops below this set value, the unit will start working in order to keep the room at the night temperature.
n This function only operates when the heating is
switched on.
en-42
e is used when the unit is switched off.
Page 43
HR MANUAL OPERATION VIA B-TOUCH
Warning:
w Be aware that the airflow of the unit can set
objects in motion. This might set off an alarm system in the building at night time.
ibration Adjust the temperature reading if this deviates from the actual
9. Cal
temperature.

3.6 Configuration

The menu Configuration allows you to enter settings in order to adjust the operation of the unit to the room and the sys­tem. Usually, this menu is used only for installation, mainte­nance and service purposes.
20. A
ccess control Pin code
Access to the entire control panel or to the menu only can be protected with a four-digit PIN code.
The default PIN code is 0000.
Access level
The control panel can be safeguarded at different access levels.

ser interface options Display on/off button

21. U
The unit can be switched ON and OFF manually. This can also be done via the internal timer or via an external release signal on the unit. In this case you can disable the manual on/off option. The on/off button is then not displayed on the Home screen.

Temperature display

By default, the room temperature (exhaust air) is displayed. With this function, you can select another temperature to dis­play or switch off the temperature display.
Manual version 4.1 (26-07-2018)
If the temperature display is switched off, there is no tempera­ture control.

Temperature control OFF option

Use this function to enable or disable the option for the user to switch the temperature controlON/OFF manually.
en-43
Page 44
Note:
Note:
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT

Error display

Some error messages may be caused by external factors such as the central heating system and do not necessarily have an influence on the functioning of the unit.
Use this function to suppress these messages. Safety-related warnings will always be displayed.
31. Auto: fan spe
ed
n These settings only have influence on usage in the
automatic mode.
Maximum fan speed
To restrict the noise level, the maximum fan speed can be lim­ited.
Use of this function can reduce comfort.
Minimum fan speed
In order to increase the level of comfort, a minimum fan speed can be set per operation:
n Set a lower value than that for the maximum fan
speed. In the event of conflicting values, the set maximum fan speed takes priority.
• Unheated
•Heating (dependent on unit type)
ooling
• C
33. Boost fun
en-44
Y
ou can set a post-rotation time for the fan. Here, set the period of time it should take for the fan to decelerate from maximum speed to standstill.
ction Only applicable to units with a heating module.
If there is a great difference between the desired and the actual room temperatures, the fan speed can be increased in order to reach the desired temperature more quickly.
Set the temperature difference at which the boost function should be activated and the fan’s increase in speed.
Page 45
HR MANUAL OPERATION VIA B-TOUCH
Note:
Note:

35. Ventilation settings Ventilation control

Only applicable to units with a recirculation module.
The relationship between ventilation air and recirculated air can be determined in various ways:
• Manual selection: Manual switching between ventilatio ecirculation.
r
• Valve regulation: Manual regula
v
entilation valve.
• Automatic selection: The quantity of ventilation air is
determined by a CO2 sensor. Manual switching between ventilation and recirculation is possible.
• Fully automatic: The quantity of ventilation air is alwa
determined b

Maximum position of ventilation valve

Only applicable to units with a recirculation module.
The maximum opening percentage of the ventilation valve can be limited.

Minimum fan speed during ventilation

Set the minimum percentage of the fan speed for ventilation.

Maximum fan speed during ventilation

y a CO2 sensor.
tion of the position of the
n and
ys
Set the maximum percentage of the fan speed for ventilation.
46. Maximum discharge temperature The
mum of 50°C. Possibly set a lower value in order to save energy.
47. Overheat protection I
f the actual room temperature becomes higher than the pre­set room temperature, the heating can be switched off in order to prevent the room from becoming too warm.
Set the temperature above which the heating must be disabled.
n This function can only be used if the unit is set to
n If this function is activated, then function 6. Minimum
controller limits the discharge temperature to a maxi-
automatic.
air temperature is ignored.
Manual version 4.1 (26-07-2018)
en-45
Page 46
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT
60. Function of inputs The unit has an input (terminal block X1) which can be used
to enable a function to be controlled by an external accessory such as a smoke or fire alarm.
Values for input
ALUE OPTION DESCRIPTION
V
0 No function The input has no function.
1 Unit off locally - NO The unit is switched OFF when the contact is closed. (This only works in
units to which the input signal is directly connected (locally).)
51 Unit off locally - NC The unit is switched OFF when the contact is open. (This only works in
units to which the input signal is directly connected (locally).)
21 Switch all units on All units are switched ON when the contact is closed.
71 All units off All units are switched OFF when the contact is closed.
6 Heating off The heating is switched OFF when the contact is closed.
56 Heating on
(dependent on software version)
7 change-over signal, cool-
ing
57 change-over signal, heat-
ing
9 Release - NO The user is allowed to switch the unit on and off when the contact is
59 Release - NC The user is allowed to switch the unit on and off when the contact is open.
10 Dirty filter – NO Displays a “dirty filter” warning if the contact is closed for longer than 60
60 Dirty filter – NC Displays a “dirty filter” warning if the contact is open for longer than 60
30 Smoke extraction When the contact is closed:
31 Fire mode When the contact is closed:
41 Fire alarm When the contact is closed:
40 Smoke alarm When the contact is closed:
Heating is available when the contact is closed.
The unit switches from heating to cooling when the contact is closed.
In the event of conflicts between different inputs, cooling has priority.
The unit switches from cooling to heating when the contact is closed.
In the event of conflicts between different inputs, cooling has priority.
closed.
seconds.
seconds.
•air is extracted.
• no air is supplied.
• an alarm signal (smoke) is sent to the building management system.
• the unit is switched off.
• any air dampers are closed.
• an alarm signal (fire) is sent to the building management system.
• an alarm signal (fire) is sent to the building management system.
• an alarm signal (smoke) is sent to the building management system.
en-46
Page 47
HR MANUAL OPERATION VIA B-TOUCH
Note:
Note:
Note:

