Biamp LSI-16e User Manual

Page 1
®
Vocia
LSI-16/LSI-16e
Operation Manual
Biamp Systems, 9300 S.W. Gemini Drive, Beaverton, Oregon 97008 U.S.A. (503) 641-7287 www.biamp.com
Page 2
IMPORTANT SAFETY INSTRUCTIONS
13) Unplug this apparatus during
Explanation of safety related
1) Read these instructions.
3) Heed all warnings.
4) Follow all instructions.
WARNING - To reduce the risk of fire or electric shock, do not expose this apparatus to rain or moisture.
The apparatus shall not be exposed to dripping or splashing and no objects filled with liquids, such as vases, shall be placed on the apparatus.
5) Do not use this apparatus near water.
6) Clean only with dry cloth.
7) Do not block any ventilation openings. Install product in accordance with the manufacturer’s instructions.
8) Do not install near any heat sources such as radiators, heat registers, stoves, or other apparatus (including amplifiers) that produce heat.
CAUTION – Installation of the apparatus should be made by a qualified installation person and should conform to all applicable local codes.
Modifications and optional equipment information referenced in this manual is for use by qualified installation and service personnel only.
WARNING – Class I Safety Grounding This apparatus employs Class I Safety Grounding and must be connected to a MAINS socket with a protective eathing connection.
Disconnect Device - The MAINS plug is used to disconnect MAINS power and must remain readily operable.
9) Do not defeat the safety purpose of the grounding-type plug. A grounding type plug has two blades and a third grounding prong. The third prong is provided for your safety. If the provided plug does not fit into your outlet, consult an electrician for replacement of the obsolete outlet.
10) Protect the power cord from being walked on or pinched particularly at plugs, convenience receptacles, and the point where they exit from the apparatus.
11) Only use attachments/accessories specified by the manufacturer.
12) Use only when secured or supported by equipment rack, cart or table designed to provide adequate mechanical strength, heat dissipation and securement to the building structure.
When a cart is used, use caution when moving the cart / apparatus combination to avoid injury from tip-over.
lightning storms or when unused for long periods of time.
14) Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or has been dropped.
symbols which appear on the outside of the apparatus.
Product labeling and the operation manual may use the internationally recognized symbols defined below to note safety messages.
Lightning Bolt: Hazardous Live voltages present when this unit is in operation. Do not touch terminals marked with this symbol while the unit is connected to live power.
Exclamation Point: Replace components (i.e. fuses) only with the values specified by the manufacturer. Failure to do so will compromise safe operation of this unit.
2
Page 3
TABLE OF CONTENTS
VOCIA LIFE SAFETY INTERFACE 16 (LSI-16/LSI-16e) FEATURES ....................4
FRONT PANEL ................................................................................5-6
Setup and Use .................................................................................5
Front Panel ................................................................................... 5
(1) Power .....................................................................................5
(2) General Alarm ...............................................................................5
(3) General Fault ...............................................................................5
(4) Power Supply Fault .......................................................................... 5
(5) Protection Fault ............................................................................. 5
(6) Path Fault .................................................................................. 5
(7) System Fault ..............................................................................5-6
(8-23) General Purpose LEDs ..................................................................... 6
REAR PANEL ................................................................................ 7-14
Device ID .....................................................................................7
Network Connection ...........................................................................7-8
Monitored I/O ..................................................................................9
Sounder Outputs/Silence Input ................................................................... 9
System Fault Reset Input ........................................................................9
System Test ..................................................................................10
Voice Active Alarm ............................................................................10
General Fault, PSU Fault, Protection Fault, and Path Fault ...........................................10
Control Inputs ................................................................................ 11
PSU Fault .................................................................................... 11
Ethernet Fault ................................................................................11
Voice Alarm Silence from CIE .................................................................... 11
Voice Alarm Reset from CIE ..................................................................... 11
Emergency Inputs ............................................................................. 11
General Purpose Inputs ........................................................................12
Connection and Input Types ....................................................................13
System Fault Relay Connection .................................................................. 13
RS232 .......................................................................................13
24V DC Connector and LED .....................................................................13
IP30 Compliance .............................................................................. 13
Sourcing 24V DC for High Range Inputs ........................................................... 14
Suggested Alarm and Fault Input Connection Diagrams .............................................14
INSTALLATION .................................................................................15
SPECIFICATIONS & BLOCK DIAGRAM ................................................16-17
LSI-16 ....................................................................................... 16
LSI-16e ...................................................................................... 17
WARRANTY ....................................................................................18
EU DECLARATION ............................................................................19
EU ROHS COMPLIANT .......................................................................20
3
Page 4
VOCIA LIFE SAFETY INTERFACE 16 (LSI-16/LSI-16e)
The LSI-16/LSI-16e are networked devices that serve as an interface between a Vocia system and emergency or re alarm systems. The LSI-16/LSI-16e may accept up to three sources of power: main power is from an external, standards compliant, battery backed 24V DC source but the LSI-16/LSI-16e can also utilize Power over Ethernet (PoE) delivered via either of its two network ports. The device is equipped with parallel I/O ports for direct interface to re and emergency control equipment. The LSI-16/LSI-16e uses Ethernet-based control protocols to function within a Vocia system.
