WARNING - To reduce the risk of fire or
electric shock, do not expose this
apparatus to rain or moisture.
The apparatus shall not be exposed to
dripping or splashing and no objects filled
with liquids, such as vases, shall be
placed on the apparatus.
5) Do not use this apparatus near water.
6) Clean only with dry cloth.
7) Do not block any ventilation openings.
Install product in accordance with the
manufacturer’s instructions.
8) Do not install near any heat sources
such as radiators, heat registers, stoves,
or other apparatus (including amplifiers)
that produce heat.
CAUTION – Installation of the apparatus
should be made by a qualified installation
person and should conform to all
applicable local codes.
Modifications and optional equipment
information referenced in this manual is
for use by qualified installation and
service personnel only.
WARNING – Class I Safety Grounding
This apparatus employs Class I Safety
Grounding and must be connected to a
MAINS socket with a protective eathing
connection.
Disconnect Device - The MAINS plug is
used to disconnect MAINS power and
must remain readily operable.
9) Do not defeat the safety purpose of
the grounding-type plug. A grounding
type plug has two blades and a third
grounding prong. The third prong is
provided for your safety. If the provided
plug does not fit into your outlet, consult
an electrician for replacement of the
obsolete outlet.
10) Protect the power cord from being
walked on or pinched particularly at
plugs, convenience receptacles, and the
point where they exit from the apparatus.
11) Only use attachments/accessories
specified by the manufacturer.
12) Use only when secured or supported
by equipment rack, cart or table designed
to provide adequate mechanical strength,
heat dissipation and securement to the
building structure.
When a cart is used, use
caution when moving the
cart / apparatus combination
to avoid injury from tip-over.
lightning storms or when unused for long
periods of time.
14) Refer all servicing to qualified service
personnel. Servicing is required when the
apparatus has been damaged in any way,
such as power-supply cord or plug is
damaged, liquid has been spilled or
objects have fallen into the apparatus,
the apparatus has been exposed to rain
or moisture, does not operate normally,
or has been dropped.
symbols which appear on the outside
of the apparatus.
Product labeling and the operation
manual may use the internationally
recognized symbols defined below to note
safety messages.
Lightning Bolt: Hazardous
Live voltages present when
this unit is in operation. Do
not touch terminals marked
with this symbol while the unit
is connected to live power.
Exclamation Point: Replace
components (i.e. fuses) only
with the values specified by
the manufacturer. Failure to
do so will compromise safe
operation of this unit.
2
Page 3
TABLE OF CONTENTS
VOCIA LIFE SAFETY INTERFACE 16 (LSI-16/LSI-16e) FEATURES ....................4
FRONT PANEL ................................................................................5-6
Setup and Use .................................................................................5
Front Panel ................................................................................... 5
(1) Power .....................................................................................5
(2) General Alarm ...............................................................................5
(3) General Fault ...............................................................................5
(4) Power Supply Fault .......................................................................... 5
EU DECLARATION ............................................................................19
EU ROHS COMPLIANT .......................................................................20
3
Page 4
VOCIA LIFE SAFETY INTERFACE 16 (LSI-16/LSI-16e)
The LSI-16/LSI-16e are networked devices that serve as an interface between a Vocia system and emergency or re alarm systems.
The LSI-16/LSI-16e may accept up to three sources of power: main power is from an external, standards compliant, battery backed 24V
DC source but the LSI-16/LSI-16e can also utilize Power over Ethernet (PoE) delivered via either of its two network ports. The device is
equipped with parallel I/O ports for direct interface to re and emergency control equipment. The LSI-16/LSI-16e uses Ethernet-based
control protocols to function within a Vocia system.
