2.3Connecting the unit to the ventilation system17
2.4Connecting the unit to the central heating and heat recovery system18
2.5Installing condensate drain19
2.6Connecting components to electronics module20
2.7Connecting the unit to Modbus21
2.8Installing the b-touch control panel (accessory)22
2.9Connecting the temperature sensor (accessory)24
2.10Installing sensors for control (accessory)24
2.11Installing external controls25
2.12Connecting the unit to the mains supply27
2.13Switching on and checking operation29
3Operation via b-touch37
3.1Control panel37
3.2The Home screen38
3.3Main menu40
3.4Preferences41
3.5Settings42
3.6Configuration43
3.7Maintenance48
3.8USB50
4Operation via Modbus52
4.1Frequently used register addresses52
4.2All register addresses58
5Errors59
5.1Resolving simple problems59
5.2Remedying errors that are accompanied by an error message60
5.3Reading out errors60
5.4Error codes registers60
5.5Error messages on the control panel61
5.6Remedying errors that are not accompanied by an error message62
en-2B
Page 3
HR MANUAL
6Maintenance64
6.1Introduction64
6.2Replacing the filter64
6.3Cleaning the unit65
6.4Scheduled maintenance65
7Service66
7.1Cleaning the plate heat exchangers66
7.2Removing the control circuit board68
7.3Connecting the control circuit board68
7.4Fuses69
7.5Setting the unit code69
7.6Resetting the PIN code70
7.7Copying the settings71
7.8Updating the software72
7.9Composition of the Biddle control cable74
en
8Dismantling75
9Addresses76
Keywords77
Manual version 4.1 (26-07-2018)
en-3
Page 4
en
Note:
Caution:
Warning:
Danger:
1.. Introduction
1.1About this manual
1.2How to read this manual
This manual describes the installation, operation and maintenance of the heat-recovery unit HR. The manual also provides
instructions and information for servicing activities.
1.2.1 Designations used in the manual
The following symbols are used in the manual:
nRefers to an important section in the text.
c If you do not carry out the procedure or action
correctly, you may cause damage to the unit.
Follow the instructions precisely.
w If you do not carry out the procedure or
action correctly, you may cause physical injury
and/or damage.
Follow the instructions precisely.
d Is used to designate actions that are not
permitted.
en-4
Ignoring this prohibition may lead to serious
damage or to accidents resulting in physical
injury.
Page 5
HR MANUALINTRODUCTION
1.2.2 Symbols used on the unit and in the manual
The following symbols indicate possible risks or hazards. The
same symbols will also be found on the unit.
YMBOLDESCRIPTION
S
w You have accessed a section of the unit containing components which carry
a voltage.
Access restricted to qualified maintenance staff only.
Caution is required.
w This surface or component may be hot. Risk of burns on contact.
en
w You have accessed a section of the unit with running fans.
Caution is required.
1.3About the unit
1.2.3 Images
The images in this manual can deviate from your specific
device type. The functioning is the same, unless indicated otherwise.
1.2.4 Related documentation
In addition to this manual, the following documentation is also
supplied with the unit:
•wiring diagram for installation and servicing.
1.3.1 Application
Manual version 4.1 (26-07-2018)
The unit is designed to use heat recovery on ventilation air,
with or without additional heating.
en-5
Page 6
en
Warning:
INTRODUCTIONHEATRECOVERYUNIT
Other versions and intended use
w Applications other than those described
above are deemed to be ‘usage other than for
the intended purpose’. Biddle is not liable for
damage or loss resulting from usage other
than for the intended purpose. Usage for the
intended purpose also entails observance of
the instructions in this manual.
1.3.2 Type designation
In combination, the type designations constitute the type
code.
Type code basic units
The type code of a basic unit is, for example, HR 35
TYPECODEELEMENT DESIGNATIONMEANING
product seriesHRgeneral designa-
tion for the series
capacity252500 m3/h
353500 m3/h
454500 m3/h
Type code additional modules
The type code for additional modules is a combination of the
type code for the corresponding basic unit, combined with the
indication for the additional module.
For example, for a recirculation module this is HR 35-RM
en-6
TYPECODEELEMENT
battery typeHC6water heating,
accessoryRMrecirculation
ADDITIONAL
DESIGNATION
DXheating via direct
MEANING
cooling and/or
ventilation
expansion
module
Page 7
HR MANUALINTRODUCTION
1.3.3 Symbols on the unit
The modules are equipped with stickers and symbols. These
symbols provide information on:
•function
•airflow
components
FUNCTIONSYMBOL
heat exchanger
recirculation damper
en
fan
filter
heating/cooling
airflow
AIRFLOWSYMBOL
supply air
extract air
exhaust air
Manual version 4.1 (26-07-2018)
fresh air
en-7
Page 8
en
Note:
Warning:
INTRODUCTIONHEATRECOVERYUNIT
1.3.4 Type plate
The type plate is located on the side of the basicunit.
Supplemental modules have their own type plate.
Designations on the type plate
DESIGNATION MEANING
Typecomplete type code of the unit
o
N
Mweight of unit
Mediummedium
p
max
Upower supply voltage
I
max
P
motor
serial number, production week and year
maximum permissible operating pressure
max. current
max. power consumption by fans
1.3.5 Field of application
Observe the following limits for the unit:
Operating limits for all models
Ambient conditionsTemperature5 °C to 40°C
Relative air
humidity
Power supply voltagesee type plate
Powersee type plate
Parameters of use for water-heated models
20% - 95%, not
condensing
nConsult Biddle if you want to connect a unit to a
water flow-path with higher temperatures and higher
pressure.
w The unit may not be used in potentially
explosive environments, outdoors or in very
dusty or aggressive air conditions.
en-8
Biddle shall not be held liable for damage caused by
use under these conditions.
Page 9
HR MANUALINTRODUCTION
Sound levels
Maximum sound power level in ducts
en
SOUNDPOWERLEVEL
(LW RE. 10
-12
W)
OCTAVEBANDCENTREFREQUENCY (HZ)
631252505001000200040008000
L
WA
DB(A)
HR 25
supply air69.865.676.475.178.880.478.574.185.5
extract air65.760.570.669.967.470.870.966.776.6
exhaust air69.865.676.475.178.880.478.574.185.5
fresh air65.760.570.669.967.470.870.966.776.6
HR 35
supply air75.870.778.678.481.381.278.375.486.6
extract air68.665.875.572.369.270.268.267.276.7
exhaust air75.870.778.678.481.381.278.375.486.6
fresh air68.665.875.572.369.270.268.267.276.7
HR 45
supply air71.974.086.778.880.379.877.571.586.2
extract air69.170.381.874.168.770.167.862.878.0
exhaust air71.974.086.778.880.379.877.571.586.2
fresh air69.170.381.874.168.770.167.862.878.0
Maximum sound power level in unit housing
D
TECHNICALSPEED
B(A)
(LWA RE.10
-12
W)
HR 25 HR 35HR 45
10 V DC (high speed)747478
8 V DC686975
6 V DC636468
5 V DC586062
Maximum sound pressure level in standard room
D
B(A)
(L
RE.2X10-5 N/M2)
TECHNICALSPEED
PA
HR 25HR 35HR 45
10 V DC (high speed)666670
8 V DC606167
6 V DC555660
5 V DC505254
Manual version 4.1 (26-07-2018)
en-9
Page 10
en
Note:
INTRODUCTIONHEATRECOVERYUNIT
Maximum number of units to be connected
The number of ventilation units that can be connected to the
heat recovery unit depends on the unit’s capacity and the
effective capacity of the ventilation units that are to be connected. If in doubt, consult your Biddle advisor.
See also:
1.3.4 "Type plate" on page 8
1.3.6 CE declaration
The unit is compliant with the applicable CE standards. The
complete CE Declaration of Conformity can be found at:
www.biddle.info.
1.3.7 Modifications and changes
Without the approval of Biddle, no changes or modifications
may be made to the unit that could adversely affect safety. The
CE declaration is no longer valid if the unit has been modified
or changed in any way.
1.4Components and accessories
1.4.1 Components supplied
nThe illustration shows the unit from above, whereby
•Modules:
•Electronics module 6
•Air dampers to fresh air 7
the air exchange with the interior takes place on the
left side and the air exchange with the fresh air takes
place on the right side.
-supply fan 1
-extract air filter 2
-extract fan 3
-fresh air filter 4
-heat exchanger 5
en-10
•Pressure switch over the heat exchanger 8
•Pressure switch over the fresh air filter 9
•Fastening material for linking the modules to each other.
Page 11
HR MANUALINTRODUCTION
Warning:
Warning:
Warning:
Caution:
1.4.2 Accessories
•Recirculation module 0
•Heating/cooling module !
•Flexible manchets @
•Pressure switch over extract air filter #
•Dirty filter warning lamp (during transport, this is stored in
the electronics module)
•b-touch operating panel with Biddle control cable
•Water-side control:
-valve and drive
-temperature sensor
•Sensor for control:
-CO
•Smoke detector
sensor
2
en
1.5Safety instructions
1.4.3 Components not supplied
The following components required for installation must be
obtained from third parties:
•threaded rods M10
•mains power cable
•control cable to building management system
•drain pipe with trap for condensate drainage
1.5.1 Safety in use
w Do not put any objects into the inlets and
outlets.
Manual version 4.1 (26-07-2018)
w Do not obstruct the unit’s inlets or outlets.
w The upper surface of the unit becomes hot
during operation.
c In exceptional situations, water may run out of the
unit. Therefore, do not place anything under the unit
that could be damaged as a result.
en-11
Page 12
en
Danger:
Warning:
Caution:
Warning:
INTRODUCTIONHEATRECOVERYUNIT
1.5.2 Safety issues relating to installation, maintenance and servicing
d The unit may only be opened by qualified
technical staff.
w Perform the following actions before opening
the unit:
1. Switch the unit off,.
2. Allow the unit to cool down.
c The heat exchanger or, as the case may be, the
heating elements, can get very hot.