LSI-16 FEATURES
• Parallel I/O ports for direct interface with re alarm and emergency equipment
• 8 monitored I/O and 8 control inputs
• Redundant network connection and power supply options
• Power and data over a single Ethernet cable
• Local storage of conguration data
• Rotary switches for unit identication
• Accepts the Interface Module 16 (IM-16) for 16 additional general purpose inputs
• Status LEDs
• Rack mountable (1RU)
• CE marked and RoHS compliant
Up to 4 discrete emergency inputs
• Up to 500 virtual inputs via RS232 port or Ethernet
• EN 54-16 certied
• EN 60849 and AS 60849 veried
Covered by Biamp Systems’ warranty
LSI-16e FEATURES
• Parallel I/O ports for direct interface with re alarm and emergency equipment
• 8 monitored I/O and 8 control inputs
• Redundant network connection and power supply options
• Power and data over a single Ethernet cable
• Local storage of conguration data
• Rotary switches for unit identication
Up to 4 discrete emeregency inputs
• 16 additional general purpose inputs can be programmed to play an emergency message, enable zone reset or zone silence; maximum of 10 inputs can be assigned per emer­gency zone
• Each general purpose input can be programmed as TTL, high
range or monitored high range
• General purpose inputs allow monitoring for short to ground
and open circuit
• Up to 500 virtual inputs via RS232 port or Ethernet
• Provides system health monitoring via RS232 port or Ethernet
• Status LEDs
• Rack mountable (1RU)
• CE marked and RoHS compliant
• EN 54-16 certication pending
Covered by Biamp Systems’ warranty
4
Page 5
LSI-16/LSI-16e FRONT PANEL
Setup and Use
The Vocia software provides an intuitive interface for conguration and programming of the LSI-16/LSI-16e. The information supplied by this manual relates to physical connections and assignment. For more details on conguration of the LSI-16/LSI-16e, please consult the Vocia software Help File.
The LSI-16/LSI-16e governs the emergency functions of a Vocia system, monitoring and reporting faults and alarm conditions through indicators and the system software. Incorrect conguration, removal, or non-installation of some system elements may result in the LSI-16/LSI-16e reporting a fault or alarm condition. This is normal operation. For correct, fault-free operation, inputs and outputs must be connected to the LSI-16/LSI-16e as detailed below, the LSI-16/LSI-16e must detect that it is the only such device installed in the Paging World, and the system must be correctly congured and correctly operating.
Front Panel
The LSI-16/LSI-16e features twenty-three LEDs on the front plate (from left to right):
(LED 1) Power
The rst LED on the left will illuminate green if the unit is powered by main or PoE supplies.
(LED 2) General Alarm
This LED will illuminate red if the LSI-16/LSI-16e receives an alarm signal from an external emergency detection system (e.g. a re alarm system) via the Alarm inputs to the LSI-16/LSI-16e. This LED indicates the general alarm state:
1. Solid red - The LSI-16/LSI-16e has received an alarm signal from an external emergency detection system (e.g. re alarm system).
2. Flashing red - The LSI-16/LSI-16e has received a general alarm silence from an external emergency detection system (e.g. re alarm system).
(LED 3) General Fault
This LED will illuminate yellow if there is a fault in the system that does not affect the delivery of a warning message.
(LED 4) Power Supply Fault
This LED will illuminate yellow if LSI-16/LSI-16e is operating on a PoE supply but the main 24V supply fails or an external power supply fault is signaled to the LSI-16/LSI-16e.
(LED 5) Protection Fault
This LED will illuminate yellow if a system amplier channel fails and this failure does not prevent an emergency zone voice announce­ment. Note: failures that do affect emergency zone voice announcements will result in a system fault.
(LED 6) Path Fault
This LED will illuminate yellow if a fault in a transmission path is detected. The path integrity is tested from microphone capsule to end of loudspeaker lines if optional Vocia ELD-1 devices are tted at the end of the loudspeaker lines.
(LED 7) System Fault
This LED indicates the integrity of the system:
1. Flashing yellow - The unit has a fault that may prevent the reliable operation of life safety announcement functions.
2. Not illuminated - The unit is operational without any faults that may prevent reliable operation of life safety announcement functions.
5
Page 6
LSI-16/LSI-16e FRONT PANEL
(LED 7) System Fault (continued)
Because it indicates a potentially serious condition, the presence of a System Fault extinguishes indicators for PSU, Path and Protection faults so as to focus attention on the primary fault. However, individual PSU, Path and Protection faults are still shown in the system software and signaled to individual fault outputs as described below.
