Benshaw retains the right to change specifications and illustrations in text without prior notification. The contents of this document may
not be copied without the explicit permission of Benshaw.
Important Reader Notice
Congratulations on the purchase of your new Benshaw RediStart MX2 Solid State Starter. This manual contains the information to install and
program the MX2 Solid State Starter. The MX2 is a standard version solid state starter. If you require additional features, please review the
expanded feature set of the MX3 Solid State Starter on page 5.
This manual may not cover all of the applications of the RediStart MX2. Also, it may not provide information on every possible contingency
concerning installation, programming, operation, or maintenance specific to the RediStart MX2 Series Starters.
The content of this manual will not modify any prior agreement, commitment or relationship between the customer and Benshaw. The sales
contract contains the entire obligation of Benshaw. The warranty enclosed within the contract between the parties is the only warranty that
Benshaw will recognize and any statements contained herein do not create new warranties or modify the existing warranty in any way.
Any electrical or mechanical modifications to Benshaw products without prior written consent of Benshaw will void all warranties and may also
void cUL listing or other safety certifications, unauthorized modifications may also result in product damage operation malfunctions or personal
injury.
Incorrect handling of the starter may result with an unexpected fault or damage to the starter. For best results on operating the RediStart MX
starter, carefully read this manual and all warning labels attached to the starter before installation and operation. Keep this manual on hand for
reference.
Do not attempt to install, operate, maintain or inspect the starter until you have thoroughly read this manual and related documents carefully
and can use the equipment correctly.
Do not use the starter until you have a full knowledge of the equipment, safety procedures and instructions.
This instruction manual classifies safety instruction levels under "WARNING" and "CAUTION".
Electrical Hazard that could result in injury or death.
2
Caution that could result in damage to the starter.
Highlight marking an important point in the documentation.
Please follow the instructions of both safety levels as they are important to personal safety.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with low voltage equipment are to perform work described in this set of instructions.
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage sensing device to confirm that the power is off.
Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of electric power.
Assume that circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to
the design of the power system. Consider all sources of power, including the possibility of backfeeding.
Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
TRADEMARK NOTICE
Benshaw and are registered trademarks of Benshaw Incorporated.
UL is a trademark of Underwriters Laboratories, Incorporated.
SAFETY PRECAUTIONS
Safety Precautions
Electric Shock Prevention
• While power is on or soft starter is running, do not open the front cover. You may get an electrical shock.
• This soft starter contains high voltage which can cause electric shock resulting in personal injury or loss of life.
• Be sure all AC power is removed from the soft starter before servicing.
• Do not connect or disconnect the wires to or from soft starter when power is applied.
• Make sure ground connection is in place.
• Always install the soft starter before wiring. Otherwise, you may get an electrical shock or be injured.
• Operate the switches with dry hands to prevent an electrical shock.
• Risk of Electric Shock - More than one disconnect switch may be required to de-energize the equipment before servicing.
Injury Prevention
• Service only by qualified personnel.
• Make sure power-up restart is off to prevent any unexpected operation of the motor.
• Make certain proper shield installation is in place.
• Apply only the voltage that is specified in this manual to the terminals to prevent damage.
Transportation and Installation
• Use proper lifting gear when carrying products, to prevent injury.
• Make certain that the installation position and materials can withstand the weight of the soft starter. Refer to the installation information in this
manual for correct installation.
• If parts are missing, or soft starter is damaged, do not operate the RediStart MX
• Do not stand or rest heavy objects on the soft starter, as damage to the soft starter may result.
• Do not subject the soft starter to impact or dropping.
• Make certain to prevent screws, wire fragments, conductive bodies, oil or other flammable substances from entering the soft starter.
2
.
Trial Run
• Check all parameters, and ensure that the application will not be damaged by a sudden start-up.
Emergency Stop
• To prevent the machine and equipment from hazardous conditions if the soft starter fails, provide a safety backup such as an emergency brake.
Disposing of the RediStart MX
• Never dispose of electrical components via incineration. Contact your state environmental agency for details on disposal of electrical components
APPENDIX A ALARM CODES .....................................194
APPENDIX B FAULT CODES ......................................196
APPENDIX C SPARE PARTS ......................................197
APPENDIX D EU DECLARATION OF CONFORMITY .......................198
APPENDIX E MODBUS REGISTER MAP ...............................199
APPENDIX F PARAMETER TABLES ..................................207
vi
1Introduction
1
1 - INTRODUCTION
1INTRODUCTION
Using this Manual
LayoutThis manual is divided into 10 sections. Each section contains topics related to the section. The sections
are as follows:
• Introduction
• Technical Information
• Installation
• Keypad Operation
• Parameters
• Parameter Description
• Applications
• Theory of Operation
• Troubleshooting & Maintenance
• Appendices
SymbolsThere are 2 symbols used in this manual to highlight important information. The symbols appear as the
following:
Electrical Hazard warns of situations in which a high voltage can cause physical injury, death
and/or damage equipment.
Caution warns of situations in which physical injury and/damage to equipment may occur by means
other than electrical.
Highlight mark an important point in the documentation.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with low voltage equipment are to perform work described in this set of instructions.
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage sensing device to confirm that the power is off.
Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of electric power.
Assume that circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to
the design of the power system. Consider all sources of power, including the possibility of backfeeding.
Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
2
General InformationBenshaw offers its customers the following:
• Start-up services
• On-site training services
• Technical support
• Detailed documentation
• Replacement parts
z NOTE: Information about products and services is available by contacting Benshaw, refer to
page 4.
1 - INTRODUCTION
Benshaw Services
Start-Up ServicesBenshaw technical field support personnel are available to customers with the initial start-up of the
RediStart MX2. Information about start-up services and fees are available by contacting Benshaw.
On-Site Training ServicesBenshaw technical field support personnel are available to conduct on-site training on RediStart MX
operations and troubleshooting.
Technical SupportBenshaw technical support personnel are available (at no charge) to answer customer questions and
provide technical support over the telephone. For more information about contacting technical support
personnel, refer to page 4.
Replacement PartsSpare and replacement parts can be purchased from Benshaw Technical Support.
Software NumberThis manual pertains to the software version numbers 810023-01-08.
Hardware NumberThis manual pertains to the hardware version numbers 300055-01-05.
All RediStart MX2 documentation is available on-line at http://www.benshaw.com.
2
Publication HistorySee page 213.
WarrantyBenshaw provides a 1 year standard warranty with its starters. An extension to the 3 year warranty is
provided when a Benshaw or Benshaw authorized service technician completes the installation and
initial start up. The warranty data sheet must also be signed and returned. The cost of this service is not
included in the price of the Benshaw soft starter and will be quoted specifically to each customers
needs. All recommended maintenance procedures must be followed throughout the warranty period to
ensure validity. This information is also available by going online to register at www.benshaw.com.
3
1 - INTRODUCTION
Contacting Benshaw
Contacting BenshawInformation about Benshaw products and services is available by contacting Benshaw at one of the
following offices:
Benshaw Inc. Corporate Headquarters
1659 E. Sutter Road
Glenshaw, PA 15116
Phone: (412) 487-8235
Tech Support: (800) 203-2416
Fax:(412) 487-4201
Benshaw Canada Controls Inc.
550 Bright Street East
Listowel, Ontario N4W 3W3
Phone:(519) 291-5112
Tech Support: (877) 236-7429 (BEN-SHAW)
Fax:(519) 291-2595
Benshaw West
14715 North 78th Way, Suite 600
Scottsdale, AZ 85260
Phone:(480) 905-0601
Fax:(480) 905-0757
Benshaw High Point
EPC Division
645 McWay Drive
High Point, NC 27263
Phone: (336) 434-4445
Fax: (336) 434-9682
Benshaw Mobile
CSD Division
5821 Rangeline Road, Suite 202
Theodor, AL 36582
Phone: (251) 443-5911
Fax: (251) 443-5966
Technical support for the RediStart MX2 Series is available at no charge by contacting Benshaw’s
customer service department at one of the above telephone numbers. A service technician is available
Monday through Friday from 8:00 a.m. to 5:00 p.m. EST.
z NOTE: An on-call technician is available after normal business hours and on weekends by calling
Benshaw and following the recorded instructions.
To help assure prompt and accurate service, please have the following information available when
contacting Benshaw:
• Name of Company
• Telephone number where the caller can be contacted
• Fax number of caller
• Benshaw product name
• Benshaw model number
• Benshaw serial number
• Name of product distributor
• Approximate date of purchase
• Voltage of motor attached to Benshaw product
• FLA of motor attached to Benshaw product
• A brief description of the application
4
1 - INTRODUCTION
MX2 & MX3 Product Comparison
1.1Additional MX
The MX2 is a standard solid state starter. If you require additional features, please review the expanded feature set of the MX3 Solid
State Starter below. For the additional information on the MX3 Solid State Starter contact Benshaw.
3
Product Features
MX3 Product Features
1
5 Additional Digital Inputs
2
3 Additional 5Amp, Form A Relays
3
Real Time Clock
4
Zero Sequence Ground Fault
5
16 RTD O/L Biasing (Platinum) Remote by RS-485
6
Motor PTC Feedback
Preset Slow Speeds (Cyclo-Convertor)
7
0.1 to 40% Motor Speed
8
99 Event Log
9
Backspin Timer
10
Starts per Hour
11
Time Between Starts
12
PORT (Power Outage Ride-Thru)
13
Squared and S Ramp Profiles
14
Speed Controlled Ramp with Tachometer Feedback
5
1 - INTRODUCTION
C = Open Chassis
Amp Rating, (0 - 999A)
Frame Size
Fault Level
S = Standard
H = High
Type of Bypass
0 = None (only available with RC)
1 = Integrated
2 = Separate, Definite Purpose (Only with 1000V Starter)
3 = Separate, ATL IEC AC3 Rated
4 = Separate, ATL NEMA Rated (AC4)
Type of Control
2
2 = MX
3
3 = MX
Family of RediStart Starter
B = Bypass
C = Continuous
Interpreting Model Numbers
Figure 1: RediStart MX2 Series Model Numbers
Example of Model Number: RX2-1S-361A-14C
A RediStart starter with bypass, MX2 control, Integrated Bypass, Standard Fault, 361 Amp unit, Frame 14, open Chassis.
6
1 - INTRODUCTION
General Overview of a Reduced Voltage Starter
General OverviewThe RediStart MX
starter can be custom designed for specific applications. A few of the features are:
2
motor starter is a microprocessor-controlled starter for single or three-phase motors. The
•Solid state design.
•Reduced voltage starting and soft stopping.
•Closed-loop motor current control, power (kW) control, torque control.
•Programmable motor protection.
•Programmable operating parameters.
•Programmable metering.
Each starter can operate within applied line voltage and frequency values of 100VAC to 600VAC (optional
1000VAC) and 23 to 72Hz.
The starter can be programmed for any motor FLA and all of the common motor service factors. It enables
operators to control both motor acceleration and deceleration. The RediStart MX2 can also protect the motor and
its load from damage that could be caused by incorrect phase order wiring.
The starter continually monitors the amount of current being delivered to the motor. This protects the motor from
overheating or drawing excess current.
FeaturesThe enhanced engineering features of the starter include:
•Multiple frame sizes
•Universal voltage operation
•Universal frequency operation
•Programmable motor overload multiplier
•Controlled acceleration and deceleration
•Phase rotation protection
•Regulated current control
•Electronic motor thermal overload protection
•Electronic over/under current protection
•Single phase protection
•Line-to-line current imbalance protection
•Stalled motor protection
•Programmable metering
•Passcode protected
•Programmable Relays
•Analog output with digital offset and span adjustment
•Analog input with digital offset and span adjustment
•Voltage and Current Accuracy of 3%
•Slow Speed (Cyclo Conversion) 7.1% & 14.3% forward and reverse
•Motor winding (Anti-Condensation)
•Anti-windmilling brake
•DC Injection Braking
7
1 - INTRODUCTION
NOTES:
8
2Technical Specifications
2 - TECHNICAL SPECIFICATIONS
2TECHNICAL SPECIFICATIONS
Technical Specifications
2.1General Information
The physical specifications of the starter vary depending upon its configuration. The applicable motor current determines the
configuration and its specific application requirements.
Specifications are subject to change without notice.
This document covers the control electronics and several power sections:
• MX
2
control card
• RB Power Stacks with Bypass, Integral and Separate
• RC Power Stacks, Continuous operation, NO bypass
Electrical Ratings
2.2Electrical Ratings
2.2.1Terminal Points and Functions
Table 1: Terminals
Function
Control Power TB1G, ground
Relay 1 (R1)TB2NO1:Normally Open Contact
Relay 2 (R2)TB2NO2: Normally Open Contact
Relay 3 (R3)TB2NO3: Normally Open Contact
Digital InputsTB31: Start
Serial CommTB41: B+
Analog I/OTB51: Ain Power
DisplayRJ45Door Mounted Display Connector
Terminal
Block
Terminal NumberDescription
N, 120VAC neutral
N, 120VAC neutral
L, 120VAC line
L, 120VAC line
RC1:Common
NC1: Normally Closed Contact
RC2: Common Contact
NC2: Normally Closed Contact
RC3: Common Contact
NC3: Normally Closed Contact
2: DI1
3: DI2
4: DI3
5: Common
2: A3: COM
2: Ain +
3: Ain 4: Common
5: Aout
6: Common
7: Shield
96 – 144 VAC input, 50/60 Hz
45VA required for control card
Relay Output, SPDT form C
NO Contact (resistive) NC Contact(resistive)
5A at 250VAC 3A at 250VAC
5A at 125VAC 3A at 125VAC
5A at 30VDC 3A at 30VDC
1250VA 750VA
Relay Output, SPDT form C
NO Contact (resistive) NC Contact(resistive)
5A at 250VAC 3A at 250VAC
5A at 125VAC 3A at 125VAC
5A at 30VDC 3A at 30VDC
1250VA 750VA
10A at 250VAC
10A at 125VAC
10A at 30VDC
2500VA
120VAC digital input
2500V optical isolation
4mA current draw
Off: 0-35VAC
On: 60-120VAC
Modbus RTU serial communication port.