Release delay input 1

When you use input 1, you can make the effect of an input sig­nal persist for some time after the signal has been given (‘release delay’).
62. A
utomatic CO2 control Only with use of automatic CO
The unit can automatically adjust the fan speed and, if required, the recirculation damper to the CO
The default values for the CO menu.
Fan speeds with stepped controls
LEVEL FAN
CO
2
< 1 without recirculation module 0 (off)
with recirculation module 1 (recirculation)
< 2 1 (ventilation)
< 3 2 (ventilation)
> 3
LEVEL DEFAULT
CO
2
1 800 ppm
2 1000 ppm
3 1200 ppm
control
2
level.
2
levels can be adjusted in this
2
SPEED
3 (ventilation)
VALUE
n The current CO
n If no CO
n In the building management system (BMS) you can
65.
Control panel input Not applicable.
Manual version 4.1 (26-07-2018)
level must be measured via the
2
building management system (BMS) or via a sensor connected to the unit.
sensor is detected, the device will operate
2
in fan setting 1 (ventilation).
indicate (register address 350) whether the speed is to operate in a continuously variable manner or at set speeds. The curve for continuously variable operation is also based on the three CO be indicated.
levels to
2
en-47
Page 48
Note:
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT

3.7 Maintenance

The Maintenance menu contains information on the use of the unit and offers a number of functions which are necessary for remedying errors.
Status The status screen displays general information about the
installation and specific information per group and per unit connected.
Current errors Gives an overview of current errors. The error messages can
also be deleted here.
Error history Gives an overview of the errors which have occurred.
Capacity test Use this function to test the capacity of the unit and your
heating installation.
The unit will run for 120 minutes at the highest fan speed and with the highest heating capacity. You can check the discharge temperature and the heating capacity. The discharge tempera­ture is limited to 50°C.
For units with water heating:
If the heating capacity is too low, check the supply and return water temperatures and the water flow.
Valve check Use this function to test the operation of the water valve:
1. Set the opening percentage of the valve to 0%;
2. Press start. The fans will start rotating at the highest speed;
3. Check whether the discharged air is cold;
n It may take some time before the valve reaches the
adjusted opening percentage.
en-48
4. Repeat steps 1 and 2 for the percentages 50% and 100 w
ell. In doing so, check whether the discharged air gets
warmer per step.
% as
Page 49
HR MANUAL OPERATION VIA B-TOUCH
Installation This installation guide leads you through the most frequently
required settings.
The installation guide is started up automatically during the first start-up of the unit or after the resetting of the factory configuration.
Unit code For entering the unit code after replacement of the control
circuit board in a unit.
Calibrate air volume Use this function to set the fan speeds.
In 2.13.5 Calibrate air volume a description is provided of how you can calibrate the fans.
Unit check Use this function to check the operation of the unit.
Run through the various modes in this function to check the operation of the dampers and fans, as indicated in 2.13.4
Checking operation.
Modbus settings The settings for Modbus can be adjusted:
•Baud rate
• Communication:
-DATA bits
- Parity (N = none, E = even, O = odd)
- Stop bits
• Modbus node address (0 = use code dip switches of ol circuit board)
contr
Default settings Restores the default factory settings of the setup menu. The
settings entered in the configuration menu are retained.
the
Manual version 4.1 (26-07-2018)
en-49
Page 50
Note:
Caution:
Warning:
OPERATION VIA B-TOUCH HEAT RECOVERY UNIT
Factory configuration Restores the standard factory configuration. All settings are
then lost.
n The installation guide will be restarted.
Reset system The control panel searches for connection with the attached
units again. Use this function when remedying errors and dur­ing connection or disconnection of units.

3.8 USB

The control panel is equipped with a USB port to which only a USB flash drive can be connected. This is used for:
• updating the software
• importing and exporting settings
• exporting usage data
This menu is automatically activated when a USB flash drive is connected. The menu is closed again when the USB flash drive is removed.
c Do not remove the USB flash drive during the
updating or during the importing or exporting of data. This can take several minutes.
w Connection of other electronic devices to the
USB port can cause serious damage to the control panel or to other electronic components.
Software update Biddle is working continuously on improving its products and
recommends that you update the software of the control panel when updates become available. Consult www.bid­dle.info/software to see if updates are available.
en-50
• The installed version of the software can be read out from
Maintenance > Status.
• Download the latest version of the software via Biddle’
bsite.
we
See also: 7.8 Updating the software
s
Page 51
HR MANUAL OPERATION VIA B-TOUCH
Note:
Note:
Upload logo It is possible to use your own logo or image as background for
the display.
Requirements for the image:
• Windows bitmap;
• Filename: logo.bmp;
• Dimensions: maximum 240 x 320 pixels;
• Colour depth: 8-bit grayscale or 24-bit colour.
n Uploading your own logo replaces the standard
Biddle logo.
Export/import settings For copying settings between control panels.
See also: 7.7 Copying the settings
Exporting system info Export the file ‘system_info’ for an overview of all connection
control circuit boards and control panels with corresponding software versions.
Export log... The Export log functions write data concerning the operation
of the unit to the USB flash drive. These files can then be ana­lysed on a computer.
The files contain the following data:
• log_func: Data concerning the operation of the unit.
• log_error: Error report history.
• log_user: User settings history.
• log_stat: not in use.
• system_info: Overview of connected control circuit boar and con
trol panels.
ds
Manual version 4.1 (26-07-2018)
n The process of exporting can take several minutes.
Repeat if 100% is not achieved.
en-51
Page 52
Note:
Caution:
Note:
Note:
Note:
4. . Operation via Modbus
The unit can be operated via the b-touch control panel and via Modbus. This chapter describes the operation via Modbus.
n Some settings and functions can only be used via the
b-touch control panel or, conversely, only via Modbus.