The LSI-16/LSI-16e will always power up in the system fault condition. Manual intervention is required to take the LSI-16/LSI-16e out of this condition. Note: this power up condition does not prevent emergency zone voice announcements provided that the system is operating reliably.
(LEDs 8–23) General Purpose LEDs
These LEDs indicate functionality of the general purpose inputs on the LSI-16e or of the LSI-16 that has been updated with an Interface Module 16 (IM-16). On an LSI-16 without an option board, these LEDs remain inactive.
• Solid Red: An Alarm is active on the associated input.
• Solid Yellow: A Fault is active on the associated input.
• Flashing Yellow: An input congured as “high range - monitored” exhibits a monitoring fault.
6
Page 7
LSI-16/LSI-16e REAR PANEL
Device ID
The rotary ID switches are located on the back of the LSI-16/LSI-16e and give the unit a unique Device ID. The switches are in hexadecimal format. To assign a Device ID of hex 07, turn the LSB switch to 7 and leave the MSB switch on 0. To create an ID of hex B7, turn the LSB switch to 7 and turn the MSB switch to B. Device ID switches should be set using a 0.1 inch (2.5mm) to 0.12 inch (3.0mm) at blade screwdriver. More information on setting IDs and the hexadecimal numbering scheme used in Vocia can be found in the Vocia Help File.
Please note: Changes made to the Device ID while connected to the network require a power cycle in order to take effect.
Network Connection
The LSI-16/LSI-16e has two RJ45 Ethernet connectors. These provide redundant network capability as well as a secondary source of power (PoE). If communication is lost on either Ethernet port, the LSI-16/LSI-16e reports a fault. For this reason, both Ethernet ports must be connected to the Vocia network. To provide Auxiliary power PoE should be supplied to both Ethernet ports. An LED adjacent to each RJ45 connector indicates that PoE is being supplied via that port.
The RJ45 connectors utilize standard copper Ethernet cabling to interface the LSI-16/LSI-16e to the Vocia system via a PoE­compliant network switch.
Left LED Right LED Description
None None No power or data connectivity. Please check the PoE network connection.
Yellow Flashing
green
Yellow None There is a network link but the port is redundant.
The RJ45 connector provides two LEDs that indicate Ethernet link and network activity (see table below).
Network link established and indicates the port is currently in use.
7
Page 8
This connection carries control data and power over a single Ethernet cable. The maximum distance between any unit and an Ethernet
LSI-16 / LSI-16e
switch is 328 feet (100 meters) when using copper cabling. Additional Ethernet switches and/or ber-optic cable can be used to further extend distances between units on a network. Note: A managed Ethernet switch is required for redundant network wiring (spanning-tree conguration or similar).
If non-Vocia network trafc shares an Ethernet switch with the Vocia network, separate VLANs must be established. All Ethernet wiring must be accomplished using shielded CAT5, CAT5e, CAT6 or CAT7 cable.
For standards-compliant systems, a managed switch with dry contact fault output is required.
LSI-16
BIAMP SYSTEMS
Designed in Australia
Assembled in USA
GND
YEL: in use GRN :link/act
PoE IEEE 802.3af
Class 3
LSI-16/LSI-16e REAR PANEL
10
N24138
0832
0832-CPD-1401
Device ID
21
LSB
MSB
52S
321 Monitored Outputs
Option A Option B
54
10V
876
(100mA)
54
1
32
876
54
321
Control InputsSystem Fault
876
54
32114131211109
NCC
NO
Power
Class 2 or LPS
14131211109
24V
15W
876
RS232
Ethernet switch with PoE
Model LSI-16
LSI-16e
LSI-16 / LSI-16e
BIAMP SYSTEMS
Designed in Australia
Assembled in USA
GND
YEL: in use GRN :link/act
PoE IEEE 802.3af
Class 3
10
N24138
Device ID
21
MSB
LSB
321 Monitored Outputs
Option A Option B
54
876
10V
(100mA)
54
32
1
54
321
Control InputsSystem Fault
54
32114131211109876
876
NCC
NO
RS232
Power
Class 2 or LPS
14131211109876
24V DC
15W
Model LSI-16
Ethernet switch without PoE
PoE
injector
AC Power
8
Page 9
LSI-16/LSI-16e REAR PANEL
Monitored I/O
Two black ve-position connectors are located next to the rotary switches. These are predominantly used for monitored inputs and outputs (I/O) to external lamps or sounders. Individual connections are labeled 1 through 8 as indicated below. One connection is congured for use as both an input and an output (1) and one as an input (2) (see table below for connector assignments).