3. Disconnect the mains supply (switch off the isolat
swi
tch).
4. If you are going to carry out maintenance or repairs on
el
ectrical components: switch the mains supply group off.
5. For water-heated models:
s
hut off the central heating feed (if possible).
ion
w The fins of the heat exchanger are sharp.
en-12
Page 13
2.. Installation
Warning:
Warning:
w Installation activities may only be performed
w Before starting installation: read the safety
See also:
1.5"Safety instructions" on page 11
en
by technical staff qualified for this purpose.
instructions.
2.1Inspection on delivery
2.2Hanging the unit up
•Check the unit and the packaging to ensure that they have
been delivered in good order. Notify the driver and
plier immediately if any shipping damage is detected.
sup
•Ensure that all components are present. Notify supplier of
any missing parts immediately.
See also:
1.4"Components and accessories" on page 10
2.2.1 Determining the location of the unit
•Make sure that the structure from which the unit is about
to be suspended can bear at least 4 times the weight of th
unit. The un
•The distance between the floor and the unit’s undersid
ust be more than 2.7 m due to the accessibility of th
m
in
spection hatch.
it’s weight is indicated on its type plate.
the
e
e
e
Manual version 4.1 (26-07-2018)
•Make sure that the electronics and the pressure meters on
the unit’s long side remain easily accessible.
For this, keep 50 cm of space free on the side of the electronics box.
en-13
Page 14
en
Note:
Note:
INSTALLATIONHEATRECOVERYUNIT
•The plate heat exchangers are wedged between the side
panels. To be able to remove them, space must be cr
y removing a side panel.
b
Keep 30 cm of space free on the side of the unit.
eated
•In exceptional situations, water may
Mak
e sure that this cannot cause any damage or danger-
ous situations.
•For models with heating: The distance between the ceilin
an
d the top of the unit must be more than 25 mm.
•Consult the symbols on the unit for the right position:
-
-
See also:
1.3.4 "Type plate" on page 8
2.2.2 Hanging the unit up
This manual explains how to suspend the unit for each module. Depending on the situation, a different sequence of suspending the units may be selected.
Consult the overview sticker (bottom view) for the module
positions in the specific composition of your unit. If required,
tick the applicable modules.
and
and
: channels to the interior space
: channels to the outside
run out of the unit.
g
Fixing the threaded rods
Fix threaded rods M10 in accordance with the dimensions in
the table. Make sure the threaded rods are perpendicular.
nOnly fix the threaded rods for the modules in the
specific composition of your unit. See the overview
sticker.
nThe illustration shows the unit from above, whereby
the air exchange with the interior takes place on the
left side and the air exchange with the exterior takes
place on the right side.
en-14
Page 15
HR MANUALINSTALLATION
Note:
Note:
Caution:
SIZETYPEDIMENSIONS
AHR 251558 mm
HR 352158 mm
HR 452758 mm
Ball models1450 mm
Call models450 mm
xall models54 mm
nThe threaded rods must be secured, otherwise the
unit may fall down.
Hanging the unit up
en
1. Mount the electronics module on the side of the
exchanger module
2. Move the heat exchanger module into position.
3. Attach the module to the threaded rods with nuts 1.
.
heat
nMake sure the rubbers and rings 2 for damping stay
in the right place.
c Make sure that the module is hanging level in both
directions.
With type HR 45, the heat exchanger can sag
slightly. After all the modules are linked, this will be
minimalised.
Manual version 4.1 (26-07-2018)
4. To each threaded rod, apply a lock nut 3.
en-15
Page 16
en
Note:
Caution:
INSTALLATIONHEATRECOVERYUNIT
5. Move the recirculation damper module into position.
nEnsure that the wiring is on the side of the
electronics module.
6. Attach the module in the same way as the heat exchange
m
odule (steps 3 and 4).
7. Connect the modules to each other with the coupling elements at top and bottom.
c Adjust the modules individually before they are
connected to each other.
8. Connect the supply fan module and the extract air filter module M5 to each other with the coupling elements at top and bottom.
9. Connect the extract fan module and the fresh air fi
uleF7 to each other with the coupling elements
mod
top an
d bottom.
10. Repeat steps 5 to 7 for both linked assemblies.
lter
at
r
11. Only applicable to units with a heating module
-Mount the coupler elements supplied on the fan mod-
ule.
-Mount and connect the heating module in th
wa
y as for the other modules.
e same
en-16
Page 17
HR MANUALINSTALLATION
Warning:
Note:
12. Place manchets (accessory)
-Mount the clamping profiles 5. To do so, use the sup-
plied screws.
-Install the manchet 6.
-Tighten the clamping screws 7.
en
Securing the unit
1. Secure the suspension to the threaded rods by tightening
all lock nuts 3.
w The threaded rods must be secured,
otherwise the unit may fall down.
2.3Connecting the unit to the ventilation system
Using channel sections, connect the unit to the fresh air, the
inside air and to the ventilation units.
nTake into account any sensors for the controls which
have to be placed in the ducts.
See 2.10 Installing sensors for control (accessory)
Manual version 4.1 (26-07-2018)
When opting for the duct cross-section, take into account:
•The maximum allowable pressure difference fo
equired capacity. (see diagram under 2.13.5
r
vo
lume)
•The desired maximum air velocity.
r the
Calibrate air
en-17
Page 18
en
Note:
Note:
Note:
Caution:
Note:
INSTALLATIONHEATRECOVERYUNIT
nIf the duct cross-section is too small, this may lead
to reduced capacity and/or noise nuisance.
nWhen adapting to different duct diameters, use
sufficient length in order to prevent turbulence.
nIn order to prevent condensation, Biddle
recommends insulating the channel sections between
the HR unit and the fresh air.
See also:
2.13"Switching on and checking operation" on page 29
2.4Connecting the unit to the central heating and heat recovery sys-
tem
2.4.1 Connecting the water-side control (accessory)
Only for models with water heating/cooling module:
The heating/cooling module can be fitted with a water-side
control to control the temperature of the water battery.
c Biddle supplies suitable 2-way and 3-way valves as
accessories.
1. Connect the control valve and the driv
excha
nger, in accordance with the diagram. In doing so, fol-
low the instructions given in the control valve manual.
e to the heat
nEnsure that the axis of the valve is in the correct
position when connecting the drive. See the control
valve manual.
en-18
Page 19
HR MANUALINSTALLATION
Caution:
WIRINGDIAGRAM 2-WAYVALVEWIRINGDIAGRAM 3-WAYVALVE
2. Connect the drive to the valve in accordance with the wiring diagram.
en
2.5Installing condensate drain
3. Connect the drive to the building management system
another contr
2.4.2 Connecting the unit
1. Connect the unit to the central heating system.
2. Vent the heat exchangers.
3. Check the connections for leakage.
The cooling of the air can cause condensation. The unit is fitted with a drain tray(s) to catch condensation water.
1. Connect one of the connection points 1 (15 mm) of the
heat exchanger to a drainage system.
ol system.
or
c On models that are used for cooling, also connect
the connection point of the cooling module 2 (15
a drainage system.
) to
mm
Manual version 4.1 (26-07-2018)
en-19
Page 20
en
Caution:
Caution:
Note:
INSTALLATIONHEATRECOVERYUNIT
Pay attention to the following installation criteria:
-Make sure the drainage pipe has a drop of at least 1:50.
-Fit the drainage pipe with a trap with dimensions
sho
wn in the illustration. Fill this with water before the
unit is used for the first time.
A160 mm
B110 mm
c The trap must always be filled with water.
2. Cap off other connection points.
as
c If the connection points are not shut off, water may
run out of the unit.
2.6Connecting components to electronics module
1. Connect the various unit components to the electronics
mod
ule in accordance with the wiring diagram:
nSome components are optional (accessories).
-supply fan module:
- p
ower supply: X1 1 (via cable gland in box)
-
control system + input valve: 2
-extract fan module:
- p
ower supply: X1 3 (via cable gland in box)
trol system: 4
- con
-recirculation damper module : 5
-heat exchanger module :
y-pass damper: 6
- b
- p
ressure difference meter: 7
-temperature sensors: 8
-fresh air filter module: 9
en-20
See also:
1.3.3 "Symbols on the unit" on page 7
Page 21
HR MANUALINSTALLATION
Note:
Note:
2.7Connecting the unit to Modbus
2.7.1 Communication parameters
Standard values of the communication parameters for ModBus are:
COMMUNICATIONPARAMETERVALUE
Baud rate9600
DATA8
Paritynone
Stop bits1
en
The turnaround time between the unit and Modbus is 4.2
msec.
The default value for the Modbus node address is 1.
nYou can modify the parameters via b-touch
menu > Maintenance > Modbus settings or
via Modbus register addresses 460-464.
2.7.2 Wiring
A twisted-pair cable must be used for connection to the Modbus system. The cable must also have a third core for the
GND (grounding). Normally, a four-pole, twisted-pair cable is
used; one pair is used for communication and one core from
the other pair is used as the GND.
Modbus A = -
Modbus B = +
GND = ground
Manual version 4.1 (26-07-2018)
nIf there is no communication, this may be caused by
incorrectly connected wiring. Swap the A- and B+
wires.
en-21
Page 22
en
Note:
Note:
Note:
Note:
INSTALLATIONHEATRECOVERYUNIT
2.7.3 Connecting the unit to Modbus
1. Lay a cable between the Modbus system and the unit.
2. Connect the cable to the electronics module 1, in accord-
ance with the wiring diagram.
nFor a more reliable signal, it is possible to connect a
120 Ohm resistor. For this purpose, place a bridge
between positions 1 and B of terminal 52X3 on the
control circuit board in the unit.
nThe b-touch control panel is no longer necessary for
the operation. After going through the installation
guide, it can be removed. However, make sure to
keep it to be able to adjust the settings in a later
stage.