RS-485 interface
19.2k baud maximum
1500V Isolation
Input:
Voltage or Current
Voltage: 0-10VDC, 67KW impedance
Current: 0-20mA, 500W impedance
Output:
Voltage or Current
Voltage: 0-10VDC, 120mA maximum
Current: 0-20mA, 500W load maximum
10
2 - TECHNICAL SPECIFICATIONS
Table 1: Terminals
Function
SCRJ6 to J111: Gate
Phase C.T.J121: CT1
Wire Gauge: The terminals can support 1- 14 AWG wire or 2-16 AWG wire or smaller.
Torque Rating: The terminals on the control card have a torque rating of 5.0-inch lb. or 0.56Nm. This MUST be followed or damage will occur to the terminals.
-0.01 to +0.01 (Lag & Lead) ± 5%
23 – 72 Hz ± 0.1 Hz
5 – 100% FLA ± 5% (Machine Protection)
± 3 seconds per 24 hour period
Accuracy ± 3% of full scale (10 bit)
Accuracy ±2% of full scale (12 bit)
z NOTE: Percent accuracy is percent of full scale of the given ranges, Current = Motor
FLA, Voltage = 1000V, Watts/Volts-Amps/Watt-Hours = Motor & Voltage range
2.2.3List of Motor Protection Features
• ANSI 19 – Reduced Voltage Start
• ANSI 27 / 59 – Adjustable over/under voltage protection (Off or 1 to 40%, time 0.1 to 90.0 sec. in 0.1 sec. intervals,
independent over and under voltage levels)
• ANSI 37 – Undercurrent detection (Off or 5 to 100% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
• ANSI 46 – Current imbalance detection (Off or 5 to 40%)
• ANSI 47 – Phase rotation (selectable ABC, CBA, Insensitive, or Single Phase)
• ANSI 48 – Adjustable up-to-speed / stall timer (1 to 900 sec. in 1 sec. intervals)
The MX2 control has an advanced I2t electronic motor overload (OL) protection function. For optimal motor protection the MX2 control
has forty standard NEMA style overload curves available for use. Separate overloads can be programmed, one for acceleration and
another for normal running operation. The overloads can be individual, the same or completely disabled if necessary. The MX2 motor
overload function also implements a NEMA based current imbalance overload compensation, user adjustable hot and cold motor
compensation and user adjustable exponential motor cooling.
Figure 2: Commonly Used Overload Curves
The motor overload will NOT trip when the current is less than motor Full Load Amps (FLA) * Service Factor (SF).
The motor overload "pick up" point current is at motor Full Load Amps (FLA) * Service Factor (SF).
The motor overload trip time will be reduced when there is a current imbalance present.
z NOTE: Refer to Theory of Operation, section 7.1 on page 132 for more motor overload details and a larger graph.
Refer to http://www.benshaw.com/olcurves.html for an automated overload calculator.
12
2.2.5CT Ratios
2 - TECHNICAL SPECIFICATIONS
Table 3: CT Ratios
CT Ratio
72:1
(4 wraps 288:1)
96:1
(3 wraps 288:1)
144:1
(2 wraps 288:1)
Minimum FLA
(A rms)
4
521
832
288:11564
864:145190
2640:1135590
3900:1200870
5760:12951285
8000:14101800
14400:1
(CT-CT combination)
28800:1
(CT-CT combination)
7403200
14756400
Maximum FLA
(A rms)
16
z NOTE: See P78/FUN 03 (CT Ratio) parameter on page 126 for more information.
2.3Starter Power Ratings
Each RB2 model starter is rated for three different starting duties. For example, a starter can operate a:
300HP motor for a standard duty start (350% for 30 seconds)
Or
200HP for a heavy duty start (500% for 30 seconds)
Or
150HP motor for a severe duty start (600% for 30 seconds)
Or
450HP motor when connected to the inside delta of a motor for a standard duty start (350% for 30 seconds)
Starter Power Ratings
13
2 - TECHNICAL SPECIFICATIONS
2.3.1Standard Duty (350% for 30 sec) Ratings
Table 4: Standard Duty Horsepower Ratings
Standard Duty (350% current for 30 seconds, 115% Continuous)
MODEL NUMBER
RB2-1-S-027A-11C277.510152025
RB2-1-S-040A-11C401015253040
RB2-1-S-052A-12C521520304050
RB2-1-S-065A-12C652025405060
RB2-1-S-077A-13C772530406075
RB2-1-S-096A-13C9630405075100
RB2-1-S-125A-14C125405075100125
RB2-1-S-156A-14C156506075125150
RB2-1-S-180A-14C1806075100150200
RB2-1-S-180A-15C1806075100150200
RB2-1-S-240A-15C24075100150200250
RB2-1-S-302A-15C302100125150250300
RB2-1-S-361A-16C361125150200300400
RB2-1-S-414A-17C414150150250350400
RB2-1-S-477A-17C477150200300400500
RB2-1-S-515A-17C515200200300450500
RB2-1-S-590A-18C590200250350500600
RB2-1-S-720A-19C720250300400600700
RB2-1-S-838A-20C838300350500700800
NOMINAL
AMPS
200-208V230-240V380-400V440-480V575-600V
HORSEPOWER RATING
z NOTE: Do not exceed Class 10 overload setting.
14
2.3.2Heavy Duty (500% current for 30 sec) Ratings
Table 5: Heavy Duty Horsepower Ratings
Heavy Duty(500% current for 30 seconds, 125% Continuous)
2 - TECHNICAL SPECIFICATIONS
MODEL NUMBER
RB2-1-S-027A-11C247.510152025
RB2-1-S-040A-11C401015253040
RB2-1-S-052A-12C541520304050
RB2-1-S-065A-12C541520304050
RB2-1-S-077A-13C541520304050
RB2-1-S-096A-13C9630405075100
RB2-1-S-125A-14C125405075100125
RB2-1-S-156A-14C125405075100125
RB2-1-S-180A-14C125405075100125
RB2-1-S-180A-15C1806075100150200
RB2-1-S-240A-15C2156075125150200
RB2-1-S-302A-15C2156075125150200
RB2-1-S-361A-16C25275100150200250
RB2-1-S-414A-17C372125150200300400
RB2-1-S-477A-17C372125150200300400
RB2-1-S-515A-17C372125150200300400
RB2-1-S-590A-18C551200200300450500
RB2-1-S-720A-19C623200250350500600
RB2-1-S-838A-20C623200250350500600
NOMINAL
AMPS
200-208V230-240V380-400V440-480V575-600V
HORSEPOWER RATING
z NOTE: Do not exceed Class 20 overload setting.
15
2 - TECHNICAL SPECIFICATIONS
2.3.3Severe Duty (600% current for 30 sec) Ratings
Table 6: Severe Duty Horsepower Ratings
Severe Duty (600% current for 30 seconds 125% Continuous)
MODEL NUMBER
RB2-1-S-027A-11C2457.5101520
RB2-1-S-040A-11C401010203040
RB2-1-S-052A-12C451015253040
RB2-1-S-065A-12C451015253040
RB2-1-S-077A-13C451015253040
RB2-1-S-096A-13C772530406075
RB2-1-S-125A-14C10530406075100
RB2-1-S-156A-14C10530406075100
RB2-1-S-180A-14C10530406075100
RB2-1-S-180A-15C1805060100125150
RB2-1-S-240A-15C1805060100125150
RB2-1-S-302A-15C1805060100125150
RB2-1-S-361A-16C2106075125150200
RB2-1-S-414A-17C310100125150250300
RB2-1-S-477A-17C310100125150250300
RB2-1-S-515A-17C310100125150250300
RB2-1-S-590A-18C515150200300450500
RB2-1-S-720A-19C515150200300450500
RB2-1-S-838A-20C515150200300450500
NOMINAL
AMPS
200-208V230-240V380-400V440-480V575-600V
HORSEPOWER RATING
z NOTE: Do not exceed Class 30 overload setting.
16
2 - TECHNICAL SPECIFICATIONS
2.3.4Inside Delta Connected Standard Duty (350% for 30 sec) Ratings
Table 7: Inside Delta Standard Duty Horsepower Ratings
C43A521_ 0 _CR52155124baT suBbaT suB1KR/T CA V006/J053Ak001B36DFCA522Ak24063
C43A651_ 0 _CR65159124baT suBbaT suB1KR/T CA V006/J004Ak001B36DFCA522Ak56534
C53A081_ 0 _CR08152224baT suBbaT suB1KR/T CA V006/J004Ak001B36DFCA052Ak56594
C53A042_ 0 _CR04200324baT suBbaT suB1KR/T CA V006/J006Ak001B36DFCA004Ak56546
C53A203_ 0 _CR20377324baT suBbaT suB1KR/T CA V006/J008Ak001B36DFCA004Ak56008
C53A163_ 0 _CR16312424baT suBbaT suB1KR/T CA V006/J008Ak001
C53A774_ 0 _CR77469524baT suBbaT suB1KR/T CA V006/J008Ak001
C63A095_ 0 _CR09573724baT suBbaT suBL0041Ak001
C63A027_ 0 _CR02700924baT suBbaT suBL0061Ak001
rebmuN ledoM
C63A048_ 0 _CR048050158baT suBbaT suBL0061Ak001
C73-A0801_0-_CR0801053158baT suBbaT suBL
C73A069_ 0 _CR069002158baT suBbaT suBL
20
2.3.8RB2 Starter Control Power Requirements
Table 8: RB2 Starter CPT VA Requirements
2 - TECHNICAL SPECIFICATIONS
Power
Model Number
RB2-1-S-027A-11C7475RB2-1-S-240A-15C243250
RB2-1-S-040A-11C7475RB2-1-S-302A-15C243250
RB2-1-S-052A-12C111125RB2-1-S-361A-16C243250
RB2-1-S-065A-12C111125RB2-1-S-414A-17C441450
RB2-1-S-077A-13C111125RB2-1-S-477A-17C441450
RB2-1-S-096A-13C111125RB2-1-S-515A-17C441450
RB2-1-S-125A-14C131150RB2-1-S-590A-18C441450
RB2-1-S-156A-14C243250RB2-1-S-720A-19C441450
RB2-1-S-180A-14C243250RB2-1-S-838A-20C243250
2.3.9RC2 Starter Control Power Requirements
Model Number
RC2-1-S-027A-31C4575RC2-1-S-240A-35C123150
RC2-1-S-040A-31C4575RC2-1-S-302A-35C123150
RC2-1-S-052A-31C4575RC2-1-S-361A-35C201250
RC2-1-S-065A-32C4575RC2-1-S-414A-35C150200
RC2-1-S-077A-32C4575RC2-1-S-477A-35C225350
RC2-1-S-096A-33C4575RC2-1-S-590A-35C225350
RC2-1-S-124A-33C4575RC2-1-S-720A-36C225350
RC2-1-S-125A-34C123150RC2-1-S-840A-19C225350
RC2-1-S-156A-34C123150RC2-1-S-960A-20C225350
RC2-1-S-180A-34C123150RC2-1-S-1200A-37C285350
Required
(VA)
Power
Required
(VA)
Recommended
Min. TX size
Table 9: RC2 Starter CPT VA Requirements
Recommended
Min. TX size
Model Number
Model Number
Power
Required
(VA)
Power
Required
(VA)
Recommended
Min. TX size
Recommended
Min. TX size
21
2 - TECHNICAL SPECIFICATIONS
Mechanical Drawings
2.4Dimensions
2.4.1RB2 Chassis with Integral Bypass
Figure 3: RB2 - 27A - 96A
Figure 4: RB2 125 - 361A
Model
RB2 27-65A
RB2 77-96A
Model
RB2 125A
RB2 156-180A
RB2 180-302A
RB2 361A
ABCDEF
141012.58.430.840.31
151013.58.430.840.31
ABCDEF
19.5 12.27 13.2540.50.31
21.25 12.00 15.2540.50.31
22.75 12.16 16.7540.50.31
23.91 13.16 18.63 4.310.50.31
22
Figure 5: RB2 414 - 838A
2 - TECHNICAL SPECIFICATIONS
Model
RB2 414-590A
RB2 720A29.38 18.52860.31
RB2 838A27.75 26.623.58.70.31
ABCDE
27.66 18.5 26.2560.31
23
2 - TECHNICAL SPECIFICATIONS
2.4.2RC2 Chassis with no Bypass
Figure 6: RC2 0 - 124A
Figure 7: RC2 156 - 590A
Model
RC2 27-52A
RC2 65-77A
RC2 96-124A
ABCDE
149.875 3.375 4.698-32 TAP
18104.375 4.75¼-20 TAP
27105.313 4.75¼-20 TAP
24
Model
RC2 156-180A
RC2 240A
RC2 302-361A
RC2 477A
RC2 590A
ABCDE
18151713.50.3
24152313.50.5
2817.252715.750.5
28202718.50.5
35203418.50.5
2.5Environmental Conditions
2 - TECHNICAL SPECIFICATIONS
Environmental Conditions
Table 10: Environmental Ratings
z NOTE: It is recommended that the starter be powered up once per year, for one hour continuously to avoid deterioration of
electrolytic capacitors and subsequent starter failure.
2.6Altitude Derating
Benshaw's starters are capable of operating at altitudes up to 3,300 feet (1000 meters) without requiring altitude derating. Table 11
provides the derating percentage to be considered when using a starter above 3,300 feet (1000 meters).
Operating Temperatures-10°C to +40°C (14°F to 104°F)enclosed
-10°C to +50°C (14°F to 122°F)open
Storage Temperatures-20°C to +70°C (-4°F to 155°F)
Humidity0% to 95% non condensing
Altitude 1000m (3300ft) without derating
Maximum Vibration5.9m/s2 (19.2ft/s2 ) [0.6G]
CoolingRC (Natural convection)
RB (Bypassed)
Altitude Derating
Table 11: Altitude Derating
AltitudePercent Derating (Amps)
3300 Feet1006 meters0.0%
4300 Feet1311 meters3.0%
5300 Feet1615 meters6.0%
6300 Feet1920 meters9.0%
7300 Feet2225 meters12.0%
8300 Feet2530 meters15.0%
9300 Feet2835 meters18.0%
For derating above 10,000 feet consult Benshaw Inc.