LSI-16 FEATURES
• Parallel I/O ports for direct interface with re alarm
and emergency equipment
• 8 monitored I/O and 8 control inputs
• Redundant network connection and power supply options
• Power and data over a single Ethernet cable
• Local storage of conguration data
• Rotary switches for unit identication
• Accepts the Interface Module 16 (IM-16) for 16 additional
general purpose inputs
• Status LEDs
• Rack mountable (1RU)
• CE marked and RoHS compliant
• Up to 4 discrete emergency inputs
• Up to 500 virtual inputs via RS232 port or Ethernet
• EN 54-16 certied
• EN 60849 and AS 60849 veried
• Covered by Biamp Systems’ warranty
LSI-16e FEATURES
• Parallel I/O ports for direct interface with re alarm
and emergency equipment
• 8 monitored I/O and 8 control inputs
• Redundant network connection and power supply options
• Power and data over a single Ethernet cable
• Local storage of conguration data
• Rotary switches for unit identication
• Up to 4 discrete emeregency inputs
• 16 additional general purpose inputs can be programmed
to play an emergency message, enable zone reset or zone
silence; maximum of 10 inputs can be assigned per emergency zone
• Each general purpose input can be programmed as TTL, high
range or monitored high range
• General purpose inputs allow monitoring for short to ground
and open circuit
• Up to 500 virtual inputs via RS232 port or Ethernet
• Provides system health monitoring via RS232 port or Ethernet
• Status LEDs
• Rack mountable (1RU)
• CE marked and RoHS compliant
• EN 54-16 certication pending
• Covered by Biamp Systems’ warranty
4
Page 5
LSI-16/LSI-16e FRONT PANEL
Setup and Use
The Vocia software provides an intuitive interface for conguration and programming of the LSI-16/LSI-16e. The information supplied by this
manual relates to physical connections and assignment. For more details on conguration of the LSI-16/LSI-16e, please consult the Vocia
software Help File.
The LSI-16/LSI-16e governs the emergency functions of a Vocia system, monitoring and reporting faults and alarm conditions through
indicators and the system software. Incorrect conguration, removal, or non-installation of some system elements may result in the
LSI-16/LSI-16e reporting a fault or alarm condition. This is normal operation. For correct, fault-free operation, inputs and outputs must be
connected to the LSI-16/LSI-16e as detailed below, the LSI-16/LSI-16e must detect that it is the only such device installed in the Paging
World, and the system must be correctly congured and correctly operating.
Front Panel
The LSI-16/LSI-16e features twenty-three LEDs on the front plate (from left to right):
(LED 1) Power
The rst LED on the left will illuminate green if the unit is powered by main or PoE supplies.
(LED 2) General Alarm
This LED will illuminate red if the LSI-16/LSI-16e receives an alarm signal from an external emergency detection system (e.g. a re alarm
system) via the Alarm inputs to the LSI-16/LSI-16e. This LED indicates the general alarm state:
1. Solid red - The LSI-16/LSI-16e has received an alarm signal from an external emergency detection system (e.g. re alarm system).
2. Flashing red - The LSI-16/LSI-16e has received a general alarm silence from an external emergency detection system (e.g. re
alarm system).
(LED 3) General Fault
This LED will illuminate yellow if there is a fault in the system that does not affect the delivery of a warning message.
(LED 4) Power Supply Fault
This LED will illuminate yellow if LSI-16/LSI-16e is operating on a PoE supply but the main 24V supply fails or an external power supply fault is
signaled to the LSI-16/LSI-16e.
(LED 5) Protection Fault
This LED will illuminate yellow if a system amplier channel fails and this failure does not prevent an emergency zone voice announcement. Note: failures that do affect emergency zone voice announcements will result in a system fault.
(LED 6) Path Fault
This LED will illuminate yellow if a fault in a transmission path is detected. The path integrity is tested from microphone capsule
to end of loudspeaker lines if optional Vocia ELD-1 devices are tted at the end of the loudspeaker lines.
(LED 7) System Fault
This LED indicates the integrity of the system:
1. Flashing yellow - The unit has a fault that may prevent the reliable operation of life safety announcement functions.
2. Not illuminated - The unit is operational without any faults that may prevent reliable operation of life safety announcement functions.
5
Page 6
LSI-16/LSI-16e FRONT PANEL
(LED 7) System Fault (continued)
Because it indicates a potentially serious condition, the presence of a System Fault extinguishes indicators for PSU, Path and Protection
faults so as to focus attention on the primary fault. However, individual PSU, Path and Protection faults are still shown in the system
software and signaled to individual fault outputs as described below.
The LSI-16/LSI-16e will always power up in the system fault condition. Manual intervention is required to take the LSI-16/LSI-16e out of
this condition. Note: this power up condition does not prevent emergency zone voice announcements provided that the system is operating
reliably.
(LEDs 8–23) General Purpose LEDs
These LEDs indicate functionality of the general purpose inputs on the LSI-16e or of the LSI-16 that has been updated with an Interface
Module 16 (IM-16). On an LSI-16 without an option board, these LEDs remain inactive.
• Solid Red: An Alarm is active on the associated input.