2.8Installing the b-touch control panel (accessory)
2.8.1 Special points regarding the control panel
Positioning
•You can attach the control panel to the electronics module, to the wall or to a standard junction box.
Cabling
nTake the following into account, otherwise errors
may occur:
- The length of the control cable between the contro
p
anel and the unit connected may not exceed 50 m.
- Keep control cables away from electromagnetic fi
d interference sources such as high-voltage ca
an
an
d fluorescent light starters.
- Lay control cables out straight or roll them in a bifilar coil by folding cables in half before rolling them.
As a result, the magnetic fields will cancel each othe
to an important extent.
out
l
elds
bles
r
en-22
nUse Biddle control cables only. Standard modular
t
elephone cable is NOT suitable.
Page 23
HR MANUALINSTALLATION
Caution:
2.8.2 Mounting and connecting the control panel
1. Lay the control cable.
2. Slide the control panel out of the wall holder.
3. Connect the control cable to terminal X397.
en
4. Screw the wall holder onto the electronics module, the
junction box or against the wall.
c Ensure that the wall behind the wall holder is even.
2.8.3 Connecting the b-touch panel to the unit
1. Connect the control cable to the electronics module 1
according to the wiring diagram.
Manual version 4.1 (26-07-2018)
en-23
Page 24
en
Caution:
Note:
INSTALLATIONHEATRECOVERYUNIT
2.9Connecting the temperature sensor (accessory)
Only for models with HC6 heating/cooling module
with water-side control
A temperature sensor is included with the water-side control
valve.
1. Position the temperature sensor in the channel for the
su
pply air 1.
c Insofar as is possible, position the sensor in the
centre of the channel.
Place the sensor as far as possible from the heating/
cooling module. Bear in mind the cable length of the
sensor.
2. Feed the cable of the sensor through a cable gland in
ectronics module.
el
3. Connect the sensor at positions 24 and 25 of terminal
2, in accor
dance with the wiring diagram:
nIf required, remove any existing connections to
positions 24 and 25 of terminal X2.
2.10Installing sensors for control (accessory)
For some controls, a sensor is required to provide the input:
•automatic CO
Connect the sensor that is to be used to the appropriate connection point in the electronics module.
control
2
to the
X2
en-24
Page 25
HR MANUALINSTALLATION
Note:
Caution:
Note:
2.10.1 Installing CO2 sensor
en
2.11Installing external controls
With automatic CO
building management system (BMS). If this information is not
available, a CO
1. Place the CO
accor
dance with the supplied instructions.
2. Connect the sensor to X3 (G UI 24VAC) 2 in the electronics module in accordance with the wiring diagram.
nThe CO
once per week so that the sensor can maintain a
good calibration level.
If this situation does not occur naturally, you can
make it happen by (for example) having the unit start
up an hour earlier once per week.
control, the CO2 level is supplied by the
2
sensor must be connected.
2
sensor (accessory) in extract channel 1, in
2
level in the room must be optimal at least
2
2.11.1 Special points regarding external controls
Unit input
The unit has an input signal interface. As examples, a smoke
detector or fire alarm can be connected to this.
Connection X3 1 is suitable for input signals that are externally powered.
Connection X1 2 is suitable for supplying the sensor that is
to be connected with a 230V power supply from the unit.
When using this, link connection X1 to X3 with a bridge.
c The input is designed for controls with potential-free
contacts and must not be loaded.
nWhen using the input, indicate what response must
be given to an input signal. (Via the b-touch control
panel: menu > Configuration > 60. Function of inputs
or via the building management system: register
address 337 Alarm functions)
Manual version 4.1 (26-07-2018)
en-25
Page 26
en
Caution:
Note:
INSTALLATIONHEATRECOVERYUNIT
Unit output
The unit has an output signal interface (X3). A warning lamp
for dirty filters can be connected to this.
c Keep the cable length to a maximum of 3 metres.
2.11.2 Installing smoke detector or fire alarm (accessory)
In emergencies, the unit can emit an alarm signal or even
actively deal with the problem by functioning in a special
mode. (See menu > Configuration > 60. Function of inputs)
This function can be activated by the building management system (register address 435) or by an external sensor.
If an external sensor is used:
1. Place a smoke detector or fire alarm (not supplied) at
su
itable location.
2. Without using the power supply (230V) from the unit:
-Connect the sensor to X3 1 in the electronics mod-
ule in accordance with the wiring diagram
3. Using the power supply (230V) from the unit:
-Connect the sensor to X1 2 in the electronics mod-
ule in accordance with the wiring diagram
-Place a bridge between X1 and X3
a
nWhen starting the unit, indicate what response must
be given to a signal from the sensor. (Via the b-touch
control panel: menu > Configuration > 60. Function
The b-touch control panel gives an alert if one of the filters is
dirty. If the control panel is not available or is hung out of
sight, a warning lamp must be installed.
nDuring transport, the warning lamp is stored in the
electronics module.
1. Place the warning lamp in a position where it is visible.
2. Using a two-core cable, connect the lamp to terminal X3
1 of the electronics module, in accordance with the
wiring diagram.
en
c Keep the cable length to a maximum of 3 metres.
nThe positions of the + and – contacts in the lamp
are indicated by: + 28V -
2.12Connecting the unit to the mains supply
2.12.1 Special points regarding the mains supply
w The unit must be earthed.
w The unit must be connected in accordance
with the applicable local requirements.
c For emergency situations and maintenance, it must
be possible to render the entire system electrically
dead.
Manual version 4.1 (26-07-2018)
Every unit has an isolation switch in order to render
the unit electrically dead in the event of emergency
situations and for maintenance.
en-27
Page 28
en
Note:
Warning:
Caution:
Warning:
Caution:
INSTALLATIONHEATRECOVERYUNIT
nThe circuit breaker (if modified) must be at least
type B.
To prevent rapid disconnection, type K is recommended preferably with 300 mA.
w However, do make sure to switch the mains
supply off if you are going to conduct
maintenance on or repair electrical
components.
c Do not turn the unit on and off at the power supply.
Use the control panel of the building management
system for that.
2.12.2 Connecting the unit
w Make sure that the mains supply is switched
off.
1. Bring the mains power cable to the unit.
2. Feed the cable into the electronics module.
3. Connect the cable on terminal X0 1, in accordan
the wiring diagram
.
ce with
c Do not switch on the mains supply yet.
See also:
2.12.1 "Special points regarding the mains supply" on page 27
en-28
Page 29
HR MANUALINSTALLATION
Danger:
2.13Switching on and checking operation
2.13.1 Introduction
d Make sure that all channel sections are
connected to fresh air, inside air and
ventilation units before you test the operation
of the unit.
2.13.2 Visual checking
1. Check the following attachments:
-lock nuts of the suspension;
-coupling elements between the modules;
-channel sections correctly connected and in the righ
positions.
t
en
2.
Check that the trap of the condensate drain is fill
wat
er.
3. Check the connections to the electronics module.
4. For models with heating/cooling module
Check whether:
-the heat exchanger is connected correctly.
-the temperature sensor in the supply channel is connected.
-the heating/cooling system is switched on.
2.13.3 Switching ON
1. Switch on the mains supply.
2. Set the isolation switch to 1.
3. Check that no error messages are given.
2.13.4 Checking operation
ed with
Manual version 4.1 (26-07-2018)
1. Check the operation of the pressure switch 7 over the
heat exchanger:
1. Check in menu > Maintenance > Unit control
value of th
2. Open the pressure switch.
e fourth input (1-2-3- 4) is a nil: x-x-x-0
that the
en-29
Page 30
en
Caution:
Note:
Note:
INSTALLATIONHEATRECOVERYUNIT
3. Make a bridge between the two switch contacts (NO/
NC).
c Do not allow the bridge to remain for longer than 1
minute. Check the input value (step 4) within that
time. If this takes longer, the unit must be powered
down to reset the pressure switch.
4. Check that the value of the fourth input (1-2-3-4) a one
is: x-x-x-1
5. Remove the bridge.
2. Open the indicated panels to check the
dampers and f
3. Connect a pressure difference meter over the extrac
2.
4.
Check the operation of differ
est mode. Use the table below for this purpose.
t
ans.
ent fans and dampers in each
operation of the
t fan
nThe extract fan 2 and the exhaust air damper 4 are
not visible. Check this with reference to the
pressure difference over the extract fan.
In the final test mode (7), the fan runs but there is
no pressure difference because the air damper is
closed.
en-30
nThe opening and closing of the dampers can take a
little while.
Page 31
HR MANUALINSTALLATION
Note:
MODEFANS (SPEED)VALVES
en
NO.DESCRIPTION
1unit offoffoff
2heat recovery
speed 1
3heat recovery
speed 2
4heat recovery
speed 3
5recirculation1off
6night cooling22
7exhaust air
damper closed
1
SUPPLY
11
22
33
off1
2
EXTRACT
(no pressure
difference)
(pressure difference)
(pressure difference)
(pressure difference)
(no pressure
difference)
(pressure difference)
(CAUTION: no pressure
difference)
3
FRESHAIR
closedclosed
openopen
closedclosed
openopen
closedclosed
4
EXHAUSTAIR
(no pressure
difference)
(pressure difference)
(no pressure
difference)
(pressure difference)
(no pressure
difference)
5
RECIRCU-
LATION
openclosed
closedclosed
openclosed
closedopen
openclosed
6
BY-PASS
Manual version 4.1 (26-07-2018)
5. Close the inspection panels.
nLeave the pressure difference meter on the extract
fan.
2.13.5 Calibrate air volume
Set the three speeds for each airflow.
en-31
Page 32
en
INSTALLATIONHEATRECOVERYUNIT
en-32
Page 33
HR MANUALINSTALLATION
Caution:
Note:
Note:
Note:
Note:
Calibrate the extract fan:
en
1. Set the unit to ‘manual’ and to ventilate
screen of the b-touch control panel.
