biasi M96A.24SR/C, M96A.28SR/C User guide

Page 1
Wall hung, fan flue, room sealed, high efficiency gas boiler
User manual and Installation instructions
RIVA COMPACT HE MK2
Models
M96A.24SR/C System boiler M96A.28SR/C System boiler
Page 2
Congratulations on your choice. RIVA COMPACT HE MK2 are condensing high efficiency sealed chamber fan flue gas
Thematerialstheyaremadeofandthecontrolsystemstheyareequippedwithgiveyousafety, a high level of comfort and energy savings to allow you to get the greatest benefit out of independent heating.
RIVA COMPACT HE MK2 allow a higher efficiency by reducing the flue gas temperature such that the water vapour formed during the combustion is condensed out. This allows a gain of useful heat that otherwise would be lost.
Remember that...
n The manual
--- must be read thoroughly, so that you will be able to use the boiler in a safe and sen­sible way;
--- must be carefully kept. It may be necess­ary for reference in the future.
n First lighting up must be carried out by
competent and responsible engineer.
n The manufacturer
--- disclaim all liability for any translations of the present manual from which incorrect in­terpretation may occur
--- cannot be held responsible for non--- ob­servance of instructions contained in this manual or for the consequences of any pro­cedure not specifically described.
Using the boiler...
n Before lighting the boiler you are ad-
vised to have a professionally qualified per­son check that the installation of the gas supply
--- is gas---tight;
--- is of the correct gauge for the flow to the
boiler;
--- is fitted with all the safety and control de­vices required by the current Regulations.
n Ensure that
--- the installer has connected the pressure relief valve outlet to a drain pipe. The manu­facturers are not responsible for damage
caused by opening of the pressure relief valve and consequent escape of water, if not connected correctly to the drain.
--- the installer has connected the conden-
sate outlet to a suitable drain pipe.
n On detecting the smell of gas
--- don’t operate any electrical switches, the telephone or any device that may produce sparks;
--- open the windows and doors at once to create a draught of air which will purge the area;
--- shut off the gas cocks;
--- get the assistance of a qualified person.
n Do not touch the appliance with parts of
thebodythatarewetordampand/orbare feet.
n Do not block or modify the condensate
outlet and pipework
n In case of structural work or mainten-
ance near the exhaust duct and/or fume ex­haust devices or their attachments, turn off the appliance. On completion of the work, have a professionally qualified person check their efficiency.
n Repairs (under guarantee) must be car-
ried out only by an approved engineer, using genuine spare parts. Thus do no more than switching off the boiler yourself (see the in­structions).
n You r boiler allows heating up of water to
a temperature less than boiling point;
--- must be connected to a central heating
Page 3
system and/or a hot water supply system, compatible with its performance and output;
--- can be used only for those purposes for
which it has been specially designed;
--- must not be touched by children or by
those unfamiliar with its operation;
--- must not be exposed to weather condi-
tions.
n During the operation it is quite normal
that the boiler produces a white plume of condensation vapour from the flue terminal. This is due to the high efficiency of the ap­pliance and may be particularly evident with low outdoor temperatures.
Safe handling of
appliance
When handling or lifting always use safe tech­niques
--- keep your back straight, bend your knees, don’t
twist
--- move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible.
Wherepossibletransporttheboilerusingasack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necess­ary.
Safe handling of
substances
These products are manufactured in accordance with ISO 9000 and do not, and will not, contain any
hazardous materials or substances such as as­bestos, mercury or C.F.C.’s. The appliance packaging does not contain any substances, which may be considereda hazard to health.
Combustion chamber panels
Material: mineral fibres
Known hazards --- Some people can suffer red­dening and itching of the skin. Fibre entry into the eye will cause foreign body irritation, which can cause severe irritation to people wearing contact lenses. Irritation to respiratory tract.
Precautions - -- Dust goggles will protect eyes. People with a history of skin complaints may be particularly susceptible to irritation. High dust le­vels are only likely to arise following harsh ab­rasion. In general, normal handling and use will not present high risk, follow good hygiene prac­tices,wash hands before, touching eyes, consum­ing food, drinking or using the toilet.
Firstaid--- Medicalattentionmustbesoughtfol­lowing eye contact or prolonged reddening of the skin.
Thermostat / Temperature gauge
Description --- Sealed phial and capillary contain­ing liquid.
Known hazards --- irritating to skin, eyes and throat. Vapour is harmful. Inflammable --- do not extinguish with water.
Precautions --- Do not incinerate. Avoid contact with broken/leaking phials. Do not purposely puncture.
Firstaidmedicalattentionmustbesoughtfollow­ing eyes/skin contact, wash with clean water.
Appliance category II Country of destination: United Kingdom (GB) Ireland (IE)
This appliance conforms with the following EEC directive:
D Gas appliance Directive 90/396/CEE D Boiler Efficiency Directive 92/42/CEE D Electromagnetic Compatibility Directive 89/336/CEE D Low voltage Directive 73/23/CEE
The manufacturer, in the continuousprocess to improve his products, reservesthe right to modify the data expressed in the present documentation at any time and without prior notice.
The present documentation is an informative support and it cannot be considered as a contract to­wards third parties.
Gas G20 20 mbar, G30 29 mbar, G31 37 mbar
2H3+
Page 4
Boiler installation and commissioning tips
n The installation must be carried out by
a qualified person who will be responsible for observing the current Regulations.
Installing the boiler...
n Donotforgettoremovethetransitcaps
and plugs from the boiler connections these are fitted to every boiler.
n Keep the boiler clear of dust during in-
stallation and in particular do not allow any dust or debris to enter the top of the boiler where the flue connection is made. It is rec­ommended that you put a dust sheet over the top of the boiler until you are ready to make the flue connection.
n Because every boiler is fired and tested
live at the factory, a small amount of water re­mains within the boiler. It is possible for this water to initially cause the pump to seize. It is therefore recommended that the pump rotor be manually turned to free its rotation before turning the boiler on.
n Remember to release the auto air purge
before filling the boiler.See the instructions to identify the location of this device.
n Do not remove the cap of the pressure
test points of the air switch (top left side of the boiler).
n Y ou are strongly advised to flush out the
system both cold and hot in order to remove system and installation debris.
n It is also sensible to initially fire and com-
mission the boiler before connecting any ex­ternal controls such as a room thermostat.By this method if you have a subsequent prob­lem following the addition of an external con­trol you can eliminate the boiler from your fault analysis.
n Donotforgettorangeratetheboilerto
suit the system requirements. This pro­cedure is covered in the commissioning sec­tion of the installation manual.
n If the boiler is fitted with a digital pro-
grammer, when setting the times for auto­matic operation, remember that for every “ON” time there must be an “OFF” time to fol­low and that on every occasion you enter a time you must also indicate which days that you want the boiler to follow the timed set­tings.
n Some products incorporate an anti cycl-
ing time delay . It is normal when first switch­ing the boiler on for the boiler to operate on heating for a few seconds then switch off. After 3 --- 4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to provide d.h.w.
n If you are in any doubts as to the installa-
tion or operation of the boiler please read the instruction manuals thoroughly and then if necessary contact Biasi UK for advice and assistance.
Please remember that if you are in any doubt about the installation of this product you can contact our Technical Helpline on tel. 0121 506 1350
Page 5
TABLE OF CONTENTS
1 Appliance description 2..........
1.1 Overview 2......................
1.2 Control panel 2..................
1.3 Isolation valves 2.................
1.4 Technical d ata 2.................
1.5 Operation lights 3................
3Usefuladvice 7.................
3.1 Central heating 7.................
3.2 Frost protection 7................
3.3 Condensate drain 7..............
3.4 Periodic maintenance 7...........
3.5 External cleaning 7...............
3.6 Operational faults 7...............
4 Technical information 9..........
4.1 Overview 9......................
4.2 Main diagram 10..................
4.3 Hydraulic specifications 11.........
4.4 Expansion vessel 11...............
4.5 Technical data mod. M96A.24SR/... 12
4.6 Technical data mod. M96A.28SR/... 14
5 General requirements 16..........
5.1 Related documents 16.............
5.2 Location of appliance 16...........
5.3 Flue system 16....................
5.4 Gas supply 17....................
5.5 Air supply 17.....................
5.6 Ventilation 17.....................
5.7 Condensate drain 17..............
5.8 Water circulation (c.h.) 18...........
5.9 Water treatment 19................
5.10 Electrical supply 19................
2 Instructions for use 4............
2.1 Warnings 4......................
2.2 Refilling procedure 4..............
2.3 Ignition 5........................
2.4 C.h. circuit temperature 5..........
2.5 Extinguishing 5..................
6 Installation 20....................
6.1 Warnings 20......................
6.2 Precautions for installation 20.......
6.3 Installing the bracket 20............
6.4 Overall dimensions 21.............
6.5 Joints 21.........................
6.6 Mounting the boiler 21.............
6.7 Fitting the flue system 22...........
6.8 Choice of flue 22..................
6.9 Electrical connections 25...........
6.10 External frost protection 26.........
6.11 Connecting a system boiler
to a cylinder 27...................