25
2 - TECHNICAL SPECIFICATIONS
Approvals
2.7Approvals
MX2 Control Card is UL, cUL Recognized
Certificate of Compliance
2.8Certificate of Compliance
CE Mark, See Appendix D on page 198.
26
3Installation
3 - INSTALLATION
3INSTALLATION
Before You Start
3.1Before You Start
3.1.1Inspection
Before storing or installing the RediStart MX2 Series Starter, thoroughly inspect the device for possible shipping damage. Upon receipt:
• Remove the starter from its package and inspect exterior for shipping damage. If damage is apparent, notify the shipping agent and
your sales representative.
• Open the enclosure and inspect the starter for any apparent damage or foreign objects. Ensure that all of the mounting hardware and
terminal connection hardware is properly seated, securely fastened, and undamaged.
• Ensure all connections and wires are secured.
• Read the technical data label affixed to the starter and ensure that the correct horsepower and input voltage for the application has
been purchased.
• The numbering system for a chassis is shown below.
3.1.2Installation Precautions
Installation of some models may require halting production during installation. If applicable, ensure that the starter is installed when
production can be halted long enough to accommodate the installation. Before installing the starter, ensure:
• The wiring diagram (supplied separately with the starter) is correct for the required application.
• The starter is the correct current rating and voltage rating for the motor being started.
• All of the installation safety precautions are followed.
• The correct power source is available.
• The starter control method has been selected.
• The connection cables have been obtained (lugs and associated mounting hardware).
• The necessary installation tools and supplies are procured.
• The installation site meets all environmental specifications for the starter NEMA/CEMA rating.
• The motor being started has been installed and is ready to be started.
• Any power factor correction capacitors (PFCC) are installed on the power source side of the starter and not on the motor side.
Failure to remove power factor correction or surge capacitors from the load side of the starter will result in serious damage to the starter
that will not be covered by the starter warranty. The capacitors must be connected to the line side of the starter. The up-to-speed (UTS)
contact can be used to energize the capacitors after the motor has reached full speed.
3.1.3Safety Precautions
To ensure the safety of the individuals installing the starter, and the safe operation of the starter, observe the following guidelines:
• Ensure that the installation site meets all of the required environmental conditions (Refer to Site Preparation, page 29).
• LOCK OUT ALL SOURCES OF POWER.
• Install circuit disconnecting devices (i.e., circuit breaker, fused disconnect or non-fused disconnect) if they were not previously
installed by the factory as part of the package.
• Install short circuit protection (i.e., circuit breaker or fuses) if not previously installed by the factory as part of the package.
• Consult Power Ratings for the fault rating on pages 18-20.
• Follow all NEC (National Electrical Code) and/or C.S.A. (Canadian Standards Association) standards or Local Codes as applicable.
• Remove any foreign objects from the interior of the enclosure, especially wire strands that may be left over from installation wiring.
• Ensure that a qualified electrician installs wiring.
• Ensure that the individuals installing the starter are wearing ALL protective eyewear and clothing.
• Ensure the starter is protected from debris, metal shavings and any other foreign objects.
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of
electrical shock, current carrying parts and other components of the starter should be inspected and replaced if damaged.
28
3.2Installation Considerations
3.2.1Site Preparation
General Information
Before the starter can be installed, the installation site must be prepared. The customer is responsible for:
• Providing the correct power source.
• Providing the correct power protection.
• Selecting the control mechanism.
• Obtaining the connection cables, lugs and all other hardware
• Ensuring the installation site meets all environmental specifications for the enclosure NEMA rating.
• Installing and connecting the motor.
Power Cables
The power cables for the starter must have the correct NEC/CSA current rating for the unit being installed. Depending upon the model,
the power cables can range from a single #14 AWG conductor to four 750 MCM cables. (Consult local and national codes for selecting
wire size).
Site Requirements
The installation site must adhere to the applicable starter NEMA/CEMA rating. For optimal performance, the installation site must meet
the appropriate environmental and altitude requirements.
3.2.2EMC Installation Guidelines
GeneralIn order to help our customers comply with European electromagnetic compatibility standards, Benshaw Inc. has
developed the following guidelines.
3 - INSTALLATION
Installation Considerations
AttentionThis product has been designed for Class A equipment. Use of the product in domestic environments may cause radio
EnclosureInstall the product in a grounded metal enclosure.
GroundingConnect a grounding conductor to the screw or terminal provided as standard on each controller. Refer to layout/power
WiringRefer to Wiring Practices on page 31.
FilteringTo comply with Conducted Emission Limits (CE requirement), a high voltage (1000V or greater) 0.1 uF capacitor
3.2.3Use of Power Factor Capacitors
Power factor correction capacitors and surge capacitors CAN NOT be connected between the starter and the motor. These devices can
damage the SCRs during ramping. These devices appear like a short circuit to the SCR when it turns on, which causes a di/dt level
greater than the SCR can handle. If used, power factor correction capacitors or surge capacitors must be connected ahead of the starter
and sequenced into the power circuit after the start is completed. A programmable relay can be configured as an up-to-speed (UTS) relay
and then used to pull-in a contactor to connect the capacitors after the motor has reached full speed.
z NOTE: If the motor manufacturer supplies surge capacitors they must be removed before starting.
3.2.4Use of Electro-Mechanical Brakes
If an electro-mechanical brake is used with the starter, it must be powered from the line side of the starter to ensure full voltage is applied
to the brake during a start so it will properly release. A programmable relay can be configured as a run relay and then used to pull-in a
contactor to power the brake whenever the starter is not providing power to the motor.
3.2.5Reversing Contactor
If the application requires a reversing contactor, it should be connected on the output side (load) of the soft starter. The contactor must
be closed before starting the soft starter. The soft starter must be off before switching the direction of the reversing contactor. The
reversing contactor must never be switched while the soft starter is operating.
interference, in which case the installer may need to use additional mitigation methods.
wiring schematic for grounding provision location.
should be connected from each input line to ground at the point where the line enters the cabinet.
29
3 - INSTALLATION
Mounting Considerations
3.3Mounting Considerations
3.3.1Bypassed Starters
Provisions should be made to ensure that the average temperature inside the enclosure never rises above 50°C. If the temperature inside
the enclosure is too high, the starter can be damaged or the operational life can be reduced.
3.3.2Non-Bypassed Starters
Provisions should be made to ensure that the temperature inside the enclosure never rises above 50°C. If the temperature inside the
enclosure is too high, the starter can be damaged or the operational life can be reduced. As a general rule of thumb, the following
ventilation guidelines can be followed.
Current RangeBottom of EnclosureTop of Enclosure
< 200 ampsFans or grills depending on enclosure size
200 to 300 amps2 x 4” grills (12 sq. in.)2 x 4” grills (12 sq.in.)
301 to 400 amps1 x 4” fan (115 cfm)2 x 4” grills (12 sq.in.)
401 to 600 amps2 x 4” fan (230 cfm)2 x 6” grills (28 sq.in.)
601 to 700 amps2 x 6” fan (470 cfm)2 x 6” grills (28 sq.in.)
> 700 ampsConsult factoryConsult Factory
Table 12: Ventilation Requirements
The starter produces 4 watts of heat per amp of current and 26 square inches of enclosure surface is required per watt of heat generation.
Contact Benshaw and ask for the enclosure sizing technical note for more information concerning starters in sealed enclosures. Benshaw
supplies starters under 124 amps non-bypassed, with the heat sink protruding from the back of the enclosure. This allows a small
enclosure size while still maintaining the cooling capability of the starter.
30
3.4Wiring Considerations
3.4.1Wiring Practices
When making power and control signal connections, the following should be observed:
• Never connect input AC power to the motor output terminals T1/U, T2/V, or T3/W.
• Power wiring to the motor must have the maximum possible separation from all other wiring. Do not run control wiring in the same
conduit; this separation reduces the possibility of coupling electrical noise between circuits. Minimum spacing between metallic
conduits containing different wire groups should be three inches (8cm).
• Minimum spacing between different wiring groups in the same tray should be six inches.
• Wire runs outside an enclosure should be run in metallic conduit or have shielding/armor with equivalent attenuation.
• Whenever power and control wiring cross it should be at a 90 degrees angle.
• Different wire groups should be run in separate conduits.
• With a reversing application, the starter must be installed in front of the reversing contactors.
z NOTE: Local electrical codes must be adhered to for all wiring practices.
3.4.2Considerations for Control and Power Wiring
Control wiring refers to wires connected to the control terminal strip that normally carry 24V to 115V and Power wiring refers to wires
connected to the line and load terminals that normally carries 208VAC - 600VAC respectively. Select power wiring as follows:
• Use only UL or CSA recognized wire.
• Wire voltage rating must be a minimum of 300V for 230VAC systems and 600V (Class 1 wire) for 460VAC and 600VAC systems.
• Grounding must be in accordance with NEC, CEC or local codes. If multiple starters are installed near each other, each must be
connected to ground. Take care to not form a ground loop. The grounds should be connected in a STAR configuration.
• Wire must be made of copper and rated 60/75°C for units 124 Amps and below. Larger amp units may use copper or aluminum wire.
Refer to NEC table 310-16 or local codes for proper wire selection.
3 - INSTALLATION
Wiring Considerations
3.4.3Considerations for Signal Wiring
Signal wiring refers to the wires connected to the control terminal strip that are low voltage signals, below 15V.
• Shielded wire is recommended to prevent electrical noise interference from causing improper operation or nuisance tripping.
• Signal wire rating should carry as high of a voltage rating as possible, normally at least 300V.
• Routing of signal wire is important to keep as far away from control and power wiring as possible.
3.4.4Meggering a Motor
If the motor needs to be meggered, remove the motor leads from the starter before conducting the test. Failure to comply may damage the
SCRs and WILL damage the control board, which WILL NOT be replaced under warranty.
3.4.5High Pot Testing
Perform a DC high pot test if it is necessary to verify the insulation of the soft starter. The factory test voltage used is two and a half
times the RMS voltage plus 1000VDC. It is recommended to test equipment that has been in service to 75% of the factory test voltage.
The SCR gate leads must be removed from the control board to perform the high pot test. Remove the twisted red and white wire pairs
labeled from 1 to 6 that connect on the right side of the control card. Failure to comply with the test voltage or removing the gate wiring
may damage the control board which will not be replaced under warranty..
31
3 - INSTALLATION
START
Starters
stop
reset
enter
menu
MX2 CARD
BIPC-300055-01
Power and Control Drawings for Bypassed and Non Bypassed Power Stacks
3.5Power and Control drawings for Bypassed and Non Bypassed Power Stacks
Figure 8: Power Schematic for RB2 Low HP
32
START
Starters
stop
reset
enter
menu
MX2 CARD
BIPC-300055-01
Figure 9: Power Schematic for RB2 High HP
3 - INSTALLATION
33
3 - INSTALLATION
START
Starters
stop
reset
enter
menu
MX2 CARD
BIPC-300055-01
Figure 10: Power Schematic for RC2
34
3.6Power Wiring
3.6.1Recommended Incoming Line Protection
Fuses or Circuit Breaker, refer to pages 18 - 20.
Input Line Requirements
The input line source needs to be an adequate source to start the motor, generally 2 times the rating of the motor FLA. (This may not
apply in some cases such as being connected to a generator).
3.6.2Recommended Wire Gauges
The wire gauge selection is based on the FLA of the motor. Refer to NEC table 310-16 or CEC Part 1, Table 2 or local code
requirements for selecting the correct wire sizing. Ensure appropriate wire derating for temperature is applied. If more than three current
carrying conductors are in one conduit, ensure NEC table 310.15(B)(2) or CEC Part 1 Table 5C is adhered to. In some areas local codes
may take precedence over the NEC. Refer to your local requirements.
3.6.3Power Wire Connections
Attach the motor cables:
• Use the T1, T2 and T3 terminals. Use lugs/crimps or terminals (Lugs and Crimps are to be provided by the user).
Attach the power source cables:
• Use the L1, L2 and L3 terminals. Use lugs/crimps or terminals (Lugs and Crimps are to be provided by the user).
3 - INSTALLATION
Power Wiring
3.6.4Motor Lead Length
The standard starter can operate a motor with a maximum of 2000 feet of properly sized cable between the “T” leads of the starter and
that of the motor. For wire runs greater than 2000 feet contact Benshaw Inc. for application assistance. If shielded cable is used, consult
factory for recommended length.
35
3 - INSTALLATION
3.6.5Compression Lugs
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for copper wire.
Wire SizePart #Wire SizePart #
1/0BLU-1/0S20500 MCMBLU-050S2
2/0BLU-2/0S4600 MCMBLU-060S1
3/0BLU-3/0S1650 MCMBLU-065S5
4/0BLU-4/0S1750 MCMBLU-075S
250 MCMBLU-025S800 MCMBLU-080S
300 MCMBLU-030S1000 MCMBLU-100S
350 MCMBLU-035S1500 MCMBLU-150S
400 MCMBLU-040S42000 MCMBLU-200s
450 MCMBLU-045S1
Wire SizePart #Wire SizePart #
1/0BLU-1/0D20500 MCMBLU-050D2
2/0BLU-2/0D4600 MCMBLU-060D1
3/0BLU-3/0D1650 MCMBLU-065D5
4/0BLU-4/0D1750 MCMBLU-075D
250 MCMBLU-025D800 MCMBLU-080D
300 MCMBLU-030D1000 MCMBLU-100D
350 MCMBLU-035D1500 MCMBLU-150D
400 MCMBLU-040D42000 MCMBLU-200D
450 MCMBLU-045D1
Table 13: Single Hole Compression Lugs
Table 14: Two Hole Compression Lugs
36
3.6.6Torque Requirements for Power Wiring Terminations
zNOTE – For a value of slot width or length not corresponding to those specified above, the largest torque value associated with
the conductor size shall be marked. Slot width is the nominal design value. Slot length is measured at the bottom of the slot.
Slotted head NO. 10 and larger
Slot width-0.047 inch
(1.2mm) or less and
slot length ¼ inch
(6.4mm) or less
3 - INSTALLATION
Tightening torque, pound-inches (N-m)
Hexagonal head-external drive socket
Slot width-over 0.047
inch (1.2mm) or slot
length – over ¼ inch
(6.4mm) or less
Split- bolt connectors
(N-m)
wrench
Other connectors
(N-m)
37
3 - INSTALLATION
FRONT VIEWSIDE VIEW DETAIL
MUST BE A 3" (MIN.)
