LayoutThis manual is divided into eight sections. Each section contains topics related to the
Parameter ListThe last chapter of the manual is a parameter list. This list gives the user a place to
SymbolsThere are two symbols used in this manual to highlight important information. The
section. The sections are as follows;
Introduction - Basic RediStart Micro II information.
•
Technical Specifications - RediStart Micro II specifications.
•
Installation - Information on installing the RediStart Micro II.
•
Operation - Information on how the starter operates.
•
Programming - Programming the RediStart Micro II.
•
Troubleshooting - Diagnosing RediStart Micro II problems.
•
Drawings - RediStart Micro II layout drawings.
•
Parameter List - List allowing user to record programmed values.
•
enter the programmed value for each parameter and also gives the page number
where the description of the parameter can be found. This list can be used as a quick
reference to find the information on a parameter.
symbols appear as the following;
Electrical hazard that could result in injury or death.
Caution that could result in damage to the starter or motor.
Highlight marking an important point in the documentation.
2
1.1 INTRODUCTION
Benshaw Services
General InformationBenshaw offers its customers the following services:
Start-Up ServicesBenshaw technical field support personnel are available to assist customers with the
On-Site Training ServicesBenshaw technical field support personnel are available to conduct on-site training on
Technical SupportBenshaw technical support personnel are available (at no charge) to answer customer
DocumentationBenshaw provides all customers with:
Start-up services.
•
On-site training services.
•
Technical support.
•
Detailed documentation.
•
Replacement parts.
•
NOTE: Information about products and services is available by contacting Benshaw.
initial start-up of the RediStart Micro II. Information about start-up services and fees
are available by contacting Benshaw.
RediStart Micro II operations and troubleshooting.
questions and provide technical support over the telephone. For information about
contacting technical support personnel, refer to Contacting Benshaw on page 4.
Benshaw West
7820 E. Evans Drive, Suite 900
Scottsdale, AZ 85260
United States of America
Phone: (480) 905 0601
Fax:(480) 905 0757
Technical support for the RediStart Micro II is available at no charge by contacting
Benshaw’s customer service department at one of the above telephone numbers. A
service technician is available Monday through Friday from 8:00 a.m. to 5:00 p.m.
EST.
NOTE: An on-call technician is available after normal business hours and on
weekends by calling Benshaw and following the recorded instructions.
To help assure prompt and accurate service, please have the following information
available when contacting Benshaw:
•
Name of company.
•
Telephone number where caller can be contacted.
•
Fax number of caller.
•
Benshaw product name.
•
Benshaw model number.
•
Benshaw serial number.
•
Name of product distributor.
•
Approximate date of purchase.
•
Voltage of motor attached to Benshaw product.
•
FLA of motor attached to Benshaw product.
•
A brief description of the application.
4
1.1 INTRODUCTION
General
Chassis or NEMA 1, 4, 12, or 3R enclosure
•
Protection (ANSI standard numbers given)
51 - Electronic motor overload (class 1 to 40)
•
86 - Overload lockout
•
48 - Adjustable up-to-speed timer (off; 0 to 300 seconds)
•
59/27 - Adjustable over/under voltage protection
•
46 - Adjustable line to average current imbalance
•
81 - Adjustable high and low frequency protection
•
Single phase protection
•
66 - Adjustable starts per hour (off or 1 to 20 starts)
•
Adjustable time between starts (off or 1 to 600 minutes)
•
Backspin timer (off or 1 to 200 minutes)
•
51 - Over current detection (Off or 50 to 800%) and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
•
37 - Undercurrent detection (Off or 10 to 100% and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
•
51G - Ground fault detection (Off or 1 to 100 amps) and time (0.1 to 90.0 sec. in 0.1 sec. intervals)
•
Over-current, undercurrent, and ground fault can each be set to trip or activate a relay
•
50 - Instantaneous electronic over-current trip
•
Shorted SCR detection
•
47 - Phase rotation selectable ABC, CBA, or Ins (insensitive)
PORT (power outage ride through) available with external 120VAC.
•
Features
Control
Two programmable current ramp profiles selectable at any time via 120 volt input
•
Initial current, maximum current, and ramp time adjustments for each ramp
•
Kick Current and time adjustments for each ramp
•
TruTorque acceleration and deceleration profiles
•
Adjustable deceleration profiles (to eliminate water hammer)
•
• Adjustable brake profile
•
Local start/stop controls
•
Emergency reset capability
•
Tachometer ramp control (requires 0-5VDC tachometer feedback signal)
Input/Output and Display
•
Plain English operation via back lit LCD display interface
•
LCD and LED status and diagnostics (full fault annunciation)
•
Programmable metering (amps, volts, frequency, overload, power factor, elapsed time, watts, VARs, watt-hours, VA,
Current Imbalance, Ground Fault Current, RTD temperatures)
•
Programmable relay outputs
•
Latched fault relay output
•
Real time clock
•
Time stamped event recorder
•
Password protection
•
Battery backed-up starter parameters and lockout times
5
2.TECHNICAL SPECIFICATIONS
2.1 TECHNICAL SPECIFICATIONS
CT (Current Transformer) Inputs
ConversionCalibrated RMS, 12 samples per cycle
Range0.01 to 1.5 × phase CT primary amps set point
Accuracy±3.5% of phase CT primary amps set point
Frequency23 to 72 Hz
Current Withstand- 2.0 × CT primary amps set point (CT ratio parameter) - continuous
- 10 × CT primary amps set point (CT ratio parameter) - 30 seconds
- 55 × CT primary amps set point (CT ratio parameter) - 1 seconds
Voltage Inputs
ConversionCalibrated RMS, 12 samples per cycle
Range1000VAC to 9999VAC
Accuracy±3.5% of full range
Current±5%, 0 to 9999Amps
Voltage±5%, 0 to 9999Volts
Watts±5%, 0 to 6553kW
Volt-Amps Reactive±5%, 0 to 6553kVAR
Volt-Amps±5%, 0 to 6553kVA
WH±5%, 0 to 6553MWH
PF±3%, -0.01 to +0.01
Metering
Accuracy±1 minute per month
Range1/1/1970 to 1/1/2069
Fault Relay- SPDT - Form C
- 2A, 125VAC, resistive
- 1A, 125VAC, 0.4 PF
- 2A, 30VDC resistive
- 100VA inrush
Output Relay #1 & #2- SPDT - Form C
- 16A, 250VAC resistive
- 8A, 250VAC 0.4 PF
- 16A, 30VDC resistive
- 2000VA inrush
8
Real Time Clock
Output Relays
2.1 TECHNICAL SPECIFICATIONS
Four Relay Card- DPDT - Dual Form C
- 5A, 250VAC, resistive
- 2A, 250VAC, 0.4 PF
- 5A, 30VDC, resistive
- 500VA inrush
Seven Relay Card- SPDT - Form C
- 8A, 250VAC resistive
- 4A, 250VAC 0.4 PF
- 8A, 30VDC resistive
- 800VA inrush
Voltage120VAC, ±15%
240VAC, ±15% (Optional)
Frequency50 to 60hz
Power ConsumptionVaries for required control.
FuseTime delay control circuit protection fuses.
Storage-20ºC (-4°F) to +60°C (+140°F)
0% to 95% relative humidity, non-condensing
Control Power
Storage and Operating Conditions
Operating0°C (+32°F) to +50°C (+122°F)
0% to 95% relative humidity, non-condensing
DeviceNet (Embedded)
ManualAvailable at www.benshaw.com or from your Benshaw sales office.
EDS FileAvailable at www.benshaw.com or from your Benshaw sales office.
Device TypeSoftstart Starter
I/O Slave MessagingPolling
Baud Rates- 125K
ConformanceSelf tested with ODVA (open DeviceNet Vendor Association) software.
- 250K
- 500K
Modbus (Optional)
ManualAvailable at www.benshaw.com or from your Benshaw sales office.
TypeModbus RTU
Connections- RS-232
- RS-485
Baud Rates- 2400
- 4800
- 9600
9
2.1 TECHNICAL SPECIFICATIONS
EU Declaration of Conformity
According to the EMC – Directive 89/336/EEC as Amended by 92/31/EEC and 93/68/EEC
Product Category:Motor Controller
Product Type:Reduced Voltage Solid State Motor Controller
Model Numbers:RSM6, RSM7, RSM10, RSM11, RMB6, MVRSM12/18
Manufactures Name:Benshaw, Inc.
Manufacture’s Address:1659 East Sutter Road
The before mentioned products comply with the following EU directives and Standards:
Safety:UL 347 Standard for Industrial Control Equipment covering devices for starting,
EMC:EN 50081-2 Emissions Radiated/Conducted
The technical files and other documentation are on file at Benshaw, Inc. and controlled by the Product Engineering
Group. Benshaw, Inc. has internal production control systems that ensures compliance between the manufactured
products and the technical documentation.
Neil AbramsHarry HagertyCharles E. Cook
Quality Control ManagerAdvanced Controls and Drives ManagerProduct Development Manager
Glenshaw, PA USA
15116
stopping, regulating, controlling, or protecting electric motors with ratings of 1500
volts or more.
EN 55011/05.98+A1:1999
EN 50082-2 Immunity/Susceptibility which includes:
EN 61000-4-2 Electrostatic Discharge
EN 61000-4-3 Radiated RF
EN 61000-4-4 Electrical Fast Transient/Burst
EN 61000-4-6 Injected Currents
10
2.1 TECHNICAL SPECIFICATIONS
Overload Curves
GeneralThe RediStart Micro II comes with forty (40) standard overload curves. The 100% (no
CurvesClass 1 to 40 in steps of 1.
Trip Time Accuracy±2 seconds up to 30 seconds
trip) point is the motor FLA setting multiplied by the service factor. These curves are
shown on the next page.
NOTE: When the overload counter is at a number other than 0%, the time to trip will
be lowered by this percentage.
11
2.1 TECHNICAL SPECIFICATIONS
RediStart Micro II Overload Curves
10000
Overload Curve Chart
Class 40
Class 35
Class 30
1000
100
10
Class 40
Class 25
Class 20
Class 15
Class 10
Class 7
Class 5
Class 3
Class 2
Class 1
Class 1
12
1
0100200300400500600700800
Current as Percent of FLA
2.1 TECHNICAL SPECIFICATIONS
RediStart Micro II Computer Card Jumpers
JumperDescriptionPosition 1-2Position 2-3Standard
JPC5LCD Start ButtonEnableDisable1-2
JPC7O/L Reset Auto/ManualAutomaticManual2-3
JPC8Display FormatStandardLocal Bus1-2
JPC12SCR FiringPulseBlockIn
JPC13LCD Stop ButtonEnableDisable1-2
JPC14RAM Size8K RAM2K RAM1-2
JPC15PWM/ADDR16ADDR16PWM1-2,3-4
JPC17Voltage Select4160 or 33002400 or 4800
JPC18Voltage Select3300 or 48002400 or 4160
JPC19Fault ResetAutomaticManual2-3
JPC25Synchronous ApplicationYesNoOut
JPC27Micro Enable/ADDR17ADDR17Enable1-2,3-4
(In - 2-pos. jumper)(Out - 2-pos. jumper)
Computer Card JC11 Header Assignments
PositionAssignment
1-16Starter equipped with voltage divider card.
2-15Not used.
3-14Starter Equipped with MODBUS master card (for RTD module).
4-13Not used.
5-12Not used.
6-11Enables emergency reset.
7-10Not used.
8-9Not used.
Old RediStart Micro II Power Card Jumpers
JumperDescriptionPosition 1-2Position 2-3Standard
JPP2Line SynchingLine to LineLine to Neutral1-2
JPP3Line SynchingLine to LineLine to Neutral1-2
JPP4Line SynchingLine to LineLine to Neutral1-2
NOTE: Jumpers JPP2, JPP3, and JPP4 do not apply to the BIPC-300030-xx Power Card.
13
2.1 TECHNICAL SPECIFICATIONS
14
3.INSTALLATION
3.1 INSTALLATION
Site Preparation
GeneralBefore the installation of the RediStart Micro II, the site should be prepared. The
Connection CablesThe connection cables for the starter must have the correct NEC/C.S.A. current rating
Site RequirementsThe installation site must adhere to the applicable starter NEMA rating. For optimal
MountingThe starter must be mounted so the heat sink fins are vertically oriented in an area
customer is responsible for:
Providing the correct power source.
•
Selecting the control mechanism.
•
Providing the connection cables and associated hardware.
•
Ensuring the installation site meets all environmental specifications for the
•
enclosure NEMA rating.
for the unit being installed. Depending upon the model, the connection cables can
range from a single #14 AWG conductor to four 750 MCM cables.
performance, the installation site must meet the following specifications, unless
equipment (such as a heater or air conditioner) was added to the unit for operation
outside of these ranges:
Temperature: 0°C (+32F) to 40°C (+104°F).
•
Humidity: 20% to 95% non-condensing.
•
Airways: Clearances are provided around all heat sinks.
•
Altitude: Less than 3300 feet (1000 meters) above sea level.
•
NOTE: The starter rating must be derated 1% for every 330 feet (100 meters) above
3300 feet (1000 meters).
that does not experience excessive shock or vibration. All models require airway
passages around the heat sink. During normal operation the heat sink may reach 194
degrees Fahrenheit (90 degrees Centigrade). Do not install the starter in direct
contact with any materials that cannot withstand these temperatures.
EMC Installation guidelines
GeneralIn order to help our customers comply with European electromagnetic compatability
EnclosureInstall the product in a grounded metal enclosure.
GroundingConnect a grounding conductor to the screw or terminal provided as standard on each
WiringWire in an industrial application can be divided into three groups: power control and
FilteringTo comply with Conducted Voltage Limits a 0.33 uF capacitor should be connected
standards, Benshaw Inc. has developed the following guidelines.
Attention: This product has been designed for Class A equipment. Use of the product
in domestic environments may cause radio interference, in which case the installer
may need to use additional mitigation methods.
controller. Refer to layout/power wiring schematic for grounding provision location.
signal. The following recommendations for physical separation between these groups
are provided to reduce the coupling effect;
•
Different wire groups should cross at 90 degrees inside an enclosure.
•
Minimum spacing between different wiring groups in the same tray should be
six inches.
•
Wire runs outside an enclosure should be run in conduit or have shielding/armor
with equivalent attenuation.
•
Different wire groups should be run in separate conduits.
•
Minimum spacing between conduits containing different wire groups should be
three inches (8cm).
between each incoming power line and ground at a point nearest to where the
incoming power enters the enclosure.
16
3.1 INSTALLATION
Installation Procedures
General InformationInstallation of some models may require halting production during installation. If
Safety PrecautionsTo ensure the safety of the individuals installing the starter, and the safe operation of
applicable, ensure that the starter is installed when production can be halted long
enough to accommodate the installation.
Before installing the starter, ensure:
The wiring diagram (supplied separately with the starter) is correct for the
•
required application.
The starter is the correct current rating for the motor being started.
•
All of the installation safety precautions are followed.
•
The correct power source is available.
•
The starter control method has been selected.
•
The necessary installation tools and supplies are obtained.
•
The installation site meets all environmental specifications for the starter
•
NEMA/CEMA rating.
The motor being started has been installed and is ready to be started.
•
Any power factor correction capacitors (PFCC) are installed on the power source
•
side of the starter and not on the motor side.
NOTE: Failure to remove power factor correction or surge capacitors from the load
side of the starter will result in serious damage to the starter which will not be
covered by the starter’s warranty. The capacitors must be powered from the line side
of the starter. The up-to-speed contact can be used to energize the capacitors after the
motor has reached full speed.
the starter, observe the following guidelines:
Ensure that the installation site meets all of the required environmental
•
conditions (Refer to Site Preparation, page 16).
LOCK OUT ALL SOURCES OF POWER.
non-fused disconnect) if they were not previously installed by the factory as part
of the package.
•
Install short circuit protection (i.e., circuit breaker or fuses) if not previously
installed by the factory as part of the package. See page 13 for the fault rating
table.
•
Follow all NEC (National Electrical Code) and/or C.S.A. (Canadian Standards
Association) standards.
•
Remove any foreign objects from the interior of the enclosure.
•
Ensure that wiring is installed by an experienced electrician.
•
Ensure that the individuals installing the starter have protective eye wear and
clothing.
The opening of the branch circuit protective device may be an indication that a fault
current has been interrupted. To reduce the risk of electrical shock, current carrying
parts and other components of the starter should be inspected and replaced if
damaged.