7 Commissioning 30...............
7.1 Electrical installation 30............
7.2 Gas supply installation 30..........
7.3 Initial filling of the system 30........
7.4 Condensatepipeandtraps 31......
7.5 Lighting the boiler 31..............
7.6 Checking the gas pressure
at the burner 31...................
7.7 Checking the burner ignition 32.....
7.8 Checking the ignition device 33.....
7.9 Checking the flue system 33........
7.10 Checking the condensate drain pipe 33
7.11 Instructing the user 33.............
USE
INSTALLATIONMAINTENANCE
8 Gas conversion 34...............
8.1 Warnings 34......................
8.2 Procedures 34....................
9 Maintenance 36..................
9.1 Warnings 36......................
9.2 Dismantling the external panels 36...
9.3 Emptying the c.h. system 36........
9.4 Combustion analysis check 37......
Abbreviations used in the manual: C.h. = Central heating
9.5 Cleaning the primary heat exchanger 37
9.6 Checking the pressurisation
in the expansion vessel 37..........
9.7 Cleaning the burner 37.............
9.8 Checking the flue 37...............
9.9 Drain pipe inspection 37............
9.10 Visual inspection of appliance 37....
9.11 Gas pressures and tightness 37.....
D.h.w. = Domestic hot water D.c.w . = Domestic cold water
1
Page 6
1 APPLIANCE DESCRIPTION
1.1 Overview
USE
Fig. 1.1
1 Case front panel
2 Control panel
3 Control panel cover
1.2 Control panel
4 C.h. circuit temperature and pressure gauge
5 Lock --- out signal lamp
6 Lockout reset button
7 Function selector and c.h. temp. control knob
8Serviceknob
9 Appliance operation lights
The service knob 8 is useless for the normal oper­ation of the boiler.
9
78 6
It must be used only by a qualified person during commissioning and servicing.
1.3 Isolation valves
1
13
2
3
12
11 Fig. 1.2 (bottom view of the boiler)
10 Condensate drain pipe
11 C.h. return valve
12 Gas inlet valve
13 C.h. flow valve
1.4 Technical data
For detailed technical data see section 4.5 or 4.6 of this manual.
5
4
10
Fig. 1.3
2
Page 7
Appliance description
L
L
1.5 Operation lights
Three lights (9 in Fig. 1.3) give detailed indication regarding the operation of the boiler.
The following table gives the relationship between each of the possible light combinations and their meaning.
A short pulse every 4 seconds: stand ---by condition Function selector in position. Anti--- freeze system active
1 second pulse every 2 seconds: normally operating boiler. Function selector in position
C.h. operation
Frost protect operation
Faulty c.h. temperature probe NTC
Faulty flue temperature probe NTC
Faulty primary circuit (no water or low c.h. pressure)
Faulty primary circuit (absence of flow)
Meaning of symbols
amp OFF
amp ON
Flashing lamp, alone or simultaneously with an other lamp.
Flashing lamp, alternate with another lamp.
If the lights combination observed is not included in the above table a fault may be indicated. Reference should be made to the following table.
In this case switch off the boiler, as described in section 2.5 on page 5 and call a competent and re­sponsible Service Engineer.
USE
Faulty air pressure sensor
Lack of burner ignition (no ignition signal from the full seqence ignition device)
Safety thermostat lock out
Flue temperature probe NTC lock out
Flame detection error
Other faults
Lack of power supply or fauly electr. control p.c.b.
3
Page 8
2 INSTRUCTIONS FOR USE
2.1 Warnings
Our Company supports the Benchmark in­itiative. The Benchmark Log Book is lo­cated at the back of this manual and should be completed by the Installing/Commiss­sioning Engineer and handed over to the
USE
User for future reference by other visiting Engineers. Also included is the Service In ­terval Record card that should be com­pleted by the Service Engineer following the annual service maintenance of the boiler and system.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your Benchmark Log Book. You can check your installer is registered by calling CORGI di­rect on 01256 372300.
In order to guarantee safety and correct oper­ation, it is essential that all the tests are carried out by a competent and responsible service engineer before lighting up the boiler.
The tests are described in the installation in- structions in section 7 commissioning.
Ensure that the c.h. circuit is regularly filled with water (even if the boiler is only used for d.h.w. supply) checking that the pressure indi­cated on the temperature and pressure gauge 4 is not lower than that shown in Fig. 2.2.
If the pressure reading on the pressure gauge is below that shown in Fig. 2.2, then the system will require topping up. A filling loop is normally provided by the installer for this purpose.
If you are in any doubt regarding this pro­cedure you are advised to contact your In­staller or an Approved Engineer.
This appliance is provided with a built in anti --­freeze system that operates the boiler when the temperature is below 5 ˚C Therefore, when the boiler is not lit or used in cold weather, with consequent risk of freezing
do not switch off the boiler at the fused spur isolation switch or close the gas inlet cock.
When you do not expect to use the boiler for a long period and the boiler is not to be used for frost protection then follow the instructions giveninsection2.5onpage5.
2.2 Refilling procedure
1 Isolate the boiler from the electrical supply at
the fused spur. Reconnect the filling loop as demonstrated in Fig. 2.1.
Control valve
Double check valve
Te m p o r a ry connection
Supply pipe
(cold water i nlet)
C.h. return pipe
Fig. 2.1
2 Open the valves of the filling loop and watch
the gauge until it reaches normal filling pres­sure as shown in Fig. 2.2.
Fig. 2.2
3 Close the valves and remove the filling loop.
If you experience any difficulty with the oper­ation of the boiler, switch off the boiler immedi­ately at the fused spur isolation switch and contactyourInstalleroranapprovedService Engineer
Air introduced into the boiler during this filling pro­cess will vent through the automatic air purger fitted to the boiler. You may also find it necessary to vent air from your radiator circuit using your radiator key, however be aware that excessive venting will cause the pressure in the system to drop.
Always ensure that the pressure gauge is set at the required pressure.
Control valve
4
Normal filling pressure
4
Page 9
Instructions for use
2.3 Ignition
1 Check that the valves located in the lower part
of the boiler are open (Fig. 2.3).
Open position
Fig. 2.3
2 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 9 (Fig. 2.4) will flash every 4 seconds (stand--- by condition).
3 To operate the boiler, position the function se-
lector 7 as in Fig. 2.4. The appliance operation light 9 will flash every 2 seconds (operating boiler).
79
Adjustment of the boiler temperature alters the gas flow at the burner according to the thermal de­mand in the system. So it is usual to see the burner lit at the minimum level for more or less long periods.
USE
Minimum
Maximum
Fig. 2.5
Adjustment
In order to achieve optimal settings for economy and comfort, we recommend adjusting the oper­ating temperature of the c.h. water according to the outside temperature, positioning the knob as follows:
From 5 to 15 ˚C
Between
--- 5 a n d + 5 ˚C
Fig. 2.4
2.4 C.h. circuit temperature
The output temperature of c.h. water is adjustable from a minimum of about 40°C to a maximum of about 85°C (Fig. 2.5), by turning the function se­lector (7).
Adjustment of c.h. output on the boiler is auto­matic. The greatest output pre---set in the factory can, however, be reduced in level according to actual system requirements; this does not affect the maximum output in d.h.w. operation.
Such adjustments must be carried out by a quali­fied person; therefore we advise you to contact yourinstallerorServiceAgent.
Lower than
--- 5 ˚C
Fig. 2.6
Your qualified installer will be able to recommend the most suitable adjustment for your system.
The temperature and pressure gauge (4, Fig. 1.3 on page 2) will allow you to check that the set tem­perature is obtained.
2.5 Extinguishing
To turn the boiler off set the function selector 7 to the position shown in Fig. 2.7.
5
Page 10
Instructions for use
The appliance operation light 9 will flash every 4 seconds.
79
USE
Fig. 2.7
When you do not expect to use the boiler for a long period:
1 Switch off the electricity supply to the boiler, by
means of the fused spur isolation switch;
2 Shut off the gas supply cock 12 and the valves
for the water circuits fitted under the boiler (Fig. 2.8).
3 Empty the water circuits, if necessary, as
showninsectionGeneral access and emptying hydraulic circuits in the service manual.
12
Fig. 2.8
Closed position
6
Page 11
3 USEFUL ADVICE
3.1 Central heating
For reasonably economical service install a room thermostat.
Never shut off the radiator in the area where the room thermostat is installed.
If a radiator (or a convector) does not heat up, check that no air is present in it and that its valve is open.
If the ambient temperature is too high, do not alter the radiator valves. Reduce the central heating temperature instead by means of the room ther­mostat and the function selector (7 in Fig. 3.1).
7
Fig. 3.1
3.2 Frost protection
This appliance is provided with a built in anti --­freeze system that operates the boiler when the temperature is below 5 ˚C Therefore, when the boiler is not lit and used in cold weather, with consequent risk of freezing do
not switch off the boiler at the fused spur isola­tion switch or close the gas inlet cock.
3.3 Condensate drain
Thecondensatedrainmustnotbemodifiedor blocked. Blockage of the condensate drain, caused by de­bris or freezing, can cause automatic shutdown of the boiler.