4.1 Frequently used register addresses

This paragraph describes frequently-used functions and their corresponding register addresses.
c Do not adjust other register addresses without
consulting Biddle.
n It may occur that the system applied uses a value of
1 higher than the register addresses given here. In that case, use 101 for register address 100, for example.
n For functions that are also in the b-touch panel, the
corresponding menu parameter is shown between brackets after the register address.
Menu parameters 0 - 1 are functions in the home screen.
en-52
n Settings in the b-touch control panel can cause
Modbus settings to be ignored. In register addresses 410 to 419 inclusive, it can be specified whether settings may be altered via the b-touch.
Register addresses 410 - 419 are related to 400 ­409 and 420 - 429 respectively.
Page 53
HR MANUAL OPERATION VIA MODBUS
Note:
REGISTER ADDRESS DESCRIPTION
400 - 409 ro User functions: Current status
410 - 419 rw User functions: Changes via the b-
touch control panel: 0 = permitted (default) 1 = not permitted
420 - 429 rw User functions: Modbus setpoint

4.1.1 General Operation

REGISTER ADDRESS
420 (0.1) Turning the unit ON and OFF rw-021
425 (0.6) Automatic or manual control rw-011
*ro = read only (read only) *rw = read & write (read and write)
420 (0.1) Turning the unit ON and OFF
VALUE OPTION DESCRIPTION
0 off Switching the unit OFF.
1 on Switching the unit ON (normal operation).
425 (0.6) Automatic or manual control The unit has an automatic mode and a manual mode. When
DESCRIPTION RO
• Special functions (register address 337) are still working.
the unit is switched on, it will begin operating in the auto­matic mode.
/RW* UNIT MINIMUM MAXIMUM DEFAULT
VALUE OPTION DESCRIPTION
0 manual The unit is operating in various settings (can be switched
manually).
1 automatic The unit automatically operates at the correct fan and
damper settings.
n Via register address 275 (1), it can be specified which
settings are allowed.
Manual version 4.1 (26-07-2018)
en-53
Page 54
Note:
OPERATION VIA MODBUS HEAT RECOVERY UNIT
Register address 275 (1)
VALUE DESCRIPTION
1allowed: manual
2 allowed: automatic
3 (default) allowed: manual, automatic

4.1.2 Manual operation

REGISTER ADDRESS
422 (0.3) Manual setting of the strength rw % 0 100 50
*ro = read only (read only) *rw = read & write (read and write)
REGISTER ADDRESS
275 (1) Select modes 1 = allowed: manual
425 (0.6) Automatic or manual control 0 = manual
422 (0.3) Manual setting of the strength In the manual mode, the strength can be set manually.
DESCRIPTION RO
DESCRIPTION VALUE
/RW* UNIT MINIMUM MAXIMUM DEFAULT
The unit can only be controlled manually if the functions below have been set as follows:
3 = allowed: manual, automatic
VALUE FAN SPEED
00%
1 - 49 35%
50 - 79 65%
80 - 100 95%
en-54
n For minimum energy consumption, Biddle
recommends selecting the lowest strength at which the desired air quality is achieved.

4.1.3 Automatic operation

The unit can only be controlled automatically if the functions below have been set as follows:
Page 55
HR MANUAL OPERATION VIA MODBUS
Note:
REGISTER ADDRESS
DESCRIPTION VALUE
275 (1) Select modes 2 = allowed: automatic
3 = allowed: manual, automatic
425 (0.6) Automatic or manual control 1 = automatic

4.1.4 Automatic CO2 control

The unit automatically adjusts the fan speed (and any recircula­tion damper) to the CO
The CO
level is supplied by the building management system
2
(BMS) or, if this information is not available, by a CO (accessory) on X377 (via connection X3).
n If no CO
sensor is detected, the device will operate
2
in fan setting 1 (ventilation).
Fan speeds with stepped controls
LEVEL FAN
CO
2
< 1 without recirculation module 0 (off)
with recirculation module 1 (recirculation)
< 2 1 (ventilation)
< 3 2 (ventilation)
> 3
level.
2
sensor
2
SPEED
3 (ventilation)
REGISTER ADDRESS
DESCRIPTION RO
/RW* UNIT MINIMUM MAXIMUM DEFAULT
351 (62.2) CO2level 1 rw ppm 200 2000 800
352 (62.3) CO
353 (62.4) CO
432 CO
level 2 rw ppm 200 2000 1000
2
level 3 rw ppm 200 2000 1200
2
level from BMS rw ppm 0 2000 0
2
151 Input voltage, analogue input X377 ro 0.01 V - - -
*ro = read only (read only) *rw = read & write (read and write)
Manual version 4.1 (26-07-2018)
en-55
Page 56
Note:
OPERATION VIA MODBUS HEAT RECOVERY UNIT