SPACE BETWEEN CT
AND TOP OF LUG
CUSTOMER MUST FASTEN CT
TO POWER WIRE WITH TWO 1/4"
NYLON WRAPS TO PREVENT
MOVEMENT DURING RUNNING
Dot, or X,
White Wire
inches(mm)Pound-inches(N-m)
1/8(3.2)45(5.1)
5/32(4.0)100(11.3)
3/16(4.8)120(13.6)
7/32(5.6)150(16.9)
¼(6.4)200(22.6)
5/16(7.9)275(31.1)
3/8(9.5)275(42.4)
½(12.7)500(56.5)
9/16(14.3)600(67.8)
z NOTE – For screws with multiple tightening means, the largest torque value associated with the conductor size
shall be marked. Slot length shall be measured at the bottom of the slot.
Current Transformers
3.7Current Transformers
3.7.1CT Mounting
For starters larger than 124 amps, the CTs are shipped loose from the power stack and need to be mounted on the power wiring. Thread
the incoming lead through the CT with the polarity mark towards the line side. (The polarity marks may be a white or yellow dot, an “X”
on the side of the CT, or the white wire.) Each phase has its own CT. The CT must then be attached to the power wiring, at least three
inches from the power wire lugs, using two tie-wraps.
Table 16: Tightening Torque for Inside Hex Screws
Socket size across flatsTightening torque
3.7.2CT Polarity
The CT has a polarity that must be correct for the starter to correctly measure Watts, kW Hours, Power Factor, and for the Power and
TruTorque motor control functions to operate properly.
Each CT has a dot on one side of the flat surfaces. This dot, normally white in color, must be facing in the direction of the line.
CT1 must be on Line L1, CT2 must be on Line L2, CT3 must be on Line L3.
Figure 11: Typical CT Mounting, Input of Starter
38
3.8Control Card Layout
A
B
C
D
E
F
G
H
123456
Unfused
120 VAC Out
Control
Power
120 VAC
Auxiliary
Relays
P52-54
I/O 5-7
Digital
Inputs
P48-50
I/O 1-3
Modbus
Communications
Port P68-71
FUN 10-13
Keypad Port
P65 I/O 18
Analog Input
P55-59
I/O 8-12
Analog Output
P60-62
I/O 13-15
Analog Voltage/Current
Selector Switch SW1
Part/Serial #
Rese
t
Pa
ram
e
t
e
r
D
ow
n
Up
En
te
r
Software Part #
120 VAC
Stack In
(Benshaw Only)
Stack
Control
SCR 1
SCR 4
SCR 2
SCR 5
SCR 3
SCR 6
CT Inputs
P78
FUN 03
120VAC
StackIn
(BenshawOnly)
Stack
Control
SCR1
SCR4
SCR2
120VAC
StackIn
(BenshawOnly)
Stack
Control
SCR1
SCR4
SCR2
120VAC
StackIn
(BenshawOnly)
Stack
Control
SCR1
SCR4
SCR2
120VAC
StackIn
(BenshawOnly)
Stack
Control
SCR1
SCR4
SCR2
120VAC
StackIn
(BenshawOnly)
Stack
Control
SCR1
SCR4
SCR2
3 - INSTALLATION
Control Card Layout
Figure 12: Control Card Layout
39
3 - INSTALLATION
120VAC LIVE
120VAC NEUTRAL
TB1
120VAC LIVE
120VAC NEUTRAL
TRIP
TRIP PILOT LIGHT
(RELAY 1 SET TO FLFS - FAULT FAILSAFE)
120VAC LIVE
120VAC NEUTRAL
STOP
RUN & STOPPED PILOT LIGHT
(RELAY 2 SET TO RUN)
RUN
TB2TB2
Control Wiring
3.9Control Wiring
3.9.1Control Power
The 120VAC control power is supplied to TB1. The connections are as follows:
1 - Ground
2 - Neutral
3 - Neutral
4 - Line (120VAC)
5 - Line (120VAC)
Figure 13: Control Power Wiring Example
3.9.2Output Relays
TB2 is for the output relays. The relays connect as follows:
1 - NO1: Relay 1 normally open
2 - RC1: Relay 1 common
3 - NC1: Relay 1 normally closed
4 - NO2: Relay 2 normally open
5 - RC2: Relay 2 common
6 - NC2: Relay 2 normally closed
7 - NO3: Relay 3 normally open
8 - RC3: Relay 3 common
9 - NC3: Relay 3 normally closed
Figure 14: Relay Wiring Examples
See AlsoRelay Output configuration (I/O 05 - 07) on page 112.
40
3.9.3Digital Input Wiring Options
120VAC LIVE
120VAC NEUTRAL
120VAC LIVE
120VAC NEUTRAL
START
DI1
DI2
DI3
120VAC LIVE
120VAC NEUTRAL
120VAC NEUTRAL
120VAC LIVE
120VAC NEUTRAL
120VAC LIVE
120VAC NEUTRAL
PLC
OUTPUT CONTACT
START
STOP
SLOW SPEED
DIGITAL INPUT WIRING
2-WIRE ON / OFF SELECTOR SWITCH
SLOW SPEED CONTROL BUTTON
3-WIRE START / STOP BUTTONS
HAND / OFF / AUTO SELECTOR SWITCH
EXTERNAL TRIP INPUT
(DI2 SET TO SSPD - SLOW SPEED)
120VAC LIVE
TRIP
(DI3 SET TO FL - FAULT LOW)
START
STOP
TB3TB3
TB3TB3
TB3TB3
(DI1 SET TO STOP)
(DI1 SET TO STOP)
TB3 is for the digital inputs. The digital inputs use 120VAC. The digital inputs are as follows:
1 - Start: Start Input
2 - DI1: Digital Input 1
3 - DI2: Digital Input 2
4 - DI3: Digital Input 3
5 - Com: 120VAC neutral
3 - INSTALLATION
Figure 15: Digital Input Wiring Examples
See AlsoDigital Input configuration (I/O 01 - 03) on page 110.
41
3 - INSTALLATION
(5K-10K ohm)
POTENTIOMETER4-20mA
4-20mA SOURCE
+
-
TB5TB5
V/I
TO METER / ANALOG INPUT CARD
+
-
TB5
3.9.4Analog Input
The analog input can be configured for voltage or current loop. The input is shipped in the voltage loop configuration unless specified in
a custom configuration. Below TB5 is SW1-1. When the switch is in the on position, the input is current loop. When off, it is a voltage
input. The control is shipped with the switch in the off position. See Figure 18.
z NOTE: The analog input is a low voltage input, maximum of 15VDC. The input will be damaged if control power (115VAC) or line
power is applied to the analog input.
The terminals are as follows:
1 ) +10VDC Power (for POT)
2 ) + input
3 ) - input
4 ) common
7 ) shield
Figure 16: Analog Input Wiring Examples
See AlsoAnalog Input (I/O 08 - 12) on page 113.
3.9.5Analog Output
The analog output can be configured for Voltage or Current loop. The output is shipped in the Voltage loop configuration unless
specified in a custom configuration. Below TB5 is SW1-2. When the switch is in the off position, the output is current. When on, it is a
Voltage loop output. The control is shipped with the Switch on. See Figure 18.
z NOTE: The analog output is a low voltage output, maximum of 15VDC. The output will be damaged if control power (115VAC)
or line power is applied to it.
The terminals are as follows:
5 - analog output
6 - common
7 - shield
Starter Type parameter (FUN 07) on page 124.
Theory of Operation section 7.11, Phase Control on page 165.
Theory of Operation section 7.12, Current Follower on page 167.
Figure 17: Analog Output Wiring Example
See AlsoAnalog Output configuration (I/O 13 - 15) on page 116.
42
3 - INSTALLATION
ANALOG OUTPUT
SW1-2
ON = 0-10V
OFF = 0-20mA
ANALOG INPUT
SW1-1
ON = 0-20mA
OFF = 0-10V
3.9.6SW1 DIP Switch
The DIP switch on the card changes the analog input and analog output between 0-10V or 0-20mA. The picture below shows how to adjust
the switch to select the desired signal. Switching to the up or top position is ON and switching towards card or down is OFF.
Figure 18: DIP Switch Settings
Remote LCD Keypad/Display
3.10Remote LCD Keypad/Display
The display has a NEMA 13/IP65 service rating. The display is available in 2 versions, a small display as P/N KPMX3SLCD and large
display as P/N KPMX3LLCD.
3.10.1Remote Display
The MX2 control has one of two types of keypads, either a LED display or a LCD display. As standard, a LED display is permanently
mounted on the control board. The LCD keypad is optional and is mounted remotely from the MX2 Control card via a straight through
CAT5 ethernet cable which connects between the MX2 RJ45 terminal and remote display's RJ45 terminal.
43
3 - INSTALLATION
50.50
[1.99"]
50.50
[1.99"]
31.50
[1.24"]
31.50
[1.24"]
101.00
[3.98"]
63.00
[2.48"]
63.50
[2.50"]
63.50
[2.50"]
38.50
[1.52"]
38.50
[1.52"]
127.00
[5.00"]
77.00
[3.03"]
3.10.2Display Cutout
Figure 19: Small Display Keypad Mounting Dimensions
Part # : KPMX3SLCD
Figure 20: Large Display Keypad Mounting Dimensions
Part # : KPMX3LLCD
44
3.10.3Installing Display
MX² DISPLAY
GASKET
ENCLOSURE DOOR
MX² DISPLAY CABLE
CLIP
CLIP
The remote display is installed as follows:
• Install the gasket onto the display.
• Insert the display through the door cutout.
• Insert the mounting clips into the holes in each side of the display.
• Tighten the mounting clips until they hold the display securely in place. Torque requirements for the display screen is 0.7 NM (6.195
in lbs).
• Plug the cable into the display connector on the MX
location.
• Route the cable through the enclosure to the display. Observe the wiring considerations as listed in section 3.4.3 on page 31.
• Plug the other end of the cable into the LCD display.
z NOTE: At temperatures less than -20°C, the LCD contrast may be impaired.
2
card. See Figure 12 – Control Card Layout on page 39 for the connector
Figure 21: Mounting Remote Keypads
3 - INSTALLATION
45
3 - INSTALLATION
NOTES:
46
4Keypad Operation
4 - KEYPAD OPERATION
PARAMDOWNUPENTERRESET
4KEYPAD OPERATION
Introduction
4.1Introduction
The MX2 provides a comprehensive set of parameters to allow the use of the reduced voltage solid state starter in nearly any industrial
application. While the starter can meet the requirements of many applications right out of the box, customization of parameter values to
better suit your particular application is easily accomplished with the standard, on-board, 4-digit, 7-segment LED display/keypad.
The MX2 has an optional 2x16 character, back-lit LCD display/keypad that may be mounted remotely from the MX2 control card. The
remote LCD keypad has the same keys as the standard display with several additional keys including start and stop keys for operation of
the starter from the keypad. When the remote LCD keypad is connected, the local display is disabled.
Standard Keypad and Display
4.2Standard Keypad and Display
The LED display provides information on starter operation and programming. The 4-digit, 7-segment display shows starter meter
outputs and programming data. Special symbols provide further information about the starter operation (see the following section).
Figure 22: The Standard Keypad and Display
Viewing Parameter Values for the Standard Keypad
4.3Viewing Parameter Values for the Standard Keypad
Parameter view mode can be entered by:
1.At the default meter display, press the [PARAM] key to enter parameter mode. "P1" is displayed to indicate
Parameter 1.
2.Use the [UP] and [DOWN] keys to scroll through the available parameters.
3.Pressing the [UP] key from "P 1" advances to parameter "P 2".
4.Pressing the [DOWN] key from "P1" wraps around to the highest parameter.
5.The value of the parameter can be viewed by pressing the [ENTER] key.
6.To view another parameter without changing/saving the parameter, press the [PARAM] key to return to the parameter number display.
To return to the default meter display either:
1.Press the [PARAM] key while in the parameter number display mode.
2.Wait 60 seconds and the display returns to the default meter display.
48
4.4Changing Parameter Values
Parameter change mode can be entered by:
1.At the default meter display, press the [PARAM] key to enter parameter mode.
2.Use the [UP] and [DOWN] keys to scroll through the available parameters.
3.The value of the parameter can be viewed by pressing the [ENTER] key.
4.When viewing the parameter value, the parameter can be changed by using the [UP] and [DOWN] keys.
5.To store the new value, press the [ENTER] key. When the [ENTER] key is pressed the value is saved and the display goes back to
parameter # "P_".
To exit parameter change mode without saving the new parameter value either:
1.Press the [PARAM] key to return to the parameter number display.
2.Wait 60 seconds and the display returns to the default meter display.
4.5Messages Displayed
In addition to being able to view and change parameters, various special messages may be displayed during different conditions. Here is
a summary of the possible special messages.
4 - KEYPAD OPERATION
Changing Parameter Values
Messages Displayed
noL
rdY
Acc
Acc2
utS
run
dcL
A OL
F OL
L OL
L CP
LOC
SSPd
L Ot
SS r
L 1 r
No Line
Ready
Accelerating or Kicking
Accelerating or Kicking with ramp 2oxxxxxx = overload content.
Up to Speed
Run - Done with Accel ramp but not yet Up to
Speed
Decelerating Motor
Overload Alarm - The motor overload level is
between 90% and 100%
Overload Fault - The motor overload level has
reached 100%
Overload Lockout - A start is not allowed until
the motor overload level cools below 15%.
Control Power Lockout - A start is not allowed
because the control power is too low.
Lock out State
Slow Speed Motor Operation
Power Stack Over Temperature Lockout
Slow Speed Reverse
Digital Inputs (Run Enable or Run Disable) are
preventing the starter from running
AbC
CbA
SPH
P xx
A xx
F xx
ioc
dFLt
HEAt
ES
FLSH
ProG
rEAd
donE
L dS
dcb
SS F
Phase order meter showing ABC
Phase order meter showing CBA
Phase order meter showing Single Phase
xx = Parameter code.
xx = Alarm code. If the condition persists, a fault
occurs.
xx = Fault code.
Instantaneous Over current
Default – Flashes when parameter defaults are
loaded.