If freezing is suspected and the pipe run is access­ible an attempt may be made to free the obstruc­tion by pouring hot water over the exposed pipe an cleaning any blockage from the end of the pipe. If this fails to remedy the problem the assist­ance of a CORGI registered installer or in IE a com­petent person should be sought.
3.4 Periodic maintenance
For efficient and continuous operation of the boiler, it is advisable to arrange maintenance and
cleaning by an Authorised Service Centre En­gineer, at least once a year.
During the service, the most important compo­nents of the boiler will be inspected and cleaned. This service can be part of a maintenance con­tract.
In particular, you are advised to have the following checks carried out:
--- primary heat exchanger;
--- burner;
--- exhaust fume duct and flue;
--- pressurisation of the expansion tank;
--- filling up of the central heating circuit;
--- bleeding of air from the central heating system;
--- general check of the appliance’s operation.
3.5 External cleaning
Before carrying out any cleaning, disconnect the appliance from the electrical mains, using the fused spur isolation switch fitted adjacent to the appliance.
To clean the external panels, use a cloth soaked in soapy water. Do not use solvents, abrasive powd­ers or sponges.
Do not carry out cleaning of the appliance and/or its parts with readily flammable substances (for example petrol, alcohols, naphtha, etc.).
3.6 Operational faults
If the lock --- out signal lamp comes on
this indicates that the safety lock--- out 5 (Fig. 3.2) has stopped the boiler
To re ---start the boiler, it is necessary to press the boiler reset button 6 (Fig. 3.2).
5
6
Fig. 3.2
Forthe first lighting up and followingmaintenance procedures for the gas supply, it may be necess­ary to repeat the resetting operation several times so as to remove the air present in the pipework.
USE
7
Page 12
Useful advice
After five consecutive resetting attempts the reset button is inhibited. To restore its function it is necessary to switch the boiler off and on from the electrical mains, using the fused spur isolation switch fitted adjacent to the appliance.
Safety lock--- out may occour even in case of an
USE
blockage of the condensate drainage (e.g. plugged drain pipe).
It is advisable to check the condensate drainage pipe and traps for cleaness.
In case of persistent lock--- out call a competent and responsible service engineer.
If noises due to air bubbles are heard during operation...
you should check that the pressure on the tem­perature and pressure gauge (Fig. 2.2 on page 4) is not below the correct setting. If required, top up the system correctly, as de­scribed in the section 2.2 of this manual. Bleed any air present in the radiators, if necessary.
If the pressure on the temperature and pres­suregauge(4onpage2)hasgonedown...
it is necessary to top up the appliance with water again, so as to raise the pressure to an adequate level as described in the section 2.2 of this manual.
If topping up with water has to be done very fre­quently, have the system checked for leaks.
If water comes out of the pressure relief valve
Check on the temperature and pressure gauge (4 on page 2) that the pressure in the central heating
circuit is not close to 3 bars. In this case, tempera­ture rise in the circuit can cause the pressure relief valve to open.
So that this does not happen and to decrease the pressure to a normal value, it is advisable to vent some of the water in the appliance through the bleed valves present in the radiators.
If water should occasionally leak from the boiler...
shut off the valves positioned under the boiler (Fig. 2.8 on pag e 6) and callan AuthorisedService Centre Engineer.
If the left appliance operation light 9 (Fig. 3.3) flashes very quickly the boiler is detecting a fault.
9
Fig. 3.3
In this case or in case of problems other than those mentioned here, switch off the boiler, as describedinsection2.5onpage5andcalla competent and responsible service engineer.
8
Page 13
4 TECHNICAL INFORMATION
4.1 Overview
15
16
36
35
34
33
32
20
31
Fig. 4.1
26
17 19
25
1814
21
23
2427
22
10 Condensate drain pipe 11 C.h. return valve 12 Gas inlet valve 13 C.h. flow valve 14 Fan
15 Air pressure sensor test points
16 Air pressure sensor
17 Flue temperature probe NTC
18 Condensing heat exchanger
19 Safety thermostat
20 C.h. temperature p robe NTC
21 Main circuit drain valve
22 Condensate trap
23 Automatic air purger valve
24 Pump vent plug
25 Pump
26 C.h. pressure relief valve
27 Modulation gas valve
28 Modulation operator
29 Gas valve outlet pressure test point
30 Gas valve inlet pressure test point
31 Primary circuit pressure switch
32 Flame---detecting electrode
33 Burner
34 Ignition electrodes
35 Combustion chamber
36 Primary heat exchanger
37 C.h. expansion tank
3 8 B y --- p a s s v a l v e
39 Fan pressure connection
40 Flue outlet pipe
41 Air intake pipe
INSTALLATION
9
Page 14
Technical information
4.2 Main diagram
41
17
18
39
14
16
36
INSTALLATION
32
33
34
22
29
27
28
30
10
37
19
23
31
26
40
25
20
38
Fig. 4.2
10
21
11 1312
Page 15
Technical information
4.3 Hydraulic specifications
kPa bar
0.6
60
50
0.5
40
0.4
0.3
30
20
0.2
0.1
10
0
0.0
0 200 400 600 800 1000 1200 1400
l/h
Fig. 4.3
The hydraulic specifications in Fig. 4.3 represent the pressure (available head for the central heat­ing system) as a function of the flow rate.
The load loss due to the boiler has already been subtracted.
Output with thermostat cocks shut off
The boiler is fitted with an automatic by ---pass valve (38 on page 9), which protects the primary heat exchanger.
In case of excessive reduction or total blockage of water circulation in the central heating system owing to closure of the thermostatic valves or sys­tem component cocks, the by---pass valve ensur-
es a minimum flow of water through the primary heat exchanger.
4.4 Expansion vessel
Note: this boiler is designed for operation only in a sealed central heating system
The heigh t difference between the pressure relief valve and the highest point in the system may be 10m at most.
For greater differences, increase the pre--- load pressure in the expansion vessel (37 on page 9) and the system, when cold, by 0.1 bar for each additional 1m.
Capacity
P r e --- l o a d p r e s s u r e kPa
Maximum volume of water in the system *
Tab . 4 . 1
* Where conditions are:
--- Average maximum temperature of the system is 85°C
--- Initial temperature when filling up the system is 10°C
For systems with volumes greater than 94 l, an additional expansion vessel must be provided.
l 6,0
100
bar
1,0
l 94
INSTALLATION
11
Page 16
Technical information
4.5 Technical data
mod. M96A.24SR/...
(B)
(B)
(A)
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
bar
bar
kPa
bar
band %
band %
Heat input
Nominal kW
Minimum kW
Useful output
Maximum kW
Minimum kW
Maximum condensing kW
INSTALLATION
Minimum condensing kW
Central heating
Maximum flow temp. ˚C 85
Minimum flow temp. ˚C 40 Minimum return temp. ˚C 40
Maximum pressure kPa
Minimum pressure kPa
Available head (in 1000 l/h)
Seasonal efficiency G20
Seasonal efficiency G30 G31
25,0
85 295
11,0
37 530
24,3
82 908
10,5
35 825
26,0
88 708
11,2
38 213
250
2,5
30
0,3
25
0,25
87,6
88,5
Gas supply pressures
Gas Natural
Butane
G20
Norm. Pa
mbar
Max Pa
mbar
Min. Pa
mbar
2 000202 900293 700
2 500253 500354 500
1 700172 000202 500
1 mbar approximately equals 10 mm H2O
Gas pressures at the burner
Gas Natural
Butane
G20
Max. Pa
mbar
Min. Pa
mbar
Ignition Pa
mbar
1130
11,3
250
2,5
850
8,5
1 mbar approximately equals 10 mm H2O
Gas rate
Gas Natural
G20
m
Butane
3
/h
Max. 2,65 1,97 1,94
Min. 1,16 0,87 0,85
B
B
G30
G30
2810
28,1
580
5,8
2110
21,1
G30
kg/h
Propane
G31
37
45
25
Propane
G31
3610
36,1
780
7,8
2700
27,0
Propane
G31
kg/h
(A)
referred to the net calorific value at 15 ˚C and 1013,25 mbar
G 20 = 34,02 MJ/m
(B)
The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating
3,
G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg
of dwellings. The test data from which it has been calculated have been certified by a notified body.
(C)
Values subject to tolerance
12
Page 17
Technical information
Injectors mm/100ø
Natural G20 130
Butane G30 77
Propane G31 77
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 140
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A F1--- F2 3,15 AF
Flue design
Type C12 C32 C42 C52 C82
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate
(A)(D)
Exhaust temperature
Mass flow rate
(D)
(D)
kW 25,0
˚C 71
g/s 16,0
Flue gas figures
Nominal heat input
(A)(D)
kW 25,0
CO2content % 6,5
O2content % 9,3
CO content ppm 75
Exhaust temperature
(D)
˚C 71
NOxclass 2
Weighted NO
x
ppm 99
Other specifications
Height mm 803
Width mm 400
Depth mm 350
Weight (dry) kg 41,0
Water volume in the boiler
l(kg) 4,0
(up to 1 bar)
INSTALLATION
(D)
Values refer to tests with a 1 m chimney working at the nominal heat input
13
Page 18
Technical information
4.6 Technical data mod.
M96A.28SR/...