4.1.5 Ventilation/Recirculation/Night cooling

REGISTER ADDRESS
426 Mode: ventilation/recirculation/
*ro = read only (read only) *rw = read & write (read and write)
426 Mode: ventilation/recirculation/night
cooling
DESCRIPTION RO
rw - 0 10 0
night cooling
The unit is designed to use heat recovery on ventilation air. Depending on the type and the settings, the unit can also recirculate or supply ventilation air without heat recovery from extracted air (night cooling).
/RW* UNIT MINIMUM MAXIMUM DEFAULT
n Register address 301 must have the value 1 (default)
UNIT
VALUE DESCRIPTION
0recirculation
(only functional in the case of units with a recirculation module and in manual control)
2 ventilation
(only functional in manual control)
10 ventilation with night cooling ventilation
FUNCTION ON
(DAYTIME)
recirculation (no heat recovery)
ventilation (heat recovery from the extracted air)
(heat recovery from the extracted air)
(100% recirculation/ventilation).
UNIT FUNCTION OFF
(NIGHT TIME)
off
off
ventilation (fan speed 2) (cooling with fresh air via by­pass, no heat recovery)
en-56

4.1.6 Alarm functions

In emergencies, the unit can emit an alarm signal or even actively deal with the problem by functioning in a special mode.
This special operation replaces the normal operation of the unit (during the day and at night time) until the signal is no longer active (435 is 0 again).
Page 57
HR MANUAL OPERATION VIA MODBUS
REGISTER ADDRESS
DESCRIPTION RO
337 Alarm functions
/RW* UNIT MINIMUM MAXIMUM DEFAULT
rw - 0 41 0 (activated by input 1 (i1) or by reg­ister address 435)
435 Activate alarm functions (register
rw-010 address 337) 0 = inactive 1 = active
*ro = read only (read only) *rw = read & write (read and write)

337 Alarm functions

VALUE OPTION DESCRIPTION
30 Smoke extraction When the contact is closed:
• air is extracted (maximum fan speed).
• no air is supplied.
• an alarm signal (smoke) is sent to the building manage­ment system.
31 Fire mode When the contact is closed:
• the unit is switched off.
• any air dampers are closed.
• an alarm signal (fire) is sent to the building ma system.
40 Smoke alarm When the contact is closed:
• an alarm signal (smoke) is sent to the building manage­ment system.
41 Fire alarm When the contact is closed:
• an alarm signal (fire) is sent to the building management system.
nagement
4.1.7 Reading out current operation
The current operation of the unit can be read out in re
gister
address 221.
REGISTER ADDRESS
DESCRIPTION RO
/RW* UNIT MINIMUM MAXIMUM DEFAULT
221 Current mode operation ro-0151-
*ro = read only (read only) *rw = read & write (read and write)
Manual version 4.1 (26-07-2018)
en-57
Page 58
OPERATION VIA MODBUS HEAT RECOVERY UNIT
221 Current mode operation
VALUE OPTION
general
01 unit off
05 test function
ventilation
20 ventilation, auto - speed 0
11 ventilation, auto - speed 1
12 ventilation, auto - speed 2
13 ventilation, auto - speed 3
14 ventilation, auto - boost
15 ventilation, manual - speed 0
16 ventilation, manual - speed 1
17 ventilation, manual - speed 2
18 ventilation, manual - speed 3
19 ventilation, manual - boost
recirculation
20 recirculation, auto - speed 0
21 recirculation, auto - speed 1
22 recirculation, auto - speed 2
23 recirculation, auto - speed 3
25 recirculation, manual - speed 0
26 recirculation, manual - speed 1
27 recirculation, manual - speed 2
28 recirculation, manual - speed 3
special operation
31 night cooling
41 fire mode (external signal)
42 smoke extraction
51 defrosting

4.2 All register addresses

en-58
An extensive list of register addresses for using ModBus is available at: www.biddle.info.
Page 59
5. . Errors
Danger:
Warning:
d All work on the inside of the unit may only be
carried out by personnel who are technically qualified to do so.
w Before you begin: read the safety instructions.
See also:
1.5 "Safety instructions" on page 11

5.1 Resolving simple problems

If you suspect an error, first try to resolve the problem using the table below. You do not need to be an expert for this.
If this fails to resolve the problem, there may be a fault; in that case, alert the installer.
ROBLEM PROBABLE CAUSE WHAT TO DO
P
The unit does not work.
The unit does not respond to changes in the b-touch control panel.
The unit only moves air from the inside to the outside.
The unit functions dif­ferently from expecta­tions.
The unit is not circu­lating enough air.
The unit has not been switched on Turn the unit on
The unit has no power supply. Check the mains supply:
•isolation switch;
• unit has power.
The unit is running in test mode. Stop the test mode: in
menu > Maintenance > Reset system click
stop .
The unit is running in defrost mode. When the pressure different across the
plate heat exchanger is once again correct, defrost mode will remain active for another ten minutes. The unit will then run in the last activated mode.
The unit is operating in a special mode. • Check which mode the unit is operat-
ing in. (Register address 221 or b- touch menu ...)
One of the inlet sections and/or the con­nected ventilation units is blocked.
Remove obstacles to the inlet and dis­charge section.
Manual version 4.1 (26-07-2018)
en-59
Page 60
ERRORS HEAT RECOVERY UNIT
P
ROBLEM PROBABLE CAUSE WHAT TO DO
Only for models with heating: The unit is not
heating or not heating sufficiently.
The maximum discharge temperature is limited.
Only for water-heated models: The central heating system is not working properly.
See also:
2.12 "Connecting the unit to the mains supply" on page 27
Check the value at 46. Maximum dis-
charge temperature
Check the central heating system.
• Check the connections.
• Check the operation.
• Check the capacity.

5.2 Remedying errors that are accompanied by an error message

ERROR MESSAGE PROBABLE CAUSE WHAT TO DO
The malfunction lamp is lit up. The filter is letting insufficient air
through, due to contamination.
See also:
6.2 "Replacing the filter" on page 64
Check the filter for contamination. Clean or replace it if necessary. You can adjust the pressure differ­ence meter over the filter to make it emit a dirty filter signal either sooner or later.