2. In the b-touch control panel, open the fu
menu
> Maintenance > Calibrate air volume.
3. Enter the PIN code and press .
4. Calibrate the extract fan:
K via the home
nction
c Adjust the highest speed (3) maximally to the
capacity of the unit (2500/3500/4500 m3/h).
For cooling with a cooling module use 500 m
3
(2000/3000 m
/h).
3
/h less
nUse the pressure difference meter over the extract
fan 5 .
nUse the chart to establish which pressure difference
gives the required flow rate.
Make sure to use the curve for the unit type that is
being used. (See type plate.)
nAlways set all three settings. Even if you only want to
change one setting.
-Set all and any connected ventilation units to the set-
ting appropriate to setting 1 (low) of the HR unit.
-Set the desired flow rate for setting 1 (low) by adjust-
ing the percentage until the appropriate pressure difference is reached.
-Store by pressing .
-In the same way, set the desired flow rate for setting
(medium) and setting 3
-Check if all speeds are set correctly.
(high).
2
nNote the flow that is used for fan speed 3 of the
extract fan. This will be used later to calibrate the
pressure switch.
Manual version 4.1 (26-07-2018)
en-33
Page 34
en
Note:
Note:
INSTALLATIONHEATRECOVERYUNIT
Calibrate the supply fan:
1. Connect the pressure difference meter to the pressure
measurement points 1 of the supply fan .
2. Calibrate the supply fan. Use the same method for this
described for the extract fan.
2.13.6 Setting the pressure switch
The unit is fitted with freezing protection for the plate heat
exchangers. If ice formation is identified, the unit will defrost
the exchangers by blowing warm indoor air over the exchangers. The airflow from outside in will be turned off.
This function will be active if the pressure difference across
the plate heat exchanger becomes too great.
as
nThe pressure difference must be measured in fan
speed 3 (high).
At outside temperatures that form the risk of freezing, the unit will carry out a check by measuring the
pressure difference at fan speed 3.
Adjust pressure switch
Adjust the pressure switch 7 to fan speed 3 (high):
1. Use the flow rate that is used for fan speed 3 of the
extract fan (see 2.13.5 Calibrate air volume).
2. Determine the corresponding pressure difference for
pr
essure switch. To do so, use the graphic.
nUse the curve for the unit type that is being used.
(See type plate.)
the
en-34
Page 35
HR MANUALINSTALLATION
en
Manual version 4.1 (26-07-2018)
en-35
Page 36
en
Note:
INSTALLATIONHEATRECOVERYUNIT
3. Set the pressure switch 7 to the pressure difference as
specified in step 2.
4. Check whether the frost protection is not unnecessarily
active:
1. Set the unit to fan speed 3.
nIf the unit was at a different speed, it will take
approximately two minutes before the valve
positions are adjusted.
2. Check in menu > Maintenance > Unit control that the
value of the fourth input (1-2-3- 4) is a nil: x-x-x-0
2.13.7 Checking temperature sensors
The unit contains temperature sensors.
1. Check in menu > Maintenance > Unit control that the sensors measure realistic values (Tfresh-Tsupply, Textract-Texhaust)
2.13.8 Checking the CO
If a CO
1. Check in menu > Maintenance > Unit control that the sen-
2.13.9 Checking the heating / c
1. Check that the heating/cooling module responds to the
con-nected heating/cooling system.
2. Limit the minimum temperature for cooling to prevent
condensation on the outside of the device and channels.
(menu > Settings > 7. Minimum air temperature cooling)
sensor is used:
2
sor is measuring a realistic value (Analog in)
sensor (accessory)
2
ooling (accessory)
en-36
2.13.10 Finishing the unit
1. Close all inspection hatches.
2. Place the b-touch control panel in the holder.
Page 37
3.. Operation via b-touch
Note:
The unit can be operated via the b-touch control panel and via
Modbus. This chapter describes operation with the b-touch
control panel
nSome settings and functions can only be used via the
b-touch control panel or, conversely, only via Modbus.
3.1Control panel
en
The b-touch control panel is equipped with a touchscreen
(touch screen) with which all the functions can be set:
•Turning the unit ON and OFF;
•Adjusting the strength of the unit;
•Switching the heating ON and OFF;
•Enter settings to adapt the function of the unit to your situation.
3.1.1 Settings
Manual version 4.1 (26-07-2018)
Select to save the settings and return to the previous
screen.
Select to return to the previous screen without saving the
changes.
en-37
Page 38
en
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
3.2The Home screen
On the home screen, information can be read and entered by
touching the symbols:
•1 on/off
•2 main menu
•3 extra information about the current point in the con-
trol panel.
•4 manual or automatic control
•5 temperature
•6 fan strength
•7 recirculation/ventilation
•8 brief information on the operation of the unit
3.2.1 Symbols
The symbol
The symbol ‘i’ indicates that there is currently a tip to be read.
Touch the symbol in order to read the tip.
3.2.2 Turning the unit ON and OFF
You can switch the unit ON and OFF manually, using the control panel.
•Touch on/off in order to turn the unit ON or OFF.
If the unit is on, the screen will become darker after some
time, in order to save energy. When the screen is touched, it
lights up again. This function cannot be deactivated.
If the unit is switched off, the screen will go black after some
time. Touch the screen to activate it again.
@ indicates that the timer is switched on.
en-38
The unit can also be switched ON and OFF in other ways:
•Using external controls (see function 60. Fu
inputs).
•
Via the internal timer or via an external releas
it.
the un
In these cases, the ON/OFF button can be hidden via Con-
figuration > 21. User interface options > Display on/o
bu
tton.
nction of
e signal on
ff
Page 39
HR MANUALOPERATIONVIAB-TOUCH
Note:
Warning:
Note:
3.2.3 Automatic or manual control
The unit has an automatic mode and a manual mode. Select
the desired setting by touching the upper part of the symbol.
You can restrict the user’s choice via menu > Settings > 1.
Select modes.
Manual
In manual mode, the unit operates in a variety of fan settings
(which can be manually selected).
Automatic
In automatic mode, the fan setting is automatically adjusted to
the CO
3.2.4 Regulating the strength
level.
2
en
In automatic mode, the strength of the airflow is controlled
automatically.
In the manual mode, the strength can be set manually (3 settings).
nFor minimum energy consumption, Biddle
recommends selecting the lowest strength at which
the desired air quality is achieved.
3.2.5 Errors
The symbol ä indicates that there is an error. The error message is displayed alongside.
•Touch this message for further information on the erro
or instructions as to how to react.
and f
r
w Some errors may cause damage or danger to
persons if they are disregarded. If ä is
displayed, follow the instructions on the
control panel as regards how to act.
Manual version 4.1 (26-07-2018)
nThe symbol ä and the error message remain
displayed as long as the error has not been
remedied.
en-39
Page 40
en
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
If an error has remedied itself, a corresponding message will
be displayed. Touch this message to display the Error history
and to read out the errors and the times of their occurrence.
This list can also be read out via Maintenance > Error history.
3.3Main menu
To u c h menu to open the Main menu.
•Touch home in order to return to the Home screen.
•You can use the arrows to browse through the list.
If the control panel is not operated for some time, it returns
automatically to the Home screen without saving the changes.
Lock screenSelect to prevent unauthorised access. The
on the screen.
Unlocking
Touch the screen for 5 seconds to unlock it.
Switch temperature control on and offOnly for units with HC6 module with water control or using free
(night) cooling.
The unit’s temperature control can be switched on and off
manually.
Switching the temperature controloff disables the room temperature control and any Heating on output functions.
This function can be deactivated via setting 21 in the configuration menu.
If the heating has been switched on via this function, it may
occur that the automatic control switches the heating off
again. This may be due to an external signal, for example, or
because the desired temperature has been reached.
# symbol appears
en-40
The heating can also be switched off by the control itself:
•by an external signal at the input of the un
nu > Configuration > 60. Function of inputs, settin
me
Heating off;
it, see
g
Page 41
HR MANUALOPERATIONVIAB-TOUCH
FilterDirty filters make the unit less effective. It is therefore neces-
sary to clean or replace the filters at regular intervals. The
contamination of filters is measured with the optional filter
sensor or calculated on the basis of the lifespan.
The lifespan of the filter is calculated on the basis of the usage
of the unit if no filter sensor has been installed. You can adjust
this by setting the maximum lifespan of the filter.
When the filters are contaminated or when the maximum
lifespan has elapsed, a message appears on the Home screen.
Also, a signal can be generated on one of the outputs.
New filters are available from Biddle.
Cleaning the displayThe screen can be cleaned using a damp, soft cloth.
en
Use this function to disable the touch screen for 20 seconds in
order to be able to clean it.
TimerThe b-touch control panel has a week timer. You can set two
start and stop times for each day of the week. The unit is on
between the start time and the stop time. The second start
and stop times are optional. When the ON/OFF button is displayed on the screen, the unit can also be switched ON or
OFF manually. From the next switching moment, the unit follows the timer again. When the timer is switched on, the sym-
@ is displayed on the Home screen.
bol
3.4Preferences
PreferencesThe menu Preferences allows you to make settings for the use
of the control panel.
Set languageThe control panel offers a choice of languages. Choose your
preferred language from the list.
Set date and timeThe date and time are necessary for the timer function, the
lifespan of the filter and for tracking usage statistics regarding
the unit.
The automatic summer time function switches the clock to
summer or winter time in accordance with the applicable
European rules. If you do not use this function, you can switch
to summer time manually. The clock is then set one hour forward.
Manual version 4.1 (26-07-2018)
en-41
Page 42
en
Note:
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
Celsius / FahrenheitChoose between a temperature display in degrees Celsius or
degrees Fahrenheit.
Display brightnessSet the brightness of the screen to your personal preferences
or to the specific situation.
Show tipsThe control panel can show tips about the usage of the unit.
The display of these tips can be enabled or disabled.