Heater/Anti-windmill Mode
Energy Saver
In reflash mode
In reflash mode, programming
In reflash mode, verifying
In reflash mode, complete
Disconnect Switch Open
DC Injection Brake Active
Slow Speed Forward
The following sections provide more detail for some of the conditions that cause special messages to be displayed.
4.5.1Power Up
The software version is displayed as a series of single digits once power has been applied to the MX2. If the parameters were being reset
on power up, “dFLt” is flashed on the display for three seconds, and then the software version is displayed.
4.5.2Stopped
When the starter is not in the run mode, the display shows the status condition of the starter, such as “rdY” (ready), “L OL” (Overload
Lockout), or “noL” (No Line).
49
4 - KEYPAD OPERATION
4.5.3Running
When running, the display shows the selected meter function. The following meters can be selected using the Meter display parameter
(P79).
Avg. RMS current
Phase 1 RMS current
Phase 2 RMS currentL2-L3 Voltage (RMS)VARSAnalog Output %Last Start Time
Phase 3 RMS currentL3-L1 Voltage (RMS)KWhRunning Time DaysPeak Start Current
Current Imbalance %Overload %MWhRunning Time Hours
GF Current (% FLA)Power FactorPhase RotationStarts
4.5.4Alarm Condition
When an alarm condition exists, the display alternates between displaying the selected meter and the alarm code. The alarm code is
displayed as “A XX”, where XX is the alarm code.
• When a thermal overload alarm condition exists, “A OL” is displayed.
• When a no line alarm condition exists, “noL” is displayed.
When the starter is stopped, the selected meter is not displayed.
4.5.5Lockout Condition
When a lockout condition exists, the display shows the lockout code. The lockout code is displayed as “L XX”: where XX is the lockout
code. Following are the defined lockout conditions and their codes:
• When a motor thermal overload lockout condition exists, “L OL” is displayed.
• When a power stack thermal overload lockout condition exists, “L Ot” is displayed.
• When a low control power lockout condition exists, “L CP” is displayed.
• When either Run Enable or Run Disable input are preventing the starter from running.
When there are multiple lockout codes, each is displayed at 2 second intervals.
4.5.6Faulted Condition
When a fault condition exists, the display shows the fault code. The exceptions to this are as follows:
• When the fault is thermal overload trip, “F OL” is displayed.
• When the fault is Instantaneous Over current, “ioc” is displayed.
Avg. Voltage (RMS)KWLine FrequencyTruTorque %
L1-L2 Voltage (RMS)KVAAnalog Input %Power %
4.5.7Quick Meters
Although any meter may be viewed by changing the Meter parameter (P79), there are 3 “Quick Meters” that are always available with a
single key press. When the starter is in the normal display mode, the display may be toggled between the information currently displayed
and the following quick meters.
Status MeterToggle between the programmed meter display and the starter operational status display (rdY, run,
Overload MeterToggle between the programmed meter display and the overload content by pressing the [DOWN] key. The
Phase Order MeterToggle between the programmed meter display and the phase order by pressing the [UP] key. The phase order
utS, dcL, etc) by pressing the [ENTER] key.
overload is displayed as “oXXX” where XXX is the overload content. For example, when the overload content
is 76 percent, it is displayed as “o 76”.
is displayed as “AbC” or “CbA”.
50
4.6Restoring Factory Parameter Settings
To restore ALL parameters to the factory default settings, press and hold the [PARAM] and [ENTER] pushbutton switch on power up.
The display blinks “dFLt”. Parameters unique to the motor starter applications need to be set again to appropriate values before motor
operation.
P76 / FUN05 - Rated RMS Voltage (set to specified equipment rating)
P78 / FUN03 - CT Ratio (set to supplied CTs rating)
P48 / I/O01 - Digital Input #1
P49 / I/O02 - Digital Input #2
P50 / I/O03 - Digital Input #3
P52 / I/O05- Relay #1
P53 / I/O06 - Relay #2
P54 / I/O07 - Relay #3
z NOTE: You must consult the wiring schematic for digital inputs and relay output configuration.
4.7Resetting a Fault
To reset from a fault condition, press [RESET].
4 - KEYPAD OPERATION
Restoring Factory Parameter Settings
Resetting a Fault
4.8Emergency Overload Reset
To perform an emergency overload reset, press [RESET] and [DOWN]. This sets the motor thermal overload content to 0.
An alternative to this is to use a digital input:
For LED display P48, P49 or P50 EOLr (E OL Reset).
For LCD display: I/O 01, I/O 02 or I/O 03 EOLreset (E OL Reset).
See page 110: I/O Digital Input Configuration for more information.
Emergency Overload Reset
51
4 - KEYPAD OPERATION
Remote LCD Keypad and Display
4.92x16 Remote LCD Keypad
Like the standard keypad, the remote LCD keypad has the same basic functions with enhancements that allow using plain text instead of
codes and a menu structure instead of a straight line of parameters.
Additional keys have been added, such as [START], [STOP], and a [LEFT] arrow for moving the cursor around in the LCD display.
Status indicators have been added, providing additional information for the starter operation.
The remote keypad is NEMA 13/IP65 when mounted directly on the door of an enclosure with the correct gasket.
Figure 23: Remote LCD Keypad
Description of the LEDs on the Keypad
4.10Description of the LEDs on the Keypad
The keypad provides three LED indicators in addition to the 2x16 character display. The LEDs provide starter status information.
Table 17: Remote Keypad LED Functions
LEDStateIndication
STOP
RUN
ALARMFlashingAlarm condition exists. If condition persists, a fault occurs.
zNOTE: By default, the [STOP] key is always active, regardless of selected control source (Local Source and Remote Source
parameters). It may be disabled though using the Keypad Stop Disable (P65 / I/O 18) parameter. For more information refer to the
Keypad Stop Disable (P65 / I/O 18) parameter on page 119.
OnStopped
FlashingFaulted
OnRunning and up-to-speed
FlashingRunning and not up-to-speed (ramping, decelerating, braking etc).
52
Description of the Keys on the Remote LCD Keypad
enterenter
menumenu
stop
reset
stop
reset
4.11Description of the Keys on the Remote LCD Keypad
The [UP] arrow, [DOWN] arrow, [ENTER] and [MENU] keys on the LCD keypad perform the same functions as the [UP], [DOWN],
[ENTER] and [PARAM] keys on the standard keypad. Three keys have been added, with one of the keys serving a dual function.
Table 18: Function of the Keys on the LCD Keypad
KeyFunction
• This key causes the starter to begin the start sequence. The direction is dependent on wiring and phase
selection.
start
• In order for this key to work, the Local Source (QST 04) parameter must be set to "Keypad".
• Increase the value of a numeric parameter.
• Select the next value of an enumerated parameter.
• It scrolls forward through a list of parameters within a group (when the last parameter is displayed, it
scrolls to the beginning of the list).
• When a list of faults is displayed, it moves from one fault to the next.
• When the starter is in the Operate Mode, pressing [UP] allows you to change which group of meter
values is monitored.
• Decrease the value of a numeric parameter.
• Select the previous value of an enumerated parameter.
• It scrolls backward through a list of parameters within a group (when the first parameter is displayed,
it scrolls to the end of the list).
• When a list of faults is displayed, it moves from one fault to the previous fault.
• When the starter is in the Operate Mode, pressing [DOWN] allows you to change which group of
meter values is monitored.
• When editing a numeric parameter, the [LEFT] arrow key moves the cursor one digit to the left. If
cursor is already at the most significant digit, it returns to the least significant digit on the right.
• When in Menu mode, the [LEFT] arrow allows groups to be scrolled through in the opposite direction
of the [MENU] Key.
• Allows editing a parameter. Stores the change of a parameter.
• When in Fault History, [ENTER] key scrolls through information logged when a fault occurred.
• When an alarm condition exists, [ENTER] scrolls through all active alarms.
4 - KEYPAD OPERATION
• [MENU] scrolls between the operate screen and the available parameter groups.
• When viewing a parameter, pressing [MENU] jumps to the top of the menu.
• When a parameter is being edited and [MENU] is pressed, the change is aborted and the parameter’s
old value is displayed.
• The [STOP/RESET] key halts the operation of the starter (Stop Key).
• If a fault has occurred, the [STOP/RESET] key is used to clear the fault.
• The [STOP] key may be disabled using the Keypad Stop Disable (I/O 18) parameter, if the control
source (QST 04/QST 05) is not set to "Keypad". The [STOP/RESET] key always halts the operation
of the starter if the control source is set to "Keypad". If the control source (QST 04/QST 05) is not set
to "Keypad".
53
4 - KEYPAD OPERATION
K
S TnOoPLP E DIVaa==
0 .00A
V
SECTION SSECTION C
SECTION BSECTION D
SECTION A
4.12Jump Code
At the beginning of each parameter group, there is a Jump Code parameter. By changing the value of this parameter and pressing
[ENTER], you can jump directly to any parameter within that group.
Alphanumeric Display
4.13Alphanumeric Display
The remote LCD keypad and display uses a 32-character alphanumeric LCD display. All starter functions can be accessed by the
keypad. The keypad allows easy access to starter programming with parameter descriptions on the LCD display.
Power UP Screen
On power up, the software part number is displayed for five seconds. Pressing any key immediately changes the display to the operate
screen.
810023-01-08
Operate Screen
The operate screen is the main screen. The Operate screen is used to indicate the status of the starter, if it’s running, what state it’s in,
and display the values of Meter 1 and Meter 2, which are selectable.
Jump Code
The Operate Screen is divided into five sections.
• Sections A and B display status information
• Section C and D displays the meter selected by the Meter 1 and 2 parameters, see FUN 01, 02.
• Section S displays the source for the start command.
Figure 24: Operate Screen
Table 19: Operate Screen Section A
DisplayDescription
NoLL1, L2, L3 not present
ReadyStarter ready to run
AlarmA fault condition is present. If it continues, a fault occurs
RunStarter is running
54
4 - KEYPAD OPERATION
Table 20: Operate Screen Section B
DisplayDescription
StoppedStarter is stopped and no Faults
FaultStarter tripped on a Fault
HeaterStarter is on and heating motor
KickStarter is applying kick current to the motor
AccelStarter is accelerating the load
Kick 2Starter is applying kick current to the motor in Ramp 2
Accel 2Starter is accelerating the load in Ramp 2
RunStarter is in Run mode and Ramp Time has expired
UTSStarter is Up To Speed
ControlPhase Control or Current Follower mode
DecelStarter is decelerating the load
WyeIn Wye-delta control indicates motor is accelerating in Wye mode
Slow Spd FwdPreset slow speed forward
Slow Spd RevPreset slow speed reverse
BrakingDC Injection Braking.
LockoutStarter is Locked Out
Table 21: Operate Screen Section S
DisplayDescription
KKeypad Control
TTerminal Block Control
SSerial Communication Control
4.13.1Parameter Group Screens
From the operate screen, the parameter group screens are accessed by pressing either the menu or the left arrow keys. The parameter
group screens display the different parameter groups; QST, CFN, PFN, I/O, FUN, FL_.
MMM: PPPPPPPPPP
MI VVVVVVVVVV
MMM:= Parameter Group
MI:= Menu Index
PPP:= Parameter Name
VVV:= Parameter Value and Units
Refer to Chapter 5 for a listing of the parameters and their ranges.
55
4 - KEYPAD OPERATION
4.13.2Meter Pages
Although any meter may be viewed by changing the two Meter parameters (FUN 01 & FUN 02), there are 13 “Meter Pages” that are
easily accessed to view all of the meter information. These meter pages are scrolled through by pressing the [UP] or [DOWN] down
arrows from the operate screen.
Current I2 = 0.0A
I1 = 0.0 I3 = 0.0A
Voltage V2= 0V
V1= 0 V3= 0V
MWatt Hour = 0
kWatt Hour = 0
Watts = 0
VA= 0
Motor PF = 0.00
vars = 0
TruTorque = 0%
Power = 0%
Overload = 0%
Curr Inbal = 0.0%
z NOTE:Run Hours00:00 – 23:59
4.13.3Fault Log Screen
More information regarding each fault is available through the remote MX2 LCD display than is available through the standard MX
LED display.
RS Gnd Cur= 0%
Lst STt Tim= xx.xs
Pk ST Cur = xx.xA
Frequency = 60.0H
Phase = AbC
Run Days = xxxx
Run Hours = xx:xx
Analog In = 0.0%
Analog Out = 0.0%
Starts = xxxxx
Run Days0 – 2730 days or 7.5 years
kWatt Hours0 – 999
MWatt Hours0 – 9999
Starts0 – 65535
2
FL#: Fault##
NNNNNNNNNNNNN
FL _:= Fault Log Number. FL1 is the most recent fault and FL9 is the oldest fault.
Fault _ _ = Fault Code
NNN…= Fault Name, or the condition when the fault occurred.
56
Press [MENU] until you get to the FL1 parameter.
Pressing the [UP] and [DOWN] keys navigates through older and newer faults in the log.
Repeatedly pressing the [ENTER] key rotates through the conditions the starter was in when the fault occurred.
Enter Step
1Fault Description.
2Status when the fault occurred, Run, Stopped, Accel. etc.
3The L1 current at the time of the fault.
4The L2 current at the time of the fault.
5The L3 current at the time of the fault.
6L1-2 voltage at the time of the fault.
7L2-3 voltage at the time of the fault.
8L3-1 voltage at the time of the fault.
9kW at the time of the fault.
10Frequency at the time of the fault.
11Run time since last run time reset.
4.13.4Fault Screen
When a Fault occurs, the main screen is replaced with a fault screen. The screen shows the fault number and the name of the fault. The
main status screen is not shown until the fault is reset.
4 - KEYPAD OPERATION
When a fault occurs, the STOP LED flashes.
Fault ##
Fault Name
z NOTE: For a list of the Faults, refer to Appendix B - Fault Codes on page 196.
4.13.5Lockout Screen
When a lockout is present, one of the following screens will be displayed. The main status screen is not shown until the lockout is
cleared.
The overload lockout displays the overload content The stack over temperature lockout will be displayed
and the time until reset if an overload occurs. if a stack over temperature is detected
Overload Lockout
96%XX:XX
The control power lockout will be displayed The disconnect open lockout will be displayed if a digital
if the control power is not within specifications. input is programmed to "disconnect" and the input if off.