Marking Function
Ground
1 Sounder Output / Silence Input
2 System Fault Reset Input
3 Voice Alarm Active
4 General Fault
5 PSU Fault
6 Protection Fault
7 Path Fault
8 External Supply Over-voltage Monitor
10V 10V Out
The inputs/outputs will sink current (pull low) when active (see the Specications section of this document for more details). The desired load (lamp, LED, etc.) must be connected between the input/output terminal and a positive voltage reference.
It should be noted that external switches and a sounder connected to the rst two inputs are typically mandatory for standards compliance. The location and physical attributes of these items may be required to conform with local norms. The switches and sounder must be wired according to the connection diagram provided below.
For each of these inputs/outputs, a load must be connected between each output and the positive voltage source. If any output on ter­minals 1 through 8 is unused, the output must be connected through an external resistor to the positive side of the voltage source (either 10V Out or user-supplied external source). To ensure correct functionality, the value of each resistor should be 22kΩ. An internally derived 10V source is provided at the 10V Out terminal; however, the total current available from this pin is limited to 100mA. This voltage source may be used for external devices provided the total load is less than 100mA. For higher-current devices, a user-supplied external volt­age source of up to 35V may be used, with the negative side connected to the pin. Due to monitoring constraints, it is impossible to use both the internal 10V source and an external source. For monitoring purposes, the positive side of the voltage source (either 10V Out or user-supplied external source) must be connected to the External Supply Over-voltage Monitor (terminal 8), as well as supplying voltage to external devices.
(I/O 1) Sounder Output/Silence Input
This connection functions as a dual purpose alarm sounder output and silence input (see connection diagram below).
Sounder Output
This output connects to a local sounder for fault and alarm warnings. A sounder is typically required for standards compliance. Note: If an emergency microphone is located near the sounder, it may be congured in Vocia software to mute the sounder while making live announcements. Silence Input This input is used to silence the local sounder. The sounder will restart in response to any new fault or alarm.
(I/O 2) System Fault Reset Input
This input is required to take the LSI-16/LSI-16e out of System Fault condition. Note: the LSI-16/LSI-16e will always power up in a system fault state (see connection diagram).
9
Page 10
LSI-16/LSI-16e REAR PANEL
(I/O 3) Voice Alarm Active
This output is active when messages are playing in response to an alarm input. This output provides indication of when a message is playing or when a message has been muted. Constant active output - indicates a message is playing in response to an alarm input. Cyclic output (1.25Hz) - indicates the message has been muted.
(I/O 4-7) General Fault, PSU Fault, Protection Fault and Path Fault
These outputs will be activated by the same alarm conditions as identically named LEDs on the front panel (described above). Note however that these outputs will be activated by the faults listed above irrespective of whether a System Fault has been activated.
The Voice Alarm Active, General Fault, PSU Fault, Protection Fault and Path Fault outputs are monitored for open-circuit or short-circuit to ground or power supply and for over-voltage on the output pin (>35V DC). If incorrect conditions are detected a Fault is signaled. Output monitoring facilitates compliance with voice evacuation standards.
System Test
A system test can be initiated by simultaneously connecting monitored outputs 1 and 2 to ground (see connection diagram). A system test runs a diagnostic test, part of which illuminates each LED in turn and momentarily activates the sounder.
Connection Diagram: external switches and sounder (Note: 10V supply may be derived from the LSI-16/LSI-16e Outputs Connector)
SW1 System Fault Reset (e.g. EAO 31-453 or equivalent switch)
SW2 System Test (e.g. EAO 31-453 or equivalent switch)
SW3 Silence Local Sounder (e.g. EAO 31-453 or equivalent switch)
D1 and D2 1N4004 or equivalent general purpose 1A diode
R1 and R2 22kΩ 0.25 watt resistor
S1 Piezo (or similar) sounder - tone and sound pressure level may be required to
comply with local norms
10
Page 11
LSI-16/LSI-16e REAR PANEL
Control Inputs
Two ve-position plug-in barrier strip connectors provide control input connections. Eight separate channels plus two ground pins are provided (see table below for connector assignments). Control inputs are fully isolated from all connections in the LSI-16/LSI-16e.
Marking Function
Ground
1 PSU Fault (contact closure indicates a PSU Fault)
2 Ethernet Fault
3 Voice Alarm Silence from CIE (common for all zones)
4 Voice Alarm Reset from CIE (common for all zones)
Ground
5 Emergency Input 1
6 Emergency Input 2
7 Emergency Input 3
8 Emergency Input 4
Input Activation Conditions Control Inputs 1 and 2
To activate an input, it must be connected to an external circuit that returns to either of the two pins. The resistance of this circuit must be less than 4kΩ.
Control Inputs 3 to 8
These inputs must be permanently connected to an external circuit that returns to either of the two pins. The resistance of this circuit must be between 1kΩ and 4kΩ. To activate an input, pull the input to a voltage between 12 and 24V.