5.3 Reading out errors

Errors are recorded with a binary code in two registers.
In the log file “log_error.csv”, which can be read out with a USB flash drive, the errors are indicated with a numeric value.

5.4 Error codes registers

Error codes register 216/ErrorFlags[0]
LOG_ERROR.CSV
BIT VALUE VALUE CODE DESCRIPTION
38 3 E7Fan error
en-60
Page 61
HR MANUAL ERRORS
Note:
Note:
Error codes register 217/ErrorFlags[1]
RRORFLAGS[1];
E MODBUS 217
BIT VALUE VALUE CODE DESCRIPTION
0 1 16 F1 Filters must be replaced
14 8192 29 F17 Faulty CO
LOGERROR.CSV
sensor
2

5.5 Error messages on the control panel

For models with b-touch control panel
Some errors are displayed with a symbol on the home screen of the b-touch panel.
n When the error message is touched, the screen
displays an explanation, together with a list of the actions to be taken.
n The message will disappear from the Home screen
when the error has been remedied.
CODE PROBABLE CAUSE WHAT TO DO
E7 Fan error 1. Check the fans. If one or more fans do not work, please
check:
- the fan wiring;
- the connections on the electronics module;
- the transformer fuse;
- the transformer itself.
2. If these are in order, then replace the fan.
F1 Dirty Filter Replace the filters.
F17 With automatic CO
The CO not working.
sensor in the inlet duct is
2
control:
2
1. Check the sensor’s wiring and connection X377).
2. If these are in order, then replace the sensor.
(connector
Manual version 4.1 (26-07-2018)
en-61
Page 62
ERRORS HEAT RECOVERY UNIT
5.6 Remedying errors that are not accompanied by an error mes-
sage
If you suspect an error but no error message is displayed:
1. Referring to the preceding sections, check whether yo can easi
2. Try to resolve the problem using the table below. Techni­cal expertise is required for this.
P
ROBLEM PROBABLE CAUSE WHAT TO DO
The unit does not respond to the building management system.
The unit functions differently from expectations.
The unit is not circulating enough air.
The building management system is not operating correctly.
The unit has no communication with the building management system.
The unit is operating in a special mode. • Check which mode the unit
One or more modules are not properly connected.
The filter(s) is/are dirty. Clean or replace filter(s).
The fan settings are not properly cali­brated.
The duct system is giving too much resistance.
An air damper is not working properly. Check the operation of the damper
The connected ventilation unit is not working properly.
ly resolve the problem.
Check the building management sys­tem.
• Check the building man system. Check the wiring.
•
operating in. If necessary, set the unit for input
• to onl adjusting addr
ess 337 or b-touch menu 60.
Function of inputs).
heck the connections of the
• C
les
modu
• Check the operation of the (See 2.13.4 Checkin
Calibrate the fan settings properly. see
2.13.5Calibrate air volume
Resolve problems in the duct system:
• ducts too narrow
• bends too sharp
• blockages
(See 2.13.4 Checking operation).
Check the operation of the connected units.
y emit a signal wi
the operation (r
g operation
u
agement
is
1
thout
egister
unit.
en-62
Page 63
HR MANUAL ERRORS
ROBLEM PROBABLE CAUSE WHAT TO DO
P
With automatic CO
control:
2
The unit functions differently from expectations.
The CO expected.
CO system for the automatic control.
settings are different than
2
is not designated as the control
2
Check the CO2 settings (register addresses 351/352/353 of b-touch menu
62. Automati
c CO2 control)
Restore the factory configuration (menu > Maintenance > Factory config-
uration)
The CO
sensor is not recognised. Check the connection of the CO2 sen-
2
sor.
The unit is making a lot of noise.
The filter(s) is/are dirty. Clean or replace filter(s).
A component is loose. Check the unit:
• are the inspection doors closed?
• are the rubber seals still in g ion?
condit
ood
See also:
2.7 "Connecting the unit to Modbus" on page 21
2.13 "Switching on and checking operation" on page 29
6.2 "Replacing the filter" on page 64
Manual version 4.1 (26-07-2018)
en-63
Page 64
Warning:
Note:
Note:
6. . Maintenance

6.1 Introduction

This chapter comprises those maintenance activities that the user himself can perform. Maintenance activities and repairs that must be performed by an installer are described in chap­ter 7Service.
See also:
7"Service" on page66

6.2 Replacing the filter

The unit is fitted with two filters:
•Fresh air filter: F7 1.
• Extract air filter: M5 2.
The filters must be replaced regularly. A dirty filter can cause inefficient operation and a high noise level.
Remove the filter:
w Set the isolation switch to 0.
1. Open the inspection hatch for the relevant filter.
2. Pull the clamps downward 3.
3. Remove the filter 4.
4. Replace the filter. New filters are available from Biddle.
5. Return the filter to its place.
en-64
n Position the correct filter back into the correct
place.
n Position the filter in the correct direction.
The air direction is shown on the filter and on the unit.
Page 65
HR MANUAL MAINTENANCE

6.3 Cleaning the unit

You can clean the interior and exterior of the unit with a damp cloth and a domestic cleaning agent. Do not use any sol­vents.