Control Power
Lockout
A "Run Enable or Run Disable" digital input is
set and is not true. See digital inputs on page 110
Run Interlock
Lockout
Stack Overload
Lockout
.
Disconnect Open
Lockout
4.13.6Alarm Screen
When an alarm is present, the word “Alarm” is displayed on the operate screen. Pressing the [ENTER] key displays more information
about the alarm.
Alarm Number
Alarm Name
57
4 - KEYPAD OPERATION
Procedure for Setting Data
4.14Procedure for Setting Data
Select a parameter that is to be changed. To change Motor FLA from 10 Amps to 30 Amps:
From the main screen:
T Ready Ia= 0.0A
Stopped Va= 480 V
Press [MENU] key and the display shows QST: (Quick Start) screen.
QST: Jump Code
00 1
Press [UP] key once to Motor FLA (QST 01).
QST: Motor FLA
01 10 Amp
Press [ENTER] key once, the cursor starts to flash in the one’s place.
QST: Motor FLA
01 10 Amp
Press [LEFT] key once, the cursor flashes in the ten’s place.
QST: Motor FLA
01 10 Amp
Press [UP] arrow to increase the value, for a value of 30, press twice.
QST: Motor FLA
01 30 Amp
Press [ENTER] to store the value.
QST: Motor FLA
01 30 Amp
Press [UP] arrow to change another parameter in QST.
Press [MENU] to change another parameter in another group.
Press [LEFT] arrow to go back to the main screen
58
5Parameter Groups
5 - PARAMETER GROUPS
5PARAMETER GROUPS
Introduction
5.1Introduction
The MX2 incorporates a number of parameters that allow you to configure the starter to meet the special requirements of your particular
application. The parameters are organized two ways, depending on the display being used. When the standard, on-board LED display is
used, the parameters are in a single group and numbered P1, P2, P3… etc.
When the remote LCD display is used, the parameters are divided into groups of related functionality, and within the groups the
parameters are identified by a short, descriptive name. The parameters are subdivided into six groups. The groups are QST (Quick
Start), CFN (Control Functions), PFN (Protection Functions), I/O (Input/Output Functions), FUN (Function) and FL1 (Faults) .
The Quick Start Group provides a collection of the parameters that are most commonly changed when commissioning a starter. Many of
the parameters in the Quick Start group are duplicates of the parameters in the other groups.
This chapter lists all of the parameters and their possible values. Section 5.3 lists the parameters in the order in which they appear on the
LED display. Section 5.4 lists them in the order in which they appear on the LCD display. Section 5.2 is a cross-reference between the
two.
60
LED & LCD Display Parameters Cross Reference
5.2LED and LCD Display Parameters Cross Reference
Parameter
Number
P1QST 01
P2QST 02
P3
P4QST 04
P5QST 05
P6
P7
P8
P9QST 09
P10CFN 01
P11CFN 08
P12CFN 09
P13CFN 10
P14CFN 11
P15CFN 14
P16CFN 15
P17CFN 16
P18CFN 17
P19CFN 18
P20CFN 19
P21CFN20
P22CFN 06
P23CFN 07
P24CFN 05
P25CFN 12
P26CFN 13
P27CFN 21
P28CFN 22
P29CFN 23
P30CFN 24
P31CFN 25
P32PFN 01
P33PFN 02
P34PFN 03
P35PFN 04
P36PFN 05
P37PFN 06
P38PFN 07
P39PFN 08
P40PFN 09
P41PFN 10
GroupParameter NamePage #
Motor FLA
Motor Service Factor
QST 03
PFN 15
QST 06
CFN 03
QST 07
CFN 04
QST 08
CFN 02
Motor Running Overload Class
Local Source
Remote Source
Initial Current 1
Maximum Current 1
Ramp Time 1
Up To Speed Time
Start Mode
Initial Voltage/Torque/Power
Maximum Torque/Power
Kick Level 1
Kick Time 1
Stop Mode
Decel Begin Level
Decel End Level
Decel Time
DC Brake Level
DC Brake Time
DC Brake Delay
Initial Current 2
Maximum Current 2
Ramp Time 2
Kick Level 2
Kick Time 2
Slow Speed
Slow Speed Current Level
Slow Speed Time Limit
Slow Speed Kick Level
Slow Speed Kick Time
Over Current Level
Over Current Time
Under Current Level
Under Current Time
Current Imbalance Level
Residual Ground Fault Level
Over Voltage Level
Under Voltage Level
Voltage Trip Time
Auto Fault Reset Time
100P75FUN 06
100P76FUN 05
101P77FUN 04
102P78FUN 03
103P79FUN 01
103n/aFUN 02
104P80FUN 14
104P81FUN 16
5 - PARAMETER GROUPS
Parameter
Number
75P42PFN 11
75P43PFN 12
76P44PFN 13
77P45PFN 14
78P46PFN 16
79P47PFN 17
80P48I/O 01
81P49I/O 02
82P50I/O 03
83P51I/O 04
84P52I/O 05
85P53I/O 06
86P54I/O 07
86P55I/O 08
87P56I/O 09
88P57I/O 10
89P58I/O 11
90P59I/O 12
91P60I/O 13
92P61I/O 14
93P62I/O 15
93P63I/O 16
93P64I/O 17
94P65I/O 18
94P66I/O 19
94P67FUN 15
95P68FUN 12
95P69FUN 11
96P70FUN 10
96P71FUN 13
97P72FUN 09
98P73FUN 08
99P74FUN 07
P82FL1
GroupParameter NamePage #
Auto Reset Limit
Controlled Fault Stop Enable
Independent Starting/Running
Overload
Motor Starting Overload Class
Motor Overload Hot/Cold Ratio
Motor Overload Cooling Time
DI 1 Configuration
DI 2 Configuration
DI 3 Configuration
Digital Fault Input Trip Time
R1 Configuration
R2 Configuration
R3 Configuration
Analog Input Trip Type
Analog Input Trip Level
Analog Input Trip Time
Analog Input Span
Analog Input Offset
Analog Output Function
Analog Output Span
Analog Output Offset
Inline Configuration
Bypass Feedback Time
Keypad Stop Disable
Power On Start Selection
Miscellaneous Commands
Communication Timeout
Communication Baud Rate
Communication Address
Communication Byte Framing
Energy Saver
Heater Level
Starter Type
Rated Power Factor
Rated Voltage
Phase Order
CT Ratio
Meter 1
Meter 2
Software Version 1
Passcode
Fault Log
104
105
106
107
108
109
110
110
110
111
112
112
112
113
114
114
115
116
116
117
117
118
118
119
119
120
121
121
121
122
122
123
124
125
125
126
126
127
127
128
129
130
61
5 - PARAMETER GROUPS
LED Display Parameters
5.3LED Display Parameters
NumberParameterSetting RangeUnitsDefaultPage
P1Motor FLA1 – 6400RMS Amps1075
P2Motor Service Factor1.00 – 1.991.1575
P3Motor Running Overload ClassOff, 1 – 401076
P4Local SourcePAd: Keypad
P5Remote Source78
P6Initial Motor Current 150 – 600%FLA10079
P7Maximum Motor Current 1100 – 800%FLA60080
P8Ramp Time 10 – 300Seconds1581
P9Up To Speed Time1 – 900Seconds2082
P10Start Mode
P11Initial Voltage/Torque/Power1 – 100%2584
P12Maximum Torque/Power10 – 325%10585
P13Kick Level 1Off, 100 to 800%FLAOff86
P14Kick Time 10.1 – 10.0Seconds1.086
P15Stop Mode
P16Decel Begin Level100 – 1%4088
P17Decel End Level99 – 1%2089
P18Decel Time1 – 180Seconds1590
P19DC Brake Level10 – 100%2591
P20DC Brake Time1 – 180Seconds592
P21DC Brake Delay0.1 – 3.0Seconds0.293
P22Initial Motor Current 250 – 600%FLA10093
P23Maximum Motor Current 2100 – 800%FLA60093
P24Ramp Time 20 – 300Seconds1594
P25Kick Level 2Off, 100 – 800%FLAOff94
P26Kick Time 20.1 – 10.0Seconds1.094
P27Slow SpeedOff, 7.1 14.3%Off95
P28Slow Speed Current Level10 – 400%FLA10095
P29Slow Speed Time LimitOff, 1 – 900Seconds1096
P30Slow Speed Kick LevelOff, 100 – 800%FLAOff96
P31Slow Speed Kick Time0.1 – 10.0Seconds1.097
P32Over Current Trip LevelOff, 50 – 800%FLAOff98
P33Over Current Trip Delay TimeOff, 0.1 – 90.0Seconds0.199
P34Under Current Trip LevelOff, 5 – 100%FLAOff100
P35Under Current Trip Delay TimeOff, 0.1 – 90.0Seconds0.1100
0: Status
1: Ave Current
2: L1 Current
3: L2 Current
4: L3 Current
5: Curr Imbal
6: Ground Fault
7: Ave Volts
8: L1-L2 Volts
9: L2-L3 Volts
10: L3-L1 Volts
11: Overload
12: Power Factor
13: Watts
14: VA
15: VARS
16: kW hours
17: MW hours
18: Phase Order
19: Line Freq
20: Analog Input
21: Analog Output
22: Run Days
23: Run Hours
24: Starts
25: TruTorque %
26: Power %
27: Peak Starting Current
28: Last Starting Duration
288126
0127
65
5 - PARAMETER GROUPS
LCD Display Parameters
5.4LCD Display Parameters
The 2x16 display has the same parameters available as the LED display, with the exception of two meter parameters instead of one since
two meters may be displayed on the main screen. The parameters are subdivided into five groups. The groups are QST (Quick Start),CFN (Control Functions), I/O (Input/Output Functions), PFN (Protection Functions) and FUN (Function).
The Quick Start Group provides a collection of the parameters that are most commonly changed when commissioning a starter. Many of
the parameters in the Quick Start group are duplicates of the same parameters in other groups.
The MX2 incorporates a number of parameters that allow you to configure the starter to meet the special requirements of your particular
application.
The parameters are divided into groups of related functionality, and within the groups the parameters are identified by a short, descriptive
name. They are numbered by the group name followed by an index within the group.
This chapter lists all of the parameters and their possible values.
The following shows the menu structure for the LCD display as well as the text that is displayed for the parameters on the display.
FUN 08Heater LevelHeater LevelOff, 1 to 40%FLAOff123
FUN 09Energy SaverEnergy SaverOff, OnSecondsOff122
FUN 10Com Drop #Communication Address1 to 2471121
FUN 11Com Baud rateCommunication Baud Rate
FUN 12Com TimeoutCommunication TimeoutOff, 1 to 120SecondsOff121
L1 Current
L2 Current
L3 Current
Curr Imbal
Ground Fault
Ave Volts
L1-L2 Volts
L2-L3 Volts
L3-L1 Volts
Overload
Power Factor
Watts
VA
vars
kW hours
MW hours
Phase Order
Line Freq
Analog Input
Analog Output
Run Days
Run Hours
Starts
TruTorque %
Power %
Pk Accel Cur
Last Start T
FUN 14Software 1Software 1 Part NumberDisplay Only810023-01-08128
FUN 15Misc CommandMiscellaneous Commands
FUN 16PasscodePasscodeOff
5.4.6LCD Fault Group
Odd, 1 Stop Bit
None, 1 Stop Bit
None, 2 Stop Bit
None
Std BIST
Powered BIST
Reset RT
Reset kWh
Reflash Mode
Store Params
Load Params
Factory Rst
Even, 1 Stop122
None
120
129
Group
FL1
FL2
FL3
FL4
FL5
FL6
FL7
FL8
FL9
5.4.7LED Fault Group
Group
F1F6
F2F7
F3F8
F4F9
F5
Fault
Number
Fault
Number
Fault Description
Fault Description
Starter
State
I1I2I3V1V2V3kWHz
Fault
Number
Fault Description
Run
Time
71
5 - PARAMETER GROUPS
NOTES:
72
6Parameter Description
6 - PARAMETER DESCRIPTION
6PARAMETER DESCRIPTION
Parameter Descriptions
6.1Parameter Descriptions
The detailed parameter descriptions in this chapter are organized in the same order as they appear on the LED display. If the remote
LCD display is being used, the table in chapter 5 beginning on page 62 can be used to find the page number of the parameter in this
chapter.
Each parameter has a detailed description that is displayed with the following format.
P__Parameter NameMMM__
LED DisplayLCD Display
MMM: Parameter
MI Value
RangeParameter Value (Default: Constant)
OR
LEDLCD
EEEKeypad
Description The description of the function.
See AlsoCross references to related parameters or other chapters.
In the above format, the header box for the parameter contains the P number (as it appears in the menu on the LED display), the
parameter name and the parameter group number (as it appears in the menu on the LCD display).
The LCD Display section shows an example of what actually appears on the remote mounted keypad. The LED display shows an
example of what actually appears on the built in display. The parameter group (represented above by “MMM”) and the (possibly
abbreviated) parameter name are shown on the first line. The parameter group number (represented above by “MI” for “menu index”)
and the parameter’s value and units are shown on the second line.
Some parameters appear in two different menus of the LCD display. This is the case for those parameters that are in the Quick Start
Group. In this case, both LCD menu groups are listed in the header box and two example LCD displays are shown.
For some parameters, the Range section is enough to describe the parameter. For others, there may be an additional Options section to
describe each of the options that a parameter may be set to. The form that the options take may be different for the LED and LCD
displays, so this section shows how the options appear on both displays.
The See Also section lists cross-references to other parameters that may be related as well as references to further detail in other
chapters.
74
6 - PARAMETER DESCRIPTION
Jump to Parameter QST 00
By changing the value of this parameter and pressing [ ENTER ], you can jump directly to any parameter within that group.
DescriptionThe Motor FLA parameter configures the motor full load amps and is obtained from the nameplate on the
attached motor.
If multiple motors are connected, the FLA of each motor must be added together for this value.
zNOTE: Incorrectly setting this parameter prevents proper operation of the motor overload protection,
motor over current protection, motor undercurrent protection, ground fault protection and acceleration control.