(Input 1) PSU Fault
This input may be derived from the primary 24V power supply to indicate to the LSI-16/LSI-16e if there is a fault in the power supply. This may be required for standards compliance.
(Input 2) Ethernet Fault
This input can be derived from an Ethernet switch to monitor the Ethernet network connection between the LSI-16/LSI-16e and amplier. This may be required for standards compliance.
(Input 3) Voice Alarm Silence from CIE (re alarm system)
This input is a signal from the CIE (re alarm system) that will mute emergency messages in all emergency zones.
(Input 4) Voice Alarm Reset from CIE (re alarm system)
This input is a signal from the CIE (re alarm system) that will reset emergency messages in all emergency zones.
(Inputs 5-8) Emergency Inputs
These four inputs are used to connect to the re alarm control and indicating equipment (CIE) and notify the LSI-16/LSI-16e that an alarm has occurred on a particular zone. Four such zone inputs may be connected; one emergency message or mute can be assigned per zone. Additional zone inputs are available with the IM-16. When an alarm is detected, the Vocia system will enter Emergency Mode as congured for that input. During Emergency Mode, some or all of the Vocia system will cease normal operation and operate as pro-
grammed for the emergency.
11
Page 12
LSI-16/LSI-16e REAR PANEL
1 2 3 4 6 7 8
24v
5
1 2
3
4
5
6
7
8 9
10
11
12
13
14
1 2
3
4
5
6
7
8 9
10
11
12
13
14
9 10 11 12 14 15 16
24v
13
Option A
Pin
Function
Option B
Pin
Function
General Purpose Inputs
These connections provide functionality of the option inputs on the LSI-16e or of the LSI-16 that has been upgraded with an Interface Module (IM-16). On an LSI-16 without an option board, these connections will remain inactive.
Two connectors, labeled Option A and Option B, are located on the back of the LSI-16e. Each slot consists of 14 pins which are labeled 1 to 14. Each connector bank allows for the following connection:
Chassis Ground: One connection per connector bank.
• Isolated Ground: Four connections per connector bank.
• Control Inputs: Eight connections per connector bank.
24 Volts DC - One output per connector. Internally sourced, this will allow up to 60mA to be shared over all general purpose inputs.
Pin-out
Pin Option A Function Option B Function
1 Chassis Ground/Shield Chassis Ground/Shield
2 General Purpose Input 1 Control Input 9
3 General Purpose Input 2 Control Input 10
4 Isolated Ground Isolated Ground
5 General Purpose Input 3 Control Input 11
6 General Purpose Input 4 Control Input 12
7 Isolated Ground Isolated Ground
8 General Purpose Input 5 Control Input 13
9 General Purpose Input 6 Control Input 14
10 Isolated Ground Isolated Ground
11 General Purpose Input 7 Control Input 15
12 General Purpose Input 8 Control Input 16
13 Isolated Ground Isolated Ground
14 24V (60mA total, shared across all inputs) 24V (60mA total, shared across all inputs)
12
Page 13
LSI-16/LSI-16e REAR PANEL
SECTION HEAD
Connections and Input Types
External Connections
Both Chassis Ground ( ) and Isolated Ground ( ) are available on the IM-16 connectors.
By default, all input circuits are isolated with respect to the LSI-16 ground. Any external input connections must be logic referenced to the Isolated Ground. This conguration allows external equipment to be interconnected to the LSI-16 without ground current interaction between devices.
The IM-16 ground appears on a single terminal (Pin 1) on each of the two connector banks (‘Option A’ and ‘Option B’). This should only be used if circuit isolation is not required and should only be connected to the cable screen.
The two issolated grounds of the IM-16 board are connected internally. For ease of wiring each connector, every Control Input pair has an Isolated Ground connection adjacent to it.
Types of Input Circuit
The logic level of each input on the IM-16 may be independently determined in the Vocia software to operate one of three ways. These are;
• TTL: 2V to 5V logic sense. To enable a TTL input, apply a TTL logic high with respect to Isolated Ground. This can be congured in software to detect a low to high or high to low transition.
• High Range: To enable a High Range input, use a dry contact to switch the input to a voltage of 24V DC with respect to Isolated Ground. This can be congured in software to detect a low to high or high to low transition.
• High Range – Monitored: This circuit is implemented in the same way as the ‘High Range’ input. This option allows monitoring of each input for short to ground and open circuit. In order to sense open circuit, a terminating resistor must be tted between each Control Input and Isolated Ground at the far end of the input circuit being sensed. The IM-16 will sense open circuits on the line between its input and the terminating resistor. Shorts to Isolated Ground are sensed across the entire line being monitored. A 6k8Ω resistor should be used for each input. If a monitoring fault is detected on any input the logic state or transitions on that input will be ignored until the fault is cleared. High Range – Monitored inputs require a low to high transition to enable the input (transition direction not congurable).