• Solid Yellow: A Fault is active on the associated input.
• Flashing Yellow: An input congured as “high range - monitored” exhibits a monitoring fault.
6
Page 7
LSI-16/LSI-16e REAR PANEL
Device ID
The rotary ID switches are located on the back of the LSI-16/LSI-16e and give the unit a unique Device ID. The switches are in
hexadecimal format. To assign a Device ID of hex 07, turn the LSB switch to 7 and leave the MSB switch on 0. To create an ID of hex B7,
turn the LSB switch to 7 and turn the MSB switch to B. Device ID switches should be set using a 0.1 inch (2.5mm) to 0.12 inch (3.0mm)
at blade screwdriver. More information on setting IDs and the hexadecimal numbering scheme used in Vocia can be found in the Vocia
Help File.
Please note: Changes made to the Device ID while connected to the network require a power cycle in order to take effect.
Network Connection
The LSI-16/LSI-16e has two RJ45 Ethernet connectors. These provide redundant network capability as well as a secondary source of
power (PoE). If communication is lost on either Ethernet port, the LSI-16/LSI-16e reports a fault. For this reason, both Ethernet ports must
be connected to the Vocia network. To provide Auxiliary power PoE should be supplied to both Ethernet ports. An LED adjacent to each
RJ45 connector indicates that PoE is being supplied via that port.
The RJ45 connectors utilize standard copper Ethernet cabling to interface the LSI-16/LSI-16e to the Vocia system via a PoEcompliant network switch.
Left LEDRight LEDDescription
NoneNoneNo power or data connectivity. Please check the PoE network connection.
YellowFlashing
green
YellowNoneThere is a network link but the port is redundant.
The RJ45 connector provides two LEDs that indicate Ethernet link and network activity (see table below).
Network link established and indicates the port is currently in use.
7
Page 8
This connection carries control data and power over a single Ethernet cable. The maximum distance between any unit and an Ethernet
LSI-16 / LSI-16e
switch is 328 feet (100 meters) when using copper cabling. Additional Ethernet switches and/or ber-optic cable can be used to further
extend distances between units on a network. Note: A managed Ethernet switch is required for redundant network wiring (spanning-tree
conguration or similar).
If non-Vocia network trafc shares an Ethernet switch with the Vocia network, separate VLANs must be established. All Ethernet wiring
must be accomplished using shielded CAT5, CAT5e, CAT6 or CAT7 cable.
For standards-compliant systems, a managed switch with dry contact fault output is required.
LSI-16
BIAMP SYSTEMS
Designed in Australia
Assembled in USA
GND
YEL: in use
GRN :link/act
PoE IEEE 802.3af
Class 3
LSI-16/LSI-16e REAR PANEL
10
N24138
0832
0832-CPD-1401
Device ID
21
LSB
MSB
52S
321
Monitored Outputs
Option AOption B
54
10V
876
(100mA)
54
1
32
876
54
321
Control InputsSystem Fault
876
54
32114131211109
NCC
NO
Power
Class 2 or LPS
14131211109
24V
15W
876
RS232
Ethernet switch
with PoE
Model LSI-16
LSI-16e
LSI-16 / LSI-16e
BIAMP SYSTEMS
Designed in Australia
Assembled in USA
GND
YEL: in use
GRN :link/act
PoE IEEE 802.3af
Class 3
10
N24138
Device ID
21
MSB
LSB
321
Monitored Outputs
Option AOption B
54
876
10V
(100mA)
54
32
1
54
321
Control InputsSystem Fault
54
32114131211109876
876
NCC
NO
RS232
Power
Class 2 or LPS
14131211109876
24V DC
15W
Model LSI-16
Ethernet switch
without PoE
PoE
injector
AC Power
8
Page 9
LSI-16/LSI-16e REAR PANEL
Monitored I/O
Two black ve-position connectors are located next to the rotary switches. These are predominantly used for monitored inputs and outputs
(I/O) to external lamps or sounders. Individual connections are labeled 1 through 8 as indicated below. One connection is congured for
use as both an input and an output (1) and one as an input (2) (see table below for connector assignments).
MarkingFunction
Ground
1Sounder Output / Silence Input
2System Fault Reset Input
3Voice Alarm Active
4General Fault
5PSU Fault
6Protection Fault
7Path Fault
8External Supply Over-voltage Monitor
10V10V Out
The inputs/outputs will sink current (pull low) when active (see the Specications section of this document for more details). The desired
load (lamp, LED, etc.) must be connected between the input/output terminal and a positive voltage reference.