17
3.1 INSTALLATION
InstallationTo begin installation:
Control WiringThe control wiring should be connected to suit the customers needs. The control
Read and follow all of the installation safety precautions.
•
Procure the necessary installation tools and any supplies.
•
Ensure the site has sufficient lighting for safe installation.
•
Move the starter to the installation site.
•
Ensure that the starter is positioned so that the cabinet door has ample
•
clearance, and all of the controls are accessible.
DO NOT install the starter in direct contact with any materials that cannot
•
withstand the maximum heat sink temperature of 194 degrees Fahrenheit (90
degrees Centigrade). All models require airway passages around the heat sink
for proper cooling.
If the starter is to be wall mounted:
Mount the starter on the applicable surface using the appropriate hardware.
•
NOTE: Moving some models may require more than one individual or lifting
equipment (e.g., forklift, crane).
terminals on the control cards are as follows:
RediStart Micro II Power Card (refer to card layout on page 111):
TBP1-124VDC common for relay and reversing card
•
TBP1-224VDC power for relay and reversing card
•
TBP2-1Run relay neutral
•
TBP2-2Run relay live
•
TBP2-5Run relay holding contact
•
TBP3-1General fault contact N.C. (not faulted)
•
TBP3-2General fault contact common
•
TBP3-3General fault contact N.O. (not faulted)
•
•
TBP3-4Programmable relay #1 N.O.
•
TBP3-5Programmable relay #1 common
•
TBP3-6Programmable relay #1 N.C.
•
TBP3-7Programmable relay #2 N.O.
•
TBP3-8Programmable relay #2 common
•
TBP3-9Programmable relay #2 N.C.
RediStart Micro II computer card inputs (refer to card layout on page 110):
•
JC13-1Heat sink thermal switch or external starter trip input.
•
JC13-2AC neutral.
•
JC13-3Run confirm.
•
JC13-4In-line monitoring.
•
JC13-5Disconnect monitoring.
•
JC13-6Reverse/Forward Jog.
•
JC13-7Bypass monitoring.
•
JC13-8Jog mode.
•
JC13-9Profile #2 select.
•
JC13-10External motor thermal overload reset.
•
JC13-11External computer reset.
•
JC13-12AC neutral.
18
3.1 INSTALLATION
RediStart Micro II Four (4) Relay Card (refer to card layout on page 113):
TB2-1Optional programmable relay #1 N.O.
•
TB2-2Optional programmable relay #1 N.C.
•
TB2-3Optional programmable relay #1 common
•
TB2-4Optional programmable relay #1 N.O.
•
TB2-5Optional programmable relay #1 N.C.
•
TB2-6Optional programmable relay #1 common
•
TB2-7Optional programmable relay #2 N.O.
•
TB2-8Optional programmable relay #2 N.C.
•
TB2-9Optional programmable relay #2 common
•
TB2-10Optional programmable relay #2 N.O.
•
TB2-11Optional programmable relay #2 N.C.
•
TB2-12Optional programmable relay #2 common
•
TB2-13Optional programmable relay #3 N.O.
•
TB2-14Optional programmable relay #3 N.C.
•
TB2-15Optional programmable relay #3 common
•
TB2-16Optional programmable relay #3 N.O.
•
TB2-17Optional programmable relay #3 N.C.
•
TB2-18Optional programmable relay #3 common
•
TB2-19Optional programmable relay #4 N.O.
•
TB2-20Optional programmable relay #4 N.C.
•
TB2-21Optional programmable relay #4 common
•
TB2-22Optional programmable relay #4 N.O.
•
TB2-23Optional programmable relay #4 N.C.
•
TB2-24Optional programmable relay #4 common
•
RediStart Micro II seven (7) Relay Card (refer to card layout on page 113):
TB2-1Optional programmable relay #1 N.O.
•
TB2-2Optional programmable relay #1 common
•
TB2-3Optional programmable relay #1 N.C.
•
TB2-4Optional programmable relay #2 N.O.
•
TB2-5Optional programmable relay #2 common
•
TB2-6Optional programmable relay #2 N.C.
•
•
TB2-7Optional programmable relay #3 N.O.
•
TB2-8Optional programmable relay #3 common
•
TB2-9Optional programmable relay #3 N.C.
•
TB2-10Optional programmable relay #4 N.O.
•
TB2-11Optional programmable relay #4 common
•
TB2-12Optional programmable relay #4 N.C.
•
TB2-13Optional programmable relay #5 N.O.
•
TB2-14Optional programmable relay #5 common
•
TB2-15Optional programmable relay #5 N.C.
•
TB2-16Optional programmable relay #6 N.O.
•
TB2-17Optional programmable relay #6 common
•
TB2-18Optional programmable relay #6 N.C.
•
TB2-19Optional programmable relay #7 N.O.
•
TB2-20Optional programmable relay #7 common
•
TB2-21Optional programmable relay #7 N.C.
19
3.1 INSTALLATION
Power WiringThread the power and motor cables through a connector into the enclosure. Strip
away the motor cable insulation and apply anti-oxidation paste to the conductors.
Attach the motor cables:
Use the T1, T2 and T3 lugs or terminals.
•
Attach the power source cables:
•
Use the L1, L2 and L3 lugs or terminals.
•
NOTE: For larger starters, thread each incoming power cable through its applicable
current transformer (CT); if not already supplied in the unit. The cables must be
threaded through the CTs in the same direction to insure proper operation (Refer to
the wiring diagram supplied with the starter).
The following is a list of the recommended crimp-on wire connectors manufactured by
Penn-union Corp.
Wire SizePart #Wire SizePart #
1/0BLU-1/0S20500 MCMBLU-050S2
2/0BLU-2/0S4600 MCMBLU-060S1
3/0BLU-3/0S1650 MCMBLU-065S5
4/0BLU-4/0S1750 MCMBLU-075S
250 MCMBLU-025S800 MCMBLU-080S
300 MCMBLU-030S1000 MCMBLU-100S
350 MCMBLU-035S1500 MCMBLU-150S
400 MCMBLU-040S42000 MCMBLU-200s
450 MCMBLU-045S1
Power Factor CapacitorsPower factor correction capacitors and surge capacitors MUST NOT be connected
FinishingAfter all of the safety precautions and installation procedures have been completed,
between the RediStart Micro II and the motor. These devices can damage the SCR’s in
the package during ramping. These devices appear like a short circuit to the SCR
when it turns on, which causes a di/dt level greater than the SCR can handle. If used,
power factor correction capacitors or surge capacitors must be connected ahead of the
RediStart Micro II. Programmable relay #2 (K6) can be set to an up-to-speed (UTS)
contact (up-to-speed is the default setting) and then used to pull-in a contactor to
connect the capacitors after the motor has reached full speed.
NOTE: The motor manufacturer should be contacted before surge capacitors are
removed from the motor terminal box.
verify that the following settings are correct for the application:
•
Current transformer scaling switches.
•
Hardware deceleration/braking control (JPC3).
•
RediStart Micro II computer card jumpers.
20
3.1 INSTALLATION
Preventative Maintenance
General InformationPreventive maintenance performed on a regular basis will help ensure that the starter
Preventive MaintenanceDuring Commissioning;
continues to operate reliably and safely. The frequency of preventive maintenance
depends upon the type of maintenance and the installation site’s environment.
NOTE: Preventive maintenance should always be performed by a trained technician.
Torque all power connections during commissioning. This includes pre-wired
•
equipment.
Check all of the control wiring in the package for loose connections.
•
For the first month after the starter has been put in operation;
Re-torque all power connections every two weeks. This includes pre-wired
•
equipment.
Inspect the cooling fans after two weeks to ensure proper operation.
•
After the first month of operation;
Re-torque all power connections every year.
•
Clean any accumulated dust from the starter using a clean source of compressed
•
air.
Inspect the cooling fans every three months to ensure proper operation.
•
Clean or replace any air vent filters on the starter every three months.
•
NOTE: If mechanical vibrations are present at the installation site, inspect the
•
connections more frequently.
Remote RTD Module
GeneralThe RediStart Micro II can have up to 2 RTD modules installed. The RTD modules
MODBUS Master CardThe MODBUS master card is installed on the RediStart Micro II CPU card to allow
can be installed in the cabinet with the RediStart Micro II or they can be installed
remotely at the motor. Refer to the Remote RTD Module manual for details on this
module.
the starter to communicate with the RTD Module.
CT Ratio Scaling
General InformationThe motor current signal scaling is set according to the motor current specified when
the starter is ordered. To ensure accurate operation, the motor current signal must be
correctly scaled for the motor current being controlled by the starter.Motor current
signal scaling may have to be changed if the motor size has been changed from the
original specification.Motor current signal scaling is accomplished by verifying the
current transformer ratio as supplied with the starter and then selecting the correct
DIP switch setting from the chart on the following page for the current transformer
ratio.
The DIP switches are:
•
ON in the right position
•
OFF in the left position
NOTE: Adjust the DIP switches only when the motor is stopped, or the switches
could be damaged.
21
3.1 INSTALLATION
Confirm Switch SettingsTo verify or change the motor current signal scaling:
Switch SettingsCT RatioMotor FLASwitch 1Switch 2
Changing FLAIf the actual motor FLA has been changed from the motor FLA documented on the
Compare the CT ratio stamped on each CT to the CT ratio listed on the wiring
•
diagram supplied with the starter to ensure the correct CTs are installed.
Inspect the RediStart Micro II power card to ensure that the DIP switches are in
•
the correct positions for the applicable CT ratio and the motor full-load current
(FLA) rating.
288:13A to 9AOffOff
288:19A to 24AOnOff
288:125A to 60AOnOn
864:120A to 24AOffOff
864:125A to 70AOnOff
864:171A to 180AOnOn
2640:140A to 80AOffOff
2640:181A to 200AOnOff
2640:1201A to 500AOnOn
5760:170A to 160AOffOff
5760:1161A to 400AOnOff
5760:1401A to 1200AOnOn
purchase order:
The DIP switch positions may need to be changed.
•
Different CTs may have to be installed in the starter and the current
•
transformer ratio parameter may need to be changed (Refer to current
transformer ratio parameter, page 88).
RediStart Micro II Computer Card Jumpers
General InformationThe RediStart Micro II computer card has a number of jumpers that affect the
JPC5 - LCD Start buttonThe LCD Start button can be enabled or disabled by this jumper. The LCD Start
JPC7 - Overload Auto/Man.The motor thermal overload can be set to require a manual reset or to automatically
operation of the starter. In some cases, these jumpers will over-ride the programmed
values.
button is factory enabled unless the purchase order requests that the LCD Start
button is disabled. The LCD Start button is controlled by jumper JPC5 on the
RediStart Micro II computer card (Refer to RediStart Micro II computer card layout
on page 110).
ModePosition
Enable1-2
Disable2-3
reset after a thermal trip. The motor thermal overload is set to the manual reset
position unless the purchase order requests that the motor thermal overload is set to
the automatic reset position. The motor thermal overload reset is controlled by jumper
JPC7 on the RediStart Micro II computer card (Refer to RediStart Micro II computer
card layout on page 110).
ModePosition
Automatic Reset1-2
Manual Reset2-3
22
3.1 INSTALLATION
JPC13 - LCD Stop ButtonThe LCD Stop button can be enabled or disabled by this jumper. The LCD Stop button
JPC17 - Voltage SelectThe RediStart Micro must be set for the line voltage that it is operating on. This is so
JPC18 - Voltage SelectThe RediStart Micro must be set for the line voltage that it is operating on. This is so
is factory enabled unless the purchase order requests that the LCD Stop button is
disabled. The LCD Stop button is controlled by jumper JPC13 on the RediStart Micro
II computer card (Refer to RediStart Micro II computer card layout on page 110).
ModePosition
Enable1-2
Disable2-3
that it will know the voltage to be able to implement the high/low voltage protection
feature. The line voltage should be set to the voltage requested when the starter was
ordered since the power poles and control power transformer must change for
different line voltages.The line voltage is set by JPC17 on the RediStart Micro
computer card, which works in conjunction with JPC18. (Refer to RediStart Micro
computer card layout on page 110).
SettingPosition
3300VAC or 4160VAC1-2
2400VAC or 4800VAC2-3
that it will know the voltage to be able to implement the high/low voltage protection
feature. The line voltage should be set to the voltage requested when the starter was
ordered since the power poles and control power transformer must change for
different line voltages.The line voltage is set by JPC18 on the RediStart Micro
computer card, which works in conjunction with JPC17. (Refer to RediStart Micro
computer card layout on page 110).
SettingPosition
3300VAC or 4800VAC1-2
2400VAC or 4160VAC2-3
JPC19 - Fault ResetThe RediStart Micro II can be set to either require a manual reset or automatically
reset after a fault occurs. The RediStart Micro II is set for manual fault reset unless
the purchase order requests that the fault reset jumper is set to automatic. The fault
reset is controlled by jumper JPC19 on the RediStart Micro II computer card (Refer to
RediStart Micro II computer card layout on page 110).
ModePosition
Automatic Fault Reset1-2
Manual Fault Reset2-3
The automatic fault reset works in conjunction with the # auto resets parameter (see
page 73) and the Fault Classes sub-menu (see page 74).
The # auto resets parameter sets how many non-critical faults will be reset in one
hour. Once this number has been reached, the starter will not automatically reset the
next fault. When this occurs, the user should check the event recorder for the cause of
the faults and correct the problem.
The fault classes sub-menu allows the user to set faults as critical, non-critical,
disabled, warning relay A, warning relay B or warning relay C. When JPC19 is set to
automatic fault reset and a fault is set to non-critical, the RediStart Micro II will
automatically reset the fault.
23
3.1 INSTALLATION
24
4.OPERATION
4.1 OPERATION
Main Display Messages
GeneralDuring normal operation, the RediStart Micro II can show a number of different
operating messages on the display. These messages give information on the present
operating state of the starter and motor. There are three locations where messages
are displayed as shown in the following diagram.
Location 1
Location 2
Run UTSI=0A
Running . V=0V
Location 3
MessagesThe messages, display locations and descriptions are as follows:
MessageLocation Description
Stop1Starter is in a stopped state.
Coast1Starter coasting between direction changes.
BKS hld1Backspin timer is active.
TBS hld1Time between starts is active.
SPH hld1Starts per hour is active.
BKS LOC1Backspin timer is locked.
TBS LOC1Time between starts counter has locked.
SPH LOC1Starts per hour counter has locked.
JOG1Starter is operating in the jog at set speed mode.
RUN1Starter is applying power to motor.
Stopping1Stop command was applied, motor is being stopped.
RUN UTS1Starter is running and motor is at full speed.
RUN SYN1Starter is running and motor is synchronized.
XXX.Xmin2Next start cannot be performed for xxx.x min.
PH Err2The phase order is incorrect.
Freq Err2The line frequency is outside of the trip settings.
Volt Err2The line voltage is outside of the trip settings.
OCT Trip2Motor current went above the over current trip setting.
UCT Trip2Motor current went below the under current trip setting.
GDF Trip2A ground fault was detected.
Door In2The Disconnect switch is open.
No Line2Line voltage is not present.
OL Warn2Motor thermal overload is over 90% content.
OL Trip2Motor thermal overload is tripped and reset is allowed.
OL Lock2Motor thermal overload tripped and reset is not allowed.
Ready2All conditions OK to run.
Accel2Starter is ramping.
Accel 22Starter is ramping using 2nd ramp profile.
Running2Starter ramp profile is complete.
FWD Acc2The motor is being accelerated in the forward direction.
REV Acc2The motor is being accelerated in the reverse direction.
Forward2The motor is running in the forward direction.
Reverse2The motor is running in the reverse direction.
LS Acc2The motor is being accelerated in low speed.
HS Acc2The motor is being accelerating in high speed.
Low Sp2The motor is running in low speed.
High Sp2The motor is running in high speed.
Kicking2Starter is applying kick start current.
Kicking 22Starter is kicking using 2nd ramp profile.
Decel2Motor is decelerating.
Braking2The motor is being braked.
FWD Jog2Motor is jogging in the forward direction.
REV Jog2Motor is jogging in the reverse direction.
ComLoss2Modbus communications lockout.
EN Save2Energy saver is active.
Heater2The motor heater is operating.
RTD Alar2A RTD went over its alarm setting.
RTD ComF2Communications with an RTD module was lost.
RTD Open2A RTD is detected as being open.
RTD Shor2A RTD is detected as being shorted.
RTD Warn2A RTD went over its warning setting.