P2Motor Service FactorQST 02
LED DisplayLCD Display
QST: Motor SF
02 1.15
Range1.00 – 1.99 (Default 1.15)
DescriptionThe Motor Service Factor parameter should be set to the service factor of the motor. The service factor is
used for the overload calculations. If the service factor of the motor is not known, then the service factor
should be set to 1.00.
zNOTE: The NEC (National Electrical Code) does not allow the service factor to be set above 1.40. Check
with other local electrical codes for their requirements.
The National Electrical Code, article 430 Part C, allows for different overload multiplier factors depending on
the motor and operating conditions. NEC section 430-32 outlines the allowable service factor for different
motors.
See AlsoTheory of Operation section 7.2, Motor Service Factor on page 139.
75
6 - PARAMETER DESCRIPTION
P3Motor Overload Class Running QST 03, PFN 15
LED DisplayLCD Display
QST: Running OL
03 10
PFN: Running OL
15 10
RangeOff, 1– 40 (Default 10)
DescriptionThe Motor Running Overload Class parameter sets the class of the electronic overload for starting and
See AlsoIndependent Starting/Running Overload (P44 / PFN 13) on page 106.
running. If separate starting versus running overload classes are desired, set the independent S\R O/L (P44 /
PFN13) parameter to "On".
The starter stores the thermal overload value as a percentage value between 0 and 100%, with 0% representing
a “cold” overload and 100% representing a tripped overload. See section 7.1, for the overload trip time
versus current curves.
When the parameter is set to "Off", the electronic overload is disabled when up to speed and a separate motor
overload protection device must be supplied.
z NOTE: Care must be taken not to damage the motor when turning the running overload class off or setting
to a high value.
zNOTE: Consult motor manufacturer data to determine the correct motor overload settings.
Motor Starting Overload Class (P45 / PFN 14) on page 107.
Motor Overload Hot/Cold Ratio (P46 / PFN 16) on page 108.
Motor Overload Cooling Time (P47 / PFN 17) on page 109.
Relay Output Configuration (P52-54 / I/O 05 - 07) on page 112.
Theory of Operation section 7.1, Solid State Motor Overload Protection on page 132.
76
6 - PARAMETER DESCRIPTION
P4Local SourceQST 04
LED DisplayLCD Display
QST: Local Src
04 Terminal
RangeLEDLCDDescription
PAdKeypadThe start/stop control is from the keypad.
tErTerminalThe start/stop control is from the terminal strip inputs. (Default)
SErSerialThe start/stop control is from the network.
DescriptionThe MX
See AlsoRemote Source (P5 / QST 05) parameter on page 78.
2
/ QST 04) - Local Source and (P5 / QST 05) - Remote Source, allows the user to change the control source.
If a digital input is programmed as “L-r” (Local / Remote), then that input selects the control source. When
the input is low, the local source is used. When the input is high, the remote source is used. If no digital input
is programmed as “L-r”, then the local/remote bit in the starter control Modbus register selects the control
source. The default value of the bit is Local (0).
Digital Input Configuration (P45-P50 / I/O 01- I/O 03) parameters on page 110.
Keypad Stop Disable (P65 / I/O 18) parameter on page 119.
Communication Timeout (P68 / FUN 12) parameter on page 121.
Communication Baud Rate (P69 / FUN 11) parameter on page 121.
Communication Address (P70 / FUN 10) parameter on page 121.
zNOTE: By default, the Stop key is always enabled, regardless of selected control source. It may be
disabled though using the P65 / I/O18 - Keypad Stop Disable parameter on page 119.
can have three sources of start and stop control; Terminal, Keypad and Serial. Two parameters, (P4
77
6 - PARAMETER DESCRIPTION
Local Source
·Keypad
Modbus Starter Control Register
Local/Remote Bit
P48, P49, P50
P5Remote SourceQST 05
LED DisplayLCD Display
QST: Remote SRC
05 Terminal
RangeLEDLCDDescription
PAdKeypadThe start/stop control is from the keypad.
tErTerminalThe start/stop control is from the terminal strip inputs. (Default)
SErSerialThe start/stop control is from the network.
DescriptionThe MX
See AlsoLocal Source (P4 / QST 04) parameter on page 77.
2
/ QST 04) - Local Source and (P5 / QST 05) - Remote Source, select the sources of the start and stop control.
If a digital input is programmed as “L-r” (Local / Remote), then that input selects the control source. When
the input is low, the local source is used. When the input is high, the remote source is used. If no digital input
is programmed as “L-r”, then the local/remote bit in the Modbus starter control register selects the control
source. The default value of the bit is Local (0).
Digital Input Configuration (P45-P50 / I/O 01- I/O 03) parameters on page 110.
Keypad Stop Disable (P65 / I/O 18) parameter on page 119.
Communication Timeout (P68 / FUN 12) parameter on page 121.
Communication Baud Rate (P69 / FUN 11) parameter on page 121.
Communication Address (P70 / FUN 10) parameter on page 121.
Modbus Register Map, refer to www.benshaw.com.
can have three sources of start and stop control; Terminal, Keypad and Serial. Two parameters, (P4
Figure 24: Local Remote Source
78
6 - PARAMETER DESCRIPTION
P6Initial Motor Current 1QST 06, CFN 03
LED DisplayLCD Display
QST: Init Cur 1
06 100 %
CFN: Init Cur 1
03 100 %
Range50 – 600 % of FLA (Default 100%)
DescriptionThe Initial Motor Current 1 parameter is set as a percentage of the Motor FLA (P1 / QST 01) parameter
See AlsoMaximum Current 1 (P7 / QST 07) parameter on page 80.
setting. The Initial Current 1 parameter sets the current that is initially supplied to the motor when a start is
commanded. The initial current should be set to the level that allows the motor to begin rotating within a
couple of seconds of receiving a start command.
To adjust the initial current setting, give the starter a run command. Observe the motor to see how long it
takes before it begins rotating and then stop the unit. For every second that the motor doesn’t rotate, increase
the initial current by 20%. Typical loads require an initial current in the range of 50% to 175%.
If the motor does not rotate within a few seconds after a start command, the initial current should be increased.
If the motor accelerates too quickly after a start command, the initial current should be decreased.
The Initial Current 1 parameter must be set to a value that is lower than the Maximum Current 1 (P7 / QST
07) parameter setting.
Ramp Time 1 (P8 / QST 08) parameter on page 81.
Start Mode (P10 / CFN 01) parameter on page 83.
Kick Level 1 (P13 / CFN 10) parameter on page 86.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times, on page 140.
79
6 - PARAMETER DESCRIPTION
P7Maximum Motor Current 1 QST 07, CFN 04
LED DisplayLCD Display
QST: Max Cur 1
07 600 %
CFN: Max Cur 1
04 600 %
Range100 – 800 % of FLA (Default 600%)
DescriptionThe Maximum Motor Current 1 parameter is set as a percentage of the Motor FLA (P1 / QST 01) parameter
See AlsoInitial Current 1 (P6 / QST 06) parameter on page 79.
setting. This parameter performs two functions. It sets the current level for the end of the ramp profile. It
also sets the maximum current that is allowed to reach the motor after the ramp is completed.
If the ramp time expires before the motor has reached full speed, the starter holds the current at the maximum
current level until either the UTS timer expires; the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower
or higher maximum current.
Ramp Time 1 (P8 / QST 08) parameter on page 81.
Up To Speed Time (P9 / QST 09) parameter on page 82.
Start Mode (P10 / CFN 01) parameter on page 83.
Kick Level 1 (P13 / CFN 10) parameter on page 86.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 140.
80
6 - PARAMETER DESCRIPTION
P8Ramp Time 1 QST 08, CFN 02
LED DisplayLCD Display
QST: Ramp Time 1
08 15 sec
CFN: Ramp Time 1
02 15 sec
Range0 – 300 seconds (Default 15)
DescriptionThe Ramp Time 1 parameter is the time it takes for the starter to allow the current, voltage, torque or power
See AlsoInitial Current 1 (P6 / QST 06) parameter on page 79.
(depending on the start mode) to go from its initial to the maximum value. To make the motor accelerate
faster, decrease the ramp time. To make the motor accelerate slower, increase the ramp time.
A typical ramp time setting is from 15 to 30 seconds.
If the ramp time expires before the motor reaches full speed, the starter maintains the maximum current level
until either the motor reaches full speed, the UTS timer expires, or the motor thermal overload trips.
zNOTE: Setting the ramp time to a specific value does not necessarily mean that the motor will take this
time to accelerate to full speed. The motor and load may achieve full speed before the ramp time expires if
the application does not require the set ramp time and maximum current to reach full speed. Alternatively, the
motor and load may take longer than the set ramp time to achieve full speed.
Maximum Current 1 (P7 / QST 07) parameter on page 80.
Up To Speed Time (P9 / QST 09) parameter on page 82.
Start Mode (P10 / CFN 01) parameter on page 83.
Kick Level 1 (P13 / CFN 10) parameter on page 86.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 140.
81
6 - PARAMETER DESCRIPTION
P9Up To Speed TimeQST 09
LED DisplayLCD Display
QST: UTS Time
09 20 sec
Range1– 900 Seconds (Default 20)
DescriptionThe Up To Speed Time parameter sets the maximum time the motor can take to accelerate to full speed. A
stalled motor condition is detected if the motor does not get up-to-speed before the up-to-speed timer expires.
The motor is considered up-to-speed once the current stabilizes below 175 percent of the FLA value and the
ramp time expires.
zNOTE: During normal acceleration ramps, the up-to-speed timer has to be greater than the sum of the
highest ramp time in use and the kick time. The up-to-speed timer does not automatically change to be greater
than the ramp time. If a ramp time greater than the up-to-speed timer is set, the starter will declare an
up-to-speed fault every time a start is attempted.
z NOTE: When the Start Mode (P10 / CFN 01) parameter is set to "Voltage Ramp", the UTS timer acts as
an acceleration kick. When the UTS timer expires, full voltage is applied to the motor. This feature can be
used to reduce motor oscillations if they occur near the end of an open loop voltage ramp start.
z NOTE: When the Starter Type (P74 / FUN 07) parameter is set to "Wye-Delta", the UTS timer is used as
the transition timer. When the UTS timer expires, the transition from Wye starting mode to Delta running
mode takes place if it has not already occurred.
Fault Code 01 - Up to Speed Fault is declared when a stalled motor condition is detected.
See AlsoRamp Time 1 (P8 / QST 08) parameter on page 81.
Start Mode (P10 / CFN 01) parameter on page 83.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Ramp Time 2 (P24 / CFN 05) parameter on page 94.
Kick Time 2 (P26 / CFN 13) parameter on page 94.
Starter Type (P74 / FUN 07) parameter on page 124.
Theory of Operation section 7.3, Acceleration Control on page 140.
Theory of Operation section 7.8, Wye-Delta on page 160.
82
6 - PARAMETER DESCRIPTION
Jump to Parameter CFN 00
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter within that group.
P10Start ModeCFN 01
LED DisplayLCD Display
CFN: Start Mode
01 Current Ramp
RangeLEDLCDDescription
oLrPVoltage RampOpen Loop Voltage acceleration ramp.
currCurrent RampCurrent control acceleration ramp. (Default)
ttTT RampTruTorque control acceleration ramp.
PrPower RampPower (kW) control acceleration ramp.
DescriptionThe Start Mode parameter allows the selection of the optimal starting ramp profile based on the application.
The closed loop current control acceleration ramp is ideal for starting most general-purpose motor
applications. Ex: crushers, ball mills, reciprocating compressors, saws, centrifuges, and most other
applications.
The closed loop TruTorque control acceleration ramp is suitable for applications that require a smooth torque
output from the motor during starting. Ex: centrifugal pumps, fans. The Tru Torque is also suitable for belt
driven applications to eliminate belt sequel that commonly occurs near full speed.
The closed loop power control acceleration ramp is ideal for starting applications using a generator or other
limited capacity source.
See AlsoInitial Current 1 (P6 / QST 06) parameter on page 79.
Maximum Current 1 (P7 / QST 07) parameter on page 80.
Ramp Time 1 (P8 / QST 08) parameter on page 81.
Initial Voltage/Torque/Power (P11 / CFN 08) parameter on page 84.
Kick Level 1 (P13 / CFN 10) parameter on page 86.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Theory of Operation section 7.3, Acceleration Control on page 140.
83
6 - PARAMETER DESCRIPTION
P11Initial Voltage/Torque/PowerCFN08
LED DisplayLCD Display
CFN: Init V/T/P
08 25 %
Range1 – 100 % of Voltage/Torque/Power (Default 25%)
DescriptionStart Mode (P10/CFN01) set to Open Loop Voltage Acceleration:
This parameter sets the starting point for the voltage acceleration ramp profile. A typical value is 25%. If the
motor starts too quickly or the initial current is too high, reduce this parameter. If the motor does not start
rotating within a few seconds after a start is commanded, increase this parameter.
Start Mode (P10/CFN01) set to Current Control Acceleration:
Not used when the Start Mode parameter is set to Current control acceleration. Refer to the P6 - Initial
Current 1 (CFN03) parameter to set the initial current level.
Start Mode (P10/CFN01) set to TruTorque Control Acceleration:
This parameter sets the initial torque level that the motor produces at the beginning of the starting ramp
profile. A typical value is 10% to 20%. If the motor starts too quickly or the initial torque level is too high,
reduce this parameter. If the motor does not start rotating within a few seconds after a start is commanded,
increase this parameter. If the value is set too low a “No Current at Run” fault may occur during acceleration.
z NOTE: It is important that the (P75 / FUN06) - Rated Power Factor parameter is set properly so that the
actual initial torque level is the value desired.
Start Mode (P10/CFN01) set to (kW) Power Control Acceleration:
This parameter sets the initial motor power (KW) level that will be achieved at the beginning of the starting
ramp profile. A typical value is 10% to 30%. If the motor starts too quickly or the initial power level is too
high, reduce this parameter. If the motor does not start rotating within a few seconds after a start is
commanded, increase this parameter. If the value is set too low a “No Current at Run” fault may occur during
acceleration.
z NOTE: It is important that the (P75 / FUN06) - Rated Power Factor parameter is set properly so that the
actual initial power level is the value desired.