System Fault Relay Connection
This relay is activated when the LSI-16/LSI-16e is fully operational. It may be used for informing external devices about the LSI-16/LSI-16e’s operating conditions or sounding an alarm that indicates the LSI-16/LSI-16e is not functioning reliably.
RS232
The RS232 port can be used to send VTP commands to the LSI-16/LSI-16e and monitor Vocia system health. Please see Help Files for details.
24V DC Connector and LED
This is the primary (main) power supply input for the LSI-16 and as such must be fed from a suitable source of 24V DC capable of 15 watts (625mA). The 24V DC supply has to be sourced separately. In typical installations, this supply will be provided from a power supply compliant with local norms and required standards (typically battery-backed). The adjacent LED indicates the presence of power.
Sourcing 24V DC for High Range Inputs
The High Range logic inputs should be driven from a contact closure (relay or switch) in connected equipment. The High Range inputs expect to sense a transition from low-state voltage (0-11V) to high-state voltage (12-30V). A 24V Logic High Reference output voltage is provided by the IM-16 for this purpose. Alternatively an external 24V reference may be used. If an external supply is used, the ground connection of the external supply must be wired to the IM-16 Isolated Ground.
IP30 Compliance
The LSI-16 is designed for ingress protection to the IP30 standard. In order to maintain this compliance, any unused terminal connectors on the back of the unit must be tted with the supplied terminal blocks.
13
Page 14
LSI-16/LSI-16e REAR PANEL
Suggested Alarm and Fault Input Connection Diagrams
SECTION HEAD
High Range Monitored
(24V provided externally)
Active State: High
COM
+
24V
-
9 10 11 12 14 15 1613
High Range Unmonitored (24V provided externally)
Active State: High
COM
+
24V
-
CIE Relay
NO
NC
CIE Relay
NO
NC
High Range Monitored
(24V provided by IM-16)
Active State: High
CIE Relay
NO
COM
6.8kΩ
24v
9 10 11 12 14 15 16
NC
13
6.8kΩ
24v
High Range Unmonitored
(24V provided by IM-16)
Active State: High
CIE Relay
NO
COM
NC
9 10 11 12 14 15 1613
High Range Unmonitored
24V (External/CIE Provided)
Active State: Low
CIE Relay
NO
COM
NC
+
24V
-
9 10 11 12 14 15 1613
24v
24v
5V TTL Logic
Active State: Voltage Dependant
CIE
+
TTL Logic
Output
(5v)
-
9 10 11 12 14 15 16
13
High Range Unmonitored
24V (IM-16 Provided)
Active State: Low
CIE Relay
NO
COM
NC
9 10 11 12 14 15 16
13
24v
24v
9 10 11 12 14 15 1613
14
24v
Page 15
LSI-16/LSI-16e INSTALLATION
Installation
The LSI-16/LSI-16e requires one 1.75 inches (44.45mm) high and 19 inches (483mm) wide rack space with 10 inches (254mm) depth.
Mounting the unit using four screws with washers will prevent marring of the front panel. PVC or nylon washers are appropriate.
Please install the unit away from heat sources, such as vents and radiators, and in rooms with adequate ventilation. Ensure that air can circulate freely behind, beside, and above the unit. Do not exceed the maximum ambient operating temperature of 32-113 degrees F (0­45°C). Be aware of conditions in an enclosed rack that may cause the temperature to exceed ambient room conditions.
Note: To operate correctly, the LSI-16/LSI-16e requires input and output connections to external components and devices as described in this manual.