26
4.1 OPERATION
If Lock2Starter is providing set maximum field current.
If CTRL2Starter is in field current control mode.
PF CTRL2Starter is in power factor control mode.
TachLoss2The tachometer feedback signal was lost.
PORT2The starter is in Power Outage Ride-Through mode.
. (dot)3Password protection is enabled.
Meter Display Pages
GeneralBesides the main display, the RediStart Micro II has a number of other display pages
that show various operational values. By pressing the Up or Down arrow buttons, it is
possible for the user to view all operational information without having to enter the
menu system. The display pages are described below in the order they appear when
pressing the Up button.
NOTE: Not every display page shown here may be present depending on the options
provided with the starter.
Current PageThe current meter page displays the currents for all three phases.
Phase 1 Current
Current I2=0A
I1=0 I3=0A
Phase 2 Current
Phase 3 Current
Voltage PageThe voltage page displays the voltages for all three phases.
Phase 1 Voltage
Voltage V2= 0V
V1=0 V3= 0V
Phase 2 Voltage
Phase 3 Voltage
Kilo-Watt Hour PageThe Kilo-Watt Hour power page displays the true power measurements for the motor.
KWatt Hour= 0.0H
MWatt Hour= 0.0H
Kilo-Watt Hours
Mega-Watt Hours
Power PageThe power page displays the KW and kVA power measurements for the motor.
KWatts= 0.0W
KVA Usage = 0.0
Kilo-Watts
KVA
Tru Torque PageThe tru torque page displays the Tru Torque % and Power Factor measurements for
the motor.
Tru Torq% = 0.0%
Motor pf = 1.0
True Torque
Power Factor
27
4.1 OPERATION
e
Runtime PageThe runtime page displays the runtime on the motor.
RunTime Hr= 123h
HoursX100 = 1.2
Operating Hours
Hundreds of Hours
User Counts PageThe user counts page displays the user resettable runtime and number of starts.
User RT Hr= 123h
User Start= 45#
User Resettable Run tim
User Resettable Starts
Motor #1 PageThe motor #1 page displays the motor current imbalance as a percentage and the
number of motor starts.
Curr. Imba=3%
# Starts = 45
Current Imbalance
Number of Starts
Motor #2 PageThe motor #2 page displays overload content and ground fault current information.
% Overload=3%
Ground Fau=0A
Overload Content
Ground Fault Current
Motor #3 PageThe motor #3 page displays operating frequency and motor power factor information.
Frequency= 60.0
Motor PF = 1.00
Line Frequency
Power Factor
Sync PageThe sync page gives the synchronous motor field current and slip.
Field Amps= 0.0A
% Rotor Sl=99.9%
Field Current
Slip Percentage
Communications PageThe communications page displays the communications statistics.
Communication Rate
Com’sTx=0#
Cr=0 Rx=0#
# of Transmits
# of Receives
RTD #1 & #2 Temp.The RTD #1 & #2 temperature page displays the temperatures those RTDs are
measuring.
RTD#1= 90C
RTD#2= 80C
RTD #1 Temperature
RTD #2 Temperature
28
4.1 OPERATION
RTD #3 & #4 Temp.The RTD #3 & #4 temperature page displays the temperatures those RTDs are
measuring.
RTD#3= 90C
RTD#4= 80C
RTD #3 Temperature
RTD #4 Temperature
RTD #5 & #6 Temp.The RTD #5 & #6 temperature page displays the temperatures those RTDs are
measuring.
RTD#5= 90C
RTD#6= 80C
RTD #5 Temperature
RTD #6 Temperature
RTD #7 & #8 Temp.The RTD #7 & #8 temperature page displays the temperatures those RTDs are
measuring.
RTD#7= 90C
RTD#8= 80C
RTD #7 Temperature
RTD #8 Temperature
RTD #9 & #10 Temp.The RTD #9 & #10 temperature page displays the temperatures those RTDs are
measuring.
RTD#9= 90C
RTD#10= 80C
RTD #9 Temperature
RTD #10 Temperature
RTD #11 & #12 Temp.The RTD #11 & #12 temperature page displays the temperatures those RTDs are
measuring.
RTD#11= 90C
RTD#12= 80C
RTD #11 Temperature
RTD #12 Temperature
RTD #13 & #14 Temp.The RTD #13 & #14 temperature page displays the temperatures those RTDs are
measuring.
RTD#13= 90C
RTD#14= 80C
RTD #13 Temperature
RTD #14 Temperature
RTD #15 & #16 Temp.The RTD #15 & #16 temperature page displays the temperatures those RTDs are
measuring.
RTD#15= 90C
RTD#16= 80C
RTD #15 Temperature
RTD #16 Temperature
29
4.1 OPERATION
e
Max. RTD Temp.The maximum RTD temperature page displays the temperature and RTD number
from the highest measuring RTD.
Max of All= 90C
M All RTD#=5#
Max. RTD Temperatur
RTD Number
Max. Bearing RTD Temp.The maximum bearing RTD temperature page displays the temperature and RTD
number from the highest measuring RTD in the bearing group.
Max Bearin= 90C
M Bea RTD#=5#
Max. Bearing Temp.
Bearing RTD Number
Max. Stator RTD Temp.The maximum stator RTD temperature page displays the temperature and RTD
number from the highest measuring RTD in the stator group.
Max Stator= 90C
M Sta RTD#=5#
Max. Stator Temp.
Stator RTD Number
Peak RTD Temp.The peak RTD temperature page displays the highest peak temperature reached and
the number of the RTD that read the temperature.
Peak of Al= 90C
P All RTD#=5#
Peak RTD Temp.
RTD Number
Peak Bearing RTD Temp.The peak bearing RTD temperature page displays the highest bearing temperature
reached and the number of the RTD that read the temperature.
Peak Beari= 90C
P Bea RTD#=5#
Peak Bearing Temp.
Bearing RTD Number
Peak Stator RTD Temp.The peak stator RTD temperature page displays the highest stator temperature
reached and the number of the RTD that read the temperature.
Peak Stato= 90C
P Sta RTD#= 5#
Peak Stator Temp.
Stator RTD Number
30
4.1 OPERATION
Parameters
Parameter UsageThe description and use of each parameter is described in the programming section of
the manual. Most parameters are fairly straightforward and don’t require any further
explanation. The rest of this chapter gives a more detailed description of the use of the
parameters that are more complicated to use.
Starter Modes
DescriptionThe Starter Mode sub menu (see page 49) contains parameters for selecting the type
Start ModesCurr (Current Ramp): The current ramp is ideal for most general-purpose motor
of start and stop to perform. By allowing the user to select the start and stop mode the
system can be operated in the optimal start and stop fashion for the load. Below are
the available modes along with some examples for typical applications.
control applications; Examples: crushers, ball mills, compressors, saws, and
centrifuges).
The Current Ramp applies to the following in the Starter Setup Main Menu:
Forward1 Profile, Forward2 Profile, Reverse1 Profile, and Reverse2 Profile.
TT (Tru Torque): The true torque ramp is suitable for applications that require a
minimum of torque transients during starting or for consistenly loaded applications
that require a reduction of torque surges during starting; Examples: pumps, fans, and
belt driven equipment).
The Tru Torque ramp applies to the following in the Starter Setup Main Menu:
True Torque Ramp
Tach (Tachometer Feedback): The tachometer feedback ramp is for applications
where torque transients must be held to a minimum, and the starting load is
unknown, vary, or change during the start cycle; Examples: Belts, and conveyors.
The Tachometer ramp applies to the following in the Starter Setup Main Menu:
Tachometer Setup
Stop ModesCoas (Coast): A coast stop should be used when no special stopping requirements are
There is no menu that applies in the Starter Setup Main Menu.
VDCL (S Curve Voltage Deceleration): A standard open loop S-Curve voltage
deceleration is best suited for applications such as pumps and compressors.
The S Curve Voltage Deceleration applies to the following in the Starter Setup Main
Menu: Decel Setup
TT (Tru Torque): The true torque deceleration is best suited to pumping and
compressor applications where pressure surges during a stop must be eliminated.
This setup is easier than the S-Curve Voltage Deceleration and is less source voltage
dependent.
The Tru Torque deceleration applies to the following in the Starter Setup Main Menu:
True Torque Ramp
31
4.1 OPERATION
)
Current Ramp Adjustment
Current RampThe current ramp sets how the motor accelerates. The current ramp is a linear
increase in current from the initial setting to the maximum setting. The ramp time
sets the speed of this linear current increase. The following figure shows the
relationships of these different ramp settings.
Current
(% of FLA)
Maximum
Current
Kick
Current
Initial
Current
Motor
Stall
Time
0
Kick
0
Time
Ramp
Time
Up To
Speed
Running
Time
(Seconds
Initial Current SettingThe initial current should be set to the level that allows the motor to begin rotating
within a couple of seconds of receiving a start command.
To adjust the initial current setting give the starter a run command. Observe the
motor to see how long it takes before it begins rotating and then stop the unit. For
every second that the motor doesn’t rotate, increase the initial current by 20%.
Typical loads will require an initial current in the 50% to 175% range.
Maximum Current SettingFor most applications, the maximum current can be left at 600%. This will ensure
that enough current is applied to the motor to accelerate it to full speed.
The maximum current can also be set to a lower current limit. This is usually done to
limit the voltage drop on the power system or to limit the torque the motor produces
to help prevent damage to the driven load.
NOTE: The motor may achieve full speed at any time during the current ramp. This
means that the maximum current setting may not be reached. Therefore, the
maximum current setting is the most current that could ever reach the motor, and not
necessarily the maximum current that will reach the motor.
NOTE: When setting a current limit, the motor must be monitored to ensure that the
current is high enough to allow the motor to reach full speed under worst case load
conditions.
32
4.1 OPERATION
Ramp Time SettingThe ramp time is the time it takes for the current to go from the initial current to the
maximum current. To make the motor accelerate faster, decrease the ramp time. To
make the motor accelerate slower, increase the ramp time.
If the ramp time expires before the motor reaches full speed, the starter will maintain
the set maximum current level until either the motor reaches full speed, the stall time
expires, or the motor thermal overload trips.
NOTE: Setting the ramp time to a specific value does not necessarily mean that the
motor will take this time to accelerate to full speed. The motor and load may achieve
full speed before the ramp time expires if the application does not require the set
ramp time and maximum current to reach full speed. Alternatively, the motor and
load may take longer than the set ramp time to achieve full speed.
Programming A Kick Current
GeneralThe kick current sets a current level that overrides the current ramp when a start is
Kick CurrentThe kick current parameter is usually set to a low value and then the kick time is
first commanded. The kick current is only useful on motor loads that are hard to get
rotating but then are much easier to move once they are rotating. An example of a
load which is hard to get rotating is a ball mill. The ball mill requires a high torque to
get it to rotate the first quarter turn (90
the material inside will begin tumbling and it is easier to turn.
adjusted to get the motor rotating. If the kick time is set to more than 2.0 seconds
without the motor rotating, increase the kick current by 100% and re-adjust the kick
time.
o
). Once the ball mill is past 90oof rotation,
Kick TimeThe kick time adjustment should begin at 0.5 seconds and be adjusted by 0.1 or 0.2
second intervals until the motor begins rotating. If the kick time is adjusted above 2.0
seconds without the motor rotating, start over with a higher kick current setting.
Tachometer Feedback
DescriptionThe Tachometer control ramp profile (see page 54)provides a method to linearly ramp
Tachometer RequirementsIn addition to the basic motor and starter setup variables, the following needs to done
the speed of the system. When this control mode is selected, the starter uses a
tachometer to provide speed feedback to the starter. This mode is commonly used on
conveyor belt applications where a smooth controlled start is necessary under various
load conditions to prevent belt breakage, lifting, or excessive stretching. The
Tachometer controller consists of an inner PID current loop and an outer PI speed
control loop.
NOTE: The maximum current limit will override the speed control loop if necessary.
If the Maximum Current level is not set high enough or the load is too great, the
RediStart Micro II starter will limit the motor current to this maximum level. When
current limiting occurs, the speed profile will no longer be linear and the motor(s) will
take longer to accelerate to full speed. Therefore, if current limiting is undesirable,
this parameter must be set higher than the peak starting current during a linear
speed ramp start.
to use the tachometer feedback control ramp:
1. Connect a tachometer with appropriate DC output voltage and correct polarity to
the Redistart Micro II power card input (terminal TBP13).
2. The tachometer feedback Start Mode is selectable as “Tach” from the Starter Modes
menu.
3. Program the appropriate variables in the Tachometer Setup menu.
4. Set the Initial Current level in either the Quick Start menu or the Forward1 Profile
menu to the desired current limit.
33
4.1 OPERATION
5. Set the Maximum Current level in either the Quick Start menu or the Forward1
Profile menu to the desired maximum current limit.
Programming The Motor Deceleration
Deceleration ControlThe standard deceleration control on the RediStart Micro II uses an open loop voltage
ramp. The RediStart Micro II will ramp the voltage down to decelerate the motor. The
curve shows the motor voltage vs the decel setting.
RediStart Micro Decel Curve
100
90
80
70
60
50
40
30
Motor Voltage (% of Line Voltage)
20
10
0
Programmed Decel Level (%)
Decel Level 1This sets the starting voltage of the deceleration ramp. Most motors require the
voltage to drop to around 60% or lower before any significant deceleration is observed.
Therefore, a good first setting for this parameter is 35%.
0102030405060708090100
To adjust this parameter, it is necessary to observe the motor operation as soon as a
stop is commanded. If the motor hunts (speed oscillations) at the beginning of the
deceleration, then lower the parameter by 5%. If the motor has a big drop in speed as
soon as a stop is commanded, then raise the parameter by 5%.
Some motors are very sensitive to the adjustment of this parameter. If a 5%
adjustment changes the motor from hunting to dropping in speed, then a smaller
change of 1% or 2% may be necessary.
Decel Level 2This sets the final voltage for the deceleration ramp. In most cases, this parameter
can be set to 10% and the decel time can be used to adjust the deceleration rate. If the
motor is coming to a stop too quickly or if the starter continues to apply current to the
motor after the motor has stopped, this parameter can be increased in 5% increments
to fix this.
Decel TimeThe decel time sets how quicky the motor decelerates. Usually a time of 30 seconds is
a good starting point. To make the motor take longer to decelerate, increase this
parameter or to make the motor decelerate quicker, decrease this parameter.
34
4.1 OPERATION
PORT (Power Outage Ride Through)
DescriptionThe Power Outage Ride Through capability (see page 58)allows the starter to ride
Bypass DelayPORT can also hold a bypass contactor in for a programmed BYP Dly when the power
through short duration brown outs, single phase, and power loss conditions.
When the system senses a voltage disturbance in a time frame greater than the Sense
Time parameter, the power will be removed from the motor for a coast to stop, and the
Fault Dly timer will begin to time; if it is not set to OFF.
If the power disturbance ends before the programmed Fault Dly time, the motor will
restart -- if a start command is still present -- from initial to maximum current in the
specified ramp time.
If the outage lasts longer than the programmed Fault Dly time, the starter will issue
a Fault 98; “No Mains PWR.”
If Fault Dly is set to OFF, the starter will use the standard motor protection fault
delay timers to sense power disturbances.
NOTE: Starts/Hou (starters per hour), Time Start (time between starts), and BKS
Timer (backspin timer) are not incremented for PORT.
NOTE: If the system Start Mode parameter is programmed with a tachometer ramp,
the system will restart using a tachometer ramp.
disturbance is Sensed.
NOTE: The BYP Dly is fixed at 0.0 seconds to protect systems that contain an
integral bypass card.
NOTE: Caution must be taken when the BYP Dly is set above 0.0 seconds. If the
bypass contactor is energized when the power disturbance ends, the motor will start
across the line. The resulting torque may damage the system.
PORT DetectionThe starter can be detected in PORT operation by monitor of the PORT relay output;
Selectable on any of the programmable relays. Once programmed, this relay can be
used to feed 120VAC to input 9 of the JC13 terminal block on the computer card. This
causes the system to use the Forward/Reverse2 Profile for starting the motor.
TruTorque Acceleration Ramp
TruTorque RampThe TruTorque ramp sub-menu (see page 59) contains the parameters that that are
used to activate and tune TruTorque Acceleration and Deceleration Control.