(B)
(B)
(A)
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
BTU/h
bar
bar
kPa
bar
band %
band %
Heat input
Nominal kW
Minimum kW
Useful output
Maximum kW
Minimum kW
Maximum condensing kW
INSTALLATION
Minimum condensing kW
Central heating
Maximum flow temp. ˚C 85
Minimum flow temp. ˚C 40 Minimum return temp. ˚C 40
Maximum pressure kPa
Minimum pressure kPa
Available head (in 1000 l/h)
Seasonal efficiency G20
Seasonal efficiency G30 G31
29,0
98 942
13,0
44 353
28,4
96 897
12,5
42 648
30,4
103 721
13,3
45 378
250
2,5
30
0,3
25
0,25
88,5
89,5
Gas supply pressures
Gas Natural
Butane
G20
Norm. Pa
mbar
Max Pa
mbar
Min. Pa
mbar
2 000202 900293 700
2 500253 500354 500
1 700172 000202 500
1 mbar approximately equals 10 mm H2O
Gas pressures at the burner
Gas Natural
Butane
G20
Max. Pa
mbar
Min. Pa
mbar
Ignition Pa
mbar
1130
11,3
240
2,4
850
8,5
1 mbar approximately equals 10 mm H2O
Gas rate
Gas Natural
G20
m
Butane
3
/h
Max. 3,07 2,29 2,25
Min. 1,38 1,03 1,01
B
B
G30
G30
2810
28,1
580
5,8
2110
21,1
G30
kg/h
Propane
G31
37
45
25
Propane
G31
3600
36,0
780
7,8
2700
27,0
Propane
G31
kg/h
(A)
referred to the net calorific value at 15 ˚C and 1013,25 mbar
G 20 = 34,02 MJ/m
(B)
The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating
3,
G 30 = 45,6 MJ/kg, G 31 = 46,4 MJ/kg
of dwellings. The test data from which it has been calculated have been certified by a notified body.
(C)
Values subject to tolerance
14
Page 19
Technical information
Injectors mm/100ø
Natural G20 130
Butane G30 77
Propane G31 77
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 150
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A F1--- F2 3,15 AF
Flue design
Type C12 C32 C42 C52 C82
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate
(A)(D)
Exhaust temperature
Mass flow rate
(D)
(D)
kW 29,0
˚C 69
g/s 17,8
Flue gas figures
Nominal heat input
(A)(D)
kW 29,0
CO2content % 6,8
O2content % 8,8
CO content ppm 52
Exhaust temperature
(D)
˚C 69
NOxclass 2
Weighted NO
x
ppm 92
Other specifications
Height mm 803
Width mm 400
Depth mm 350
Weight (dry) kg 42,5
Water volume in the boiler
l(kg) 4,1
(up to 1 bar)
INSTALLATION
(D)
Values refer to tests with a 1 m chimney working at the nominal heat input
15
Page 20
5 GENERAL REQUIREMENTS
Our Company supports the Benchmark initiat­ive. The Benchmark Log Book is located at the back of this manual and should be completed by the Installing/Commisssioning Engineer and handed over to the User for future r efer­ence by other visiting Engineers. Also in­cluded is the Service Interval Record card that should be completed by the Service Engineer following the annual service maintenance of the boiler and system.
For Ireland (IE), it is necessary to complete a “Declaration of Conformity” to indicate com­pliance to I.S.813.2002.
This appliance must be installed by a compet­ent person in accordance with the Gas Safety (installation & Use) R egulations.
INSTALLATION
5.1 Related documents
The installation of this appliance must be in ac­cordance with the relevant requirements of the current Gas Safety (Installation & Use) Regula­tions, the Local Building Regulations, the current I.E.E. Wiring Regulations, the Regulations and by ---laws of the local water undertaking, and in Scotland, in accordance with the Building Stan­dards (Scotland) Reg ulation. Health and safety document n˚ 635 ”Electricity at work regs.”.
It should also be in accordance with the British Standard Codes of Practice:
In Ireland (IE). The installation must be carried out by a Competent Person and installed in accord­ance with the current edition of I.S.813.2002 “Do­mestic Gas Installations” the current Building Regulationsand reference should be made to the current ETCI rules for electrical installations.
5.2 Location of appliance
The appliance may be installed in any room or in­ternal space, although particular attention is drawn to the requirements of the current I.E.E. Wir­ing Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower.
For Ireland (IE), reference should be made to the current edition of I.S.813.2002 and the current ETCI rules for electrical installations.
Where a room --- sealed appliance is installedin a room containing a bath or shower, any electri­cal switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
The location must permit the provision of an ad­equate flue and termination.
For unusual locations special procedures may be necessary and BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed specifically for this purpose.
This appliance is not suitable for external installa­tion.
5.3 Flue system
The provision for satisfactory flue termination must be made as described in BS 5440 part 1.
For Ireland (IE), refer to I.S.813.2002.
The appliance must be installed so that the flue ter­minal is exposed to external air.
It must not be installed so that the terminal dis­charges into an other room or space as an out­house or lean--- to. It is important that the position of the terminal allows a free passage of air across at all times.
The terminal should be located withdue regard for the damage or discoloration that might occur to building products in the vicinity.
In cold and/or humid weather water vapour may condenseon leaving the flue terminal;the effect of such ”steaming” must be considered.
Pluming may easily occur at the terminal. Where possible, terminal position which could cause a nuisance should be avoided.
16
Page 21
General requirements
The minimum acceptable spacing from the ter­minal to obstructions and ventilation openings are specified in Fig. 5.1.
Pipework must be of adequate size. Pipes of a smaller size than the boilerinlet connectionshould not be used.
Installation pipes should be fitted in accordance with BS 6891 and the complete installation should be tested for tightness.
For Ireland (IE), refer to I.S.813.2002.
BC
G
E
JK
L
Fig. 5.1
Ter m i n a l p o s iti o n m m
A Directly below a window or other opening 300. ...
B Below gutters, soil pipes or drain pipes 75. .....
C Below eaves 200. ............................
D Below balconies* 600. ........................
E Below car port roof NO. .......................
F From vertical drain pipes and soil pipes 150. ....
G From internal corners** 450. ..................
H From external corners 300. ...................
I Above ground or balcony l evel 300.. ............
J From a surface facing a terminal 600. ...........
K From a terminal facing a terminal 1 200. .........
L From an opening in the car port.
(e.g.door,window)intodwelling NO...........
M Vertically from a terminal in the same wall 1 500. N Horizontally from a terminal in the same wall 300.. O Above the roof pitch with roof slope less.
than or equal to 30˚ 350......................
Above the r oof pitch with roof slope
more than 30˚ 600...........................
P From wall face 600. ..........................
Q From,aboveortosideofanopening 300. .......
*Wherever practicable to do so, the flue should be ex­tended beyond the perimeter of the balcony ** Consideration should be given to adding protection against condensate to the adjacent structure
O
F
A
D
Q
H
I
P
5.5 Air supply
The room in which the boiler is installed does not require a purpose provided air vent.
MN
I
5.6 Ventilation
If installed in a cupboard or compartment, it is not necessary to provide additional ventilation for cooling for this particular product. However con­sideration must be given to clearance require­ments for maintenance (see section 6.2) and under no circumstancesmust stored articles be al­lowed to come into contact with the boiler or flue pipe.
5.7 Condensate drain
Ensure that the condensate discharge complies with the national or local regulations in force.
The condensate pipe must be fitted in accordance with Building Regulations.
Drainpipe material should be resistant to acid as the condensate is slightly acid with a pH less than
6.5.
The boiler includes a trap (22 on page 9) that pre­vents the combustionproducts entering the drain.
The boilers incorporate a condensate trap a 75mm seal ti comply with BS6798.2000.
Two schematic diagrams of possible connections are given in Fig. 5.2 and Fig. 5.3.
The length of the condensate pipe should be kept at minimum.
To avoid condensate being trapped:
5.4 Gas supply
The Gas meter is connected to the service pipe by the local gas region or a local gas region contrac­tor.
If the gas supply for the boiler serves other appliances ensure that an adequate supply is
--- the drainpipe should be run witha fallof atleast
2.5˚ (45 mm/m) away from the boiler;
--- the number of bends and joints should be kept at minimum;
--- the drainpipe should be adequately fixed to pevent pipe sagging.
available both to the boiler and the other appliance when they are in use at the same time.
INSTALLATION
17
Page 22
General requirements
If a part of the drainpipe runs externally this part shouldbe kept as short as possible and protected to reduce the risk of freezing.
Connection of condensate drainage pipe to in­ternal soil and vent stack.
A
Condensate drain
B
D
C
450
INSTALLATION
Dimensions in mm
Fig. 5.2
ABoiler
B Internal soil and vent stack
CInvert
D 450 mm up to three storeys
Connection of condensate drainage pipe downstream of a sink waste trap
A
Condensate drain
E
Dimensions in mm
Fig. 5.3
ABoiler ESink
F Open end of condensate drainage pipe direct
into gully below grating but above water level
5.8 Water circulation (c.h.)
Detailed recommendations are given in BS 6798 and BS 5449; the following notes are given for general guidance.