15
Page 16
Life Safety Interface 16 SPECIFICATIONS
System Fault Relay:
Type:
Load: Maximum operating voltage: Maximum operating current: Maximum switching capacity: Minimum permissible load:
Control Inputs:
Number: Type: Cathode presented at input – pull low to enable. Sink Current: Min: Max: Maximum Terminal Voltage: Isolation:
Single ‘Form C’ voltage-free SPST
LSI-16 SPECIFICATIONS
RS232 Port
Type:
change-over contact
Resistive
125VAC, 60VDC
600mA AC, 1A DC
37.5VA, 30W
10µA @ 10mVDC
Eight
Opto Isolator LED
1mA 6mA
24V 3kV
Baud Rate:
Connection:
Power:
Main: PoE:
Base Dimensions:
Height: Width: Depth:
DTE
57600
RJ45 with shielded Ethernet/PoE cable
(CAT5, CAT 5e, CAT6, or CAT7)
24V DC 15W
802.3af Class 3
1.75 inches (44.5mm) 19 inches (483mm)
10 inches (254mm
Monitored I/O:
Number: Type:
Maximum Continuous Current: Current Limit: Maximum External Supply: VMon Input Shutdown:
Life Safety Interface 16 BLOCK DIAGRAM
LEDs
ID Switches
Vocia
System
PoE
24V DC
FET switch, open drain
Eight
(low side driver)
0.35A
0.8A 35V 35V
Host Processor
Weight:
Ambient Operating Temperature Range:
Compliance:
8 Control Inputs
8 Monitored Outputs
IM-16 (optional)
Approx 6.4 lbs. (2.8kg)
32-113 degrees F (0-45 degrees C)
FCC Part 15, class B
EC marked
EN 54-16 certified
RoHS Directive
UL 60065 Listed, E215636
C-UL Listed, E215636
C-Tick, N24138 (Australia)
16
Page 17
Life Safety Interface 16e SPECIFICATIONS
System Fault Relay:
Type:
Load: Maximum operating voltage: Maximum operating current: Maximum switching capacity: Minimum permissible load:
Control Inputs:
Number: Type: Cathode presented at input – pull low to enable. Sink Current: Min: Max: Maximum Terminal Voltage: Isolation:
Single ‘Form C’ voltage-free SPST
LSI-16e SPECIFICATIONS
SECTION HEAD
RS232 Port
Type:
change-over contact
Resistive
125VAC, 60VDC
600mA AC, 1A DC
37.5VA, 30W
10µA @ 10mVDC
Eight
Opto Isolator LED
1mA 6mA
24V 3kV
Baud Rate:
Connection:
Power:
Main: PoE:
Base Dimensions:
Height: Width: Depth:
DTE
57600
RJ45 with shielded Ethernet/PoE cable
(CAT5, CAT 5e, CAT6 or CAT7)
24V DC 15W
802.3af Class 3
1.75 inches (44.5mm) 19 inches (483mm)
10 inches (254mm
Monitored I/O:
Number: Type:
Maximum Continuous Current: Current Limit: Maximum External Supply: VMon Input Shutdown:
Option Inputs:
Number: High Range Logic Low: High Range Logic High: High Range Hysteresis: TTL Logic Low: TTL Logic High: TTL Hysteresis: Input Transient Protection: Input Isolation:
FET switch, open drain (low
500V RMS (isolation from LSI-16)
Life Safety Interface 16e BLOCK DIAGRAM
LEDs
ID Switches
Vocia
System
PoE
24V DC
Eight
side driver)
0.35A
0.8A 35V 35V
16
0-11 DC
12-30 DC
1V ± 20%
0-0.8V
2-5V
1V ± 20%
± 8KV peak
Host Processor
Weight:
Ambient Operating Temperature Range:
Compliance:
8 Control Inputs
8 Monitored Outputs
16 General Purpose
Approx 6.4 lbs. (2.8kg)
32-113 degrees F (0-45 degrees C)
FCC Part 15, class B
CE marked
EN 54-16 certification pending
RoHS Directive
UL 60065 Listed, E215636
C-UL Listed, E215636
C-Tick, N24138 (Australia)
Inputs
17
Page 18
LSI-16/LSI-16e WARRANTY
BIAMP SYSTEMS IS PLEASED TO EXTEND THE FOLLOWING 5-YEAR LIMITED WARRANTY TO THE ORIGINAL PURCHASER OF THE PROFESSIONAL SOUND EQUIPMENT DESCRIBED IN THIS MANUAL
1. BIAMP Systems warrants to the original purchaser of new products that the product will be free from defects in material and workmanship for a period of 5 YEARS from the date of purchase from an authorized BIAMP Systems dealer, subject to the terms and conditions set forth below.
2 If you notify BIAMP during the warranty period that a BIAMP Systems product fails to comply with the warranty, BIAMP Systems
will repair or replace, at BIAMP Systems’ option, the nonconforming product. As a condition to receiving the benets of this warranty, you must provide BIAMP Systems with documentation that establishes that you were the original purchaser of the products. Such evidence may consist of your sales receipt from an authorized BIAMP Systems dealer. Transportation and insurance charges to and from the BIAMP Systems factory for warranty service shall be your responsibility.
3. This warranty will be VOID if the serial number has been removed or defaced; or if the product has been altered, subjected to damage, abuse or rental usage, repaired by any person not authorized by BIAMP Systems to make repairs; or installed in any manner that does not comply with BIAMP Systems’ recommendations.
4. Electro-mechanical fans, electrolytic capacitors, gooseneck microphones, cords connecting handheld microphones, hard-drives, displays, and normal wear and tear of items such as paint, knobs, handles, keypads and covers are not covered under this war­ranty. All server-based devices are warranted for 3 years only.
5. This warranty is in lieu of all other warranties, expressed or implied. Biamp Systems disclaims all other warranties, expressed or implied, including, but not limited to, implied warranties of merchantability and tness for a particular purpose.
6. The remedies set forth herein shall be the purchaser’s sole and exclusive remedies with respect to any defective product.