3.5Settings
The Settings menu allows you to enter settings which influence the day-to-day use of the unit.
Sel
1.
ect modesThe control panel has an automatic mode and a manual mode.
With the function Select modes, you can set which of these
modes can be selected in the HOME screen.
5. Room temperatureHer
nimum air temperatureFor units with water heating module:
6. Mi
nimum air temperature, coolingIn order to increase the level of comfort, a minimum dis-
7. Mi
e, set the temperature which is to be used by default as
the room temperature when starting up the unit.
The desired room temperature can temporarily be adjusted
on the home screen until the next start-up moment.
Set the minimum difference between the room temperature
(extract air) and the discharge temperature (supply air).
This difference can be increased for more comfort. A smaller
difference saves energy.
charge temperature for cooling can be set.
8. Night temperatureThe night temperatur
When the room temperature drops below this set value, the
unit will start working in order to keep the room at the night
temperature.
nThis function only operates when the heating is
switched on.
en-42
e is used when the unit is switched off.
Page 43
HR MANUALOPERATIONVIAB-TOUCH
Warning:
w Be aware that the airflow of the unit can set
objects in motion. This might set off an alarm
system in the building at night time.
ibrationAdjust the temperature reading if this deviates from the actual
9. Cal
temperature.
3.6Configuration
The menu Configuration allows you to enter settings in order
to adjust the operation of the unit to the room and the system. Usually, this menu is used only for installation, maintenance and service purposes.
en
20. A
ccess controlPin code
Access to the entire control panel or to the menu only can be
protected with a four-digit PIN code.
The default PIN code is 0000.
Access level
The control panel can be safeguarded at different access levels.
ser interface optionsDisplay on/off button
21. U
The unit can be switched ON and OFF manually. This can also
be done via the internal timer or via an external release signal
on the unit. In this case you can disable the manual on/off
option. The on/off button is then not displayed on the Home
screen.
Temperature display
By default, the room temperature (exhaust air) is displayed.
With this function, you can select another temperature to display or switch off the temperature display.
Manual version 4.1 (26-07-2018)
If the temperature display is switched off, there is no temperature control.
Temperature control OFF option
Use this function to enable or disable the option for the user
to switch the temperature controlON/OFF manually.
en-43
Page 44
en
Note:
Note:
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
Error display
Some error messages may be caused by external factors such
as the central heating system and do not necessarily have an
influence on the functioning of the unit.
Use this function to suppress these messages. Safety-related
warnings will always be displayed.
31. Auto: fan spe
ed
nThese settings only have influence on usage in the
automatic mode.
Maximum fan speed
To restrict the noise level, the maximum fan speed can be limited.
Use of this function can reduce comfort.
Minimum fan speed
In order to increase the level of comfort, a minimum fan speed
can be set per operation:
nSet a lower value than that for the maximum fan
speed. In the event of conflicting values, the set
maximum fan speed takes priority.
•Unheated
•Heating (dependent on unit type)
ooling
•C
33. Boost fun
en-44
Y
ou can set a post-rotation time for the fan. Here, set the
period of time it should take for the fan to decelerate from
maximum speed to standstill.
ctionOnly applicable to units with a heating module.
If there is a great difference between the desired and the
actual room temperatures, the fan speed can be increased in
order to reach the desired temperature more quickly.
Set the temperature difference at which the boost function
should be activated and the fan’s increase in speed.
Page 45
HR MANUALOPERATIONVIAB-TOUCH
Note:
Note:
35. Ventilation settingsVentilation control
Only applicable to units with a recirculation module.
The relationship between ventilation air and recirculated air
can be determined in various ways:
en
•Manual selection: Manual switching between ventilatio
ecirculation.
r
•Valve regulation: Manual regula
v
entilation valve.
•Automatic selection: The quantity of ventilation air is
determined by a CO2 sensor. Manual switching between
ventilation and recirculation is possible.
•Fully automatic: The quantity of ventilation air is alwa
determined b
Maximum position of ventilation valve
Only applicable to units with a recirculation module.
The maximum opening percentage of the ventilation valve can
be limited.
Minimum fan speed during ventilation
Set the minimum percentage of the fan speed for ventilation.
Maximum fan speed during ventilation
y a CO2 sensor.
tion of the position of the
n and
ys
Set the maximum percentage of the fan speed for ventilation.
46. Maximum discharge temperatureThe
mum of 50°C. Possibly set a lower value in order to save
energy.
47. Overheat protectionI
f the actual room temperature becomes higher than the preset room temperature, the heating can be switched off in
order to prevent the room from becoming too warm.
Set the temperature above which the heating must be disabled.
nThis function can only be used if the unit is set to
nIf this function is activated, then function 6. Minimum
controller limits the discharge temperature to a maxi-
automatic.
air temperature is ignored.
Manual version 4.1 (26-07-2018)
en-45
Page 46
en
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
60. Function of inputsThe unit has an input (terminal block X1) which can be used
to enable a function to be controlled by an external accessory
such as a smoke or fire alarm.
Values for input
ALUEOPTIONDESCRIPTION
V
0No functionThe input has no function.
1Unit off locally - NOThe unit is switched OFF when the contact is closed. (This only works in
units to which the input signal is directly connected (locally).)
51Unit off locally - NCThe unit is switched OFF when the contact is open. (This only works in
units to which the input signal is directly connected (locally).)
21Switch all units onAll units are switched ON when the contact is closed.
71All units offAll units are switched OFF when the contact is closed.
6Heating offThe heating is switched OFF when the contact is closed.
56Heating on
(dependent on software
version)
7change-over signal, cool-
ing
57change-over signal, heat-
ing
9Release - NOThe user is allowed to switch the unit on and off when the contact is
59Release - NCThe user is allowed to switch the unit on and off when the contact is open.
10Dirty filter – NODisplays a “dirty filter” warning if the contact is closed for longer than 60
60Dirty filter – NCDisplays a “dirty filter” warning if the contact is open for longer than 60
30Smoke extractionWhen the contact is closed:
31Fire modeWhen the contact is closed:
41Fire alarmWhen the contact is closed:
40Smoke alarmWhen the contact is closed:
Heating is available when the contact is closed.
The unit switches from heating to cooling when the contact is closed.
In the event of conflicts between different inputs, cooling has priority.
The unit switches from cooling to heating when the contact is closed.
In the event of conflicts between different inputs, cooling has priority.
closed.
seconds.
seconds.
•air is extracted.
• no air is supplied.
• an alarm signal (smoke) is sent to the building management system.
• the unit is switched off.
• any air dampers are closed.
• an alarm signal (fire) is sent to the building management system.
• an alarm signal (fire) is sent to the building management system.
• an alarm signal (smoke) is sent to the building management system.
en-46
Page 47
HR MANUALOPERATIONVIAB-TOUCH
Note:
Note:
Note:
Release delay input 1
When you use input 1, you can make the effect of an input signal persist for some time after the signal has been given
(‘release delay’).
en
62. A
utomatic CO2 controlOnly with use of automatic CO
The unit can automatically adjust the fan speed and, if
required, the recirculation damper to the CO
The default values for the CO
menu.
Fan speeds with stepped controls
LEVELFAN
CO
2
< 1without recirculation module0 (off)
with recirculation module1 (recirculation)
< 21 (ventilation)
< 32 (ventilation)
> 3
LEVELDEFAULT
CO
2
1800 ppm
21000 ppm
31200 ppm
control
2
level.
2
levels can be adjusted in this
2
SPEED
3 (ventilation)
VALUE
nThe current CO
nIf no CO
nIn the building management system (BMS) you can
65.
Control panel inputNot applicable.
Manual version 4.1 (26-07-2018)
level must be measured via the
2
building management system (BMS) or via a sensor
connected to the unit.
sensor is detected, the device will operate
2
in fan setting 1 (ventilation).
indicate (register address 350) whether the speed is
to operate in a continuously variable manner or at
set speeds. The curve for continuously variable
operation is also based on the three CO
be indicated.
levels to
2
en-47
Page 48
en
Note:
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
3.7Maintenance
The Maintenance menu contains information on the use of the
unit and offers a number of functions which are necessary for
remedying errors.
StatusThe status screen displays general information about the
installation and specific information per group and per unit
connected.
Current errorsGives an overview of current errors. The error messages can
also be deleted here.
Error historyGives an overview of the errors which have occurred.
Capacity testUse this function to test the capacity of the unit and your
heating installation.
The unit will run for 120 minutes at the highest fan speed and
with the highest heating capacity. You can check the discharge
temperature and the heating capacity. The discharge temperature is limited to 50°C.
For units with water heating:
If the heating capacity is too low, check the supply and return
water temperatures and the water flow.
Valve checkUse this function to test the operation of the water valve:
1. Set the opening percentage of the valve to 0%;
2. Press start. The fans will start rotating at the highest speed;
3. Check whether the discharged air is cold;
nIt may take some time before the valve reaches the
adjusted opening percentage.
en-48
4. Repeat steps 1 and 2 for the percentages 50% and 100
w
ell. In doing so, check whether the discharged air gets
warmer per step.
% as
Page 49
HR MANUALOPERATIONVIAB-TOUCH
InstallationThis installation guide leads you through the most frequently
required settings.
The installation guide is started up automatically during the
first start-up of the unit or after the resetting of the factory
configuration.
Unit codeFor entering the unit code after replacement of the control
circuit board in a unit.
Calibrate air volumeUse this function to set the fan speeds.
In 2.13.5Calibrate air volume a description is provided of how
you can calibrate the fans.
en
Unit checkUse this function to check the operation of the unit.
Run through the various modes in this function to check the
operation of the dampers and fans, as indicated in 2.13.4
Checking operation.