For Ireland (IE), refer to I.S.813.2002.
Pipework
The return temperature must not be lower of 40 ˚C.
Copper tubing to BS EN 1057 is recommended for water pipes. Jointing should be either with capil­lary soldered or with compression fittings.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps.
The appliance has a built--- in automatic air release valve, it should be ensured as far as possible that the appliance heat exchanger is not a natural col­lecting point for air.
Except where providing useful heat, pipes should be insulated to prevent heat loss and to avoid freezing.
Particular attention should be paid to pipes pas­sing through ventilated spaces in roofs and under floors.
B y --- p a s s
The appliance includes an automatic by --- pass valve which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system due to the closing of thermostatic valves or cock --- type valves within the system.
The by--- pass is calibrated to assure a minimum flow of 200 --- 300 lts/hr through the main heat ex­changer.
If you are installing a system that includes thermo­static radiator valves (TRV) and/or small bore
F
(8--- 10 mm) it may be necessary to fit an external by ---pass to facilitate correct operation of the boiler.
The fitting of an external bypass helps to prevent and limit system noise.
Air release points
Thesemustbefittedatallhighpointswhereairwill natural collect and must be sited to facilitate com­pletefillingofthesystem.
18
Page 23
General requirements
Expansion vessel
The appliance has an integral sealed expansion vessel to accommodate the increase of water vol­ume when the system is heated.
Refer to Tab. 4.1 on page 11 for its technical data. If the heating circuit has an unusually high water
content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
Mains water feed: central heating
There must be no direct connection to the mains water supply even through a non return valve, without the approval of the Local Water Authority.
Filling
A method for initially filling the system and replac­ing water lost during servicing must be provided and it must comply with localwater authorityregu­lations.
The correct method is shown in Fig. 5.4.
The temporary connection must be removed immediately after filling.
Control valve
Double check valve
Te m p o r a ry connection
Supply pipe
(cold water i nlet)
C.h. return pipe
Control valve
Fig. 5.4
The installer should ensure that no leaks exist either inside the boiler or on the system as fre­quent filling of the system could cause premature scaling of the heat exchanger.
5.9 Water treatment
Central heating circuit
Where a new boiler is fitted to a new system with either plastic or copper pipes, it is important the system is fully flushed, on completion, to ensure flux residues, swarfs, oils and other installation de­bris is removed.
Where a new boiler is fitted to an existing system, it is important the debris from the existing system is fully removed in order to ensure the efficiency of the new appliance is maintained.
Details on flushing procedure are given in the sec­tion 7.3 of this manual.
5.10 Electrical supply
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and any local regulations which apply.
Reference should be made to the current ETCI rules for electrical installations.
For Ireland (IE), refer to I.S.813.2002.
The boiler is supplied for connection to a 230 V~ 50 Hz supply. The supply must be fused at 3A.
The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance by the use of a fused spur isolation switch. Its installation permits a complete switch­ing off in the conditions of the overvoltage cat­egory III. Alternatively it can be used a 3A fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363.
The point of connection to the electricity supply must be readily accessible and adjacent to the applianceexcept were the applianceis installed in a bathroom this must then be sited outside the bathroom.
INSTALLATION
19
Page 24
6 INSTALLATION
6.1 Warnings
The use of gas appliances is subject to statutory control; it is essential to observe the current regulations and laws in force (see also chapter 5).
The appliance must discharge combustion products directly outside or into a suitable ex­haust duct designed for this purpose.
Combustion products must be discharged using original flue kits only, since they are inte­gral parts of the boiler.
ForLPG, the appliance must also conformwith the requirements of the distributors and com­ply with current Regulations and laws in force.
The safety relief valve and the condensate drain must be connectedto a suitable drain, or discharge in a safe manner.
INSTALLATION
The electricalwiring must conform with current Regulations, in particular:
--- the boiler must be earthed using the cor­rect bonding clamp.
--- Adjacent to the boiler a fused spur isolation switch must be installed which permits a complete switching off in the conditions of the overvoltage category III. Refer to sec­tion 6.9 in this chapter for the electrical con­nections.
In no circumstances will the manufacturer be held responsible if the warnings and in­structions contained in this manual have not been complied with.
6.2 Precautions for installation
For the installation proceed as follows:
--- The boiler must be fixed to a strong wall.
--- The dimensions for the exhaust fume duct de-
tailed in section 6.7 and the correct procedures for installing the duct, depicted in the instruc­tion leaflet included with the flue kit, must be complied with during installation.
--- To allow maintenance procedures it is necess­ary to leave the minimum gaps indicated in Fig. 6.1.
250
25 50
200
Fig. 6.1 (all dimensions in mm)
--- When installing the boiler in a cupboard, cover or alcove allow at least 50mm permanent clear­ance from the front face of the boiler. Also en­sure sufficient clearance to allow free access for servicing and the lowering of the front con­trol panel.
--- If the boiler is installed outside, cover the ap­pliance to protect it against the elements and add some special anti --- freeze (neutralised) to the c.h. system.
--- Before installing the boiler on an existing c.h. system,flush it out thoroughlybefore fitting the boiler, so as to remove muddy deposits.
--- It is advisable to equip the system with a sedi­ment filter, or use a water--- treatment product in the circulating water. The latter option in particular, not only cleans out the system, but also has an anti--- corrosive effect by promoting formation of a protective skin on metal surfaces and neutralising gases present in the water. We recommend the use of a suitable universal inhibitory to protect the c.h. system from cor­rosion.
6.3 Installing the bracket
Precautions
Before mounting the bracket, check that the di­mensions for fitting the exhaust fume duct are complied with (refer to the leaflet included with the flue kit, packed separately).
Utilise the paper template supplied with the boiler to determine the fixing position for the bracket and boiler. Securely mount the bracket to the wall using appropriate fixings suitable for the type of wall construction and capable of supporting the total (wet) load. Refer to the weight given in the technical data tables specific for each model.
20
Page 25
Installation
6.4 Overall dimensions
C
ø80 ø80
803
245
700
C.h. flow
50
196
35
100
60 60
47
400
115 142
Electric
connection
area
Gas
A --- a i r i n t a k e / f l u e o u t l e t p i p e ( c o --- a x i a l ) B --- flue outlet pipe ø 80 mm (twin kit) C --- air intake pipe ø 80 mm (twin kit)
B
A
ø100
73
200
31
16
257
C.h.
return
129117
200
198
Condensate drain
connection
area
A, B and C
350
6.6 Mounting the boiler
1 Take the protective caps off the boiler pipe-
work.
2 Thoroughly clean the connections.
3 Mount the boiler on its bracket.
4 Fix the c.h. valves A and gas cock B (¾”) to the
boiler using the ¾” gaskets (Fig. 6.3)
5 Fix the ø 22 mm pipes C (c.h. circuit) to the c.h.
valves A and the ø 22 mm pipe D (gas) to the cock B using the ¾” gaskets.
C
A
Boiler front
B
A
Fig. 6.3
6 Connect the pipe E (Fig. 6.4) from the pressure
relief valve to the safety discharge pipework.
7 Fit the condensate drain 10 (Fig. 6.4) in the air
brake connected to the drainage pipework. See also section 5.7 in this manual.
D
C
INSTALLATION
Fig. 6.2 (all dimensions in mm)
6.5 Joints
Functions Pipe sizes (o.d)
Gas, c.h. return, c.h. flow ø22
Pressure relief valve ø15
Condensate drain ø25(plastic)
Tab. 6.1 (sizes in mm o.d.)
10E
Fig. 6.4
21
Page 26
Installation
6.7 Fitting the flue system
Refer to the assembly instructions contained with­in the chosen flue kit packaging for the correct as­sembly and installation.
In general, it has to be taken in consideration that the horizontal sections of the flue pipe must have an horizontal sloping not less than 1.5 deg. (25 mm per metre) towards the boiler.
In the standard horizontal flue kit (Fig. 6.6A) the flue pipe is angled within the air duct therefore the air duct must be horizontally installed.
Ifoneormoreextensionshavetobeusedthey must be adequately supported so that there is no sag in the flue pipe and a minimum fall of 1,5 deg. (25 mm per metre) over the whole length towards the boiler is ensured.
Before fitting the flue system, ensure that the flue
INSTALLATION
gasket shown in Fig. 6.5 (given with the boiler) is fitted to the boiler.
only be used to discharge horizontally, it is not de­signed to enable termination in the vertical plane.
Vertical kit with 90˚ elbow (Fig. 6.6B)
Co--- axial 60/100 mm
Supplied with a straight flanged adapter a co--­axial elbow and a co ---axial pipe with terminal, this kit allows for a vertical rise of 0,5 m from the boiler. In all circumstances the flue terminal must dis­charge horizontally and the equivalent flue length must not exceed 2,7 metres.
Elbows 45˚ &90˚ (Fig. 6.6C)
Co--- axial 60/100mm.
Elbow kits enable the standard flue kitsto be offset to overcome obstructions or ensure the correct clearancesfor the flue terminal. Each elbow used in addition to the standard flanged elbow reduces the overall acceptable length of the flue system as follows:
45˚ reduce length by 0,5 m. 90˚ reduce length by 1 m.