It should be noted that external switches and a sounder connected to the rst two inputs are typically mandatory for standards compliance.
The location and physical attributes of these items may be required to conform with local norms. The switches and sounder must be wired
according to the connection diagram provided below.
For each of these inputs/outputs, a load must be connected between each output and the positive voltage source. If any output on terminals 1 through 8 is unused, the output must be connected through an external resistor to the positive side of the voltage source (either
10V Out or user-supplied external source). To ensure correct functionality, the value of each resistor should be 22kΩ. An internally derived
10V source is provided at the 10V Out terminal; however, the total current available from this pin is limited to 100mA. This voltage source
may be used for external devices provided the total load is less than 100mA. For higher-current devices, a user-supplied external voltage source of up to 35V may be used, with the negative side connected to the pin. Due to monitoring constraints, it is impossible to use
both the internal 10V source and an external source. For monitoring purposes, the positive side of the voltage source (either 10V Out or
user-supplied external source) must be connected to the External Supply Over-voltage Monitor (terminal 8), as well as supplying voltage to
external devices.
(I/O 1) Sounder Output/Silence Input
This connection functions as a dual purpose alarm sounder output and silence input (see connection diagram below).
Sounder Output
This output connects to a local sounder for fault and alarm warnings. A sounder is typically required for standards compliance.
Note: If an emergency microphone is located near the sounder, it may be congured in Vocia software to mute the sounder while
making live announcements.
Silence Input
This input is used to silence the local sounder. The sounder will restart in response to any new fault or alarm.
(I/O 2) System Fault Reset Input
This input is required to take the LSI-16/LSI-16e out of System Fault condition. Note: the LSI-16/LSI-16e will always power up in a system
fault state (see connection diagram).
9
Page 10
LSI-16/LSI-16e REAR PANEL
(I/O 3) Voice Alarm Active
This output is active when messages are playing in response to an alarm input. This output provides indication of when a message is
playing or when a message has been muted.
Constant active output - indicates a message is playing in response to an alarm input.
Cyclic output (1.25Hz) - indicates the message has been muted.
(I/O 4-7) General Fault, PSU Fault, Protection Fault and Path Fault
These outputs will be activated by the same alarm conditions as identically named LEDs on the front panel (described above). Note
however that these outputs will be activated by the faults listed above irrespective of whether a System Fault has been activated.
The Voice Alarm Active, General Fault, PSU Fault, Protection Fault and Path Fault outputs are monitored for open-circuit or short-circuit to
ground or power supply and for over-voltage on the output pin (>35V DC). If incorrect conditions are detected a Fault is signaled. Output
monitoring facilitates compliance with voice evacuation standards.
System Test
A system test can be initiated by simultaneously connecting monitored outputs 1 and 2 to ground (see connection diagram). A system test
runs a diagnostic test, part of which illuminates each LED in turn and momentarily activates the sounder.
Connection Diagram: external switches and sounder (Note: 10V supply may be derived from the LSI-16/LSI-16e Outputs Connector)
SW1System Fault Reset (e.g. EAO 31-453 or equivalent switch)
SW2System Test (e.g. EAO 31-453 or equivalent switch)
SW3Silence Local Sounder (e.g. EAO 31-453 or equivalent switch)
D1 and D21N4004 or equivalent general purpose 1A diode
R1 and R222kΩ 0.25 watt resistor
S1Piezo (or similar) sounder - tone and sound pressure level may be required to
comply with local norms
10
Page 11
LSI-16/LSI-16e REAR PANEL
Control Inputs
Two ve-position plug-in barrier strip connectors provide control input connections. Eight separate channels plus two ground pins are
provided (see table below for connector assignments). Control inputs are fully isolated from all connections in the LSI-16/LSI-16e.
MarkingFunction
Ground
1PSU Fault (contact closure indicates a PSU Fault)
2Ethernet Fault
3Voice Alarm Silence from CIE (common for all zones)
4Voice Alarm Reset from CIE (common for all zones)
Ground
5Emergency Input 1
6Emergency Input 2
7Emergency Input 3
8Emergency Input 4
Input Activation Conditions
Control Inputs 1 and 2
To activate an input, it must be connected to an external circuit that returns to either of the two pins. The resistance of this circuit must
be less than 4kΩ.
Control Inputs 3 to 8
These inputs must be permanently connected to an external circuit that returns to either of the two pins. The resistance of this circuit
must be between 1kΩ and 4kΩ. To activate an input, pull the input to a voltage between 12 and 24V.
(Input 1) PSU Fault
This input may be derived from the primary 24V power supply to indicate to the LSI-16/LSI-16e if there is a fault in the power supply. This
may be required for standards compliance.
(Input 2) Ethernet Fault
This input can be derived from an Ethernet switch to monitor the Ethernet network connection between the LSI-16/LSI-16e and amplier.
This may be required for standards compliance.
(Input 3) Voice Alarm Silence from CIE (re alarm system)
This input is a signal from the CIE (re alarm system) that will mute emergency messages in all emergency zones.
(Input 4) Voice Alarm Reset from CIE (re alarm system)
This input is a signal from the CIE (re alarm system) that will reset emergency messages in all emergency zones.
(Inputs 5-8) Emergency Inputs
These four inputs are used to connect to the re alarm control and indicating equipment (CIE) and notify the LSI-16/LSI-16e that an
alarm has occurred on a particular zone. Four such zone inputs may be connected; one emergency message or mute can be assigned per
zone. Additional zone inputs are available with the IM-16. When an alarm is detected, the Vocia system will enter Emergency Mode as
congured for that input. During Emergency Mode, some or all of the Vocia system will cease normal operation and operate as pro-
grammed for the emergency.
11
Page 12
LSI-16/LSI-16e REAR PANEL
1 23 467 8
24v
5
1 2
3
4
5
6
7
8 9
10
11
12
13
14
1 2
3
4
5
6
7
8 9
10
11
12
13
14
9 1011 121415 16
24v
13
Option A
Pin
Function
Option B
Pin
Function
General Purpose Inputs
These connections provide functionality of the option inputs on the LSI-16e or of the LSI-16 that has been upgraded with an Interface
Module (IM-16). On an LSI-16 without an option board, these connections will remain inactive.
Two connectors, labeled Option A and Option B, are located on the back of the LSI-16e. Each slot consists of 14 pins which are
labeled 1 to 14. Each connector bank allows for the following connection:
• Chassis Ground: One connection per connector bank.
• Isolated Ground: Four connections per connector bank.
• Control Inputs: Eight connections per connector bank.
24 Volts DC - One output per connector. Internally sourced, this will allow up to 60mA to be shared over all general purpose inputs.
Pin-out
PinOption A FunctionOption B Function
1Chassis Ground/ShieldChassis Ground/Shield
2General Purpose Input 1Control Input 9
3General Purpose Input 2Control Input 10
4Isolated GroundIsolated Ground
5General Purpose Input 3Control Input 11
6General Purpose Input 4Control Input 12
7Isolated GroundIsolated Ground
8General Purpose Input 5Control Input 13
9General Purpose Input 6Control Input 14
10Isolated GroundIsolated Ground
11General Purpose Input 7Control Input 15
12General Purpose Input 8Control Input 16
13Isolated GroundIsolated Ground
1424V (60mA total, shared across all inputs)24V (60mA total, shared across all inputs)
12
Page 13
LSI-16/LSI-16e REAR PANEL
SECTION HEAD
Connections and Input Types
External Connections
Both Chassis Ground ( ) and Isolated Ground ( ) are available on the IM-16 connectors.
By default, all input circuits are isolated with respect to the LSI-16 ground. Any external input connections must be logic referenced to the Isolated
Ground. This conguration allows external equipment to be interconnected to the LSI-16 without ground current interaction between devices.
The IM-16 ground appears on a single terminal (Pin 1) on each of the two connector banks (‘Option A’ and ‘Option B’). This should only be used if
circuit isolation is not required and should only be connected to the cable screen.
The two issolated grounds of the IM-16 board are connected internally. For ease of wiring each connector, every Control Input pair has an Isolated
Ground connection adjacent to it.
Types of Input Circuit
The logic level of each input on the IM-16 may be independently determined in the Vocia software to operate one of three ways. These are;
• TTL: 2V to 5V logic sense. To enable a TTL input, apply a TTL logic high with respect to Isolated Ground. This can be congured in software
to detect a low to high or high to low transition.
• High Range: To enable a High Range input, use a dry contact to switch the input to a voltage of 24V DC with respect to Isolated Ground.
This can be congured in software to detect a low to high or high to low transition.
• High Range – Monitored: This circuit is implemented in the same way as the ‘High Range’ input. This option allows monitoring of each input
for short to ground and open circuit. In order to sense open circuit, a terminating resistor must be tted between each Control
Input and Isolated Ground at the far end of the input circuit being sensed. The IM-16 will sense open circuits on the line between its input and
the terminating resistor. Shorts to Isolated Ground are sensed across the entire line being monitored. A 6k8Ω resistor should be used for each
input. If a monitoring fault is detected on any input the logic state or transitions on that input will be ignored until the fault is cleared. High
Range – Monitored inputs require a low to high transition to enable the input (transition direction not congurable).
System Fault Relay Connection
This relay is activated when the LSI-16/LSI-16e is fully operational. It may be used for informing external devices about the LSI-16/LSI-16e’s
operating conditions or sounding an alarm that indicates the LSI-16/LSI-16e is not functioning reliably.
RS232
The RS232 port can be used to send VTP commands to the LSI-16/LSI-16e and monitor Vocia system health. Please see Help Files for details.
24V DC Connector and LED
This is the primary (main) power supply input for the LSI-16 and as such must be fed from a suitable source of 24V DC capable of 15 watts (625mA).
The 24V DC supply has to be sourced separately. In typical installations, this supply will be provided from a power supply compliant with local
norms and required standards (typically battery-backed). The adjacent LED indicates the presence of power.
Sourcing 24V DC for High Range Inputs
The High Range logic inputs should be driven from a contact closure (relay or switch) in connected equipment. The High Range inputs expect to
sense a transition from low-state voltage (0-11V) to high-state voltage (12-30V). A 24V Logic High Reference output voltage is provided by the IM-16
for this purpose. Alternatively an external 24V reference may be used. If an external supply is used, the ground connection of the external supply
must be wired to the IM-16 Isolated Ground.
IP30 Compliance
The LSI-16 is designed for ingress protection to the IP30 standard. In order to maintain this compliance, any unused terminal connectors on the back
of the unit must be tted with the supplied terminal blocks.
13
Page 14
LSI-16/LSI-16e REAR PANEL
Suggested Alarm and Fault Input Connection Diagrams
SECTION HEAD
High Range Monitored
(24V provided externally)
Active State: High
COM
+
24V
-
9 1011 121415 1613
High Range Unmonitored
(24V provided externally)
Active State: High
COM
+
24V
-
CIE Relay
NO
NC
CIE Relay
NO
NC
High Range Monitored
(24V provided by IM-16)
Active State: High
CIE Relay
NO
COM
6.8kΩ
24v
9 1011 121415 16
NC
13
6.8kΩ
24v
High Range Unmonitored
(24V provided by IM-16)
Active State: High
CIE Relay
NO
COM
NC
9 1011 121415 1613
High Range Unmonitored
24V (External/CIE Provided)
Active State: Low
CIE Relay
NO
COM
NC
+
24V
-
9 1011 121415 1613
24v
24v
5V TTL Logic
Active State: Voltage Dependant
CIE
+
TTL Logic
Output
(5v)
-
9 1011 121415 16
13
High Range Unmonitored
24V (IM-16 Provided)
Active State: Low
CIE Relay
NO
COM
NC
9 1011 121415 16
13
24v
24v
9 1011 121415 1613
14
24v
Page 15
LSI-16/LSI-16e INSTALLATION
Installation
The LSI-16/LSI-16e requires one 1.75 inches (44.45mm) high and 19 inches (483mm) wide rack space with 10 inches (254mm) depth.
Mounting the unit using four screws with washers will prevent marring of the front panel. PVC or nylon washers are appropriate.
Please install the unit away from heat sources, such as vents and radiators, and in rooms with adequate ventilation. Ensure that air can
circulate freely behind, beside, and above the unit. Do not exceed the maximum ambient operating temperature of 32-113 degrees F (045°C). Be aware of conditions in an enclosed rack that may cause the temperature to exceed ambient room conditions.
Note: To operate correctly, the LSI-16/LSI-16e requires input and output connections to external components and devices as described in
this manual.