The primary purpose of TruTorque Control is to reduce the torque surge that occurs
as an AC induction motor comes up to full speed. This torque surge can be a problem
in applications especially in pumps and belt driven applications. In pumping
applications this torque surge results in a pressure peak as the motor comes up to
speed. In most situations this small pressure peak is not a problem. However in
selected cases, even a small pressure peak can be highly undesirable. In belt drive
applications, TruTorque prevents the slipping of belts as the motor reaches full speed.
Note: When TruTorque acceleration control is enabled the second ramp (Ramp #2)
and Kick Current functions are disabled.
TruTorque control can be very useful for a variety of applications. However it is best
used for pump and other variable torque applications. TruTorque generally should not
be used in applications where the starting load varies greatly from one start to
another.
35
4.1 OPERATION
Initial TorqueThis value sets the initial torque value for the motor. The initial torque level should
Maximum TorqueThis value sets the final torque reference value at the end of the ramp time. Typical
be set to a level that allows the motor to begin rotating within a couple of seconds of
receiving a start command. Typical loads will require values between 10% to 30%
If the value is set too high a current surge may result. If the value is set too low a “No
current at Run” fault may occur.
loads require a value around 100-110%. If the load is less than motor rating then the
maximum torque value can be decreased. If the load is hard to start or the motor is a
NEMA C or D type motor then this value may need to be increased.
If the motor reaches full speed too quickly then decrease the Maximum Torque value
by 5% and retest. If the motor does not achieve full speed, increase the Maximum
Torque value by 10% and retest.
If the motor can be started either by using default TruTorque values or current ramp
control, the Maximum Torque value can be more precisely determined so that the
motor comes up to speed in approximately the preset Ramp Time. In this case, while
the motor is running at full load, display the TT% meter on the display (see Meter
Setup for information on how to display the TT% meter). Record the value displayed
when the motor is running with full load. The Maximum Torque value should then be
set to the recorded running value of TT% plus an additional 10%. Retest with this
value to verify correct operation.
Note: When setting the Maximum Torque value the motor must be monitored to
ensure that the torque is high enough to allow the motor to reach full speed under
worst case load conditions.
Ramp TimeThe Ramp Time setting is the time it takes for the torque to go from the Initial Torque
Setting to the Maximum Torque Setting. To make the motor accelerate faster,
decrease the ramp time. To make the motor accelerate slower, increase the ramp time.
If the ramp time expires before the motor reaches full speed the starter will maintain
the set Maximum Torque level until either the motor reaches full speed, the stall
(UTS) timer expires, or the motor thermal overload trips.
Note: Setting the ramp time to a specific value does not necessarily mean that the
motor will take this time to accelerate to full speed. The motor and load may achieve
full speed before the ramp time expires if the application does not require the set
ramp time and maximum torque to reach full speed. Alternatively, the motor and load
may take longer than the set ramp time to achieve full speed.
TruTorque Deceleration Ramp
GeneralThe TruTorque ramp sub-menu (see page 59) contains the parameters that activate
TruTorque Decel ModeAs a default deceleration control will be an open-loop voltage ramp. TruTorque Decel
TruTorque Acceleration and Deceleration Control.
TruTorque deceleration is a closed-loop deceleration control. The RediStart MicroII
will ramp down the torque to smoothly decelerate the motor. TruTorque deceleration
is very simple to setup.
Mode needs to be turned on to utilize TruTorque deceleration control. When
TruTorque deceleration is enabled the TruTorque deceleration settings listed below
will be used for deceleration control.
36
4.1 OPERATION
TT End Decel TorqueThe value sets the final torque level for the TruTorque deceleration ramp. In most
TT Decel Ramp TimeThe TruTorque deceleration time sets how quickly the motor decelerates. Usually a
cases, this parameter can be set to 10%.
To adjust this parameter, it is necessary to observe the motor. If the motor is coming
to a stop too quickly or if the starter continues to apply current to the motor after the
motor has stopped this parameter can be increased in 5% increments.
If the motor is still rotating when the desired deceleration time has expired, decrease
this parameter by 5% and retest.
time of 30 seconds is a good starting point. To make the motor decelerate at a slower
rate increase this time or to make the motor stop quicker decrease this time.
How Fault Classes Work
GeneralThe Fault classes sub-menu (see page 74) allows the starter behavior for different
NonCNon-critical fault. If this fault occurs, the starter will shut down and display the fault
faults to be altered. There are six different options that a fault can be set to. These
options are described in the following paragraphs. See page 98 for a complete fault
code and description listing.
number and description on the display. A non-critical fault can be set to either require
a manual reset or to automatically reset.
The automatic resetting of a non-critical fault is dependant on the automatic
computer reset jumper JPC19 (see page 23). WhenJPC19 is set to auto reset (position
1-2), the starter will automatically reset the fault. The number of automatic resets
parameter (# Auto RST) on page 73 sets how many times the starter will perform this
automatic reset sequence in one hour.
CritCritical fault. If this fault occurs, the starter will shut down and display the fault
DisFault is Disabled. If this fault occurs, the starter will ignore the fault and continue to
WrnAFault warning relay A. If this fault occurs, the starter will continue to operate. If a
WrnBFault warning relay B. If this fault occurs, the starter will continue to operate. If a
WrnCFault warning relay C. If this fault occurs, the starter will continue to operate. If a
number and description on the display. To clear the fault, the computer reset button
must be pressed or the control power to the starter cycled.
operate.
programmable relay is programmed to WrnA, that relay will be energized when the
fault occurs. The WrnA relay can be assigned to as many different faults as the user
requires.
programmable relay is programmed to WrnB, that relay will be energized when the
fault occurs. The WrnB relay can be assigned to as many different faults as the user
requires.
programmable relay is programmed to WrnC, that relay will be energized when the
fault occurs. The WrnC relay can be assigned to as many different faults as the user
requires.
37
4.1 OPERATION
Use of Overcurrent and Undercurrent
GeneralFor the over current and undercurrent trips, there are settings for the current level
OvercurrentThe overcurrent parameters are for the user to set a user defined high current trip.
UndercurrentThe undercurrent parameters are used to set a user defined low current trip. The
Activating a RelayTo make the starter activate a relay when an overcorrect or undercurrent is detected,
Tripping vs RunningAs the default, the starter will trip when an over-current or undercurrent is detected.
and the detect time. The motor current must go above or below the current level
settings for the detect time before the overcurrent or undercurrent condition is
detected. The overcurrent and undercurrent trips do not become active until the
starter is up-to-speed (UTS is shown in top line of display).
The overcurrent parameters are not used for the thermal overload. If the driven load
can be damaged by the full motor torque being applied during a stall or jam of the
driven load, the over-current should be used to prevent this.
undercurrent parameters are used to protect a driven load from running empty. A
good example of the undercurrent trip usage is a water pump. If the pump can run
dry, the undercurrent parameters can be set to detect the low current and shut the
pump down. To use this, the current could be set to 50% and the detect delay to 5
seconds to shut the pump down 5 seconds after the current falls below 50% of the
motor FLA parameter.
a programmable relay must be programmed to OCT or UCT respectively.
To keep the starter operating, the over-current fault (fault #78) or undercurrent fault
(fault #79) must be set to dis (disabled) in the fault classes sub-menu (see page 74) to
turn off the fault trip.
Once the over-current or undercurrent fault is disabled, the starter will not trip when
the over-current or undercurrent condition is detected, The relay programmed to OCT
or UCT will still operate when the condition is detected. Once the condition clears, the
relay will remain active for the programmed release delay time. The user must
monitor the relay output and take appropriate action when the relay is energized.
Overload
GeneralThe RediStart Micro II comes with a programmable overload that allows classes 1-40
Overload ClassesThe overload class sets the time it takes for the overload to trip when the motor
to be programmed plus an overload disable and overload bypass during starting. The
thermal overload is displayed as a percentage of overload used, with 0% representing
a “cold” overload and 100% representing a “tripped” overload. The overload always
operates on the highest phase current.
current is six (6) times the motor FLA. The overload follows an exponential curve that
gives a long trip time for slight overloads and a short trip time for large overloads.
This models the heating of a typical squirrel cage induction motor. See page 11 for the
motor thermal overload curves.
38
4.1 OPERATION
Overload OperationThere are two ways that the overload can operate. The operation is changed in the
fault classes sub-menu by changing the overload lock fault (fault #90) from Crit to Dis.
When fault #90 is set to Crit;
The overload warning relay will energize when the O/L content goes above 90%
•
and de-energize when the O/L content goes back below 80%.
The starter will shut down if the overload content reaches 100%.
•
The overload lock relay will energize when the O/L content reaches 100% and
•
de-energize when the O/L content goes back below 60%.
The starter will not allow an overload reset once the overload trips until the
•
overload content goes back below 60%.
The overload relay will energize when the overload trips and will de-energize
•
when the overload condition is cleared by an automatic or manual reset.
When fault #90 is set to Dis;
The overload warning relay will energize if the overload content goes above 90%
•
and will de-energize when the overload content goes back below 80%.
The starter will not shut if the overload content reaches 100%.
•
The overload lock relay will never energize.
•
The overload relay will energize when the overload content goes above 100% and
•
will de-energize when the overload content goes back below 100%.
Overload OKOverload Warning
Starter Prohibited: No
OLW Relay: Off
OLL Relay: Off
OL Relay: Off
OL Reset
(Manual or Automatic)
OL > 90%
OL < 80%
Starter Prohibited: No
OLW Relay: OnOLW Relay: On
OLL Relay: Off
OL Relay: Off
OL > 100%
& F90 = Crit
OL > 100%
& F90 = Dis
OL < 100%
Overload > 100%
Starter Prohibited: No
OLL Relay: Off
OL Relay: On
Overload Tripped
Starter Prohibited: Yes
OLW Relay: OffOLW Relay: On
OLL Relay: Off
OL Relay: On
OL < 60%
Overload Lock
Starter Prohibited: Yes
OLW Relay: Off
OLL Relay: On
OL Relay: On
Overload Warning & Lock
Starter Prohibited: Yes
OLL Relay: On
OL Relay: On
OL < 80%
Running OverloadWhen the RediStart Micro II is running the overload content will never discharge
below 30%. The overload content will always hold at any value below 30% during the
running period. As soon as the unit is stopped the overload will begin to discharge
back to 0%.
39
4.1 OPERATION
Resolving Overload TripsThe National Electrical Code, article 430 Part C, allows for different overload
multiplier factors depending on the motor and operating conditions.
NEC section 430-32 outlines the allowable service factor (Serv. Fact) for different
motors as follows:
MotorOverload Multiplier
Service factor 1.15 or more1.25
Motor temp. rise 40°C or less1.25
All others1.15
NEC section 430-34 permits further modifications if the service factor (Serv. Fact) is
not sufficient to start the motor:
MotorOverload Multiplier
Service factor 1.15 or more1.40
Motor temp. rise 40°C or less1.40
All others1.30
Although the NEC doesn’t address the effect of the ambient temperature of the motor
location, guidance can be derived by examining NEC limits. If the motor is operating
in an ambient temperature that is less than 40°C, then the overload multiplier can be
increased while still protecting the motor from exceeding it maximum designed
temperature. The following curve gives the ambient temperature vs the correction
factor.
Temperature vs Correction Factor
100
80
e
60
peratur
40
Tem
20
0
Correction Factor
1.001.500.50
Example: If a motor operates at 0°C then a 1.36 correction factor could be applied to
the overload multiplier. This could give a theoretical overload multiplier of 1.36 x 1.25
or 1.70. The highest legal value of overload multiplier is 1.40 so this could be used.
Performing an Emergency Restart
GeneralThe RediStart Micro II has an emergency restart feature which allows the user to
Performing a ResetPlace a jumper between pins 6 and 11 of JC11 on the computer card. Hold the Enter
override any lock-outs that are present. This feature should only be used in an
emergency. Before an emergency reset is performed, the reason for the lock-out and
the condition of the motor should be examined to ensure that the motor is capable of
being re-started without causing any damage.
button on the display and press the thermal overload reset pushbutton until a
microprocessor reset occurs.
40
5.PROGRAMMING
5.1 PROGRAMMING: How To Program
Menu Buttons
GeneralThe RediStart Micro II has a display/keypad that allows the user to set the starter
Press to enter the menu system.
•
Press to abandon changes made to a parameter (before pressing the Enter key).
•
Press to exit a sub-menu.
MENU
ENTER
•
Press to exit the menu system.
•
Press to enter a menu.
•
Press to enter a sub-menu.
•
Press to change the parameter displayed.
•
Press to store the new value entered.
•
Select the menu to enter.
•
Select the sub-menu to enter.
•
Scroll between parameters when in a specific menu or sub-menu.
•
Increase a parameter value.
•
Press to view the meter pages when the main display is shown.
•
Select the menu to enter.
•
Select the sub-menu to enter.
•
Scroll between parameters when in a specific menu or sub-menu.
•
Decrease a parameter value.
•
Press to view the meters when the main display is shown.
•
parameters using a plain English interface. The functions of the display buttons are
as follows.
START
STOP
•
Press to start the motor when the starter is connected for local display control.
•
Press to activate the BIST (Built-In Self Test).
•
If 2-wire control is used or the Start button is disabled, this button is inoperative.
•
Press to stop the motor when the starter is connected for local display control.
•
If 2-wire control is used or the Stop button is disabled, this button is inoperative.
42
5.1 PROGRAMMING: How To Program
Menu Structure
Menu StructureThe RediStart Micro II has a 2 level menu structure. There are eight main menus that
contain parameters related to the different functions of the starter and five of the
main menus contain additional sub-menus that divide the parameters into functional
groups. The following shows the structure of the menu structure.
Main Menu
Quick Start Motor Nameplate Starter SetupMotor Protection Meters & Relays
Starter Modes
Forward1 Profile
Forward2 Profile
Tachometer Setup
Decel Setup
PORT Ctl Setup
True Torque ramp
Overload Class
Line Current
Line Voltage
Line Frequency
Ground Fault
Shorted SCR
Over Curr. Trip
Under Curr. Trip
Start Lockouts
Starting Timers
Permissive Input
Misc.
Fault Classes
Meters Setup
Standard Relays
Extended Relays
Event Recorder
Control Config
System Clock
System Password
Comm. Settings
Options List
Software Part#
Factory Setup
Hardware Setup
BIST Setup/Run
Factory Control
RTD Setup
RTD Module Setup
RTD Setpnts 1-8
RTD Setpnts 9-16
43
5.1 PROGRAMMING: How To Program
Viewing a Parameter
Viewing a ParameterTo access a specific parameter in the RediStart Micro II menu structure, follow these
steps. Refer to the previous page for a graphical representation of the menu structure.
Press the Menu button to enter the menu system.
•
Press the Up or Down buttons to get the desired menu on the display.
•
Press the Enter button to go into the menu.
•
Press the Up or Down button to get to the desired sub-menu, if necessary.
•
Press the Enter button to go into the sub-menu, if necessary.
•
Press the Up or Down arrow buttons until the parameter is displayed.
•
Changing a Parameter
Changing a ParameterTo change a parameter, follow these steps;
An ExampleThe ramp time is set to 30 seconds and it is to be changed to 20 seconds.
View the desired parameter by following the Viewing a Parameter instructions.
•
Press the Enter button to switch to the change parameter screen.
•
Press the Up or Down buttons to get the desired value on the screen.
•
Press the Enter button to store the new value.
•
The following steps must be taken to change the ramp time.
Press the Menu button to enter the menu system.
•
Press the Down button twice to get to the Starter Setup screen.
•
Press the Enter button to access the Starter Setup menu.
•
Press the Down button once to display the Forward1 Profile.
•
Press the Enter button to access the Forward1 Profile sub-menu.
•
Press the Down button twice to display the Ramp Time parameter.
•
Press the Enter button to allow a change to the ramp time.
•
Press the Down button repeatedly to change the Ramp Time to the desired
•
value.
• Press the Enter button to store the value.
•
Press the Menu button repeatedly to return to the main display.
44
5.2 PROGRAMMING: Quick Start
Motor FLA
Parameter DescriptionThe motor FLA parameter must be set to the full load amps of the motor connected to
Parameter ValuesThe motor FLA parameter is adjustable from 1 to 1200 amps in 1 amp increments.
Parameter DefaultThe default value for the motor FLA is 1 amp.
the starter for the starter to function correctly. If there is more than one motor
connected, the motor FLA should be set to the sum of the connected motor full load
amps.
NOTE: The starter uses the entered motor FLA for every current based calculation. If
the motor FLA is not entered correctly, the current ramp profile and many of the
starter’s advanced protection features will not function properly.