6.4 Scheduled maintenance

It is recommended to have the following inspection and main­tenance activities performed annually by an installer or other technical expert.
• Check the casing, the suspension or mounting structure, and the securing of the unit.
• Check whether the filters are clean enough and undam­aged. Replace the filters if necessary.
• Check that the heat exchanger or the electrical heatin
ements are clean. Settled dust may cause an unple
el smell.
Car
efully remove dust with a vacuum cleaner.
• Check that the plate heat exchangers are clean.
em if necessary.
th
• Check all connections of the cabling.
• Check the operation of the fans and the valves.
• Check the condensate drain:
-Clean the drainage container.
- Flush the drain pipe.
- Check that the trap is filled with water.
See also:
2.13 "Switching on and checking operation" on page 29
6.2 "Replacing the filter" on page 64
6.3 "Cleaning the unit" on page 65
7.1 "Cleaning the plate heat exchangers" on page 66
asant
Clean
g
Manual version 4.1 (26-07-2018)
en-65
Page 66
Warning:
Warning:
Warning:
Note:
7. . Service
w Servicing activities may only be carried out by
personnel who are technically qualified to do so.
w Before you begin: read the safety instructions.
See also:
1.5 "Safety instructions" on page 11

7.1 Cleaning the plate heat exchangers

Dirty plate heat exchangers can cause inefficient operation and a high noise level. If they are dirty, clean the exchangers.
The exchangers can be extracted in two ways:
•Via the side.
• Via the underside.
w Set the isolation switch to 0.
1. Open the side shield 1.
n Preferably, also open the side shield if you extract
the exchangers via the underside. This will ensure that the exchangers are no longer clamped fast.
2. Open the two inspection hatches of the heat ex odule that are located next to the recircul
m
2.
changer
ation module
en-66
Page 67
HR MANUAL SERVICE
Note:
3. Loosen the screws of the clamping strips so as to allow the strips to
4. Remove the air separation plates:
-Unscrew bolts 4 and 5.
- Extract the plates.
5. Extract the plate heat exchangers:
- Via the side: 6.
- Via the underside: 7.
drop down slightly 3.
6. The last exchanger is located behind the by-pass valve. Make room in order to extract the exchanger:
- Open the value of the by-pass 8.
- Unscrew the valve motors from the valve 9.
- When extracting via the underside:
Push the by-pass slightly to the side.
- When extracting via the side:
Disconnect the cables located on top of the by-p
extract the by-pass via the underside of the unit.
and
- Extract the last exchanger.
7. Clean the plate heat exchangers by spraying water through them.
8. Return all components to their places in reverse order.
ass
n Tighten the screws/bolts of the air separation plates
and the clamping strips again, so that the exchangers are clamped fast and no air leaks can arise.
Manual version 4.1 (26-07-2018)
en-67
Page 68
Warning:
Warning:
Note:
SERVICE HEAT RECOVERY UNIT

7.2 Removing the control circuit board

1. Switch the unit off using the control panel or the building management system.
w Shut off the mains supply.
2. Open the electronic housing.
3. Disconnect all unit-connected connectors and gr connections fr
4. Remove the screw 3.
5. Slide the control circuit board 4 un
it.

7.3 Connecting the control circuit board

w Make sure that the mains supply is switched
off
1. Slide the control circuit board into its place and screw it fi
rmly.
2. Connect all connectors and earth connections to the con­trol circuit board again.
3. Switch the unit on and check the operation.
ounded
om the control circuit board.
loose and lift it out of the
in
en-68
n With a new control circuit board, an E1 error may
occur because the old control circuit board can no longer be found. Resolve this by reconfiguring the system via menu > Maintenance > Reset system
Page 69
HR MANUAL SERVICE
Note:
Warning:
Caution:

7.4 Fuses

The unit is fitted with various fuses:
• In the electronics module 1.
• On the control circuit board 2.
The values are indicated on the fuses and/or are listed in the wiring diagram.
n First identify and remove the cause of the error
before replacing the fuses.

7.5 Setting the unit code

The unit code must be set after replacement of the control circuit board in the unit. The unit code depends on the unit type and is indicated on the type plate.
To set the unit code, there are two methods:
• directly via the control panel if a single unit is connected;
• via the control circuit board and the control panel if more than one unit is connected.
w Entering an incorrect code will result in poor
performance of the unit.

7.5.1 Setting the unit code via the control panel

c Setting the unit code using this method will only
work if just a single unit is connected to the control panel. If necessary, connect the control panel separately to the unit in question.
Manual version 4.1 (26-07-2018)
1. Select menu > Maintenance > Unit code.
2. Enter the unit code via the control panel and press ok.
The control panel will now search for the unit again.
en-69
Page 70
Warning:
Note:
SERVICE HEAT RECOVERY UNIT

7.5.2 Setting the unit code via the control circuit board and the control panel

7.6 Resetting the PIN code

1. Connect the mains supply (insert the plug into the sock
or mo
ve the isolation switch to ON).
w Do NOT touch any live parts.
2. Press down the microswitch 1 on the control circuit
board .
The LED next to the microswitch will start flashing.
The control panel displays numbers: these comprise
it code.
un
3. Enter the unit code via the control panel and press ok.
4. Press down microswitch .
The LED next to the microswitch will stop flashing.
The unit code is now set.
5. Reset the control panel.
the
et
The PIN code of the control panel can be reset using a USB flash drive:
1. Connect a USB flash drive to the control panel.
The USB menu is activated
2. Press x for 15 seconds.
n The screen shows no change.
The PIN code has now been reset to the default pin code: 0000
3. Exit the USB menu by removing the USB flash drive.
en-70
Page 71
HR MANUAL SERVICE
Note:
Note:

7.7 Copying the settings

The settings of the unit can be copied to another unit.