15
Page 16
Life Safety Interface 16 SPECIFICATIONS
System Fault Relay:
Type:
Load:
Maximum operating voltage:
Maximum operating current:
Maximum switching capacity:
Minimum permissible load:
Control Inputs:
Number:
Type:
Cathode presented at input –
pull low to enable. Sink Current:
Min:
Max:
Maximum Terminal Voltage:
Isolation:
Single ‘Form C’ voltage-free SPST
LSI-16 SPECIFICATIONS
RS232 Port
Type:
change-over contact
Resistive
125VAC, 60VDC
600mA AC, 1A DC
37.5VA, 30W
10µA @ 10mVDC
Eight
Opto Isolator LED
1mA
6mA
24V
3kV
Baud Rate:
Connection:
Power:
Main:
PoE:
Base Dimensions:
Height:
Width:
Depth:
DTE
57600
RJ45 with shielded Ethernet/PoE cable
(CAT5, CAT 5e, CAT6, or CAT7)
24V DC 15W
802.3af Class 3
1.75 inches (44.5mm)
19 inches (483mm)
10 inches (254mm
Monitored I/O:
Number:
Type:
Maximum Continuous Current:
Current Limit:
Maximum External Supply:
VMon Input Shutdown:
Life Safety Interface 16 BLOCK DIAGRAM
LEDs
ID Switches
Vocia
System
PoE
24V DC
FET switch, open drain
Eight
(low side driver)
0.35A
0.8A
35V
35V
Host Processor
Weight:
Ambient Operating
Temperature Range:
Compliance:
8 Control Inputs
8 Monitored Outputs
IM-16 (optional)
Approx 6.4 lbs. (2.8kg)
32-113 degrees F (0-45 degrees C)
FCC Part 15, class B
EC marked
EN 54-16 certified
RoHS Directive
UL 60065 Listed, E215636
C-UL Listed, E215636
C-Tick, N24138 (Australia)
16
Page 17
Life Safety Interface 16e SPECIFICATIONS
System Fault Relay:
Type:
Load:
Maximum operating voltage:
Maximum operating current:
Maximum switching capacity:
Minimum permissible load:
Control Inputs:
Number:
Type:
Cathode presented at input –
pull low to enable. Sink Current:
Min:
Max:
Maximum Terminal Voltage:
Isolation:
Single ‘Form C’ voltage-free SPST
LSI-16e SPECIFICATIONS
SECTION HEAD
RS232 Port
Type:
change-over contact
Resistive
125VAC, 60VDC
600mA AC, 1A DC
37.5VA, 30W
10µA @ 10mVDC
Eight
Opto Isolator LED
1mA
6mA
24V
3kV
Baud Rate:
Connection:
Power:
Main:
PoE:
Base Dimensions:
Height:
Width:
Depth:
DTE
57600
RJ45 with shielded Ethernet/PoE cable
(CAT5, CAT 5e, CAT6 or CAT7)
24V DC 15W
802.3af Class 3
1.75 inches (44.5mm)
19 inches (483mm)
10 inches (254mm
Monitored I/O:
Number:
Type:
Maximum Continuous Current:
Current Limit:
Maximum External Supply:
VMon Input Shutdown:
Option Inputs:
Number:
High Range Logic Low:
High Range Logic High:
High Range Hysteresis:
TTL Logic Low:
TTL Logic High:
TTL Hysteresis:
Input Transient Protection:
Input Isolation:
FET switch, open drain (low
500V RMS (isolation from LSI-16)
Life Safety Interface 16e BLOCK DIAGRAM
LEDs
ID Switches
Vocia
System
PoE
24V DC
Eight
side driver)
0.35A
0.8A
35V
35V
16
0-11 DC
12-30 DC
1V ± 20%
0-0.8V
2-5V
1V ± 20%
± 8KV peak
Host Processor
Weight:
Ambient Operating
Temperature Range:
Compliance:
8 Control Inputs
8 Monitored Outputs
16 General Purpose
Approx 6.4 lbs. (2.8kg)
32-113 degrees F (0-45 degrees C)
FCC Part 15, class B
CE marked
EN 54-16 certification pending
RoHS Directive
UL 60065 Listed, E215636
C-UL Listed, E215636
C-Tick, N24138 (Australia)
Inputs
17
Page 18
LSI-16/LSI-16e WARRANTY
BIAMP SYSTEMS IS PLEASED TO EXTEND THE FOLLOWING 5-YEAR LIMITED WARRANTY TO THE ORIGINAL PURCHASER OF
THE PROFESSIONAL SOUND EQUIPMENT DESCRIBED IN THIS MANUAL
1. BIAMP Systems warrants to the original purchaser of new products that the product will be free from defects in material and
workmanship for a period of 5 YEARS from the date of purchase from an authorized BIAMP Systems dealer, subject to the
terms and conditions set forth below.
2 If you notify BIAMP during the warranty period that a BIAMP Systems product fails to comply with the warranty, BIAMP Systems
will repair or replace, at BIAMP Systems’ option, the nonconforming product. As a condition to receiving the benets of this warranty,
you must provide BIAMP Systems with documentation that establishes that you were the original purchaser of the products. Such
evidence may consist of your sales receipt from an authorized BIAMP Systems dealer. Transportation and insurance charges to
and from the BIAMP Systems factory for warranty service shall be your responsibility.
3. This warranty will be VOID if the serial number has been removed or defaced; or if the product has been altered, subjected to
damage, abuse or rental usage, repaired by any person not authorized by BIAMP Systems to make repairs; or installed in any
manner that does not comply with BIAMP Systems’ recommendations.
4. Electro-mechanical fans, electrolytic capacitors, gooseneck microphones, cords connecting handheld microphones, hard-drives,
displays, and normal wear and tear of items such as paint, knobs, handles, keypads and covers are not covered under this warranty. All server-based devices are warranted for 3 years only.
5. This warranty is in lieu of all other warranties, expressed or implied. Biamp Systems disclaims all other warranties, expressed or
implied, including, but not limited to, implied warranties of merchantability and tness for a particular purpose.
6. The remedies set forth herein shall be the purchaser’s sole and exclusive remedies with respect to any defective product.
7. No agent, employee, distributor or dealer of BIAMP Systems is authorized to modify this warranty or to make additional warranties on behalf of BIAMP Systems. Statements, representations or warranties made by any dealer do not constitute warranties by
BIAMP Systems. BIAMP Systems shall not be responsible or liable for any statement, representation or warranty made by any
dealer or other person.
8. No action for breach of this warranty may be commenced more than one year after the expiration of this warranty.
9. BIAMP Systems shall not be liable for special, indirect, incidental, or consequential damages, including lost prots or loss of use
arising out of the purchase, sale, or use of the products, even if BIAMP Systems was advised of the possibility of such damages.
18
012011_585.0245.90B
Page 19
COMPLIANCE
DoC VLSI201101
EC Declaration of Conformity
Biamp Systems Corporation, as manufacturer having sole responsibility, hereby
declares that the following described product complies with the applicable provisions of
the DIRECTIVES below except as noted herein. Any alterations to the product not
agreed upon and directed by Biamp Systems Corporation will invalidate this declaration.
Product Model
Product Description
Applicable EC Directives
LVD Directive (2006/95/EC) Safety EN 60065:2002
EMC Directive (2004/108/EC) Emissions EN 55103-1:1996, Environment E2
Immunity EN 55103-2:1996, Environment E2
Special Considerations for Product Environment or Compliance
Use only CE marked Power over Ethernet (PoE) device.
Use only CE and “LPS” marked 24 VDC External Power Adaptor.
Shielded cabling must be used for system connections.
Technical Construction File, Location and Contact
Biamp Systems Corporation phone: (503) 641.7287
9300 S.W. Gemini Drive fax: (503) 626.0281
Beaverton, OR USA 97008 e-mail: biamp@biamp.com
Authorized Representative: Larry Copley, Compliance Engineer
: Vocia® LSI-16, LSI-16e
: Life Safety Interface for networking with audio DSPs
: Applicable Harmonized Standards:
:
:
Authorized Signature:
Revised: January 2011
19
Page 20
COMPLIANCE
EU RoHS COMPLIANT
This Biamp product, including all attendant cables and accessories
supplied by Biamp, meets all requirements of EU Directives
2002/95/EC of January 27, 2003, and 2005/618/EC of August 18,
2005, the EU RoHS Directives. An EU RoHS Materials Content
Declaration document may be obtained at www.biamp.com
(This information is presented to comply with the requirements of Chinese law SJ/T11363-2006)”
有害物质表
Biamp Systems Corporation
生命安全接口 (Life Safety Interface)
Vocia LSI-16, LSI-16e
部件名称
设备机箱(Equipment Chassis)
插拔式接线端子 (Plug-in Terminal Blocks)
光盘(CD ROM)
手册和其他书面文档 (Manual and Documentation)
包装箱和所有包装材料 (Box and Packing Materials)