Serv. Fact (service factor)
DescriptionThe service factor parameter should be set to the service factor of the motor. The
ValuesThe service factor can be set from 1.00 to 1.99, in 0.01 increments.
service factor is used for the overload calculations. If the service factor of the motor is
not known then the service factor should be set to 1.00. See the motor overload
parameter on page 11 for a detailed description on how to set the service factor for
different applications to avoid overload trips.
NOTE: The NEC (National Electrical Code) does not allow the service factor to be set
above 1.40. Check with other local electrical codes for their requirements.
DefaultThe default value for the service factor is 1.15.
Start Mode
DescriptionThe Start Mode parameter allows for an optimal start of the motor based on the
ValuesThe Start Mode Parameter can be set to Curr, TT, or Tach.
DefaultThe default value for the Start Mode is Curr.
application. For a description of the possible Start Mode parameters, refer to page 31
in the Operations chapter.
Stop Mode
DescriptionThe Stop Mode parameter allows for the most suitable stop of the motor based on the
ValuesThe Stop Mode can be set to Coas, VDCL, or TT.
DefaultThe default value for the Stop Mode is Coas.
application. For a description of the possible Stop Mode parameters, refer to page 31
in the Operations chapter.
45
5.2 PROGRAMMING: Quick Start
Int. Curr. (initial current)
DescriptionThe initial current parameter is set as a percentage of the motor FLA parameter
ValuesThe initial current is adjustable from 50% to 400% in 1% intervals.
DefaultThe default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the
motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial
current should be increased. If the motor takes off too quickly after a start command,
the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current
parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
DescriptionThe maximum current parameter is set as a percentage of the motor FLA parameter
setting. The maximum current parameter performs two functions. It sets the current
for the end of the ramp profile. It also sets the maximum current that is allowed to
reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold
the current at the maximum current level until the stall time expires, the motor
reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load
dictates the setting of a lower maximum current.
ValuesThe maximum current is adjustable from 100% to 600% in 1% intervals.
DefaultThe default value for the maximum current is 600%.
Ramp Time
DescriptionThe ramp time sets the amount of time that it takes for the starter to linearly
SettingsThe ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
DefaultThe default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
46
5.2 PROGRAMMING: Quick Start
Overload
DescriptionThe overload parameter sets the class of the electronic overload. The starter stores the
ValuesClass 1 to 40 in steps of 1.
DefaultThe default value for the overload parameter is 10.
thermal overload value as a percentage value between 0 and 100%, with 0%
representing a “cold” overload and 100% representing a tripped overload. See page 11
for the overload trip time vs current curves.
Phase Order
DescriptionThe line phasing parameter sets the phase sensitivity of the starter. This can be used
ValuesThe line phasing can be set to;
DefaultThe default value for the phase sensitivity parameter is INS.
to protect the motor from a possible change in the incoming phase sequence. If the
incoming phase sequence does not match the set phase rotation, the starter will
display phs err while stopped and will fault if a start is attempted.
INS- will run with either phase sequence
•
ABC- will only run with ABC phase sequence
•
CBA- will only run with CBA phase sequence
•
47
5.3 PROGRAMMING: Motor Nameplate
Motor FLA
DescriptionThe motor FLA parameter must be set to the full load amps of the motor connected to
ValuesThe motor FLA parameter is adjustable from 1 to 1200 amps in 1 amp increments.
DefaultThe default value for the motor FLA is 1 amp.
the starter for the starter to function correctly. If there is more than one motor
connected, the motor FLA should be set to the sum of the connected motor full load
amps.
NOTE: The starter uses the entered motor FLA for every current based calculation. If
the motor FLA is not entered correctly, the current ramp profile and many of the
starter’s advanced protection features will not function properly.
Serv. Fact (service factor)
DescriptionThe service factor parameter should be set to the service factor of the motor. The
ValuesThe service factor can be set from 1.00 to 1.99, in 0.01 increments.
service factor is used for the overload calculations. If the service factor of the motor is
not known then the service factor should be set to 1.00. See the motor overload
parameter on page 11 for a detailed description on how to set the service factor for
different applications to avoid overload trips.
NOTE: The NEC (National Electrical Code) does not allow the service factor to be set
above 1.40. Check with other local electrical codes for their requirements.
DefaultThe default value for the service factor is 1.15.
DescriptionThe Motor RPMs can be set to match the RPM rating of the motor.
ValuesThe Motor RPMs can be set from 1 to 3600 RPM’s in increments of 1.
DefaultThe default value for the Motor RPMs is 1760.
Motor RPMs
48
5.4 PROGRAMMING: Starter Setup - Starter Modes
Start Mode
DescriptionThe Start Mode parameter allows for an optimal start of the motor based on the
ValuesThe Start Mode Parameter can be set to Curr, TT, or Tach.
DefaultThe default value for the Start Mode is Curr.
application. For a description of the possible Start Mode parameters, refer to page 31
in the Operations chapter.
Stop Mode
DescriptionThe Stop Mode parameter allows for the most suitable stop of the motor based on the
ValuesThe Stop Mode can be set to Coas, VDCL, or TT.
DefaultThe default value for the Stop Mode is Coas.
application. For a description of the possible Stop Mode parameters, refer to page 31
in the Operations chapter.
49
5.5 PROGRAMMING: Starter Setup - Forward1 Profile
Int. Curr. (initial current)
DescriptionThe initial current parameter is set as a percentage of the motor FLA parameter
ValuesThe initial current is adjustable from 50% to 400% in 1% intervals.
DefaultThe default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the
motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial
current should be increased. If the motor takes off too quickly after a start command,
the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current
parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
DescriptionThe maximum current parameter is set as a percentage of the motor FLA parameter
setting. The maximum current parameter performs two functions. It sets the current
for the end of the ramp profile. It also sets the maximum current that is allowed to
reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold
the current at the maximum current level until the stall time expires, the motor
reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load
dictates the setting of a lower maximum current.
ValuesThe maximum current is adjustable from 100% to 600% in 1% intervals.
DefaultThe default value for the maximum current is 600%.
Ramp Time
DescriptionThe ramp time sets the amount of time that it takes for the starter to linearly
SettingsThe ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
DefaultThe default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
50
5.5 PROGRAMMING: Starter Setup - Forward1 Profile
Kick Curr. (kick current)
DescriptionThe kick current parameter is set as a percentage of the motor FLA parameter
ValuesThe kick current is adjustable from 100% to 600% in 1% increments.
DefaultThe default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile,
for the set kick time, when a start is commanded. If a kick time is programmed, the
starter will provide the current level specified by the kick current setting for this set
time. This current can be used to overcome the break over torque of some loads, while
still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
DescriptionThe kick time parameter sets the amount of time that the kick current level is
ValuesThe kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
DefaultThe default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick
current level for the set time. The kick time should be increased or decreased to reach
the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
51
5.6 PROGRAMMING: Starter Setup - Forward2 Profile
Forward #2 Ramp Profile
GeneralThe forward #2 ramp profile sub-menu contains the parameters that set the starting
ramp profile when the second ramp is selected. The second ramp is selected by
applying 120VAC to input 9 of the JC13 terminal block on the RediStart Micro II CPU
card.
Int. Curr. (initial current)
DescriptionThe initial current parameter is set as a percentage of the motor FLA parameter
ValuesThe initial current is adjustable from 50% to 400% in 1% intervals.
DefaultThe default value for the initial current is 100%.
setting. The initial current parameter sets the current that will initially reach the
motor when a start is commanded.
If the motor does not rotate within a few seconds after a start command, the initial
current should be increased. If the motor takes off too quickly after a start command,
the initial current should be decreased.
The initial current must be set to a value that is lower than the maximum current
parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Max. Curr. (maximum current)
DescriptionThe maximum current parameter is set as a percentage of the motor FLA parameter
ValuesThe maximum current is adjustable from 100% to 600% in 1% intervals.
DefaultThe default value for the maximum current is 600%.
setting. The maximum current parameter performs two functions. It sets the current
for the end of the ramp profile. It also sets the maximum current that is allowed to
reach the motor while the motor is being started.
If the ramp time expires before the motor has reached full speed, the starter will hold
the current at the maximum current level until the stall time expires, the motor
reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load
dictates the setting of a lower maximum current.
Ramp Time
DescriptionThe ramp time sets the amount of time that it takes for the starter to linearly
SettingsThe ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
DefaultThe default value for the ramp time is 15 seconds.
increase the current from the initial current level to the maximum current level.
A typical ramp time setting is from 15 to 30 seconds.
52
5.6 PROGRAMMING: Starter Setup - Forward2 Profile
Kick Curr. (kick current)
DescriptionThe kick current parameter is set as a percentage of the motor FLA parameter
ValuesThe kick current is adjustable from 100% to 600% in 1% increments.
DefaultThe default value for the kick current is 300%.
setting. The kick current sets a current level that overrides the current ramp profile,
for the set kick time, when a start is commanded. If a kick time is programmed, the
starter will provide the current level specified by the kick current setting for this set
time. This current can be used to overcome the break over torque of some loads, while
still allowing the starter to smoothly accelerate the load to full speed.
Kick Time
DescriptionThe kick time parameter sets the amount of time that the kick current level is
ValuesThe kick time is adjustable from 0.1 to 10.0 seconds in 0.1 second intervals. If a kick
DefaultThe default value for the kick time is Off.
provided to the motor when a start is commanded.
If the kick time is set to any time other than Off, the starter will provide the kick
current level for the set time. The kick time should be increased or decreased to reach
the time required to begin rotating the load.
current is not required, the kick time should be set to Off.
53
5.7 PROGRAMMING: Starter Setup - Tachometer Setup
FS Volts (Full Speed Volts)
DescriptionThe FS Volts parameter sets the tachometer input voltage at full speed. This value
ValuesThe tachometer FS Volts value can be set between 1.00 and 7.00 volts in 0.01
DefaultThe default value for the tachometer FS Volts value is 5.00 volts.
should be set at full (unloaded) motor speed.
For example: A tachometer rated at 0.0033 volts-per-rpm is mounted on a 4-pole 1800
rpm motor. Therefore, the FS Volts should be set to: 0.0033 x 1800 = 5.94 volts.
increments.
Stab Cnst (Stability Constant)
DescriptionThe Stab Cnst parameter is used to control the speed and bandwidth of the of the
ValuesThe Stab Cnst parameter is adjustable from 10% to 150% in 1% increments.
DefaultThe default value for the Stab Cnst parameter is 100%.
speed controller.
NOTE: Lower values slow down the controller’s response,which is useful if the system
has a large inertia and/or low stiffness. Higher values will speed up the controler’s
response, which can be useful if the more precise speed control is necessary. If the
stability constant is set too low, the starter will not track the speed reference properly
and the motor speed profile will not be linear.
Ramp#1 Tim
DescriptionThe Ramp#1 Tim parameter sets the length of time that the D.C. brake current is
ValuesThe Ramp#1 Tim is adjustable from 0 to 120 seconds in 1 second intervals. The
DefaultThe default value for the Ramp#1 Tim is 15 seconds.
applied to the motor.
Ramp#1 Tim can also be set to Off.
Ramp#2 Tim
DescriptionThe Ramp#2 Tim parameter sets the length of time that the D.C. brake current is
ValuesThe Ramp#2 Tim is adjustable from 0 to 120 seconds in 1 second intervals. The
DefaultThe default value for the Ramp #2 Tim is 15 seconds.
applied to the motor.
Ramp#2 Tim can also be set to Off.
54
5.7 PROGRAMMING: Starter Setup - Tachometer Setup
TLoss Dela (Tachometer Signal Loss Delay)
DescriptionThe TLoss Delay time is the allowable time the starter will operate when a
ValuesThe TLoss Delay time parameter is adjustable from 0.1 seconds to 90.0 seconds in 0.1
DefaultThe default value for the TLoss Delay time is 1.5 seconds.
tachometer signal is lost. If the signal is lost, the starter will perform the action set by
the TLoss Mode parameter.
NOTE: Nuisance tachometer loss faults at start can be prevented by setting the
initial current parameter to a value that allows the motor to begin rotating soon after
a start is commanded.
second intervals.
TLoss Mode (Tachometer Signal Loss Mode)
DescriptionThe TLoss Mode determines the starter’s action if it has been detected the tachometer
ValuesThe TLoss Mode parameter can be set to Shut (shutdown), Curr (Current Ramp), or
DefaultThe default value for the TLoss Mode is Shut.
signal is lost.
NOTE: If Current ramp or TruTorque ramp is selected, all values within these ramp
profiles must be set for proper operation.
NOTE: If Current ramp or TruTorque ramp is selected, and the tachometer signal is
lost, the starter will shut down and automatically restart with the new starting mode.
The new start mode will apply until a manual reset to Tach is performed.
TT (TruTorque Ramp).
55
5.8 PROGRAMMING: Starter Setup - Decel Setup
V Level #1
DescriptionThe V Level #1 parameter sets the starting voltage for the voltage ramp deceleration
ValuesThe decel level #1 is adjustable from 10% to 100% in 1% increments. The decel level
DefaultThe default value for the decel level #1 parameter is 40%.
ramp profile.
The deceleration profile uses an open loop voltage ramp profile. The decel level #1
parameter sets the starting point on the S curve. This means that decel level #1 is not
set as a percentage of actual line voltage.
If the motor initially surges when a stop is commanded, decrease this parameter
value. If there is a sudden drop in motor speed when a stop is commanded, increase
this parameter value.
A typical decel level #1 setting is between 30% and 40%.
#1 setting must be greater than the decel level #2 setting.
V Level #2
DescriptionThe V Level #2 parameter sets the ending voltage for the voltage ramp profile. Decel
level #2 can not be set greater than decel level #1.
The deceleration profile uses an open loop voltage ramp profile. The decel level #2
parameter sets the ending point on the S curve. This means that decel level #2 is not
set as a percentage of actual line voltage.
If the motor stops rotating before the deceleration time has expired, increase this
parameter value. If the motor is still rotating when the deceleration time has expired,
decrease this parameter value. A typical decel level #2 setting is between 10% and
20%.
ValuesThe decel level #2 parameter is adjustable from 1% to 99% in 1% increments. The
DefaultThe default value for the decel level #2 parameter is 20%.
decel level #2 must be less than the decel level 1 setting.
V DCL Time (decel time)
DescriptionThe V DCL Time parameter sets the amount of time taken to go from the decel level
ValuesThe decel time parameter is adjustable from 0 to 60 seconds in 1 second intervals.
DefaultThe default value for the decel time parameter is 0 seconds.
#1 setting to the decel level #2 setting.
If the motor stops rotating before the decel time has expired, decrease the decel time.
If the motor is still rotating when the decel time expires, increase the decel time.
A typical decel time setting is 20 to 40 seconds.
56
5.8 PROGRAMMING: Starter Setup - Decel Setup
TT DCL Tim (TruTorque deceleration time)
DescriptionThe TruTorque deceleration time sets how quickly the motor decelerates. Usually a
ValuesThe TruTorque deceleration time parameter is adjustable from 0 to 100 seconds in 1
DefaultThe default TruTorque deceleration time is 0 seconds.
time of 30 seconds is a good starting point. To make the motor decelerate at a slower
rate increase this time or to make the motor stop quicker decrease this time.
second intervals
TT DCL Tor (ending deceleration torque)
DescriptionThe value sets the final torque level for the Trutorque deceleration ramp. In most
ValuesThe TruTorque deceleration ending torque value can be set from 1% to 100% torque in
DefaultThe default TruTorque deceleration ending torque setting is 10%
cases, this parameter can be set to 10%.
To adjust this parameter, it is necessary to observe the motor. If the motor is coming
to a stop too quickly or if the starter continues to apply current to the motor after the
motor has stopped this parameter can be increased in 5% increments.
If the motor is still rotating when the desired deceleration time has expired, decrease
this parameter by 5% and retest.
1% steps.
57
5.9 PROGRAMMING: Starter Setup - PORT CTL Setup
Fault Dly (Fault Delay)
DescriptionThe Fault Dly parameter determines how long a power disturbance can exist before
ValuesThe Fault Dly parameter is adjustable from OFF, 0.1 through 90.0 seconds in 0.1
DefaultThe default value for the Fault Dly parameter is OFF.
the micro system will fualt out on a power loss; and no longer restart. If the Fault Dly
parameter is set to OFF, the PORT detection wil be disabled and the standard motor
protection features will be enabled.
second intervals.