7.7.1 What you need

Before copying the setting, check that you have the following:
• An empty USB flash drive. The USB flash drive must be for­matted for FAT or DOS. Do not use a USB hard disk fo
e software update.
th
7.7.2 Step 1: Copying the settings of the correctly-set
unit
1. Check whether the settings to be copied on the original b­touch control panel are all correctly set.
r
2. Connect the USB flash drive to the USB port of the b­touch control panel.
n If the USB flash drive is not detected, disconnect it
and then connect it again.
The control panel detects the USB flash drive and displays the USB menu
3. Select Export Settings
The progress percentage is displayed.
4. When this has been completed, disconnect the USB flash drive from the control panel.

7.7.3 Step 2: Copying the settings to another unit

1. Connect the USB flash drive (with the settings that are to be copied) to the USB port on the other control panel.
2. Keep the function Import settings pressed down
ogress of the process is displayed.
pr
until the
Manual version 4.1 (26-07-2018)
The settings are now being imported.
n Below the progress percentage, the name of the file
to be imported is visible:‘settings_export.txt’
3. When this has been completed, disconnect the USB flash drive from the control panel.
4. Repeat steps 1 to 3 for each control panel to which yo wish to a
pply the same settings.
u
en-71
Page 72
SERVICE HEAT RECOVERY UNIT

7.8 Updating the software

Biddle is working continuously on improving its products and recommends that you update the software of the control panel and of the control circuit board when updates become available. Consult Biddle’s website for availability.

7.8.1 What you need.

Before updating the software of the control panel, check that you have the following:
• An empty USB flash drive. The USB flash drive must be for­matted for FAT or DOS. Do not use a USB hard disk fo the softwar
• A PC with Internet access.
e update.
r

7.8.2 Step 1: Check the current software version

Before you update the software of the control panel or of the control circuit board, you must check the existing software version. If the software version is the same as that of the most recent update file on Biddle’s website, you do not need to update the software.
1. Press menu in the Home screen.
2. Select Maintenance. The version of the current software is displayed in the status overview.

7.8.3 Step 2: Download the most recent software

1. Connect the USB flash drive to a USB port on your PC.
2. On your PC, go to Biddle’s website and look under Down­loads.
3. Look for your product and the available software for yo
it.
un
4. If the software version is more recent than the ve
our control panel, click on the software update.
y
ur
rsion on
en-72
5. Accept the licence agreement and save the file to the main directory of the USB flash drive.
6. Disconnect the USB flash drive from the PC.
Page 73
HR MANUAL SERVICE
Warning:
Note:

7.8.4 Step 3: Updating the software

w Do not switch off the unit or disconnect the
USB flash drive during the software update. Do not disconnect the USB flash drive from the control panel even if there is a power failure during the update. The update will resume as soon as the power returns. If an error occurs during the update, start the procedure again. If the error continues to occur, contact Biddle.
1. Connect the USB flash drive (with the software up th
e USB port on the control panel.
date) to
n If the USB flash drive is not detected, disconnect it
and then connect it again.
The control panel detects the USB flash drive and displays the USB menu
2. Select Software update to update the software.
3. When this has been completed, disconnect the USB flash drive from the control panel.
Manual version 4.1 (26-07-2018)
en-73
Page 74
SERVICE HEAT RECOVERY UNIT