Modbus settingsThe settings for Modbus can be adjusted:
•Baud rate
•Communication:
-DATA bits
-Parity (N = none, E = even, O = odd)
-Stop bits
•Modbus node address (0 = use code dip switches of
ol circuit board)
contr
Default settingsRestores the default factory settings of the setup menu. The
settings entered in the configuration menu are retained.
the
Manual version 4.1 (26-07-2018)
en-49
Page 50
en
Note:
Caution:
Warning:
OPERATIONVIAB-TOUCHHEATRECOVERYUNIT
Factory configurationRestores the standard factory configuration. All settings are
then lost.
nThe installation guide will be restarted.
Reset systemThe control panel searches for connection with the attached
units again. Use this function when remedying errors and during connection or disconnection of units.
3.8USB
The control panel is equipped with a USB port to which only a
USB flash drive can be connected. This is used for:
•updating the software
•importing and exporting settings
•exporting usage data
This menu is automatically activated when a USB flash drive is
connected. The menu is closed again when the USB flash drive
is removed.
c Do not remove the USB flash drive during the
updating or during the importing or exporting of
data. This can take several minutes.
w Connection of other electronic devices to the
USB port can cause serious damage to the
control panel or to other electronic
components.
Software updateBiddle is working continuously on improving its products and
recommends that you update the software of the control
panel when updates become available. Consult www.biddle.info/software to see if updates are available.
en-50
•The installed version of the software can be read out from
Maintenance > Status.
•Download the latest version of the software via Biddle’
bsite.
we
See also:7.8 Updating the software
s
Page 51
HR MANUALOPERATIONVIAB-TOUCH
Note:
Note:
Upload logoIt is possible to use your own logo or image as background for
the display.
Requirements for the image:
•Windows bitmap;
•Filename: logo.bmp;
•Dimensions: maximum 240 x 320 pixels;
•Colour depth: 8-bit grayscale or 24-bit colour.
nUploading your own logo replaces the standard
Biddle logo.
Export/import settingsFor copying settings between control panels.
en
See also: 7.7 Copying the settings
Exporting system infoExport the file ‘system_info’ for an overview of all connection
control circuit boards and control panels with corresponding
software versions.
Export log...The Export log functions write data concerning the operation
of the unit to the USB flash drive. These files can then be analysed on a computer.
The files contain the following data:
•log_func: Data concerning the operation of the unit.
•log_error: Error report history.
•log_user: User settings history.
•log_stat: not in use.
•system_info: Overview of connected control circuit boar
and con
trol panels.
ds
Manual version 4.1 (26-07-2018)
nThe process of exporting can take several minutes.
Repeat if 100% is not achieved.
en-51
Page 52
en
Note:
Caution:
Note:
Note:
Note:
4.. Operation via Modbus
The unit can be operated via the b-touch control panel and via
Modbus. This chapter describes the operation via Modbus.
nSome settings and functions can only be used via the
b-touch control panel or, conversely, only via Modbus.
4.1Frequently used register addresses
This paragraph describes frequently-used functions and their
corresponding register addresses.
c Do not adjust other register addresses without
consulting Biddle.
nIt may occur that the system applied uses a value of
1 higher than the register addresses given here. In
that case, use 101 for register address 100, for
example.
nFor functions that are also in the b-touch panel, the
corresponding menu parameter is shown between
brackets after the register address.
Menu parameters 0 - 1 are functions in the home
screen.
en-52
nSettings in the b-touch control panel can cause
Modbus settings to be ignored. In register addresses
410 to 419 inclusive, it can be specified whether
settings may be altered via the b-touch.
Register addresses 410 - 419 are related to 400 409 and 420 - 429 respectively.
Page 53
HR MANUALOPERATIONVIA MODBUS
Note:
REGISTERADDRESSDESCRIPTION
400 - 409roUser functions: Current status
410 - 419rwUser functions: Changes via the b-
touch control panel:
0 = permitted (default)
1 = not permitted
420 - 429rwUser functions: Modbus setpoint
4.1.1 General Operation
en
REGISTER
ADDRESS
420 (0.1)Turning the unit ON and OFFrw-021
425 (0.6)Automatic or manual controlrw-011
*ro = read only (read only)
*rw = read & write (read and write)
420 (0.1) Turning the unit ON and OFF
VALUEOPTIONDESCRIPTION
0offSwitching the unit OFF.
1onSwitching the unit ON (normal operation).
425 (0.6) Automatic or manual controlThe unit has an automatic mode and a manual mode. When
DESCRIPTIONRO
• Special functions (register address 337) are still working.
the unit is switched on, it will begin operating in the automatic mode.
/RW* UNITMINIMUMMAXIMUMDEFAULT
VALUEOPTIONDESCRIPTION
0manualThe unit is operating in various settings (can be switched
manually).
1automaticThe unit automatically operates at the correct fan and
damper settings.
nVia register address 275 (1), it can be specified which
settings are allowed.
Manual version 4.1 (26-07-2018)
en-53
Page 54
en
Note:
OPERATIONVIA MODBUSHEATRECOVERYUNIT
Register address 275 (1)
VALUEDESCRIPTION
1allowed: manual
2allowed: automatic
3 (default)allowed: manual, automatic
4.1.2 Manual operation
REGISTER
ADDRESS
422 (0.3)Manual setting of the strengthrw%010050
*ro = read only (read only)
*rw = read & write (read and write)
REGISTER
ADDRESS
275 (1)Select modes1 = allowed: manual
425 (0.6)Automatic or manual control0 = manual
422 (0.3) Manual setting of the strengthIn the manual mode, the strength can be set manually.
DESCRIPTIONRO
DESCRIPTIONVALUE
/RW* UNITMINIMUMMAXIMUMDEFAULT
The unit can only be controlled manually if the functions below
have been set as follows:
3 = allowed: manual, automatic
VALUEFANSPEED
00%
1 - 4935%
50 - 7965%
80 - 10095%
en-54
nFor minimum energy consumption, Biddle
recommends selecting the lowest strength at which
the desired air quality is achieved.
4.1.3 Automatic operation
The unit can only be controlled automatically if the functions
below have been set as follows:
Page 55
HR MANUALOPERATIONVIA MODBUS
Note:
en
REGISTER
ADDRESS
DESCRIPTIONVALUE
275 (1)Select modes2 = allowed: automatic
3 = allowed: manual, automatic
425 (0.6)Automatic or manual control1 = automatic
4.1.4 Automatic CO2 control
The unit automatically adjusts the fan speed (and any recirculation damper) to the CO
The CO
level is supplied by the building management system
2
(BMS) or, if this information is not available, by a CO
(accessory) on X377 (via connection X3).
nIf no CO
sensor is detected, the device will operate
2
in fan setting 1 (ventilation).
Fan speeds with stepped controls
LEVELFAN
CO
2
< 1without recirculation module0 (off)
with recirculation module1 (recirculation)
< 21 (ventilation)
< 32 (ventilation)
> 3
level.
2
sensor
2
SPEED
3 (ventilation)
REGISTER
ADDRESS
DESCRIPTIONRO
/RW* UNITMINIMUMMAXIMUMDEFAULT
351 (62.2)CO2level 1rwppm2002000800
352 (62.3)CO
353 (62.4)CO
432CO
level 2rwppm20020001000
2
level 3rwppm20020001200
2
level from BMSrwppm020000
2
151Input voltage, analogue input X377ro0.01 V---
*ro = read only (read only)
*rw = read & write (read and write)
Manual version 4.1 (26-07-2018)
en-55
Page 56
en
Note:
OPERATIONVIA MODBUSHEATRECOVERYUNIT
4.1.5 Ventilation/Recirculation/Night cooling
REGISTER
ADDRESS
426Mode: ventilation/recirculation/
*ro = read only (read only)
*rw = read & write (read and write)
426 Mode: ventilation/recirculation/night
cooling
DESCRIPTIONRO
rw-0100
night cooling
The unit is designed to use heat recovery on ventilation air.
Depending on the type and the settings, the unit can also
recirculate or supply ventilation air without heat recovery
from extracted air (night cooling).
/RW* UNITMINIMUMMAXIMUMDEFAULT
nRegister address 301 must have the value 1 (default)
UNIT
VALUEDESCRIPTION
0recirculation
(only functional in the case of units
with a recirculation module and in
manual control)
2ventilation
(only functional in manual control)
10ventilation with night coolingventilation
FUNCTIONON
(DAYTIME)
recirculation
(no heat recovery)
ventilation
(heat recovery from the
extracted air)
(heat recovery from the
extracted air)
(100% recirculation/ventilation).
UNITFUNCTIONOFF
(NIGHTTIME)
off
off
ventilation (fan speed 2)
(cooling with fresh air via bypass, no heat recovery)
en-56
4.1.6 Alarm functions
In emergencies, the unit can emit an alarm signal or even
actively deal with the problem by functioning in a special
mode.
This special operation replaces the normal operation of the
unit (during the day and at night time) until the signal is no
longer active (435 is 0 again).
Page 57
HR MANUALOPERATIONVIA MODBUS
en
REGISTER
ADDRESS
DESCRIPTIONRO
337Alarm functions
/RW* UNITMINIMUMMAXIMUMDEFAULT
rw-0410
(activated by input 1 (i1) or by register address 435)
435Activate alarm functions (register
rw-010
address 337)
0 = inactive
1 = active
*ro = read only (read only)
*rw = read & write (read and write)
337 Alarm functions
VALUEOPTIONDESCRIPTION
30Smoke extractionWhen the contact is closed:
• air is extracted (maximum fan speed).
• no air is supplied.
• an alarm signal (smoke) is sent to the building management system.
31Fire modeWhen the contact is closed:
• the unit is switched off.
• any air dampers are closed.
• an alarm signal (fire) is sent to the building ma
system.
40Smoke alarmWhen the contact is closed:
• an alarm signal (smoke) is sent to the building management system.
41Fire alarmWhen the contact is closed:
• an alarm signal (fire) is sent to the building management
system.
nagement
4.1.7 Reading out current operation
The current operation of the unit can be read out in re
gister
address 221.