7. No agent, employee, distributor or dealer of BIAMP Systems is authorized to modify this warranty or to make additional warran­ties on behalf of BIAMP Systems. Statements, representations or warranties made by any dealer do not constitute warranties by BIAMP Systems. BIAMP Systems shall not be responsible or liable for any statement, representation or warranty made by any dealer or other person.
8. No action for breach of this warranty may be commenced more than one year after the expiration of this warranty.
9. BIAMP Systems shall not be liable for special, indirect, incidental, or consequential damages, including lost prots or loss of use
arising out of the purchase, sale, or use of the products, even if BIAMP Systems was advised of the possibility of such damages.
18
012011_585.0245.90B
Page 19
COMPLIANCE
 DoC VLSI201101
EC Declaration of Conformity
Biamp Systems Corporation, as manufacturer having sole responsibility, hereby declares that the following described product complies with the applicable provisions of the DIRECTIVES below except as noted herein. Any alterations to the product not agreed upon and directed by Biamp Systems Corporation will invalidate this declaration.
Product Model
Product Description
Applicable EC Directives
LVD Directive (2006/95/EC) Safety EN 60065:2002
EMC Directive (2004/108/EC) Emissions EN 55103-1:1996, Environment E2 Immunity EN 55103-2:1996, Environment E2
Special Considerations for Product Environment or Compliance
Use only CE marked Power over Ethernet (PoE) device.
Use only CE and “LPS” marked 24 VDC External Power Adaptor.
Shielded cabling must be used for system connections.
Technical Construction File, Location and Contact
Biamp Systems Corporation phone: (503) 641.7287 9300 S.W. Gemini Drive fax: (503) 626.0281 Beaverton, OR USA 97008 e-mail: biamp@biamp.com
Authorized Representative: Larry Copley, Compliance Engineer
: Vocia® LSI-16, LSI-16e
: Life Safety Interface for networking with audio DSPs
: Applicable Harmonized Standards:
:
:
Authorized Signature:
Revised: January 2011
19
Page 20
COMPLIANCE
EU RoHS COMPLIANT
This Biamp product, including all attendant cables and accessories supplied by Biamp, meets all requirements of EU Directives 2002/95/EC of January 27, 2003, and 2005/618/EC of August 18, 2005, the EU RoHS Directives. An EU RoHS Materials Content Declaration document may be obtained at www.biamp.com
(This information is presented to comply with the requirements of Chinese law SJ/T11363-2006)”
有害物质表
Biamp Systems Corporation
生命安全接口 (Life Safety Interface)
Vocia LSI-16, LSI-16e
部件名称
设备机箱(Equipment Chassis)
插拔式接线端子 (Plug-in Terminal Blocks) 光盘(CD ROM) 手册和其他书面文档 (Manual and Documentation) 包装箱和所有包装材料 (Box and Packing Materials)
󰥎󰱆󰥎󰈣󰾼质或元󱘼
Pb 铅Hg汞Cd 镉Cr+6
PBB PBDE
六价铬
X O X O O O O O O O O O
O O O O O O O O O O O O O O O O O O
0:表示该部件所有均质材料中的这种有毒有害物质低于 SJ/T11363-2006 的限制要求.
X:表示该部件中至少有一种均质材料所含的这种有毒有害物质高于 SJ/T11363-2006 的限制要求.
在电触头和(或)镀镉所含的均质材料中,镉及其化合物的含量可以超过 0.01%,但欧盟指令 91/338/EEC(根据欧盟指令 76/769/EEC)限制销售和使用某些危险物质和制剂部分中所禁止的用途除外
在以下一种或多种物质所含的均质材料中,铅及其化合物的含量可以超过 0.1%:
1) 电子元器件中玻璃内所含的铅
2) 铅在钢材中是作为一种合金元素,含量可达 0.35%
3) 铅在铝材中是作为一种合金元素,含量可达 0.4%
4) 铅在铜材中是作为一种合金元素,含量可达 4%
5) 高熔点类焊料中的铅(即铅料合金,铅含量超过 85%
6) 电子陶瓷部件内的铅
7) 由两种以上元素组成的焊料中所含的铅,用于连接针脚和微处理器包装,其中 铅的含量超过 80% 但低于 85%
8) 顺应针连接系统内的铅
9) 󱳾󱥭󰾣󰉞󱳾󱥭󰾣载体之间形成󲓸󰜳󰙓󱅋焊料中󱈼
在正常使用情况下,中国环保使用期限为 10 年,条件是:
环境温度为 0-40C (32-104°F)
湿度为 0-95%,无凝结
海拔高度为 0-10,000 英尺
气流不受阻碍
没有水或其他液体进入任何部件
电源为 IEEE 802.3af PoE
部件没有损坏(损坏部件应立即修理)
󱅒󰍠󰜝󱅋󰙶󱈼󰥻󰡒󱲶󰙓󰥎
20
Loading...