7.9 Composition of the Biddle control cable

The control cable for the control system is constructed as fol­lows:
• The plugs are modular connectors of the type 6P4C.
• Connectors are untwisted, i.e. at both ends of the cable, cores are connected to the same electrode.
Colour coding of Biddle cables
LECTRODE COLOUR
E
1 (not used)
2black
3red
4 green
5yellow
6 (not used)
en-74
Page 75
8. . Dismantling
The dismantling of the installation and the handling of the coolant, oil and other components must be carried out by a qualified fitter in accordance with the relevant local and national legislation and regulations.
Pursuant to EU legislation, used electrical and electronic appli­ances must be collected for recycling. By ensuring that this product is disposed of in the correct manner, you are helping to prevent potential negative consequences for the environ­ment and public health. For more information about this, please contact your supplier or the relevant government authority.
Manual version 4.1 (26-07-2018)
en-75
Page 76
DISMANTLING HEAT RECOVERY UNIT
en-76
Page 77
9. . Addresses
If you have any comments or queries relating to this product, please do not hesitate to contact your Biddle branch.
Biddle bv
P. O. B o x 1 5 9288 ZG Kootstertille The Netherlands
T +31 (0)512 33 55 55 E [email protected] I www.biddle.nl
Biddle nv
Battelsesteenweg 455 B 2800 Malines Belgium
T +32 (0)15 28 76 76 E [email protected] I www.biddle.be
Biddle Air Systems Ltd.
St. Mary’s Road, Nuneaton Warwickshire CV11 5AU United Kingdom
T +44 (0)24 7638 4233 E [email protected] I www.biddle-air.com
Biddle GmbH
Emil-Hoffmann-Straße 55-59 50996 Cologne Germany
T +49 (0)2236 9690 0 E [email protected] I www.biddle.de
Biddle France
21 Allée des Vendanges 77183 Croissy Beaubourg France
T +33 (0)1 64 11 15 55 E [email protected] I www.biddle.fr
Manual version 4.1 (26-07-2018)
en-77
Page 78
HEAT RECOVERY UNIT
. . . Keywords
A
accessories . . . . . . . . . . . . . . . . . . . . . . . . 11
addresses . . . . . . . . . . . . . . . . . . . . . . . . . 76
application . . . . . . . . . . . . . . . . . . . . . . . . . 5
application limits . . . . . . . . . . . . . . . . . . . . 8
automatic . . . . . . . . . . . . . . . . . . . . . . . . . 39
B
BACnet . . . . . . . . . . . . . . . . . . . . . . . . . . 21
battery type . . . . . . . . . . . . . . . . . . . . . . . . 6
baud rate . . . . . . . . . . . . . . . . . . . . . . . . . 21
building management system . . . . . . . . . . 52
C
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CE declaration . . . . . . . . . . . . . . . . . . . . . 10
central heating system . . . . . . . . . . . . . . . 18
cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 65
communication parameters. . . . . . . . . . . 21
condensate drain . . . . . . . . . . . . . . . . . . . 19
connecting power supply. . . . . . . . . . . . . 27
control cable . . . . . . . . . . . . . . . . . . . . . . 74
control valve . . . . . . . . . . . . . . . . . . . . . . 18
F
fan speeds. . . . . . . . . . . . . . . . . . . . . . . . . 31
filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
fire alarm . . . . . . . . . . . . . . . . . . . . . . 26, 56
freezing protection . . . . . . . . . . . . . . . . . 34
frequently used . . . . . . . . . . . . . . . . . . . . 52
fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
H
heat recovery system. . . . . . . . . . . . . . . . 18
home screen . . . . . . . . . . . . . . . . . . . . . . 38
I
installation . . . . . . . . . . . . . . . . . . . . . . . . 13
external controls . . . . . . . . . . . . . . . 25
M
mains supply . . . . . . . . . . . . . . . . . . . . . . . 27
maintenance . . . . . . . . . . . . . . . . . . . . . . . 64
scheduled . . . . . . . . . . . . . . . . . . . . . 65
manual . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Modbus. . . . . . . . . . . . . . . . . . . . . . . . 21, 49
modifications . . . . . . . . . . . . . . . . . . . . . . 10
D
delivery inspection . . . . . . . . . . . . . . . . . . 13
designations . . . . . . . . . . . . . . . . . . . . . . . . 4
dismantling . . . . . . . . . . . . . . . . . . . . . . . . 75
duct system . . . . . . . . . . . . . . . . . . . . . . . 17
O
operation . . . . . . . . . . . . . . . . . . . . . . . . . 52
connecting . . . . . . . . . . . . . . . . . . . . 23
P
E
electronics module . . . . . . . . . . . . . . . . . 15
elektronica-module . . . . . . . . . . . . . . . . . 15
errors. . . . . . . . . . . . . . . . . . . . . . . . . 39, 59
reading out. . . . . . . . . . . . . . . . . . . . 60
en-78 B
parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
PIN code . . . . . . . . . . . . . . . . . . . . . . . . . 70
plate heat exchanger . . . . . . . . . . . . . . . . 66
power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
power supply voltage. . . . . . . . . . . . . . . . . 8
pressure switch . . . . . . . . . . . . . . . . . . . . 34
problems . . . . . . . . . . . . . . . . . . . . . . . . . 59
product series . . . . . . . . . . . . . . . . . . . . . . 6
Page 79
HR MANUAL
R
register addresses. . . . . . . . . . . . . . . . . . . 52
S
safety instructions
installation. . . . . . . . . . . . . . . . . . 12, 13
maintenance . . . . . . . . . . . . . . . . 12, 59
service. . . . . . . . . . . . . . . . . . . . . 12, 66
usage . . . . . . . . . . . . . . . . . . . . . . . . . 11
service. . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
smoke detector . . . . . . . . . . . . . . . . . 26, 56
sound levels . . . . . . . . . . . . . . . . . . . . . . . . 9
stop bits . . . . . . . . . . . . . . . . . . . . . . . . . . 21
strength. . . . . . . . . . . . . . . . . . . . . . . . . . . 39
suspension. . . . . . . . . . . . . . . . . . . . . . 13, 14
switching ON . . . . . . . . . . . . . . . . . . . . . . 29
symbols . . . . . . . . . . . . . . . . . . . . . . . . 4, 5, 7
T
temperature sensor . . . . . . . . . . . . . . . . . 24
turn on . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
type code . . . . . . . . . . . . . . . . . . . . . . . . . . 6
type designation . . . . . . . . . . . . . . . . . . . . . 6
type plate . . . . . . . . . . . . . . . . . . . . . . . . . . 8
U
unit code . . . . . . . . . . . . . . . . . . . . . . . . . . 69
updating software . . . . . . . . . . . . . . . . . . . 72
USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
V
ventilatorstanden . . . . . . . . . . . . . . . . . . . 31
W
warning lamp. . . . . . . . . . . . . . . . . . . . . . . 27
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
wiring diagram . . . . . . . . . . . . . . . . . . . . . . 5
Manual version 4.1 (26-07-2018) en-79
Page 80

Copyright and Trademarks

All information and drawings contained in this manual are the property of Biddle and may not be used (other than for the purpose of unit operation), photocopied, reproduced, translated and/or communicated to third parties without prior written permission from Biddle.
The name Biddle is a registered trademark of Biddle bv.

Warranty and liability

For the warranty and liability provisions and terms, please refer to the terms & conditions of sale and supply.
At all times, Biddle shall not be held liable for consequential damages.

Liability as regards the manual

Although great care has been taken to ensure the correct and, where necessary, complete description of the relevant components, Biddle shall not be held liable for damages as a consequence of errors and/or imperfections in this manual.
Biddle reserves the right to alter the specifications as mentioned in this manual.
Should you nevertheless discover any errors or ambiguities in the manual, we shall be glad to learn that from you. It helps us to improve the documentation still further.

For more information

If you have any comments or queries relating to this product, please do not hesitate to contact Biddle. You will find the contact information for your Biddle branch in chapter 9 Addresses.
Biddle bv
P.O. Box 15 9288 ZG Kootstertille The Netherlands
T +31 (0)512 33 55 55 E [email protected] I www.biddle.nl
Name and telephone number of installer: