Berner DP21036S User Manual

No.: PD-269
p
pply
g
(1)
Date: March, 2006
DIPLOMAT II
STEAM/HOT WATER
Performance Data
STEAM
Steam Coil (1) Row (8) Fins Per Inch
Same End Su
Model
Tem
. Rise °F Capacity mbtu/hr
High Med Low High Med Low High Med Low
DP21036S 34 38 41 57 54 46 59 56 52 DP21042S 37 42 45 62 52 50 65 55 52 DP21048S 39 44 47 67 59 55 70 62 57 DP22048S 34 38 41 77 72 68 81 75 71 DP22060S 33 37 40 100 92 87 105 96 90 DP22072S 36 40 43 115 110 100 120 114 104 DP22084S 38 43 46 126 106 101 131 110 105 DP22096S 43 48 52 134 119 110 140 124 114 DP23096S 37 39 42 151 140 132 158 146 138 DP23108S 36 41 44 173 165 151 181 172 157 DP23120S 37 42 45 179 164 152 186 171 158
For other steam pressures - see chart on reverse side. Berner recommends that maximum Leaving Air Temperature (L.A.T.) never exceed 120° F Berner recommends coils should be supplied by a solenoid valve that energizes only when air curtain is on.
/Return
Condensate lbs/hr
HOT WATER
Hot Water Coil
Same End Supply/Return
Model
High Med Low High Med Low High Med Low gpm ft. wg.
DP21036W 26 28 31 39 37 34 175 176 178 3.1 0.3 DP21042W 29 34 36 43 37 36 175 179 180 3.6 0.4 DP21048W 31 35 38 48 43 40 176 178 180 4.0 0.5 DP22048W 27 29 31 56 52 50 175 177 178 4.6 0.7 DP22060W 27 30 32 74 69 65 175 177 178 6.0 1.2 DP22072W 29 31 34 85 82 75 175 176 178 7.0 1.8 DP22084W 31 37 39 95 81 77 175 179 180 7.8 2.3 DP22096W 33 37 40 101 90 84 174 177 178 8.0 2.6 DP23096W 29 31 33 120 112 106 174 176 177 9.5 3.6 DP23108W 30 32 35 133 127 117 173 174 176 10.0 4.2 DP23120W 31 34 36 138 127 118 173 175 177 10.5 4.7
Performance based on 70°F Entering Air Temperature (E.A.T.) and 200°F Entering Water Temperature (E.W.T.)
Consult factory for other E.A.T., E.W.T. or G.P.M.
Row (8) Fins Per Inch
Leavin
Water Temp °FTemp. Rise °F Capacity mbtu/hr
Water Flow
Drop or
Loss
Berner reserves the right to alter specifications without prior notice.
Berner International Corporation New Castle, PA 16101 / USA / Telephone (724) 658-3551 / FAX (724) 652-0682 / www.berner.com / airdoors@berner.com
MADE IN U.S.A. ©Copyright, 2006 Berner International Corporation
Constants For Obtaining Temperature Rise
At Various Steam Pressures & Inlet Temperatures
STEAM PRESSURES IN POUNDS PER SQUARE INCH (GAUGE)
0 2 5 10 15 20 30 40 50 60 80 100 125 150 175 200
-30 1.54 1.59 1.64 1.71 1.78 1.84 1.94 2.02 2.10 2.16 2.25 2.34 2.44 2.52 2.59 2.67
-20 1.48 1.52 1.57 1.65 1.72 1.77 1.87 1.95 2.02 2.08 2.19 2.28 2.37 2.46 2.53 2.59
-10 1.41 1.45 1.51 1.59 1.65 1.71 1.81 1.89 1.96 2.02 2.12 2.21 2.31 2.39 2.46 2.53
00 1.35 1.39 1.45 1.54 1.59 1.65 1.74 1.82 1.89 1.96 2.06 2.15 2.25 2.33 2.40 2.47
10 1.28 1.33 1.38 1.46 1.52 1.58 1.68 1.76 1.83 1.89 2.00 2.09 2.18 2.26 2.34 2.40
20 1.22 1.26 1.31 1.40 1.46 1.52 1.62 1.70 1.77 1.83 1.93 2.02 2.12 2.20 2.27 2.34
30 1.16 1.20 1.25 1.33 1.40 1.46 1.55 1.63 1.70 1.76 1.87 1.96 2.05 2.14 2.21 2.28
40 1.09 1.14 1.19 1.27 1.33 1.39 1.49 1.57 1.64 1.70 1.81 1.89 1.99 2.07 2.15 2.22
45 1.06 1.10 1.16 1.24 1.30 1.36 1.46 1.54 1.61 1.67 1.77 1.86 1.96 2.04 2.12 2.18
50 1.03 1.07 1.13 1.21 1.27 1.33 1.42 1.51 1.58 1.64 1.74 1.83 1.93 2.01 2.08 2.15
55 1.00 1.04 1.10 1.17 1.24 1.30 1.39 1.47 1.54 1.61 1.71 1.80 1.89 1.98 2.05 2.12
60 0.97 1.01 1.06 1.14 1.21 1.26 1.36 1.44 1.51 1.57 1.68 1.77 1.86 1.95 2.02 2.09
65 0.93 0.98 1.03 1.11 1.17 1.23 1.33 1.41 1.48 1.54 1.65 1.74 1.83 1.91 1.99 2.05
70 0.90 0.95
75 0.87 0.91 0.97 1.05 1.11 1.17 1.27 1.35 1.42 1.48 1.59 1.67 1.77 1.85 1.92 1.99
80 0.84 0.88 0.94 1.01 1.08 1.14 1.24 1.32 1.39 1.45 1.55 1.64 1.74 1.82 1.89 1.96
85 0.81 0.85 0.90 0.98 1.05 1.11 1.20 1.28 1.35 1.41 1.52 1.61 1.71 1.79 1.86 1.93
ENTERING AIR TEMPERATURE °F
90 0.78 0.82 0.87 0.95 1.02 1.07 1.17 1.25 1.32 1.38 1.49 1.58 1.67 1.76 1.83 1.89
100 0.71 0.75 0.81 0.89 0.95 1.00 1.11 1.19 1.26 1.32 1.42 1.51 1.61 1.69 1.77 1.83
110 0.65 0.69 0.75 0.82 0.89 0.95 1.04 1.12 1.20 1.26 1.36 1.45 1.55 1.63 1.70 1.77
120 0.59 0.63 0.68 0.76 0.83 0.88 0.98 1.06 1.13 1.19 1.30 1.40 1.48 1.56 1.64 1.71
140 0.46 0.50 0.55 0.63 0.70 0.76 0.85 0.93 1.00 1.07 1.17 1.26 1.35 1.44 1.51 1.58
160 0.33 0.37 0.43 0.50 0.57 0.63 0.73 0.81 0.88 0.94 1.04 1.13 1.23 1.31 1.38 1.45
180 0.20 0.24 0.30 0.38 0.44 0.50 0.60 0.68 0.75 0.81 0.91 1.00 1.10 1.18 1.26 1.32
200 0.08 0.12 0.17 0.25 0.32 0.37 0.47 0.55 0.62 0.68 0.79 0.88 0.97 1.06 1.13 1.20
T = T° + U t x C T = Temperature at exit T° = Temperature at intake
1.00 1.08 1.14 1.20 1.30 1.38 1.45 1.51 1.62 1.70 1.80 1.88 1.96 2.02
U t = Temperature rise from data sheet C = Constant from above table