REGISTER
ADDRESS
DESCRIPTIONRO
/RW* UNITMINIMUMMAXIMUMDEFAULT
221Current mode operationro-0151-
*ro = read only (read only)
*rw = read & write (read and write)
Manual version 4.1 (26-07-2018)
en-57
Page 58
en
OPERATIONVIA MODBUSHEATRECOVERYUNIT
221 Current mode operation
VALUEOPTION
general
01unit off
05test function
ventilation
20ventilation, auto - speed 0
11ventilation, auto - speed 1
12ventilation, auto - speed 2
13ventilation, auto - speed 3
14ventilation, auto - boost
15ventilation, manual - speed 0
16ventilation, manual - speed 1
17ventilation, manual - speed 2
18ventilation, manual - speed 3
19ventilation, manual - boost
recirculation
20recirculation, auto - speed 0
21recirculation, auto - speed 1
22recirculation, auto - speed 2
23recirculation, auto - speed 3
25recirculation, manual - speed 0
26recirculation, manual - speed 1
27recirculation, manual - speed 2
28recirculation, manual - speed 3
special operation
31night cooling
41fire mode (external signal)
42smoke extraction
51defrosting
4.2All register addresses
en-58
An extensive list of register addresses for using ModBus is
available at: www.biddle.info.
Page 59
5.. Errors
Danger:
Warning:
en
d All work on the inside of the unit may only be
carried out by personnel who are technically
qualified to do so.
w Before you begin: read the safety instructions.
See also:
1.5"Safety instructions" on page 11
5.1Resolving simple problems
If you suspect an error, first try to resolve the problem using
the table below. You do not need to be an expert for this.
If this fails to resolve the problem, there may be a fault; in that
case, alert the installer.
ROBLEMPROBABLECAUSEWHATTODO
P
The unit does not
work.
The unit does not
respond to changes in
the b-touch control
panel.
The unit only moves
air from the inside to
the outside.
The unit functions differently from expectations.
The unit is not circulating enough air.
The unit has not been switched onTurn the unit on
The unit has no power supply.Check the mains supply:
•isolation switch;
• unit has power.
The unit is running in test mode.Stop the test mode: in
menu > Maintenance > Reset system click
stop .
The unit is running in defrost mode.When the pressure different across the
plate heat exchanger is once again correct,
defrost mode will remain active for
another ten minutes. The unit will then
run in the last activated mode.
The unit is operating in a special mode.• Check which mode the unit is operat-
ing in. (Register address 221 or b-touch menu ...)
One of the inlet sections and/or the connected ventilation units is blocked.
Remove obstacles to the inlet and discharge section.
Manual version 4.1 (26-07-2018)
en-59
Page 60
en
ERRORSHEATRECOVERYUNIT
P
ROBLEMPROBABLECAUSEWHATTODO
Only for models with
heating: The unit is not
heating or not heating
sufficiently.
The maximum discharge temperature is
limited.
Only for water-heated models: The central
heating system is not working properly.
See also:
2.12"Connecting the unit to the mains supply" on page 27
Check the value at 46. Maximum dis-
charge temperature
Check the central heating system.
• Check the connections.
• Check the operation.
• Check the capacity.
5.2Remedying errors that are accompanied by an error message
ERRORMESSAGEPROBABLECAUSEWHATTODO
The malfunction lamp is lit up.The filter is letting insufficient air
through, due to contamination.
See also:
6.2"Replacing the filter" on page 64
Check the filter for contamination.
Clean or replace it if necessary.
You can adjust the pressure difference meter over the filter to make
it emit a dirty filter signal either
sooner or later.
5.3Reading out errors
Errors are recorded with a binary code in two registers.
In the log file “log_error.csv”, which can be read out with a
USB flash drive, the errors are indicated with a numeric value.
5.4Error codes registers
Error codes register 216/ErrorFlags[0]
LOG_ERROR.CSV
BITVALUEVALUECODEDESCRIPTION
383E7Fan error
en-60
Page 61
HR MANUALERRORS
Note:
Note:
Error codes register 217/ErrorFlags[1]
RRORFLAGS[1];
E
MODBUS 217
BITVALUEVALUECODEDESCRIPTION
0116F1Filters must be replaced
14819229F17Faulty CO
LOGERROR.CSV
sensor
2
5.5Error messages on the control panel
For models with b-touch control panel
Some errors are displayed with a symbol on the home
screen of the b-touch panel.
en
nWhen the error message is touched, the screen
displays an explanation, together with a list of the
actions to be taken.
nThe message will disappear from the Home screen
when the error has been remedied.
CODEPROBABLECAUSEWHATTODO
E7Fan error1. Check the fans. If one or more fans do not work, please
check:
-the fan wiring;
-the connections on the electronics module;
-the transformer fuse;
-the transformer itself.
2. If these are in order, then replace the fan.
F1Dirty FilterReplace the filters.
F17With automatic CO
The CO
not working.
sensor in the inlet duct is
2
control:
2
1. Check the sensor’s wiring and connection
X377).
2. If these are in order, then replace the sensor.
(connector
Manual version 4.1 (26-07-2018)
en-61
Page 62
en
ERRORSHEATRECOVERYUNIT
5.6Remedying errors that are not accompanied by an error mes-
sage
If you suspect an error but no error message is displayed:
1. Referring to the preceding sections, check whether yo
can easi
2. Try to resolve the problem using the table below. Technical expertise is required for this.
P
ROBLEMPROBABLECAUSEWHATTODO
The unit does not respond
to the building management
system.
The unit functions differently
from expectations.
The unit is not circulating
enough air.
The building management system is not
operating correctly.
The unit has no communication with
the building management system.
The unit is operating in a special mode.• Check which mode the unit
One or more modules are not properly
connected.
The filter(s) is/are dirty.Clean or replace filter(s).
The fan settings are not properly calibrated.
The duct system is giving too much
resistance.
An air damper is not working properly.Check the operation of the damper
The connected ventilation unit is not
working properly.
ly resolve the problem.
Check the building management system.
• Check the building man
system.
Check the wiring.
•
operating in.
If necessary, set the unit for input
•
to onl
adjusting
addr
ess 337 or b-touch menu 60.
Function of inputs).
heck the connections of the
• C
les
modu
• Check the operation of the
(See 2.13.4Checkin
Calibrate the fan settings properly. see
2.13.5Calibrate air volume
Resolve problems in the duct system:
• ducts too narrow
• bends too sharp
• blockages
(See 2.13.4Checking operation).
Check the operation of the connected
units.
y emit a signal wi
the operation (r
g operation
u
agement
is
1
thout
egister
unit.
en-62
Page 63
HR MANUALERRORS
ROBLEMPROBABLECAUSEWHATTODO
P
With automatic CO
control:
2
The unit functions differently
from expectations.
The CO
expected.
CO
system for the automatic control.
settings are different than
2
is not designated as the control
2
Check the CO2 settings (register
addresses 351/352/353 of b-touch menu
62. Automati
c CO2 control)
Restore the factory configuration
(menu > Maintenance > Factory config-
uration)
The CO
sensor is not recognised.Check the connection of the CO2 sen-
2
sor.
The unit is making a lot of
noise.
The filter(s) is/are dirty.Clean or replace filter(s).
A component is loose.Check the unit:
• are the inspection doors closed?
• are the rubber seals still in g
ion?
condit
ood
en
See also:
2.7"Connecting the unit to Modbus" on page 21
2.13"Switching on and checking operation" on page 29
6.2"Replacing the filter" on page 64
Manual version 4.1 (26-07-2018)
en-63
Page 64
en
Warning:
Note:
Note:
6.. Maintenance
6.1Introduction
This chapter comprises those maintenance activities that the
user himself can perform. Maintenance activities and repairs
that must be performed by an installer are described in chapter 7Service.
See also:
7"Service" on page66
6.2Replacing the filter
The unit is fitted with two filters:
•Fresh air filter: F7 1.
•Extract air filter: M5 2.
The filters must be replaced regularly. A dirty filter can cause
inefficient operation and a high noise level.
Remove the filter:
w Set the isolation switch to 0.
1. Open the inspection hatch for the relevant filter.
2. Pull the clamps downward 3.
3. Remove the filter 4.
4. Replace the filter. New filters are available from Biddle.
5. Return the filter to its place.
en-64
nPosition the correct filter back into the correct
place.
nPosition the filter in the correct direction.
The air direction is shown on the filter and on the
unit.
Page 65
HR MANUALMAINTENANCE
6.3Cleaning the unit
You can clean the interior and exterior of the unit with a
damp cloth and a domestic cleaning agent. Do not use any solvents.
6.4Scheduled maintenance
It is recommended to have the following inspection and maintenance activities performed annually by an installer or other
technical expert.
•Check the casing, the suspension or mounting structure,
and the securing of the unit.
•Check whether the filters are clean enough and undamaged. Replace the filters if necessary.
en
•Check that the heat exchanger or the electrical heatin
ements are clean. Settled dust may cause an unple
el
smell.
Car
efully remove dust with a vacuum cleaner.
•Check that the plate heat exchangers are clean.
em if necessary.
th
•Check all connections of the cabling.
•Check the operation of the fans and the valves.
•Check the condensate drain:
-Clean the drainage container.
-Flush the drain pipe.
-Check that the trap is filled with water.
See also:
2.13"Switching on and checking operation" on page 29
6.2"Replacing the filter" on page 64
6.3"Cleaning the unit" on page 65
7.1"Cleaning the plate heat exchangers" on page 66
asant
Clean
g
Manual version 4.1 (26-07-2018)
en-65
Page 66
en
Warning:
Warning:
Warning:
Note:
7.. Service
w Servicing activities may only be carried out by
personnel who are technically qualified to do
so.
w Before you begin: read the safety instructions.
See also:
1.5"Safety instructions" on page 11
7.1Cleaning the plate heat exchangers
Dirty plate heat exchangers can cause inefficient operation and
a high noise level. If they are dirty, clean the exchangers.
The exchangers can be extracted in two ways:
•Via the side.
•Via the underside.
w Set the isolation switch to 0.
1. Open the side shield 1.
nPreferably, also open the side shield if you extract
the exchangers via the underside. This will ensure
that the exchangers are no longer clamped fast.
2. Open the two inspection hatches of the heat ex
odule that are located next to the recircul
m
2.
changer
ation module
en-66
Page 67
HR MANUALSERVICE
Note:
3. Loosen the screws of the clamping strips so as to allow the
strips to
4. Remove the air separation plates:
-Unscrew bolts 4 and 5.
-Extract the plates.
5. Extract the plate heat exchangers:
-Via the side: 6.
-Via the underside: 7.
drop down slightly 3.
en
6. The last exchanger is located behind the by-pass valve.
Make room in order to extract the exchanger:
-Open the value of the by-pass 8.
-Unscrew the valve motors from the valve 9.
-When extracting via the underside:
Push the by-pass slightly to the side.
-When extracting via the side:
Disconnect the cables located on top of the by-p
extract the by-pass via the underside of the unit.
and
-Extract the last exchanger.
7. Clean the plate heat exchangers by spraying water through
them.
8. Return all components to their places in reverse order.
ass
nTighten the screws/bolts of the air separation plates
and the clamping strips again, so that the exchangers
are clamped fast and no air leaks can arise.
Manual version 4.1 (26-07-2018)
en-67
Page 68
en
Warning:
Warning:
Note:
SERVICEHEATRECOVERYUNIT
7.2Removing the control circuit board
1. Switch the unit off using the control panel or the building
management system.
w Shut off the mains supply.
2. Open the electronic housing.
3. Disconnect all unit-connected connectors and gr
connections fr
4. Remove the screw 3.
5. Slide the control circuit board 4
un
it.
7.3Connecting the control circuit board
w Make sure that the mains supply is switched
off
1. Slide the control circuit board into its place and screw it
fi
rmly.
2. Connect all connectors and earth connections to the control circuit board again.
3. Switch the unit on and check the operation.
ounded
om the control circuit board.
loose and lift it out of the
in
en-68
nWith a new control circuit board, an E1 error may
occur because the old control circuit board can no
longer be found. Resolve this by reconfiguring the
system via menu > Maintenance > Reset system
Page 69
HR MANUALSERVICE
Note:
Warning:
Caution:
7.4Fuses
The unit is fitted with various fuses:
•In the electronics module 1.
•On the control circuit board 2.
The values are indicated on the fuses and/or are listed in the
wiring diagram.
nFirst identify and remove the cause of the error
before replacing the fuses.
7.5Setting the unit code
en
The unit code must be set after replacement of the control circuit
board in the unit. The unit code depends on the unit type and is
indicated on the type plate.
To set the unit code, there are two methods:
•directly via the control panel if a single unit is connected;
•via the control circuit board and the control panel if more
than one unit is connected.
w Entering an incorrect code will result in poor
performance of the unit.
7.5.1 Setting the unit code via the control panel
c Setting the unit code using this method will only
work if just a single unit is connected to the control
panel. If necessary, connect the control panel
separately to the unit in question.
Manual version 4.1 (26-07-2018)
1. Select menu > Maintenance > Unit code.
2. Enter the unit code via the control panel and press ok.
The control panel will now search for the unit again.
en-69
Page 70
en
Warning:
Note:
SERVICEHEATRECOVERYUNIT
7.5.2 Setting the unit code via the control circuit
board and the control panel
7.6Resetting the PIN code
1. Connect the mains supply (insert the plug into the sock
or mo
ve the isolation switch to ON).
w Do NOT touch any live parts.
2. Press down the microswitch 1 on the control circuit
board .
The LED next to the microswitch will start flashing.
The control panel displays numbers: these comprise
it code.
un
3. Enter the unit code via the control panel and press ok.
4. Press down microswitch .
The LED next to the microswitch will stop flashing.
The unit code is now set.
5. Reset the control panel.
the
et
The PIN code of the control panel can be reset using a USB
flash drive:
1. Connect a USB flash drive to the control panel.
The USB menu is activated
2. Press x for 15 seconds.
nThe screen shows no change.
The PIN code has now been reset to the default pin code:
0000
3. Exit the USB menu by removing the USB flash drive.
en-70
Page 71
HR MANUALSERVICE
Note:
Note:
7.7Copying the settings
The settings of the unit can be copied to another unit.
7.7.1 What you need
Before copying the setting, check that you have the following:
•An empty USB flash drive. The USB flash drive must be formatted for FAT or DOS. Do not use a USB hard disk fo
e software update.
th
7.7.2 Step 1: Copying the settings of the correctly-set
unit
1. Check whether the settings to be copied on the original btouch control panel are all correctly set.
r
en
2. Connect the USB flash drive to the USB port of the btouch control panel.
nIf the USB flash drive is not detected, disconnect it
and then connect it again.
The control panel detects the USB flash drive and displays
the USB menu
3. Select Export Settings
The progress percentage is displayed.
4. When this has been completed, disconnect the USB flash
drive from the control panel.
7.7.3 Step 2: Copying the settings to another unit
1. Connect the USB flash drive (with the settings that are to
be copied) to the USB port on the other control panel.
2. Keep the function Import settings pressed down
ogress of the process is displayed.
pr
until the
Manual version 4.1 (26-07-2018)
The settings are now being imported.
nBelow the progress percentage, the name of the file
to be imported is visible:‘settings_export.txt’
3. When this has been completed, disconnect the USB flash
drive from the control panel.
4. Repeat steps 1 to 3 for each control panel to which yo
wish to a
pply the same settings.
u
en-71
Page 72
en
SERVICEHEATRECOVERYUNIT
7.8Updating the software
Biddle is working continuously on improving its products and
recommends that you update the software of the control
panel and of the control circuit board when updates become
available. Consult Biddle’s website for availability.
7.8.1 What you need.
Before updating the software of the control panel, check that
you have the following:
•An empty USB flash drive. The USB flash drive must be formatted for FAT or DOS. Do not use a USB hard disk fo
the softwar
•A PC with Internet access.
e update.
r
7.8.2 Step 1: Check the current software version
Before you update the software of the control panel or of the
control circuit board, you must check the existing software
version. If the software version is the same as that of the most
recent update file on Biddle’s website, you do not need to
update the software.
1. Press menu in the Home screen.
2. Select Maintenance. The version of the current software is
displayed in the status overview.
7.8.3 Step 2: Download the most recent software
1. Connect the USB flash drive to a USB port on your PC.
2. On your PC, go to Biddle’s website and look under Downloads.
3. Look for your product and the available software for yo
it.
un
4. If the software version is more recent than the ve
our control panel, click on the software update.
y
ur
rsion on
en-72
5. Accept the licence agreement and save the file to the main
directory of the USB flash drive.
6. Disconnect the USB flash drive from the PC.
Page 73
HR MANUALSERVICE
Warning:
Note:
7.8.4 Step 3: Updating the software
w Do not switch off the unit or disconnect the
USB flash drive during the software update.
Do not disconnect the USB flash drive from
the control panel even if there is a power
failure during the update. The update will
resume as soon as the power returns. If an
error occurs during the update, start the
procedure again. If the error continues to
occur, contact Biddle.
en
1. Connect the USB flash drive (with the software up
th
e USB port on the control panel.
date) to
nIf the USB flash drive is not detected, disconnect it
and then connect it again.
The control panel detects the USB flash drive and displays
the USB menu
2. Select Software update to update the software.
3. When this has been completed, disconnect the USB flash
drive from the control panel.
Manual version 4.1 (26-07-2018)
en-73
Page 74
en
SERVICEHEATRECOVERYUNIT
7.9Composition of the Biddle control cable
The control cable for the control system is constructed as follows:
•The plugs are modular connectors of the type 6P4C.
•Connectors are untwisted, i.e. at both ends of the cable,
cores are connected to the same electrode.
Colour coding of Biddle cables
LECTRODECOLOUR
E
1(not used)
2black
3red
4green
5yellow
6(not used)
en-74
Page 75
8.. Dismantling
The dismantling of the installation and the handling of the
coolant, oil and other components must be carried out by a
qualified fitter in accordance with the relevant local and
national legislation and regulations.
Pursuant to EU legislation, used electrical and electronic appliances must be collected for recycling. By ensuring that this
product is disposed of in the correct manner, you are helping
to prevent potential negative consequences for the environment and public health. For more information about this,
please contact your supplier or the relevant government
authority.
en
Manual version 4.1 (26-07-2018)
en-75
Page 76
en
DISMANTLINGHEATRECOVERYUNIT
en-76
Page 77
9.. Addresses
If you have any comments or queries relating to this product,
please do not hesitate to contact your Biddle branch.
en
Biddle bv
P. O. B o x 1 5
9288 ZG Kootstertille
The Netherlands
All information and drawings contained in this manual are the property of Biddle and may not be used (other than
for the purpose of unit operation), photocopied, reproduced, translated and/or communicated to third parties
without prior written permission from Biddle.
The name Biddle is a registered trademark of Biddle bv.
Warranty and liability
For the warranty and liability provisions and terms, please refer to the terms & conditions of sale and supply.
At all times, Biddle shall not be held liable for consequential damages.
Liability as regards the manual
Although great care has been taken to ensure the correct and, where necessary, complete description of the
relevant components, Biddle shall not be held liable for damages as a consequence of errors and/or imperfections
in this manual.
Biddle reserves the right to alter the specifications as mentioned in this manual.
Should you nevertheless discover any errors or ambiguities in the manual, we shall be glad to learn that from you.
It helps us to improve the documentation still further.
For more information
If you have any comments or queries relating to this product, please do not hesitate to contact Biddle. You will find
the contact information for your Biddle branch in chapter 9Addresses.