See AlsoInitial Current 1 (P6 / QST 06) parameter on page 79.
Ramp Time 1 (P8 / QST 08) parameter on page 81.
Start Mode (P10 / CFN 01) parameter on page 83.
Maximum Torque/Power (P12 / CFN 09) parameter on page 85.
Rated Power Factor (P75 / FUN 06) parameter on page 125.
Theory of Operation section 7.3, Acceleration Control on page 140.
84
6 - PARAMETER DESCRIPTION
P12Maximum Torque/PowerCFN 09
LED DisplayLCD Display
CFN: Max T/P
09 105 %
Range10 – 325 % of Torque/Power (Default 105%)
DescriptionStart Mode (P10/CFN01) set to Open Loop Voltage Acceleration:
Not used when the Start Mode parameter is set to open-loop voltage acceleration. When in open loop voltage
acceleration mode, the final voltage ramp value is always 100% or full voltage.
Start Mode (P10/CFN01) set to Current Control Acceleration:
Not used when the Start Mode parameter is set to Current control acceleration mode. Refer to the Maximum
Current 1 (P7 / CFN04) parameter to set the maximum current level.
Start Mode (P10/CFN01) set to TruTorque Control Acceleration:
This parameter sets the final or maximum torque level that the motor produces at the end of the acceleration
ramp time. For a loaded motor, the maximum torque value initially should be set to 100% or greater. If the
maximum torque value is set too low, the motor may not produce enough torque to reach full speed and may
stall. On lightly loaded motors, this parameter may be reduced below 100% to produce smoother starts.
z NOTE: It is important that the (P75 / FUN06) - Rated Power Factor parameter is set properly so that the
desired maximum torque level is achieved.
Start Mode (P10/CFN01) set to Power Control Acceleration:
This parameter sets the final or maximum power (KW) consumption level that will be achieved at the end of
the ramp time. For a loaded motor, the maximum power value initially should be set to 100% or greater. If
the maximum power level is set too low, the motor may not produce enough torque to reach full speed and
may stall. On lightly loaded motors, this parameter may be reduced below 100% to provide for smoother
starts.
z NOTE: It is important that the (P75 / FUN06) - Rated Power Factor parameter is set properly so that the
actual maximum power level is achieved.
See AlsoInitial Current 1 (P6 / CFN03) on page 79.
Maximum Current 1 (P7 / QST 07) parameter on page 80.
Ramp Time 1 (P8 / QST 08) parameter on page 81.
Start Mode (P10 / CFN 01) parameter on page 83.
Initial Voltage/Torque/Power (P11 / CFN 08) parameter on page 84.
Rated Power Factor (P75 / FUN 06) parameter on page 125.
Theory of Operation section 7.3, Acceleration Control, on page 140.
85
6 - PARAMETER DESCRIPTION
P13Kick Level 1CFN 10
LED DisplayLCD Display
CFN: Kick Lvl 1
10 Off
RangeOff, 100 – 800% of FLA (Default Off)
DescriptionThe Kick Level 1 parameter sets the current level that precedes any ramp when a start is first commanded.
See AlsoStart Mode (P10 / CFN 01) parameter on page 83.
The kick current is only useful on motor loads that are hard to get rotating but then are much easier to move
once they are rotating. An example of a load that is hard to get rotating is a ball mill. The ball mill requires a
high torque to get it to rotate the first quarter turn (90°). Once the ball mill is past 90° of rotation, the material
inside begins tumbling and it is easier to turn.
The kick level is usually set to a low value and then the kick time is adjusted to get the motor rotating. If the
kick time is set to more than 2.0 seconds without the motor rotating, increase the kick current by 100% and
re-adjust the kick time.
Kick Time 1 (P14 / CFN 11) parameter on page 86.
Theory of Operation section 7.3.2, Programming A Kick Current on page 141.
P14Kick Time 1CFN 11
LED DisplayLCD Display
CFN: Kick Time 1
11 1.0 sec
Range0.1 – 10.0 seconds (Default 1.0)
DescriptionThe Kick Time 1 parameter sets the length of time that the kick current level (P13 / CFN 10) is applied to the
motor.
The kick time adjustment should begin at 0.5 seconds and be adjusted by 0.1 or 0.2 second intervals until the
motor begins rotating. If the kick time is adjusted above 2.0 seconds without the motor rotating, start over
with a higher kick current setting.
z NOTE: The kick time adds to the total start time and must be accounted for when setting the UTS time.
See AlsoStart Mode (P10 / CFN 01) parameter on page 83.
86
Up To Speed (P9 / QST 09) parameter on page 82.
Kick Level 1 (P13 / CFN 10) parameter on page 86.
Theory of Operation section 7.3.2, Programming a Kick Current on page 141.
6 - PARAMETER DESCRIPTION
P15Stop ModeCFN 14
LED DisplayLCD Display
CFN: Stop Mode
14 Coast
RangeLEDLCDDescription
CoSCoastCoast to stop. (Default)
SdcLVolt DecelOpen loop voltage deceleration.
tdcLTT DecelTruTorque deceleration.
dcbDC BrakeDC Braking.
DescriptionCoast:
A coast to stop should be used when no special stopping requirements are necessary; Example: crushers, balls
mills, centrifuges, belts, conveyor. The bypass contactor is opened before the SCRs stop gating to reduce
wear on the contactor contacts.
Voltage Decel:
In this mode, the starter linearly phases-back the SCRs based on the parameters Decel Begin Level, Decel End
Level, and Decel Time.
TruTorque Decel:
In this mode, the starter linearly reduces the motor torque based on the Decel End Level and Decel Time.
DC Brake:
In this mode the starter provides D.C. injection for frictionless braking of a three phase motor.
zNOTE: The MX2 stops the motor when any fault occurs. Depending on the application, it may be
desirable for the motor to be stopped in a controlled manner (Voltage Decel, TT Decel or D.C. Braking)
instead of being allowed to coast to a stop when this occurs. This may be achieved by setting the Controlled
Fault Stop Enable (P43 / PFN12) parameter to "On". Be aware, however, that not all fault conditions allow
for a controlled fault stop.
See AlsoDecel Begin Level (P16 / CFN 15) parameter on page 88.
Decel End Level (P17 / CFN 16) parameter on page 89.
Decel Time (P18 / CFN 17) parameter on page 90.
DC Brake Level (P19 / CFN 18) parameter on page 91.
DC Brake Time (P20 / CFN 19) parameter on page 92.
DC Brake Delay (P21 / CFN 20) parameter on page 93.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Digital Input Configuration (P48-P50 / I/O 01-03) parameters on page 110.
Relay Output Configuration (P52-P54 / I/O 05-07) parameters on page 112.
Theory of Operation section 7.4, Deceleration Control on page 149.
Theory of Operation section 7.5, Braking Controls on page 151.
87
6 - PARAMETER DESCRIPTION
P16Decel Begin LevelCFN 15
LED DisplayLCD Display
CFN: Decel Begin
15 40 %
Range1 % – 100% of phase angle firing (Default 40%)
DescriptionStop Mode (P15/CFN14) set to Voltage Deceleration:
The voltage deceleration profile utilizes an open loop S-curve voltage ramp profile. The Decel Begin Level
parameter sets the initial or starting voltage level when transferring from running to deceleration. The
deceleration beginning level is not a precise percentage of actual line voltage, but defines a point on the
S-curve deceleration profile.
A typical voltage decel begin level setting is between 30% and 40%. If the motor initially surges (oscillates)
when a stop is commanded, decrease this parameter value. If there is a sudden drop in motor speed when a
stop is commanded, increase this parameter value.
Stop Mode (P15/CFN14) set to TruTorque Deceleration:
Not used when the Stop Mode parameter is set to TruTorque Decel. The TruTorque beginning deceleration
level is automatically calculated based on the motor load at the time the stop command is given.
z NOTE: It is important that the (P75 / FUN06) - Rated Power Factor parameter is set properly so that the
actual deceleration torque levels are the levels desired.
See AlsoStop Mode (P10 / CFN 14) parameter on page 87.
Decel End Level (P17 / CFN 16) parameter on page 89.
Decel Time (P18 / CFN 17) parameter on page 90.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Rated Power Factor (P75 / FUN 06) parameter on page 125.
Theory of Operation section 7.4, Deceleration Control on page 149.
88
6 - PARAMETER DESCRIPTION
P17Decel End LevelCFN 16
LED DisplayLCD Display
CFN: Decel End
16 20 %
Range1 – 99 % of phase angle firing (Default 20%)
DescriptionStop Mode (P15/CFN14) set to Voltage Deceleration:
The voltage deceleration profile utilizes an open loop S-curve voltage ramp profile. The Decel End Level
parameter sets the ending voltage level for the voltage deceleration ramp profile. The deceleration ending
level is not a precise percentage of actual line voltage, but defines an ending point on the S-curve deceleration
profile.
A typical voltage decel end level setting is between 10% and 20%. If the motor stops rotating before the
deceleration time has expired, increase this parameter value. If the motor is still rotating when the
deceleration time has expired, decrease this parameter value. If the value is set too low a “No Current at Run”
fault may occur during deceleration.
z NOTE: The deceleration end level cannot be set greater than the decel begin level.
Stop Mode (P15/CFN14) set to TruTorque Deceleration:
The decel end level parameter sets the ending torque level for the TruTorque deceleration ramp profile.
A typical TruTorque decel end level setting is between 10% and 20%. If the motor stops rotating before the
deceleration time has expired, increase this parameter value. If the motor is still rotating when the
deceleration time has expired, decrease this parameter value.
See AlsoStop Mode (P15 / CFN 14) parameter on page 87.
Decel Begin Level (P16 / CFN 15) parameter on page 88.
Decel Time (P18 / CFN 17) parameter on page 90.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Theory of Operation section 7.4, Deceleration Control on page 149.
89
6 - PARAMETER DESCRIPTION
P18Decel TimeCFN 17
LED DisplayLCD Display
CFN: Decel Time
17 15 sec
Range1 – 180 seconds (Default 15)
DescriptionThe Decel Time parameter sets the time that the deceleration profile is applied to the motor and sets the slope
of the deceleration ramp profile. When in voltage decel mode, this time sets the time between applying the
initial decel level to the final decel level.
z NOTE: If the motor is not up to speed when a stop is commanded, the voltage decel profile begins at the
lower of either the decel begin level setting or at the motor voltage level when the stop is commanded.
Although the profile may be adjusted, the deceleration time remains the same.
When in the TruTorque deceleration mode, the decel time sets the time between when a stop is commanded
and when the decel end torque level is applied.
If the motor stops rotating before the decel time expires, decrease the decel time parameter. If the motor is
still rotating when the decel time expires, increase the decel time parameter.
A typical decel time is 20 to 40 seconds.
z NOTE: Depending on the motor load and the decel parameter settings, the motor may or may not be fully
stopped at the end of the deceleration time.
See AlsoStop Mode (P15 / CFN 14) parameter on page 87.
Decel Begin Level (P16 / CFN 15) parameter on page 88.
Decel End Level (P17 / CFN 16) parameter on page 89.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Theory of Operation section 7.4, Deceleration Control on page 149.
90
6 - PARAMETER DESCRIPTION
P19DC Brake LevelCFN 18
LED DisplayLCD Display
CFN: Brake Level
18 25 %
Range10 – 100 % of available brake torque (Default 25%)
DescriptionWhen the Stop Mode (P15 / CFN 14) is set to DC brake, the DC Brake Level parameter sets the level of DC
current applied to the motor during braking. The desired brake level is determined by the combination of the
system inertia, system friction, and the desired braking time. If the motor is braking too fast the level should
be reduced. If the motor is not braking fast enough the level should be increased. Refer to Nema MG1, Parts
12 and 20 for maximum load inertia. A Thermistor, Thermostat or RTD MUST be installed to protect the
motor.
DC Brake Function Programming Steps:
1. The DC Brake function may be enabled by setting the stop mode (P15 / CFN 14) to DC Brake.
2. Once this function is enabled, a relay output configuration (P52,53,54 / I/O 05,06,07) must be
used to control the DC brake contactor or 7th SCR gate drive card during braking. It is
recommended to use Relay K3 - (P54 / I/O 07).
z NOTE: Standard braking
z NOTE: Heavy duty braking
z NOTE: When DC injection braking is utilized, discretion must be used when setting up the DC Brake
Level. Motor heating during DC braking is similar to motor heating during starting. Even though the Motor
OL is active (if not set to "Off") during DC injection braking, excessive motor heating could still result if the
load inertia is large or the brake level is set too high. Caution must be used to assure that the motor has the
thermal capacity to handle braking the desired load in the desired period of time without excessive heating.
z NOTE: Consult motor manufacturer for high inertia applications.
z NOTE: Not to be used as an emergency stop. When motor braking is required even during a power outage
an Electro mechanical brake must be used.
- For load inertia less than 6 x motor inertia
- For NEMA MG1 parts 12 and 20 maximum load inertia
See AlsoStop Mode (P15 / CFN 14) parameter on page 87.
DC Brake Time (P20 / CFN 19) parameter on page 92.
DC Brake Delay (P21 / CFN 20) parameter on page 93.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Digital Input (P48-50 / I/O 01-03) parameters on page 110.
Theory of Operation section 7.1, Solid State Motor Overload Protection, on page 132.
Theory of Operation section 7.5.9, DC Injection Braking Control, on page 156.
91
6 - PARAMETER DESCRIPTION
P20DC Brake TimeCFN 19
LED DisplayLCD Display
CFN: Brake Time
19 5 sec
Range1 – 180 Seconds (Default 5)
DescriptionWhen the Stop Mode (P15 / CFN 14) is set to "DC brake", the DC Brake Time parameter sets the time that
See AlsoMotor Running Overload Class (P3 / QST 03) parameter on page 76.
DC current is applied to the motor. The required brake time is determined by the combination of the system
inertia, system friction, and the desired braking level. Increase the brake time if the motor is still rotating when
the braking finishes to minimize unnecessary motor heating.
Stop Mode (P15 / CFN 14) parameter on page 87.
DC Brake Level (P19 / CFN 18) parameter on page 91.
DC Brake Delay (P21 / CFN 20) parameter on page 93.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
Theory of Operation section 7.5.9, DC Injection Braking Control, on page 156.
92
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.