Bypass Dly (Bypass Delay)
DescriptionThe Bypass Dly parameter determines when the bypass contactor will drop after a
ValuesThe Bypass Dly parameter is adjustable from OFF, 0.0 through 3.0 seconds in 0.1
DefaultThe default value for the Bypass Dly time is 0.0 seconds.
power disturbance is sensed.
second intervals.
Sense Time
DescriptionThe Sense Time parameter determines how long a power outage must exist before the
micro will drop to a coast to stop, and wait for a valid line voltage before restarting.
ValuesThe Sense Time parameter is adjustable from 0.01 through 0.50 seconds in 0.01
DefaultThe default value for the Sense Time parameter is 0.05 seconds.
second intervals.
58
5.10 PROGRAMMING: Starter Setup - TruTorque Ramp
Int Torque (initial torque)
DescriptionThe initial torque parameter sets the initial torque level that the motor will produce
ValuesThe initial torque is adjustable from 1% to 100% in 1% increments.
DefaultThe default value for initial torque is 20%.
during starting. This parameter should be set to a level that allows the motor to begin
acceleration with a few seconds of a start command being received.
Max Torque (maximum torque)
DescriptionThe maximum torque parameter sets the final level of torque that is supplied to the
ValuesThe maximum torque is adjustable from 10% to 325% in 1% increments.
DefaultThe default value for the maximum torque parameter is 105%.
motor during starting. For a loaded motor, the maximum torque parameter initially
should be set to 100% or greater. If the maximum torque value is set too low, the
motor may not produce enough torque to reach full speed (UTS). On a lightly loaded
motor this parameter may be reduced below 100% to provide for smoother starts.
Ramp Time
DescriptionThe ramp time parameter sets the time it takes for the commanded torque to go from
the Initial Torque Setting to the Maximum Torque Setting. To make the motor
accelerate faster, decrease the ramp time. To make the motor accelerate slower,
increase the ramp time.
If the ramp time expires before the motor reaches full speed the starter will maintain
the set Maximum Torque level until either the motor reaches full speed, the stall
(UTS) timer expires, or the motor thermal overload trips.
Note: This ramp time setting is only used for TruTorque starts. It is not the same
ramp time parameter that is used for current ramp profile starts.
Note: Setting the ramp time to a specific value does not necessarily mean that the
motor will take this time to accelerate to full speed. The motor and load may achieve
full speed before the ramp time expires if the application does not require the set
ramp time and maximum torque to reach full speed. Alternatively, the motor and load
may take longer than the set ramp time to achieve full speed.
ValuesThe TruTorque ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
DefaultThe default value for the TruTorque ramp time is 15 seconds.
59
5.10 PROGRAMMING: Starter Setup - TruTorque Ramp
TT Over Cu (TruTorque overcurrent trip)
DescriptionThe TruTorque overcurrent trip parameter is set as a percentage of FLA. If the motor
ValuesThe TruTorque overcurrent can be set to Off or from 100% to 800% of FLA in 1%
DefaultThe default value for the TruTorque Overcurrent parameter is Off
current remains above this level for longer than the delay time the starter will trip. In
order to protect applications such as pumps from water hammer when a fault does
occur a normal deceleration profile will occur to "gracefully" shut down the system
before the TruTorque Overcurrent Fault is displayed and the starter is disabled.
Note: The TruTorque Overcurrent Trip only operates during TruTorque ramping
before the starter has indicated an up-to-speed condition. If overcurrent protection is
desired after the motor has come up to speed the Over Current parameter under the
Motor Protection menu must be used.
increments.
Ovr Cur Dl (TruTorque overcurrent trip delay)
DescriptionThe TruTorque overcurrent trip delay parameter sets the time that the motor current
ValuesThe TruTorque overcurrent delay parameter can be set from 0.1 to 90.0 seconds in 0.1
DefaultThe default value for the TruTorque overcurrent delay parameter is 0.1 seconds.
must exceed the TruTorque Overcurrent Trip setting, while the starter is ramping,
before a trip will occur.
second intervals.
60
5.11 PROGRAMMING: Motor Protection - Overload
Overload
DescriptionThe overload parameter sets the class of the electronic overload. The starter stores the
ValuesClass 1 to 40 in steps of 1.
DefaultThe default value for the overload parameter is 10.
thermal overload value as a percentage value between 0 and 100%, with 0%
representing a “cold” overload and 100% representing a tripped overload. See page 11
for the overload trip time vs current curves.
61
5.12 PROGRAMMING: Motor Protection - Line Current
% Imbalanc (percent imbalance)
DescriptionThe percent imbalance parameter sets the allowable phase to average current
ValuesThe percent imbalance is adjustable from 10 to 40% in 1% increments.
DefaultThe default value for the percent imbalance is 15%.
difference that is allowed before the starter will shut down. The current imbalance
must exist for the amount of time set by the imbalance delay time before this will
occur.
The current imbalance for each phase is calculated as the percentage difference
between the phase current and the average current. The equation for the current
imbalance is;
II
−
% imbalance
If the highest calculated current imbalance is greater than the current imbalance
level, the starter will shut down the motor and display a fault 23 to fault 28
depending on the phase that has the out of range current.
avephase
=
100%
×
ave
I
Imbal Dela (imbalance delay)
DescriptionThe imbalance delay parameter sets the time that the current imbalance must be
ValuesThe imbalance delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
greater than the percent imbalance parameter before a trip will occur.
intervals.
DefaultThe default value for the imbalance delay parameter is 0.5 seconds.
@ Stop Dly (current at stop delay)
DescriptionThe current at stop delay parameter sets the time that a phase current must be
ValuesThe current at stop delay parameter can be set from 0.1 to 10.0 seconds in 0.1 second
DefaultThe default value for the current at stop delay parameter is 1.5 seconds.
greater than 5% of the motor FLA parameter, while the starter is in a stopped state,
before a trip will occur.
intervals
62
5.12 PROGRAMMING: Motor Protection - Line Current
% No C@Run (percent no current at run)
DescriptionThe percent no current at run parameter sets a low current operating level. If the
ValuesThe percent no current at run parameter can be set from 2 to 40% in 1% increments.
DefaultThe default value for the percent no current at run parameter is 5%.
current falls below this level, the RediStart Micro II will shut down the starter and
give a no current at run fault. This level is set as a percentage of the motor full load
amps. The current must remain below this parameter setting for the no current at run
delay time before a fault will occur.
No C@R Dly (no current at run delay)
DescriptionThe no current at run delay parameter sets the time that the motor current must be
ValuesThe no current at run parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the no current at run parameter is 1.0 seconds.
less than the percent no current at run parameter setting, while the starter is in a run
state, before a trip will occur.
intervals.
63
5.13 PROGRAMMING: Motor Protection - Line Voltage
H/L Volts (high/low voltage)
DescriptionThe high/low voltage trip sets the allowable operating voltage range. If the voltage on
ValuesThe high/low voltage is adjustable from 10 to 30% in 1% increments.
any line goes outside of the allowable operating range, the starter will shut down and
give a high or low line fault.
The low and high voltage trip points are calculated as follows;
The base voltage (V
voltage parameter (see page 48) or automatically selected according to the following
list;
The base voltage (V
and JPC18 on the RediStart Micro computer card. Refer to the jumper settings on
page for information on setting these parameters.
The line voltage must be out of the specified range for the time specified by the delay
time parameter before the starter will trip.
lowbasebase=−×÷
VVV(Parameter 100)
highbasebase=+×÷
VVV(Parameter 100)
) that is used for the calculations is either set by the source
base
208VAC if average line voltage is between 180VAC and 224VAC.
240VAC if average line voltage is between 225VAC and 269VAC.
315VAC if average line voltage is between 270VAC and 334VAC.
380VAC if average line voltage is between 345VAC and 409VAC.
460VAC if average line voltage is between 410VAC and 489VAC.
480VAC if average line voltage is between 490VAC and 524VAC.
575VAC if average line voltage is between 525VAC and 650VAC.
1000VAC if average line voltage is between 651VAC and 1000VAC.
) used for the calculations is selected by setting jumpers JPC17
base
DefaultThe default value for the high/low voltage parameter is 20%.
Delay Time
DescriptionThe delay time parameter sets the time that the line voltage must go outside of the
ValuesThe voltage delay parameter is adjustable from 0.1 to 3.0 seconds in 0.1 second
DefaultThe default value for the voltage delay parameter is 0.5 seconds.
voltage range set by the high/low voltage parameter before a high or low voltage trip
will occur.
This parameter may be lengthened to allow for temporary voltage fluctuations outside
of the allowable voltage range. If the time is extended, the control voltage must be
monitored to ensure it remains within acceptable limits. If the control voltage is
fluctuating, an un-interruptible power supply should be used.
intervals.
PH Dect Dl (Phase detect delay)
DescriptionThe phase detect delay parameter sets the delay time on Fault #56: “Phase Detection.”
This fault detects a loss of proper phase timing even when the phase code remains
valid; example: loss of line when the motor back generates a voltage. This allows a
much faster detection than low line or no current at run faults.
ValuesThe PH Dect Dl parameter is adjustable from 0.3 to 5.0 seconds in 0.1 second
DefaultThe default value for the PH Dect Dl parameter is 0.8 seconds.
64
intervals.
5.14 PROGRAMMING: Motor Protection - Line Frequency
High Freq. (high frequency)
DescriptionThe high frequency parameter sets the highest line frequency that the starter will
ValuesThe high frequency trip is adjustable from 72 to 24hz in 1hz increments.
DefaultThe default value for the high frequency trip parameter is 72hz.
operate on.
When operating on line power, the default setting will usually suffice. If the
application is speed sensitive, or the line power is suspect, the high frequency
parameter can be set to the highest acceptable frequency. When operating on
generator power, the high frequency parameter should be set to the highest acceptable
frequency. This will ensure that a generator problem will not cause unnecessarily
large fluctuations in the speed of the motor.
The frequency must be above the high frequency setting for the frequency delay
parameter before the starter will recognize a high frequency condition. Once a high
frequency condition exists, the starter will shut down and display a fault 4, High Freq.
Trip.
Low Freq. (low frequency)
DescriptionThe low frequency parameter sets the lowest line frequency that the starter will
operate on.
When operating on line power, the default setting will usually suffice. If the
application is speed sensitive, or the line power is suspect, the low frequency
parameter can be set to the lowest acceptable frequency. When operating on generator
power, the low frequency parameter should be set to the lowest acceptable frequency.
This will ensure that a generator problem will not cause unnecessarily large
fluctuations in the speed of the motor.
The frequency must be below the low frequency setting for the frequency delay
parameter before the starter will recognize a low frequency condition. Once a low
frequency condition exists, the starter will shut down and display a fault 5, frequency
< Low Freq. Trip.
ValuesThe low frequency trip is adjustable from 23 to 71hz in 1 Hz intervals.
DefaultThe default value for the low frequency trip parameter is 23hz.
Freq Delay (frequency delay)
DescriptionThe frequency delay parameter sets the time that the line frequency must go above
ValuesThe frequency delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the frequency delay parameter is 0.1 seconds.
the high frequency trip point or below the low frequency trip parameter before a high
or low frequency fault will occur.
intervals.
65
5.15 PROGRAMMING: Motor Protection - Ground Fault
GND Fault (ground fault)
DescriptionThe ground fault parameter sets a ground fault current trip or indicate level that can
ValuesThe ground fault is adjustable from 1 to 100 amps in 1 amp increments. The ground
DefaultThe default value for the ground fault parameter is Off.
be used to protect the system from a ground fault condition.
The starter monitors the instantaneous sum of the three line currents to detect the
ground fault current. This is often referred to as residual ground fault
protection. This type of protection is meant to provide machine ground fault
protection only. It is not meant to provide human ground fault protection.
The ground fault current has to remain above the ground fault level for the ground
delay parameter time before the starter will recognize a ground fault condition. Once
the starter recognizes a ground fault condition, it will shut down the motor and
display a fault 71-Ground Fault. If a programmable relay is set to ground fault (GND),
the starter will energize the relay when the condition exists.
If it is desired to have the starter continue to operate after a ground fault is detected,
enter the fault classes menu (see page 74) and change the classification of fault 71 to
either Dis, WrnA, WrnB, or WrnC.
A typical value for the ground fault current setting is 10% to 20% of the full load amps
of the motor.
fault current can also be set to Off by setting it below 1 amp.
GND Delay (ground delay)
DescriptionThe ground delay parameter sets the period of time that the ground fault current
ValuesThe ground delay parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the ground delay parameter is 1.0 seconds.
must be above the ground fault current setting before a ground fault trip will occur.
intervals.
66
5.16 PROGRAMMING: Motor Protection - Shorted SCR
@ Ramp DLY (shorted SCR at ramp delay)
DescriptionThe shorted SCR at ramp parameter sets the period of time that there must be a
ValuesThe shorted SCR at ramp parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the shorted SCR at ramp parameter is 0.2 seconds.
current imbalance of more than 50%, while the starter is accelerating, before a
shorted SCR fault occurs.
intervals.
@ Stop DLY (shorted SCR at stop delay)
DescriptionThe shorted SCR at stop parameter sets the period of time that there must be a
ValuesThe shorted SCR at stop parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the shorted SCR at stop parameter is 1.0 seconds.
current flow of more than 50% of the motor FLA value, while the motor is stopped,
before a shorted SCR fault will occur.
intervals.
67
5.17 PROGRAMMING: Motor Protection - Over Current
Current
DescriptionThe current parameter is set as a percentage of the motor FLA parameter. It sets a
ValuesThe current is adjustable from 50 to 800%, in 1% increments. The current can also be
DefaultThe default value for the current parameter is Off.
high current trip or indicate level that can be used to protect the system from an
overloaded condition.
The motor current has to remain above the current setting for the delay time
parameter before the starter will recognize an over current condition.
NOTE: The overcurrent parameter does not become active until after the starter has
reached full speed.
set to Off by going above 800%.
Detect Dly (detect delay)
DescriptionThe detect delay time parameter sets the period of time that the motor current must
ValuesThe detect delay time can be set from 0.1 to 90.0 seconds in 0.1 second intervals.
DefaultThe default value for the detect delay time parameter is 0.1 second.
be greater than the over current level before a shear pin trip will occur.
Release Dl (release delay)
GeneralThe release delay time sets how long the relay is energized after the over current
ValuesThe release delay time parameter can be set from 1.0 to 90.0 seconds in 0.1 second
DefaultThe default value for the release delay time parameter is 10.0 seconds.
condition is cleared. This parameter is only functional if a relay has been programmed
to OCT (over current trip) in the relay sub-menu (see page 77) and the fault has been
disabled in the fault classes sub-menu (see page 74).
intervals
68
5.18 PROGRAMMING: Motor Protection - Under Current
Current
DescriptionThe current parameter is set as a percentage of the motor FLA parameter. It sets a
ValuesThe current is adjustable from 10 to 100% in 1% increments. The current can also be
DefaultThe default value for the current parameter is Off.
low current trip or indicate level and can be used to protect the system from an
unloaded condition. The under current protection is especially useful to protect a
pump. The motor current will fall when the pump becomes unloaded and the under
current protection can be used to shut down the motor or warn of this unloaded
condition.
The motor current has to remain below the under current setting for the under
current delay time parameter before the starter will recognize an under current
condition.
set to Off by going below 10%
Detect Dly (detect delay)
DescriptionThe detect delay time parameter sets the period of time that the motor current must
ValuesThe detect delay time parameter can be set from 0.1 to 90.0 seconds in 0.1 second
DefaultThe default value for the detect delay time parameter is 0.1 seconds.
be less than the current level before an under current trip will occur.
intervals.
Release Dl (release delay)
GeneralThe release delay time sets how long the relay is energized after the under current
ValuesThe release delay time parameter can be set from 1.0 to 90.0 seconds in 0.1 second
DefaultThe default value for the release delay time parameter is 10.0 seconds.
condition is cleared. This parameter is only functional if a relay has been programmed
to UCT (under current trip) in the relay sub-menu (see page 77) and the fault has
been disabled in the fault classes sub-menu (see page 74).
intervals
69
5.19 PROGRAMMING: Motor Protection - Start Lockouts
Starts/Hou (starts per hour)
DescriptionThe starts per hour parameter will set the number of allowed starts in one hour. If the
ValuesThe starts per hour is adjustable from 1 to 20 starts, in 1 start intervals. The starts
DefaultThe default value for the starts per hour parameter is Off.
starter has been stopped and the number of starts given in the last hour has exceeded
this setting, the starter will display SPH in the top left of the display and the time, in
minutes, until the next start is allowed in the bottom left of the display.