Typ e C1 2
ø 60/100
B
Min = 0,3 m Max = 2,7 m
A
Fig. 6.5
6.8 Choice of flue
The following flue kits are available for connecting to the boiler:
Standard horizontal flue kit (Fig. 6.6A)
Co--- axial 60/100mm --- nominal length 1m
This kit is normally supplied with the boiler and can be fitted to allow discharge to the rear or either side of the boiler via the flanged boiler adapter elbow. Minimum length required is 0.3 m. Maxi­mum equivalent length of 2,7 metres can be achieved utilising extensions. This flue system can
22
ø 60/100
90˚= --- 1 m
45˚= --- 0 , 5 m
C
Fig. 6.6
Tw i n p i p e k i t s ø 8 0 m m ( F i g . 6 . 7 --- F i g . 6 . 8 --­Fig. 6.9)
Various twin (split) pipes kits and optional acces­sories (elbows) are available to assist in the ter­mination of the flue where the boiler is installed in a location remote to an outside wall.
These kits allow for separation of the air supply pipe from the pipe that discharges the exhaust gasses. Consequently it is possible to extend the flue system to a greater distance than that pro­vided by the standard horizontal co--- axial flue.
Page 27
Installation
Typ e C1 2
Fig. 6.7
If either an additional 45˚ or 90˚ accessory elbow is used then the maximum permissible length of either pipe must be reduced by 0.90 m or 1,65 m respectively.
N.B: The air intake and the flue outlet must not terminate on opposite sides of the building.
Typ e C4 2
90˚=--- 1,65 m
Typ e C8 2
Fig. 6.9
Two restrictors with different size are supplied with the twin pipe kit and have to be installed between the boiler and the air intake adapter (Fig. 6.10).
Air intake adapter
Restrictor
Gasket
INSTALLATION
Typ e C5 2
Fig. 6.8
45˚=--- 0,90 m
Fig. 6.10
For the correct use of the restrictors with twin pipes refer to Tab. 6.2.
Equivalent length (air duct + flue duct)
Between 1 and 15 m ø50mm
More than 15 m up to 30 m ø55mm
Tab . 6 . 2
Restrictor
23
Page 28
Installation
)
Vertical--- roof kit (Fig. 6.11)
Typ e C3 2
90˚= --- 1 m
max =8,5 m
ø 125
Fig. 6.11
This kit allows vertical termination of the flue pipe
INSTALLATION
through the roof. The kit is 1.2 m in length. Exten­sion pieces (Co--- axial) are also available which al­lows the flue system to be extended to a total overall maximum permissible length. Optional45˚ and 90˚ elbows can be used to offset theflueroute.
Each additionalelbow reduces the overall accept­able length of the flue system as follows:
45˚ reduce length by 0,5 m. 90˚ reduce length by 1 m.
Pluming kit (Fig. 6.12)
Co--- axial ø 60/100mm + vertical part ø 60mm (flue outlet)
Thiskitallowsthecomburentairtobesuckedup and expel the burnt gasses directly to the outside t h r o u g h a t e l e s c o p i c c o --- a x i a l f l u e ( 4 5 0 --- 9 5 0 mm).
In the last section, the fumes are expelled through a vertical section.
Extensions and elbows can be added to extend the kit’s length.
45˚= --- 0 , 5 m
Typ e C5 2
90˚=--- 0,85 m
ø60mm
45˚=--- 0,65 m
90˚= --- 1 m
ø 60/100 mm
45˚= --- 0 , 5 m
Fig. 6.12
The chart of Fig. 6.13 gives the allowable dimen­sionsoftheducts“a”and“b”ofFig.6.12
”a” vertical length (m)
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
Fig. 6.13
Each additionalelbow reduces the overall accept­able length of the flue system as follows:
45˚ (60/100 mm) reduce length by 0,5 m. 90˚ (60/100 mm) reduce length by 1 m. 45˚ (60 mm) reduce length by 0,65 m. 90˚ (60 mm) reduce length by 0,85 m.
Allowed values
”b” horizontal length (m
24
Page 29
Installation
6.9 Electrical connections
Connection to the electricity supply
1 Remove the front panel of the case (see the
section 9.2 in this manual).
2 Remove the screws F and G (Fig. 6.14).
F
G
H
Fig. 6.14
3 Loosen the screws H.
4 Remove the side panels or move the lower part
of the side panels as indicated in Fig. 6.15 and pull the control panel. When completely pulled out, the panel can ro­tate 45˚ downwards to facilitate the operations on the internal parts.
Fig. 6.15
5 Loosen the screws I and remove the service
panel (Fig. 6.16).
G
I
Fig. 6.16
Forthe electrical connection to the boiler use elec­tricwireswhichconform to the current regulations, with flexible cord, each core having a cross sec­tion area notlessthan0,75mm
6 Connect the electrical supply flexible cord
coming from the fused spur isolation switch to the power supply terminal block of the boiler (Fig. 6.17) keeping the same connections for the live (brown wire) and the neutral (blue wire). External 3 A fuse or fused plug with same current rating is recommended.
Do not connect live wires to terminals to which the room thermostat must be con­nected.
7 Connect the earth wire (yellow/green).
Connection of a room thermostat
The room thermostat must be connected to the terminal block situated next to the control panel.
Any external controls and connection lines must be rated at 230 V but under no circum­stances should external live voltage be con­nected to the room thermostat link on the boiler.
Do not connect live wires to terminals to which the room thermostat must be connected.
When connecting any type of external control, the link J in Fig. 6.17 must be removed.
2
.
INSTALLATION
25
Page 30
Installation
k
t
LN
12
External controls terminal block
Power supply terminal block
J
To f u s e d s p ur isolation switch
3
Fig. 6.17
8 Connect the room thermostat between ter-
minals 1 and 3 as shown in Fig. 6.18 or Fig. 6.19.
INSTALLATION
T
Room thermostat
(230V rating)
LN
3
Fig. 6.18
12
Power supply terminal block
External controls terminal block
9 Route the electrical supply flexible cord and
the external control flexible cord as illustrated in Fig. 6.20. Lock the flexible cordsin place with the flexible cord clamps
To t h e e x t e r n a l control de vice
To t h e f u s e d s p u r isolation switch
Fig. 6.20
6.10 External frost protection
10 Connect the frost thermostat between ter-
minals 1 and 2 as shown in Fig. 6.21 or Fig. 6.22
Do not connect live wires to terminals to which the room thermostat must be con­nected.
Frost Thermostat
(230V rating)
T
T
Room thermosta
(230V rating)
T
Room thermostat
with delay resistor
(230V rating)
LN
LN
3
Fig. 6.19
26
12
External controls terminal block
Power supply terminal block
Fig. 6.21
External controls terminal block
12
3
Power supply terminal bloc
Page 31
Installation
Room
L
12
thermostat
with anticipating
resistor
(230V rating)
N
Power supply terminal block
Frost
thermostat
(230V rating)
External controls terminal block
T
T
3
Fig. 6.22
6.11 Connecting a system bo iler
to a cylinder
Two schematic wiring diagrams are given in this section showing two possible ways to connect an
external programmer to a mid--- position diverter valve to provide independent timed and thermo­static control of heating and hot water.
Fig. 6.23 and Fig. 6.24 are divided in two parts. Theuppershowsthesinglecomponentsusedon the diagrams with their connection to the 10 way junction box. The bold numbers represent the ter­minal of the j unction box where the component must be connected to. The lower part shows how to realize a system that provides independent timed and thermostatic control of heating and hot water.
In Fig. 6.23 the boiler is permanentlyconnectedto the main supply. The boiler operation is controlled by the external control terminal block.
In Fig. 6.24 the boiler is not permanently con­nected to the supply line. The boiler operation is controlled by switching the mains supply. In this case, when the boiler is switched off some important features like the antifreeze system, the monitoring of the boiler b y the operation lights, the post circulation of the pump, etc. are completely deactivated.
For these reasons it is advisableto use the firstdia­gram (Fig. 6.23).