NOTE: Starts/Hou does not increment on a PORT restart.
per hour can also be set to Off by going below 1.
Time Start (time between starts)
DescriptionThe time between starts parameter sets the minimum allowed time between starts.
ValuesThe time between starts is adjustable from 1 to 600 minutes, in 1 minute intervals.
DefaultThe default value for the time between starts parameter is Off.
Once a start command has been given, the next start cannot be performed until this
time has expired. If the starter is stopped and the time between starts has yet to
expire, the starter will display TBS in the top left of the display and the time, in
minutes, until the next start is allowed in the bottom left of the display.
NOTE: Time Start does not increment on a PORT restart.
The time between starts can also be set to Off by going below 1 minute.
BKS Timer (backspin timer)
DescriptionThe backspin timer parameter sets the minimum time between a stop and the next
ValuesThe backspin timer is adjustable from 1 to 200 minutes, in 1 minute intervals. The
DefaultThe default value for the backspin timer parameter is Off.
allowed start. If the starter is stopped and a time has been set, the starter will display
BKS in the top left of the display and the time, in minutes, until the next allowed
start in the bottom left.
NOTE: The BKS Timer does not increment on a PORT restart.
backspin timer can also be set to Off by going below 1 minute.
70
5.20 PROGRAMMING: Motor Protection - Starting Timers
UTS Timer (up-to-speed timer)
DescriptionThe up-to-speed timer parameter sets the maximum acceleration time to full speed
ValuesThe up-to-speed timer parameter can be set from 1 to 300 seconds. The up-to-speed
DefaultThe default value for the up-to-speed timer parameter is 30 seconds.
that the motor can take. A stalled motor condition will be detected if the motor does
not get up-to-speed before the up-to-speed timer expires. This allows the programming
of a maximum acceleration time for the motor. The motor is considered up-to-speed
once the current stabilizes below 175 percent of the FLA value and the ramp time
expires.
NOTE: The up-to-speed timer has to be set to a time that is greater than the highest
ramp time in use. The up-to-speed timer will not automatically change to be greater
than the ramp time. If a ramp time greater than the up-to-speed timer is set, the
starter will display a up-to-speed fault every time a start is attempted.
Fault Code 74 - Up to Speed Fault will be displayed when a stalled motor condition is
detected.
timer can be set to Off by setting it below 1 second.
Zero Speed
DescriptionWhen using the zero speed stall protection, the starter will start monitoring the zero
speed input (at JC13-8) as soon as a run command is given and will recognize a stalled
motor if the zero speed time has elapsed before the zero speed signal is removed. The
zero speed input requires a 120VAC signal to indicate the zero speed condition.
Fault Code 69 - Zero Speed Timer will be displayed when a stalled motor condition is
detected.
NOTE: The zero speed timer is not available on synchronous starters.
ValuesThe zero speed parameter can be set from 1 to 30 seconds, The zero speed timer can be
DefaultThe default value for the zero speed parameter is Off.
set to Off by setting it below 1 second.
71
5.21 PROGRAMMING: Motor Protection - Permissive Input
Inline
DescriptionThe starter has a 120VAC feedback input from the inline contactor It uses this
ValuesThe inline delay time is adjustable from 1 to 10 seconds in 1 second intervals.
DefaultThe default value for the inline parameter is 4 seconds.
feedback to check that the contactor is energized when it should not be. This time is
the delay before a fault will occur.
Bypass
DescriptionThe starter has a 120VAC feedback input from the bypass contactor. It uses this
ValuesThe bypass time is adjustable from 1 to 10 seconds in 1 second intervals.
DefaultThe default value for the bypass parameter is 4 seconds.
feedback to check that the contactor is energized when it should. This time is the
delay before a fault will occur.
Trip Input
DescriptionThe trip input parameter sets the time that power must be removed from the 120VAC
input at JC13 terminal #1 on the RediStart Micro II CPU card before a fault occurs.
When an external fault occurs, the starter will shut down and display a Fault 75 External Fault.
ValuesThe trip input parameter can be set from 0.1 to 90.0 seconds in 0.1 second intervals.
DefaultThe default value for the trip input parameter is 0.5 seconds.
72
5.22 PROGRAMMING: Motor Protection - Misc.
Phase Orde (phase order)
DescriptionThe line phasing parameter sets the phase sensitivity of the starter. This can be used
ValuesThe line phasing can be set to;
DefaultThe default value for the phase sensitivity parameter is INS.
to protect the motor from a possible change in the incoming phase sequence. If the
incoming phase sequence does not match the set phase rotation, the starter will
display phs err while stopped and will fault if a start is attempted.
INS- will run with either phase sequence
•
ABC- will only run with ABC phase sequence
•
CBA- will only run with CBA phase sequence
•
# Auto RST (number of auto resets)
DescriptionThe number of auto resets parameter sets how many times in one hour the RediStart
ValuesThe number of auto resets parameter can be set from 1 to 5.
DefaultThe default value for the number of auto resets parameter is 4.
Micro II will reset a non-critical fault.
This parameter is used in conjunction with the automatic fault reset jumper JPC19
(see page 23) and with the fault classes sub-menu (see page 74). When JPC19 is
placed in the automatic fault reset position (1-2), this parameter sets how many times
in one hour any non-critical faults are reset. Non-critical faults are set in the fault
classes sub-menu (see page 74).
No Main PW (no main power)
DescriptionThe no mains power delay parameter sets the period of time that the starter must
ValuesThe no mains power delay parameter is adjustable from 1 to 5 seconds in 1 second
DefaultThe default value for the no mains power parameter is 1 second.
have a run command without mains power before a no mains fault will occur.
intervals
73
5.23 PROGRAMMING: Motor Protection - Fault Classes
Fault Classes
DescriptionThe fault classes menu allows the user to change the action taken when a fault occurs.
ValuesEach fault can be classified as;
DefaultThe default value for each fault depends on the fault.
The menu will allow every fault to be given a different classification depending on the
user requirements. This allows the user to set the starter to;
Trip the starter and display the fault code and description if it occurs.
•
Ignore the fault if it occurs and continue to run.
•
Activate a relay if the fault occurs and continue to run.
•
Note: Not all faults can be assigned every classification. Faults critical to starter
operation may only be programmed to non-critical (NonC) and/or critical (Crit).
NonC - Non-critical fault. Starter will trip. Resets if JPC19 set to 1-2.
•
Crit- Critical fault. Starter will trip and require a manual reset.
•
Dis- Fault is disabled. No action will be taken when fault occurs.
•
WrnA - Fault will not trip starter. Energizes relay programmed to WrnA.
•
WrnB - Fault will not trip starter. Energizes relay programmed to WrnB.
•
WrnC - Fault will not trip starter. Energizes relay programmed to WrnC.
•
Note: Each relay output can be assigned to as many different faults as required.
74
5.24 PROGRAMMING: Meters & Relays - Meter Setup
2
Meter #1 , Meter #2
DescriptionThe RediStart Micro II displays two meter functions on the right side of the display.
ValuesThe meter#1 display and meter#2 display parameters can each be set to one of the
These parameters set what each meter will display. The meter locations are as shown.
Stop
Ready
following;
Asc- Each phase current in a scrolling manner.
•
Aav- Average current.
•
A1- Phase 1 current.
•
A2- Phase 2 current.
•
A3- Phase 3 current.
•
Vsc- Each phase voltage in a scrolling manner.
•
Vav- Average voltage.
•
V1- Phase 1 voltage.
•
V2- Phase 2 voltage.
•
V3- Phase 3 voltage.
•
Hz- Frequency.
•
O/L- Thermal overload in percentage from 0% to 100% (100% = Trip).
•
pf- Motor power factor.
•
etm- The elapsed running time in tenths of an hour.
•
Hetm - The elapsed running time in hours.
•
Uetm - The user resettable elapsed running time.
•
Ustr- The user resettable motor starts counter.
•
I1=0A
V1=0V
Meter #1
Meter #
• KW- Motor real power consumption.
•
KWH - Kilo-watt-hours used by the motor.
•
MWH - Mega-watt-hours used by the motor.
•
KVar- Motor reactive power consumption.
•
KVA- Motor apparent power consumption.
•
Tv- Tachometer voltage.
•
%s- Maximum speed in percentage.
•
Ms- Motor speed.
•
GDF- Ground fault current in amps.
•
Srts- Motor starts counter.
•
Ibal- Motor current imbalance in percentage.
•
ComR - The number of communication requests received.
•
ComT - The number of communication transmits sent.
•
CRat- The communications rate.
•
RTD#? - The temperature being read by RTD with the number ?.
•
TAmx - The maximum temperature being read by a RTD.
•
TSmx - The maximum temperature being read by a stator RTD.
•
TBmx - The maximum temperature being read by a bearing RTD.
•
TApk - The peak temperature being read by a RTD.
•
TSpk- The peak temperature being read by a stator RTD.
•
TBpk - The peak temperature being read by a bearing RTD.
•
IAmx - The number of the RTD reading the highest temperature.
•
ISmx- The number of the RTD reading the stator highest temperature.
•
IBmx - The number of the RTD reading the highest bearing temperature.
•
IApk- The number of the RTD reading the peak temperature.
•
ISpk- The number of the RTD reading the peak stator temperature.
•
IBpk- The number of the RTD reading the peak bearing temperature.
•
TT%- Calculated TruTorque torque value in % of Micro II torque units.
DefaultThe default value for the meter #1 display parameter is Asc.
The default value for the meter #2 display parameter is Vsc.
75
5.24 PROGRAMMING: Meters & Relays - Meter Setup
NOTE: The following meters will show a single decimal place when below the
AutoRange setpoint: etm, Hetm, Uetm, KW, KWH, MWH, KVar, KVA. The value will
show MAX and stop incrementing when they reach (6553). All other meters will show
MAX when they reach (9999).
AutoRange
DescriptionThe autorange parameter sets the value where the display meter will change ranges.
ValuesThe autorange can be set from 50.0 to 99.9 in 0.1 intervals.
DefaultThe default value for the autorange parameter is 99.9.
Meter Rsts (meter resets)
DescriptionThe meter resets parameter allows the user to reset the different RediStart Micro II
ValuesThe meter resets can be set to the following;
DefaultThe default value for the meter resets parameter is None.
meters.
None- No meter resets.
•
KWH - Reset the kilo-watt hour meter.
•
RunT - Reset the user run time hours meter.
•
Strt- Reset the user number of starts counter.
•
SCtr- Reset the serial communication counters.
•
RTDP - Reset the peak RTD meters.
•
When set to any of these values, the parameter will automatically return to None but
the meter will be reset.
Scroll Tim (scroll time)
DescriptionThe scroll time parameter sets the delay time between display pages. If this is set to a
ValuesThe scroll time is adjustable from 1 second to 120 seconds in 1 second intervals. The
DefaultThe default value for the scroll time is Off.
time, the display will switch between different pages which will show all the different
metering values. See page 27 for a description of the display pages. If this is set to Off,
the display pages can be viewed by pressing the Up or Down buttons.
meter scroll time can also be turned Off.
76
5.25 PROGRAMMING: Meters & Relays - Standard Relays
Relay#1, K5 and Relay#2, K6
DescriptionThe relay #1, K5 and relay #2, K6 parameters set the functionality of the two
ValuesThe relay #1 output and relay #2 output can each be set to one of the following;
programmable relays on the RediStart Micro II power card (see power card layout on
page 111).
The relay #1 default is RUN so it should be used to control an in-line contactor or for
any other operation requiring a run contact. The relay #2 default is UTS so it should
always be used to control a bypass contactor or for any other operation requiring an
up-to-speed signal.
The shunt trip (SHT) contact option will change the relay state on various fault
scenarios. If the automatic fault reset jumper is set to manual, this relay will change
state on any fault. If the automatic fault reset jumper is set to automatic, this relay
will change state on any critical fault or the number of auto resets parameter value
has been reached (see page 73).
OL- The thermal overload has tripped.
•
OLL- The thermal overload is locking out starter operation.
•
OLW- The thermal overload is above 90% content and about to trip.
•
RUN- The starter is running.
•
UTS- The motor is running at full speed.
•
SCR- The starter has detected a shorted SCR.
•
SHT- Provides a shunt trip output for tripping a circuit breaker.
•
GDF- Changes state when a ground fault condition is detected.
•
OCT- Changes state when an over-current condition is detected.
•
UCT- Changes state when an under-current condition is detected.
•
TL- Unit has sensed a tachometer loss.
•
PORT - Starter is in Power Outage Ride Thru mode.
•
RDY- All conditions ready to run.
•
• RM#1 - Remote MODBUS operated contact #1.
•
RM#2 - Remote MODBUS operated contact #2.
•
RM_R - Remote communications run contact.
•
RTDw - A RTD is sensing a temp. over it’s programmed warning level.
•
RTDa - A RTD is sensing a temp. over it’s programmed alarm level.
•
RTDf- A RTD has failed either open or shorted.
•
WrnA - Fault warning relay for faults set to a WrnA classification.
•
WrnB - Fault warning relay for faults set to a WrnB classification.
•
WrnC - Fault warning relay for faults set to a WrnC classification.
DefaultThe default value for the relay #1 output parameter is RUN.
The default value for the relay #2 output parameter is UTS.
DescriptionThe optional #?, K? (where ? represents the relays numbered 1 to 7) parameters set
ValuesThe optional #x, Kx output can each be set to one of the following;
the functionality of the four or seven programmable relays on the optional relay cards.
If the optional four (4) relay card is used, only parameters #1 to #4 will each set the
operation of one of the relays on the card (see the four relay card layout on page 113).
If the optional seven (7) relay card is used, then parameters #1 to #7 will each set the
operation of one of the relays on the card (see the seven relay card layout on page
113).
NOTE: If communications is enabled. Optional Relay #4 will be fixed as RM_R.
OL- The thermal overload has tripped.
•
OLL- The thermal overload is locking out starter operation.
•
OLW- The thermal overload is above 90% content and about to trip.
•
RUN- The starter is running.
•
UTS- The motor is running at full speed.
•
SCR- The starter has detected a shorted SCR.
•
SHT- Provides a shunt trip output for tripping a circuit breaker.
•
GDF- Changes state when a ground fault condition is detected.
•
OCT- Changes state when an over-current condition is detected.
•
UCT- Changes state when an under-current condition is detected.
•
TL- Unit has sensed a tachometer loss.
•
PORT - Starter is in Power Outage Ride Thru mode.
•
RDY- All conditions ready to run.
•
RM#1 - Remote MODBUS operated contact #1.
•
RM#2 - Remote MODBUS operated contact #2.
•
RM_R - Remote communications run contact.
•
RTDw - A RTD is sensing a temp. over it’s programmed warning level.
•
•
RTDa - A RTD is sensing a temp. over it’s programmed alarm level.
•
RTDf- A RTD has failed either open or shorted.
•
WrnA - Fault warning relay for faults set to a WrnA classification.
•
WrnB - Fault warning relay for faults set to a WrnB classification.
•
WrnC - Fault warning relay for faults set to a WrnC classification.
DefaultThe default values vary with the starter model and options supplied.
78
5.27 PROGRAMMING: Event Recorder
r
Event Recorder
DescriptionThe event recorder stores the last 99 events. An event is anything that changes the
Event Recorder LayoutThe first screen that is displayed in the event recorder gives the starter state on the
present state of the starter. Examples of events include an operation fault, a Start
command, or a Stop command.
When the event recorder is entered, the last (newest) event is displayed. This is event
number 00 as shown in the bottom right side of the display. To look at the events from
the newest to oldest, press the Up button to advance from event 01 to 99.
second line of the display. See below;
Event Description
Starter
State
The time of the event can be displayed on the bottom line of the display by pressing
the Enter button once. See below;
LOG: System Reset
Stopped03
Index
Number
Event Description
LOG: System Reset
Time
The date of the event can be displayed on the bottom line of the display by pressing
the Enter button twice. See below;
Time:11:04:2503
Index
Numbe
Event Description
LOG: System Reset
Date
The fault/Log number can be displayed on the bottom line of the display by pressing
the Enter button three times. For more information on the fault, look up the fault
number in the table on page 98. See below;
Event
Number
Date:03-04-9903
Event Description
LOG: System Reset
Event#15603
Index
Number
Index
Number
Press the Enter button again to return to the first display screen.
79
5.27 PROGRAMMING: Event Recorder
Event DescriptionThe top line of the event recorder lists the event description. The two things that can
be listed in the event recorder are a change in the state of the starter or a fault. A
change in the state of the starter is listed in the event recorder with “Log:” before the
description. A fault that occurred is just listed in the event recorder by its description.
Starter StateThe starter state lists what state the starter was in when the event occurred. The
TimeThe time gives the time of day that the event occurred. The format is
hours:minutes:seconds.
DateThe date gives the day on which the event occurred. The format is month-day-year.
Fault/Log NumberThe fault/log number can be used when referring to the event. This number, along
with the fault description, will be shown on the display at the time the fault occurred
and caused the starter to trip. The number can also be referred to in the fault table on
page 98 for a more detailed description of the fault as well as some possible solutions.
80
5.28 PROGRAMMING: Control Config - System Clock
System Clock
DescriptionThe RediStart Micro II comes with a real time clock. The user can enter the actual
RestrictionsThe RediStart Micro II clock can not be set if there is a starter lockout timer is
MinutesThe minutes parameter should be set to the present minute.
HoursThe hours parameter should be set to the present hour using 24 hour convention.
DayEnter the current day of the month
MonthEnter the current month of the year.
YearEnter the current year.
time and the starter will use this time when it logs events in the event recorder. This
can help with troubleshooting.
The RediStart Micro II clock is year 2000 compatible.
present or if the factory password has been entered.
81
5.29 PROGRAMMING: Control Config - System Password
Password
DescriptionThe system password protection will lock out the adjustment of all parameters except
Setting the PasswordTo set a password, change the value of the password from Off to any user selected
Removing the PasswordTo remove the password protection, change the value of the password from 500 to the
ValuesThe password can be set to any value between 001 and 999, excluding 500. The
for the meter #1 display and meter #2 display.
The RediStart Micro II is shipped with the password feature disabled. This is
confirmed by a password setting of Off. When the password has been set, a password
of 500 appears under this parameter.
number between 001 and 999, excluding 500.
To make the password active, press the computer reset button, change the password
to 500, or cycle the control power.
When the parameters are password protected, a dot will appear in the bottom middle
of the display and the password will be 500 when the password menu is entered.
user selected number. Once this is done, change the password to Off. This will remove
the user selected password and disable the password protection. The password can not
be set to off unless the correct password has been entered.
To change any parameter when a password is set, change the password from 500 to
the user selected number. Once the parameter has been changed, press the computer
reset button or change the password to any other value except for Off.
password can also be set to Off by setting it under 001.
DefaultThe default value for the password parameter is Off.
82
5.30 PROGRAMMING: Control Config - Comm. Settings
COMM. Mode (communications mode)
DescriptionThe communications mode parameter sets the mode of serial communications.
The starter requires the addition of a serial communications card to be able to use
serial communications. See the RS232/RS485 Communications Manual for details on
serial communications.
The starter is capable of DeviceNet communications without any additional hardware.
See the DeviceNet manual for details.
ValuesThe communications mode can be set to the following values:
DefaultThe default value for the communications mode parameter is OFF.
OFF- Serial communications is disabled.
M232- Use RS-232 serial communications with MODBUS RTU protocol.
M485- Use RS-485 serial communications with MODBUS RTU protocol.
A232- Use RS-232 serial communications with Benshaw ASCII protocol.
A485- Use RS-232 serial communications with Benshaw ASCII protocol.
DNet- Use DeviceNet communications.
COM Addres (communications address)
DescriptionThe communications address parameter sets the starter address when using RS-485
ValuesThe communications address can be set from 0 to 255.
DefaultThe default value for the communications address is 127.
communications. The equipment that is communicating with the RediStart Micro II
must use the same address as this to communicate with the starter.
COM Delay (communications delay)
DescriptionThe communications delay parameter sets the delay time between the starter
receiving a communications request and it responding to the request. The
communications delay may have to be increased to give the equipment that sent the
communications request enough time to switch to receiving mode before the response
is sent.
ValuesThe communications response delay can be set from 0.02 to 2.00 seconds in 0.01
second intervals.
DefaultThe default value for the communications response delay is 0.35 seconds.
83
5.30 PROGRAMMING: Control Config - Comm. Settings
MB:Baud (MODBUS baud rate)
DescriptionThe MODBUS baud rate parameter sets the communications speed.
NOTE: The RediStart Micro II must be reset after this parameter is changed.
ValuesThe MODBUS baud rate parameter can be set to;
DefaultThe default value for the MODBUS baud rate parameter is 2400 bits per second.
2400- 2400 bits per second.
•
4800- 4800 bits per second.
•
9600- 9600 bits per second.
•
MB:Com T/O (MODBUS communications timeout)
GeneralThe MODBUS communications timeout sets the time that the serial port controlled
ValuesThe MODBUS communications timeout can be set from 1 to 900 seconds in 1 second
DefaultThe default value for the MODBUS communications timeout parameter is Off.
relays will stay energized without receiving a valid communications request. If a valid
serial communications request is not received for the time that is set, the starter will
de-energize the relays. The relays that are affected by this parameter are the RM#1,
RM#2 and RM_R relays.
intervals. If can also be set to Off by going below 1 second.
DN:MAC ID (DeviceNet MAC ID)
GeneralThe DeviceNet MAC ID sets the address for the starter as a DeviceNet node.
NOTE: The RediStart Micro II must be reset after this parameter is changed.
ValuesThe DeviceNet MAC ID can be set from 0 to 63.
DefaultThe default value for the DeviceNet MAC ID is 63.
DN:Baud (DeviceNet baud rate)
GeneralThe DeviceNet baud rate sets the DeviceNet communications speed.
NOTE: The RediStart Micro II must be reset after this parameter is changed.
ValuesThe DeviceNet baud rate parameter can be set to;
DefaultThe default value for the DeviceNet baud rate is 125 kbps.
•
125 kbps
•
250 kbps
•
500 kbps
84
5.30 PROGRAMMING: Control Config - Comm. Settings
DN:InAssy (DeviceNet input assembly)
GeneralThe DeviceNet input assembly parameter sets the format for the input data. Refer to
ValuesThe DeviceNet input assembly can be set to;
DefaultThe default value for the DeviceNet input assembly is 61.
the DeviceNet manual for details.
NOTE: The RediStart Micro II must be reset after this parameter is changed.
50
•
51
•
52
•
53
•
60
•
61
•
DN:OutAssy (DeviceNet output assembly)
GeneralThe DeviceNet output assembly parameter sets the format for the output data. Refer
ValuesThe DeviceNet output assembly can be set to;
to the DeviceNet manual for details.
NOTE: The RediStart Micro II must be reset after this parameter is changed.
1
•
2
•
3
•
• 100
DefaultThe default value for the DeviceNet output assembly is 100.
DN:T/O Act (DeviceNet timeout action)
GeneralThe DeviceNet timeout action parameter selects what the RediStart Micro II does in
ValuesThe DeviceNet timeout action can be set to none or stop.
DefaultThe default value for the DeviceNet timeout action is none.
the event that the DeviceNet connection times out.
DN:Rev (DeviceNet interface revision)
GeneralThe DeviceNet interface revision reports the revision stored in the Identity Object
ValuesThe revision is listed in the form Major, Minor.
(class1, attribute 4). The revision refers to the set of objects and attributes
implemented in the RediStart Micro II. As new objects and attributes are
implemented, the revision will increase. The revision may be used to ensure the
correct version of the DeviceNet manual and EDS file are obtained.
85
5.31 PROGRAMMING: Control Config - Options List
Options List
DescriptionThe options list menu provides a list of the installed options on the starter. It can be
ValuesThe following is a list of the possible options;
used to determine what options have been added to the starter.
RSM MICROII- RediStart Micro II reduced voltage software.
•
Reversing- Starter has reversing capability.
•
Braking- Starter has DC injection braking.
•
HD Braking- Starter has heavy duty braking.
•
Two Speed- Starter is for two speed motor.
•
MV Series- Medium Voltage 2200 to 4800VAC.
•
Tachometer- Starter has tach feedback for linear ramp.
•
Jog/Heater- Starter has jog and motor heater.
•
SYNC- Starter has synchronous motor control.
•
SEP- Stand-alone synchronous field controller.
•
PORT- Power-outage ride through.
•
ID Motor- Inside-delta motor starter.
•
Dyn. Brake- Synchronous motor braking using field DC.
•
NOTE: Some options are not available on some starter series. For example, reversing
and braking are not available on a medium voltage starter. Contact Benshaw for
details.
86
5.32 PROGRAMMING: Control Config - Software Part#
Software Part#
DescriptionThe software part number sub-menu gives the part number of the software. This
ValuesThe following is a list of possible software part numbers. The xx represents the
information is useful for future service reasons.
If calling Benshaw for service, this number should be recorded so it can be provided to
the service technician.
software revision number which changes as the software is updated.
810010-01-xx - LV standard soft-starter.
•
810010-02-xx - MV standard soft-starter.
•
810010-03-xx - LV Synch soft-starter.
•
810010-04-xx - MV Synch soft-starter.
•
810010-05-xx - LV Heavy Duty Brake soft-starter.
•
810010-06-xx - MV ATL Synch soft-starter.
•
810010-07-xx - MV extended soft-starter.
•
810010-08-xx - MV ATL soft-starter.
•
* LV=low voltage and MV=medium voltage
87
5.33 PROGRAMMING: Factory Setup - Hardware Setup
C.T. Ratio
DescriptionThe CT ratio must be set to match the CT’s (current transformers) supplied with the
ValuesThe CT ratio can be set to following values;
DefaultThe default value for the CT ratio is 288 (:1).
starter. This allows the starter to properly calculate the current supplied to the motor.
Only Benshaw supplied CTs can be used on a RediStart Micro II starter. These are
custom 0.2 amp secondary CTs specifically designed for use on the starter. The CT
ratio is then normalized to a 1A secondary value. The supplied CT ratio can be
confirmed by reading the part number on the CT label. The part number is of the form
BICTxxx1M, where xxx is the CT primary and the 1 indicates the normalized 1 amp
secondary.
100 (:1 or 20:0.2)
•
288 (:1 or 58:0.2)
•
720 (:1 or 144:0.2)
•
864 (:1 or 173:0.2))
•
1000 (:1 or 200:0.2))
•
2640 (:1 or 528:0.2)
•
2880 (:1 or 576:0.2)
•
3900 (:1 or 780:0.2))
•
5000 (:1 or 1000:0.2)
•
5760 (:1 or 1152:0.2)
•
Relay Card
DescriptionThe relay card parameter should be set to reflect the optionally installed relay card.
ValuesThe relay card can be set to;
DefaultThe default value for the relay card parameter is None.
•
None- no relay card installed
•
OUT4 - four relay output card installed
•
OUT7 - seven relay output card installed
88
5.34 Programming: Factory Setup - BIST Setup/Run
Start BIST
DescriptionThe Start BIST parameter sets the starter to perform the Built In Self Test when
ValuesThe Start BIST parameter can be set to Yes or No.
DefaultThe default value for the Start BIST parameter is No.
programmed to “Yes” and the Run/Test switch is in the test position. When
programmed to “No” and the switch is in the test position, the operator can program
or review the parameters without medium voltage present.
Test Inlin (test in-line)
DescriptionThe test in-line parameter sets the starter to test the in-line contactor. If the in-line
ValuesThe test in-line parameter can be set to Yes or No.
DefaultThe default value for the test in-line parameter is Yes.
contactor can not be tested by the BIST test (see page 106), then this parameter
should be set to no.
Test Bypas (test bypass)
DescriptionThe test bypass parameter sets the starter to test the bypass contactor. If the bypass
contactor can not be tested by the BIST test (see page 106), then this parameter
should be set to no.
ValuesThe test bypass parameter can be set to Yes or No.
DefaultThe default value for the test bypass parameter is Yes.
100% Gates
DescriptionThe 100% gates parameter sets the SCR gate firing pattern when a BIST test is
ValuesThe 100% gates parameter can be set to Yes or No.
DefaultThe default value for the 100% gates parameter is No.
performed (see page 106). If this parameter is set to Yes, the SCR gates will all be
fired continuously. If this parameter is set to No, the SCR gates will be fired in a
sequential pattern.
89
5.35 PROGRAMMING: Factory Setup - Factory Control
FACT Pass. (factory password)
DescriptionThe factory password parameter must be set to the proper password to allow access to
ValuesThe factory password is adjustable from 0 to 9999.
DefaultThe default value for the factory password parameter is 0.
the rest of this menu. The password is different for each day of the year. If it is
required, Benshaw will supply the password for this menu for the day it is needed.
NOTE: Entering a password will lock the System Clock to the set values, and it is not
possible to enter the password twice in the same day.
Reset Def (reset to default parameters)
DescriptionWhen the Reset Def parameter is set to Yes, all parameters are reset to their default
ValuesThe Reset Def parameter can be set to No or Yes.
DefaultThe default value for the Reset Def parameter is No.
values.
CLR Events (clear event log)
DescriptionWhen the CLR Events parameter is set to Yes, the event log is cleared of its events.
ValuesThe CLR Events parameter can be set to No or Yes.
DefaultThe default value for the CLR Events parameter is No.
CLR Pass. (clear password)
DescriptionIf a System Password has been set through the Control Config. menu, setting the CLR
ValuesThe CLR Pass. parameter can be set to No or Yes.
DefaultThe default value for the CLR Pass. parameter is No.
Pass. parameter to Yes will clear this password.
Cal Volt L1, L2, L3 (calibrate voltage meter)
DescriptionIf greater accuracy is desired for line voltage measurements, the Cal Volt L1, L2, L3
ValuesThe Cal Volt L1, L2, or L3 parameters are adjustable from 900 to 1100 volts in 1 volt
parameters can be used for calibration.
NOTE: A calibrated voltage source or independent calibrated voltage meter is
required.
increments.
DefaultThe default value for the Cal Volt L1, L2, or L3 parameter is 1000 volts.
90
5.35 PROGRAMMING: Factory Setup - Factory Control
Cal Curr L1, L2, L3 (calibrate current meter)
DescriptionIf greater accuracy is desired for line current measurements, the Cal Curr L1, L2, L3
ValuesThe Cal Curr L1, L2, or L3 parameters are adjustable from 900 to 1100 amps in 1
DefaultThe default value for the Cal Curr L1, L2, or L3 parameter is 1000 amps.
parameters can be used for calibration.
NOTE: A calibrated current source or independent calibrated current meter is
required.
amp increments.
91
5.36 PROGRAMMING: RTD Setup - RTD Module Setup
Mod#1 Addr (module #1 address)
DescriptionThe module #1 address parameter has to be set to the MODBUS address of the first
ValuesThe RTD module #1 address can be set from 16 to 23 in increments of 1.
DefaultThe default value for the RTD module #1 address is 16.
RTD module attached to the soft-starter. The address of the RTD module can be
verified by checking the rotary switch on the top of the RTD module.
Mod#2 Addr (module #2 address)
DescriptionThe module #2 address parameter has to be set to the MODBUS address of the second
ValuesThe RTD module #2 address can be set from 16 to 23 in increments of 1.
DefaultThe default value for the RTD module #2 address is 17.
RTD module attached to the soft-starter. The address of the RTD module can be
verified by checking the rotary switch on the top of the RTD module. Ensure that
module #2 is not set to the same address as module #1.
#RTDs Mod1 (number of RTDs on module #1)
DescriptionThe number of RTDs on module 1 parameter sets the number of RTD inputs that are
being used on first RTD module. If this parameter is set to None, then the RediStart
Micro II will not attempt to communicate with module #1.
ValuesThe # of RTD’s on module 1 parameter can be set from 1 to 8. The parameter can also
DefaultThe default value for the # or RTD’s on module 1 parameter is None.
be set to None by going below 1.
#RTDs Mod2 (number of RTDs on module #2)
DescriptionThe number of RTDs on module 2 parameter sets the number of RTD inputs that are
ValuesThe # of RTD’s on module 2 parameter can be set from 1 to 8. The parameter can also
DefaultThe default value for the # or RTD’s on module 2 parameter is None.
being used on second RTD module. If this parameter is set to None, then the
RediStart Micro II will not attempt to communicate with module #2.
be set to None by going below 1.
Temp Scale (temperature scale)
DescriptionThe temperature scale parameter sets the units used for temperature measurements.
ValuesThe temperature scale can be set to;
•
C - All RTD temperature values and set points are in degrees Celsius.
•
F - All RTD temperature values and set points are in degrees Fahrenheit.
DefaultThe default value for the temperature scale is C (degrees Celsius).
92
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.