INSTALLATION
27
Page 32
Installation
A
L
N
INSTALLATION
L
Room thermostat
MAINS 230V a.c. Switched 3 Amp fused, spur
B
5
4
Cylinder thermostat
C
1
3
2
Room thermostat
AB
10 way
junction b ox
1
2
Progra mmer
BU
8 7
6
GRYE
WH
GY
OR
2 3
5 7
8
External control
terminal block
1
L
N
HTG
HW ON
HW OFF
2 4
6 7
LN
Power supply
BL
GRYE
WH
GY
OR
Cylinder thermostat
C
remove room thermostat link
123
bnbkbu
M i d --- p o s i t i o n diverter valve
1
2
8
1 3 2
N
MAINS 230V a.c. Switched 3 Amp fused, spur
HTG = Heati ng HW ON = Hot Water ON HW OFF = Hot Water OFF
Valve colour key
BU --- Blue GRYE --- Green/Yellow WH --- White GY --- Grey OR --- Orange BK --- Black BN --- Brown
F i g . 6 . 2 3 --- P e r m a n e n t l i v e Y --- p l a n
28
L
Progra mmer
321 4 567 1098
321 4 567 1098
N
HTG
HW ON
HW OFF
123
bnbkbu
External control
terminal block
LN
Power supply
Page 33
Installation
L
N
MAINS 230V a.c. Switched 3 Amp fused, spur
L
Room thermostat
A
B
5
4
Room thermostat
AB
1
3
2
10 way
junction b ox
Cylinder thermostat
C
L
Progra mmer
N
1
2
HTG
HW ON
HW OFF
BU
8 7
6
GRYE
WH
GY
OR
1
2
2 3
5 7
8
8 3
2
4
6 7
LN
Power supply
BU
GRYE
WH
GY
OR
Cylinder thermostat
C
Do not
remove room thermostat link
M i d --- p o s i t i o n diverter valve
1
2
INSTALLATION
N
MAINS 230V a.c. Switched 3 Amp fused, spur
HTG = Heati ng HW ON = Hot Water ON HW OFF = Hot Water OFF
Valve colour key
BU --- Blue GRYE --- Green/Yellow WH --- White GY --- Grey OR --- Orange BK --- Black BN --- Brown
L
Progra mmer
F i g . 6 . 2 4 --- N o t p e r m a n e n t l i v e Y --- p l a n
321 4 567 1098
321 4 567 1098
N
HTG
HW ON
HW OFF
123
bnbkbu
External control
terminal block
LN
Power supply
29
Page 34
7 COMMI SSIONING
WARNING The commissioning of this boiler and system must only be undertaken by a professionally qualified person in accordance with the re­quirements of the Gas Safety Installation and Use Regulations and be approved by C.O.R.G.I.
Ensure that the Benchmark Log Book is satis ­factorily completed during the commissioning process. The Log Book is located at the end of this manual. This manual should be handed to the User following completion of the installa ­tion and commissioning process. Failure to comply with these requirements may invali­date the manufacturers guarantee.
For Ireland (IE), it is necessary to complete a “Declaration of Conformity” to indicate com-
INSTALLATION
pliance to I.S.813.2002.
7.1 Electrical installation
Preliminary electrical system checks to ensure electrical safety shall be carried out by a compet­ent person. i.e. polarity, earth continuity, resis­tance to earth and short circuit.
If a fault has occurred on the appliance the fault find­ing procedure should be foll o we d as specified in the service manual.
7.2 Gas supply installation
1 Inspect the entire installation including the gas
meter, test for tightness and purge, all as de­scribed in BS 6891; For Ireland (IE), refer to I.S.813.2002.
2 Open the gas cock 12 (Fig. 7.1) on the
appliance and check the gas connector on the appliance for leaks.
12
Fig. 7.1
Open position
7.3 Initial filling of the system
1 Open the c.h. flow and return valves.
2 Remove the front panel of the case (see the
section 9.2 in this manual.
3 Lift the cap on the automatic air purger valve23
(Fig. 7.2) one full turn and leave open perma­nently.
4 Gradually open stopcock at the filling point
connection to the c.h. system until water is heard to flow; do not open fully.
23
24
Fig. 7.2
5 Open each radiator air vent starting at the
lowest point of the system and close it only when clear water, free of bubbles, flows out.
6 Purge the air from the pump by unscrewing the
pump plug 24 (Fig. 7.2); release the pump shaft by turning in the direction indicated by the arrow on the information plate.
7 Replace the pump plug.
8 Continue filling the system. The actual reading
should ideally be 1,3 bar and not less than 0,3 bar.
9 Close all air release valves on the c.h. system.
10 Inspect the boiler and the system for water
soundness and remedy any leaks discovered.
11 Cold flush the system to remove any loose par-
ticles and any system debris before startingthe boiler for the first time
The flushing procedure must be in line with BS7593 Treatment of Water in d.h.w. c.h. Sys-
tems.
30
Page 35
Commissioning
When the installation and second filling are completed turn on the c.h. system and run it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through.
This procedure must be repeated twice more.
During this operation we highly recommend the use of a c.h. flushing detergent in the quan­titiesas specified by the appropriate manufac­turer, whose function it is to dissolve any foreignmatterwhichmaybeinthesystem.
The above operation could save the invalida ­tion of your boilers guarantee and will also pre­vent problems which you may exper ience in the future if a n inhibitory is not used.
7.4 Condensate pipe and traps
The full length of the condensate pipe should be check for leaks.
The boiler has a built--- in condensate trap pro­vided with a ball valve that prevents the escape of combustion products when the trap is empty.
It is however recommended that any other trap in the drain system is correctly filled with water before to run the boiler.
7.5 Lighting the boiler
Some products incorporate an anti cycling time delay. It is normal when first switching the boiler on for the boiler to operate on heating for a few sec­onds then switch off. After 3 --- 4 minutes has elapsed the boiler will then re ignite and operate perfectly normally. The ignition delay cycle does not prevent normal operation of the boiler to pro­vide d.h.w..
If external controls are fitted (e. g. Timeclock, room thermostat) ensure they ”call for heat”.
1 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch. The appliance operation light 9 will flash every 4seconds.
2 Turn the function selector 7 as in Fig. 7.3. The
appliance operation light 9 will flash every 2 seconds.
79
6 5
Fig. 7.3
The boiler will now go through an ignition se­quence and the burner will light.
If during the ignition attempt period the boiler fails to light, the full sequence control p.c.b. will go to lockout and the lock ---out signal lamp 5 will ap­pear.
To reset the boiler press and release the boiler re­set button 6.
7.6 Checking the gas pressure at
the burner
This boiler has been tested to the highest qual­ity control standards.
The maximum and minimum gas pressures are already set during this quality control process however the checking procedure must be fol­lowedto ensure maximum operating efficiency from the boiler.
1 Remove the front panel of the case (see sec-
tion 9.2 in this manual) and the sealed chamber lid.
2 Loosen the internal screw 29 (Fig. 7.4) on the
Outlet Pressure TestPoint of the Gas Valve and connect a pressure gauge using a suitable hose.
3 Set the c.h. temperature control knob to its
maximum position. If external controls are fitted (e. g. Timeclock, room thermostat) en­sure they ”call for heat”.
4 Switchontheboiler.
5 Check the maximum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.5 or 4.6 (gas pressures at the burner), accordingly with the model of boiler installed.
INSTALLATION
31
Page 36
Commissioning
6 Check the maximum gas flow at the gas meter
and compare the value indicated in the sec­tions 4.5 or 4.6 (gas rate), accordingly with the model of boiler installed.
7 Switch off the boiler.
8 Disconnect the gas modulator coil by remov-
ing the electrical connector A (Fig. 7.4).
29
A
INSTALLATION
Fig. 7.4
9 Switchontheboiler.
10 Check the minimum gas pressure and com-
pare the value on the gauge with the value indi­cated in the sections 4.5 or 4.6 (gas pressures at the burner), accordingly with the model of boiler installed.
11 Switch off the boiler and re--- connect the elec-
trical connector A to the modulator coil.
12 Switch on the boiler .
13 Check that the boiler lights up uniformly.
If not refer to section “Ignition gas pressure ad­justment” of the Service Manualfor the necess­ary adjustment procedures.
14 Switch off the boiler and disconnect the pres-
sure gauge.
15 Reassemble the sealed chamber lid and the
front panel of the case (see section 9.2 in this manual).
If the maximum and minimum gas pressures measuredaboveare not in accordance with the technical data (sections 4.5 or 4.6) then a djust­mentwill be necessary.A full explanationof the gas pressure adjustment procedure is given in the Gas Valve section of the service manual. If
maximum a nd/or minimum gas pressures are adjusted then the ignition gas pressure must be checked and adjusted if necessary.
Important: after the gas pressure checks and any adjustment operations, all of the test points and a djustment devices must be sealed. Re ­place the adjustment protection cap.
7.7 Checking the burner ignition
1 Turn the boiler OFF
2 Open the gas valve outlet pressure test point
29 (Fig. 7.4) and connect the gauge.
3 Turn the boiler ON positioning the control se-
lectors 7 in the positions as shown in as in Fig. 7.5 and ensure that the timer selector switch and room thermostat, if fitted, are set to “heat demand”.
79
6 5
Fig. 7.5
4 Watch the gauge and check to see if the igni-
tion pressure registered corresponds to the va­lues as given in the Technical Data. Turn off the boiler and reignite it by turning the function se­lector 8 to the OFF position and then back to that indicated in Fig. 7.5
5 Repeat this process two to three times leaving
30 second intervals between each ignition. Check the ignition pressures and visually check that the burner lights uniformly and in a controlled manner.
6 If the burner ignition is not uniformly controlled
then checks should be made to:
--- the flue installation and termination.
--- that the flue gasket as shown in Fig. 6.5 page
22 is in place.
--- that the burner and injectors are clean.
--- that the boiler is set for the correct gas used
(see Section Gas Conversion of this manual)
32
Page 37
Commissioning
7 If the ignition pressure recorded is not as indi-
cated in the Technical Data then refer to section “Ignition gas pressure adjustment” of the Ser­vice Manual for the necessary adjustment pro­cedures.
Important: after the gas pressure checks and any adjustment operations, all of the test points must be sealed and replace the adjustment protection cap.
7.8 Checking the ignition device
With the burner on high flame close the gas cock. After three ignition attempts (within about three
minutes), the lock---out signal lamp 5 (Fig. 1.3 on page 2) must appear.
To reset the boiler press and release the boiler reset button 6 (Fig. 1.3 on page 2).
7.9 Checkingthefluesystem
Thefluesystemshouldbevisuallycheckedfor soundness. Check all clamps, gaskets and fixing aresecureandtight.
Ensure that the flue terminal is sited correctly in ac­cordance with the flue fitting instructions and Fig. 5.1 on page 17 of this manual.
To carry out a combustion check refer to the in­structions given in the section 9.4 of this manual.
Reference figures are given in the sections 4.5 or
4.6 of this manual (Flue gas figures).
7.10 Checking the condensate
drain pipe
Check the soundness and integrity of the conden­sate drain pipe.
Verify the cleanness and correct filling of the con­densate traps.
7.11 Instructing the user
Hand over this combined User & Installation man­ual and the Servicemanual to the end user and ex­plain how to use the unit.
Take the User step by step through the lighting in­structions.
Show the User how to switch off the appliance quickly and indicate the position of the electric supply isolator.
Explain the proper use and adjustment of all sys­tem controls; this will ensure the greatest possible fuel economy.
Explain the function and use of the function selec­tor.
Explain and demonstrate the function of time and temperature controls (if fitted).
Explain how to turn off the appliance for both short and long periods and advise on the precautions necessary to prevent damage should the appliance be inoperative when freezing condi­tions may occur.
Fill in the details required on the Boiler Guarantee Certificate and hand to the User advising them to return the correct section for boiler Guarantee reg­istration.
Finally, advise the User that, for continued safe and efficient operation, the appliance must be ser­viced by a competent person at least once a year.
INSTALLATION
33
Page 38
8 GAS CONVERSION
8.1 Warnings
The commissioning of this boiler and sys­tem must only be undertaken by a pro­fessionally qualified person in accordance with the requirements of the Gas Safety In­stallation and Use Regulations and be ap­proved by C.O.R.G.I.
Components used to adapt it to the type of gas available must be genuine parts only.
8.2 Procedures
1 Check that the gas cock (12 in Fig. 8.1) fitted
under the boiler is turned off and the appliance is switched off at the mains isolating spur.
12
Fig. 8.1
MAINTENANCE
2 Remove the front panel of the case (see the
section Generalaccessand emptying hydraulic circuits in the service manual).
3 Takeoffthelidofthesealedchamber.
4 Take the front panel of the combustion
chamber off and remove the burner (33 on page 9). See section Ignition and detection electrodes in the service manual for detailed in­structions.
5 Carry out the conversion for the type of gas, re-
placing the burner injectors correctly.
6 Re --- assemble the burner, the front panel of the
combustion chamber.
7 Switch on the appliance at the mains isolating
spur.
Closed position
8 Turn the boilerOFF positioning the function se-
lector 7 as indicated in Fig. 8.2.
79 6 58
Fig. 8.2
9 Disconnect the electrical connectors of the
C.h. temperature probe NTC 20 in Fig. 8.3
20
Fig. 8.3
10 Keep pressed the reset button 6 for about 10
seconds until the lock--- out signal lamp 5 blinks.
11 Connect the the elctrical connectors of the C .h.
temperature probe NTC 20 in Fig. 8.3
12 Press the reset button 6 repeatedly (4 times)
until the lamps 9 give the indication as in Fig. 8.4 (gas type mode).
Where: Lamp OFF
Lamp ON
Fig. 8.4
At this step it is possible to visualize the current set­ting by keeping the reset button 6 pressed for more than 5 seconds. The lamps 9 will flash a
34
Page 39
Gas conversion
number of times corresponding to the setting of the knob 8 in Fig. 8.5.
Gas type
Setting No.
NATURAL
GAS
Fig. 8.5
Gas supply
Natural gas
L.P.G. 4 165 mA
Fig. 8.6
13 Tochange the setting turn the knob 8 on a posi-
tion corresponding to the gas used as shown in Fig. 8.5. By turning the knob 8, the lock --- out signal lamp 5 blinks quickly (2 per seconds) indicat­ing that the setting has changed and must be memorised.
14 To memorize the setting keep pressed the
reset button 6 for about 5 seconds until the lamps 9 briefly blinks simultaneously.
1
Position of knob 8
1 125 mA
Approx. Max current through the modulator device
L.P.G.
4
8
15 Open the gas cock (12 in Fig. 8.7)
12
Fig. 8.7
16 To reset the boiler to the normal operation turn
it ON by the function selector 7 on the desired operation and checking the ignition pressure and that the burner lights up uniformly. In any case, the boiler automatically resets to its nor­mal operation after 10 minutes.
Factory setting = Natural gas (as illustrated)
17 Calibrate the gas valve according to the in-
structions given in the service manual, section Modulating gas valve --- Adjustment.
18 Re ---assemble the lid of the sealed chamber.
19 Replace the self --- adhesive label indicating the
type of gas, and the gas pressures to which the appliance has been set with the label included with the conversion kit. The label is placed on the botton of the appliance.
20 Replace the adjustment protection cap.
21 Replace the front panels of the case.
Open position
MAINTENANCE
35
Page 40
9 MAINTENANCE
9.1 Warnings
The procedures detailed in this chapter must be carried out only by a professionally qualified person. Thus you are advised to
contact an Authorised Service Agent.
For Ireland (IE), the servicing work must be carried out by a competent Person
For efficient and continuous operation of the boiler you are advised to have, at least once a year, maintenance and cleaning done by an Approved Service engineer.
Isolate the appliance from the electricity supply by turning off the fused spur isolation switch adjacent to the appliance and turn off the gas cock, before carrying out any pro-
cedures, whatsoever, for cleaning, mainten­ance, opening or dismantling boiler panels.
9.2 Dismantling the external
panels
Front panel
Air--- Flue e xhaust Sampling points
MAINTENANCE
1 Loosen the three screws A (Fig. 9.1).
2Liftandremovethepanel.
Side panels
3 Loosen the screws B. Bring the bottom of the
panels away from the boiler and lift them, free­ingthemfromthetophooks(Fig.9.2).
B
Fig. 9.2
9.3 Emptying the c.h. system
A
1 Close the c.h. isolating valves (11 and 13 in
Fig. 9.3).
Fig. 9.1
36
Closed position
11
1213
Fig. 9.3
Page 41
Maintenance
2 Open the central heating drain cock (21 in
Fig. 9.4).
21
Fig. 9.4
9.4 Combustion analysis check
If it is necessary to carry out a combustion analysis remove the plugs indicated in Fig. 9.1.
Reference figures are given in the sections 4.5, 4.6 of this manual (Flue gas figures).
9.5 Cleaning the primary heat
exchanger
1 Takeoffthefrontofthecase.
2 Take off the removable front of the sealed
chamberand the front panel of the combustion chamber.
If you notice dirt on the fins of the primary heat ex­changer (36 on page 9):
3 cover the sloping surfaces of the burner (33 on
page 9) entirely in a protective layer (sheets of newspaper or similar).
4 Brush out the primary heat exchanger (36 on
page 9) with a bristle paintbrush.
9.6 Checking the pressurisation
in the exp ansion vessel
Empty the central heating system as described in section 9.3 of this chapter and check that the pres­sure in the expansion vessel is not less than 1 bar. See also section 4.4 page 11 of this manual.
If the pressure is lower, take steps to correct the pressure level.
9.7 Cleaning the burner
The sloping and multi--- gas type burner (33 on page 9) does not need special maintenance, but it is sufficient to dust it with a bristle paintbrush.
To reach the burner:
1 Takeoffthefrontofthecase.
2 Take off the removable front of the sealed
chamberand the front panel of the combustion chamber.
3 Brush out the burner with a bristle paintbrush.
9.8 Checking the flue
Have the integrity of the flue outlet pipe (40 on page 10) air intake pipe (41 on page 10), checked periodically, the air pressure sensor* (16 on page
9) and the efficiency of the flue safety circuit checked at least once a year.
* For details see the section Fan and air pressure sensor in the service manual.
For all the above maintenance operations it is ad­visable to call an approved Service Engineer.
9.9 Drain pipe inspection
Check the soundness and integrity of the conden­sate drain pipe.
Verify the cleaness and correct filling of the con­densate traps.
9.10 Visual inspection of
appliance
Visually inspect all water joints, seals and connec­tions for any evidence of leakage and retighten, grease or replace them as necessary.
9.11 Gas pressures and tightness
Check appliance for gas tightness.Recheckoper­ational pressures and adjust as necessary as de­scribed in section 7.6 page 31 of this manual.
MAINTENANCE
37
Page 42
Page 43
Page 44
*1796215520*
03/12
2008
N
17962.1552.0 4908 44A5 UK
Biasi UK Ltd Newman Park, Western Way Wednesbury, WS10 7BJ Sales Tel No: 0121 506 1340 Sales Fax No: 0121 506 1360 Service Tel No: 0121 506 1350 Service Fax No: 0121 506 1370 www.biasi.co.uk
Loading...